OTTV Calculation - Muhd Adam Roslan

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 9

A B C

OTTV COMPONENT
Solar Absorption
Wall location Wall Area (m²) Constant
Factor (α)

Northeast wall 1149.12 15 0.20


CONDUCTION
THROUGH

Southwest wall 1149.12 15 0.20


WALLS
HEAT

Northwest wall 1322.02 15 0.20


Southeast wall 1322.02 15 0.20
Σ Wall Area 4942.28 Equation for Heat Conduction Walls
Northwest window 740.60 6 N/A
CONDUCTION

WINDOWS
THROUGH

Southeast window 710.64 6 N/A


HEAT

Northeast window 810.04 6 N/A


Southwest window 810.04 6 N/A
Equation for Heat Conduction Through Windows
Northwest window 740.60 194 N/A
GAIN THROUGH
SOLAR HEAT

WINDOWS

Southeast window 710.64 194 N/A


Northeast window 810.04 194 N/A
Southwest window 810.04 194 N/A
Equation for Solar Heat Gain Through Window
D E F G H

Window to Wall Wall Constr U- Orientation Factor


(1-WWR) Glass U-Value (Uf)
Ratio (WWR) Value (Uv) (OF)

0.70 0.30 2.60 N/A N/A


0.70 0.30 2.60 N/A N/A
0.56 0.44 2.60 N/A N/A
0.54 0.46 2.60 N/A N/A
tion Walls = 15 × α × ( 1 - WWR ) Uv
0.70 N/A N/A 5.70 N/A
0.70 N/A N/A 5.70 N/A
0.56 N/A N/A 5.70 N/A
0.54 N/A N/A 5.70 N/A
tion Through Windows = 6 × WWR × Uf
0.70 N/A N/A N/A 1.09
0.70 N/A N/A N/A 0.90
0.56 N/A N/A N/A 0.90
0.54 N/A N/A N/A 1.13
ain Through Window = 194 × WWR × OF × SC
I J K L

Wall OTTV (ie


Shading Coefficient
Glass Shading Device Shading multiply all shaded
SC1 × SC2 (ie % of OTTV
Coeff (SC1) Coeff (SC2) celss in the same
columns I × J)
row)

N/A N/A N/A 2688.94


N/A N/A N/A 2688.94
N/A N/A N/A 4537.17
N/A N/A N/A 4743.41
Σ 14658.46 5.4%
N/A N/A N/A 17729.96
N/A N/A N/A 17012.72
N/A N/A N/A 15513.89
N/A N/A N/A 14959.82
Σ 65216.39 24.2%
0.51 1.00 0.51 55908.80
0.51 1.00 0.51 44295.75
0.51 1.00 0.51 40393.26
0.51 1.00 0.51 48904.70
Σ 189502.51 70.3%
Σ WALL OTTV = 269377.36 100%
Σ WALL AREA = 4942.28
OTTV = 54.50
A B C

COMPONENT
OTTV
Solar Absorption
Wall location Wall Area (m²) Constant
Factor (α)

Northeast wall 1149.12 15 0.20


CONDUCTIO CONDUCTIO
THROUGH N THROUGH N THROUGH

Southwest wall 1149.12 15 0.20


WALLS
HEAT

Northwest wall 1322.02 15 0.20


Southeast wall 1322.02 15 0.20
Σ Wall Area 4942.28 Equation for Heat Conduction Walls =
Northwest window 740.60 6 N/A
WINDOWS

Southeast window 710.64 6 N/A


HEAT

Northeast window 810.04 6 N/A


Southwest window 810.04 6 N/A
Equation for Heat Conduction Through Windows =
Northwest window 740.60 194 N/A
SOLAR HEAT

WINDOWS

Southeast window 710.64 194 N/A


GAIN

Northeast window 810.04 194 N/A


Southwest window 810.04 194 N/A
Equation for Solar Heat Gain Through Window =
D E F G H

Window to Wall Wall Constr U- Glass U-Value Orientation


(1-WWR)
Ratio (WWR) Value (Uv) (Uf) Factor (OF)

0.70 0.30 2.60 N/A N/A


0.70 0.30 2.60 N/A N/A
0.56 0.44 2.60 N/A N/A
0.54 0.46 2.60 N/A N/A
duction Walls = 15 × α × ( 1 - WWR ) Uv
0.70 N/A N/A 5.70 N/A
0.70 N/A N/A 5.70 N/A
0.56 N/A N/A 5.70 N/A
0.54 N/A N/A 5.70 N/A
duction Through Windows = 6 × WWR × Uf
0.70 N/A N/A N/A 1.09
0.70 N/A N/A N/A 0.90
0.56 N/A N/A N/A 0.90
0.54 N/A N/A N/A 1.13
t Gain Through Window = 194 × WWR × OF × SC
I J K L

Shading Wall OTTV (ie


Glass Shading Device Shading Coefficient SC1 × multiply all
% of OTTV
Coeff (SC1) Coeff (SC2) SC2 (ie columns I shaded celss in
× J) the same row)

N/A N/A N/A 2688.94


N/A N/A N/A 2688.94
N/A N/A N/A 4537.17
N/A N/A N/A 4743.41
Σ 14658.46 6.6%
N/A N/A N/A 17729.96
N/A N/A N/A 17012.72
N/A N/A N/A 15513.89
N/A N/A N/A 14959.82
Σ 65216.39 29.3%
0.51 0.74 0.38 41372.51
0.51 0.77 0.39 34107.73
0.51 0.77 0.39 31102.81
0.51 0.74 0.38 36189.48
Σ 142772.53 64.1%
Σ WALL OTTV = 222647.38 100%
Σ WALL AREA = 4942.28
OTTV = 45.05