Electrical Engineering Department
Electrical Engineering Department
Many RL circuits contain multiple resistors and inductors that are in series. The total
inductive reactance of a circuit is determined in much the same way as total circuit
resistance. When inductors are in series, the total inductive reactance (XLT) is the sum of
the individual reactances.
XLT = XL1 + XL2 + XL3 + …
The total inductive reactance increases as the number of inductors in series
increases. The result is lower circuit and higher circuit impedance. As in circuits with
resistors only, the current flowing through each component in a series RL circuit is the
same. Figure 2.1-1 shows a series RL circuit.
Circuit impedance (Z) is the square root of the sum of the squares of the total
resistance (RT) and the total inductive resistance (XLT). For the circuit in Figure 2.1-1, Z is
determined as follows.
Z= √ (RT + X ¿ )
2 2
Z= √ (1700 +25002 )
2
Z= √ ( 9 , 140 ,000 )
Z= 3, 023 Ω
To applied voltage (Vac), Z, and Ohm’s law is then used to determine the circuit
current.
I-T = V-ac/Z
I-T = 8/3023
I-T = 0.00265 mApk-pk (2.65 mApk-pk)
Voltage drops across individual components are determined from the circuit
current, Ohm’s law, and the resistance or reactance of the individual component. For
example, the voltage drop across L1 (V L1) in Figure 2.1-1 is as shown.
VL1 = I x XL1
VL1 = 0.00265 x 1000
VL1 = 2.65 Vpk-pk
In circuits with resistors only, the sum of the voltage drop across each resistor
equals the applied voltage. In RL circuits, however, the applied voltage does not equal
the sum of the voltage drops, but the square root of the sum of the squares of the voltage
drops. For the circuit in Figure 2.1-1, Vac is determined by the following formula.
Figure 2.1-2 shows this relationship in a phasor diagram. If the voltage drops in
the circuit in Figure 2.1-1 were added together, the sum would be greater than the applied
voltage (Vac).
1.5 Materials/Equipment
1- F. A. C. E. T. Base Unit
1- AC 1 FNDAMENTALS Circuit Board
2- Power supply, 15 Vdc
1- Oscilloscope, dual trace
1- Multimeter
Figure 1. Title
1.7 Procedure/s
PROCEDURE A:
1. Turn off the power sources. Insert the AC 1 FUNDAMENTALS circuit board.
2. If your generator does not have an output impedance of 50Ω, you must use the Generator
Buffer, install on on the AC 1 FUNDAMENTALS circuit board.
4. Locate the DC/AC waveforms circuit board. Use a two-post connector to connect the
generator source to resistor R1. Does the circuit indicate that an external generator supply is
required? ________________________________________
5. Use terminal posts to connect the generator leads, (use the Generator Buffer if necessary) to
the DC/AC Waveforms circuit block. Turn on the generator. Set up the oscilloscope for basic
operation (refer to Procedure A of EXERCISE 1.1). Use terminal posts to connect the channel 1
x10 probe across R. Set the generator function control for a sine wave output, and adjust the
amplitude control to about midpoint. Set the generator frequency to approximately 1.5 kHz.
6. Set the channel 1 vertical coupling to AC, and adjust the attenuator and time base controls to
produce a display similar to the one in Figure 1.2-3.
7. Increase the generator frequency control. Do the number of cycles displayed on the
oscilloscope increase or decrease as the frequency is increased?
________________________________.
9. Turn down the intensity on the oscilloscope, and remove all connections from the DC/AC
waveforms circuit block.
B. GENERATOR IMPEDANCE:
At the beginning of this exercise, you found that the generator output impedance (Rs) and
the circuit load (RL) form a voltage divider. Recall from studying dc circuits that a voltage
divider consisting of two equal resistances divides the source voltage in half. This knowledge
can be used to measure the output impedance of a generator. In this procedure, you will refer to
Figure 1.2-4 and adjust RL so that the loaded generator output is half the open circuit generator
output. At this point, RL and Rs will be equal. Measuring the value of RL with a multimeter will
then give you the value of Rs.
PROCEDURE B:
2. Connect the channel 1 x10 probe to the generator output (if you are using the Generator
Buffer, connect the probe to the Generator Buffer output).
3. Turn up the oscilloscope intensity to about midrange, and apply the generator output directly
to the channel 1 x 10 probe. Adjust the generator amplitude to produce a sine wave that is 6
vertical divisions high. Does this voltage represent the open circuit or loaded output of the
generator? ________________________________
4. Locate the GENERATOR IMPEDANCE circuit block. Turn potentiometer R on the generator
impedance circuit block fully clockwise. Connect the generator to the GENERATOR
____________________.
6. Disconnect the generator and the oscilloscope probe from the GENERATOR IMPEDANCE
circuit block.
7. Measure and record the combined resistance of R1 and R2 (RL) with a multimeter. Does RL
equal the output impedance of the generator? _____________________
8. Turn off power source, and remove all circuit board connections.
REVIEW QUESTIONS:
1. The controls that adjust frequency on an ac waveform generator are the frequency and
1. Range controls
2. Amplitude controls
3. Function controls
4. Vertical control
4. The load (RL) equals the output impedance of the generator (Rs) when the
5. Which symbol in the F.A. C. E. T. program indicates that an external generator connection is
required?
1.8.2 Calculations
6.8.5 Rating
Score
Pre-initiation Initiating Implementing Refining
Sustaining
Criteria Member1 Member2
1 2 3 4 Member3 Member
5 Member5
Total Score