SC200 PLC
SC200 PLC
Central System
Installation and Maintenance
Series 200
Central System
Installation and Maintenance
Copyright © 1999-2001 ABB Automation Products AB.
The contents of this document can be changed by ABB Automation Products AB without prior no-
tice and do not constitute any binding undertakings from ABB Automation Products AB. ABB Au-
tomation Products AB is not responsible under any circumstances for direct, indirect, unexpected
damage or consequent damage that is caused by this document.
Release: 200102
Document version: 3-1
Document number: 493-1068-11
Printed in Sweden.
493-1068-11 (3-1)
Contents
1 Introduction 11
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
How to Read this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
European Union Directive Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
UL Listing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2 System Overview 13
2.1 System Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.2 Central System Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3 Safety Instructions 17
Be Careful - Prevent Accidents and Protect Valuable Equipment . . . . . . . 17
Before Replacing I/O Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Operating Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Signal Noise Due to Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Hazardous Electrical Supplies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Warnings and Information Symbols in the Text Margin . . . . . . . . . . . . . . 18
Mandatory Installation Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4 System Configuration 21
4.1 Central System Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Example 1. Central System Unit Location . . . . . . . . . . . . . . . . . . . . . . . . . 22
Example 2. Central System Units on two DIN Rails . . . . . . . . . . . . . . . . . 23
4.2 Connecting a Central I/O System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
4.3 Connecting a Remote I/O System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
4.4 Addressing Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4.5 Power Calculation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Example 1: Calculating the Number of PSSGs . . . . . . . . . . . . . . . . . . . . . 29
Example 2: Calculating the 24 volt Supply Current to the Central System 29
4.6 24 V DC Power Supply for Central System . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.7 Connecting Alert I/O to the Central System . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
5 General Installation Instructions 33
5.1 Installation Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.2 Power Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
493-1068-11 (3-1) v
Contents
vi 493-1068-11 (3-1)
Contents
200-CI232 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
7.7 Communication Interface RS485, 200-CI485G . . . . . . . . . . . . . . . . . . . . . . . . 77
Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
200-CI485G Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
7.8 Communication Interface Ethernet, 200-CIE . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
200-CIE Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
7.9 Communication Interface SattBus, 200-CISB . . . . . . . . . . . . . . . . . . . . . . . . . 87
Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
200-CISB Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Installation of SattBus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
7.10 Communication Interface ControlNet, 200-CICN . . . . . . . . . . . . . . . . . . . . . . 90
Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
200-CICN Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
7.11 Communication Interface PROFIBUS-DP, 200-CIPB/DP-G . . . . . . . . . . . . . 94
Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
PROFIBUS-DP, Installation of PROFIBUS Fieldbus . . . . . . . . . . . . . . . . 96
7.12 Communication Interface PROFIBUS-DP, 200-CIPB/DP-SL . . . . . . . . . . . . 97
Installation of PROFIBUS Fieldbus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
7.13 Backplane Unit, 200-BPN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
7.14 Dummy Unit, 200-DU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
7.15 Central System Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
8 Start-up of Series 200 105
8.1 Hardware Test, Position 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
The Self-test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Check of Backplanes, Position 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Error Help . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
9 Maintenance and Service 113
9.1 Replacing Central System Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
9.2 Changing Batteries and Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Changing the Battery in CPU20, CPU30 and CPU40 . . . . . . . . . . . . . . . . 114
Changing the Battery in 200-CPU50 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Changing the Battery in 200-CIE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Changing Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
9.3 Troubleshooting the Central System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Troubleshooting 200-PSMG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
D Standards 171
E Directive Considerations 175
E.1 Electromagnetic Compatibility (EMC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
E.2 Low-Voltage Directive (LVD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
Index 177
493-1068-11 (3-1) ix
Contents
x 493-1068-11 (3-1)
Chapter 1: Introduction
Chapter 1
Introduction
This manual is intended for those involved in the configuration, installation and
maintenance of the Series 200 Central System.
Safety
It is mandatory for all potential users of the control system to read the chapter en-
titled ”Safety instructions” before taking any further actions. The warning and in-
formation symbols used in the manual are also described there.
493-1068-11 (3-1) 11
Chapter 1: Introduction
Appendices at the end of the manual provide technical data, recommended com-
ponents, mounting dimensions and information on CSA and UL standards.
UL Listing
Units mentioned in this document are UL listed if product or packing is
marked with the UL logo. indicates UL approval for the USA, and
also for Canada. The logo indicates UL approval for
Canada only.
The applied standard is UL508, Industrial Control Equipment. Units approved for
use in hazardous locations also comply with the standard UL1604. To fulfill the
UL requirements for hazardous locations, the instructions in the appendix "Stan-
dards", on page 171 must be followed.
12 493-1068-11 (3-1)
Chapter 2: System Overview
Chapter 2
System Overview
The Series 200 Central system is a compact modular system built around small
backplanes which can be connected to suit the desired system configuration.
The Central systemhas Interface units for communication to other systems and
devices via serial channels (COMLI), ControlNet™, Sattbus, Ethernet and
PROFIBUS-DP.
The other basic hardware consists of central processing units, power supply units,
adapters, backplane units and cables.
Series 200 Central units have the following main features:
• Capability of remote I/O via ControlNet and PROFIBUS-DP
• Supports a variety of I/O systems, see corresponding data sheet
• Optimal for most applications due to several Central Processing Units of dif-
ferent performance
• Modular design. DIN rail mounted units which reduce the installation and
maintenance costs
• Communication via Ethernet, SattBus, RS232, RS485, and COMLI
• Plug-in screw terminal blocks
• The system is easy to expand
Series 200 is to be used in industrial environment and meets the EMC directive
89/336/EEC.
Note. The use of Series 200 units with the control systems SattCon 200 and
SattLine is restricted to certain versions and configurations. Refer to relevant data
sheets.
493-1068-11 (3-1) 13
2.1 System Design Chapter 2: System Overview
DIN rail
Power supply
unit
ce units
n ication Interfa
Commu
Central
processing unit
stem
l I/O sy
Centra
An example of a Central system and a central I/O system configuration. The six controller
units are mounted on three backplane units.
14 493-1068-11 (3-1)
Chapter 2: System Overview 2.2 Central System Components
Backplane interconnec-
Backplane screw terminal block:
tor: 200-BPF
200-BPP
Backplane termination:
Backplane unit for 200-BPT
Central system: Cable backplane to adapter: 200-CBA/
200-BPN L260 and 200-CBA/L260V
Cable backplane to backplane: 200-CBB/
R360
Cable adapter to adapter: 200-CAA/L190
493-1068-11 (3-1) 15
2.2 Central System Components Chapter 2: System Overview
16 493-1068-11 (3-1)
Chapter 3: Safety Instructions
Chapter 3
Safety Instructions
This chapter is mandatory reading for anyone planning to use the control system.
Maintenance
In order to avoid long shutdowns, it is advisable to keep spares of components in
stock.
493-1068-11 (3-1) 17
Chapter 3: Safety Instructions
Operating Environment
Before the system is brought on-line, find out which environmental conditions are
applicable. The following points are important.
• The product must not be exposed to conditions exceeding the stated values in
the technical specifications.
• The product must not be used in an environment where it is exposed to strong
electrical interference. Electrical machines can produce interference which
exceeds the permitted levels for the equipment, e.g. during repair work.
• All products must be handled with appropriate precautions with regard to
electrostatic damage.
Important: Software
Check:
• Use the system’s fault-monitoring facility to prevent mishaps and accidents.
• Check before executing any changes.
Important: Hardware
Do not disconnect the power supply to a system which is in operation.
18 493-1068-11 (3-1)
Chapter 3: Safety Instructions
493-1068-11 (3-1) 19
Chapter 3: Safety Instructions
20 493-1068-11 (3-1)
Chapter 4: System Configuration 4.1 Central System Connection
Chapter 4
System Configuration
This chapter describes how to incorporate Central System units into a control sys-
tem and how to calculate the power consumption. Refer to the appendix "Mount-
ing Dimensions", on page 161, regarding installation details, dimensions, etc.
493-1068-11 (3-1) 21
4.1 Central System Connection Chapter 4: System Configuration
The CPU unit, power unit and communication interface units, are interconnected via the
backplanes.
Central System with one CPU unit. Example with enhanced power supply.
22 493-1068-11 (3-1)
Chapter 4: System Configuration 4.2 Connecting a Central I/O System
Central system
Termination
BPT stop (red)
CBB/R360
CBA/L260
Termination
BPT start (green)
The Central system can be extended using two DIN rails and the extension cable 200-CBB/
R360.
493-1068-11 (3-1) 23
4.3 Connecting a Remote I/O System Chapter 4: System Configuration
The Central System bus (NNbus) is extended without any special interfaces when
a central I/O system is used. The I/O system must be installed together with the
CPU in one cabinet and M on the same metal mounting plate.
A maximum of 6 rows of 8 I/O units can be installed, giving 48 I/O units.
Note. Total current consumption must be considered. See "Power Calculation",
on page 28.
Central System
Termination
BPT stop
(red)
CBA/L260
200-ANN
CAA/L190
24 493-1068-11 (3-1)
Chapter 4: System Configuration 4.3 Connecting a Remote I/O System
Central System
493-1068-11 (3-1) 25
4.4 Addressing Format Chapter 4: System Configuration
All addresses are represented in decimal notation and are determined by the sys-
tem software.
Basic rules
• The units are numbered from the left to the right.
• The first adapter for central I/O has number 0 (see example below).
Example 1. Central System with central I/O
The first unit in the Central System is numbered 10 and the first central
I/O adapter, 200-ANN, is numbered 0. Unit number 17 is an RS232 Communica-
tion Interface, 200-CI232.
26 493-1068-11 (3-1)
Chapter 4: System Configuration 4.4 Addressing Format
Central System
10 11 12 13 14 15 16 17
NNbus
Addressing format a.d: 17.1
ANN
0 0.0 0.1 0.2 0.3 0.4
ANN
2 2.0 2.1 2.2 2.3 2.4
493-1068-11 (3-1) 27
4.5 Power Calculation Chapter 4: System Configuration
Communication Interface
Central System
10 11 12 13 14 15 16 17
Fieldbus
Adapter
8 8.0 8.1 8.2 8.3 8.4 Remote I/O system
Adapter
4 4.0 4.1 4.2 4.3 4.4
28 493-1068-11 (3-1)
Chapter 4: System Configuration 4.5 Power Calculation
493-1068-11 (3-1) 29
4.6 24 V DC Power Supply for Central System Chapter 4: System Configuration
30 493-1068-11 (3-1)
Chapter 4: System Configuration 4.7 Connecting Alert I/O to the Central System
Redundant power
If redundant 24 V DC is required, this can be achieved with diodes of sufficient
current rating (see figure below). In this case the 24 V DC supply voltage must be
within limits after the diode voltage drop.
24 V +
Mains DC Diodes: 6 A, minimum 100 V DC,
–
e.g. BYX 38/300 or MR 751.
24 V + +
Mains To Series 200
DC – –
Redundant 24 V DC supply.
493-1068-11 (3-1) 31
4.7 Connecting Alert I/O to the Central System Chapter 4: System Configuration
PSMG
BIAL
BIAL
CPU
CIE
DU
I/O rack 1
I/O rack 2
I/O Bus flat cables
I/O rack 3
I/O rack 4
Power supply
The Central system built into a PRI cabinet controlling the four Alert I/O racks.
32 493-1068-11 (3-1)
Chapter 5: General Installation Instructions 5.1 Installation Precautions
Chapter 5
General Installation Instructions
A system installed according to the instructions in this document is prepared to meet the
ABB Automation environmental specifications for industrial equipment.
493-1068-11 (3-1) 33
5.2 Power Installation Chapter 5: General Installation Instructions
By taking the proper precautions, control systems can operate safely and reliably
in normal industrial environments. Avoid locating equipment -
• where the ambient temperature is outside the range specified in the Technical
specifications
• where the relative humidity exceeds the range specified in the Technical spec-
ifications
• where condensation may occur following sudden temperature changes
• where it may be exposed to high electric or magnetic fields
• where it may be exposed to corrosive or inflammable gases
• where it may be exposed to dust, conductive particles, oil mist or organic solu-
tions
• where it may be exposed to direct sunlight
• where it may be exposed to vibration or mechanical shock
• where it may be exposed to water
M • close to powerful high-frequency sources. Possible problems may be solved by
means of external filters.
Do not use communication radios and cellular phones within one meter of the
control system, as there is a risk that industrial interference levels may be
exceeded, which may disturb the system.
34 493-1068-11 (3-1)
Chapter 5: General Installation Instructions 5.2 Power Installation
493-1068-11 (3-1) 35
5.2 Power Installation Chapter 5: General Installation Instructions
Controller
Filter 24 V DC
230 V AC
Type A
•
Digital I/O
24 V DC •
Filter
Type B
Filtering for a controller and I/O system mounted in the same cabinet, without a fieldbus
connection. Digital and analog I/O units have separate serial buses which are supplied with
power by the controller.
36 493-1068-11 (3-1)
Chapter 5: General Installation Instructions 5.2 Power Installation
Controller
Filter Filter
230 V AC 24 V DC •
Type A Type B
Analog I/O
Digital I/O and pulse
counter I/O
Filter
Type B
Filtering for a controller and I/O system mounted in the same cabinet, without a fieldbus
connection. Digital and analog I/O units are combined on a common serial bus which is
supplied with power by the controller.
Analog I/O
Fieldbus Digital I/O and pulse
adapter counter I/O
Filter Filter
230 V AC 24 V DC • •
Type A Type B
Analog I/O
Fieldbus Digital I/O and pulse
adapter counter I/O
Filter Filter
24 V DC
Type A
• •
Type B
Filtering for I/O systems connected to the controller via a fieldbus and fieldbus adapter (for
instance ControlNet or PROFIBUS-DP). Digital and analog/pulse counter I/O units are
combined on a common serial bus. The power to the serial bus is supplied by the fieldbus
adapter. Alternative power supplies, 230 V AC and 24 V DC, are shown.
493-1068-11 (3-1) 37
5.3 Installation of External Cables Chapter 5: General Installation Instructions
M If filters and lightning protectors are not connected to ground via the mechanical
fastening devices, the ground connection should be made with a ground wire,
maximum 100 mm long and minimum 1.5 mm2 or AWG 16.
38 493-1068-11 (3-1)
Chapter 5: General Installation Instructions 5.3 Installation of External Cables
493-1068-11 (3-1) 39
5.3 Installation of External Cables Chapter 5: General Installation Instructions
Two wires are allowed in each terminal, unless ferrules are used.
Unshielded Cables
Unshielded cables can be used in normal industrial environments for digital
I/O signals.
M Shielded Cables
Shielded cables must be used for analog I/O and communication (except SattBus
and Ethernet twisted pair).
The shields must be clamped to ground (normally the mounting plate) using one
of the following alternatives.
40 493-1068-11 (3-1)
Chapter 5: General Installation Instructions 5.3 Installation of External Cables
493-1068-11 (3-1) 41
5.3 Installation of External Cables Chapter 5: General Installation Instructions
42 493-1068-11 (3-1)
Chapter 6: Mounting Instructions 6.1 Mounting Backplanes and their Interconnectors
Chapter 6
Mounting Instructions
This chapter describes how to mount the Central System units and their accesso-
ries. Refer to the appendix "Mounting Dimensions", on page 161 regarding scale
drawings and recommended distances between components on a mounting plate.
493-1068-11 (3-1) 43
6.1 Mounting Backplanes and their Interconnectors Chapter 6: Mounting Instructions
Locking tab
The two backplane units are attached by the hook (1) on the left backplane and the slot on
the right backplane.
44 493-1068-11 (3-1)
Chapter 6: Mounting Instructions 6.1 Mounting Backplanes and their Interconnectors
493-1068-11 (3-1) 45
6.2 Mounting the Screw Terminal Blocks and Bus Terminators Chapter 6: Mounting Instructions
46 493-1068-11 (3-1)
Chapter 6: Mounting Instructions 6.2 Mounting the Screw Terminal Blocks and Bus Terminators
493-1068-11 (3-1) 47
6.3 Connecting Central System to the Central I/O System Chapter 6: Mounting Instructions
Central System
BPT
stop
Central System
BPN BPN BPN BPT
BPT start stop
ANN
BPN BPN BPN
BPT
start
Bus termination with central I/O system (and/or remote I/O system ) and bus termination
without central I/O system with or without remote I/O system.
48 493-1068-11 (3-1)
Chapter 6: Mounting Instructions 6.3 Connecting Central System to the Central I/O System
CBA/L260 CBA/L260
CAA/L190
CE1
CAA/L380
Curve block
Figure 1 Profile
Figure 2
493-1068-11 (3-1) 49
6.4 Final Mounting Measures Chapter 6: Mounting Instructions
Key hole
50 493-1068-11 (3-1)
Chapter 6: Mounting Instructions 6.4 Final Mounting Measures
493-1068-11 (3-1) 51
6.4 Final Mounting Measures Chapter 6: Mounting Instructions
52 493-1068-11 (3-1)
Chapter 7: Functional Description 7.1 Central Processing Units, 200-CPU20, 200-CPU30 and 200-CPU40
Chapter 7
Functional Description
Front Panel
Indicators
Indication Function
Fail Red LED. Lit when start-up tests detect a fault or when there
is a system program fault.
Power Green LED.
Steady lit Internal 5 V DC is present and the internal logic
is initiated.
Flashing Battery low
Stop Red LED. Lit when the program is stopped.
SB TD 2 Green LED. Transmit data on the SattBus channel
SB RD 2 Green LED. Receive data on the SattBus channel
TD 1 Green LED. Transmit data on the serial channel 1
RD 1 Green LED. Receive data on the serial channel 1
493-1068-11 (3-1) 53
7.1 Central Processing Units, 200-CPU20, 200-CPU30 and 200-CPU40 Chapter 7: Functional Description
Indication Function
Designation Function
Functional Description
The Central Processing Unit interfaces to the other units in the system via the
Central Systembus (NNbus) and with external units via a SattBus interface
(except 200-CPU 20/10) and two non-insulated RS232 channels.
The Central Processing Unit has a 32 bit microprocessor (CPU) and a floating
point unit (FPU) (except CPU20/10) to improve floating point calculation.
There are memories with battery back-up for the system and user programs.
Note. For connection of the battery see "Changing Batteries and Fuses", on page
113.
The Central Processing Unit has a real-time clock with battery back-up.
The power supply part of the Central Processing Unit takes its power from the
system bus and generates the required internal voltages.
The power fail signal (PF) generated in the power unit 200-PSMG, is necessary
for normal operation. A power loss brings the Central Processing Unit to a power
fail mode.
A start mode switch on the front of the unit is used to select different program
modes, and a reset button is used to reset the system.
The LED indicators on the front of the units show program, power and
communication status.
54 493-1068-11 (3-1)
Chapter 7: Functional Description 7.1 Central Processing Units, 200-CPU20, 200-CPU30 and 200-CPU40
Power
+5V x2 RS232
interface
channel 0 6
Micro-processor
(CPU) Communication
FPU controller
x2 RS232
interface
Battery channel 1 2
NNbus Logic
Interface
Real
System and SattBus
time
user memories board
clock
NNbus
200-CPU30/40 Connections
Connector for serial channel 0
9-pin female D-type connector.
Pin Function
493-1068-11 (3-1) 55
7.1 Central Processing Units, 200-CPU20, 200-CPU30 and 200-CPU40 Chapter 7: Functional Description
Pin Function
9 Not connected
Terminal Function
56 493-1068-11 (3-1)
Chapter 7: Functional Description 7.2 Central Processing Unit, 200-CPU50
Front Panel
Indicators
Indication Function
Fail Red LED. Lit when start-up tests detect a fault or when there
is a system program fault.
Power Green LED.
Lit when internal 5 V DC is present and the internal logic is
initiated.
Flashing when internal 5 V DC is present and the internal
logic is initiated, but the battery contains less than 50% of
total backup capacity.
Stop Red LED. Lit when the program is stopped.
TD 0 Green LED. Data being transmitted on the serial channel.
RD 0 Green LED. Data being received on the serial channel.
493-1068-11 (3-1) 57
7.2 Central Processing Unit, 200-CPU50 Chapter 7: Functional Description
Indication Function
Designation Function
Functional Description
The Central Processing Unit functions as an interface to the other units in the
system via the Central System bus (NNbus) and external units via a non-
galvanically isolated RS232 channel.
A floating point unit for basic floating point operations is built into the main
processor.
There are dynamic RAM memories (DRAM) with battery backup and flash
memories for the system and for application programs.
The Central Processing Unit has a real-time clock (RTC) with battery backup.
The power supply part of the Central Processing Unit takes its power from the
system bus and generates the internal voltages required.
The power fail signal (PF), generated in the power unit 200-PSMG, is necessary
for normal operation. A power loss brings 200-CPU50 to a power fail mode.
58 493-1068-11 (3-1)
Chapter 7: Functional Description 7.2 Central Processing Unit, 200-CPU50
A start mode switch on the front of the unit is used to select different program
modes. A reset button is used to reset the system. The LED indicators show
program, power, battery and communication status.
32
NNbus
interface
16
NNbus
The 200-CPU50 function block diagram.
Backup
Unlike the other CPU models, 200-CPU50 has DRAMs with rechargeable
batteries, which means that the backup time is shorter. 200-CPU50 must be
powered for 15 hours before the battery can supply the memories (DRAM) and
the real-time clock during a power failure of maximum length. If 200-CPU50 has
been powered for less than 15 hours after the battery has been discharged, the
backup time will be shorter. After 15 hours, the 200-CPU50 starts to trickle-
charge the battery.
Note. The battery must be connected before operation. See "Changing Batteries
and Fuses", on page 113.
493-1068-11 (3-1) 59
7.2 Central Processing Unit, 200-CPU50 Chapter 7: Functional Description
Capacity available (% C)
100
90
80 0°C
70
60
50 20°C
40
30
20
45°C
10
0
0 1 2 3 4 5 6 7 8 9 10 11 12 Months
60 493-1068-11 (3-1)
Chapter 7: Functional Description 7.2 Central Processing Unit, 200-CPU50
200-CPU50 Connections
Connector for serial channel 0
9-pin female D-type connector
Note. For connection of the battery, see "Changing Batteries and Fuses", on page
113.
Pin Function
1 Not connected
2 Receive Data (RD)
3 Transmit Data (TD)
4 Not connected
5 Signal ground (0 V)
6 Not connected
7 Request To Send (RTS)
8 Clear To Send (CTS)
9 Not connected
493-1068-11 (3-1) 61
7.2 Central Processing Unit, 200-CPU50 Chapter 7: Functional Description
Terminal Function
62 493-1068-11 (3-1)
Chapter 7: Functional Description 7.3 Power Supply Unit, 200-PSMG
RS232 communication
See "RS232 communication", on page 76.
Front Panel
Indicators
Indication Function
Fail Red LED. Lit during power up. If it does not go out a short
time after power up, this means a hardware error.
Power Green LED. Lit when PSMG is in normal operation.
Clock Green LED. Lit when PSMG is in normal operation (200-
PSMG drives the clock).
Power Fail Red LED. Lit during power fail.
Functional Description
The PSMG is a power supply intended to be the primary DC power source. It uses
an external 24 V DC supply which is converted to a galvanically isolated semi-
regulated voltage 7 - 9 V (+Vu).
PSMG has a power fail circuitry (PF) for detection of power loss which senses a
24 V DC failure with the PF output connected to the screw terminal block. Other
units use the PF signal as input. The PF signal must be connected to the CPU. The
PF output status can also be read by the application program. See "Strapping PF-
signals and 0 V DC", on page 66.
The NNbus clock frequency is automatically set by the system program in the
CPU. The clock generator is supplied from +Vu in the Central System bus and
continues to operate during an error in the 200-PSMG DC/DC converter (see
figure on next page).
493-1068-11 (3-1) 63
7.3 Power Supply Unit, 200-PSMG Chapter 7: Functional Description
The LED indicators in the front of the unit show the status of the power, internal
logic and clock.
DC/DC
+Vu converter Fuse
24V
+
with power –
Power fail function
Clock
Clock
generator
Internal Fail
logic
64 493-1068-11 (3-1)
Chapter 7: Functional Description 7.4 Power Supply Unit, 200-PSSG
Front Panel
Indicators
Indication Function
Power Green LED. Lit when PSSG is in normal operation.
Power Fail Red LED. Lit during power fail.
Functional Description
The PSSG is a power supply intended to be an additional DC power source. It uses
an external 24 V DC supply which is converted to a galvanically isolated semi-
regulated voltage 7 - 9 V (+Vu).
PSSG has a power fail circuitry (PF) for detection of power loss which senses a
24 V DC failure. The PF output status can be read by the application program.
The LED indicators in the front of the unit show the status of the power and of the
power fail.
493-1068-11 (3-1) 65
7.4 Power Supply Unit, 200-PSSG Chapter 7: Functional Description
Power fail
+5V
NNbus
Interface
Terminal Function
1 0 V DC supply voltage
2 + 24 V DC supply voltage
3 Reserved (internally connected to terminal 1)
4 Reserved (internally connected to terminal 2)
5 Not connected
6 Not connected
7 Not connected
8 PF output for power fail circuitry (not used on PSSG)
9 Not connected
10 Not connected
11 Not connected
12 Not connected
66 493-1068-11 (3-1)
Chapter 7: Functional Description 7.4 Power Supply Unit, 200-PSSG
8 2
1 1 1
493-1068-11 (3-1) 67
7.5 Backup Unit, 200-BUP Chapter 7: Functional Description
Front Panel
Indicators
Indication Function
Note 1. The LEDs “Save”, “Verify” and “Load” are lit for a few seconds up to a
few minutes when the “SmartMedia” card is inserted into the card slot and it has
been identified by the system software.
Note 2. The two LEDs “Verify” and “Save” flash during the formatting
procedure.
68 493-1068-11 (3-1)
Chapter 7: Functional Description 7.5 Backup Unit, 200-BUP
Push buttons
Name Function
Functional Description
200-BUP is connected to the system via the Central System bus (NNbus). Note
that the screw terminal block connections are not used.
200-BUP uses a “SmartMedia” memory card to store the information to be
backed up. The backup unit has a slot in the front for the memory card. The card
is available in different versions, see "Backup Unit, 200-BUP", on page 143. The
memory cards are delivered pre-formatted, and can thus be used to make backups
without any preparation. The write protection label (enclosed with the card) is
adhesive and should be stuck onto the card after performing a backup to prevent
the information from being overwritten. It is recommended to use the write
protection label during “autoload”.
Important. Avoid to touch its surface and, if necessary, clean the gold plated
memory card connector using pure alcohol. .
200-BUP has Save, Load, Verify and Format functions. An “Autoload” function
is available for, e.g., automatic loading after a power failure.
The power supply part of 200-BUP takes its power from the system bus and
generates the required internal voltages.
493-1068-11 (3-1) 69
7.5 Backup Unit, 200-BUP Chapter 7: Functional Description
Power
Power 5V
conversion +3.3 V
Central Systembus (NNbus)
3.3 V
+5 V
Backup Err, Load, Verify, Save SmartMedia
Logic
Bus SmartMedia
and
Interface interface
level shifter
x3
70 493-1068-11 (3-1)
Chapter 7: Functional Description 7.5 Backup Unit, 200-BUP
“SmartMedia”
memory card
The write protection label must be absent to enable writing of information onto the memory
card.
2. Press the push button “Save” for about 2 seconds until the LED “Save” is lit.
The backup has been successful if the “Save” LED goes off and the “Backup
Err” LED is not lit.
3. To prevent further writing to the card, remove the card and affix the adhesive
write protection label onto the card (see figure above).
Loading information from the memory card into the control system
Follow the steps below to load information, e.g. an application program, from the
memory card into the control system.
1. Insert the memory card into the slot on the front of the backup unit, see figure
above.
2. Press the push button “Load” for about 2 seconds until the “Load” LED is
lit. Loading has been successful if the “Load” LED goes off and the LED
“Backup Err” is not lit.
Verifying information on the memory card and the control system
Follow the steps below to verify that information in the control system, e.g. an
application program, is the same as the information on the memory card.
493-1068-11 (3-1) 71
7.5 Backup Unit, 200-BUP Chapter 7: Functional Description
1. Insert the memory card into the slot on the front of the backup unit, see figure
above. The three LEDs “Save”, “Load” and “Verify” will be lit for about 5
seconds.
2. Press the push button “Verify” for about 2 seconds until the LED “Verify” is
lit. No discrepancies were detected if the LED “Verify” goes off and the LED
“Backup Err” is not lit.
Formatting the memory card
The memory cards are delivered pre-formatted and can thus be used to make
backups without any preparation. In some situations, however, reformatting can
repair a faulty memory card.
Note 1. All information on the card will be erased.
Note 2. The formatting procedure performed by the 200-BUP is more thorough
than the formatting procedure of a PC, as it makes an extensive test of every single
bit on the card. This procedure detects bad areas and prevents them from being
used to store data.
The formatting procedure can be activated by depressing the push-buttons Save
and Verify simultaneously for about 2 seconds until the two Leds “Save” and
“Verify” are flashing. The formatting procedure may also be activated by a
software command. Refer to the control system manual to achieve information on
how to activate the formatting function.
Since there is a risk of getting the wrong function when two push-buttons are
depressed simultaneously, i.e. only one of the buttons may be depressed by
accident, we recommend to use the software command above all.
Saving and reading the memory card information in a PC
The information on the memory card is stored in a standard format which can
easily be read and written by a PC. The PC must be equipped with a PC Card
adapter for “SmartMedia”. Information can then be transferred from the memory
card to the hard disk of the PC, and vice versa.
Autoloading the memory card information into the control system
An autoload function can be activated to automatically load the memory card
information into the control system. This function can be useful in restoring an
application program in the control system after a power failure. Refer to the
control system manual to read how to activate this autoload function.
72 493-1068-11 (3-1)
Chapter 7: Functional Description 7.6 Communication Interface RS232, 200-CI232
Front Panel
Indicators
Indication Function
Functional Description
CI232 interfaces to the system via the Central System bus (NNbus) and with
external units via two non-isolated RS232 channels.
The communication controller converts data to/from serial format. The signals are
converted to RS232 levels in the RS232 interfaces. All these signals have
protection against overvoltage.
The power supply part of the CI232 takes its power from the system bus and
generates required internal voltages.
LED indicators in the front of the unit are indicating the status of the
communication signals between the communication controller and the RS232
interfaces. One LED also indicates the status of the internal power.
493-1068-11 (3-1) 73
7.6 Communication Interface RS232, 200-CI232 Chapter 7: Functional Description
RD 0 TD 0 RTS 0
RS 232
Interface
Channel 6
0
NNbus Communication
Interface controller
RD 1 TD 1 RTS 1
NNbus
RS 232
Interface
Channel 6
1
+5V
Power
200-CI232 Connections
Connectors Ch0 and Ch1 for serial channels 0 and 1
9-pin female D-type connector
Pin Function
74 493-1068-11 (3-1)
Chapter 7: Functional Description 7.6 Communication Interface RS232, 200-CI232
Pin Function
Terminal Function
Terminal Function
1 Not connected
2 Not connected
3 Not connected
493-1068-11 (3-1) 75
7.6 Communication Interface RS232, 200-CI232 Chapter 7: Functional Description
Terminal Function
4 Not connected
5 Signal ground (0V), channel 1
6 Transmit Data (TD), channel 1
7 Receive Data (RD), channel 1
8 Request To Send (RTS), channel 1
9 Data Terminal Ready (DTR), channel 1
10 Clear To Send (CTS), channel 1
11 Data Carrier Detect (DCD), channel 1
12 Not connected
RS232 communication
This is a point-to-point communication standard with a maximum cable length of
15 meters. M The shield must be grounded where the cable enters the cabinet or
close to 200-CI232, see page 52. Also see "Recommended Components", on page
155. The cable connectors must have metallized covers.
If cable FKAR-PG is used for RS232, one conductor of each pair should be
connected to GND, the pins on the D-type connector (RTS-CTS).
If a standard cable without strapping on 7 - 8 is used, the strapping can be done
on the screw terminal block 200-BPP instead. Note. The strapping can be done on
200-BPP even if a front connector is used.
1
RD 2 TD
TD 3 RD
4
GND 5 GND
6
RTS 7
CTS 8
9
Series 200 side Controlled
device side
76 493-1068-11 (3-1)
Chapter 7: Functional Description 7.7 Communication Interface RS485, 200-CI485G
Front Panel
Indicators
Indication Function
Functional Description
CI485G interfaces to the system via the Central System bus (NNbus) and with
external units via 2 opto-isolated RS485 channels.
The communication controller converts data to/from serial format. The signals are
galvanically separated (isolated) by optocouplers and converted to RS485 levels
in the RS485 interfaces. All these signals have protection against overvoltage.
CI485G contains for each channel pull up and pull down resistors for the
communication wires. It also contains termination resistors and logic for selection
of two or four wire communication.
The power supply part of CI485G takes its power from the system bus and
generates required internal voltages.
493-1068-11 (3-1) 77
7.7 Communication Interface RS485, 200-CI485G Chapter 7: Functional Description
CI485G needs an external 24 V DC power supply for the two channels. This is
then converted to another voltage and galvanically separated from the two
channels.
The LED indicators in the front of the unit show the status of the communication
signals between the Communication Controller and the RS485 interfaces. A LED
also indicates the status of the external and internal power.
Channel 0
+5V Pull up
RD+/RDTD+
RD0 TD0 RTS0
RD-/RDTD-
Opto-
RS485 Termination
Interface Pull down
0V
TD+/RTS+
coupler
TD-/RTS-
Termination
NNbus Communication
Interface controller Logic for
control T/F
coupler
Power
+5V
9
NNbus
Power
DC +
24V
DC –
78 493-1068-11 (3-1)
Chapter 7: Functional Description 7.7 Communication Interface RS485, 200-CI485G
200-CI485G Connections
Screw terminal block connections
CI485G uses two screw terminal blocks.
The upper screw terminal block
Channel 0 with 2 wires:
Terminal Function
Terminal Function
493-1068-11 (3-1) 79
7.7 Communication Interface RS485, 200-CI485G Chapter 7: Functional Description
Terminal Function
Terminal Function
1 0 V DC supply voltage
2 +24 V DC supply voltage
3 Connect to 7 at cable ends (pull-down resistor)
4 Connect to 6 at cable ends (pull-up resistor)
5 Receive/Transmit Data - (RD/TD-)
6 Receive/Transmit Data + (RD/TD+)
7 Connect to 5 at cable ends (termination resistor)
8 Not connected
9 Connect to 11 at cable ends (termination resistor)
10 Isolated signal ground (0VG)
11 Request To Send - (RTS-) (output)
12 Request To Send + (RTS+) (output)
80 493-1068-11 (3-1)
Chapter 7: Functional Description 7.7 Communication Interface RS485, 200-CI485G
Terminal Function
1 0 V DC supply voltage
2 +24 V DC supply voltage
3 Connect to 7 at cable ends (pull-down resistor)
4 Connect to 6 at cable ends (pull-up resistor)
5 Receive Data negative, (RD-)
6 Receive Data positive, (RD+)
7 Connect to 5 at cable ends (termination resistor)
8 Connect to 10 (for 4-wire connection)
9 Connect to 11 at cable ends (termination resistor)
10 Isolated signal ground (0VG)
11 Transmit Data - (TD-)
12 Transmit Data + (TD+)
RS485 communication
Maximum length of the communication cable is 1200 metres and the maximum
number of connected units is 32.
M The shield must be grounded where the cable enters the cabinet. Also see
"Grounding Devices", on page 155.
Using the termination and the pull-up/pull-down resistors
When communicating over long distances (up to 1200 metres) the wire pairs must
be terminated at both ends. CI485G has built in termination resistors available on
the screw terminal block (see figure). One end of each termination resistor is
internally connected to the positive wire of each connection pair. If termination is
needed, the other end of the resistor can be strapped to the negative connection via
the screw terminal block.
In this case the pull-up/pull-down resistors should also be connected.
493-1068-11 (3-1) 81
7.7 Communication Interface RS485, 200-CI485G Chapter 7: Functional Description
1 - - 11 1 - - 11
RD- TD-
2-wire 4-wire
Strap for pull-up Strap for termination Strap for pull-up Strap for termination
Strap for 4-wire
1. The RTS signals are used to control, for example, repeaters. In normal installations
RTS is not used and should remain unconnected.
82 493-1068-11 (3-1)
Chapter 7: Functional Description 7.8 Communication Interface Ethernet, 200-CIE
Front Panel
Indicators
Indication Function
Switches
There are four rotary switches for unit address selection. The address is in decimal
format with the most significant digit on the top.
Example: Set an appropriate end IP address 172.16.X.Y
BCDE
x1000
7 8 9A
Example: x1000 =1
F 0 1 2
X
6
3 4 5
BCDE
x100 =2
7 8 9A
F 0 1 2
x100 x10 =3 Y
6
3 4 5
BCDE x1 =4
7 8 9A
F 0 1 2
3 4 5
BCD
i.e IP address: 172.16.12.34
7 8 9A
E
F 0 1 2
x1
6
3 4 5
493-1068-11 (3-1) 83
7.8 Communication Interface Ethernet, 200-CIE Chapter 7: Functional Description
Functional Description
200-CIE is an interface to the system via the NNbus and external units via an
Ethernet AUI port.
The Ethernet Controller performs all logic operations needed for the
communication.
A battery is used for back-up of the buffer memory in case of a system power
down.
Note. For connection of the battery see "Changing Batteries and Fuses", on page
113.
The power supply part of the CIE takes its power from the system bus and
generates needed internal voltages.
CIE needs an external 24 V DC supply. A DC/DC converter converts the voltage
to 12V DC which is connected to the standard (AUI) front panel connector.
Four rotary switches in the front of the unit are used to select the communication
address.
The LED indicators on the front of the unit show the communication and power
status.
A transceiver (MAU) should always be connected to the AUI port via a drop cable
to interface with the Ethernet network.
+
DC/DC 24V
Converter
Data buffer
memory
Power +5V
Power
84 493-1068-11 (3-1)
Chapter 7: Functional Description 7.8 Communication Interface Ethernet, 200-CIE
200-CIE Connections
Ethernet connector
A 15-pin D-type female connector with slide latch is provided for connection to
an external Ethernet transceiver via a drop cable.
Screw terminal block connections
200-CIE uses the lower screw terminal block.
Terminal Function
1 0 V DC supply voltage
2 + 24 V DC supply voltage
3 Not connected
4 Not connected
5 Not connected
6 Not connected
7 Not connected
8 Not connected
9 Not connected
10 Not connected
11 Not connected
12 Not connected
Transceiver connection
A transceiver must be connected (via a drop cable) to the AUI port of the CIE unit
to provide an interface with the Ethernet network. It is recommended that
200-CIE drop cable mountkit, CIE/MKIT1.0 or CIE/MKIT2.5 is used. 1.0 and 2.5
correspond to the length of the AUI cable in metres. Select a kit with an AUI cable
no longer than needed by the application. If possible fix the cable to the mounting
plate to avoid excessive mechanical stress on the AUI connectors and the
grounding device, 200-GDS. Ethernet cables should be regarded as sensitive to
electrical noise and should be installed separately from power and I/O cables as
recommended in "Installation of External Cables", on page 38.
493-1068-11 (3-1) 85
7.8 Communication Interface Ethernet, 200-CIE Chapter 7: Functional Description
A transceiver is connected via a drop cable to the AUI port of 200-CIE with CIE/MKIT 1.0
or CIE/MKIT 2.5.
Install the 200-CIE drop cable mountkit according to the installation instruction
included in the kit.
M Drop cable grounding
The drop cable is grounded by connecting the cable shield (at the stripped sheath
area, see figure above) to the grounding device, 200-GDS, included in the kit.
Trunk cable and transceiver
Select transceiver and type of trunk cable suited for the environment and install
according to manufacturers recommendations.
86 493-1068-11 (3-1)
Chapter 7: Functional Description 7.9 Communication Interface SattBus, 200-CISB
Front Panel
Indicators
Indication Function
Functional Description
200-CISB is an interface to the system via the Central System bus (NNbus) and
with external units via two SattBus channels.
There is a separate communication processor for each SattBus channel handling
the communication on the bus.
The two channels are individually isolated via transformers.
The two individual connections on each SattBus channel are equivalent and thus
the polarity does not matter.
The power supply part of the 200-CISB takes its power from the system bus and
generates required internal voltages.
The LED indicators in the front of the unit show the traffic on the two SattBus
channels and the power status.
493-1068-11 (3-1) 87
7.9 Communication Interface SattBus, 200-CISB Chapter 7: Functional Description
TD 0 RD 0
SattBus 0
TD 1 RD 1
NNbus
Interface
SattBus 1
Power +5V
Power
NNbus
200-CISB Connections
Screw terminal block connections
200-CISB uses the lower screw terminal block:
Terminal Function
88 493-1068-11 (3-1)
Chapter 7: Functional Description 7.9 Communication Interface SattBus, 200-CISB
Terminal Function
Installation of SattBus
For installation of the SattBus fieldbus, refer to the manual “This is SattBus”.
For recommended cables, see "Cables for Process Signals", on page 160.
Termination if SattBus is not used
If SattBus channel 0 is not used, terminals 11 and 12 should be connected via a
100 Ω resistor (min. 1/8 W). Otherwise the SattBus LEDs may flash
intermittently.
If SattBus channel 1 is not used, terminals 7 and 8 should be connected via a 100
Ω resistor (min. 1/8 W). Otherwise the SattBus LEDs may flash intermittently.
493-1068-11 (3-1) 89
7.10 Communication Interface ControlNet, 200-CICN Chapter 7: Functional Description
Front Panel
Indicators
Indication Function
OK Red/Green LED:
Off No power
Flashing Green Self test OK but not connected to
system
Green Connected to system
Flashing Red Recoverable fault
Red Critical, unit failure
Power Green LED: Lit if there is power from the system
90 493-1068-11 (3-1)
Chapter 7: Functional Description 7.10 Communication Interface ControlNet, 200-CICN
Indication Function
Mode switch
Normal in position 0.
Node address switches
Indication Function
Functional Description
The 200-CICN has an interface to the system via the Central System bus and with
external units via the ControlNet.
The microprocessor executes the communication protocol and system interface
software. It also includes a DMA controller and a serial communication
controller. The ControlNet controller controls the medium access functions.
The ControlNet transceiver has drivers and receivers for the ControlNet
connection. Connection is performed via an insulation transformer to a BNC
connector.
493-1068-11 (3-1) 91
7.10 Communication Interface ControlNet, 200-CICN Chapter 7: Functional Description
The power supply part of 200-CICN takes its power from the system bus and
generates required internal voltages.
Node address selection
The network address can be defined by 2 rotary switches. In normal
configurations, i.e. one 200-CICN that controls a number of distributed 200-ACN,
the address must be set to ”01”.
It is highly recommended to select addresses in a consecutive manner, i.e. 01, 02,
03 etc. Following this rule will minimize network load.
OK Power Com.
A B
Micro CN CN
Memories transceiver
Port processor controller
NNbus
Interface
DMA
controller
Mode Node Node
switch address address
X10 X1
Power +5V
NNbus
92 493-1068-11 (3-1)
Chapter 7: Functional Description 7.10 Communication Interface ControlNet, 200-CICN
200-CICN Connections
Connect the drop cable to the BNC connector on unit 200-CICN.
Installation
Refer to the document ”ControlNet, Planning and Installation” for instructions on
how to install the cables.
BNC connection
to ControlNet
493-1068-11 (3-1) 93
7.11 Communication Interface PROFIBUS-DP, 200-CIPB/DP-G Chapter 7: Functional Description
Front Panel
Indicators
Indication Function
Switch
A switch on the front of the unit connects a terminating resistor combination as
described in the “COMLI-PROFIBUS/DP User’s Manual”.
COMLI Connection
9-pin male D-type connector.
1 - Not used
2 RXD Receive data
3 TXD Transmit data
4 DTR Data terminal ready
94 493-1068-11 (3-1)
Chapter 7: Functional Description 7.11 Communication Interface PROFIBUS-DP, 200-CIPB/DP-G
PROFIBUS Connection
9-pin female D-type connector.
Functional Description
200-CIPB/DP-G unit serves as a gateway to transfer registers and I/O bits via
PROFIBUS-DP between a host system using the COMLI protocol and remote I/
O systems. A 9-pin D-type male connector on the front is used for configuration
and COMLI and a female one for PROFIBUS-DP.
There are LED indicators on the front for power supply, unit, communication and
field bus device diagnostics.
493-1068-11 (3-1) 95
7.11 Communication Interface PROFIBUS-DP, 200-CIPB/DP-G Chapter 7: Functional Description
The power is taken from a power supply unit 200-PSMG or 200-PSSG via a 200-
BPN backplane unit. No screw terminal block is required for the
200-CIPB/DP unit.
Dual port
PROFIBUS-DP
memory
PROFIBUS-DP
COMLI slave
master
The 200-CIPB/DP-G block diagram. The COMLI slave decodes the COMLI message, and
writes to and reads from the dual port memory. The PROFIBUS master reads from and
writes to the same memory.
96 493-1068-11 (3-1)
Chapter 7: Functional Description 7.12 Communication Interface PROFIBUS-DP, 200-CIPB/DP-SL
Indication Function
Switch
The PROFIBUS fieldbus must be terminated at the two ends which have the
longest cable path between them. This can be done in two different ways:
• using connectors with built-in termination. This method is recommended since
the fieldbus will always be terminated even if the cable is removed from the
unit.
493-1068-11 (3-1) 97
7.12 Communication Interface PROFIBUS-DP, 200-CIPB/DP-SL Chapter 7: Functional Description
• using the switch on the front of the unit. An internal terminator may be
connected to the end of the cable by setting the switch to ON.
COMLI Connection
9-pin male D-type connector.
1 - Not used
2 RXD Receive data
3 TXD Transmit data
4 DTR Data terminal ready
5 GND Signal ground (0 V)
6 - Not used
7 RTS Request to send
8 CTS Clear to send
9 - Not used
PROFIBUS Connection
Use a 9-pin female D-type connector.
98 493-1068-11 (3-1)
Chapter 7: Functional Description 7.12 Communication Interface PROFIBUS-DP, 200-CIPB/DP-SL
9 - Not used
Functional Description
200-CIPB/DP-SL handles cyclic read and write messages to the slaves on the
fieldbus. The minimum cycle time can be 1 ms, but depends on the baud rate and
the number of attached slaves.
32 nodes are allowed on one segment, but by use of repeaters, a maximum of 124
nodes may be connected. The table below shows the supported baud rates and the
maximum cable lengths.
Baudrate 9,6 19,2 93,75 187,5 500 1500 3000 6000 12000
(kbit/s)
Cable length 1200 1200 1200 1000 400 200 100 100 100
(m)
493-1068-11 (3-1) 99
7.12 Communication Interface PROFIBUS-DP, 200-CIPB/DP-SL Chapter 7: Functional Description
Micro Memory
processor
NNbus
Interface
PROFIBUS
Power ASIC
+5V
RS485
Driver
NNbus
Snap lock
Backplane
interconnector
(200-BPF)
Screw terminal
blocks 200-BPP
Code key
200-BPP
200-BPP is a 12-pole screw terminal block used for connecting power and
communication signals. It can only be inserted or removed when the Central
System unit has been removed.
200-BPP is located above and below an Central System unit. Some Central
Processing Units use only the lower 200-BPP and other use both. When used in
the lower position the terminals are numbered 1 - 12 (lower row, odd 1-11 and
upper row, even 2-12) and in the upper position 13 - 24 (upper row, odd 13-23 and
lower row, even 14-24).
Cable cross sectional area should be 0.5 - 2.5 mm2 or AWG 20-12 stranded.
Recommended tightening torque is 0.5 - 0.8 Nm. It is possible to attach Phoenix
ZB type markings on 200-BPP.
Note! Use copper wires only.
200-BPT
Backplane termination pair. There is one "START"-plug (green) and one "STOP"-
plug (red). Internal current consumption: 0.2 A. Read "Mounting the Bus
Terminators", on page 47 for more information on how to use them.
200-CBA/L260 and 200-CBA/L260V
Cable backplane to adapter that connects the Central System backplane to the
closest local I/O adapter. 200-CBA/L260V is used for vertical I/O mounting, see
appendix "Mounting Dimensions", on page 161.
200-CBB/R360
Cable backplane to backplane. This cable connects two Central System
backplanes. It is placed on the far right side of the Central system.
200-CAA/L190 and 200-CAA/L380
Cable adapter to adapter. Connects one central I/O adapter 200-ANN to another
200-ANN, see appendix "Mounting Dimensions", on page 161.
Chapter 8
Start-up of Series 200
This chapter describes how the SattCon 200 Central System is started up and what
happens during start-up. For SattLine see ”SattLine Installation Manual”.
Warning! Read the safety instructions in this manual before start-up! Before
start-up and any fault finding, make sure that no output can affect any part of the
process. This is to avoid any mishaps as a result of work with the test function. If
necessary, make sure that the process is completely disconnected.
Different situations require different start-up sequences. These situations are:
• The first start-up as part of the installation procedure.
• A start-up in order to load a new system program (not application) into the
system.
• A normal start-up to restart the application program (warm start/soft reset).
• A start-up to clear the application program (cold start/total reset).
There are two ways to achieve a start-up:
• Turn on the power supply.
• Press the reset button on the front of the CPU and keep it depressed for at least
1 second.
Note. The system enters the debug mode if the reset button is pressed for less than
1 second. If you accidentally press the reset button for less than 1 second, press it
once more, this time for more than 1 second.
The mode switch on the front of the CPU decides which start-up sequence is to
be activated. A list is given later in this section showing which switch position
gives which start-up sequence.
The figure below shows the steps comprising different start-up sequences.
Check of
backplanes
Fig. 0-1 A self-test is performed at all situations except when loading the system program.
Position Situation
• A small screwdriver to set the required position of the mode switch on the front
of the CPU.
Mode switch
Fig. 0-2 A VT100 terminal or a PC with a terminal emulator is connected to the CPU.
The Self-test
The test procedure is performed as follows.
1. Set the mode switch on the front of the CPU to position 6.
2. Power up the system or press the reset button (for longer than 1 second) and
check that the green power LEDs are lit on all units.
The CPU system is now entering the test mode, i.e. the CPU is tested (test of
EPROM, RAM, communication channels, floating point processor, battery
status, etc.).
3. Check that all the appropriate tests are passed, if not see Error Help on page
110.
The following printout is an example of the printout from the correct start-
up of a CPU. Note that the first 3 lines appear whenever when you press the
reset button (> 1 second).
pROBE+ 1.1-6 12-JUL-1994 12:44:55.50
Serial Number 2043
CPU3 0.Pb 07-OCT-1993 Hardware Configuration: 492****-**
Error Help
If the hardware test fails, the printout from the test reports the faults by entering
<FAIL> beside the failed test:
The printout below is an example of the printout from a faulty start-up:
.
.
Diagnostic level 1 /version 1.4 -- 910207
PORT_PWR Verify power-fail status................... <PASS>
PORT_ABO Verify abort switch status................. <PASS>
PORT_BAT Battery low-level voltage check............
Battery low detected .................. <FAIL>
ROM0_CSM Verify debug checksum...................... <PASS>
.
.
Diagnostic level 1 ........................ <FAIL>
.
.
In this case, the voltage level from the battery is detected as low. This can be due
to the fact that the battery is disconnected or needs changing.
Troubleshooting table
The following table may be of help if start-up errors are encountered. Also see
Troubleshooting the Central System on page 124. Follow the troubleshooting
procedure step by step. Continue if the error persists.
Error Measure
Error Measure
Chapter 9
Maintenance and Service
This chapter describes the maintenance needed for the Series 200 and how to
troubleshoot the system.
Note! Read the ”Safety warnings” at the beginning of this manual before
performing operations which can be dangerous for personnel or cause damage to
equipment.
Warning: Battery change may not be performed during conditions with explo-
sion hazards.
Battery
Battery
connector
2a. If the unit includes CL 1 DIV 2 on the product label, detach the battery at the
connector closest to the battery (not on the circuit board). Recycle the old
battery. See figure below.
3a. If the unit includes CL 1 DIV 2 on the product label, attach the new battery
from the BAT200 battery kit to the battery cable on the unit according to the
figure below. Recycle the conversion cable that remains in the BAT200 bat-
tery kit. This cable is not used on units labelled CL 1 DIV 2.
BAT200-CPU50
3b. If the unit does not include CL 1 DIV 2 on the product label and does not
have a connection that fits to the new battery, attach the new battery from the
BAT200 battery kit to the conversion cable from the BAT200 battery kit.
Then attach it to the connector on the circuit board. See figure below. If the
conversion cable is already present from a preceding battery exchange, then
it should not be exchanged. Recycle the conversion cable that remains in the
BAT200 battery kit.
BAT200-CPU50
Note! During installation of the conversion cable from the BAT200-CPU50 bat-
tery kit, (see step 2b and 3b below), the system should not be powered.
To change the battery, follow step 1 to 7 below:
1. Slide the battery holder on the front panel upwards and pull it out.
2a. If the unit includes CL 1 DIV 2 on the product label, detach the battery at the
connector closest to the battery, (not on the circuit board). Recycle the old
battery. See figure below.
2b. If the unit does not include CL 1 DIV 2 on the product label and does not
have a connection that fits to the new battery, remove the front panel as
described in chapter "Changing the Battery in CPU20, CPU30, CPU40...".
Then detach the battery at the connector on the circuit board. Recycle the old
battery and the old connection cable. See figure below.
3a. If the unit includes CL 1 DIV 2 on the product label, attach the new battery
from the BAT200 battery kit to the battery cable on the unit according to the
figure below. Recycle the conversion cable that remains in the BAT200 bat-
tery kit. This cable is not used on units labelled CL 1 DIV 2.
BAT200-CPU50
3b. If the unit does not include CL 1 DIV 2 on the product label and does not
have a connection that fits to the new battery, attach the conversion cable
from the BAT200 battery kit to the connector on the circuit board. Remount
the front panel and lead the conversion cable through the hole for the battery
holder. Connect the new battery from the BAT200 battery kit to the conver-
sion cable. See figure below. If the conversion cable is already present from
a preceding battery exchange, then it should not be exchanged. Recycle the
conversion cable that remains in the BAT200 battery kit.
BAT200-CPU50
No manual reset is needed though since this is performed automatically when the
system power is restored.
Battery
connector
Battery
Changing Fuses
The power supply units, 200-PSMG, 200-PSSG and the Communication Inter-
face Ethernet, 200-CIE, contain fuses. The type is described in the appendix
"Technical Specifications", on page 133.
Note! Before changing fuses, turn system power off and remove the unit in ques-
tion.
Changing the fuse in 200-PSMG and 200-PSSG
There is one fuse on the printed circuit board inside the unit. It protects the input
of the power supply. The fuse can be replaced.
Remove the front panel using a small screwdriver and bend carefully to open the
two snaps locks on each side of the panel, see figure. The fuse is located on the
printed circuit board facing the front panel, see figure. Remove and replace the
fuse. Remount the front panel onto the unit again.
Fuse
Fuse
Troubleshooting 200-PSMG
Symptom Measure
Troubleshooting 200-PSSG
Symptom Measure
Symptom Measure
Troubleshooting 200-CPU50
Symptom Measure
Symptom Measure
Troubleshooting 200-BUP
Symptom Measure
LED Backup Error is lit 1. Check that the SmartMedia card is inserted
properly into the slot.
2. If a “Load”, “Autoload” or “Format” operation is to
be performed, check that the card is not
write-protected.
3. If a “Verify”, “Load” or “Autoload” operation is
activated, check in the relevant Programmer’s
Manual.
4. If the error is still not identified, try to reformat the
SmartMedia card. Note that the formatting procedure
erases all information on the card.
LEDs “Verify” and 1. Check that the SmartMedia card is inserted
“Save” are flashing properly into the slot.
faster than usual during
formatting, and the 2. Make sure there is nothing which prevents
LED Backup Error is lit electrical contact between the connector and any of
(after a few seconds) the connections on the “SmartMedia” card.
3. Test with another card. If this card works properly,
the malfunctioning one is probable damaged.
Troubleshooting 200-CI232
Symptom Measure
Troubleshooting 200-CI485G
Symptom Measure
Troubleshooting 200-CISB
Symptom Measure
Troubleshooting 200-CIE
Symptom Measure
Troubleshooting 200-CICN
OK status LED
Symptom Measure
Symptom Measure
Symptom Measure
Symptom Measure
Symptom Measure
Appendix A
Technical Specifications
Function Data
Technical data
Number of slots 2
Internal current Max. 0.04 A.
consumption Note. The current consumption is included in the current
(from PSMG/ consumption data given for the Central System units, i.e. do
PSSG) not add this current when calculating the total system
current
Connectors 4 connections for screw terminal blocks 200-BPP
2x32-pole Euro Connector for electrical connections
between the backplane and the units
Mounting On DIN rail 35x7,5 mm according to the EN 50022 standard
Weight 0.17 kg excl. package
0.24 kg incl. package
Dimensions Width: 91 mm excluding a 5 mm hook to the next
backplane
Height: 163 mm excluding the screw terminal blocks
239 mm including one screw terminal block on each
edge
Depth: 43 mm (127 mm including Central unita and DIN-
rail)
Order code 200-BPN
a. Some units have front connectors, which increase the required panel depth when
installing the units.
CPU Description
All types have RAM memory and real time clock, both with battery back-up. Two
RS232 serial channels are also included on all types.
Technical data
Technical data
Clock frequency 16.7 MHz for CPU20 and 30, 28.8 MHz for CPU40
Math co-processor Yes (not on CPU20/10)
Memory for 200-CPU20/10 1 Mbyte RAM with battery back-up
system and 200-CPU30/10 1 Mbyte RAM with battery back-up
application 200-CPU30/20 2 Mbyte RAM with battery back-up
program 200-CPU30/30 4 Mbyte RAM with battery back-up
200-CPU30/40 4 Mbyte RAM with battery back-up
200-CPU40/40 4 Mbyte RAM with battery back-up
200-CPU30/30 4 Mbyte RAM with battery back-up
200-CPU30/40 4 Mbyte RAM with battery back-up
200-CPU30/40-SL 4 Mbyte RAM with battery back-up
200-CPU40/40-SL 4 Mbyte RAM with battery back-up
200-CPU40/80-SL 8 Mbyte RAM with battery back-up
200-CPU40/120-SL 12 Mbyte RAM with battery back-up
Status indicators Green LEDs for Power, SattBus signals SB TD0, SB RD0
and the serial channel signals TD 0, TD 1, RD 0 and RD 1
Red LEDs for Fail and Stop
Communication Serial channels:
channels 2 RS232 channels with baudrates 75, 110, 134.5, 150, 300,
600, 1200, 1800, 2000, 2400, 4800, 9600 (default) and
19200 baud
Channel 0 has connections for TD, RD, RTS, CTS, DCD
and DTR
Channel 1 has connections for RD and TD
Maximum cable length: 15 metres
Data bits: 7 or 8 (default)
Parity: Odd, even or none (default)
Stop bits: 1 (default) or 2
SattBus: 1 channel, supervisor (not available on CPU20/
10)
Technical data
CPU Description
All types have dynamic RAM memories (DRAM) and a real-time clock, both
with battery backup. An RS232 serial channel is also included..
Technical data
Technical data
Technical data
Technical data
Status indicators Green LEDs for Power, Load, Save and Verify
Red LED for Backup error
Push buttons Load, Save, Verify and Format
SmartMedia slot Slot for SmartMedia memory cards
SmartMedia card 4 Mbyte, 8 Mbyte or 16 Mbyte, 3.3 V DC
Power supply From power supply unit 200-PSMG/PSSG
Internal current Max. 0.3 A
consumption (from
PSMG/PSSG)
Backplane key 8
code
Weight 0.18 kg excl. package
0.25 kg incl. package
Dimensions W 45 x H 163 x D 91 mm (excl. connectors and snap
locks)
Order codes 200-BUP, 200-MEM4, 200-MEM8 and 200-MEM16
Technical data
Number of 2
channels
Communication Asynchronous serial communication RS232-C
interface
Status indicators Green LEDs for RD, TD, RTS and Power
Galvanic No
isolation
Speed of transfer 75, 110, 134.5, 150, 300, 600, 1200, 1800, 2000, 2400,
4800, 9600 (default) and 19200 baud
Maximum cable length: 15 metres
Data bits 7 or 8 (default)
Parity Odd, even or none (default)
Stop bits 1 (default) or 2
Max load on 5 mA
DTR
Power supply From Power supply unit 200-PSMG/PSSG
Internal current Max. 0.2 A
consumption
(from PSMG/
PSSG)
Connectors Two 9-pin D-type female connectors
Two Screw terminal blocks
Backplane key 8
code
Weight 0.20 kg excl. package
0.27 kg incl. package
Dimensions W 45 x H 163 x D 91 mm (excl. connectors and snap locks)
Order code 200-CI232
Technical data
Number of channels 2
Number of nodes 32 per channel
Communication Asynchronous serial communication RS485
interface
Status indicators Green LEDs for RD, TD, RTS and Power
Galvanic isolation 500 V AC rms. The channels are individually isolated
from the main logic and 24 V DC
Speed of transfer 75, 110, 134.5, 150, 300, 600, 1200, 1800, 2000, 2400,
4800, 9600 (default) and 19200 baud. Max. cable length
1200 m
Data bits 7 or 8 (default)
Parity Odd, even or none (default)
Stop bits 1 (default) or 2
Power supply From Power supply unit 200-PSMG/PSSG and external
power supply (24 V DC)
Internal current Max. 0.2 A
consumption
(from PSMG/PSSG)
External current Max. 0.1 A (taken from external 24 V DC)
consumption
Connectors Two Screw terminal blocks
Backplane key code 8
Weight 0.22 kg excl. package
0.29 kg incl. package
Technical data
Technical data
Number of channels 1
Communication IEEE 802.3 (Ethernet)
standard
Status indicators Green LEDs for Power, Transmit data TD 0, Received
data RD 0 and Ethernet traffic NET
Red LED for Fail (software controlled)
Galvanic isolation According to the IEEE 802.3 standard, the transceiver
(MAU) must provide isolation between the AUI cable
and the broadband coaxial medium. When taking
current from the AUI, it must not exceed 0.5 A as
provided by the AUI source
For further details see ANSI/IEEE Std. 802.3 and the
SS-ISO 8802-3
Speed of transfer 10 Mbits per second
Access method CSMA/CD (Carrier Sense, Multiple Access with
Collision Detect)
Input fuse Fuse 1.25 A slow. Microfuse TR5 IEC-127-3
Backup battery Lithium (3.67 V, 0.8 Ah, 1/2 AA / 1/2 RG /1/2 UM-3)
with connection cable
Power supply From Power supply unit PSMG/PSSG and external
power supply (24 V DC)
Internal current Max. 0.25 A
consumption (from
PSMG/PSSG)
External current Max. 0.5 A at 19.2 V DC in (typically 0.2 A) taken from
consumption external 24 V DC supply (depending on transceiver
type)
Technical data
Technical data
Number of channels 2
Communication SattBus
protocol
Number of nodes 120 nodes
Speed of transfer 62.5 kbits/s
Access method Token bus
Status indicators Green LED for RD 0, TD 0, RD 1, TD 1 and Power
Galvanic isolation 500 V AC rms. The channels are individually isolated
via signal transformers
Connector One Screw terminal block
Power supply From Power supply unit PSMG/PSSG
Internal current Max. 0.3 A
consumption (from
PSMG/PSSG)
Backplane key code 8
Weight 0.25 kg excl. package
0.32 kg incl. package
Dimensions W 45 x H 163 x D 91 mm (excl. connectors and snap
locks)
Order code 200-CISB
Technical data
Number of channels 1
Communication protocol ControlNet
Access method CTDMA (Concurrent Time Division Multiple
Access)
Galvanic isolation Isolation via a signal transformer
Speed of transfer 5 Mbit/sec
Status indicators Green/Red LED for unit status (OK)
Green/Red LED for Communication information
(COM A and B)
Power LED
Power supply From Power supply unit 200-PSMG/PSSG
Internal current Max. 0.5 A
consumption (from
PSMG/PSSG)
ControlNet connector BNC 75 Ω
Backplane code key 8
Weight 0.25 kg excl. package
0.33 kg incl. package
Dimensions H 163 x W 45 x D 91 mm (excl. connectors and
snap locks)
Order code 200-CICN
Technical data
Technical data
Technical Data
Weight 0.092 kg
Dimensions
Length 260 mm
Technical Data
Dimensions
Length 190 mm
Technical Data
Dimensions
Length 380 mm
Technical Data
Dimensions
Length 3.0 m
Appendix B
Recommended Components
This appendix lists recommended cables and components available on the market
to be used when installing the Central system/Controllers/I/O system.
Power-Line Filters
Power-line filters for 230 V AC and external 24 V DC (Filter type A)1
Recommended type: Schaffner: FN 660, Schaffner FN 2060 or a correspond-
ing two-stage filter for mounting plate assembly.
Power-line filters for analog signals and pulse counter signals 24 V DC
(Filter type B)1
Recommended type (1): Schaffner FN 610, Schaffner FN 2010 or a correspond-
ing one-stage filter for mounting plate assembly.
Recommended type (2) : Phoenix NEF 1 or a corresponding one-stage filter for
DIN rail assembly.
Grounding Devices
Universal ground terminal blocks
Recommended type (1): Phoenix: USLKG4 (green/yellow)
Recommended type (2): Weidmüller: WPE 2,5 (green/yellow)
Earth rail
Recommended type: Weidmüller: Ssch 10x3 Cu
Grounding clamp for shielded cables
Recommended type: Weidmüller: KLBÜ4-13.5
Comments: Earth rail (10x3 mm) mounted. Used to connect
a cable shield to the ground (0 V).
Complement: Phoenix:
DATA-PLUGTRAB UFBK 2-PE-5DC-HB-BE or
corresponding type.
Description: Signal circuit protection that protects data interfaces
operating at high transmission rates. Base element
with grounding foot for mounting rails. Used
together with the plug-in module above.
Comments: Used if SattBus runs between buildings.
Surge voltage protection for telephone line
Recommended type (1): Phoenix: LINETRAB UFB 2-PE-220 DC
Description: Complete for DIN rail. Is to be connected via
adjacent ground terminal block.
Recommended type (2): Phoenix:
MCR-PLUGTRAB-UFBK 2 PE-220DC-ST
Description: Plug-in module needed together with base element
below.
Complement: Phoenix:
MCR-PLUGTRAB-UFBK 2 PE-220DC-BE
Description: Base element with universal foot for mounting
on rails.
Comments: Is used for surge voltage protection of telephone
lines. It is to be interconnected between the modem
and the telephone line if there is a risk of over-
voltage caused by direct lightning strikes. Fuse
protected from the telephone line.
Miscellaneous
DIN rail
Recommended type: Phoenix:
TS 35/7,5. Steel, yellow chromated with holes
DIN 46 277
EN 50 022
DIN rail accessories
Recommended type: Phoenix: UK 4-TG
+ ST-BE
Description: Component adapter
Power Supplies
Power supply output 24 V DC
Recommended type (1): Phoenix1: CM90-PS-230 AC/24 DC/2
Description: Input: 230 V AC
Output: 24 V DC/2A
Recommended type (2): Phoenix1: CM125-PS-230 AC/24 DC/5
Description: Input: 230 V AC
Output: 24 V DC/5A
Recommended type (3): Omron: S82K-05024
Description: 2 A, switchable 115/230 V.
Recommended type (4): MEAN WELL: S-60-24 DIN
Description: 2.5 A, input range 90-260 V.
Appendix C
Mounting Dimensions
200 mm
130 mm
I005261D
Front connectors on Central System units require a cabinet depth of 200 mm or more.
1 2
1. Central system
3
2. 24 V DC power supply
for Central system
3. Central I/O system
4. Cable backplane to
Adapter 4
5. Power supply for the
central I/O system
6. Power-line filter
6
5
Two central I/O systems installed in a wall cabinet and a floor cabinet, respectively.
Central system 6
4
1
2
1. Central system
2. 24 V power supply
for remote system
3. Remote I/O system
4. Tap for connection
to ControlNet
5. Power-line filter 3
6. ControlNet cable
A central I/O system and a remote I/O system installed in two cabinets.
M Central system
360
Central system
255
37
220
M Maximum 200
200-CAA/
L190
⊗
This measure may be reduced by 15
mm if no identification strip (1) is used
200-
CBA/
L260
200-CAA/
⊗ L190
200-CBA/
L260
200-CAA/L380
⊗
This measure may be reduced by 15
mm if no identification strip (1) is used.
200-CBA/ 200-CAA/L190
L260V
200-CBA/
L260
200-CAA/L380
⊗
All dimensions in mm.
200-CAA/L190
200-CBA/
L260V
Appendix D
Standards
Warning: Explosion hazard – Do not replace components unless the power has
been switched off or the area is known to be non-hazardous.
Appendix E
Directive Considerations