0% found this document useful (0 votes)
44 views4 pages

Why A 0-Ma Signal Is Not Practical

This document discusses why a 0 mA signal is not practical for process instrumentation compared to the industry standard 4-20 mA signal. It provides three key reasons: 1) a 0 mA signal represents an open circuit which is difficult and expensive to detect, 2) a 0 mA signal cannot clearly differentiate between a measurement of zero and a system failure, and 3) a 0 mA signal does not provide loop-powered devices with enough current to operate.

Uploaded by

Alex De La Rosa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
44 views4 pages

Why A 0-Ma Signal Is Not Practical

This document discusses why a 0 mA signal is not practical for process instrumentation compared to the industry standard 4-20 mA signal. It provides three key reasons: 1) a 0 mA signal represents an open circuit which is difficult and expensive to detect, 2) a 0 mA signal cannot clearly differentiate between a measurement of zero and a system failure, and 3) a 0 mA signal does not provide loop-powered devices with enough current to operate.

Uploaded by

Alex De La Rosa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Why a 0 mA Signal

is Not Practical

by DEL MAURICIO

For decades, process instrumentation has largely relied on 4-20 mA signals to transmit process data
easily and reliably. Moreover, it is the signal of choice in the process control industry for many reasons. One in

particular is the fact that current does not degrade and it remains constant at any point in the loop, as discussed

in our review of the Fundamentals of 4-20 mA Current Loops. Therefore, it is a very efficient means to transmit

process information. In most cases, this range represents a two-point linear scale where a 4 mA signal represents

0% of a sensor’s measurement, while 20 mA indicates 100% of the measurement [1]. But, why do we use 4-20 mA

instead of 0-20 mA? That is a very common question among individuals in the industry. And the answer is simple;

a 0 mA signal is not practical. This article will discuss three reasons why a 0 mA signal is not as useful and why

4-20 mA is the industry standard.

Page 1 of 4
WHY A 0 mA SIGNAL IS NOT PRACTICAL

Before we delve into the reasons why a 0 mA signal is not practical, let’s get to know a little bit of the

history behind the 4-20 mA signal. Prior to the invention of electronic circuitry, process control systems used

pneumatic control signals [2]. In these systems, controllers were powered by distinct pressures of compressed

air. Eventually, air compression of 3-15 psi became the industry standard for a few reasons. First, it was very

expensive to engineer a system that would detect pressure signals under 3 psi. Second, signals below 3 psi were

unrecognizable. Lastly, using 3 psi to indicate a value of 0% measurement made it easier to identify when system

faults occurred, in other words, when the signal dropped to zero. As electronic systems made their debut in the

1950s, current became the preferred, more precise, and more efficient process control signal. Later, the industry

established the 4-20 mA signal as the standard for similar reasons as those that made 3-15 psi range an effective

signal. Now let’s take a look at why a 0 mA signal is not efficient.

1. Difficult and Expensive


A 0 mA signal is essentially an open circuit in which no flow of current exists at all. Thus, engineering any

device with circuitry capable of handling a signal level that reached 0 mA and remain accurate is more difficult

and expensive than limiting the design to 4-20 mA. This was especially true during the 1950s when electrical

signals like 4-20 mA had just emerged and surpassed pneumatic signals like the old 3-15 psi standard. Further,

in a circuit where 0-20 mA is used, it would be very hard to detect and distinguish low ranges. A 4-20 mA circuit

is much easier to work with because there is in fact a consistent flow of current that can be detected and used to

reliably transmit process information [3]. As a result, the industry adopted the 4-20 mA range for its cost efficiency

as well as other similar benefits that made the former 3-15 psi signal popular.

2. Inability to Detect a System Failure


Another reason why a 0 mA signal is not efficient is the inability to clearly differentiate between a

measurement of zero and a system failure in which the signal would drop to zero. The term live zero is used

to describe a loop signal where the zero value is a number higher than zero (i.e. 4 mA) [4]. The term dead zero

denotes a loop signal where the zero value is indeed zero (i.e. 0 mA). The advantage of using a live zero versus

a dead zero is that it allows receiving instruments to quickly detect when a system failure has occurred due to a

break in the line, devices wired incorrectly, etc. Again, that is because a live zero interprets 4 mA as 0% of the

sensor’s measurement, and when current falls to any number below 4 mA then that is an indicator of a fault in the

system [5].

Page 2 of 4
WHY A 0 mA SIGNAL IS NOT PRACTICAL

3. Does Not Allow Devices to Operate


Lastly, a 0 mA signal does not provide a loop-powered, or two-wire, device with a minimum amount of

current to function. Loop-powered transmitters, displays, and other equipment require some power for operation,

which is drawn from the current flowing through the loop [6]. In a situation where a 0 mA signal exists, that

means there is no flow of current at all in the loop, thus it is unable to meet the minimum current requirements

to power up the connected devices. Even without the 0 mA problem, designing loop-powered instruments is not

easy because of power requirements and the need to maintain a low loop voltage drop; which would be even

more difficult to support at currents well below 4 mA. As a result, using a 4-20 mA signal is preferred because it

supports two-wire transmission that supplies the power needed for loop-powered devices like transmitters and

displays to operate.

Why 4-20 mA is the Industry Standard


Now that we have reviewed the reasons why a 0 mA signal is not practical, it’s easy to see why the

process control industry has preferred the 4-20 mA signal range. In addition, it provides other benefits such as

easier wiring, easier configuration, it’s more cost-effective, it’s better for traveling long distances [7], and it is less

sensitive to background electrical noise than many other signals available. Another benefit of a 4-20 mA signal is

safety. The low current is not an electrical shock hazard and it is also an easy signal to work with when designing

equipment to be intrinsically safe for hazardous areas [8]. If you would like to learn more about this and other

analog signals, then check out the ANSI/ISA-50.00.01-1975 (R2012) Compatibility of Analog Signals for Electronic

Industrial Process Instruments.

by DEL MAURICIO
Marketing Communications Specialist
Precision Digital Corporation

Page 3 of 4
WHY A 0 mA SIGNAL IS NOT PRACTICAL

References
1. Kuphaldt, Tony R. “Electrical Instrumentation Signals.” Current Signal Systems. All About Circuits.

Accessed 13 Nov 2018. allaboutcircuits.com/textbook/direct-current/chpt-9/current-signal-systems/

2. “The Science of 4 to 20 mA Current Loops – Application Note.” BAPI, Accessed 12 Nov 2018.

bapihvac.com/application-note/the-science-of-4-to-20-ma-current-loops-application-note/

3. Heath, Janet. “Why Do Industrial Sensors Measure in 4-20mA to Programmable Logic Controllers?” Analog IC

Tips. 14 Nov 2016. analogictips.com/faq-industrial-sensors-measure-4-20ma-programmable-logic-controllers/

4. Kuphaldt, Tony R. “Electrical Instrumentation Signals.” Analog and Digital Signals. All About Circuits. Accessed

13 Nov 2018. allaboutcircuits.com/textbook/direct-current/chpt-9/analog-and-digital-signals/

5. NAMUR standard NE 043

“Standardisation of the Signal Level for the Failure Information of Digital Transmitters”

6. Paonessa, Simon. “Back to Basics: Loop vs Line Power.” Precision Digital Corp. Accessed 9 Nov 2018.

predig.com/indicatorpage/back-basics-loop-vs-line-power

7. Rosenberger, Scott. “Analog Signals: 0 to 10V Vs. 4-20 mA.” Automation Insights. Accessed 13 Nov 2018.

automation-insights.blog/2010/06/22/analog-signals-0-to-10v-vs-4-20-ma/

8. Heath, Janet. “Why Do Industrial Sensors Measure in 4-20mA to Programmable Logic Controllers?” Analog IC

Tips. 14 Nov 2016. analogictips.com/faq-industrial-sensors-measure-4-20ma-programmable-logic-controllers/

PRECISION DIGITAL CORPORATION


1-800-343-1001 • [email protected]
© 2018 Precision Digital Corporation. All rights reserved. www.predig.com

You might also like