Building Standard
Building Standard
Page 1 of 4
Insulation
Insulation used in these storages can be Based on the actual construction, an “R” value
polyurethane, styrofoam, fiberglass batts, any (insulation factor) is calculated. See Table 1 for
other good insulating material or any combination thermal properties of selected insulating and
of the above. Walls should have a minimum “R” building materials. Typical “R” calculations are
value (insulation factor) of 20, ceilings of 30 and given:
floors and foundations of 10.
Ceiling
Outside air 0.28
5-1/2” fiberglass 18.26
2” rigid insulation 10.52
½” plywood 0.63
Inside air 0.17
Total “R” for ceiling 29.86 (hr ft2 oF/BTU)
Page 2 of 4
Table 1
Insulation
Building Materials
Page 3 of 4
Layout Rooms should always be stacked with the pallet
bin runners oriented in the same direction as the
The storage room layout and refrigeration system evaporator discharge. It is essential that the bins
should be designed for maximum temperature be properly oriented to provide air distribution
pull-down efficiency. Optimum field heat removal channels for faster cooling. If the pallet runners
is obtained in a system having both adequate are properly aligned, cooling air can absorb heat
refrigeration capacity and an efficient air from the top and bottom bin surfaces more
distribution system. effectively. It is important to use identical pallet
bins in each row to ensure that the runner
The cooling air from the evaporators must be openings are continuous from the front to the back
delivered in sufficient quantity and at proper of the room.
velocity to provide effective cooling throughout
the storage volume. Ceiling mounted, direct throw It is desirable to leave a four to six inch spacing
evaporators must be sized according to the cooling between stacks of bins to promote heat transfer
load, be equipped with fans of correct capacity to along the sides of the containers. Bin spacing is
move air throughout the storage, and be positioned easily managed if the bin row location is marked
in the proper location to facilitate maximum air on the floor of the storage with paint. The stacking
movement. Better air distribution is obtained with patterns for new storage rooms should be
several small evaporators located along one wall established so that the bin orientation and spacing,
than a single, large unit of equivalent capacity relative to the refrigeration system, is known
located in the centre of the same wall. Coils must before construction takes place. This will ensure
be kept free of ice to ensure efficient heat optimum use of floor space and refrigeration
exchange and proper air velocity. capacity during pull-down.
Page 4 of 4