5 - Main Harmonic Generators
5 - Main Harmonic Generators
5 - Main Harmonic Generators
5 Main Harmonics
Generators And Their
Detrimental Effects On
Industrial Applications
By Edvard | January, 31st 2018 | 4 comments | Save to PDF
Share!
Home / Technical Articles / 5 Main Harmonics Generators And Their Detrimental Effects On Industrial Applications
• Harmonics generators:
• Static converters
• Lighting
• Arc furnaces
• Saturated reactors and
• Rotating machines (which generate slot harmonics)
• Calculation model
• Calculation method
• Principal disturbances caused by harmonic currents and voltages
• Instantaneous effects
• Long-term effects
Figure 1 – Alternating current upstream of a Graetz bridge rectifier delivering a perfect direct current on a
highly inductive load
Or tips when the bridge is followed by a capacitor (see figure 2):
The characteristic harmonic components of the current pulses supplying rectifiers have harmonic orders n,
such as n=kp±1, where:
•k = 1, 2, 3, 4, 5…
•p = number of rectifier arms, for example:
• Graetz bridge (p=6)
• 6-pulse bridge (p=6)
• 12-pulse bridge (p=12)
Applying the formula, the p = 6 rectifiers cited above generate harmonics 5, 7, 11, 13, 17, 19, 23, 25, etc.,
and the p = 12 rectifiers generate harmonics 11, 13, 23, 25, etc.
The characteristic harmonics are all odd-numbered and their currents, when nearing the ideal case of figure
5, respect approximately the amplitude relation In = I1 / n where I1 is the amplitude of the fundamental. This
means that I5 and I7 will have the greatest amplitudes. Note that they can be eliminated by using a 12-pulse
bridge (p = 12).
In practice, the current spectrum is slightly different.
New even and odd harmonics, referred to as non-characteristic harmonics, of low amplitudes, are created
and the amplitudes of the characteristic harmonics are modified by several factors including:
• Asymmetry,
• Inaccuracy in thyristor firing times,
• Switching times,
• Imperfect filtering.
For thyristor bridges, a displacement of the harmonics as a function of the thyristor phase angle may
also be observed.
Mixed thyristor-diode bridges generate even harmonics. They are used only at low ratings because the 2nd
harmonic produces serious disturbances and is very difficult to eliminate. Other power converters such as
cyclo- converters, dimmers, etc. have richer and more variable spectra than rectifiers.
Note that they are sometimes replaced by rectifiers using the PWM (Pulse Width Modulation) technique.
These devices operate at high chopping frequencies (around 20 kHz) and are generally designed to
generate only low levels of harmonics.
The harmonic currents of several converters combine vectorially at the common supply busbars. Their
phases are generally unknown except for the case of diode rectifiers.
It is therefore possible to attenuate the 5th and 7th current harmonics using two equally loaded 6-pulse
diode bridges, if the couplings of the two power supply transformers are carefully chosen (see figure
3).
Figure 3 – Attenuation circuit for I5 and I7
Go back to contents ↑
2. Lighting
Lighting systems made up of discharge lamps or fluorescent lamps are generators of harmonic currents.
A 3rd harmonic ratio may even exceed 100% in certain cases of modern fluocompact lamps. The neutral
conductor then carries the sum of the 3rd harmonic currents of the three phases, and may consequently be
subjected to dangerous overheating if not adequately sized.
Go back to contents ↑
3. Arc furnaces
Arc furnaces used in the steel industry may be of the AC or DC type.
Go back to contents ↑
4. Saturated reactors
The impedance of a saturable reactor is varying with the current flowing through it, resulting in considerable
current distortion.
This is, for instance, the case for transformers at no load, subjected to a continuous overvoltage.
Go back to contents ↑
5. Rotating machines
Rotating machines generate high order slot harmonics, often of negligible amplitude. However small
synchronous machines generate 3rd order voltage harmonics than can have the following detrimental effects:
Calculation model
When calculating disturbances, static converters and arc furnaces are considered to be harmonic current
generators (see figure 7).
These currents can therefore be considered to be injected into the network by the disturbing equipment.
It is simply necessary to arbitrarily change the sign so that, for calculation purposes, the disturbing
equipment can be considered as current sources.
The approximation is somewhat less accurate for arc furnaces. In this case, the current source model must
be corrected by adding a carefully selected parallel impedance. It is also possible to take into
consideration existent voltage harmonics at the connection to upstream network using the Norton equivalent
model (see figure 8).
For each order of UH, the current IH is calculated taking into account Z and the downstream network
impedance.
Figure 8 – Norton type equivalent model
Calculation method
When harmonic current arguments (phase-shifts) are known, vector processing may be used. For a number
of single phase disturbing sources, it could be of interest to use unbalanced modelling.
When the harmonic currents produced by disturbing sources are known only for their amplitudes, the
technical report IEC 61000-3-6 suggests a method of adding the effects of such sources.
Interesing readings on this subject (PDF):
The detrimental effects of these harmonics depend on the type of load encountered, and include:
Harmonics can cause additional errors in induction-disk electricity meters. For example, the error of a
class 2 meter will be increased by 0.3% by a 5th harmonic ratio of 5% in current and voltage.
Ripple control receivers, such as the relays used by electrical utilities for centralized remote control, can be
disturbed by voltage harmonics with frequencies in the neighbourhood of the control frequency. Other
sources of disturbances affecting these relays, related to the harmonic impedance of the network, will be
discussed further on.
Pulsating mechanical torque, due to harmonic rotating fields, can produce vibrations in rotating
machines.
2. Long-term effects
Over and above mechanical fatigue due to vibrations, the main long-term effect of harmonics is heating.
Capacitor heating
The losses causing heating are due to two phenomena: conduction and dielectric hysteresis.
As a first approximation, they are proportional to the square of the rms current. Capacitors are therefore
sensitive to overloads, whether due to an excessively high fundamental or to the presence of voltage
harmonics.
These losses are defined by the loss angle δ of the capacitor, which is the angle whose tangent is the
ratio of the losses to the reactive power produced (see figure 9). Values of around 10-4 may be cited
for tanδ.
• Increase in the rms value of the current for an equal active power consumed;
• Increase in the apparent resistance of the core with frequency, due to the skin effect;
• Increase in dielectric losses in the insulation with frequency, if the cable is subjected to non-
negligible voltage distortion;
• Phenomena related to the proximity of conductors with respect to metal cladding and shielding
earthed at both ends of the cable, etc. Calculations for steady state can be carried out as described in
IEC 60287.
Generally speaking, all electrical equipment (electrical switchboards) subjected to voltage harmonics or
through which harmonic currents flow, exhibit increased energy losses and should be derated if
necessary.
For example, a capacitor feeder cubicle should be designed for a current equal to 1.3 times the reactive
compensation current. This safety factor does not however take into account the increased heating due to
the skin effect in the conductors.
Harmonic distortion of currents and voltages is measured using spectrum analysers, providing the amplitude
of each component. It is important to use current or voltage sensors having a sufficient band width for the
measured frequencies.
The rms value of the distorted current (or voltage) may be assessed in any of three ways:
Reference // Harmonic disturbances in networks, and their treatment by Christian COLLOMBET, Jean-Marc
LUPIN and Jacques SCHONEK (Schneider Electric)