900ELR-2 Earth Leakage Relay: Features

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

900ELR-2 Earth Leakage Relay

Features :
1Ø - 2 Wire, 3Ø - 3 Wire & 3Ø - 4 Wire Input
!
Leakage Current Monitoring
!
True RMS Measurement
!
CBCT Connection Monitoring
!
Power ON Delay, Trip Time Delay and Recovery Time Delay
!
Adjustable Switching Hysteresis
!
Two Separate Alarm Relays with NO or NC Operation Selectable
!
Test and Reset Function via Front / Remote
!
DIN Rail Mount
!

DIN 35mm Certification :

Display Specifications Accuracy


Type Digital Current ±5% of Setting
Display Liquid Crystal Display with Backlight Power on Delay ±5% of Setting ±100ms
No. of LED 2
No. of Push Button 3 Output Specifications

No. of Relays 2
LED Indication Chart Type of Output (Relay1) 1 C/O (SPDT)
Condition 'R1' LED 'R2' LED Type of Output (Relay2) 1 C/O (SPDT)
Relay Rating NO / 5A@250V AC
Nominal Condition OFF OFF
NC / 3A@250V AC
Fault ON ON
(If programmed for Relay1)

Pre-Alarm OFF ON Auxiliary Supply Specifications


Fault ON ON
(If programmed for both Relay) Supply Voltage 230V AC
CBCT Error Blinking Blinking Frequency 45 / 65Hz
Power Consumption 3VA max
Input Specifications

Functions Environmental Specifications


Measurements Earth Leakage Current Monitoring Temperature Operating Temperature : 00 to +500
(via external CBCT) Storage Temperature : -200 to +700
Time Settings Power ON delay, Trip time delay, Humidity (non-condensing) 95% RH
Recovery timer delay
Pollution Degree
Alarm Indications Pre - warning alarm, Trip, CBCT error
For PCB 2
Latching Selectable
For Product 3
Reset Auto / Manual (Selectable)
Degree of Protection Devices IP20
Electrical Connection 1Ø - 2 wire, 3Ø - 3 wire, 3Ø - 4 wire
Current Rating
Measuring Range (RMS Value) 4mA - 30A Mechanical Specifications

Trip Settings Mounting DIN Rail


Leakage Current 10mA - 30A Weight 217gms
Pre Alarm 50 - 100% of Leakage Current Setting Screw Tightening Torque 0.5 NM
Trip Time Settings
Power ON Delay 0.5 - 99.9sec
Trip Time Delay 0 - 99.9sec
Recovery Time Delay 0 - 99.9sec
Response Time < 30ms (If trip current 5 x set value)
< 50ms (If trip current 1 x set value)
Hysteresis
Hysteresis 5 to 40%
Resolution
Current 0.1mA, 1mA, 0.01A, 0.1A
(Depends on trip Setting)

www.selec.com 1
900ELR-2 Earth Leakage Relay

Dimensions Compliance

Applicable EMI / EMC Standards


35mm
Product Standard : IEC 60947-2
Category Reference Standards Testing Level

Conducted Emissions IEC 61000-6-3 Class-A

67.50mm
Conducted RF Immunity IEC 61000-4-6 Class-A
90mm

45mm
90mm

Electrical Fast Transient IEC 61000-4-4 Class-B

Electrostatic Discharge IEC 61000-4-2 Class-B

Radiated Emission CISPR-22 Class-A


70.50mm
Radiated Susceptibility IEC 61000-4-3 Class-A

Surge IEC 61000-4-5 Class-B

Terminal Connection High Voltage Test IEC 61010-1 Clause 6.8

Resistance To Heat Test IEC 61010-1 Clause 10.5


RELAY 2

25 28 26
Single Fault Test IEC 61010-1 Clause 4.4
COM2 NO2 NC2 Temperature Rise Test IEC 61010-1 Clause 10

R T C
Ordering Information
TEST
Product Code Supply Voltage Certification
RESET
900ELR-2-230V-CE 230V AC

Accessories
S1 S2 N
Product Code Inner Diameter Turns Ratio
CBCT

L L1 CBCT-35-1 35mm 1000:1


Auxiliary Supply

O L2
A L3
D N CBCT-70-1 70mm 1000:1
E
CBCT-120-1 120mm 1000:1
RELAY 1

16 18 15 L
CBCT-210-1 210mm 1000:1
NC1 NO1 COM1
CBCT-310-1 310mm 1000:1

www.selec.com 2