0% found this document useful (0 votes)
190 views4 pages

Vm-741B Local Communication & Phase Marker Module

This document provides specifications for the VM-741B Local Communication & Monitoring System Phase Marker Module. It includes details on phase marker input/output, operation contact input, outputs, security function specifications, materials and finish, mass, and accessory specification code. The module has options for event history backup, non-incendive classification, custom setup, tropical specification, and I/O terminal blocks.

Uploaded by

Van Quynh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
190 views4 pages

Vm-741B Local Communication & Phase Marker Module

This document provides specifications for the VM-741B Local Communication & Monitoring System Phase Marker Module. It includes details on phase marker input/output, operation contact input, outputs, security function specifications, materials and finish, mass, and accessory specification code. The module has options for event history backup, non-incendive classification, custom setup, tropical specification, and I/O terminal blocks.

Uploaded by

Van Quynh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

VM-7 VM-741B LOCAL COMMUNICATION &

MONITORING SYSTEM
PHASE MARKER MODULE
SPECIFICATIONS Page 1 of 4

No entry if additional
Model Code / Additional Spec. Code ( spec. code is not specified. )

【When "Security function" is not selected】


VM-741B /MEM /NB1 /CSU /TRP /TB

EVENT HISTORY BACKUP Non-incendive Custom setup Tropical spec. I/O terminal block for:
1 Class I Division 2 CSA 1 VM-761B instrument rack
2 VM-762B instrument rack

【When "Security function" is selected】


VM-741B2 /MEM /NB1 /CSU /TRP /TB

Security Function*1 EVENT HISTORY BACKUP Non-incendive Custom setup Tropical spec. I/O terminal block for:
Available 1 Class I Division 2 CSA 1 VM-761B instrument rack
2
(Achilles Certificate Level2) 2 VM-762B instrument rack

Specification

PHASE MARKER INPUT OUTPUT


Input points (tachometer) : 4 points Monitor output : Input signal is output via a buffer amplifier
Location : BNC (Front) and connector (Back)
Input Impedance : 50kΩ
Output Impedance : Approx. 100Ω
Input voltage range : Less than 50Vp-p Output current : Max. 5mA
Hysteresis : 1V, 2V, 5V Pulse output : Shaped pulse signal is output via a buffer amplifier.
Maximum rotation speed : 60,000rpm Location : BNC (Front)
Signal waveform : 0V (VOL), 5V (VOH)
PHASE MARKER INPUT TRANSDUCER Output Impedance : Approx. 100Ω
Proximity transducer : FK-202F, RD-05A Output current : Max. 5mA

OPERATION CONTACT INPUT Transducer power supply


: proximity transducer
RES : Outside reset signal -24VDC±10% / 25mA Max.
SEQ : Sequence signal Contact output : SYS-OK
FIL : Filter enable signal Output points : 1
Contact type : Dry contact (SPDT)
OUTPUT Enagization method
Indicators : DAN LED (Red) : Normally de-energized or
On : When DANGER alarm occurs Normally energized field changeable
(This indicator lights up when DANGER alarm is output Contact capacity : 250VAC/5A, 30VDC/5A
from at least one of the modules stored in the instrument ALARM
rack .)
Alarm reset : AUTO-RESET or SELF-HOLD field changeable.
Off : During normal status
ALT LED (Yellow)
On : When ALERT Alarm occur PROGRAMMABLE INDICATOR COMMUNICATION
(This indicator lights up when ALERT alarm is output
Network : RS-485
from at least one of the modules stored in the instrument
rack .) Protocol : Modbus/RTU
Off : During normal status Connector : 5-pin connector (Back side of rack)
SYS-OK LED (Green)
On : During normal status MCL VIEW (VM-771B) COMMUNICATION
Flash : When OK alarm occurs Network : Ethernet 100Base-TX
(This indicator flashes when an input abnormality of the Protocol : TCP/IP
phase marker signal is output or an OK alarm is output
within the rack.) Connector : RJ-45 (Back side of rack)
D-BYP LED (Red) DEVICE CONFIG (VM-772B) COMMUNICATION
On : While the DANGER bypass is set
Off : During normal status Network : USB 2.0/1.1
COMM LED (Green) Connector : Type-B (Front side of rack)
On : Communication is connected
Flash : Communication data is being passed
Off : Communication is disconnected
TRG LED (Yellow)
On : A phase marker pulse is not detected
Flash : A phase marker pulse is detected

6H14-106 Rev.4
Issued Feb. 2015
Revised Mar. 2019
VM-7 VM-741B LOCAL COMMUNICATION &
MONITORING SYSTEM
PHASE MARKER MODULE
SPECIFICATIONS Page 2 of 4

Specification

SECURITY FUNCTION*
1 MATERIAL and FINISH
Network : Ethernet 100Base-TX Face plate : ABS (Black)
Protocol : TCP/IP Sheet : Polyester tough top (Gray)

Connector : RJ-45(Back side of rack) Base plate : Alminium alloy (Silver)

Filter function : None(non-compliant Security Function) MASS


Off(Filter OFF : Maintenance only) Body : Max. 1.0 kg (2.2 lb)
On(Filter ON : In Operation)
ACCESSORY SPECIFICATION CODE / IDENTIFIED BY TB□
Client MAC Address : MAC Address of PC for MCL View
Client IP Address : IP Address of PC for MCL View Quantity
Code Accessory
(Part Code)
*1 About the Security Function /TB1 Phase Marker input terminal block plug (15pin) 1piece
・When selecting the presence of "security function", other networks FRONT-MC-1.5/15-STF-3.81(PHOENIX CONTACT) (7072NAB)
(VM-742B: Fieldbus(Modbus / TCP), Analysis software communication Phase Marker input terminal block plug (6pin) 1piece
(TCP / IP)) to unify security policies are also " Please select the presence of FRONT-MC-1.5/6-STF-3.81(PHOENIX CONTACT) (7072NAC)
security function ". SYSTEM-OK output terminal block plug (6pin) 1piece
・Custom setup of "Security function" can’t be order. FRONT-MC-1.5/6-STF-3.81(PHOENIX CONTACT) (7072NAC)
・Select "Security Function", you can meet a global certification program Contact input terminal block plug (6pin) 1piece
(Achilles Certification Level 2) that proves to have a certain network FRONT-MC-1.5/6-STF-3.81(PHOENIX CONTACT) (7072NAC)
robustness. /TB2 SYSTEM-OK output terminal block plug (6pin) 1piece
・Achilles is a registered trademark of GE Digital. FRONT-MC-1.5/6-STF-3.81(PHOENIX CONTACT) (7072NAC)

ENVIRONMENTAL CONDITION Contact input terminal block plug (6pin) 1piece


FRONT-MC-1.5/6-STF-3.81(PHOENIX CONTACT) (7072NAC)
Operating temperature : 0 to +65°C
Note) *1 D-sub plugs and hoods are not included in this code. Please make
Storage temperature : -30 to +85°C necessary arrangement separately, if required.
Relative humidity : 20 to 95%RH (non-condensing) *2 When individually ordering specify the parts code, it is require
to arrange for a necessary amount.
POWER CONSUMPTION
Module alone : Less than 15W ! WARNING
Some functions may not be available with old version.
For details, please refer to "infiSYS Family Improvement
Information" (6H16-011).

Default Value

INPUT (PHASE MARKER) SECURITY FUNCTION(Case of None)


Not used Filter : None

SYSTEM-OK ALARM Client MAC Address : FF-FF-FF-FF-FF-FF

Alarm reset : Auto Reset Client IP Address :192.168.8.100

Enagization method : NORMALLY DE-ENERGIZED SECURITY FUNCTION(Case of Available)


Relay logic : “OR” of all OK alarm Filter : Off

COMMUNICATION Client MAC Address : FF-FF-FF-FF-FF-FF

IP Adress : 192.168.8.8 Client IP Address :192.168.8.100

Subnet mask : 255.255.255.0 OTHERS


IP Port No. : 8888

Alarm Contact Operation

Power ON
Contact type Enagization method Power OFF
Normal state Alarm state
NORMALLY DE-ENERGIZED OPEN OPEN CLOSE
N.O. contact
NORMALLY ENERGIZED OPEN CLOSE OPEN
NORMALLY DE-ENERGIZED CLOSE CLOSE OPEN
N.C. contact
NORMALLY ENERGIZED CLOSE OPEN CLOSE

6H14-106 Rev.4
Issued Feb. 2015
Revised Mar. 2019
VM-7 VM-741B LOCAL COMMUNICATION &
MONITORING SYSTEM
PHASE MARKER MODULE
SPECIFICATIONS Page 3 of 4

Plug/ Terminal Block (Connector) Pin Assignment

VM-761B Instrument Rack


(Back)
1 Monitor Output Connector

2 Phase Marker Input Terminal Block

3 Phase Marker Input Terminal Block

4 SYSTEM-OK Output Terminal Block

5 Contact Input Terminal Block

Back of Instrument Rack Plug/ Terminal Block (Connector) Pin Assignment Fitting Plug Part Code

1 CH1 MON 6 CH3 MON


Plug
1 2 CH1 COM 7 CH3 COM
7072NAD
3 CH2 MON 8 CH4 MON
Hood
4 CH2 COM 9 CH4 COM
5 N/A
7072NAG

2 A1 CH1 SIG
A2 CH1 COM
A3 N/A
A
A4 CH1 POW
A5 CH1 SHIELD
A6 CH2 SIG
A7 CH2 COM
A8 N/A 7072NAB
A9 CH2 POW
A10 CH2 SHIELD
A11 CH3 SIG
A12 CH3 COM
A13 N/A
A14 CH3 POW
A15 CH3 SHIELD

3 B B1 CH4 SIG
B2 CH4 COM
B3 N/A
7072NAC
B4 CH4 POW
B5 CH4 SHIELD
B6 N/A

4 C C1 N/A
C2 N/A
C3 N/A
7072NAC
C4 N.O.
C5 SYSTEM-OK
C6 N.C.

5 D D1 RES1
D2 RES2
D3 SEQ1
7072NAC
D4 SEQ2
D5 FILT1
D6 FILT2

Note) For the accessory specification code “/TB1”, the fitting terminal block plugs 2 3 4 5 are included.
For the accessory specification code “/TB1”, the D-sub plug and hood 1 are not included. If required,
please make necessary arrangement separately referring to the part code above.

6H14-106 Rev.4
Issued Feb. 2015
Revised Mar. 2019
VM-7 VM-741B LOCAL COMMUNICATION &
MONITORING SYSTEM
PHASE MARKER MODULE
SPECIFICATIONS Page 4 of 4

Plug/ Terminal Block (Connector) Pin Assignment

VM-762B Instrument Rack


(Back) 1 Monitor Output Connector

2 Phase Marker Input Connector

3 SYSTEM-OK Output Terminal Block

4 Contact Input Terminal Block

Back of Instrument Rack Plug/ Terminal Block (Connector) Pin Assignment Fitting Plug Part Code

1 1 CH1 MON 6 CH3 MON


Plug
2 CH1 COM 7 CH3 COM
7072NAD
3 CH2 MON 8 CH4 MON
Hood
4 CH2 COM 9 CH4 COM
5 N/A
7072NAG

2 A1 CH1 IN A20 CH4 IN


A2 CH1 COM A21 CH4 COM
A3 N/A A22 N/A
A
A4 CH1 POW A23 CH4 POW
A5 CH1 SLD A24 CH4 SLD
A6 CH2 IN A25 N/A
A7 CH2 COM A26 N/A
A8 N/A A27 N/A
Plug
A9 CH2 POW A28 N/A
7072NAF
A10 CH2 SLD A29 N/A
Hood
A11 CH3 IN A30 N/A
A12 CH3 COM A31 N/A
7072NAJ
A13 N/A A32 N/A
A14 CH3 POW A33 N/A
A15 CH3 SLD A34 N/A
A16 N/A A35 N/A
A17 N/A A36 N/A
A18 N/A A37 N/A
A19 N/A

3 C C1 N/A
C2 N/A
C3 N/A
7072NAC
C4 N.O.
C5 SYSTEM-OK
C6 N.C.

4 D D1 RES1
D2 RES2
D3 SEQ1
7072NAC
D4 SEQ2
D5 FILT1
D6 FILT2

Note) For the accessory specification code “/TB2”, the fitting terminal block plugs 3 4 are included.
For the accessory specification code “/TB2”, the D-sub plugs and hoods 1 2 are not included. If
required, please make necessary arrangement separately referring to the part code above.

6H14-106 Rev.4
Issued Feb. 2015
Revised Mar. 2019

You might also like