Operating Manual Controls: AC1 AC2 AC3

Download as pdf or txt
Download as pdf or txt
You are on page 1of 110

Operating manual

Controls

AC 1
AC 2
AC 3VARIABLE 35 - 130
ALMiG Kompressoren GmbH
Adolf-Ehmann-Straße 2
73257 Köngen
Telephone: +49 7024 9614 240
Fax: +49 7024 9614 209
email: [email protected]
Internet: www.almig.de
Service Hotline:
Telephone: +49 1805 25 87 00
Fax: +49 1805 25 87 01

Translation of the original operating instructions


Almi-12135-DE

© ALMiG Kompressoren GmbH 2010

2 2012-07-13
Controllers AC 1, AC 2, AC 3

Supplemental instructions

Overview of the Controllers For the controller variant installed, please consult the
label on the controller.

AIR CONTROL 1
 Chapter 4 ‘Air Control AC 1 controller’ on pa-
ge 25

AIR CONTROL 2
 Chapter 5 ‘Air Control AC 2 controller’ on pa-
ge 49

AIR CONTROL 3
 Chapter 6 ‘Air Control AC 3 controller’ on pa-
ge 70

2012-07-13 3
Controllers AC 1, AC 2, AC 3

Table of contents

Table of contents
1 General information ...............................................................7
1.1 Information about these instructions ..............................7
1.2 Explanation of symbols ..................................................8
1.3 Limitation of liability......................................................10
1.4 Copyright ......................................................................10
1.5 Warranty terms.............................................................10
1.6 Customer service .........................................................11

2 Safety.....................................................................................12
2.1 Proper use....................................................................12
2.2 Responsibility of the owner ..........................................13
2.3 Personnel requirements...............................................14
2.3.1 Qualifications ................................................14
2.3.2 Unauthorised persons ..................................15
2.3.3 Training.........................................................15
2.4 Personal protective equipment ....................................16
2.5 Basic dangers ..............................................................17
2.5.1 General dangers in the workplace................17
2.5.2 Dangers due to electric power......................17
2.6 Safety equipment .........................................................18
2.6.1 Description of the safety equipment
installed.........................................................18
2.7 Securing to prevent restart...........................................20
2.8 Behaviour in case of fire or accidents ..........................22

3 General safety instructions for all controllers ..................23


3.1 Safety instructions for the operation ............................23
3.2 Operating personnel and personal protective
equipment ....................................................................23
3.3 Shutdown in emergency situations ..............................24

4 Air Control AC 1 controller..................................................25


4.1 Overview of Air Control AC 1 .......................................25
4.2 Brief description ...........................................................26
4.3 Operating modes..........................................................26
4.4 Overview of display ......................................................27
4.4.1 Other display indicators ................................27
4.4.2 Operating mode display................................28
4.5 Switching the compressor on/off..................................28
4.6 Calling up information ..................................................29
4.7 Setting parameters via code input menu .....................30

4 2012-07-13
Controllers AC 1, AC 2, AC 3

Table of contents

4.7.1 Calling up the code input menu....................30


4.7.2 Overview of code input menu.......................31
4.7.3 Inputting a code ............................................31
4.7.4 Overview of submenus.................................32
4.7.5 Select operating mode: Code 0002..............33
4.7.6 Switch automatic restart on/off: Code 0003 .35
4.7.7 Set on-site operation/remote operation:
Code 0008 ....................................................36
4.7.8 Set switch on/off pressure: Code 0011 ........38
4.7.9 Switch Basic load switching mode on/off:
Code 0018 ....................................................39
4.7.10 Switch the pressure unit: Code 0090 ...........40
4.7.11 Switch the temperature unit: Code 0095......41
4.7.12 Display the software version: Code 9999.....42
4.8 Fault and warning messages.......................................43
4.8.1 Fault message ..............................................43
4.8.2 Warning/maintenance messages .................45
4.8.3 Acknowledging fault and warning
messages .....................................................47
4.9 Setting the display contrast..........................................48

5 Air Control AC 2 controller .................................................49


5.1 Overview of Air Control AC 2.......................................49
5.2 Brief description ...........................................................50
5.3 Operating modes .........................................................50
5.4 Overview of display......................................................51
5.4.1 Operating data display area .........................51
5.4.2 Operating mode display ...............................52
5.5 Switching the compressor on/off..................................53
5.6 Calling up information ..................................................53
5.7 Setting parameters via code input menu .....................55
5.7.1 Calling up the code input menu....................55
5.7.2 Overview of code input menu.......................55
5.7.3 Inputting a code ............................................56
5.7.4 Overview of submenus.................................56
5.7.5 Select operating mode: Code 0002..............57
5.7.6 Switch automatic restart on/off: Code 0003 .59
5.7.7 Set on-site operation/remote operation:
Code 0008 ....................................................60
5.7.8 Setting the switch-on/switch-off pressure
and minimum pressure/BLS: Code 0011 .....61
5.7.9 Switch Basic load switching mode on/off:
Code 0018 ....................................................62

2012-07-13 5
Controllers AC 1, AC 2, AC 3

Table of contents

5.7.10 Switch the pressure unit: Code 0090 ...........63


5.7.11 Switch the temperature unit: Code 0095 ......64
5.7.12 Display the software version: Code 9999 .....65
5.8 Fault and warning messages .......................................65
5.8.1 Fault message ..............................................65
5.8.2 Warning/maintenance messages .................67
5.8.3 Acknowledging fault and warning
messages .....................................................69

6 Air Control AC 3 controller..................................................70


6.1 Overview of Air Control AC 3 .......................................70
6.2 Brief description ...........................................................71
6.3 Operating modes..........................................................72
6.4 Overview of display ......................................................73
6.5 Switching the compressor on/off..................................74
6.6 Calling up displays/information via function keys ........75
6.6.1 Changing the function programming of the
function keys.................................................75
6.6.2 Calling up the Capacity utilisation display ....76
6.6.3 Calling up the Basic load switch display.......77
6.6.4 Calling up the Service display ......................77
6.6.5 Calling up the System pass display..............78
6.6.6 Calling up the Diagram-network pressure
display...........................................................79
6.6.7 Calling up the Diagram-compression final
temperature display ......................................80
6.6.8 Calling up the Diagram-compressed
air/day display...............................................81
6.6.9 Calling up the Diagram-compressed
air/week display ............................................81
6.7 Editing axis values of the display diagrams .................82
6.8 Setting parameters via menu system...........................84
6.8.1 Calling up the code input menu ....................84
6.8.2 Overview of code input menu .......................84
6.8.3 Inputting a code ............................................84
6.8.4 Selecting overview of submenus and
submenus .....................................................85
6.8.5 Fault and warning messages......................102
6.8.6 Setting the display contrast ........................104

7 Index ....................................................................................105

8 Appendix .............................................................................108

6 2012-07-13
Controllers AC 1, AC 2, AC 3

General information

1 General information
1.1 Information about these instructions
This manual enables safe and efficient handling of the machine. It is
an integral part of the machine, and must be kept in close proximity to
the machine where it is permanently accessible to the personnel.
Before starting any work, the personnel must have read the manual
thoroughly and understood its contents. Compliance with all specified
safety instructions and operating instructions is vital to ensure safe
operation.
In addition, local accident prevention regulations and general safety
instructions must be observed for the operational area of the machine.
Illustrations in this manual are intended to facilitate basic understand-
ing, and may differ from the actual design.

The instructions for the controller are a separate part of the compres-
sor. Therefore, the instructions and content of the instructions for the
compressor in question must also be taken into account.

2012-07-13 7
Controllers AC 1, AC 2, AC 3

General information

1.2 Explanation of symbols


Safety instructions The safety instructions provided in this manual are marked by sym-
bols. The safety instructions are introduced by keywords used to ex-
press the extent of the danger.
Strictly adhere to all safety instructions and use caution to prevent
accidents, personal injury and material damage.

DANGER!
This combination of symbol and keyword points to a si-
tuation of immediate danger which may lead to serious
injury or death unless avoided.

WARNING!
This combination of symbol and keyword points to a si-
tuation of possible danger which may lead to serious in-
jury or death unless avoided.

CAUTION!
This combination of symbol and keyword points to a
possibly dangerous situation which may lead to slight or
minor injury unless avoided.

NOTICE!
This combination of symbol and keyword points to a
possibly dangerous situation which may lead to material
and environmental damage unless avoided.

Tips and recommendations This symbol highlights useful tips and recommendations
as well as information designed to ensure efficient and
smooth operation.

8 2012-07-13
Controllers AC 1, AC 2, AC 3

General information

Special safety instructions The following symbols are used in the safety instructions to draw at-
tention to specific dangers:

DANGER!
This combination of symbol and signal word indicates
dangers posed by electric power. If the safety instruc-
tions are not observed, there is a danger of serious or
fatal injuries.

WARNING!
This combination of symbol and signal word indicates
dangers posed by an atmosphere capable of exploding.
If the safety instructions are not observed, there is a
danger of serious or fatal injuries.

Signs used in this manual The following signs and highlighting is used in this manual to identify
instructions, descriptions of results, numerations, references and other
elements:

Sign Explanation
1., 2., 3., ,,, Identifies step-by-step instructions.

 Identifies a state or automatic sequence as


result of steps.

Identifies references to chapters in this manual


and to other valid documents.

Identifies random numerations and list entries.

[Key] Indicates names of keys, buttons and other


operating controls.

2012-07-13 9
Controllers AC 1, AC 2, AC 3

General information

1.3 Limitation of liability


All specifications and instructions in this manual have been compiled
taking account of applicable standards and regulations, the current
state of technology and the experience and insights we have gained
over the years.
The manufacturer accepts no liability for damage due to:
 Failure to observe this manual
 Improper use
 Deployment of untrained personnel
 Unauthorised modifications
 Technical modifications
 Use of unauthorised spare parts
The actual scope of supply may differ from the explanations and de-
pictions in this manual in the case of special designs, take-up of addi-
tional ordering options, or as a result of the latest technical modifica-
tions.
The undertakings agreed in the supply contract as well as the manu-
facturer's Terms and Conditions and Terms of Delivery and the legal
regulations applicable at the time of conclusion of the contract shall
apply.

1.4 Copyright
This manual is protected by copyright and intended solely for internal
use.
This manual must not be made available to third parties, duplicated in
any manner or form – whether in whole or in part – and the content
must not be used and/or communicated, except for internal purposes,
without the written consent of the manufacturer.
Violation of the copyright will result in legal action for damages. We
reserve the right to assert further claims.

1.5 Warranty terms


The warranty terms are included in the manufacturer's Terms and
Conditions.

10 2012-07-13
Controllers AC 1, AC 2, AC 3

General information

1.6 Customer service


Our customer service division is available to provide technical informa-
tion. See page 2 for contact details.
In addition, our employees are always interested in acquiring new
information and experience gained from practical application; such
information and experience may help improve our products.

2012-07-13 11
Controllers AC 1, AC 2, AC 3

Safety

2 Safety
This section provides an overview of all the main safety aspects in-
volved in ensuring optimal personnel protection and safe and smooth
operation.
Non-compliance with the action guidelines and safety instructions
contained in this manual may result in serious hazards.

2.1 Proper use


The controllers are designed and constructed exclusively for the pro-
per use described here.

The controllers Air Control AC 1, AC 2 and AC 3 are intended


exclusively to control Almig screw compressors.

The proper use also includes adherence to all details in these instruc-
tions.
Any use beyond the proper use or other type of use counts as misuse.

WARNING!
Danger due to misuse!
Misuse of the controllers can cause dangerous situa-
tions.
- Do not manipulate the controller software.
- Handle the access codes confidentially.
- Parameters that are protected by a service code may
only be changed by the manufacturer.

Claims of any type for damage due to misuse are excluded.

12 2012-07-13
Controllers AC 1, AC 2, AC 3

Safety

2.2 Responsibility of the owner


Owner The owner is the person who operates the controller for commercial or
business purposes himself or hands it over to a third party for
use/application and who bears the legal product responsibility for the
protection of the user, the personnel or third parties during operation.

Duties of the owner The controller is used in the commercial realm. Therefore, the owner
of the controller is subject to legal occupational safety regulations.
In addition to the safety instructions in these instructions, the valid
safety, accident prevention and environmental protection regulations
for the area of application of the controller must be adhered to.
Here, the following points apply in particular:
 The owner must inform himself about the applicable occupational
safety provisions and also determine in a hazard assessment the
dangers that arise due to the special working conditions in the
controller's area of application. He must implement these in the
form of operating instructions for the operation of the controller.
 During the entire time the controller is used, the owner must check
whether the operating instructions he has created correspond to
the current state of the body of rules and regulations and adapt the
operating instructions if necessary.
 The owner must regulate and specify clearly the responsibilities for
the installation, operation, troubleshooting, maintenance and
cleaning.
 The owner must ensure that all employees who handle the
controller have read and understood these instructions. In addition,
he must train the personnel at regular intervals and inform them
about the dangers.
 The owner must provide personnel with the required protective
equipment and instruct them in binding fashion about how to wear
the required protective equipment.
Furthermore, the owner is responsible for ensuring that the controller
is always in technically-perfect condition. Therefore, the following
points apply:
 The owner must ensure that the maintenance intervals described
in these instructions are adhered to.
 The owner must have all safety equipment checked regularly to
ensure that it is functional and complete.
 The owner must ensure that the appropriate media connections
are provided.
 The owner must ensure that the supply of the required quantity of
cool air is guaranteed.
 The owner must ensure that the required heat extraction is
guaranteed.

2012-07-13 13
Controllers AC 1, AC 2, AC 3

Safety

2.3 Personnel requirements


2.3.1 Qualifications

WARNING!
Danger of injury if personnel are insufficiently quali-
fied!
If insufficiently qualified personnel perform work on the
controller, dangers arise that can cause severe injuries
and significant property damage.
- Therefore, all work must only be carried out by ap-
propriately qualified personnel.
- Unqualified personnel must be kept away from the
danger zones.

These instructions specify the personnel qualifications required for the


different areas of work, listed below:

Trained Person
The trained person has been instructed in an instruction by the owner
about the tasks assigned to him and possible hazards in the case of
improper behaviour.

The workforce must only consist of persons who can be expected to


carry out their work reliably. Persons with impaired reactions due to,
for example, the consumption of drugs, alcohol, or medication are
prohibited.
When selecting personnel, the age-related and occupation-related
regulations governing the usage location must be observed.

14 2012-07-13
Controllers AC 1, AC 2, AC 3

Safety

2.3.2 Unauthorised persons

WARNING!
Risk to life for unauthorised persons due to hazards
in the danger and working zone!
Unauthorised persons who do not meet the requirements
described here will not be familiar with the dangers in the
working zone. Therefore, unauthorised persons face the
risk of serious injury or death.
- Unauthorised persons must be kept away from the
danger and working zone.
- If in doubt, address the persons in question and ask
them to leave the danger and working zone.
- Cease work while unauthorised persons are in the
danger and working zone.

2.3.3 Training

The personnel must be trained regularly by the owner. For better trac-
ing, the execution of the training must be logged ( Appendix A
‘Training log’ on page 109).

2012-07-13 15
Controllers AC 1, AC 2, AC 3

Safety

2.4 Personal protective equipment


Personal protective equipment is used to protect the personnel from
dangers which could affect their safety or health while working.
When performing the various work on and with the controller, the per-
sonnel must wear personal protective equipment. This equipment will
be indicated separately in the individual chapters of these instructions.
This personal protective equipment is described below:
 It is mandatory to put on the personal protective equipment
specified in the different chapters of these instructions before
starting work.
 Always comply with the instructions governing personal protective
equipment posted in the work area.

Description of the personal


protective equipment
Ear protection
Ear protection provides protection against hearing damage.

16 2012-07-13
Controllers AC 1, AC 2, AC 3

Safety

2.5 Basic dangers


The following section describes remaining risks that can arise from the
controller and were determined by a risk assessment.
In order to minimize health hazards and avoid dangerous situations,
follow the safety instructions specified here as well as in the following
chapters of these instructions.

2.5.1 General dangers in the workplace

Noise
WARNING!
Danger of injury from noise!
The noise levels arising in the workplace may result in
serious hearing damage.
- Always wear ear protection while working.
- Do not stay in the danger zone more than necessary.

2.5.2 Dangers due to electric power

Electric current
DANGER!
Danger to life from electric power.
There is an immediate danger to life from electric shock
in the case of contact with live parts. Damage to the in-
sulation or individual components can be fatal.
- Only allow qualified electricians to work on the elec-
trical system.
- In the case of damage to the insulation, immediately
disconnect the power supply and arrange repairs.
- Establish the absence of voltage before starting work
on active parts of electrical systems and equipment
and ensure this remains so for the duration of the
work. Observe the 5 safety rules:
- Disconnect from the power supply.
- Secure against restarting.
- Verify absence of voltage.
- Earth and short-circuit.
- Cover or shield any neighbouring live parts.
- Never bypass or disable fuses. Comply with the cor-
rect current intensity information when replacing fu-
ses.
- Keep moisture away from live parts. This can result in
short circuits.

2012-07-13 17
Controllers AC 1, AC 2, AC 3

Safety

Stored charges
DANGER!
Danger to life from stored charges!
Electric charges may be stored in electrical components;
these charges may be maintained even after the system
has been switched off and disconnected from the power
supply. Contact with these components may result in
serious or fatal injury.
- Before working on the specified components, ensure
that they have been completely disconnected from
the power supply. Allow 10 minutes to elapse in order
to ensure that the internal capacitors have been fully
discharged.

2.6 Safety equipment

WARNING!
Danger to life from nonfunctional safety devices!
If safety devices are not functioning or are disabled, the-
re is a danger of grave injury or death.
- Check that all safety devices are fully functional and
correctly installed before starting work.
- Never disable or bypass safety devices.
- Ensure that all safety devices are always accessible.

2.6.1 Description of the safety equipment installed

The controllers Air Control AC 1, AC 2, and AC 3 are


installed in various models of the Almig screw compres-
sors. These screw compressor have various pieces of
safety equipment that are described below.

18 2012-07-13
Controllers AC 1, AC 2, AC 3

Safety

EMERGENCY-STOP button
Pressing the EMERGENCY-STOP button shuts down the machine by
immediately cutting off the power supply or disconnecting the drives
mechanically. After it has been pressed, the EMERGENCY-STOP
button must be unlocked by turning so that a restart is possible.

WARNING!
Danger to life due to uncontrolled restart!
An uncontrolled restart of the machine may cause seri-
ous injuries including death.
Fig. 1: EMERGENCY-STOP button
- Before switching the machine back on, make sure the
cause of the Emergency Stop has been removed and
all safety devices have been installed and function
properly.
- Do not unlock the EMERGENCY-STOP button until
there is no more danger.

Main switch with emergency off


function
The main switch is also set up as an emergency stop switch. By turn-
ing the main switch to the "0" position, the machine is stopped by
switching off the power immediately and an emergency stop is thus
triggered.

WARNING!
Danger to life from an unauthorised restart!
An uncontrolled restart of the machine may cause seri-
ous injuries including death.
- Before switching the machine back on, make sure the
cause of the emergency stop has been removed and
Fig. 2: Main switch all safety devices have been installed and function
properly.
- Only turn the main switch to the "l" position when the-
re is no more danger.

2012-07-13 19
Controllers AC 1, AC 2, AC 3

Safety

2.7 Securing to prevent restart

WARNING!
Life-threatening danger if restarted without authori-
sation or due to uncontrolled restart!
Uncontrolled or unauthorised switching on of the ma-
chine can cause severe or fatal injuries.
- Prior to restart ensure that all safety devices are
mounted and functional, and that there is no danger
for personnel.
- Always adhere to the procedure described below to
secure against restart.

Securing to prevent restart


1. Switch off the power supply. To do this, turn the main switch to
the "0" position.

2. Secure the main switch with a padlock (Fig. 3).

3. Have a responsible employee keep the key for the padlock.

4. After all work has been performed, make sure that there are no
dangers to people.

5. Ensure that all safety and protective equipment is installed and


functional.

WARNING!
Danger to life from an unauthorised restart!
If the main switch is secured with a padlock, people can
Fig. 3: Securing the main switch
be in the danger zone. These people can be fatally in-
jured by the switching on of the power supply.
- Before removing the padlock and switching the power
supply back on, make sure that there are no dangers
to people.

6. Remove the padlock from the main switch.

If no main switch is installed, proceed as follows.

20 2012-07-13
Controllers AC 1, AC 2, AC 3

Safety

WARNING!
Life-threatening danger if restarted without authori-
sation or due to uncontrolled restart!
Uncontrolled or unauthorised switching on of the ma-
chine can cause severe or fatal injuries.
- Prior to restart ensure that all safety devices are
mounted and functional, and that there is no danger
for personnel.
- Always adhere to the procedure described below to
secure against restart.

Securing to prevent restart 1. Switch off the power supply.

2. Inform responsible people about work in the danger zone.

3. Mark machine with a sign that indicates the work in the danger
zone and forbids switching on. Include the following details on the
sign:
 Switched off on:
 Switched off at:
 Switched off by:
 Note: do not switch on!
 Note: Only switch on after it has been ensured that there are
no dangers to people.

4. After all work has been performed, make sure that there are no
dangers to people.

5. Ensure that all safety and protective equipment is installed and


functional.

WARNING!
Danger to life from an unauthorised restart!
People in the danger zone can be fatally injured by the
unauthorised or uncontrolled switching on of the power
supply.
- Before switching the power supply back on, ensure
that there are no dangers for people.

6. Remove the sign.

2012-07-13 21
Controllers AC 1, AC 2, AC 3

Safety

2.8 Behaviour in case of fire or accidents


Preventive measures  Be prepared for fire and accidents at all times!
 Keep first-aid equipment (first-aid kit, blankets, etc.) and fire
extinguishing devices operational and readily available.
 Make your personnel familiar with accident reporting equipment as
well as first-aid and rescue equipment.
 Keep access paths clear for rescue vehicles.

Steps in case of fire and accidents  Immediately trigger an Emergency Stop using EMERGENCY-
STOP devices.
 Provided your own health is not in danger, rescue all personnel
from the danger area.
 If necessary, initiate first aid measures.
 Alert the fire department and/or emergency medical services.
 In case of fire: provided your own health is not in danger,
extinguish the fire using fire extinguishing equipment and continue
to do so until the fire department arrives.
 Notify the person in charge at the machine's place of installation.
 Clear access paths for rescue vehicles.
 Wave rescue vehicles into position.

22 2012-07-13
Controllers AC 1, AC 2, AC 3

General safety instructions for all controllers

3 General safety instructions for all controllers


3.1 Safety instructions for the operation
Improper operation
WARNING!
Danger of injury due to improper operation!
Improper operation can cause serious injury and signifi-
cant material damage.
- Carry out all operating steps in accordance with the
information and notices in this manual.
- Pay attention to the following points before starting
work:
- Ensure that all covers and safety devices are in-
stalled and work properly.
- Ensure that that no one is in the danger zone.
- Never override or bridge safety features during opera-
tion.

3.2 Operating personnel and personal protective equipment


The following personnel qualifications and personal protective equip-
ment apply for all work on all controllers:

Personnel:  Trained Person

Protective equipment:  Ear protection

2012-07-13 23
Controllers AC 1, AC 2, AC 3

General safety instructions for all controllers

3.3 Shutdown in emergency situations


In dangerous situations component movements must be stopped as
quickly as possible and the power supply must be switched off.

Shutdown in emergency situations In an emergency situation proceed as follows:


1. Immediately trigger an emergency stop through the emergency
stop device.

2. If there is no danger to your own health get people out of the


danger zone.

3. Initiate first-aid measures if necessary.

4. Alert the fire department and/or rescue service.

5. Inform the responsible parties at the implementation site.

6. Switch off the machine and safeguard it from being switched on


again.

7. Keep entry ways clear for rescue vehicles.

8. Give directions to rescue vehicles.

After the rescue measures 9. Depending on the seriousness of the emergency situation, inform
the responsible government agencies.

10. Assign specialized personal to resolve the malfunction.

WARNING!
Life-threatening danger if restarted without authori-
zation or due to uncontrolled restart!
Uncontrolled or unauthorized switching on of the power
supply can cause severe or fatal injuries.
- Prior to restart ensure that all safety devices are
mounted and functional, and that there is no danger
for personnel.

11. Prior to restarting the machine check and ensure that all safety
devices are installed and functioning.

24 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 1 controller

4 Air Control AC 1 controller

4.1 Overview of Air Control AC 1

Fig. 4: Overview of Air Control AC 1

No. Key/icon Description of function


Displays settings and operating
1 Display
parameters.

Serves to switch on the compres-


2 sor. The integrated green LED
indicates the operating state.

Indicates warnings with flashing


3 and faults with red LEDs that light
up.

Serves to switch off the compres-


sor, to acknowledge fault/warning
4
messages and to call up the code
input menu.

Serves to call up additional operat-


5
ing data.

6 Serves to confirm inputs.

7 Serves to scroll and reduce values.

Serves to scroll and increase val-


8
ues.

2012-07-13 25
Controllers AC 1, AC 2, AC 3

Air Control AC 1 controller

4.2 Brief description


The Air Control AC 1 controller serves
 to display operating data/the compressor state
 to switch on/off the compressor/the compressed air generation
 to program the compressor and the compressed air generation.

4.3 Operating modes


Overview Four operating modes can be set using the controller.

Operating mode Description


Automatic operation After reaching the switch-off pressure,
the system switches to idle for the
duration of the idle time (run-on). After
the run-on time has elapsed, the mo-
tor switches off. The compressor can
start up by itself at any time if the ma-
chine drops below the switch-on pres-
sure.

Load/idle operation The compressor switches between


"Load" and "Idle" operation; that is,
there is an unlimited run-on.

Optional automatic After reaching the switch-off pressure,


the compressor switches to idle. After
10 and 40 seconds, the respective
network pressure is measured. If the
pressure drop determined this way is
above the threshold "Max. pressure
drop", the compressor remains in idle
for the duration of the run-on time. If
the value determined is below the
threshold "Max. pressure drop", the
compressor switches off after the
shutdown time has elapsed.

Basic load switching The switch on/off pressure set is not


mode (BLS mode)) taken into account by the controller.
The compressor is controlled by a
superior controller.

Safety pressure The safety pressure is the sum of the set maximum pressure +0.8 bar.
If the pressure exceeds the value of the safety pressure, the com-
pressor is switched off with a fault message. If the maximum pressure
is exceeded by 0.5 bar, a warning appears on the display.

26 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 1 controller

4.4 Overview of display


The display shows all operation-relevant information such as the pa-
rameters set.
1 Display [Aktueller Netzdruck (Current network pressure)]: Displays
the current network pressure.
2 Display [Aktuelle Verdichtertemperatur (Current compressor
temperature)]: Displays the current compressor temperature.
3 [Betriebsart (Operating mode)] display: Displays the current
operating mode.

By pressing the key, the current coolant liquid tem-


perature can also be shown on the [Current compressor
temperature] display.

Fig. 5: Overview of basic display

4.4.1 Other display indicators

The following symbols can also appear on the display:

Sym- Description
bol
Motor is running.

Compressor is compressing air.

Fault present.

Automatic restart after power failure is activated.

Flashing: compressed air generation on/off via remote


switch.
Static: compressed air generation is controlled by supe-
rior controller.

Warning/maintenance message present.

2012-07-13 27
Controllers AC 1, AC 2, AC 3

Air Control AC 1 controller

4.4.2 Operating mode display

The following text/symbols can appear on the [Betriebsart (Operating


mode)] display:

Symbol Description
Operating mode automatic/optional automatic ac-
tive.

If the compressor is in load/idle operation, nothing is


shown on the [Operating mode] display.

4.5 Switching the compressor on/off


Switching the compressor on 1. Press .

 The integrated green LED lights up.

Switching the compressor off 1. Press .

 The green LED in the key goes out.

28 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 1 controller

4.6 Calling up information


It is possible to display various information about operating states and
parameter values on the display. In order to switch between the infor-
mation and the parameter displays, it is only necessary to press the
key. The Information menu with parameter number and the pa-
rameter value then appears on the display.
1 Parameter number
2 Parameter value
1. Press .

 The next parameter value is shown on the display.

In the information menu, the parameter [Einschaltdruck


(Switch-on pressure)] is always shown as the first value.

After approx. 5 seconds without pressing the key, the


Fig. 6: Information menu display switches back to the basic display.

Key Parameter displayed Parameter number Unit of the pa-


rameter value
Switch-on pressure [1] [bar, MPa, psi]

Switch-off pressure [2] [bar, MPa, psi]

Safety pressure [3] [bar, MPa, psi]

Minimum pressure monitoring [4] [bar, MPa, psi]


in BLS operation

Minimum compressor tempe- [5] [°C, °F, Kelvin]


rature

Maximum compressor tempe- [6] [°C, °F, Kelvin]


rature

Hours of operation [7] [h]

Load hours [8] [h]

Remaining time intake filter [9] [kh]

Remaining time coolant liquid [10] [kh]


and coolant liquid filter

2012-07-13 29
Controllers AC 1, AC 2, AC 3

Air Control AC 1 controller

Key Parameter displayed Parameter number Unit of the pa-


rameter value
Remaining time fine [11] [kh]
precipitator

Remaining time motor [12] [kh]


lubrication

Remaining time compressor [13] [kh]


maintenance

4.7 Setting parameters via code input menu


The parameters for all basic settings of the compressor can be chan-
ged with code input insofar as these changes do not influence the
operational stability. However, this is only possible when the com-
pressed air generation is switched off.

4.7.1 Calling up the code input menu

1. Press and hold for three seconds.

 The code input menu appears on the display.

2. Press .

 A 1 appears on the display.

3. Press .

In order to exit the code input menu again, press .

30 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 1 controller

4.7.2 Overview of code input menu

1 Currently-set code (flashing, can be changed with the


keys)

Fig. 7: Code input menu

4.7.3 Inputting a code

Prerequisite: the code input menu has been called up.

1. Set the desired code with the keys.

2. To confirm the selected code, press .

 The submenu for the selected code appears on the display.

For some codes, several parameters can be input one


after another. By pressing the key, the next parame-
ter is selected automatically in such cases.

2012-07-13 31
Controllers AC 1, AC 2, AC 3

Air Control AC 1 controller

4.7.4 Overview of submenus

The submenus for setting the parameters are similar in their structure.
Generally, it is possible to distinguish two types:

Submenu for selection parameters The submenu for selection parameters appears for all codes for which
(operating mode example) there is an opportunity to select between different, specified setting
values. For the setting of the operating mode, e.g., it is possible to
select from among three specified values/operating modes.
1 Current selection (can be changed with the keys)
2 [Untermenüpunkt (Submenu element)] display

Fig. 8: Selection parameter submenu

Submenu for value parameters The submenu for value parameters appears for all codes through
(switch-on pressure example) which a parameter can be changed without selection possibility. For
the switch-on pressure, e.g., only the value of the switch-on pressure
can be changed.
1 Current parameter value (can be changed with the keys)
2 [Untermenüpunkt (Submenu element)] display

Fig. 9: Value parameters submenu

32 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 1 controller

4.7.5 Select operating mode: Code 0002

By entering the code 0002, the operating mode can be selected.

1. Press and hold for three seconds.

 The code input menu appears on the display.

2. Press .

 A 1 appears on the display.

3. Press .

4. Set the code 0002 with the keys.

5. To confirm the selected code, press .

6. Press .

 The submenu for setting the operating mode appears on the


display.

7.
There are three values from which to choose:
- 0: Automatic operation
- 1: Load/idle operation
- 2: Optional automatic

Set the desired value with the keys.

8. To confirm the selected value, press .

 The set value is saved and the code input menu appears on
the display again.

9. Press again to go back to the basic display.

2012-07-13 33
Controllers AC 1, AC 2, AC 3

Air Control AC 1 controller

Value Operating Description


mode
0 Automatic After reaching the switch-off pres-
operation sure, the compressor switches to
idle for the duration of the idle time
(run-on). After the idle time has
elapsed, the compressor then swit-
ches off, but it remains ready for
operation. If the switch-on pressure
is reached, the compressor starts
up again automatically.

1 Load/idle The compressor switches between


operation "Load" and "Idle" operation; that is,
there is an unlimited run-on.

2 Optional The "Automatic" symbol and an


automatic additional point are shown on the
display in front of the temperature
value. Here it is possible to influ-
ence how frequently the motors
stops. To do this, after the confir-
mation, the parameters "maximum
pressure drop" (input range 0.0 to
9.9 bar) and "maximum operating
cycle" (input range 1 to 55 operat-
ing cycles/hour) are queried.

Maximum pressure drop If the system switches from load operation to idle, the Air Control 1
saves the current network pressure after 10 and 40 seconds. If the
pressure drop determined this way is above the "maximum pressure
drop", the motor switches off after the idle time has elapsed; otherwise
after the shutdown time.

Maximum operating cycles The motor is not switched off after the idle time (run-on) has elapsed if
the number of switch-on processes of the compressor exceeds the
number of the "maximum operating cycles".

34 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 1 controller

4.7.6 Switch automatic restart on/off: Code 0003

By inputting the code 0003, the automatic restart can be switched


on/off after a power failure.

1. Press and hold for three seconds.

 The code input menu appears on the display.

2. Press .

 A 1 appears on the display.

3. Press .

4. Set the code 0003 with the keys.

5. To confirm the selected code, press .

 The submenu for switching the automatic restart on/off ap-


pears on the display.

6.
There are two values from which to choose:
- 0: Automatic restart OFF
- 1: Automatic restart ON

Set the desired value with the keys.

7. To confirm the selected value, press .

 The set value is saved and the code input menu appears on
the display again.

8. Press again to go back to the basic display.

2012-07-13 35
Controllers AC 1, AC 2, AC 3

Air Control AC 1 controller

Value Setting Description


0 Automatic If the automatic restart after power
restart OFF failure is switched off, then after a
power failure, the fault "no AC" is
displayed. This fault must be ac-
knowledged manually by pressing
the key. Otherwise, the com-
pressor will not restart.

1 Automatic If the automatic restart after power


restart ON failure is switched on, the time set in
the "shutdown time" parameter must
elapse. If the compressor was oper-
ating before the power failure, then
after this time has elapsed, it will
start up again. Otherwise, the com-
pressor will then switch to STOP
mode.

4.7.7 Set on-site operation/remote operation: Code 0008

By inputting the code 0008, it is possible to switch between on-site


operation and remote operation.

1. Press and hold for three seconds.

 The code input menu appears on the display.

2. Press .

 A 1 appears on the display.

3. Press .

4. Set the code 0008 with the keys.

5. To confirm the selected code, press .

 The on-site operation/remote control submenu appears on the


display.

6.
There are three values from which to choose:
- 0: On-site operation
- 1: Remote control
- 2: BLS-OK

Set the desired value with the keys.

36 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 1 controller

7. To confirm the selected value, press .

 The set value is saved and the code input menu appears on
the display again.

8. Press again to go back to the basic display.

Value Designa- Description


tion
0 On-site The compressed air generation can only
operation be switched off on the control con-
sole/display of the Air Control 1.

1 Remote The compressed air generation can only


control be switched on via a positive edge (24
VDC) on terminal 23 and switched off via
low level (0 V) on terminal 23 or via the
key. This functionality is identified by
the flashing text on the display
of the Air Control 1. If the key is
pressed on the system on-site, the sys-
tem switches off after 120 seconds and
for safety reasons, it can only be started
via remote control after the key has
been pressed (acknowledgement) on-
site. This also applies for a start via
PLANT CONTROL V/T.

2 BLS-OK The input on terminal 23 serves to report


the operational readiness of an external
controller. Only with an existing high level
(24 VDC) can the external controller
switch between load operation and idle.
During existing low level, the BLS opera-
tion is switched off automatically and the
internal pressure sensor is used.

2012-07-13 37
Controllers AC 1, AC 2, AC 3

Air Control AC 1 controller

4.7.8 Set switch on/off pressure: Code 0011

By inputting the code 0011, it is possible to set the switch-on and


switch-off pressure. The switch-on pressure specifies the pressure at
which the switched-on compressor will begin automatically with the
compression. The switch-off pressure specifies the pressure at which
the compressor will be switched off automatically. However, both func-
tions are only active in automatic operation.

1. Press and hold for three seconds.


 The code input menu appears on the display.
2. Press .
 A 1 appears on the display.
3. Press .
4. Set the code 0011 with the keys.
5. To confirm the selected code, press .
6. Press .
 The submenu for setting the switch-on pressure appears on
the display.
7.
The adjustment range for the switch-on pressure is,
with switch-off pressure set at the factory, between
3.5 and 7.9 bar. The upper limit for the switch-on
pressure is 0.1 bar less than the switch-off pressure.

Set the desired switch-on pressure with the keys.


8. To confirm the setting, press the key.
 The set value was saved and the submenu for setting the
switch-off pressure appears on the display.
9.
The adjustment range for the switch-off pressure is,
with switch-on pressure set at the factory, between
7.1 and 10 bar. The upper limit for the switch-off
pressure is equal to the maximum pressure. The
lower limit for the switch-off pressure is 0.1 bar hig-
her than the switch-on pressure.

Set the desired switch-off pressure with the keys.


10. To confirm the setting, press the key.
 The set value is saved and the code input menu appears on
the display again.
11. Press again to go back to the basic display.

38 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 1 controller

4.7.9 Switch Basic load switching mode on/off: Code 0018

By inputting the code 0018, the Basic load switching mode can be
switched on/off.

1. Press and hold for three seconds.

 The code input menu appears on the display.

2. Press .

 A 1 appears on the display.

3. Press .

4. Set the code 0018 with the keys.

5. To confirm the selected code, press .

 The Basic load switching mode submenu appears on the dis-


play.

6.
There are two values from which to choose:
- 0: Basic load switching mode is switched off
- 1: Basic load switching mode is switched on

Set the desired value with the keys.

7. To confirm the selected value, press .

 The set value is saved and the code input menu appears on
the display again.

8. Press again to go back to the basic display.

2012-07-13 39
Controllers AC 1, AC 2, AC 3

Air Control AC 1 controller

4.7.10 Switch the pressure unit: Code 0090


By entering the code 0090, the pressure unit can be switched.

1. Press and hold for three seconds.

 The code input menu appears on the display.

2. Press .

 A 1 appears on the display.

3. Press .

4. Set the code 0090 with the keys.

5. To confirm the selected code, press .

 The submenu for setting the pressure unit appears on the


display.

6.
There are three values from which to choose:
- 0: bar
- 1: MPa
- 2: psi (pounds per square inch)

Set the desired value with the keys.

7. To confirm the selected value, press .

 The set value is saved and the code input menu appears on
the display again.

8. Press again to go back to the basic display.

Value Pressure Description


unit
0 bar All pressure displays will be in bar.

1 MPa All pressure displays will be in Mega-


pascals.

2 psi All pressure displays will be in psi


(pounds per square inch).

40 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 1 controller

4.7.11 Switch the temperature unit: Code 0095


By entering the code 0095, the temperature unit can be switched.

1. Press and hold for three seconds.

 The code input menu appears on the display.

2. Press .

 A 1 appears on the display.

3. Press .

4. Set the code 0095 with the keys.

5. To confirm the selected code, press .

 The submenu for setting the temperature unit appears on the


display.

6.
There are three values from which to choose:
- 0: °C
- 1: °F
- 2: K

Set the desired value with the keys.

7. To confirm the selected value, press .

 The set value is saved and the code input menu appears on
the display again.

8. Press again to go back to the basic display.

2012-07-13 41
Controllers AC 1, AC 2, AC 3

Air Control AC 1 controller

Value Pressure Description


unit
0 Degrees All temperature displays will be in °C.
Celsius

1 Degrees All temperature displays will be in °F.


Fahrenheit

2 Kelvin All temperature displays will be in Kel-


vin.

4.7.12 Display the software version: Code 9999


By inputting the code 9999, the software version can be displayed.

1. Press and hold for three seconds.

 The code input menu appears on the display.

2. Press .

 A 1 appears on the display.

3. Press .

4. Set the code 9999 with the keys.

5. To confirm the selected code, press .

 The software version appears on the display.

6. Press the key again to go back to the code input menu.

42 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 1 controller

4.8 Fault and warning messages


4.8.1 Fault message

When a fault occurs, the compressor switches off and it


can only be switched on again after the cause of the fault
has been eliminated. Subsequently, the fault message
must be acknowledged with the key.

1 Fault abbreviation
2 Fault symbol
3 Fault number
If a fault occurs during operation, a fault message (Fig. 10) and the
fault symbol appear on the display. If a fault occurs, the compres-
sor switches off.

Fig. 10: Fault message

2012-07-13 43
Controllers AC 1, AC 2, AC 3

Air Control AC 1 controller

4.8.1.1 Fault table

Fault Fault Cause of the fault Fault remedy Personnel


no. abbreviation
1 [Par.] Parameter incorrect Check and change Trained per-
pressure set points son

2 [EprOm] Eprom faulty Replace controller Qualified elec-


trician

3 [Lo AC] Low voltage Check power supply Qualified elec-


trician

4 [no AC] Power failure Check power supply Qualified elec-


trician

5 [DEFEC] Comparison parameter in- Set comparison pa- Manufacturer


correct rameters

6 [Emerg] Emergency stop pressed Eliminate cause of Trained per-


emergency stop son

7 [rotot] Direction of rotation of the Set correct direction Qualified elec-


motor incorrect of rotation of the mo- trician
tor

8 [Mott] Motor temperature too high Let motor cool off Trained per-
son

9 [hiCur] Ventilator flow too high Check ventilator flow Qualified elec-
trician

10 [hi P] Network pressure too high Reduce network Trained per-


pressure son

11 [Dif P] Differential pressure fine Set differential pres- Manufacturer


precipitator too high sure fine precipitator

12 [SE t] Temperature sensor faulty Check cabling of Qualified elec-


temperature sen- trician
sor/replace tempera-
ture sensor

13 [SE t2] Coolant liquid temperature Check cabling of Qualified elec-


sensor faulty coolant liquid tem- trician
perature sen-
sor/Replace coolant
liquid temperature
sensor

44 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 1 controller

Fault Fault Cause of the fault Fault remedy Personnel


no. abbreviation
14 [SE P] Pressure sensor faulty Check cabling for Qualified elec-
pressure sen- trician
sor/replace pressure
sensor

15 [hi t] Compressor temperature Let compressor cool Trained per-


too high off son

16 [hi P] Network pressure too high Reduce network Trained per-


pressure son

If a fault not listed in the fault table occurs, contact the


manufacturer immediately.

4.8.2 Warning/maintenance messages

1 Warning symbol
2 Warning number
If an unexpected change to parameters occurs during operation, a
warning message and the warning symbol appear on the display.
However, in comparison to the fault message, the compressor does
not switch off.

Fig. 11: Warning/maintenance message

2012-07-13 45
Controllers AC 1, AC 2, AC 3

Air Control AC 1 controller

4.8.2.1 Warning table

War- Cause of warning Warning re- Personnel


ning medy/warning
no. cause
2 Compressor tempera- Let compres- Trained
ture increased sor cool off person

3 Network pressure Reduce net- Trained


increased work pressure person

4 Compressor tempera- Warm up Trained


ture too low compressor person

7 Lower pressure thres- Check BLS Qualified


hold reached network personnel

11 Intake filter mainte- Change intake Qualified


nance due filter personnel

12 Maintenance coolant Change coo- Qualified


liquid/coolant liquid lant liquid filter personnel
filter due

13 Maintenance of fine Maintain fine Qualified


precipitator due precipitator personnel

14 Maintenance motor Lubricate mo- Qualified


lubrication due tor personnel

15 Maintenance of com- Maintain com- Qualified


pressor due pressor personnel

16 Warning EA module Check EA Qualified


module personnel

If a fault not listed in the warning table occurs, contact


the manufacturer immediately.

46 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 1 controller

4.8.3 Acknowledging fault and warning messages

NOTICE!
Danger of property damage due to improperly per-
formed fault remedy/maintenance work!
Acknowledgement of fault and warning messages with-
out properly-executed fault remedy/maintenance work
can cause severe damage to the compressor on through
to total failure.
- Only have fault remedy/maintenance work performed
by qualified personnel.
- Only acknowledge fault and warning messages if fault
remedy/maintenance work has been performed prop-
erly.

Acknowledging a fault message 1. Press .

 The fault message on the display goes out.

Acknowledging a warning message 1. Press .

 The fault message on the display goes out.

2012-07-13 47
Controllers AC 1, AC 2, AC 3

Air Control AC 1 controller

4.9 Setting the display contrast


The display contrast of the controller was select so that optimal legibil-
ity is guaranteed under nearly all conditions of use. If under certain
circumstances (e.g. unfavourable lighting, direct solar radiation) it is
necessary to adjust the contrast, carry out the following steps:

DANGER!
Danger to life from electric power!
Touching voltage-conducting components can cause
deadly electric shock.
- Before all work for setting the display contrast, de-
energise the compressor on the main switch and se-
cure it against being switched on again.

1. De-energise compressor on the main switch.

2. Open the switch cabinet/switch box of the compressor.

3. Insert a small screwdriver in the opening (Fig. 12/arrow) on the


back of the controller.

4. Turn the screwdriver clockwise in order to increase the display


contrast. Turn the screwdriver anti-clockwise in order to decrease
the display contrast.

5. Pull the small screwdriver out of the opening on the back of the
Fig. 12: Display opening controller.

6. Close the switch cabinet/switch box of the compressor again.

48 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 2 controller

5 Air Control AC 2 controller

5.1 Overview of Air Control AC 2

Fig. 13: Overview of Air Control AC 2

No. Key/icon Description of function


Displays settings and operating
1 Display
parameters.

Serves to switch on the compres-


2
sor.

Indicates warnings with flashing


3 and faults with red LEDs that light
up.

Serves to switch off the compres-


sor, to acknowledge fault/warning
4
messages and to call up the code
input menu.

5 Serves to confirm inputs.

6 Serves to scroll and reduce values.

Serves to scroll and increase val-


7
ues.

2012-07-13 49
Controllers AC 1, AC 2, AC 3

Air Control AC 2 controller

5.2 Brief description


The Air Control AC 2 controller serves
 to display operating data/the compressor state
 to switch on/off the compressor/the compressed air generation
 to program the compressor and the compressed air generation.

5.3 Operating modes


Overview Four operating modes can be set using the controller.

Operating mode Description


Automatic operation After reaching the switch-off pressure,
the system switches to idle for the
duration of the idle time (run-on). After
the run-on time has elapsed, the mo-
tor switches off. The compressor can
start up by itself at any time if the ma-
chine drops below the switch-on pres-
sure.

Load/idle operation The compressor switches between


"Load" and "Idle" operation; that is,
there is an unlimited run-on.

Optional automatic After reaching the switch-off pressure,


the compressor switches to idle. After
10 and 40 seconds, the respective
network pressure is measured. If the
pressure drop determined this way is
above the threshold "Max. pressure
drop", the compressor remains in idle
for the duration of the run-on time. If
the value determined is below the
threshold "Max. pressure drop", the
compressor switches off after the
shutdown time has elapsed.

Basic load switching The switch on/off pressure set is not


mode (BLS mode)) taken into account by the controller.
The compressor is controlled by a
superior controller.

Safety pressure The safety pressure is the sum of the set maximum pressure +0.8 bar.
If the pressure exceeds the value of the safety pressure, the com-
pressor is switched off with a fault message. If the maximum pressure
is exceeded by 0.5 bar, a warning appears on the display.

50 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 2 controller

5.4 Overview of display


The display shows all operation-relevant information such as the pa-
rameters set.
1 Display [Aktuelle Verdichtertemperatur (Current compressor
temperature)]: Displays the current compressor temperature.
2 Operating data display area: Displays current operating data.
3 [Betriebsart (Operating mode)] display: Displays the current
operating mode.
4 Display [Aktueller Netzdruck (Current network pressure)]: Displays
the current network pressure.

Fig. 14: Overview of basic display

5.4.1 Operating data display area

The following symbols can appear in the operating data display area:

Sym- Description
bol
Motor is running.

Compressor is compressing air.

Ventilator is activated.

Fault present.

Automatic restart after power failure is activated.

2012-07-13 51
Controllers AC 1, AC 2, AC 3

Air Control AC 2 controller

Sym- Description
bol
Flashing: compressed air generation on/off via remote
switch.
Static: compressed air generation is controlled by supe-
rior controller.

Warning/maintenance message present.

Additional heating activated.

Communication is taking place via the 2nd interface.

5.4.2 Operating mode display

The following text/symbols can appear on the [Betriebsart (Operating


mode)] display:

Symbol Description
Automatic operating mode active.

Automatic optional operating mode active.

Basic load switching mode active.

If the compressor is in load/idle operation, nothing is


shown on the [Betriebsart (Operating mode)] display.

52 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 2 controller

5.5 Switching the compressor on/off


Switching the compressor on 1. Press .

Switching the compressor off 1. Press .

During the switch-off process, the compressor initially


switches to "Idle" (motor running, however the compres-
sor is not compressing any air; a flashing dot appears on
the display) for the duration of the shutdown time (45 s).
Only then does the compressor switch off (the motor
stops).

5.6 Calling up information


It is possible to display various information about operating states and
parameter values on the display. In order to switch between the infor-
mation and the parameter displays, it is only necessary to press the
key. The Information menu with parameter number and the pa-
rameter value then appears on the display.
1 Parameter value
2 Parameter number
1. Press .

 The next parameter value is shown on the display.

In the information menu, the parameter [Switch-on pres-


sure] is always shown as the first value.

Fig. 15: Information menu


After approx. 5 seconds without pressing the key, the
display switches back to the basic display.

2012-07-13 53
Controllers AC 1, AC 2, AC 3

Air Control AC 2 controller

Key Parameter displayed Parameter number Unit of the pa-


rameter value
Switch-on pressure [1] [bar, MPa, psi]

Switch-off pressure [2] [bar, MPa, psi]

Safety pressure [3] [bar, MPa, psi]

Minimum pressure monitoring [4] [bar, MPa, psi]


in BLS operation

Minimum compressor tempe- [5] [°C, °F, Kelvin]


rature

Maximum compressor tempe- [6] [°C, °F, Kelvin]


rature

Hours of operation [7] [h]

Load hours [8] [h]

Remaining time intake filter [9] [h]

Remaining time coolant liquid [10] [h]


and coolant liquid filter

Remaining time fine precipita- [11] [h]


tor

Remaining time motor lubrica- [12] [h]


tion

Remaining time compressor [13] [h]


maintenance

54 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 2 controller

5.7 Setting parameters via code input menu


The parameters for all basic settings of the compressor can be chan-
ged with code input insofar as these changes do not influence the
operational stability. However, this is only possible when the com-
pressed air generation is switched off.

5.7.1 Calling up the code input menu

1. Press and hold for three seconds.

 The code input menu appears on the display.

2. Press .

 A 1 appears on the display.

3. Press .

In order to exit the code input menu again, press .

5.7.2 Overview of code input menu

1 Currently-set code (can be changed with the keys)

Fig. 16: Code input menu

2012-07-13 55
Controllers AC 1, AC 2, AC 3

Air Control AC 2 controller

5.7.3 Inputting a code

Prerequisite: the code input menu has been called up.

1. Set the desired code with the keys.

2. To confirm the selected code, press .

 The submenu for the selected code appears on the display.

For some codes, several parameters can be input one


after another. By pressing the key, the next parame-
ter is selected automatically in such cases.

5.7.4 Overview of submenus

The submenus for setting the parameters are similar in their structure.
Generally, it is possible to distinguish two types:

Submenu for selection parameters The submenu for selection parameters appears for all codes for which
(operating mode example) there is an opportunity to select between different, specified setting
values. For the setting of the operating mode, e.g., it is possible to
select from among three specified values/operating modes.
1 Current code
2 Current selection (can be changed with the keys)
3 [Untermenüpunkt (Submenu element)] display

Fig. 17: Selection parameter submenu

56 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 2 controller

Submenu for value parameters The submenu for value parameters appears for all codes through
(switch-on pressure example) which a parameter can be changed without selection possibility. For
the switch-on pressure, e.g., only the value of the switch-on pressure
can be changed.
1 Current parameter value (can be changed with the keys)
2 [Untermenüpunkt (Submenu element)] display

Fig. 18: Value parameters submenu

5.7.5 Select operating mode: Code 0002

By entering the code 0002, the operating mode can be selected.

1. Press and hold for three seconds.

 The code input menu appears on the display.

2. Set the code 0002 with the keys.

3. To confirm the selected code, press .

 The submenu for setting the operating mode appears on the


display.

4.
There are three values from which to choose:
- 0: Automatic operation
- 1: Load/idle operation
- 2: Optional automatic

Set the desired value with the keys.

5. To confirm the selected value, press .

 The set value is saved and the code input menu appears on
the display again.

6. Press again to go back to the basic display.

2012-07-13 57
Controllers AC 1, AC 2, AC 3

Air Control AC 2 controller

Value Operating Description


mode
0 Automatic ope- After reaching the switch-off pres-
ration sure, the compressor switches to
idle for the duration of the idle time
(run-on). After the idle time has
elapsed, the compressor then swit-
ches off, but it remains ready for
operation. If the switch-on pressure
is reached, the compressor starts
up again automatically.

1 Load/idle opera- The compressor switches between


tion "Load" and "Idle" operation; that is,
there is an unlimited run-on.

2 Optional auto- The "Automatic" symbol and two


matic additional slashes are shown on the
display below the temperature va-
lue. Here it is possible to influence
how frequently the motors stops. To
do this, after the confirmation, the
parameters "maximum pressure
drop" (input range 0.0 to 9.9 bar)
and "maximum operating cycle"
(input range 1 to 55 operating cy-
cles/hour) are queried.

Maximum pressure drop If the system switches from load operation to idle, the Air Control 2
saves the current network pressure after 10 and 40 seconds. If the
pressure drop determined this way is above the "maximum pressure
drop", the motor switches off after the idle time has elapsed; otherwise
after the shutdown time.

Maximum operating cycles The motor is not switched off after the idle time (run-on) has elapsed if
the number of switch-on processes of the compressor exceeds the
number of the "maximum operating cycles".

58 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 2 controller

5.7.6 Switch automatic restart on/off: Code 0003

By inputting the code 0003, the automatic restart can be switched


on/off after a power failure.

1. Press and hold for three seconds.

 The code input menu appears on the display.

2. Set the code 0003 with the keys.

3. To confirm the selected code, press .

 The submenu for switching the automatic restart on/off ap-


pears on the display.

4.
There are two values from which to choose:
- 0: Automatic restart OFF
- 1: Automatic restart ON

Set the desired value with the keys.

5. To confirm the selected value, press .

 The set value is saved and the code input menu appears on
the display again.

6. Press again to go back to the basic display.

2012-07-13 59
Controllers AC 1, AC 2, AC 3

Air Control AC 2 controller

Value Setting Description


0 Automatic If the automatic restart after power
restart OFF failure is switched off, then after a
power failure, the fault "no AC" is
displayed. This fault must be ac-
knowledged manually by pressing
the key. Otherwise, the com-
pressor will not restart.

1 Automatic If the automatic restart after power


restart ON failure is switched on, the time set in
the "shutdown time" parameter must
elapse. If the compressor was oper-
ating before the power failure, then
after this time has elapsed, it will
start up again. Otherwise, the com-
pressor will then switch to STOP
mode.

5.7.7 Set on-site operation/remote operation: Code 0008

By inputting the code 0008, it is possible to switch between on-site


operation and remote operation.

1. Press and hold for three seconds.

 The code input menu appears on the display.

2. Set the code 0008 with the keys.

3. To confirm the selected code, press .

 The on-site operation/remote control submenu appears on the


display.

4.
There are two values from which to choose:
- 0: On-site operation
- 1: Remote control

Set the desired value with the keys.

5. To confirm the selected value, press .

 The set value is saved and the code input menu appears on
the display again.

6. Press again to go back to the basic display.

60 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 2 controller

5.7.8 Setting the switch-on/switch-off pressure and minimum pressure/BLS: Code 0011

By inputting the code 0011, it is possible to set the switch-on and


switch-off pressure. The switch-on pressure specifies the pressure at
which the switched-on compressor will begin automatically with the
compression. The switch-off pressure specifies the pressure at which
the compressor will be switched off automatically. However, both func-
tions are only active in automatic operation.

1. Press and hold for three seconds.

 The code input menu appears on the display.

2. Set the code 0011 with the keys.

3. To confirm the selected code, press .

 The submenu for setting the switch-on pressure appears on


the display.

4.
The adjustment range for the switch-on pressure is,
with switch-off pressure set at the factory, between
3.5 and 7.9 bar. The upper limit for the switch-on
pressure is 0.1 bar less than the switch-off pressure.

Set the desired switch-on pressure with the keys.

5. To confirm the setting, press the key.

 The set value was saved and the submenu for setting the
switch-off pressure appears on the display.

6.
The adjustment range for the switch-off pressure is,
with switch-on pressure set at the factory, between
7.1 and 10 bar. The upper limit for the switch-off
pressure is equal to the maximum pressure. The
lower limit for the switch-off pressure is 0.1 bar hig-
her than the switch-on pressure.

Set the desired switch-off pressure with the keys.

7. To confirm the setting, press the key.

 The set value was saved and the submenu for setting the
minimum pressure/BLS appears on the display.

8. Set the desired minimum pressure/BLS with the keys.

9. To confirm the setting, press the key.

 The set value is saved.

10. Press the key again to go back to the code input menu.

2012-07-13 61
Controllers AC 1, AC 2, AC 3

Air Control AC 2 controller

5.7.9 Switch Basic load switching mode on/off: Code 0018

By inputting the code 0018, the Basic load switching mode can be
switched on/off.

1. Press and hold for three seconds.

 The code input menu appears on the display.

2. Set the code 0018 with the keys.

3. To confirm the selected code, press .

 The Basic load switching mode submenu appears on the dis-


play.

4.
There are two values from which to choose:
- 0: Basic load switching mode is switched off
- 1: Basic load switching mode is switched on

Set the desired value with the keys.

5. To confirm the selected value, press .

 The set value is saved and the code input menu appears on
the display again.

6. Press again to go back to the basic display.

62 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 2 controller

5.7.10 Switch the pressure unit: Code 0090


By entering the code 0090, the pressure unit can be switched.

1. Press and hold for three seconds.

 The code input menu appears on the display.

2. Set the code 0090 with the keys.

3. To confirm the selected code, press .

 The submenu for setting the pressure unit appears on the


display.

4.
There are three values from which to choose:
- 0: bar
- 1: MPa
- 2: psi (pounds per square inch)

Set the desired value with the keys.

5. To confirm the selected value, press .

 The set value is saved and the code input menu appears on
the display again.

6. Press again to go back to the basic display.

Value Pressure Description


unit
0 bar All pressure displays will be in bar.

1 MPa All pressure displays will be in Mega-


pascals.

2 psi All pressure displays will be in psi


(pounds per square inch).

2012-07-13 63
Controllers AC 1, AC 2, AC 3

Air Control AC 2 controller

5.7.11 Switch the temperature unit: Code 0095


By entering the code 0095, the temperature unit can be switched.

1. Press and hold for three seconds.

 The code input menu appears on the display.

2. Set the code 0095 with the keys.

3. To confirm the selected code, press .

 The submenu for setting the temperature unit appears on the


display.

4.
There are three values from which to choose:
- 0: °C
- 1: °F
- 2: K

Set the desired value with the keys.

5. To confirm the selected value, press .

 The set value is saved and the code input menu appears on
the display again.

6. Press again to go back to the basic display.

Value Pressure Description


unit
0 Degrees All temperature displays will be in °C.
Celsius

1 Degrees All temperature displays will be in °F.


Fahrenheit

2 Kelvin All temperature displays will be in Kel-


vin.

64 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 2 controller

5.7.12 Display the software version: Code 9999


By inputting the code 9999, the software version can be displayed.

1. Press and hold for three seconds.

 The code input menu appears on the display.

2. Set the code 9999 with the keys.

3. To confirm the selected code, press .

 The software version appears on the display.

4. Press again to go back to the basic display.

5.8 Fault and warning messages


5.8.1 Fault message

When a fault occurs, the compressor switches off and it


can only be switched on again after the cause of the fault
has been eliminated. Subsequently, the fault message
must be acknowledged with the key.

1 Fault abbreviation
2 Fault number
3 Fault symbol
If a fault occurs during operation, a fault message (Fig. 19) and the
fault symbol appear on the display. If a fault occurs, the compres-
sor switches off.

Fig. 19: Fault message

2012-07-13 65
Controllers AC 1, AC 2, AC 3

Air Control AC 2 controller

5.8.1.1 Fault table

Fault Fault abbreviati- Cause of the fault Fault remedy Personnel


no. on
1 [Par.] Parameter incorrect Check and change Trained
pressure set points person

2 [EprOm] Eprom faulty Replace controller Qualified


electrician

3 [Lo AC] Low voltage Check power supply Qualified


electrician

4 [no AC] Power failure Check power supply Qualified


electrician

5 [DEFEC] Comparison parameter in- Set comparison pa- Manufacturer


correct rameters

6 [Mot t] Motor temperature too high Let motor cool off Trained
person

7 [hiCur] Ventilator flow too high Check ventilator flow Qualified


electrician

8 [LoCur] Ventilator flow too low Check ventilator flow Qualified


electrician

9 [SE t] Temperature sensor faulty Check cabling of Qualified


temperature sen- electrician
sor/replace tempera-
ture sensor

10 [SE P] Pressure sensor faulty Check cabling for Qualified


pressure sen- electrician
sor/replace pressure
sensor

11 [hi t] Compressor temperature Let compressor cool Trained


too high off person

12 [hi P] Network pressure too high Reduce network Trained


pressure person

13 [Fu] Frequency converter fault Check frequency Qualified


converter electrician

14 [dryER] Dryer fault Check dryer Qualified


electrician

15 [SE t2] Temperature sensor heating Change temperature Qualified


faulty sensor heating electrician

66 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 2 controller

If a fault not listed in the fault table occurs, contact the


manufacturer immediately.

5.8.2 Warning/maintenance messages

1 Waning abbreviation
2 Warning number
3 Warning symbol
If an unexpected change to parameters occurs during operation, a
warning message and the warning symbol appear on the display.
However, in comparison to the fault message, the compressor does
not switch off.

Fig. 20: Warning/maintenance message

2012-07-13 67
Controllers AC 1, AC 2, AC 3

Air Control AC 2 controller

5.8.2.1 Warning table

Warning Waning abbre- Cause of warning Warning reme- Personnel


no. viation dy/warning cause
2 [hi t] Compressor temperature too Let compressor Trained
high cool off person

3 [hi P] Network pressure increased Reduce network Trained


pressure person

4 [Cold] Compressor temperature too Warm up compres- Trained


low sor person

5 [oilHE] Coolant liquid level/heating Check coolant liq- Qualified


uid level/heating personnel

7 [min P] Lower pressure threshold Check BLS network Qualified


reached personnel

11 [M Air] Intake filter maintenance due Change intake filter Qualified


personnel

12 [M oilF] Maintenance coolant li- Change coolant Qualified


quid/coolant liquid filter due liquid filter personnel

13 [M SEP] Maintenance of fine precipita- Maintain fine pre- Qualified


tor due cipitator personnel

14 [M Mot] Maintenance motor lubricati- Lubricate motor Qualified


on due personnel

15 [M Com] Maintenance of compressor Maintain compres- Qualified


due sor personnel

If a fault not listed in the warning table occurs, contact


the manufacturer immediately.

68 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 2 controller

5.8.3 Acknowledging fault and warning messages

NOTICE!
Danger of property damage due to improperly per-
formed fault remedy/maintenance work!
Acknowledgement of fault and warning messages with-
out properly-executed fault remedy/maintenance work
can cause severe damage to the compressor on through
to total failure.
- Only have fault remedy/maintenance work performed
by qualified personnel.
- Only acknowledge fault and warning messages if fault
remedy/maintenance work has been performed prop-
erly.

Acknowledging a fault message 1. Press .

 The fault message on the display goes out.

Acknowledging a warning message 1. Press .

 The warning message on the display goes out.

2012-07-13 69
Controllers AC 1, AC 2, AC 3

Air Control AC 3 controller

6 Air Control AC 3 controller

6.1 Overview of Air Control AC 3

Fig. 21: Overview of Air Control AC 3

70 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 3 controller

No. Key/icon Description of function No. Key/icon Description of function


Displays settings and Serves to scroll and reduce
1 Display 7
operating parameters. values.

Serves to call up dis-


plays/information and to
2 8 Serves to confirm inputs.
move the cursor to the
left.

Serves to call up dis- Serves to display additional


plays/information and to operating data and to call up
3 9
move the cursor to the the main menu and for code
right. input.

Serves to switch off the com-


Serves to call up dis-
4 10 pressor, to acknowledge
plays/information.
fault/warning messages.

Indicates warnings with flash-


Serves to call up dis-
5 11 ing and faults with red LEDs
plays/information.
that light up.

Serves to switch on the com-


Serves to scroll and pressor. The integrated
6 12
increase values. green LED indicates the op-
erating state.

6.2 Brief description


The Air Control AC 3 controller serves
 to display operating data/the compressor state
 to switch on/off the compressor/the compressed air generation
 to program the compressor and the compressed air generation.

2012-07-13 71
Controllers AC 1, AC 2, AC 3

Air Control AC 3 controller

6.3 Operating modes


Overview Four operating modes can be set using the controller.

Operating mode Description


Automatic operation After reaching the switch-off pressure,
the system switches to idle for the
duration of the idle time (run-on). After
the run-on time has elapsed, the mo-
tor switches off. The compressor can
start up by itself at any time if the ma-
chine drops below the switch-on pres-
sure.

Load/idle operation The compressor switches between


"Load" and "Idle" operation; that is,
there is an unlimited run-on.

Optional automatic After reaching the switch-off pressure,


the compressor switches to idle. After
10 and 40 seconds, the respective
network pressure is measured. If the
pressure drop determined this way is
above the threshold "Max. pressure
drop", the compressor remains in idle
for the duration of the run-on time. In
the basic display, the text "Run-on"
appears with the corresponding re-
maining time. If the value determined
is below the threshold "Max. pressure
drop", the compressor switches off
after the shutdown time has elapsed.

Basic load switching The switch on/off pressure set is not


mode (BLS mode)) taken into account by the controller.
The compressor is controlled by a
superior controller.

Safety pressure The safety pressure is the sum of the set maximum pressure +0.8 bar.
If the pressure exceeds the value of the safety pressure, the com-
pressor is switched off with a fault message. If the maximum pressure
is exceeded by 0.5 bar, a warning appears on the display.

72 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 3 controller

6.4 Overview of display


Basic display
1 [Zusatzinformationen (Additional information)] display area
2 [Verdichtungsendtemperatur (Final compressor temperature)]
display
3 [Datum/Uhrzeit (Date/Time)] display
4 Function programming of the keys. Here: Call up the
[Anlagenpass (System pass)] display
5 Function programming of the keys. Here: Call up the [Service]
display
Fig. 22: Overview of display 6 Function programming of the keys. Here: Call up the [GLW
(BLS)] display
7 Function programming of the keys. Here: Call up the
[Auslastung (Capacity utilisation)] display
8 [Stör-/Warnmeldungen (Fault/warning messages)] display area
9 [Statusanzeige (Status display)]
10 [Netzdruck (Network pressure)] display

Additional information display area In the additional information display area, various information is shown
depending on the operating state and status.

Symbol/Text Description
Switching times are programmed.
Symbol flashes: The compressor was swit-
ched off by the timer.
Symbol lights up: The compressor was swit-
ched on by the timer.

Switching times are programmed.

Frost protection active, compressor does not


start up.

Automatic restart programmed

Remote mode programmed.


Symbol flashes: Compressor off.
Symbol lights up: for remote mode, compres-
sor on.

BLS operation/Load-ideal by superior control-


ler

2012-07-13 73
Controllers AC 1, AC 2, AC 3

Air Control AC 3 controller

Symbol/Text Description
Automatic optional operating mode active.

Motor is running.

Magnetic valve opened. (compressor com-


pressing)

Additional heating is switched on.

6.5 Switching the compressor on/off


Switching the compressor on 1. Press .

 The integrated green LED lights up. The compressor is ready


and can start up automatically at any time.

Switching the compressor off 1. Press .

 The green LED in the key goes out. The compressor


switches to idle for the duration of the shutdown time and then
off.

During the switch-off process, the compressor initially


switches to "Idle" (motor running, however the compres-
sor is not compressing any air) for the duration of the
shutdown time. Only then does the compressor switch
off (the motor stops).

74 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 3 controller

6.6 Calling up displays/information via function keys

6.6.1 Changing the function programming of the function keys

The basic display has two display modes in which various dis-
plays/information can be called up using the function keys.

Basic display mode 1


1 Function programming of the keys. Here: Call up the
[Auslastung (Capacity utilisation)] display
2 Function programming of the keys. Here: Call up the [GLW
(BLS)] display
3 Function programming of the keys. Here: Call up the [Service]
display
4 Function programming of the keys. Here: Call up the
[Anlagenpass (System pass)] display
Fig. 23: Basic display [Mode 1]

Basic display mode 2


1 Function programming of the keys. Here: Calling up the
[Diagramm-Netzdruck (Diagram-network pressure)]
2 Function programming of the keys. Here: Calling up the
[Diagramm-Verdichtungstemperatur (Diagram-compressor
temperature)]
3 Function programming of the keys. Here: Calling up the
[Diagramm-Luftmenge/Tag (Diagram-air quantity/day)] display
4 Function programming of the keys. Here: Calling up the
Fig. 24: Basic display [Mode 2] [Diagramm-Luftmenge/Woche (Diagram-air quantity/week)]
display

Changing the display mode 1. Press or .

2012-07-13 75
Controllers AC 1, AC 2, AC 3

Air Control AC 3 controller

6.6.2 Calling up the Capacity utilisation display

Calling up Prerequisite: Basic display [Modus 1 (Mode 1)] is selected


 Chapter 6.6.1 ‘Changing the function programming of the function
keys’ on page 75.

1. Press .

 [Auslastung (Capacity utilisation)] appears on the display

By pressing the key, it is possible to return to the ba-


sic display.

Overview
1 Shutdown hours
2 Idle hours
3 Load hours
4 Total hours of operation

Fig. 25: [Auslastung (Capacity utilisation)]


display

Description The [Capacity utilisation] display shows the operating hours, load, idle,
and shutdown hours in the form of a bar graph. In the bar graph, the
current number of hours is also displayed. With the exception of the
idle hours, all bars are displayed in ascending order from left to right.
The total of load hours and idle hours produces the total operating
hours. The scaling of this diagram is done according to the hours of
operation. If the number of shutdown hours is greater than that of
hours of operation, the bar for the shutdown hours is cut off.

76 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 3 controller

6.6.3 Calling up the Basic load switch display

Calling up Prerequisite:
 Basic display [Modus 1 (Mode 1)] is selected  Chapter 6.6.1
‘Changing the function programming of the function keys’ on
page 75.
 Basic load switch/Basic load switch activated operating mode

1. Press .

 [Grundlastwechsel (Basic load switch)] appears on the display

By pressing the key, it is possible to return to the ba-


sic display.

Overview
1 Compressors
2 Fault
3 Operational readiness
4 Idle
5 Load

Fig. 26: [Grundlastwechsel (Basic load


switch)] display

Description The [Grundlastwechsel (Basic load switch)] display shows the operat-
ing status of the compressors that are working on a BLS network.
6.6.4 Calling up the Service display

Calling up Prerequisite: Basic display [Modus 1 (Mode 1)] is selected


 Chapter 6.6.1 ‘Changing the function programming of the function
keys’ on page 75.

1. Press .

 [Service] appears on the display

By pressing the key, it is possible to return to the ba-


sic display.

2012-07-13 77
Controllers AC 1, AC 2, AC 3

Air Control AC 3 controller

Overview
1 Remaining time compressor
2 Remaining time motor lubrication
3 Remaining time fine precipitator
4 Remaining time coolant liquid filter
5 Remaining time intake filter

Fig. 27: [Service] display

Description The [Service] display shows the remaining time until the next mainte-
nance of individual components in the form of a bar chart. In the bar
graph, the current number of remaining hours is also displayed. With a
remaining time of less than 100 hours until the next maintenance of a
component, the associated bar begins to flash and a corresponding
warning appears on the display in the [Stör-/Warnmeldungen
(Fault/warning messages)] display area.

6.6.5 Calling up the System pass display

Calling up Prerequisite: Basic display [Modus 1 (Mode 1)] is selected


 Chapter 6.6.1 ‘Changing the function programming of the function
keys’ on page 75.

1. Press .

 [Anlagenpass (System pass)] appears on the display

By pressing the key, it is possible to return to the ba-


sic display.

78 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 3 controller

Overview

Fig. 28: [Anlagenpass (System pass)] display

Description The [Anlagenpass (System pass)] display shows the saved, individual
compressor data. This data is intended for the manufacturer's owner
service.

6.6.6 Calling up the Diagram-network pressure display

Calling up Prerequisite: Basic display [Modus 2 (Mode 2)] is selected


 Chapter 6.6.1 ‘Changing the function programming of the function
keys’ on page 75.

1. Press .

 [Diagramm Netzdruck (Diagram-network pressure)] appears


on the display

By pressing the key, it is possible to return to the ba-


sic display.

Overview

Fig. 29: [Diagramm Netzdruck (Diagram-network pressure)] display

2012-07-13 79
Controllers AC 1, AC 2, AC 3

Air Control AC 3 controller

Description The [Diagramm Netzdruck (Diagram-network pressure)] display shows


the temporal course of network pressure in the form of a diagram.

6.6.7 Calling up the Diagram-compression final temperature display

Calling up Prerequisite: Basic display [Modus 2 (Mode 2)] is selected


 Chapter 6.6.1 ‘Changing the function programming of the function
keys’ on page 75.

1. Press .

 [Diagramm Verdichtungsendtemperatur (Diagram-compressor


final temperature)] appears on the display

By pressing the key, it is possible to return to the ba-


sic display.

Overview

Fig. 30: [Diagramm Verdichtungsendtemperatur (Diagram-compression final


temperature)] display

Description The [Diagramm Verdichtungsendtemperatur (Diagram-compression


final temperature)] display shows the temporal course of the compres-
sion final temperature in the form of a diagram.

80 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 3 controller

6.6.8 Calling up the Diagram-compressed air/day display

Calling up Prerequisite: Basic display [Modus 2 (Mode 2)] is selected.

1. Press .

 [Diagramm Druckluft/Tag (Diagram-compressed air/day)] ap-


pears on the display

By pressing the key, it is possible to return to the ba-


sic display.

Overview

Fig. 31: Overview of display

Description The [Diagramm Druckluft/Tag (Diagram compressed air/day)] display


shows the temporal course of the compressed air delivery quantity for
a day in the form of a diagram.

6.6.9 Calling up the Diagram-compressed air/week display

Calling up Prerequisite: Basic display [Modus 2 (Mode 2)] is selected


 Chapter 6.6.1 ‘Changing the function programming of the function
keys’ on page 75.

1. Press .

 [Diagramm Druckluft/Woche (Diagram-compressed air/week)]


appears on the display

By pressing the key, it is possible to return to the ba-


sic display.

2012-07-13 81
Controllers AC 1, AC 2, AC 3

Air Control AC 3 controller

Overview

Fig. 32: Overview of [Diagramm Druckluft/Woche (Diagram-compressed


air/week)] display

Description The [Diagramm Druckluft/Woche (Diagram compressed air/week)]


display shows the temporal course of the compressed air delivery
quantity for a week in the form of a diagram.

6.7 Editing axis values of the display diagrams


By editing the axis values, the scaling of the axes can be changed.

Axis Description
x In the [Diagramm Druckluft/Woche (Diagram-
compressed air/week)] display, the x-axis values
cannot be changed; in all other diagrams, a change
is possible.

y The values of the y-axis can be changed in each


diagram. The data in the diagram is also updated
continuously after editing. After editing the x-axis
values, the diagram is no longer updated continu-
ously.

82 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 3 controller

Overview of axes
1 Axis value 2 x-axis (point in time 2:11PM).
2 [X-Auto Ein/Aus (X-Auto on/off)] display. With [X-AUTO EIN (X-
AUTO ON)] the values of the x-axis are updated automatically.
Here, X-AUTO relies on the set default values. The manually-
edited x-axis values are deleted.
3 Axis value 1 x-axis (point in time 13:11:00).
4 Axis value 1 y-axis (0 bar).
5 Cursor
Fig. 33: Overview of axis values 6 Axis value 2 y-axis (11 bar).

By pressing the key, it is possible to return to the ba-


sic display.

Changing the axis values 1. Select the axis value; to do this, use the keys.

2. Press the key to confirm the selection.

 The selected value begins to flash.

3. Change the flashing value with the keys.

With the and keys, the cursor can be moved


to the left and right.

4. Press the key to confirm the selections.

Switching X-AUTO on/off 1. Press .

In order to switch X-AUTO on again, press


again.

Resetting axis values to default 1. Press .


settings
Deleting recorded measurement 1. Press .
values

2012-07-13 83
Controllers AC 1, AC 2, AC 3

Air Control AC 3 controller

6.8 Setting parameters via menu system


All basic settings of the compressor can be viewed on the menu sys-
tem. The parameters for all basic settings of the compressor can be
changed insofar as these changes do not influence the operational
stability.

6.8.1 Calling up the code input menu

1. Press .

 The code input menu appears on the display.

In order to exit the code input menu again, press the


key.

6.8.2 Overview of code input menu

1 Code input area


2 Cursor

Fig. 34: Code input menu

6.8.3 Inputting a code

Code Description
00000 View the parameters in the
submenus WITHOUT chang-
ing.

00001 View and change the parame-


ters in the submenus.

Prerequisite: the code input menu has been called up.

84 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 3 controller

1. Use the keys to change the flashing value in the code


input area (Fig. 34/1).

With the and keys, the cursor can be moved


to the left and right.

2. To confirm the selected code, press .

 The overview menu for the submenus appears on the display.

6.8.4 Selecting overview of submenus and submenus

After inputting one of the two codes, the overview menu for the sub-
menus appears.
1 Display area for the available submenus
2 Cursor

Fig. 35: Overview menu for submenus

Selecting a submenu 1. Press the keys until the desired submenu is marked by
the cursor.

2. Press the key to confirm the selection.

 The selected submenu appears on the display.

By pressing the key, it is possible to return to the ba-


sic display.

2012-07-13 85
Controllers AC 1, AC 2, AC 3

Air Control AC 3 controller

6.8.4.1 Changing parameters in the submenus

1. Call up the desired submenu.

2. Select the editable parameters with the keys.

3. Press the key to confirm the selection.

 The cursor under the parameter begins to flash.

4. Change the parameter value with the keys.

With the and keys, the cursor can be moved


to the left and right.

5. Press the key to confirm the selection.

By pressing the key, it is possible to return to the


overview menu for the submenus.

86 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 3 controller

6.8.4.2 Limit values submenu

Brief description Temperature and pressure limit values are on the [Grenzwerte (Limit
values)] submenu.

Parameter Description Status


[Einschaltdruck Lower value for the Editable
(Switch-on pressu- pressure regulation.
re)] The switch-on
pressure specifies
the pressure at
which the switched-
on compressor will
begin automatically
with the compres-
sion.

[Ausschaltdruck Upper value for the Editable


(Switch-off pressu- pressure regulation.
re)] The switch-off
pressure specifies
the pressure at
which the compres-
sor will be switched
off automatically.

[Sicherheitsdruck Maximum permissi- Display


(Safety pressure)] ble pressure for
fault triggering (al-
ways 0.8 bar above
the maximum pres-
sure)

[GLW-Betrieb (BLS Minimum pressure Display


operation)] monitoring in BLS
operation

[Verdichtungsend- Minimum permissi- Display


temperatur min ble compression
(Compression final final temperature
temperature min)]

[Verdichtungsend- Maximum permissi- Display


temperatur max ble compression
(Compression final final temperature
temperature max)]

2012-07-13 87
Controllers AC 1, AC 2, AC 3

Air Control AC 3 controller

6.8.4.3 Operating parameters submenu

Brief description Parameters for the operating modes and temporal control are located
on the [Betriebsparameter (Operating parameters)] submenu.

Parameter Description Status


[Nachlaufzeit (Run- Run-on time of the Display
on time)] motor in automatic
operation

[Stillstandszeit Run-on time of the Display


(Shutdown time)] motor with manual
switch-off and delay
with automatic re-
start.

[Sicherheitsdruck Maximum permissi- Display


(Safety pressure)] ble pressure for
fault triggering (al-
ways 0.8 bar above
the maximum pres-
sure)

[Hochlaufzeit (Run- Duration of the start Display


up time)] phase

[Automatischer Start after power Editable


Wiederanlauf restoration
Ein/Aus (Automatic
restart on/off)]

[Betriebsart (Opera-  Chapter 6.3 Editable


ting mode)] ‘Operating modes’
on page 72

[Max. Druckabfall Maximum pressure Display


(Max. pressure drop
drop)]

[Max. Schaltspiele Maximum operating Display


(Max. operating cycles of the motor
cycles)] per hour. If this is
exceeded, the
compressor swit-
ches temporarily
into the "Load/idle"
operating mode.

88 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 3 controller

6.8.4.4 Maintenance intervals submenu

Brief description All set point values for the maintenance intervals for components are
displayed on the [Wartungsintervalle (Maintenance intervals)] sub-
menu. Maintenance messages must be acknowledged on the sub-
menu. With the acknowledgement, the interval is reset to the default
value again.

Parameter Description Status


[Wartungsintervall Intake filter mainte- Display
ASF (ASF mainte- nance interval
nance interval)]

[Wartungsintervall Coolant liquid filter Display


OLF (OLF mainte- maintenance filter
nance interval)]

[Wartungsintervall Fine precipitator Display


OLAB (OLAB main- maintenance inter-
tenance interval)] val

[Wartungsintervall Motor lubrication Display


Motor (Motor main- maintenance inter-
tenance interval)] val

[Wartungsintervall Compressor main- Display


Komp (Comp main- tenance interval
tenance interval)]

[Betriebsstunden Hours of operation Display


(Hours of operati- (motor on)
on)]

[Laststunden (Load Load hours Display


hours)]

[Stillstandsstunden Shutdown hours Display


(Shutdown hours)] (system on and
motor off)

[Gesamt- Previous delivery Display


Liefermenge (Total quantity of the
delivery quantity)] compressor

2012-07-13 89
Controllers AC 1, AC 2, AC 3

Air Control AC 3 controller

6.8.4.5 Timer submenu

Brief description The setting for the integrated timer and all switching procedures that
depend on this are located on the [Schaltuhr (Timer)] submenu. With
the timer, both switching times and pressure times can be pro-
grammed independently of one another. By programming switching
times, the compressor does not have to be switched on and off manu-
ally. This prevents the compressor from starting up at night by itself in
order to full up the loss on the compressed air network again. Values
that deviate from the set limit values can be set for the switch-on and
switch-off pressure, with a temporal limitation. This way, only the mi-
nimum required operating pressure will be generated and energy will
thus be saved.

Parameter Description Status


[Datum/Zeit Setting of the cur- Editable
(Date/time)] rent date and time

[Schaltzeiten Kom- Branching into the Editable


pressor (Compres- submenu
sor switching ti-
mes)]

[Druckzeiten Kom- Branching into the Editable


pressor (Compres- submenu
sor pressure times)]

[Schaltzeiten GLW Branching into the Editable


(BLS switching submenu
times)]

[Druckzeiten GLW Branching into the Editable


(BLS pressure ti- submenu
mes)]

[Schaltzeiten Pri- Branching into the Editable


oritäten (Priorities submenu
switching times)]

Setting switching times of the After selecting the parameter [Compressor switching times], the set-
compressor ting menu for the switching times of the compressor appears on the
display. The switch-on/off times of the compressor are defined on this
menu.

If switching times are set for the compressor, the com-


pressor works only at the specified switching times.

90 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 3 controller

1 Timer channel on/off display


2 Switch-off times
3 Switch-on times
4 Days of the week
5 Channels
6 Cursor

Fig. 36: Switching times setting menu 7 switching times can be programmed with the channels
K1-K7. A channel is active if at least one of the days of
the week is marked in black. In order to activate the ti-
mer channel continuously for one or more days, enter
the switching time 00:00.

1. Select the timer channel with the cursor.

2. Press .

3. Set the timer channel value with the keys to [ON].

4. Press the key to confirm the selection.

5. Select channel with the keys.

6. Press the key to confirm the selection.

7. With the and keys, place the cursor on the desired day of
the week.

8. Mark the day of the week with the key.

By pressing the key, the day of the week can be


unmarked again.

9. With the and keys, set the cursor to the switch-on or off
time for the channel.

10. Change the time with the keys.

11. Press the key to confirm the input.

By pressing the key, it is possible to return to the


[Timer] submenu.

2012-07-13 91
Controllers AC 1, AC 2, AC 3

Air Control AC 3 controller

Setting pressure times of the After selecting the parameter [Druckzeiten Kompressor (Compressor
compressor pressure times)], the setting menu for the pressure times of the com-
pressor appears on the display. The pressure times of the compressor
are defined on this menu.

92 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 3 controller

1 Switch-on/switch-off times
2 Pressure times on/off display
3 Switch-on and switch-off pressure
4 Channels
5 Cursor
6 Days of the week

Fig. 37: Pressure times setting menu 7 switching times can be programmed with the channels
K1-K7. A channel is active if at least one of the days of
the week is marked in black. In order to activate the ti-
mer channel continuously for one or more days, enter
the switching time 00:00.

1. Select the timer channel with the cursor.

2. Press .

3. Set the timer channel value with the keys to [ON].

4. Press the key to confirm the selection.

5. Select channel with the keys.

6. Press the key to confirm the selection.

7. With the and keys, place the cursor on the desired day of
the week.

8. Mark the day of the week with the key.

By pressing the key, the day of the week can be


unmarked again.

9. With the and keys, set the cursor to the switch-on or off
time for the channel.

10. Change the time with the keys.

11. With the and keys, place the cursor on the desired switch-
on pressure for the channel.

12. Change the switch-on pressure with the keys.

13. With the and keys, place the cursor on the switch-off
pressure for the channel.

14. Change the switch-off pressure with the keys.

15. Press the key to confirm the input.

2012-07-13 93
Controllers AC 1, AC 2, AC 3

Air Control AC 3 controller

By pressing the key, it is possible to return to the


[Schaltuhr (Timer)] submenu.

Setting other switching and pres- After selecting the parameter in question, the switching and pressure
sure times times of the other parameter on the [Schaltuhr (Timer)] submenu can
be set as described in this section.
6.8.4.6 Fault memory submenu

The last 20 maintenance, warning and fault messages are displayed


on the [Störspeicher (Fault memory)] submenu.
6.8.4.7 Display parameters submenu

Parameters for the output on the display are stored on the [An-
zeigeparameter (Display parameters)] submenu.

Parameter Description Status


[Druckeinheit Setting of the pres- Editable
(Pressure unit)] sure unit (bar, psi,
MPa)

[Temperatureinheit Setting of the tem- Editable


(Temperature unit)] perature unit (°C,
°F, Kelvin)

[Volumeneinheit Setting of the vol- Editable


(Volume unit)] ume unit

[Sprache (Langua- Setting of the dis- Editable


ge)] play language (12
languages avail-
able)

[Druck-Offset Readjustment pos- Display


(Pressure offset)] sibility for the net-
work pressure sen-
sor

[Diagramme (Dia- Settings for dia- Editable


grams)] grams, branching to
the submenu

[Texte (Texts)] Texts for the sys- Display


tem pass

94 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 3 controller

Diagrams settings menu Parameters for the display of the diagrams on the display are stored
on the [Diagramme (Diagrams)] settings menu.

Parameter Description Status


[Speicherintervall Storage interval for the Editable
(Storage interval)] recording of the net-
work pressure, the
compression final tem-
perature and the cur-
rent delivery quantity.
The controller always
saves the last 8000
values. With a storage
interval of 12 s (basic
setting), there is a his-
tory duration of 12 s x
8000 = 9600 s = 26.7 h

[Anzahl Punkte bei Number of recorded Editable


X-AUTO (Number values for the X-AUTO
of points for X- function. On the time
AUTO)] axis, with a storage
interval of 12 s and a
number of 300 points
for X-AUTO, a time
axis scaling of 12 s x
300 = 3600 s = 1 h

[Netzdruck Unter- Lower scale value of Editable


grenze (Network the y-axis of the [Netz-
pressure lower druck (Network pres-
limit)] sure)] diagram

[Netzdruck Ober- Upper scale value of Editable


grenze (Network the y-axis of the [Netz-
pressure upper druck (Network pres-
limit)] sure)] diagram

[Temperatur Unter- Lower scale value of Editable


grenze (Tempera- the y-axis of the [Ver-
ture lower limit)] dichtungsendtempera-
tur (Compression final
temperature)] diagram

2012-07-13 95
Controllers AC 1, AC 2, AC 3

Air Control AC 3 controller

Parameter Description Status


[Temperatur Ober- Upper scale value of Editable
grenze (Tempera- the y-axis of the [Ver-
ture upper limit)] dichtungsendtempera-
tur (Compression final
temperature)] diagram
(basic setting 120 °C)

[Druckluftmen- Lower scale value of Editable


ge/Tag Untergren- the y-axis of the [Dia-
ze (Compressed air gramm Druckluft/Tag
q./day lower limit)] (Diagram-compressed
air/day)] diagram

[Druckluftmen- Upper scale value of Editable


ge/Tag Obergrenze the y-axis of the [Dia-
(Compressed air gramm Druckluft/Tag
q./day upper limit)] (Diagram-compressed
air/day)] diagram

[Druckluftmen- Lower scale value of Editable


ge/Woche Unter- the y-axis of the [Dia-
grenze (Compres- gramm Druck-
sed air q./week luft/Woche (Diagram-
lower limit)] compressed air/week)]
diagram

[Druckluftmen- Upper scale value of Editable


ge/Woche Ober- the y-axis of the [Dia-
grenze (Compres- gramm Druck-
sed air q./week luft/Woche (Diagram-
upper limit)] compressed air/week)]
diagram

96 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 3 controller

6.8.4.8 Configuration submenu

Parameters for the basic configuration are stored on the [Konfigura-


tion (Configuration)] submenu.

Parameter Description Status


[Anlagentyp (System type)] Details about the compressor Display
type

[Maximaler Druck (Maximum Maximum permissible pressure Display


pressure)]

[Maximale Liefermenge (Maxi- Delivery quantity for maximum Display


mum delivery quantity)] speed in load mode

[Fern-Modus (Remote mode)] Specifies how the compressor is Editable


switched on and off.
On-site operation: The compres-
sor can only be switched off on
the control console/display of the
Air Control 3.
Remote compressor: The com-
pressor can be switched on by
an electric signal and switched
off by an electric signal or the
key. The flashing text
[REMOTE] appears in the
[Grundanzeige (Basic display)].
Remote BLS: The BLS network
can be switched on by an elec-
tric signal and switched off by an
electric signal or the key.
If the system was switched off
by the key, the key
must also be pressed with active
remote mode for switching the
compressor on.

[BLS-OK] Serves to indicate the opera- Editable


tional readiness of a superior
controller on the compressor.

2012-07-13 97
Controllers AC 1, AC 2, AC 3

Air Control AC 3 controller

Parameter Description Status


[GLW-Betrieb (BLS operation)] Operation with a master system Editable
in the BLS network.
The compressor is controlled by
a superior controller. The flash-
ing text [GLW-BETR (BLS-
OPER)] appears in the [Grun-
danzeige (Basic display)].

[Unterspannungs Stop (Under- Switch-off with detected under- Display


voltage stop)] voltage

[Frequenzumrichter (Frequency Settings for the frequency con- Display


converter)] verter

[Kommunikation (Communicati- Settings for serial communicati- Display


on)] on

[Heizung (Heating)] Settings for the additional heat- Display


ing

6.8.4.9 Basic load switching submenu

Parameters for the operation of the compressor as BLS master are


stored on the [Grundlastwechsel (Basic load switching)] submenu. To
use the basic load switching function, the Air Control 3 must be equip-
ped with a RS-485 interface.

NOTICE!
Property damage due to incorrect parameterisation
for BLS operation!
If the compressor is not used as a master system de-
spite activation of the BLS master function, the compres-
sor may fail.
- Only activate the BLS master function if the compres-
sor will really be used as a BLS master.

98 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 3 controller

Parameter Description Status


[Grundlastwechsel Parameter for the Display
(Basic load swit- activation of the
ching)] BLS master charac-
teristics (basic set-
ting: NO)

[Wechsel sofort NO: Switch of the Editable


(Switch immediate- compressor priority
ly)] only takes place if
the switch-on or
switch-off pressure
is reached.
YES: Switch takes
place immediately.

[Zuschaltdruck Lower pressure Editable


(Switch-on pressu- threshold for the
re)] switch-on of a com-
pressor

[Abschaltdruck Upper pressure Editable


(Switch-off pressu- limit for switching
re)] off a compressor

[Abschaltung bei Percentage actuat- Editable


(Switch-off at)] ing variable below
which the slave
compressors are
switched off.

[Zuschaltung bei Percentage actuat- Editable


(Switch-on at)] ing variable above
which the slave
compressors are
switched on.

[Zuschaltdämpfung Delay starts when Editable


Erstzuschaltung reaching the re-
(Switch-on damping spective pressure
initial switch-on)] threshold

[Abschaltdämpfung Delay starts when Editable


Erstabschaltung reaching the re-
(Switch-off damping spective pressure
initial switch-off)] threshold

[Zuschaltdämpfung Minimal time be- Editable


Folgezuschaltung tween the switching
(Switch-on damping on of two compres-
subsequent switch- sors
on)]

2012-07-13 99
Controllers AC 1, AC 2, AC 3

Air Control AC 3 controller

Parameter Description Status


[Abschaltdämpfung Minimal time be- Editable
Folgeabschaltung tween the switching
(Switch-off damping off of two compres-
subsequent switch- sors
off)]

[Wechselintervall Time between the Editable


Priorität 1 (Switch further switching of
interval priority 1)] the BLS for the
compressor with
priority 1

[Wechselintervall Time between the Editable


Priorität 2 (Switch further switching of
interval priority 2)] the BLS for the
compressor with
priority 2

[Wechselintervall Time between the Editable


Priorität 3 (Switch further switching of
interval priority 3)] the BLS for the
compressor with
priority 3

[Prioritäten (Priori- Assignment of the Editable


ties)] switch-on priority

100 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 3 controller

6.8.4.10 Accessories submenu

Parameters for the incorporation of accessories are located on the


[Zubehör (Accessories)] submenu. To use this function, the Air Con-
trol 3 must be equipped with the accessory expansion modules.

For the electrical data, please consult the attached wiring


diagram.

Parameter Description Status


[Zubehörmodul Additional module Display
vorhanden (Acces- for accessories
sory module pre- present
sent)]

[Eingangskonfigura- Function of the Editable


tion (Input configu- digital inputs
ration)]

[Ausgangskonfigu- Function of the Editable


ration (Output con- digital outputs
figuration)]

[Schaltzeiten Aus- Define switching Editable


gang 1 (Switching times for accessory
times output 1)] 1 Chapter 6.8.4.5
‘Timer submenu’ on
page 90

[Schaltzeiten Aus- Define switching Editable


gang 2 (Switching times for accessory
times output 2)] 2 Chapter 6.8.4.5
‘Timer submenu’ on
page 90

[Schaltzeiten Aus- Define switching Editable


gang 3 (Switching times for accessory
times output 3)] 3 Chapter 6.8.4.5
‘Timer submenu’ on
page 90

[Schaltzeiten Aus- Define switching Editable


gang 4 (Switching times for accessory
times output 4)] 4 Chapter 6.8.4.5
‘Timer submenu’ on
page 90

2012-07-13 101
Controllers AC 1, AC 2, AC 3

Air Control AC 3 controller

6.8.4.11 Diagnosis submenu

The current states of the inputs and output are described on the [Di-
agnose (Diagnosis)] submenu.

For the electrical data, please consult the attached wiring


diagram.

6.8.5 Fault and warning messages


6.8.5.1 Fault message

When a fault occurs, the compressor switches off and it


can only be switched on again after the cause of the fault
has been eliminated. Subsequently, the fault message
must be acknowledged with the key.

If a fault occurs during operation, a fault message appears in the


[Stör-/Warnmeldungen (Fault/warning messages)] area on the display
and the LED on the display lights up red.

Acknowledging a fault message 1. Switch compressor on again after fault eliminated.

2. Press to acknowledge the fault.

102 2012-07-13
Controllers AC 1, AC 2, AC 3

Air Control AC 3 controller

6.8.5.2 Warning/maintenance message

Necessary maintenance appears as a warning message in the [Stör-


/Warnmeldungen (Fault/warning messages)] area on the display and
the LED in the display flashes red. Warning messages must
be acknowledged by the manufacturer's service on the [Wartunginter-
valle (Maintenance intervals)] submenu.

NOTICE!
Danger of property damage due to improperly per-
formed maintenance!
Acknowledgement of warning messages without prop-
erly-executed maintenance work can cause severe dam-
age to the compressor on through to total failure.
- Only have maintenance work performed by qualified
personnel.
- Only acknowledge warning messages if maintenance
work has been performed properly.

2012-07-13 103
Controllers AC 1, AC 2, AC 3

Air Control AC 3 controller

6.8.6 Setting the display contrast

The display contrast of the controller was select so that optimal legibil-
ity is guaranteed under nearly all conditions of use. If under certain
circumstances (e.g. unfavourable lighting, direct solar radiation) it is
necessary to adjust the contrast, however, carry out the following
steps:

DANGER!
Danger to life from electric power!
Touching voltage-conducting components can cause
deadly electric shock.
- Before all work for setting the display contrast, de-
energise the compressor on the main switch and se-
cure it against being switched on again.

1. De-energise compressor on the main switch.

2. Open the switch cabinet/switch box of the compressor.

3. Insert a small screwdriver in the opening (Fig. 38/arrow) on the


back of the controller.

4. Turn the screwdriver clockwise in order to increase the display


contrast. Turn the screwdriver anti-clockwise in order to decrease
the display contrast.

5. Pull the small screwdriver out of the opening on the back of the
Fig. 38: Display opening controller.

6. Close the switch cabinet/switch box of the compressor again.

104 2012-07-13
Controllers AC 1, AC 2, AC 3

Index

7 Index

Set on-site operation/remote operation......36


A Set switch on/off pressure ...........................38
Accident.............................................................22 Setting parameters........................................30
Air Control AC 1 controller ..............................25 Setting the display contrast .........................48
Acknowledging a fault message .................47 Switch automatic restart on/off ...................35
Acknowledging a warning message ...........47 Switch the pressure unit ..............................40
Basic display .................................................27 Switch the temperature unit.........................41
Brief description ...........................................26 Switching off..................................................28
Calling up information..................................29 Switching on..................................................28
Calling up parameter values ........................29 Value parameters submenu .........................32
Calling up the code input menu ..................30 Warning message .........................................45
Code 0002 ......................................................33 Warning table ................................................46
Code 0003 ......................................................35 Air Control AC 2 controller ..............................49
Code 0008 ......................................................36 Acknowledging a fault message .................69
Code 0011 ......................................................38 Acknowledging a warning message ...........69
Code 0018 ......................................................39 Basic display .................................................51
Code 0090 ......................................................40 Brief description............................................50
Code 0095 ......................................................41 Calling up information ..................................53
Code 9999 ......................................................42 Calling up parameter values ........................53
Display ...........................................................27 Calling up the code input menu ..................55
Display the software version .......................42 Code 0002 ......................................................57
Fault message ...............................................43 Code 0003 ......................................................59
Fault table ......................................................44 Code 0008 ......................................................60
Inputting a code ............................................31 Code 0011 ......................................................61
Maintenance message..................................45 Code 0018 ......................................................62
Maximum operating cycles ..........................34 Code 0090 ......................................................63
Maximum pressure drop ..............................34 Code 0095 ......................................................64
Operating mode display ...............................28 Code 9999 ......................................................65
Operating modes ..........................................26 Display............................................................51
Other display indicators...............................27 Display the software version .......................65
Overview ........................................................25 Fault message ...............................................65
Overview of code input menu......................31 Fault table ......................................................66
Overview of submenus.................................32 Inputting a code ............................................56
Safety pressure .............................................26 Maintenance message ..................................67
Select operating mode .................................33 Maximum operating cycles ..........................58
Set Basic load switching mode ...................39

2012-07-13 105
Controllers AC 1, AC 2, AC 3

Index

Maximum pressure drop ..............................58 Calling up the Diagram-compression final


Operating data display area .........................51 temperature display.................................. 80

Operating mode display ...............................52 Calling up the Diagram-network pressure


display........................................................ 79
Operating modes...........................................50
Calling up the Service display .................... 77
Overview ........................................................49
Calling up the System pass display ........... 78
Overview of code input menu ......................55
Changing parameters .................................. 86
Overview of submenus.................................56
Changing the axis values ............................ 83
Safety pressure .............................................50
Changing the basic display mode .............. 75
Select operating mode..................................57
Changing the function key programming.. 75
Selection parameter submenu...............32, 56
Configuration submenu............................... 97
Set Basic load switching mode ...................62
Deleting measurement values .................... 83
Set on-site operation/remote operation ......60
Description of basic load switch display... 77
Set switch on/off pressure ...........................61
Description of Capacity utilisation display 76
Setting parameters........................................55
Description of Diagram-compressed air/day
Setting the minimum pressure/BLS ............61 display........................................................ 81
Switch automatic restart on/off ...................59 Description of Diagram-compressed
Switch the pressure unit ..............................63 air/week display ........................................ 82
Switch the temperature unit.........................64 Description of Diagram-compression final
Switching off..................................................53 temperature display.................................. 80

Switching on ..................................................53 Description of Diagram-network pressure


display........................................................ 80
Value parameters submenu .........................57
Description of Service display .................... 78
Warning message .........................................67
Description of System pass display........... 79
Warning table.................................................68
Diagnosis submenu ................................... 102
Air Control AC 3 controller ..............................70
Diagrams settings menu.............................. 95
Accessories submenu ................................101
Display........................................................... 73
Acknowledging a fault message ...............102
Display parameters submenu ..................... 94
Additional information display area ............73
Editing diagram axis values ........................ 82
Basic display .................................................73
Fault memory submenu............................... 94
Basic display mode 1....................................75
Fault message ............................................ 102
Basic display mode 2....................................75
Function keys ............................................... 75
Basic load switching submenu....................98
Inputting a code............................................ 84
Brief description............................................71
Limit values submenu.................................. 87
Calling up the Basic load switch display....77
Maintenance intervals submenu................. 89
Calling up the Capacity utilisation display.76
Menu system................................................. 84
Calling up the code input menu...................84
Operating modes .......................................... 72
Calling up the Diagram-compressed air/day
display ........................................................81 Operating parameters submenu................. 88
Calling up the Diagram-compressed Operating the function keys........................ 75
air/week display .........................................81 Other switching and pressure times .......... 94

106 2012-07-13
Controllers AC 1, AC 2, AC 3

Index

Overview ........................................................70 E
Overview of axes...........................................83 Electric current .................................................17
Overview of basic load switch display .......77 Emergency..........................................................24
Overview of Capacity utilisation display ....76 Emergency stop..................................................24
Overview of code input menu......................84 EMERGENCY-STOP button .............................19
Overview of Diagram-compressed air/day
display ........................................................81 F

Overview of Diagram-compressed air/week Fire .....................................................................22


display ........................................................82 First aid ..............................................................22
Overview of Diagram-compression final
M
temperature display ..................................80
Main switch .......................................................19
Overview of Diagram-network pressure
display ........................................................79
O
Overview of Service display ........................78
Owner.................................................................13
Overview of submenus.................................85
Overview of System pass display ...............79 P
Resetting axis values ...................................83 Personnel ..........................................................14
Safety pressure .............................................72 Proper use .........................................................12
Selecting a submenu ....................................85 Protective equipment .......................................16
Setting parameters .......................................84
R
Setting pressure times of the compressor.92
Rescue measures...............................................24
Setting switching times of the compressor90
Setting the display contrast.......................104 S
Switching off .................................................74 Safety
Switching on..................................................74 General ...........................................................12
Timer submenu .............................................90 Safety devices...................................................18
Warning/maintenance message ................103 Service ...............................................................11
X-AUTO ..........................................................83 Symbols
in this manual ..................................................8
C
Contact person .................................................11 U
Copyright...........................................................10 Use .....................................................................12
Customer service .............................................11
W
Warranty terms .................................................10

2012-07-13 107
Controllers AC 1, AC 2, AC 3

Appendix

8 Appendix

108 2012-07-13
Controllers AC 1, AC 2, AC 3

Training log

A Training log
Date Name Type of training Training conducted Signature
by

2012-07-13 109
Article number 195 03351REV01

You might also like