2017 Failure-Rates PDF
2017 Failure-Rates PDF
2017 Failure-Rates PDF
2. Figure 1 shows the different types of information that are available in this document. For the full
structure, see Figure 2. This introductory section also outlines a framework used in CEMHD5 to
keep references pertaining to failure rates and a system for recording the use of non-generic
failure rates used in particular cases.
3. The first section covers failure rates. CEMHD5 currently has established failure rates or has
some information for most of the items. The items on the diagram in Figure 2 contain a failure
rate value(s) and a brief derivation. For rates that have ranges the derivation also contains a
brief guide on what factors may affect the value.
4. The second section (see page 87) contains information on event data. The derivation of the
rates to be used and how to use them are described.
5. The third section (see page 98) covers human factors. This aim of this section is to help non-
human factors specialists determine whether the use of human reliability analysis, and
associated values, is adequate or not.
Failure rate and event data
Failure rate
FR
Containers
Vessels Components Pipework Pipelines Tankers Ship Freight FR4.1
FR1.1 FR1.2 FR1.3 FR3.1 FR3.2 FR3.3
IBCs
Hard Arms Rail tankers FR4.1.4
FR1.2.4 Compressors FR3.2.3
LNG LOX
FR1.1.2.1 FR1.1.2.2 FR3.1.4
Portable containers
FR4.1.5
Flanges and gaskets
FR1.2.5
Pressure vessels
FR1.1.3
Small containers
FR4.1.6
Chlorine pressure
LPG pressure vessels Spherical vessels
vessels
FR1.1.3.2 FR1.1.3.3
FR1.1.3.1
Chemical reactors
FR1.1.4
Page 2 of 102
PCAG chp_6K Version 14 – 06/11/17
Failure Rates
8. When non-generic values are used in CEMHD5 assessments they should be justified and the
reasoning behind their derivation recorded within an FR note. If the assessment case is
panelled for peer review the relevant FR note should be presented with the case so that
CEMHD5 inspectors can endorse the value(s) used. The Topic Specialist will place completed
FR notes on TRIM and a note made alongside the appropriate generic failure rate.
Date:
Request:
Advice:
Basis of Advice:
Associated Documents:
Signed: Date:
Page 3 of 102
PCAG chp_6K Version 14 – 06/11/17
Item FR 1 Mechanical
Page 4 of 102
PCAG chp_6K Version 14 – 06/11/17
10. Failure rates for vessels are split into four categories that are further subdivided as shown in
Figure 3 below. These vessels refer to fixed storage. Moveable storage (e.g. drums) are
considered under Item FR 4.
Vessels
FR1.1
Ambient temperature
and pressure vessels
FR1.1.1
Refrigerated vessels
FR1.1.2
LNG LOX
FR1.1.2.1 FR1.1.2.2
Chemical
Pressure reactors
vessels
FR1.1.4
FR1.1.3
Chemical reactors
FR1.1.4
Page 5 of 102
PCAG chp_6K Version 14 – 06/11/17
11. Ambient temperature and pressure vessels are divided as follows. Ambient pressure may be
extended to cover vessels at slightly elevated pressure.
Page 6 of 102
PCAG chp_6K Version 14 – 06/11/17
-4
Major 1 x 10
-3
Minor 2.5 x 10
-3
Roof 2 x 10
RELEASE SIZES
3
Hole diameters for Tank volumes (m )
Category >12000 12000 – 4000 4000 - 450
Major 1000 mm 750 mm 500 mm
Minor 300 mm 225 mm 150 mm
Derivation
12. The failure rates apply to fixed position, single walled vessels with a capacity greater than
450m3, which operate at ambient temperature and pressure.
13. Roof failures includes all failures of the roof and does not include liquid pooling on the ground.
For vessels that are storing flammable liquids, this could lead to a flammable atmosphere being
formed and possible ignition and escalation. For tanks that store toxic chemicals a toxic cloud
could be formed. Most atmospheric storage tanks are specifically designed so that the roof wall
seam will preferentially fail hopefully mitigating the effects of an incident.
14. The above rates are derived from historical data in work carried out by Glossop (RAS/01/06).
They are applicable to large flat-bottomed metal storage vessels where flammable liquids are
stored at atmospheric temperature and pressure. These values are not directly applicable to
vessels storing non-flammable liquids because a different set of failure modes is relevant.
However, they may be used as a basis for such vessels – seek advice from the Topic Specialist.
References
Title Author Date Comments
Failure Rates for Atmospheric Storage Tanks M Glossop 2001
for Land Use Planning. HSL internal report
RAS/01/06.
Page 7 of 102
PCAG chp_6K Version 14 – 06/11/17
FR No Application Comments
FR128 Large mounded kerosene tanks shrouded in concrete Rates are provided that give
credit for the concrete shroud
Page 8 of 102
PCAG chp_6K Version 14 – 06/11/17
16. Small and Medium Atmospheric Tanks (SMATs) have a capacity of less than 450m 3, and can
be made of steel or plastic.
17. Large releases are defined as a rapid loss of most or all contents e.g. large hole in a vessel
leaking over several minutes.
18. Small releases are defined as smaller or much slower loss of contents e.g. through a small leak
over 30 minutes.
19. FR117_2 defines hole sizes for tanks of unknown size (large holes are defined as 250 mm
diameter and small holes as 75 mm diameter).
20. To calculate the hole sizes when the size of the tank is known, assume that a large hole would
empty the tank in 5 minutes and a small hole would empty the tank in 30 minutes. What this
equates to in terms of volumetric flow per second (tank volume/ time in seconds) can then be
calculated and, from this, using the substance density, the mass flow in kg/s can be obtained.
Using STREAM, it is then possible to determine what hole sizes would result in the calculated
mass flow rates for small and large holes. The calculated hole sizes should be used unless they
are larger than those specified in paragraph 19 (250/75mm), in which case the default 250mm
and 75mm holes should be chosen.
Derivation
21. Failure rates are taken from RSU/08/14 by Brownless and Keeley. The rates were derived by
fault tree analysis. The analysis suggested that the failure rates are sensitive to whether the
substance stored is flammable or explosive and if so, whether the vessel has a weak roof seam
(giving a preferential failure mode under pressure build up). The results also suggested that for
catastrophic failures and large releases, corrosion is an important cause of failure, with spills
(e.g. due to pipe or valve failure) and overpressure being important for smaller releases. Given
the dominance of corrosion as a causal factor for catastrophic and large releases, consideration
should be given to the applicability of the derived failure rates when considering vessels of
plastic construction.
References
Title Author Date Comments
Review of Failure Rates for Small G Brownless and D 2008
Atmospheric Pressure Storage Tanks. HSL Keeley
internal report RSU/08/14.
Page 9 of 102
PCAG chp_6K Version 14 – 06/11/17
FR No Application Comments
3
117_2 SMATs, fixed tank up to 400-450m , plastic or metal and range of Revision to FR117. Provides
designs. generic hole sizes for tanks of
unknown capacity.
Page 10 of 102
PCAG chp_6K Version 14 – 06/11/17
23. Currently there are no agreed HSE failure rates for this item. For small tanks, refer to Item FR
1.1.1.2 which also covers plastic tanks. Otherwise, see failure rate advice notes for specific
failure rates, or refer to the Topic Specialist.
FR No Application Comments
101 HDPE spiral wound vertical atmospheric tank for HF acid. Catastrophic, 50 mm and 13
mm diameter hole failure rates
provided.
79 25te plastic wound, double skin vessels and half height containment. Catastrophic, 50 mm, 25 mm,
13 mm and 6 mm diameter hole
failure rates provided.
32 Allibert 5000 (PE) bunded polyethylene tank for HF acid. Failure rates are provided for
the catastrophic failure of the
inner tank, and also for the
inner tank and bund tank
combined.
Page 11 of 102
PCAG chp_6K Version 14 – 06/11/17
RELEASE SIZES
3
Hole diameters for Tank volumes (m )
Category >12000 12000 – 4000 4000 - 450
Major 1000 mm 750 mm 500 mm
Minor 300 mm 225 mm 150 mm
Derivation
25. All rates are based on the report by J.Gould, RAS/00/10. For the purposes of applying generic
failure rates the various vessel designs have been placed into three categories:
1 Single wall tanks, where there is no outer containment designed to hold the
cryogenic liquid or vapour.
2 Double walled tanks, where on failure of the inner wall the outer wall is
designed to retain the liquid but not the vapour.
3 Full containment tanks, where the outer wall is designed to retain the liquid and
the vapour.
26. A review of literature was performed to identify the failure rates for single walled vessels. The
failure rates derived are based largely on experience from ammonia, LPG and LNG vessels of
around 15000m3. Event trees were produced using expert judgement to take into account the
benefit of double walled tanks in containing releases from the inner tank. No credit should be
given if the outer wall has not been designed to withstand the very low temperatures of the
refrigerated contents.
27. The failure rates of the inner tank were not reduced to take account of any protection the outer
wall and roof might provide, which could be significant for reinforced concrete outer
containment. The review found no record of failures of LNG vessels so it is arguable that the
generic figures should be reduced when applied to LNG facilities. Specific failure rates for
double walled LNG tanks are derived in Item FR 1.1.2.1. The failure rates for double walled
Page 12 of 102
PCAG chp_6K Version 14 – 06/11/17
tanks should be used for full containment tanks, although the failure rate for the release of
vapour only should be set to zero.
28. The rates quoted do not include failures due to overpressure as a result of the addition of a
lower boiling point material to one stored at a higher temperature (e.g. the addition of propane
to a butane storage tank). If this is considered a credible scenario the advice of the Topic
Specialist should be sought. Failure rates for semi-refrigerated vessels will be based on those
for pressure vessels and the advice of the Topic Specialist should be sought.
29. BS 7777 states that refrigerated storage vessels built up to the 1970’s were predominantly
single containment tanks. It is also still the practice that liquid oxygen, liquid nitrogen, and liquid
argon are stored in single containment tanks. If a double wall is mentioned in regard to these
vessels its function is generally to support the insulation and the roof, and not to contain the
refrigerated liquid. Also, where other materials are stored refer to the Topic Specialist for advice
on the applicability of these rates.
References
Title Author Date Comments
New failure rates for land use planning QRA. J Gould May
HSL internal report RAS/00/10. 2000
BS 7777: Flat-bottomed, vertical, cylindrical British Standards 1993
storage tanks for low temperature service. Institute
FR No Application Comments
105 Cryogenic ethylene (pressurised, semi-refrigerated), 20 te, temperature - Refrigerated pressure vessel.
53°C, pressure 12 barg. BLEVE frequency given.
89 Liquefied HCl. Refrigerated pressure vessel.
Catastrophic failure rate given.
84 Single skinned LPG tanks. Catastrophic failure rate, 2000
mm, 1000 mm and 300 mm
diameter holes and vapour
release failure rates are
provided.
19 Double skinned 66000 l liquid hydrogen vessels. Working pressure of Catastrophic, 50 mm, 25 mm,
inner tank is 12 barg although normal storage pressure is 4-5 barg. 13 mm and 6 mm diameter hole
failure rates are provided.
Bibliography
31. These references represent other sources of information on the subject.
Page 13 of 102
PCAG chp_6K Version 14 – 06/11/17
Page 14 of 102
PCAG chp_6K Version 14 – 06/11/17
-8
Catastrophic 5 x 10
-6
Major failure 1 x 10
-6
Minor failure 3 x 10
-5
Vapour release 4 x 10
RELEASE SIZES
3
Hole diameters for Tank volumes (m )
Category >12000 12000 – 4000 4000 - 450
Major 1000 mm 750 mm 500 mm
Minor 300 mm 225 mm 150 mm
Derivation
32. The failure rates above are taken from RAS/06/05 by Keeley.
33. RAS/06/05 reviews the basis for refrigerated vessel failure rates in general and considers their
applicability to LNG storage. The report recommends that the double wall vessel failure rates for
LNG tanks should be reduced from the generic values in Item FR 1.1.2.
34. The failure rates for single walled LNG tanks are unchanged and the generic values in Item FR
1.1.2 should be used. The failure rates for double walled tanks should be used for full
containment tanks, although the failure rate for the release of vapour only should be set to zero.
35. Where single walled LNG tanks have reinforced concrete high collared bunds they may be
regarded as equivalent to double walled vessels and the double wall failure rates shown above
may be used in assessments.
References
Title Author Date Comments
Review of LNG storage tank failure rates. HSL D Keeley 2006
internal report RAS/06/05. Confidential, not in
the public domain.
FR No Application Comments
FR126 Failure rates for LNG tanks with reinforced concrete high collar bunds Considered to be equivalent to
double wall tanks
Page 15 of 102
PCAG chp_6K Version 14 – 06/11/17
RELEASE SIZES
3
Hole diameters for tank volumes (m )
Category 4000 – 2000 200 – <2000
Major 400 mm 250 mm
Minor 120 mm 75 mm
37. Catastrophic failure is modelled as the instantaneous loss of vessel contents forming a
vaporising pool.
38. A typical cluster tank usually consists of 5 or 7 smaller pressure vessels located inside a
common large skin, which is used to contain the insulation material. The outer vessel is not
designed to contain the vapour or liquid in the event of vessel failure.
Derivation
39. The partitioning between major and minor releases follows that for refrigerated ambient
pressure vessels (Item FR 1.1.2). Scaling is applied to the tank size ranges used for refrigerated
ambient pressure vessels to obtain the hole sizes and tank size ranges shown above. The
values for single walled vessels for major and minor failures for refrigerated ambient pressure
vessels are then used.
40. The cluster tank failure rates, excluding minor failures, are taken from FR 9.
41. The major failure rate for cluster tanks were obtained by summing the failure rates for the larger
two hole sizes (50 mm and 25 mm) for pressure vessels (Item FR 1.1.3). Similarly, the minor
Page 16 of 102
PCAG chp_6K Version 14 – 06/11/17
failure rate for cluster tanks was calculated from the summation of the failure rates for the two
smaller hole sizes (13 mm and 6 mm) from pressure vessels (Item FR 1.1.3).
References
Title Author Date Comments
Revised LOX risk assessment methodology – G Tickle, AEA 14/01/03 Quotes the rates adopted by panel
HSE Panel Paper. Confidential, not in the Technology on 17 July 2001, which includes the
public domain. single walled catastrophic failure
rate.
LOX methodology modifications to address G Tickle, AEA 22/03/04 This introduces the release sizes,
th
comments from 19 January 2004 MSDU Technology modifies the cluster tank minor
Panel meeting – HSE Panel Paper. failure rate and details its
Confidential, not in the public domain. calculation along with that of major
failures in cluster tanks. Major and
minor failures for single walled
vessels are also discussed.
FR No Application Comments
55 Pressure vessels for LOX storage, 35te, operating pressure Catastrophic, 50 mm and 25
17 bar. Vertical bullets with liquid off-take feeding an air mm diameter hole failure rates
warmed vaporiser delivering oxygen gas under pressure of provided.
around 10 bar.
53 66te LOX vacuum insulated tanks. Uses FR19 which derived
catastrophic failure rates and
rates for holes of size 50 mm,
25 mm, 13 mm and 6 mm.
9 LOX cluster tanks and internal explosions. LOX cluster tanks and internal
explosions. Catastrophic and
major failure rates are derived.
Page 17 of 102
PCAG chp_6K Version 14 – 06/11/17
43. Failure rates for pressure vessels are further subdivided into those for chlorine vessels, Item FR
1.1.3.1, LPG vessels, Item FR 1.1.3.2, and spherical vessels, Item FR 1.1.3.3. For general
pressure vessels the rates below, which are based on those for chlorine vessels, should be
used as a starting point.
-6
25 mm diameter hole 5 x 10
-5
13 mm diameter hole 1 x 10
-5
6 mm diameter hole 4 x 10
Derivation
44. The cold catastrophic and hole failure rates are taken from the MHAU handbook (now
archived). These are derived in the Chlorine Siting Policy Colloquium and are applicable to
chlorine pressure vessels in a typical water treatment plant. Although they are not applicable to
all types of pressure vessels the values are a good starting point when trying to derive failure
rates for vessels in other applications. The value chosen for catastrophic failure should normally
be 2 chances per million (cpm), assuming that the vessel conforms to BS5500 or an equivalent
standard and that there is good compliance with the HSW etc. act (1974), unless there are site-
specific factors indicating that a higher rate is appropriate (e.g. semi refrigerated vessels
[cryogenic pressure vessels]).
45. The values above take the effects of external hazards into account at a rate of 1 x 10 -6 per
vessel year for catastrophic failures. If site specific conditions are known to result in a higher
external hazard rate then the overall failure rate used should be adjusted as necessary.
Examples of external hazards are shown in Figure 4.
46. Domino effects on adjacent tanks are possible. Assuming a split along a longitudinal seam and
that 50% of such splits are orientated such that the vessel is driven into an adjacent one, then
the rate of impact on a second vessel following a catastrophic failure would be 10 -6. Not all of
these impacts would cause catastrophic failure of the second vessel, however. If it is further
assumed that 25% of the impacts cause catastrophic failure, this gives a total frequency of 1/8
of the catastrophic failure rate. This is very much an estimate and, if the scenario proves to be
dominant in the risk assessment, further advice should be sought.
47. A review of pressure vessel failure rates was carried out in 2006. The outcome of the review
was to recommend that HSE continue to use the current values within PCAG for pressure
Page 18 of 102
PCAG chp_6K Version 14 – 06/11/17
vessel failure rates unless new information suggests otherwise. This work is documented in a
HSL report by Keeley and Prinja, RAS/06/04.
48. The HSE pressure vessel failure rates have also recently been reviewed by Nussey (2006). The
review concluded that the HSE failure frequencies for pressure vessels continue to be soundly
based and justified.
References
Title Author Date Comments
Components Failure Rates. Confidential, E M Pape 1985 From the Chlorine Siting Policy
not in the public domain. Colloquium
Pressure Vessel Failure Rates – A D Keeley and A 2006
Summary Report. HSL internal report Prinja
RAS/06/04. Confidential, not in the public
domain.
FR 87. Confidential, not in the public S C Pointer 2005 Domino failures of adjacent tanks
domain.
FR No Application Comments
139 LNG stored in Vacuum Insulated Tanks (VITs) Catastrophic failure rate given.
135 LNG storage tank BLEVE frequency Use LPG BLEVE rate.
134 Glass lined bromine pressure vessel Catastrophic failure rate given.
105 Cryogenic ethylene (pressurised, semi-refrigerated), 20 te. Temperature BLEVE frequency given.
-53°C, pressure 12 barg.
89 Liquefied HCl, 13.5 bar g and temperature of -40°C. Catastrophic failure rate
produced.
63 High pressure gas bullets. Cold and hot catastrophic, full
manhole, 50 mm and 25 mm
diameter hole failure rates
produced.
55 Pressure vessels for LOX storage, 35te, operating pressure 17 bar. Catastrophic failures, 50 mm
Vertical bullets with liquid off-take feeding an air warmed vaporiser and 25 mm diameter hole
delivering oxygen gas under pressure of around 10 bar. failure rates produced.
19 Double skinned 66000 l liquid hydrogen vessels. Catastrophic failures, 50 mm,
25 mm, 13 mm and 6 mm
holes. Working pressure of
inner tank is 12 barg although
normal storage pressure is 4-5
barg.
14 29.6 te fixed bromine tanks. Catastrophic failure rate
produced.
Page 19 of 102
PCAG chp_6K Version 14 – 06/11/17
Bibliography
50. These references represent other sources of information on the subject.
Page 20 of 102
PCAG chp_6K Version 14 – 06/11/17
Page 21 of 102
PCAG chp_6K Version 14 – 06/11/17
Earthquake
Flooding - see ED 2
Lightning - see ED 3
Ignition probabilities
Vehicle (dependent on
degree of protection,
Part vessel failure movement of site vehicles,
proximity of roads and
railway)
External impacts
Aircraft - see ED 1
Collapse of overhead
structures, e.g. due to wind
or fire
Page 22 of 102
PCAG chp_6K Version 14 – 06/11/17
-6
25 mm diameter hole 5 x 10
-5
13 mm diameter hole 1 x 10
-5
6 mm diameter hole 4 x 10
Derivation
51. The cold catastrophic failure rates are taken from the MHAU handbook (now archived). These
are derived in the Chlorine Siting Policy Colloquium and are applicable to chlorine pressure
vessels. The above values have been adopted as the generic failure rates for pressure vessels
for use within RISKAT.
52. The catastrophic failure rate should be taken as 2 x 10 -6 per vessel yr unless site specific factors
are known to increase that value.
53. The values above take the effects of external hazards into account at a rate of 1 x 10 -6 per
vessel year for catastrophic failures. If site specific conditions are known to result in a higher
external hazard rate then the overall failure rate used should be adjusted as necessary.
Examples of external hazards are shown in Figure 4.
54. A review of pressure vessel failure rates was carried out in 2006. The outcome of the review
was to recommend that HSE continue to use the current values within PCAG for pressure
vessel failure rates unless new information suggests otherwise. This work is documented in a
HSL report by Keeley and Prinja, RAS/06/04.
55. The HSE pressure vessel failure rates have also recently been reviewed by Nussey (2006). The
review concluded that the HSE failure frequencies for pressure vessels continue to be soundly
based and justified.
References
Title Author Date Comments
Components Failure Rates. Confidential, E M Pape 1985 From the Chlorine Siting Policy
not in the public domain. Colloquium
Pressure Vessel Failure Rates – A D Keeley and A 2006
Summary Report. HSL internal report Prinja
RAS/06/04. Confidential, not in the public
domain.
Page 23 of 102
PCAG chp_6K Version 14 – 06/11/17
FR No Application Comments
No specific advice issued.
Bibliography
57. These references represent other sources of information on the subject.
Page 24 of 102
PCAG chp_6K Version 14 – 06/11/17
-6
50 mm diameter hole 5 x 10
-6
25 mm diameter hole 5 x 10
-5
13 mm diameter hole 1 x 10
Derivation
58. The cold catastrophic and BLEVE failure rates are taken from the MHAU handbook (now
archived). These are standard failure rates for use within RISKAT.
59. The value for catastrophic failure is based on a survey carried out in 1983 by the LPGTA (now
renamed to UKLPG) on LPG releases and vessel populations in the UK. From calculations by
E.M. Pape in the file MHAU/PR/6003/94 the survey gave 280,000 vessel years with no
catastrophic failures. This gave a failure rate of <2.5 x 10-6 per vessel yr. This survey has been
updated assuming no failures up to 1992, which gives a failure rate of 9.4 x 10 -7 per vessel yr.
This failure rate is derived from LPG tanks most of which (95%) are less than 1 te and larger
vessels may have different failure rates. Taking this into account, and the generic failure rates
used within HSE, the value of 2 x 10-6 continues to be used.
60. The cold catastrophic failure rate was reviewed by Nussey in 2006 and the conclusion was that
the value of 2 cpm was still reasonable. The review also concluded that the HSE failure
frequencies for pressure vessels continue to be soundly based and justified.
61. The mounding or burying of LPG tanks gives protection from fire engulfment and significantly
reduces the possibility of a BLEVE. The mounding or burying also changes the likelihood of the
possible causes of cold failure.
62. Where the LPG tank is fully mounded or completely buried, the BLEVE frequency can be taken
as zero. Partially mounded tanks or other tanks that have part of the surface exposed are
assigned the standard BLEVE frequency. In all cases the cold catastrophic failure frequency
and the vessel hole rates remain unchanged unless demonstrated otherwise.
63. The values above take the effects of external hazards into account at a rate of 1 x 10 -6 per
vessel year for catastrophic failures. If site specific conditions are known to result in a higher
external hazard rate then the overall failure rate used should be adjusted as necessary.
Examples of external hazards are shown in Figure 4.
64. A review of pressure vessel failure rates was carried out in 2006. The outcome of the review
was to recommend that HSE continue to use the current values within PCAG for pressure
vessel failure rates unless new information suggests otherwise. This work is documented in a
HSL report by Keeley and Prinja, RAS/06/04.
Page 25 of 102
PCAG chp_6K Version 14 – 06/11/17
References
Title Author Date Comments
Pressure Vessel Failure Rates – A D Keeley and A 2006
Summary Report. HSL internal report Prinja
RAS/06/04. Confidential, not in the public
domain.
FR No Application Comments
No specific advice issued.
Bibliography
66. These references represent other sources of information on the subject.
Page 26 of 102
PCAG chp_6K Version 14 – 06/11/17
public domain. Tolchard failure of LPG pressure vessels.
Guidelines for the preparation and review of BP CIMAH May 93 Quotes value for hot failure
-6
a report under the CIMAH regulations. Liaisons Group (BLEVE) of 26 x 10 per yr,
Confidential, not in the public domain. probably for an LPG vessel.
Page 27 of 102
PCAG chp_6K Version 14 – 06/11/17
-6
25 mm diameter hole 5 x 10
-5
13 mm diameter hole 1 x 10
-5
6 mm diameter hole 4 x 10
Derivation
67. The failure rates are taken from RSU/SR/2010/02 by Z Chaplin.
68. No evidence was found in the literature to suggest that the failure rates for spherical vessels
would differ significantly from those used for pressure vessels.
69. However, it was considered that the supporting legs of spherical vessels provide an additional
failure mode for this type of vessel, although there was no firm evidence in the literature.
70. It is therefore recommended that a cautious approach is taken and the median value for
catastrophic failure is used.
References
Title Author Date Comments
Failure rates for spherical tanks. HSL short Z Chaplin 2010
report RSU/SR/2010/02. Confidential, not
in the public domain.
FR No Application Comments
No specific advice issued.
Page 28 of 102
PCAG chp_6K Version 14 – 06/11/17
-6
25 mm diameter hole 5 x 10
-5
13 mm diameter hole 1 x 10
-5
6 mm diameter hole 4 x 10
Derivation
72. The catastrophic failure rate is taken from the panel paper by P Betteridge (Panel Paper 1999-
003) and has been reviewed by Chaplin (MSU/LET/2013/37/1). The value is for pressurised
chemical reactors, and includes both batch and continuous, but not non-metallic reactors or
small lab-scale reactors. It includes both reactors that are capable of thermal runaway and
those that are not. The main assumption is that both pressure vessels and reactor vessels will
share a set of common failure modes and that the failure rate due to these will be the same for
both types of vessel. Both types of vessel will also have a set of failure modes that are unique to
that type of vessel.
73. The values proposed for less than catastrophic failure are those for chlorine storage vessels. To
take into account the number of large flanges often found on reactors, each flange should be
given a failure rate of 3 x 10-6 per year with a hole size equivalent to assuming a loss of a
segment of gasket between two bolts. The value obtained should then be added to the
appropriate value from the table above to give the net failure rate. This would mean that for a
reactor with four 8-bolt 200 mm flanges, the failure rate would be 1.2 x 10-5 per reactor year with
an equivalent hole size of 13 mm for a 2 mm gasket.
References
Title Author Date Comments
HSE Panel Paper 1999-003. (Confidential, not P. Betteridge 1999
in the public domain)
Chemical Reactor Failure Rates Z. Chaplin 2013
MSU/LET/2013/37/1. Confidential, not in the
public domain.
Page 29 of 102
PCAG chp_6K Version 14 – 06/11/17
FR No Application Comments
No specific advice issued.
Page 30 of 102
PCAG chp_6K Version 14 – 06/11/17
Spray Releases
76. Spray releases covers a specific type of leak that occurs at different kinds of plant and
pipework. Spray releases are normally only considered when assessing risks from toxic
substances that would otherwise have very small hazard ranges because of their low volatility.
77. A spray release is defined as a release where the spray from a hole is broken into droplets
small enough to not rain out, i.e. it is atomised. It could occur in fixed pipework or in a flexible
hose connection (say between a tanker and a storage vessel). Spray releases also arise from
plant such as pumps and valves, particularly around shafts and drives. In order for a spray
release to occur, two conditions are required:
78. Only crack-like holes, (i.e. with considerable length) need be considered, because point defects
of 50 m size will have negligible flow rate. Clearly, these small breaches with specific geometry
are a small subset of the range of failures that could occur. No data is available directly from
industry on spray frequencies. Frequencies were estimated by considering sprays as a subset
of all small holes. Data for small holes in the type of plant that might give rise to sprays were
obtained from a variety of sources. The judgements used in deriving the spray release figures
were agreed in an MSDU Panel Paper of 4 February 2004, entitled ‘Spray Releases’ by P J
Buckley (Confidential, not in the public domain). The paper was presented at a panel meeting
on 16 February 2004.
79. Spray releases frequencies are given for Items FR 1.2.1- FR 1.2.3 and FR 1.2.5.
Page 31 of 102
PCAG chp_6K Version 14 – 06/11/17
Derivation
80. All rates are taken from the MHAU handbook volume 3 (now archived). These values are
derived in the Components Failure Rates paper, which is a comparison of 12 sources of failure
rates derived elsewhere. The values are for chlorine duty although the review included LPG,
petrochemical, steam/water, nuclear and other data.
81. The failure to close manual chlorine valves is given as 1 x 10 -4 per demand not including human
error. Manual valves are valves that have to be closed in an emergency by the operator taking
suitable precautions, e.g. donning a SCBA (self-contained breathing apparatus).
82. A ROSOV is a remotely operated shut-off valve that allows rapid remote isolation of significant
processes. The failure to close a ROSOV is given as 3 x 10-2 per demand.
83. An ASOV (Automatic shut-off valve) is a valve normally held open and is closed by detection
equipment with no need for manual intervention. The failure to close for ASOVs is given as 1 x
10-2 per demand. The value may be higher if gas detection equipment is used as opposed to a
pressure drop system.
84. Excess flow valves (XSFV) have a failure rate of 1.3 x 10-2 per demand if tested every year and
an order of magnitude higher if tested every 10 years.
85. Where human error is likely to be a significant factor the advice of HID Human Factors
Specialists should be sought. The advice of Control and Instrumentation Specialists should also
be sought where there is a need for a site-specific assessment.
References
Title Author Date Comments
Components Failure Rates. Confidential, not E M Pape 1985 From the Chlorine Siting Policy
in the public domain. Colloquium
Page 32 of 102
PCAG chp_6K Version 14 – 06/11/17
FR No Application Comments
49 Relief valve for natural gas. Rate per year or per demand.
Bibliography
87. These references represent other sources of information on the subject.
Page 33 of 102
PCAG chp_6K Version 14 – 06/11/17
Page 34 of 102
PCAG chp_6K Version 14 – 06/11/17
Page 35 of 102
PCAG chp_6K Version 14 – 06/11/17
Derivation
88. All rates are taken from the MHAU handbook volume 3 (now archived). The failure rate refers to
the catastrophic failure of the pump casing giving a release rate equivalent to a full bore leak
from the pipework.
References
Title Author Date Comments
Components Failure Rates. Confidential, not E M Pape 1985 From the Chlorine Siting Policy
in the public domain. Colloquium
FR No Values Application
No specific advice
Bibliography
90. These references represent other sources of information on the subject.
Page 36 of 102
PCAG chp_6K Version 14 – 06/11/17
Page 37 of 102
PCAG chp_6K Version 14 – 06/11/17
Page 38 of 102
PCAG chp_6K Version 14 – 06/11/17
Derivation
91. The hose and coupling probabilities of failure apply to road tanker transfers. The guillotine
probabilities of failure are taken from the report by Gould and Glossop, RAS/00/10. An
extension of this work by Keeley (RAS/04/03/1) derived the smaller hole probabilities of failure.
The work was carried out for chlorine transfer facilities but should be applicable to similar
transfer operations. The safety systems applicable to the facilities are pullaway prevention (e.g.
wheel chocks, interlock brakes, interlock barriers), pullaway mitigation that stops the flow in the
event of pullaway (e.g. short airline, but only if it will separate and activate a shut off valve
before the transfer system fails, movement detectors), and hose failure protection (pressure
leak test, hose inspection). Facilities have been divided into three categories to typify the range
of precautions that might be found in practice:
Basic These have one pullaway prevention system such as wheel chocks,
carry out pressure/leak tests to prevent transfer system leaks and
bursts, but have no pullaway mitigation.
Average Two pullaway prevention systems (one of which should be wheel
chocks) as well as inspection and pressure/leak tests to prevent
transfer system leaks and bursts but no effective pullaway mitigation.
Multi safety Two pullaway prevention systems, and also an effective pullaway
systems mitigation system and inspection and pressure/leak tests to prevent
transfer system leaks and burst.
92. Fault trees were produced to reflect the three types of facilities. No additional credit should be
given for duplicate non-redundant safety systems. Note that an emergency shutdown (ESD)
system by itself does not affect the likelihood of a release. Only when used in conjunction with a
movement detector or short airline will the probability be changed. The effect of an ESD system
activated by gas detectors, pressure drop in the transfer system or the operator will be to
change the duration of the releases used in estimating the risk.
93. The failure rates are not applicable to transfers over an extended time period (e.g. from tank
containers to a process), nor do they include transfer by hard arms. Probabilities of failure for
hard arms can be found in Item FR 1.2.4.
Page 39 of 102
PCAG chp_6K Version 14 – 06/11/17
References
Title Author Date Comments
New Failure Rates for Land Use Planning J Gould and M May
QRA. HSL internal report RAS/00/10. Glossop 2000
Hose and Coupling: Less than catastrophic D Keeley and A 2004
failure rates – Milestone 2. HSL internal report Collins
RAS/04/03/1.
FR No Application Comments
65 Tanker unloading drive away prevention for ethylene oxide or propylene Driveaway failure rate provided.
oxide.
Bibliography
95. These references represent other sources of information on the subject.
Page 40 of 102
PCAG chp_6K Version 14 – 06/11/17
Page 41 of 102
PCAG chp_6K Version 14 – 06/11/17
Page 42 of 102
PCAG chp_6K Version 14 – 06/11/17
Derivation
96. These probabilities of failure apply to hard arms that are used to transfer material between a
road tanker and fixed storage tanks. The values are derived in a report by Keeley,
MSU/LET/2013/20, and are based on the hose and coupling work detailed in Item FR 1.2.3
(Gould and Anderson, 2000, Keeley and Collins, 2004).
97. A simple analysis of the fault trees used to derive the hose and coupling probabilities of failure
was carried out. The hose and coupling fault trees were re-analysed to determine which failure
modes were applicable to hard arm transfers and which were specific to flexible hoses. In
addition, any unique failure modes that were specific to hard arms were also identified.
98. For guillotine failure a number of events were not considered to be relevant for hard arms and
the fault trees were reanalysed with the following events removed:
brittle hose
99. For less than catastrophic hole sizes the following events were not considered to be relevant to
hard arms and therefore removed from the fault trees:
100. An additional failure mode for hard arms that needed to included was failure of the swivel joints
and a typical hard arm was assumed to have five swivel joints per arm.
101. The fault trees were re-evaluated and the calculated probabilities of failure were found to be
similar to those for flexible hoses at multi-safety system sites. Given the uncertainty in the
analysis the hose and coupling probabilities of failure have been adopted for sites with multi-
safety systems and average type facilities.
102. For basic type facilities which may not carry out such rigorous inspection, a site specific
probability of failure will need to be calculated.
Page 43 of 102
PCAG chp_6K Version 14 – 06/11/17
References
Title Author Date Comments
New Failure Rates for Land Use Planning J Gould and M May
QRA. HSL internal report RAS/00/10. Glossop 2000
Hose and Coupling: Less than catastrophic D Keeley and A 2004
failure rates – Milestone 2. HSL internal report Collins
RAS/04/03/1.
Failure rates for hard arms. HSL internal D Keeley 2013
report MSU/LET/2013/20. Confidential, not in
the public domain.
Page 44 of 102
PCAG chp_6K Version 14 – 06/11/17
Derivation
103. All rates are taken from the MHAU handbook volume 3 (now archived). The 5 x 10-6 value is
derived in the Components Failure Rates paper, which is a comparison of 9 sources of joint
failure rates derived elsewhere. The values were derived for chlorine duty although the review
included LPG, petrochemical, steam/water, nuclear and other data. Assuming a fibre or ring
type gasket in a 25 mm pipe, four bolt flange and a 3.2 mm gasket the gasket failure will
produce an equivalent hole of 13 mm diameter.
References
Title Author Date Comments
Components Failure Rates. Confidential, not E M Pape 1985 From the Chlorine Siting Policy
in the public domain. Colloquium
FR No Application Comments
No specific advice.
Bibliography
105. These references represent other sources of information on the subject.
Page 45 of 102
PCAG chp_6K Version 14 – 06/11/17
Page 46 of 102
PCAG chp_6K Version 14 – 06/11/17
Page 47 of 102
PCAG chp_6K Version 14 – 06/11/17
Derivation
106. The original values for pipework diameter < 150 mm were set out in the MHAU handbook
volume 3 (now archived). They were derived in the Components Failure Rates paper, which is a
comparison of 22 sources of pipework failure rates derived elsewhere. The values were derived
for chlorine pipework although the review included LPG, petrochemical, steam/water, nuclear
and other data. This information has been updated and augmented in an MHAU Panel
discussion and Paper presented by the MHAU Topic Specialist on failure rates. The information
presented in the table above is applicable to all process pipework.
107. Failure rates for pipework with a diameter greater than 150 mm are derived in Gould (1997) –
Large bore pipework failure rates, which considers data from 9 other references.
108. Further detail on the derivation of the pipework failure rates is given in FRED, Failure Rate and
Event Data for Use in Risk Assessment (Betteridge and Gould, 1999).
109. For pipework with diameter greater than 1000mm discussion with the topic specialist is required.
References
Title Author Date Comments
Components Failure Rates. Confidential, not E M Pape 1985 From the Chlorine Siting Policy
in the public domain. Colloquium.
Large bore pipework failure rates. J Gould Sep 97 Suggests failure rates for a range of
Confidential, not in the public domain. pipe sizes and failure scenarios.
Failure Rate and Event Data for Use in Risk P Betteridge and J 1999
Assessment Gould
Page 48 of 102
PCAG chp_6K Version 14 – 06/11/17
FR No Application Comments
90 Blast furnace gas main, diameter between 1.8 m and 2.75 m. Rates for 1000 mm pipe
assumed.
61 Failure of plastic lining of steel pipework. Failure rate per unit given.
40 Solid pipework swivel jointed loading arm for liquid sulphur dioxide. Catastrophic and leak failure
rates given.
Bibliography
111. These references represent other sources of information on the subject.
Page 49 of 102
PCAG chp_6K Version 14 – 06/11/17
m per yr
-8
> 150 mm: 8.8 x 10 per m per yr.
HF QRA. Confidential, not in the public Unknown Jul 94 Guillotine failure for ¼” piping 1.1 x
-6
domain. 10 per m per yr.
Guidelines for the preparation and review of a BP CIMAH Liaisons May 93 Pipework failure is collated and
report under the CIMAH regulations. Group expressed as an equation.
Confidential, not in the public domain.
Some social, technical and economical J L Hawksley 1984 Graph representing failure rate data
aspects of the risks of large chemical plants. for various pipe diameters.
Handbook of risk analysis. Confidential, not in Hydro Not given For average diameter failure rate is
-7
the public domain. 3 x 10 per m per yr.
Generic land-use planning consultation zones Unknown 1994 For guillotine failure (both liquid and
-6
- chlorine. Confidential, not in the public gas lines) 1 x 10 per m per yr.
domain.
Failure rates for pipework. NW Hurst, et al. Feb 94 Mean value for all the diameters
-7
considered is 4.6 x 10 per m per
yr.
Safety cases within the Control of Industrial M L Ang & F P 1989 Guillotine failure for 25 mm pipe
-6
Major Accident Hazards (CIMAH) regs. Lees given as 0.3 x 10 per m per yr.
Failure data collection and analysis in the K Boesebeck & P Not Various values for different
Federal Republic of Germany. Homke Given materials, table 2 p. 16.
The likelihood of accidental release events. Unknown Not given For catastrophic failures:
Page 50 of 102
PCAG chp_6K Version 14 – 06/11/17
Page 51 of 102
PCAG chp_6K Version 14 – 06/11/17
Item FR 2 Electrical
112. Currently there are no agreed HSE failure rates for this item. The following references
represent other sources of relevant information. A range of equipment will fall under this
category, such as motors, contactors, relays and actuators such as solenoids. Much of the
equipment will fall under IEC 61508 or IEC 61511. This data will be used for SIL (Safety
Integrity Level) assessments and on Layers of Protection Analysis (LOPA).
Bibliography
Title Author Date Comments
IEEE Guide to the collection and presentation Institute of Electrical 1983 Covers a wide range of electrical
of electrical, electronic, sensing component and Electronics components
and mechanical equipment reliability data for Engineers Inc
nuclear power generating stations
Reliability Technology Green and Bourne 1972 Average failure rates quoted for a
wide range of electrical components
in table A.7 (p.564)
Loss prevention in the process industries (V2) F P Lees 1986 Variety of electrical components in
table A9.2 and A9.3
Failure data collection and analysis in the Boesebeck and Not Table 7 gives failure rates for
Federal Republic of Germany Homke dated electrical devices
Reliability and maintainability in perspective D J Smith 1988 Table 1 gives failure rates for a
rd
(3 Edition) wide range of electrical and non-
electrical equipment. Table 2 gives
failure rates for micro-electric
components
A review of instrument failure data F P lees 1976 A range of instrumentation
considered
OREDA – Offshore reliability data handbook OREDA 1984, A variety of process control and
1992, electric equipment are included
1997,
2002
Handbook of reliability data for electronic British 1994
components used in communications Telecommunications
systems, HRD5
Reliability data for safety instrumented SINTEF 2006
systems, PDS data handbook
rd
Safety equipment reliability handbook (3 Exida.com LLC 2007 Part 1 Sensors, Part 2 Logic solvers
edition) and interface modules, part 3 Final
elements
IEC 61508: Functional safety of electrical/ International 2005
electronic/ programmable electronic safety- Electrotechnical
related systems. Commission
IEC 61511: Functional safety – safety International 2003
instrumented systems for the process industry Electrotechnical
sector. Commission
Page 52 of 102
PCAG chp_6K Version 14 – 06/11/17
Bulk Transport
FR3
Rail tankers
Compressors FR3.2.3
FR3.1.4
Page 53 of 102
PCAG chp_6K Version 14 – 06/11/17
Introduction
114. Assessors carrying out Land Use Planning assessment may have cause to assess pipelines
carrying a range of substances. The report by Chaplin, RR1035, listed under FR 3.1.1, provides
failure rates for a number of different substances.
115. The failure frequencies fall into three categories, those for buried pipelines, those where the
pipeline is above ground at a gas installation and those where the pipeline is above ground but
not within a gas installation.
116. More information can also be found in PCAG Chapter 6O and PCAS Chapter 6O.
Item FR 3.1.3 Above Ground Pipelines That Are Not Within a Gas Installation Page 60
Page 54 of 102
PCAG chp_6K Version 14 – 06/11/17
118. CEMHD5’s PIPIN (PIPeline INtegrity) Version 3 software package calculates failure frequencies
for buried transmission pipelines transporting a range of substances. The failure frequencies are
used as inputs to the pipeline risk assessment program MISHAP12, which is described in
Chaplin, RR1040 and in PCAS 6C. The failure frequencies are automatically calculated by
PIPIN from within MISHAP12, or they may be input manually. PIPIN is described in more detail
in the references and in PCAS 6O.
PIPIN Description
119. PIPIN contains two principal models: -
Operational Experience: using a generic approach derived from historical records of pipeline
releases.
Predictive: a predictive probabilistic approach using a Monte Carlo solution method with
fracture mechanics models to calculate failure frequencies due to third party damage for
transmission pipelines.
Current policy is to use a combination of both models: Operational Experience for Mechanical,
Corrosion, and Ground movement and other failures, and Predictive for Third Party Failures.
An option is available to enable this combination to be calculated automatically.
120. Assessors should refer to PCAG Chapter 6O for details on running the PIPIN software.
Current advice
121. The table illustrates which source of data should be used for each cause of damage. Gasoline,
for example, uses CONCAWE data for mechanical and corrosion failures, UKOPA for natural
failures and the PIPIN predictive model for TPA.
Data set
Cause CONCAWE UKOPA EGIG PIPIN predictive
Mechanical Gasoline Natural Gas LPG
Vinyl Chloride Ethylene
Carbon dioxide Spike crude oil (factored
values based on a ratio
between EGIG and
CONCAWE data)
Natural All commodity types
Corrosion Gasoline Natural Gas LPG
Spike crude oil Ethylene
Vinyl Chloride
Carbon dioxide
TPA All commodity types*
122. *May underestimate values for substances that lead to embrittlement of pipeline, for example,
CO2.
Page 55 of 102
PCAG chp_6K Version 14 – 06/11/17
123. PIPIN calculates failure rates for three hole sizes and ruptures, the definitions of which are
shown in the subsequent table. These were selected a number of years ago and represent HID
CEMHD5 policy.
References
Title Author Date Comments
FR No Application Comments
116-3 Carbon dioxide pipeline Cautious best estimate –
assume rates for hazardous
Page 56 of 102
PCAG chp_6K Version 14 – 06/11/17
liquid pipelines
Page 57 of 102
PCAG chp_6K Version 14 – 06/11/17
Applicability
125. The values above are applicable to general natural gas above ground installations where no site
specific information is available. The values are subject to the following general limitations:
126. Where site specific information (e.g. pipeline diameter, wall thickness, pipeline length, number
of lifts and vehicle movements) is known, a spreadsheet (Chaplin, 2011), which calculates site
specific failure rates, is available from the topic specialist.
Derivation
127. The generic failure rates are taken from a panel paper by S Pointer.
References
Title Author Date Comments
Above ground pipelines. HSL letter report Z Chaplin 2011
MSU/LET/2011/36. Confidential, not in the
public domain.
Failure frequencies for above ground natural S Pointer 2004
gas pipelines.
Page 58 of 102
PCAG chp_6K Version 14 – 06/11/17
FR No Application Comments
No specific advice issued.
Page 59 of 102
PCAG chp_6K Version 14 – 06/11/17
Item FR 3.1.3 Above Ground Pipelines That Are Not Within a Gas
Installation
129. CEMHD5 have a software package to calculate the failure rates associated with above ground
pipelines that are not contained within an installation. The program can be used for the same
substances currently considered for buried pipelines in PIPIN (Item FR 3.1.1).
Above Ground Pipelines That Are Not Within a Gas Installation Program
Description
130. The program calculates contributions to the failure rates from roads and railways in the vicinity
of the pipeline. These are combined with historical information on failures due to corrosion,
mechanical, ground movement and other natural causes. The program can also incorporate
aircraft crash frequencies into the calculations.
131. Failure rates are derived for three hole sizes and ruptures, the definitions of which are shown in
the subsequent table. These were selected a number of years ago for buried pipelines and
represent HID CEMHD5 policy.
Derivation
132. The derivation of the computer program is detailed in a report by Chaplin (2016).
References
Title Author Date Comments
Failure rates for above ground pipelines that Z Chaplin 2016 To be published as an HSE
are not within an above ground installation Research Report
(AGI)
FR No Application Comments
No specific advice issued.
Page 60 of 102
PCAG chp_6K Version 14 – 06/11/17
Derivation
134. The above values are taken from MSU/LET/2012/16 by Chaplin.
135. MSU/LET/2012/16 reviews compressor failure rates available in the literature and accident
databases. The recommended failure rates are derived from incident data in the HSE
Hydrocarbons Release database.
136. The choice of hole size categories is based on those defined for pipelines in the absence of any
other data. However, it is recommended that, if known, the size of the inlet or outlet to the
compressor should be used as the rupture size.
References
Title Author Date Comments
Compressor failure rates MSU/LET/2012/16. Z Chaplin 2012
Confidential, not in the public domain.
FR No Application Comments
No specific advice issued.
Page 61 of 102
PCAG chp_6K Version 14 – 06/11/17
Page 62 of 102
PCAG chp_6K Version 14 – 06/11/17
Derivation
139. Failure rates are based on the report by J.Gould, RAS/00/10. Tank containers are tanks built
within an ISO standard frame, 8 ft square and either 20 or 40 ft in length, allowing them to be
fitted on several modes of transport and stacked. The failure rates apply to cold failures of
pressure vessels not induced by fire engulfment or impingement. Empty tank containers are
expected to contribute little to the off-site risk and should be excluded.
140. A literature search was performed to identify failure events of the tank containers and lifting
equipment. It is assumed that tank containers dropped from up to about one ISO container high
(less than 5m) such as when stacking two-high will only produce a 50 mm hole. Tank containers
dropped from a greater height such as when lifted above two-high stacks are assumed to suffer
catastrophic failure 5% of the time, and a 50 mm hole for the remainder.
References
Title Author Date Comments
New Failure Rates for Land Use Planning J Gould 2000
QRA. HSL internal report RAS/00/10.
Page 63 of 102
PCAG chp_6K Version 14 – 06/11/17
FR No Application Comments
133 ISO tanks storing LNG Rates derived from the generic
rates with open valve
contribution removed.
132 Liquid hydrogen tanker offloading facility Use generic rates ignoring
those associated with lifting.
Rates for hose and coupling
failure also given.
121 Liquid hydrogen isotank used as semi-permanent storage tank Use generic rates ignoring
those associated with lifting
Bibliography
142. These references represent other sources of information on the subject.
Page 64 of 102
PCAG chp_6K Version 14 – 06/11/17
Derivation
143. Failure rate is based on a report by Z. Chaplin, RSU/SR/2009/10. The rate was derived from
MOD data for “serious” on-site accidents involving vehicles of over 4 tonnes in weight, for the
period 1997 - 2008. A serious accident was defined as one for which the cost of repair was at
least £10,000.
References
Title Author Date Comments
Derivation of an on-site failure rate for road Z Chaplin 2009
tankers. HSL internal report RSU/SR/2009/10.
Confidential, not in the public domain.
FR No Application Comments
66 Unloading Ethylene oxide from road tankers Catastrophic failure rate
13 Road tanker unloading rates for chlorine and bromine tank containers Catastrophic failure rate
Bibliography
145. These references represent other sources of information on the subject.
Page 65 of 102
PCAG chp_6K Version 14 – 06/11/17
Risk Assessment Acrylonitrile. Risk Courtaulds August Tanker failure for acrylonitrile
-8 -6
Assessment Butadiene. Confidential, not in Research 1988 delivery; 9x10 – 3.3x10 per yr.
the public domain.
The Major Hazard Aspects of the Transport of D Leeming and F August Compares different data sources for
Chlorine. Confidential, not in the public Saccomanno 1993 road and rail tanker accident rates
domain. and fault probability.
-6
The Likelihood of Accidental Release Events. Rhone-Poulenc Not Given A value of 1x10 per yr for
Confidential, not in the public domain. Chemicals Ltd – catastrophic failure of a road tanker.
Avonmouth Site
-7
The Likelihood of Accidental Chlorine Release W S Atkins 1994 Catastrophic rupture: 2.9x10 per
Events (Extract From a CIMAH Safety Case). yr.
-6
Confidential, not in the public domain. Partial rupture: 2.9x10 per yr.
-5
Risks Associated with the Storage of and Use SRD November Assumes 5x10 per yr as a base
of Chlorine at a Water treatment Plant (2
nd
1981 rate for catastrophic failure.
Draft). Confidential, not in the public domain.
Page 66 of 102
PCAG chp_6K Version 14 – 06/11/17
Derivation
146. All rates are based on the report by Z. Chaplin, MSU/LET/2011/38. Typical mitigation measures
are detailed in the LP Gas Association Code of Practice 1.
147. Small tanks are considered to typically have a capacity of less than 5 tonnes. Such tanks are
likely to be found at domestic or educational sites and are unlikely to have any built-in mitigation
systems.
148. Large tanks are more likely to be found at larger industrial installations and have capacities of
around 25 tonnes or greater. These types of site are likely to contain a significant number of the
mitigation measures listed.
149. If a site has manifolded tanks, then this should be treated as one visit, otherwise, each
individual tank will be counted as a tanker delivery operation.
References
Title Author Date Comments
LPG road tanker BLEVE frequencies. HSL Z Chaplin 2011
internal report MSU/LET/2011/38.
Confidential, not in the public domain.
LP Gas Association 2009
Code of practice 1. Bulk LPG storage at fixed
installations. Part 1:2009. Design, installation
and operation of vessels located above
ground.
Page 67 of 102
PCAG chp_6K Version 14 – 06/11/17
FR No Application Comments
108 BLEVE of road tanker carrying 26 te LPG
Page 68 of 102
PCAG chp_6K Version 14 – 06/11/17
Derivation
151. The incompatible deliveries failure rates apply to scenarios whereby two incompatible
substances are accidentally mixed during a delivery, for example, the contents of a tanker being
offloaded into the wrong tank. The failure rates are based on the report by Bell and Keeley,
MSU/LET/2011/39.
152. Three site type classifications have been defined based on safety management system
standards:
Below average The process of receiving a tanker to site and the delivery itself is not
always well managed. The offloading points are not locked and are not
clearly separated, well laid out or well labelled. Incompatible connectors
are generally used.
Average The process of receiving a tanker to site and the delivery itself are well
controlled by operating procedures. The offloading points are normally
locked and are well laid out and labelled. Incompatible connectors are
used.
Above average The process of receiving a tanker to site and the delivery itself are well
controlled by operating procedures. In addition, there is evidence that the
site is working to maximise the safety and reliability benefits of the
acknowledged operating conditions and to continuously improve. The
offloading points are normally locked and keys are controlled. The
offloading points are physically separated, well laid out and clearly
labelled. Incompatible connectors are used.
153. For all site types, work is completed free of unreasonable time pressures.
154. The site type definitions do not refer to the site’s ability to comply with their legal requirements
but to their success at meeting their own safety management standards. The choice of site type
will be an operational issue.
References
Title Author Date Comments
Failure frequency for incompatible deliveries J Bell and D Keeley 2011
MSU/LET/2011/39.
Page 69 of 102
PCAG chp_6K Version 14 – 06/11/17
FR No Application Comments
No specific advice issued.
Page 70 of 102
PCAG chp_6K Version 14 – 06/11/17
156. Currently there are no agreed HSE failure rates for this item. The following references
represent another source of information on the subject.
Bibliography
Title Author Date Comments
Major hazard aspects of the transport of Advisory 1991 Frequency of spills from various
dangerous substances. Committee on initiating events (p237).
Dangerous Frequencies for punctures and
Substances small spills during stopovers (p252).
Unloading event frequencies for
LPG (p258).
Gaskets, coupling and joint failures
for ammonia (p259).
Gasket and valves for chlorine
(p264 and 285-6).
Hose and coupling failure for
ammonia unloading (p288).
The Major Hazard Aspects of the Transport of D Leeming and F August Compares different data sources for
Chlorine. Confidential, not in the public Saccomanno 1993 road and rail tanker accident rates
domain. and fault probability.
Page 71 of 102
PCAG chp_6K Version 14 – 06/11/17
157. The transfer of substances via ship hardarms is covered in Item FR 3.3.1.
Page 72 of 102
PCAG chp_6K Version 14 – 06/11/17
158. The item failure rates are relevant to transfer operations via ship hardarms.
Page 73 of 102
PCAG chp_6K Version 14 – 06/11/17
Total failure rates when 3 arms used (8) 6.2e-5 9.9e-5 2.6e-6
1 The table does not include failures on the ship itself e.g. pipes, pumps, valves, flanges.
Incidents of overfilling of the ship during transfers to a ship are not included. Some of the
failure frequencies are dependent on the length of transfer time and a 12-hour transfer time
has been assumed.
2 Connection failures apply to every unloading arm that is used during the transfer operation.
Failure may lead to flow from both ends of the disconnected arm.
3 It is assumed that all unloading arms handling liquified gases have emergency release
couplings (ERC) designed to achieve a quick release with a minimum of spillage. The
coupler failures specified here are events where the ERC parts without the valves in the
coupling closing. Incidents where the coupling parts correctly will lead to minimal spillage.
4 This includes not making a connection correctly, opening the wrong valve or at the wrong
time, or spilling cargo when disconnecting or venting.
5 Ranging failures are due to gross movement of the ship at the jetty. It is assumed that the
unloading system is fitted with ranging alarms. (Absence of ranging alarms is assumed to
increase the failure frequency due to Mooring faults by a factor of 5 and absence of ERC
couplings would increase the Passing ships frequency by a factor of 5).
6 The failure frequency due to passing ships assumes 10 passing ships during offloading.
7 Ranging failures may simultaneously affect more than one connection where multiple hard
arms are in use (i.e. the ship moves and more than one hard arm becomes disconnected).
When ranging incidents occur where multiple hard arms are connected it is assumed that
10% of the failures will lead to flow from two of the connections.
8 The totals in the last three rows indicate how the data should be used. If there is only one
arm then it is not possible to have two simultaneous guillotine breaks. If two are used then
the probability of the connection failures is doubled, the ranging failures probability remains
the same and there is now a probability that two simultaneous guillotine breaks can occur.
If three hard arms are used then the probability of a connection failure is tripled, the
probability of a ranging failure remains the same, and the probability of any two out of the
three hard arms suffering a simultaneous guillotine break is assumed to be the same as
when two hard arms are used.
Derivation
162. The failure rates presented here are based on the panel paper by P Buckley ‘Failures during
ship transfers’ 8/11/04, 10/01/05 and 27/06/05 that reviewed a number of available reports and
data sources. Failure Rate Advice note 124 summarises the derivation of the failure rates.
References
Title Author Date Comments
Major hazard aspects of the transport of Advisory 1991
dangerous substances, HSC HMSO1991 Committee on
ISBN 0-11-885676-6. Dangerous
Substance
Risk assessment of QEII dock, Eastham. DNV 1992
340/CD/1024/2001. Confidential, not in the
Page 74 of 102
PCAG chp_6K Version 14 – 06/11/17
public domain.
Failures during ship transfers, Panel Paper P Buckley 08/11/04
Panel minutes. Confidential, not in the public 08/11/04
domain.
Failures during ship transfers – Proposal for P Buckley 10/01/05
PCAG 6K, Panel Paper. Confidential, not in
the public domain.
Panel minutes. Confidential, not in the public 10/01/05
domain.
Failures during ship transfers – Proposal for P Buckley 27/06/05
PCAG 6K, Panel Paper. Confidential, not in
the public domain.
Panel minutes. Confidential, not in the public 27/06/05
domain.
FR No Application Comments
FR 124 Ship hardarms. Guillotine and hole failure rates
due to a number of causes.
Page 75 of 102
PCAG chp_6K Version 14 – 06/11/17
165. For Items FR 4.1.3 and FR 4.1.6 there are currently no agreed HSE failure rates but relevant
advice notes have been included in each section.
Page 76 of 102
PCAG chp_6K Version 14 – 06/11/17
166. Where:
Derivation
167. The original values were taken from the MHAU handbook volume 3 (now archived) for chlorine
drums, and are applicable to other 1 te pressure vessel drums. Fault and event trees are used
with a review of previous work and expert judgement to derive the failure rates. Drum failure is
derived from static chlorine storage vessel failure rates, while those for holes and sheared
valves are derived from a drum dropping frequency.
Page 77 of 102
PCAG chp_6K Version 14 – 06/11/17
References
Title Author Date Comments
FR No Application Comments
No specific advice issued.
Bibliography
169. These references represent other sources of information on the subject.
Page 78 of 102
PCAG chp_6K Version 14 – 06/11/17
3.6 10 T/4
-5
Major failure of 2 drums (10 mm hole)
2.0 10 T/4
-6
Major failure of 1 drum (10 mm hole)
6.0 10 T/4 + 8.0 10 Q
-6 -5
Minor failure of 1 drum (5 mm hole)
170. Where:
Derivation
171. The assumptions in the derivation of the failure rates are:
The drums have openings on the top that are sealed or capped, but no valves;
Two movements are associated with each drum, both by fork-lift truck (FLT);
If a FLT driver misjudges the location of the pallet, there is the potential for the forks to
impinge on 2 drums simultaneously.
172. Values for 210 l drums have been derived using a combination of information in the FR notes,
the Vectra work on Intermediate Bulk Containers (IBCs), and the review of the IBC Vectra work.
The hole sizes are the same as those used for IBCs.
173. A large hole in the base of the drum could lead to the release of all the contents. This will have
similar effects to a catastrophic failure. Assessors should model a catastrophic failure as an
instantaneous release, rather than a hole.
Page 79 of 102
PCAG chp_6K Version 14 – 06/11/17
References
Title Author Date Comments
Review of Failure Rates for Drums Storing Zoe Chaplin 2014
Hazardous Materials, MSU/2014/16.
Confidential, not in the public domain.
Failure rates for Intermediate Bulk Containers Zoe Chaplin 2013
(IBCs) MSU/2013/21. Confidential, not in the
public domain.
Report No. 300-232-R01, Revision A. Vectra 2001
Confidential, not in the public domain.
FR No Application Comments
No specific advice issued.
Page 80 of 102
PCAG chp_6K Version 14 – 06/11/17
175. Currently there are no agreed HSE failure rates for this item. See failure rate advice notes for
specific failure rates, or refer to Topic Specialist.
FR No Application Comments
119 Chlorine cylinders Catastrophic and valve shear
failure rates provided.
Page 81 of 102
PCAG chp_6K Version 14 – 06/11/17
177. Where:
Derivation
178. Values for IBCs were initially derived by Vectra in 2001 using a fault tree approach, but the
failure rates were never formally adopted. Various FR notes have been issued since the Vectra
analysis to provide failure rates for non-UN IBCs and to allow for 2 movements per container on
site. A review of the FR notes and the Vectra analysis was performed in 2013, leading to a
restructure of the fault trees and revised failure rates. A review of the representative hole sizes
was also performed which concluded that the definitions for the minor, major and catastrophic
releases should be revised to 5 mm for minor releases, 10 mm for major releases and 25 mm
for catastrophic releases. The advice has since been modified so that catastrophic failures
should be modelled as an instantaneous release, rather than a hole. It was found that there was
minimal difference in the failure rates calculated for UN and non-UN IBCs and so the same
failure rates should be applied to all types of IBC.
179. The failure rates include leaks from the cap and valves as well as from the main body of the
IBC. They are split between failures that may occur during movement (e.g. fork lift truck
puncture) and those that may occur during storage (e.g. degradation of the body of the IBC over
time). The failure rate due to movement should be multiplied by the number of IBCs passing
through the site per year, and assumes that each IBC will be subject to two movements on the
site. The failure rate due to storage should be multiplied by the average number of IBCs
continuously in store.
180. It should be noted that a large hole half way up an IBC will lead to the loss of approximately half
the contents. If the hole is in the base of the IBC, however, the full contents of a 1 m 3 IBC will be
lost within 30 minutes. This will have similar effects to a catastrophic failure for this size of IBC.
Some IBCs can have larger volumes and hence assessors should model a catastrophic failure
as an instantaneous release, rather than a hole.
181. In order to derive a value for N, the applied for quantity should be divided by the density of the
substance (either named or exemplar). For example, for 50 te of B1 very toxic material,
assuming methyl chloroformate as the exemplar, N will be 41 (50000 kg of substance divided by
the density of methyl chloroformate at 15C, which is 1229 kg m-3).
References
Title Author Date Comments
Page 82 of 102
PCAG chp_6K Version 14 – 06/11/17
FR No Application Comments
No specific advice issued.
Page 83 of 102
PCAG chp_6K Version 14 – 06/11/17
183. Where:
Being required to have a pressure release device (disk, gauge and PRV or just PRV);
and
185. A typical portable container is 1 m3 and rated to ~5 bar, containing very toxic or volatile
substances.
186. The failure rates are based on the 1 te drum failure rates (see Item FR 4.1.1), and the hole
sizes are consistent with IBCs.
187. A large hole in the base of the portable container could lead to the release of all the contents.
This will have similar effects to a catastrophic failure. Some portable containers can have larger
volumes and hence assessors should model a catastrophic failure as an instantaneous release,
rather than a hole.
References
Title Author Date Comments
Page 84 of 102
PCAG chp_6K Version 14 – 06/11/17
FR No Application Comments
138 800 litre portable cylinders, operating at 9.8 barg. Catastrophic, large and small
hole rates derived, together
with valve and coupling failures
and errors.
137-2 Portable storage tanks, type T22, for acrolein, pressurised to a minimum Catastrophic, large and small
of 10 bar. hole rates derived.
136 Portable stainless steel containers, pressurised between 1.5 and 10 bar. Catastrophic, large and small
hole rates derived.
Page 85 of 102
PCAG chp_6K Version 14 – 06/11/17
189. Currently there are no agreed HSE failure rates for the different types of small containers. See
failure rate advice notes for specific failure rates, or refer to Topic Specialist.
FR No Application Comments
106 52 l containers, rated to 200 bar, of pressurised liquid WF6 and 8 l toxic Catastrophic and 50 mm, 25
containers`, rated to 200 bar, of pressurised liquid Cl2. mm, 13 mm and 6 mm hole
failure rates provided for 52 l
and 8 l containers.
67 5 l UN-certified HF drums. Catastrophic (2 types of
release), major and minor
failure rates provided.
57 25 l HF plastic carboys, delivered by lorry, removed to storage by FLT Catastrophic (2 release rates),
and transported on wooden pallets with 16 carboys to a pallet. major and minor failure rates
provided.
50 Plastic containers for hydrogen peroxide transported by lorry on wooden Catastrophic, major (90 mm)
pallets and transferred on site by FLT. and minor (25 mm) failure rates
provided.
Page 86 of 102
PCAG chp_6K Version 14 – 06/11/17
Event Data
191. Event data consists of external hazards that need to be taken into consideration when deriving
an overall probability of failure for an item. The event data are split as follows:
Page 87 of 102
PCAG chp_6K Version 14 – 06/11/17
Introduction
192. The following is taken from Chaplin (2017), with additional information taken from Chaplin
(RSU/SR/2009/06). The background crash rates quoted should be used for all sites whereas
the remainder of the methodology need only be used when a site lies close to an airfield or
beneath a flight path.
193. Table 1 have been derived by Chaplin (2017) and are updates to Chaplin (RSU/SR/2009/06).
The earlier work was based on Atkinson and Thompson (2008), which was an update to the
report by Byrne (1997).
Airfield Rates
The values reported in
194. Table 1 assume that the site is not within 5 miles of an airfield. For sites within this distance, a
different set of values has been derived. According to the report by Byrne, consideration should
only be given “to airfields within 10 km of the site unless the airfield is particularly busy (>
20,000 movements annually), or if the runway orientation is unfavourable for the site (i.e. the
runway is pointing roughly in the direction of the site)”. Table 2 reports the probability of an
aircraft crashing on take-off or landing as calculated by Chaplin (2017).
Page 88 of 102
PCAG chp_6K Version 14 – 06/11/17
195. Using the values in Table 2 is not straightforward as it depends on the direction of the site from
the airfield and the directions of the runways. The equation that determines the frequency, g,
with which a unit ground area at position (r,) relative to the runway would suffer an impact as a
result of N runway movements per year is given by:
g NRf (r , ) (1)
where R is the probability per movement of a landing or take-off accident and f(r,) is the probability of
unit ground area at (r,) suffering an impact, given that an accident has occurred. Unit ground area is
defined as 1 km2 whilst r is measured in km from the runway threshold and is the angle measured in
degrees between the extended runway centreline and a vector parallel to r (see Figure 6). R can be
found from Table 2 whilst different expressions exist for calculating f(r,) depending on the category of
aircraft. For some categories of aircraft, alternative equations have been derived using an (x,y)
coordinate system to generate probabilities of accidents for take-offs and landings separately (FT(x,y)
and FL(x,y) respectively). See Byrne for more detail. The calculated values of g would need to be
added to those in
196. Table 1 to provide a total crash rate for a specific location if it is near an airfield.
Figure 6 The r, coordinate system for accident locations in the vicinity of an airfield
Flight Paths
197. It is possible to calculate crash rates associated with particular airways so that a specific rate
may be derived if the site lies beneath a flight path. This will also take into account whether the
site is below an upper or lower airway. The calculation is based on the assumption that crashes
are normally distributed about the airway centreline, with a standard deviation equal to the
airway altitude. The actual equations can be found in Byrne but the in-flight reliabilities for each
aircraft category are also required and these are shown in Table 3. These values have not been
updated and are taken from Byrne.
Page 89 of 102
PCAG chp_6K Version 14 – 06/11/17
Worked Example
The values in
Table 1 can be used to calculate catastrophic failures and leaks from different hole sizes for vessels.
The methodology illustrated in
The consequences of a crash within a specified distance of the vessel are assumed for various aircraft
types. For example, it is assumed that a light aircraft crashing within a 50 m radius of the vessel will
cause a catastrophic failure, whereas, if it falls between 50 m and 70 m from the vessel, it will generate
a 50 mm hole, etc. The values are shown in
Table 4. Note that the values calculated differ from FR19 as there were errors in the original work,
which have been corrected in
199. Table 4. Also, the distances used are for the purposes of illustration only. Each site will require
a specific assessment to determine at what distance each aircraft type is likely to cause
damage. This may depend on the construction of the site, the topology of the land or any other
factor that could affect how much damage an aircraft crash would cause.
Page 90 of 102
PCAG chp_6K Version 14 – 06/11/17
200. Table 1, Table 2 and Table 3. Assume a site of 1 km2 that is located 1 km to the west and 1 km
to the north of an airfield where the prevailing winds mean that aircraft take-off from east to west
at all times, meaning that only take-offs need to be considered for this exercise. This is
equivalent to an r value of 2 km and a of 45. Using equation (6) from Byrne gives a value of
f of 0.021, which should be used for light aircraft and can be applied to either take-offs or
landings. For the other aircraft categories (excluding helicopters), as only take-offs need to be
considered, equation (8) from Byrne should be used. This gives a value for FT of 0.013. Next it
is necessary to have information on the number of movements at the airfield. Example values
for an imaginary airfield are shown in Table 5.
201. These values are then halved to take into account that it is only take-offs that are of interest
(landings occur in the same direction as take-offs so it is assumed that they do not pass over
the site) and they are then multiplied by the relevant f or F value and the values in Table 2. This
is shown in Table 6.
Page 91 of 102
PCAG chp_6K Version 14 – 06/11/17
The total frequency can be found by adding these together, giving a rate of 10.29 x 10-6 /year. Next the
values in
202. Table 1 need to be added to this value to take into account the background crash rate. This
gives a new total of 4.87 x 10-5 /year.
203. The final step is to calculate the contribution from an airway. Assume the site is directly below a
lower airway (i.e. the aircraft altitude is 5 km). This gives, according to Byrne, an area factor of
0.395. The in-flight reliabilities (Table 3) can then be multiplied by the number of movements on
that airway per year to give a crash rate. This is shown in Table 7, assuming values for the
number of movements for each of the aircraft types.
204. The total crash rate below an airway is 2.86 x 10-5 /year. This can then be added to the previous
total to give an overall rate of 7.73 x 10-5 crashes/year
References
Title Author Date Comments
Update of aircraft crash rates used in HSE’s Chaplin Z 2017
Failure Rate and Event Data document.
MSU/2015/19. To be published on HSE’s
website.
Aircraft crash rates, HSL internal report Chaplin Z 2009
RSU/SR/2009/06. Confidential, not in the
public domain.
Review of aircraft crash rates for the UK up to Atkinson T and 2008 This is an update of the report by
2006. ESR/D1000646/001/Issue 1. Thompson P Byrne
Confidential, not in the public domain.
The calculation of aircraft crash risk in the UK. Byrne JP 1997
AEA Technology, Contract Research Report
150/1997.
Page 92 of 102
PCAG chp_6K Version 14 – 06/11/17
FR No Application Comments
19 Liquid hydrogen vessels Demonstrates methodology
Page 93 of 102
PCAG chp_6K Version 14 – 06/11/17
Item ED 2 Flooding
206. The first stage when trying to derive a value for frequency of flooding for a specific site is to
determine whether or not the site falls within a coastal or river flood plain. The Environment
Agency (EA) website, which covers England and Wales, or the Scottish Environment Protection
Agency (SEPA) website, can be used to assess where a particular site falls. If it is outside a
flood plain then the risk from flooding can be considered to be negligible and the contribution
from this event can be ignored.
207. If the site does fall within a flood plain, then more information on the probability of flooding per
year can be obtained from either the EA or the SEPA. In the case of the former, they identify
three areas to which they assign low, moderate or significant likelihood categories. Low
likelihood areas correspond to a 1 in 200 chance per year or less of flooding, moderate is
between a 1 in 200 chance per year and a 1 in 75 chance per year and significant likelihood
corresponds to a greater than 1 in 75 chance per year of flooding. The SEPA website indicates
areas in Scotland with a greater than 1 in 200 chance per year of flooding.
208. Even if the site is considered to be within one of the areas at risk of flooding, further information
would be required to assess the likelihood of flood waters reaching a level at which damage
could be caused to the site. This would require expert judgement and liaison with the relevant
environment regulatory body. Once a probability of reaching this level of flooding has been
determined, it would then be necessary to use further expert judgement to determine the level
of plant damage sustained, e.g. the relative chance of a catastrophic failure occurring, or holes
of differing sizes. It is not possible to produce a generic value as each site will have a different
level of flood protection in place and will be potentially subject to different levels of flooding.
References
Title Author Date Comments
http://www.environment-agency.gov.uk/default.aspx accessed on 2 Specifically, the
September 2009. flood maps were
viewed.
http://www.sepa.org.uk/flooding/flood_map.aspx accessed on 2
September 2009.
Page 94 of 102
PCAG chp_6K Version 14 – 06/11/17
209. The British Standards Institute document, BS EN 62305-2:2006, details the calculations
required to determine the frequency with which lightning will strike a structure and cause
damage to it. The first stage is to calculate the average annual number of events that have the
potential to cause damage. In order to do this, it is first necessary to calculate the collection
area around the structure in question. For isolated structures on flat ground, this is defined as
“the intersection between the ground surface and a straight line with 1/3 slope which passes
from the upper parts of the structure (touching it there) and rotating around it” (in BS EN 62305-
2:2006). For the simplest structure of a cylinder with height H and radius R, this would equate to
an area, A, enclosed by the radius 3H + R, i.e.
210. This is illustrated in Figure 7 and all dimensions are measured in metres. As the shape of the
structure becomes more complex, so approximations may need to be made to calculate the
collection area but the general principle remains the same. Refer to BS EN 62305-2:2006 for
more detail. For complex sites it is possible to divide the site into various zones, calculate the
collection area of each zone and then follow all further calculations for each of the zones. The
results from each zone are then summed together to give an overall damage probability.
3H
3H
Page 95 of 102
PCAG chp_6K Version 14 – 06/11/17
211. The second stage is to calculate the number of dangerous events, ND, for a structure using the
equation:
where:
212. The lightning ground flash density varies across the UK, from 0.02 /km 2/year in the north of
Scotland, to 1.0 /km2/year in parts of central England. The values can be found from Figure 1 in
BS EN 62305-2:2006. The location factors are listed in Table 8 and were obtained from BS EN
62305-2:2006.
213. To calculate the probability that a structure will be damaged, given a lightning strike, it is first
necessary to consider whether there is a lightning protection system (LPS) in place. According
to BS EN 62305-1:2006 there are four levels of protection that these systems can offer, I
through to IV with I offering the highest level of protection. These are detailed in Table 5 of BS
EN 62305-1:2006. The probabilities of damage being caused are listed in Table 9 and were
obtained from BS EN 62305-2:2006.
Page 96 of 102
PCAG chp_6K Version 14 – 06/11/17
Table 9 Probabilities of damage given a lightning strike, depending on the lightning protection measures in
place
Details of structure Class of lightning protection system Probability
(LPS)
Not protected by LPS - 1
Protected by LPS IV 0.2
III 0.1
II 0.05
I 0.02
Air-termination system conforming to LPS I and a continuous metal or reinforced 0.01
concrete framework acting as a natural down-conductor system.
Metal roof or an air-termination system, possibly including natural components, with 0.001
complete protection of any roof installations against direct lightning strikes and a
continuous metal or reinforced concrete framework acting as a natural down-conductor
system.
214. These probabilities can then be multiplied by the number of dangerous events, ND, to produce
an overall frequency of damage to a structure. The type of failure associated with the damage is
likely to be structure dependent. Expert judgement may be required to produce factors that can
be used as multipliers to the existing results to determine the likelihood of catastrophic failures
and holes of varying sizes.
Worked example
215. To show how the data in Table 8 and Table 9 and equations 2 and 3 may be used, consider a
storage tank of radius 10 m and height 20 m. Using equation 2, the collection area is 15394 m2.
Assume there are nearby structures of the same height, which will give a location factor of 0.5
(from Table 8) and also assume that the site is located in an area with a lightning ground flash
density of 0.7 per km2 per year. The value of ND is then 0.0054 per year (from equation 3). Next
assume that the structure has a lightning protection system of class I, which implies a probability
of damage, given a lightning strike, of 0.02 (from Table 9). When multiplied by ND, this gives an
overall frequency of damage of 1.08x10-4 per year. This number can then be multiplied by
factors to give frequencies of different types of failure.
References
Title Author Date Comments
Protection against lightning – Part 2: Risk management. BS EN 62305- British 2006
2:2006. Standard
Protection against lightning – Part 1: General principles. BS EN 62305- British 2006
1:2006. Standard
Page 97 of 102
PCAG chp_6K Version 14 – 06/11/17
Human Factors
A comment on the use of human error potential (HEP) values; both observed and generated by HRA
techniques
A brief description of the techniques that are commonly used for determining human reliability values
Guidance on the limits that should be placed on the use of those techniques
Overview
217. In most cases, a human error potential of 0.1 can be considered a conservative or cautious
estimate of the risk of human failure. This value can generally be accepted as appropriate for
use in order of magnitude tools, like Layers of Protection Analysis (LOPA). However, human
factors specialists would still expect to see the duty holder demonstrate a thorough
understanding of the tasks being undertaken and the conditions in which they are performed.
218. Claims of reliability beyond 0.1 will require significantly more demonstration and justification;
typically this is when a site might use a human reliability assessment tool but quantification is
not always necessary. The HID Human Factors Specialist Inspectors team advocate using a
qualitative approach to ensure the duty holder has a thorough understanding of the issues.
Where quantified methods are used, HSE has found that values are often taken from publicly
available data sources and HRA methods without any justification or consideration of the site-
specific conditions that might influence their applicability. For example, documents such as ‘BS
EN 61511-3:2004 (annex F) and the Center for Chemical Process Safety (CCPS) book on
LOPA have tables that provide examples of HEPs. While these values are probably appropriate
in many situations, the associated text to describe the context is extremely limited; duty holders
need to consider how applicable the data are to the situation being assessed and to justify their
use. If a duty holder has adequate site-specific performance data regarding human reliability,
this data could be used to support HEPs obtained from HRA methods and other sources. This
historical data can be considered adequate if it has been collected over a sufficient timescale to
be statistically significant. However, in many cases such data are not readily available and duty
holders, having decided on a quantitative analysis, must draw upon their knowledge of the task
to work through a HRA method.
219. In order to complete a HRA correctly, qualitative knowledge is essential because without a
thorough analysis of the site-specific issues the assessor cannot adequately assess the risk,
determine a realistic HEP or identify ways to improve safety. It is important to note that even
with a good qualitative underpinning to the assessment, the uncertainties inherent in all HRA
techniques mean that the generated HEP can only ever be an estimate. Therefore, when using
HEP data, for example in COMAH safety reports, we should expect to see the duty holder
express caution about the claims they make and how data have been used in risk assessments.
Page 98 of 102
PCAG chp_6K Version 14 – 06/11/17
221. At a minimum, it is realistic to expect that the duty holder has provided information about points
1 and 4, with reference to points 2 and 3.
Overview of methods
223. There are a large number of HRA techniques and approaches available, many are publicly
available but others are proprietary methods.Typically, tools are assigned into the following
three groups.
Page 99 of 102
PCAG chp_6K Version 14 – 06/11/17
of uptake in the UK the benefits of the second generation over first generation approaches are
yet to be established. They have also yet to be empirically validated.
227. New tools are emerging based on earlier first generation tools such as HEART, and are being
referred to as third generation methods.
229. There are 9 Generic Task Types (GTTs) described in HEART, each with an associated nominal
HEP, and 38 Error Producing Conditions (EPCs) that may affect task reliability, each with a
maximum amount by which the nominal HEP can be multiplied. The assessor must determine
an Assessed Proportion of Affect (APOA) for each EPC; APOA is a concept that relates to how
‘present’ each EPC is.
231. The assessment should not contain more than a maximum of 3 to 4 EPCs; if there are more it
indicates a problem with either the analysts’ understanding of HEART or a poorly designed task
that is highly likely to fail. If an assessment truly reveals a high number of EPCs, the task should
be investigated further and appropriate changes made to address the issues.
233. The handbook presents tabled entries of HEPs that can be modified by the effects of plant
specific Performance Shaping Factors (PSFs) using other tables. HSE has found data is taken
from the tables without following the THERP methodology and applied without appropriate
justification for its applicability to the task being assessed.
235. Action tasks – carrying out one or more activities indicated by diagnosis, operating rules or
written procedures. For example, operating equipment, performing line-ups, starting pumps,
conducting calibration or testing, carrying out actions in response to alarms, and other activities
performed during the course of following plant procedures or work orders. (Generic error rate of
0.001)
236. Diagnosis tasks – reliance on knowledge and experience to understand existing conditions,
planning and prioritising activities, and determining appropriate courses of action. (Generic error
rate 0.01)
237. Eight PSFs were identified as being capable of influencing human performance and are
accounted for in the SPAR-H quantification process. When using SPAR-H for general purposes,
only three of the eight PSFs are evaluated: time available, stress and stressors, and complexity.
The remaining five PSFs are generally considered to be event, plant or personnel specific and
would be evaluated when a plant-specific model is being developed.
240. The APJ technique is prone to biases, as well as to personality/group problems and conflicts,
which can significantly undermine the validity of the technique. The technique is often likened to
‘guessing’, and therefore, has a low degree of ‘face’ validity.
241. The PC approach differs from APJs in that subject matter experts (SMEs) make simple
comparative judgements rather than absolute judgements. Each expert compares pairs of error
descriptions and decides, in each case, which of the two errors is more probable. When
comparisons made by different experts are combined, a relative scaling of error likelihood can
then be constructed. This is then calibrated using a logarithmic calibration equation, which
243. If using PC, the SMEs should have experience of the tasks being assessed. Each pair of tasks
should be presented on its own, so that the expert only considers one pair at any one time. The
process should include a determination of the within-judge level of consistency and the inter-
judge level of consistency. As with APJ, to determine the levels of consistency between SMEs
an analysis of variance could be performed. Some estimation of the uncertainty bounds should
also be made.
References
Title Author Date Comments
Review of Human Reliability Assessment J Bell and J 2009 Overview of the various HRA
Methods. HSL internal report RSU/08/20 Holroyd methods and their applicability for
use by HSE
BS EN 61511-3:2004 (annex F) Functional British Standard 2004
safety —Safety instrumented systems for the
process industry sector — Part 3: Guidance
for the determination of the required safety
integrity levels. Incorporating Amendment No.
1 to BS IEC 61511-3:2003
Layer of Protection Analysis. Simplified Center for 2001
Process Risk Assessment Chemical Process
Safety
A Guide to Practical Human Reliability B Kirwan 1994 Details the HRA process including
Assessment useful techniques and approaches
for each stage of an assessment.