Why A 0-Ma Signal Is Not Practical
Why A 0-Ma Signal Is Not Practical
is Not Practical
by DEL MAURICIO
For decades, process instrumentation has largely relied on 4-20 mA signals to transmit process data
easily and reliably. Moreover, it is the signal of choice in the process control industry for many reasons. One in
particular is the fact that current does not degrade and it remains constant at any point in the loop, as discussed
in our review of the Fundamentals of 4-20 mA Current Loops. Therefore, it is a very efficient means to transmit
process information. In most cases, this range represents a two-point linear scale where a 4 mA signal represents
0% of a sensor’s measurement, while 20 mA indicates 100% of the measurement [1]. But, why do we use 4-20 mA
instead of 0-20 mA? That is a very common question among individuals in the industry. And the answer is simple;
a 0 mA signal is not practical. This article will discuss three reasons why a 0 mA signal is not as useful and why
Page 1 of 4
WHY A 0 mA SIGNAL IS NOT PRACTICAL
Before we delve into the reasons why a 0 mA signal is not practical, let’s get to know a little bit of the
history behind the 4-20 mA signal. Prior to the invention of electronic circuitry, process control systems used
pneumatic control signals [2]. In these systems, controllers were powered by distinct pressures of compressed
air. Eventually, air compression of 3-15 psi became the industry standard for a few reasons. First, it was very
expensive to engineer a system that would detect pressure signals under 3 psi. Second, signals below 3 psi were
unrecognizable. Lastly, using 3 psi to indicate a value of 0% measurement made it easier to identify when system
faults occurred, in other words, when the signal dropped to zero. As electronic systems made their debut in the
1950s, current became the preferred, more precise, and more efficient process control signal. Later, the industry
established the 4-20 mA signal as the standard for similar reasons as those that made 3-15 psi range an effective
device with circuitry capable of handling a signal level that reached 0 mA and remain accurate is more difficult
and expensive than limiting the design to 4-20 mA. This was especially true during the 1950s when electrical
signals like 4-20 mA had just emerged and surpassed pneumatic signals like the old 3-15 psi standard. Further,
in a circuit where 0-20 mA is used, it would be very hard to detect and distinguish low ranges. A 4-20 mA circuit
is much easier to work with because there is in fact a consistent flow of current that can be detected and used to
reliably transmit process information [3]. As a result, the industry adopted the 4-20 mA range for its cost efficiency
as well as other similar benefits that made the former 3-15 psi signal popular.
measurement of zero and a system failure in which the signal would drop to zero. The term live zero is used
to describe a loop signal where the zero value is a number higher than zero (i.e. 4 mA) [4]. The term dead zero
denotes a loop signal where the zero value is indeed zero (i.e. 0 mA). The advantage of using a live zero versus
a dead zero is that it allows receiving instruments to quickly detect when a system failure has occurred due to a
break in the line, devices wired incorrectly, etc. Again, that is because a live zero interprets 4 mA as 0% of the
sensor’s measurement, and when current falls to any number below 4 mA then that is an indicator of a fault in the
system [5].
Page 2 of 4
WHY A 0 mA SIGNAL IS NOT PRACTICAL
current to function. Loop-powered transmitters, displays, and other equipment require some power for operation,
which is drawn from the current flowing through the loop [6]. In a situation where a 0 mA signal exists, that
means there is no flow of current at all in the loop, thus it is unable to meet the minimum current requirements
to power up the connected devices. Even without the 0 mA problem, designing loop-powered instruments is not
easy because of power requirements and the need to maintain a low loop voltage drop; which would be even
more difficult to support at currents well below 4 mA. As a result, using a 4-20 mA signal is preferred because it
supports two-wire transmission that supplies the power needed for loop-powered devices like transmitters and
displays to operate.
process control industry has preferred the 4-20 mA signal range. In addition, it provides other benefits such as
easier wiring, easier configuration, it’s more cost-effective, it’s better for traveling long distances [7], and it is less
sensitive to background electrical noise than many other signals available. Another benefit of a 4-20 mA signal is
safety. The low current is not an electrical shock hazard and it is also an easy signal to work with when designing
equipment to be intrinsically safe for hazardous areas [8]. If you would like to learn more about this and other
analog signals, then check out the ANSI/ISA-50.00.01-1975 (R2012) Compatibility of Analog Signals for Electronic
by DEL MAURICIO
Marketing Communications Specialist
Precision Digital Corporation
Page 3 of 4
WHY A 0 mA SIGNAL IS NOT PRACTICAL
References
1. Kuphaldt, Tony R. “Electrical Instrumentation Signals.” Current Signal Systems. All About Circuits.
2. “The Science of 4 to 20 mA Current Loops – Application Note.” BAPI, Accessed 12 Nov 2018.
bapihvac.com/application-note/the-science-of-4-to-20-ma-current-loops-application-note/
3. Heath, Janet. “Why Do Industrial Sensors Measure in 4-20mA to Programmable Logic Controllers?” Analog IC
4. Kuphaldt, Tony R. “Electrical Instrumentation Signals.” Analog and Digital Signals. All About Circuits. Accessed
“Standardisation of the Signal Level for the Failure Information of Digital Transmitters”
6. Paonessa, Simon. “Back to Basics: Loop vs Line Power.” Precision Digital Corp. Accessed 9 Nov 2018.
predig.com/indicatorpage/back-basics-loop-vs-line-power
7. Rosenberger, Scott. “Analog Signals: 0 to 10V Vs. 4-20 mA.” Automation Insights. Accessed 13 Nov 2018.
automation-insights.blog/2010/06/22/analog-signals-0-to-10v-vs-4-20-ma/
8. Heath, Janet. “Why Do Industrial Sensors Measure in 4-20mA to Programmable Logic Controllers?” Analog IC