Protection
Relays Guide 2012
2012
www.schneider-energy.pl
[ Protection Relays Guide ] List of ANSI Codes Applied in the Guide 2
Function symbols in accordance with ANSI / IEEE Std C37.2 - 1996 Standards
* - the symbol does not appear in the Standard
[ Protection Relays Guide ] Contents 3
CONTENTS:
System Products..............................................................................................................................4
Overcurrent Protections...............................................................................................................6
MV Bay Protections.........................................................................................................................12
Motor Protections............................................................................................................................16
Generator Protections...................................................................................................................20
Line Distance Protections.............................................................................................................24
Line Differential Protections........................................................................................................29
Differential Protections for Transformers, Generators and Motors..............................32
Voltage Protections........................................................................................................................34
Busbar Protections.........................................................................................................................36
MV Changeover Automation.......................................................................................................38
Accessories........................................................................................................................................39
Services...............................................................................................................................................41
MV Network Automation / Easergy Range of Products.....................................................42
Network Analysers / Metering and Control Devices............................................................44
SEPAM Range of Protections.......................................................................................................46
Product Catalogue (DVD) / MiCOM S1 Studio Software..................................................48
Product Tables..................................................................................................................................49
Contact Details / Service Info-Line
PACiS
Protection, Automation & Control integrated Solution
CONTROL AND SUPERVISION SYSTEM FOR ELECTRICAL POWER SUBSTATIONS
PACiS Gateway
ACCESS GATEWAY
Application
• 4 doubled communication ports
• Interface between PACiS system bus and a
• Time synchronisation
dispatching centre
• Possibility of parallel operations (redundancy)
• Supervision of modes: remote/local,
Protection and Logic Control
„maintenance”
• Data acquisition, processing and transmission
• Computer without rotating components, power
• Self-diagnosis and monitoring of data transfers
supply within thresholds of safe voltage
• Communication in V.24 and 802.3 standards:
• Windows Embedded software
Slave DNP3, Modbus RTU, IEC 60870-5-101,
IEC 60870-5-104, GI74, OPC, Server/Client
IEC61850
Enhanced Efficiency
• Object including more than 50,000 pieces of data
• „Hot Redundancy” mode - takeover of supervision
functions (without data loss) by a backup computer
• Acquisition and archiving of 5,000 pieces of data per
second in real-time
• Acquisition and archiving of 1,000 measurements
per second in real-time
• Up to 12 data servers (redundant)
• Up to 64 graphic interfaces on the data servers
[ Protection Relays Guide ] Overcurrent Protections 6
Application Measurements
• Phase and earth fault overcurrent protections • Phase currents
applicable in HV and MV substations and to • Earth current
protect MV and LV transformers
Other Functions
Protections • 2 setting group
• P120: • Circuit breaker control
• Single-phase or earth fault overcurrent, 3-stage • CB status monitoring
DT or IDMT, co-operation with core balanced CT • Protection blocking logic
or in Holmgreen arrangement • Output contact latching
• P121: • Programmable binary inputs, outputs relays and
• 3-phase overcurrent, phase-to-phase, 3-stage, LEDs, 2 inputs / 4 outputs
DT or IDMT • Communication in RS485/RS232 standard
• Earth fault, 3-stage DT or IDMT, co-operation • Transmission protocols: Courier, Modbus,
with core balanced CT or in Holmgreen IEC60870-5-103 and DNP 3.0
Documents
arrangement • Recording of:
• Catalogue card
• Events - 250
• User manual
• Faults - 25 (1600 Hz, 3s window)
• Triggers - 25
• Trips - 5 (display)
Documents
• Catalogue card
• User manual
[ Protection Relays Guide ] Overcurrent Protections 7
MiCOM P122C
COMPACT OVERCURRENT PROTECTION RELAY
Functions: 50/51, 50N/51N, 37, 49, 46, 46BC, 50BF, 79, 74TCS, 50HS, CTS
Application
• Circuit breaker failure detection
• Utilities
• Blocking logic for reverse interlocking
• Industrial electrical networks
• Circuit breaker status monitoring
• HV and MV substations
• Trip circuit supervision
• MV and LV transformers
• Switch on to fault
• Cold load pick-up
Protection and Logic Control
• Output contacts testing mode
• 3 independent non-directional phase and earth
overcurrent thresholds
Measurements & Recording
• DT and IDMT curves
• IA, IB, IC, IN, Is1, Is2, Is2/Is1, f, Θ
• Thermal overload
• Rolling and peak phase current values
• Unbalance / Loss of phase
• Recording of events, disturbances and fault
• Loss of load
parameters
• Output contacts latching
• Broken conductor detection Documents
• Catalogue card
• User manual
MiCOM P116
OVERCURRENT PROTECTION RELAY DUAL-POWERED WITH CTs / AUXILIARY SUPPLY VOLTAGE
Functions: 50/51, 50N/51N, 37, 49, 46, 46BC, 50BF, 79, 74TCS
MiCOM P115
AUTONOMOUS OVERCURRENT PROTECTION RELAY
Functions: 50/51, 50N/51N, 37, 49, 46, 46BC, 50BF, 79, 74TCS
Application Measurements
• Phase and earth fault dual-powered overcurrent • Measurements accessible via communication
protection applicable in MV substations link (no display):
• Applicable in systems where auxiliary supply • Phase currents
voltage may be interrupted or lost • Earth current
• Auxiliary protection of HV/MV transformers
Other Functions
Interaction with Circuit Breaker • Autonomous operation: dual-powered supply
• Tripping a CB when powered by current from current circuits or/and Vx auxiliary voltage
transformers only, achieved by: • 2 setting groups
• cooperation with a current coil of the circuit • Circuit breaker failure detection
breaker, an optional piece of equipment for (undercurrent criterion)
modern CB’s, • Circuit breaker control from P115 front panel
• an energy output in P115 (24VDC 0,1J) to trigger or/and via RS485
a highly sensitive trip coil, an optional piece of • Circuit breaker state monitoring
equipment for modern CB’s, • Protection blocking logic from binary inputs
• cooperation with E124 capacitor trip unit, being (decentralised bus bar protection)
a separate product by Schneider Electric (an • Programmable digital inputs (2 inputs), output
application for CB’s of older types), relays (up to 4 outputs) and LEDs (6 LCD’s)
• an energy output in P115 (12VDC 0,02mJ) to • Communication standards: USB (local),
trigger an external striker coil (Striker K1 type RS 485 (remote)
- mechanical coupling with the CB), being a • Transmission protocols: Modbus, IEC60870-5-103
E124 separate product by Schneider Electric (an • Special current output for CB tripping coil
capacitor
trip unit
application for CB’s of older types). • Recording of:
• Events - 200 with time stamping
Protections • Faults - 20
• Overcurrent, against phase-to-phase faults,
2-stage, DT or IDMT
• Earth fault, 2-stage, DT or IDMT
• Overcurrent, against asymmetry, IDMT
• Auxiliary (AUX1 and AUX2), IDMT
Documents
• Catalogue card
• User manual
[ Protection Relays Guide ] Overcurrent Protections 9
MiCOM P114D
AUTONOMOUS OVERCURRENT PROTECTION RELAY
Functions: 50/51, 50N/51N
Application Measurements
• Phase and earth fault dual-powered overcurrent • Measurements accessible via communication
protection applicable in MV substations link (no display):
• Applicable in systems where auxiliary supply • Phase currents
voltage may be interrupted or lost • Earth current
• Auxiliary protection of HV/MV transformers
Other Functions
Interaction with Circuit Breaker • Autonomous operation: dual-powered supply
• Tripping a CB when powered by current from current circuits or/and Vx auxiliary voltage
transformers only, achieved by: • Protection criteria set with DIP-switches
• cooperation with a current coil of the circuit • I/O configuration with DIP-switch
breaker, an optional piece of equipment for or MiCOM S1 software
modern CB’s, • Circuit breaker control via RS485
• an energy output in P114D (24VDC 0,1J) to • Circuit breaker state monitoring
trigger a highly sensitive trip coil, an optional • Protection blocking logic from binary inputs
piece of equipment for modern CB’s, (decentralised bus bar protection)
• cooperation with E124 capacitor trip unit, being • Programmable digital inputs (2 inputs) and
a separate product by Schneider Electric output relays (up to 4 outputs)
(an application for CB’s of older types), • Communication standards: USB (local),
• an energy output in P114D (12VDC 0,02mJ) RS 485 (remote)
to trigger an external striker coil (Striker K1 type • Transmission protocols: Modbus, IEC60870-5-103
E124
- mechanical coupling with the CB), being a • Special current output to the CB tripping coil capacitor
separate product by Schneider Electric • Recording of: trip unit
(an application for CB’s of older types). • Events - 200 with time stamping via USB
• Faults – 20 via USB
Protections
• Overcurrent, against phase-to-phase faults,
2-stage, DT or IDMT
• Earth fault, 2-stage, DT or IDMT
Documents
• Catalogue card
• User manual
[ Protection Relays Guide ] Overcurrent Protections 10
MiCOM P125
DIRECTIONAL EARTH FAULT PROTECTION RELAY
Functions: 50N/51N, 67N, 32N, 59N
Application Measurements
• Phase and earth overcurrent protection • Earth current
applicable in MV and HV stations and to protect • Residual voltage
LV and MV transformers
MiCOM P111
UNIVERSAL OVERCURRENT PROTECTION RELAY
Functions: 50N/51N, 50/51, 67N/67YN, 26/38, 79
Application Features
• Thanks to its favourable „price vs technical • Operation in 1, 2, or 3-phase arrangement in
features” ratio, P111 may be used both in various types of networks
medium voltage and in low voltage applications • True RMS phase current value measurement
(specifically where communication facilities are within a frequency range from 10Hz to 250Hz
required). Detailed technical specifications and • Protections (see the Table below)
setting procedures for P111 are included in the • Possibility to configure protections: trip or signal
product’s user manual. • RS485 communication facility via Modbus Flush mounted version
The P111 series includes the following models: RTU protocol (option)
A, B, E, D, G, H, R. • Local or remote control of a contactor or circuit
Their features are enumerated in the Table below. breaker
• Independent programmable output relays (2 in
basic version + optionally 2 extra)
• Programmable NO output relays (P2, P3)
• Programmable binary inputs (S1-S2 and T1-T2
in basic version + optionally V1-C, V2-C, V3-C,
V4-C 35 mm DIN rail version
• LEDs to indicate protection triggering or tripping
• 4-digit LED display
• 5-button keypad to input settings and to Documents
configure protections • Catalogue card
• 2 types of case: flush or 35 mm DIN rail mounted • User manual
(R model is available in the flush version only)
Overcurrent Ip> (DT or IDMT) (Overload) X X X X X Output relays P3 (no) and P4 (c/o) X X X X X
Earth fault Io> (DT or IDMT) X X X X X X 2 binary inputs: S1-S2 and T1-T2 X X X X X X X
Earth fault Io>> (DT lub IDMT) X X X X X X 2 binary inputs: V1-C and V2-C X X X X X X
Earth fault directional Ifi (0-90) X X 2 binary inputs: V3-C and V4-C X
MiCOM P132
TIME-OVERCURRENT PROTECTION RELAY
Functions: 50/51, 50N/51N, 67, 67N, ADMIT, 37, 49, 46, 50BF, 79 (3), 32N, 27, 59, 47, 27D, 59N, 32R/32(F), 81O, 81U, 81R,
51V, 26/38 (R), 48, 50S/51LR, 66, 74TCS
Application Measurements
• Phase and earth overcurrent protections • Phase currents
applicable in MV and HV substations for both • Earth current
incoming and outgoing feeders and transformer • Phase and phase-to-phase voltages
applications • Power P, Q
• Auxiliary earth fault directional protection for HV • Energy: active, reactive
lines
Other Functions
Protections • Auto-reclosing control
• Overcurrent protection: • Circuit breaker failure detection
• DT, three-stage, separate circuits for phase • Switch on to fault protection
and residual currents, • Limit values monitoring
• IDMT, separate circuits for phase and residual • Interlocking
currents • 4 setting groups
• Thermal overload protection (thermal image) • Measuring circuit monitoring (voltage and current)
• Motor protection • Cold load pick-up logic
• Unbalance protection (negative sequence • Programmable scheme logic
current) • Freely configurable inputs / outputs / LEDs
• Under- and overvoltage • max 16 x I / 30 x O
• Short-circuit direction determination • 3 communication ports (optional)
• Ground fault direction determination - wattmetric • Communication protocols: IEC60870-103 / -101 /
and admittance Modbus / DNP 3.0 / IEC61850 (KEMA certified)
• Frequency: f, df/dt, Δf/Δt • Recording of:
• Faults – 8x200 events
Control Functions • Overload loads – 8x200 events
• Control and supervision of 3 switches • Ground faults – 8x200 events
• 6 configurable buttons • Disturbances – 8 waveforms (1kHz)
• Monitoring of extra signals and measurements • Circuit breaker monitoring
• Interlocking logic
• Over 80 pre-defined bay types
REMARK:
Voltage -dependent functions
(U>, U<, f<, f>, directionality
for I> and IN> ...) are available
for a version with measuring
voltage inputs
Documents
• Catalogue card
[ Protection Relays Guide ] MV Bay Protections 13
MiCOM P139
FEEDER MANAGEMENT AND BAY CONTROL
Functions: 50/51, 50N/51N, 50BF, 67, 67N, ADMIT, 37, 49, 79 (3), 32N, 27, 59, 47, 27D, 59N, 32R/32F (F), 81O, 81U, 81R, 51V,
26/38 (R), 48, 50S/51LR, 66, 25, 74TCS
Application Measurements
• One-box solution in MV and HV systems - a main • Phase currents
element of dissipated change-over automatics • Earth current
• Voltages
Protections • Power P, Q, S
• Short-circuit directional against phase-to-phase • Energy: active, reactive
faults, overcurrent, 3-stage DT and 1-stage IDMT • Thermal load
• Earth fault, directional
• Under- and overfrequency f, df/dt, Δf/Δt Other Functions
• Directional power motor protection with true • Autoreclose scheme
RMS value measurement • 4 setting groups
• Unbalance, checking of negative sequence • CB failure scheme
current • Programmable inputs/outputs /LEDs
• Thermal overload with 1 thermal time constant • max. 70 x I / 23 x O or
• Motor protection features (excessive start time, • 3 communication ports (option)
limitation of number of starts etc.) • Communication protocols: IEC 60870-103 /
• Admittance earth fault -101 / Modbus / DNP 3.0 / IEC 61850 (KEMA
• Under- and overvoltage certified)
• Switch onto fault protection • Recording of:
• Synchro-check (option) • Faults – 8 x 200 events
• Overload faults – 8 x 200 events
Control Functions • Ground faults – 8 x 200 events
• Control of 6 switches • Disturbances – 8 waveforms (1kHz)
• Monitoring of 10 switches • Circuit breaker monitoring
• Monitoring of extra signals and measurements
• Mimic diagram
• Interlocking logic
• More than 290 pre-defined bay types
REMARK:
Voltage -dependent functions
(U>, U<, f<, f>, directionality
for I> and IN> ...) are available
for a version with measuring
voltage inputs
Documents
• Catalogue card
• User manual
[ Protection Relays Guide ] MV Bay Protections 14
Measurements
• Phase currents
• Earth current
• Voltages
• Power P, Q, S
• Energy: active, reactive
• Thermal load
[ Protection Relays Guide ] MV Bay Protections 15
MiCOM P145
FEEDER MANAGEMENT RELAY WITH CONTROL FUNCTIONS
Functions: 50/51/67, 50N/51N/67N, YN/ADMIT, 49, 46, 46BC, 50BF, 32N, 27, 59, 59N, 74CTS, 81U/O, 81R, 32F, 51V,
64N/87N, VTS/CTS, 79, 25
Documents
• Catalogue card
• User manual
[ Protection Relays Guide ] Motor Protections 16
MiCOM P211
THREE-PHASE LV MOTOR PROTECTION RELAY
Functions: 50/51, 50N/51N, 37, 49, 46, 26/38 (P), 48, 50S/51LR
Application Measurements
• Comprehensive protection of LV motors. • Phase currents
• Replacement for RIz, RIzc, RIzx relays. • Thermal load
• Available models: A, B, C, U - see details in the • Earth current
catalogue card
Other Functions
Protections • Easy connection of motor feeders
• Overload - thermal image: • Pre-fault indication of overload
Flush mounted version • measurement of true RMS from 10 to 250Hz • Up to 4 programmable output relays
• nominal motor current setting from 0.37 do • Up to 4 programmable binary inputs
80A (direct wiring) • RS 485 with Modbus RTU protocol
• time constants specified through tripping time
setting at 6xIn current value
• Unbalance, loss of supply and loss-of-phase
condition
• Excessive starting time
• Locked rotor
• Over temperature (with PTC sensors)
35 mm DIN rail version • Underload with time delay setting
• Short circuit
• Earth fault protection
• Self motor restart after a voltage loss
on a substation busbar
• Limitation of the number of start-ups
Documents
• Catalogue card
• User manual
[ Protection Relays Guide ] Motor Protections 17
MiCOM P220
INTEGRATED PROTECTION & CONTROL SOLUTION FOR MOTOR MANAGEMENT
Functions: 50/51, 50N/51N, 37, 49, 46, 26/38 (RP), 48, 50S/51LR, 66
Application Measurements
• Comprehensive protection of LV/MV motors • Phase currents (up to 10th harmonic)
• Earth current
Protections • Thermal load
• Thermal overload with thermal image (logarithmic • Temperature
characteristic). Configuration of 3 thermal time
constants (starting, overload, cooling), 3 stages Other Functions
of thermal loading: alarm, trip and inhibition of • 2 setting groups
CB closing. • Switchgear monitoring
• Three-phase overcurrent against phase-to-phase • Trip statistics
faults; 1-stage • Analogue output
• Earth fault, 2-stage. Co-operation with core • Emergency start-up
balanced CT or three-phase CTs (Holmgreen • CB control
arrangement). • Programmable binary inputs, output relays and
• Excessive starting time. Overcurrent criteria. LEDs
Detection of the motor’s starting on the basis of • Communication standards: RS232, RS485
the starting current value or of a change in CB • Transmission protocols: Courier, Modbus,
status IEC60870-5-103
• Locked rotor while running or starting. • Recording of:
Overcurrent criteria • Events – 75
• Unbalance, loss of phase and single phasing. • Faults – 5 (1600 Hz, window 3s)
2-stage protection based on the negative • Starting current (40s)
sequence component of the current
• Loss of load. 1-stage. Undercurrent criteria.
Deactivated during start-up
• Temperature supervision. Co-operation with
6 RTD sensors (Pt, Ni, Cu) or 2 thermistors.
2-stage settings for each channel.
• Limitation of the number of successive start-ups.
Inhibition of CB closing after last unsuccessful
start-up. Separate settings for cold and hot start-
ups.
Documents
• Catalogue card
• User manual
[ Protection Relays Guide ] Motor Protections 18
MiCOM 225
INTEGRATED PROTECTION & CONTROL SOLUTION FOR MOTOR MANAGEMENT
Functions: 50/51, 50N/51N, 37, 49, 46, 50BF, 27, 59, 26/38 (P), 48, 50S/51LR, 66, ABS, 74TCS
Application Measurements
• Comprehensive MV motors protection with • Phase currents (up to 10th harmonic)
power and energy measurement • Earth current
• Voltages
Protections • Power P, Q, S
• Thermal overload with thermal image. • Energy: active, reactive
Configuration of 3 thermal time constants • Thermal load
(starting, overload, cooling), 3 stages of thermal • Temperature
loading: alarm, trip and inhibition of CB closing
• Three-phase overcurrent against phase-to-phase Other Functions
faults, 1-stage • CB failure
• Earth fault, 2-stage • 2 setting groups
• Excessive starting time. Overcurrent criteria • Switchgear monitoring
• Locked rotor while running or starting. • Trip statistics
Overcurrent criteria • 2 analogue output
• Unbalance, loss of phase and single phasing. • Emergency starting
2-stage protection based on negative sequence • CB control
component of the current • Programmable inputs, outputs and LEDs
• Loss of load. 1-stage. Undercurrent criteria • Communication standards: RS232, RS485
• Temperature supervision. Co-operation with 10 • Transmission protocols: Courier, Modbus,
RTD sensors (Pt, Ni, Cu) or 3 thermistors. IEC60870-5-103
• 2-stage setting for each channel. • Recording of:
• Limitation of the number of successive start-ups. • Events – 250
Separate settings for cold and • Fault – 25
Documents
• hot start-ups. Inhibition of CB closing after last • Disturbance – 5 (1600 Hz, window 2.5s)
• Catalogue card
unsuccessful start-up. Separate settings for cold • Starting current (200s)
• User manual
and hot start-ups • Starting voltage (200s)
• Undervoltage
• Anti-backspin protection
[ Protection Relays Guide ] Motor Protections 19
Protections Measurements
• Motor differential (P243) • Phase currents (up to 10th harmonic)
• Thermal overload with thermal image. 3 thermal • Earth current, voltages
time constants (starting, overload, cooling) • Power P, Q, S
• Three-phase overcurrent against phase-to-phase • Energy: active, reactive
faults, 2-stage • Thermal load
• Earth fault, directional, 2-stage, overcurrent, DT • Temperature
or IDMT Other Functions
• Residual overvoltage • 2 setting groups
• Wattmetric earth fault (for Petersen coil earthed • Switchgear monitoring
system) • Trip statistics
• Excessive starting time. Overcurrent criteria • Emergency starting
• Locked rotor while running or starting. • CB control
Overcurrent criteria • Programmable inputs (256 AND/OR gates and
• Unbalance, loss of phase and single phasing, timers), output relays and LEDs
2-stage protection based on negative sequence • 8 x I / 7 x O (P241)
component of the current • 16 x I / 14 x O (P242, P243)
• Loss of load; 2-stage, underload criteria • Communication standards: RS232/RS485
• Temperature supervision. Co-operation with 10 • Transmission protocols: Courier, Modbus,
RTD sensors (Pt, Ni, Cu); 2-stage setting for each IEC 60870-5-103, DNP3.0, IEC61850
channel (KEMA certified)
• Limitation of the number of successive start-ups. • Dual redundant Ethernet: RSTP, DHP, SHP
Separate settings for cold and • Recording of:
• hot start-ups. Inhibition of CB closing after last • Events – 512
unsuccessful start-up. Separate settings for cold • Faults – 20 (1200Hz, window 10.5s)
and hot start-ups
• Under- / overvoltage
• Anti-Backspin protection
• Out of step (monitoring of cos ϕ)
• Reverse power
• Underfrequency
• Loss of field
Documents
• Catalogue card
• User manual
[ Protection Relays Guide ] Generator Protections 20
MiCOM P341
INTERCONNECTION PROTECTION FOR EMBEDDED GENERATOR
Functions: 50/51, 50N/51N, 67, 67N, 49, 46, 50BF, 27, 59, 59N, 32R/32F, 32O, 32L, 81O, 81U, 81R, VVS, 64N/87N, 60/VTS, 25, DLR
Documents
• Catalogue card
• User manual
[ Protection Relays Guide ] Generator Protections 21
Application Measurements
• Medium and high power generators • Phase currents and voltages
• Unit protections for high-power turbine • Sequence current and voltage, neutral
generators current and voltage
• Protections for pumped-storage water power • Differential and bias currents
plants • 3rd harmonic neutral voltage
• Power: P, Q, S; energies: Ec, Eb
Protections • Temperature in °C
• Generator/Transformer differential - only
P343/4/5 models Other Functions
• Rotor earth fault protection (P391 auxiliary unit) • Frequency tracking: from 5 Hz to 70 Hz
• Interturn protection • Supervision of voltage and current
• 100% stator earth fault, 3 harmonic analysis - transformer circuits
only P343/4/5 models and 20Hz generator (P345) • Diagnostics and continuous self-monitoring
• Non-directional phase overcurrent • Communication standards: RS232, RS485
• Non-directional earth fault • Optional transmission protocols: Courier,
• Neutral displacement Modbus, IEC60870-5-103, DNP 3.0,
• Sensitive directional earth fault IEC61850 (KEMA certified)
• Restricted earth fault • Dual redundant Ethernet: RSTP, DHP, SHP
• Voltage dependent overcurrent or under- • Programmable inputs (logic - 256 AND/OR
impedance gates and timers), output relays and LEDs
• Under- / overvoltage • P342 - 8 x I / 7 x O
• Under- / overfrequency • P343 - 16 x I / 14 x O
• Reverse power, low forward load and overload • P344 - 16 x I / 14 x O
• Loss of field • P345 - 24 x I / 24 x O
• Unbalance load • Extra I/O card - option
• Overfuxing • Recording of:
• Accidental energisation at standstill - only • Events – 512
P343/4/5 models • Faults – 5
• Resistance temperature devices 10 RTDs - • Disturbance waveforms – 20
option (max. window 10.5 s)
• CLIO analogue measurements
• Frequency rate of change
• Check synchronism
Documents
• Catalogue card
• User manual
[ Protection Relays Guide ] Generator Protections 22
MX3EG1A
NUMERICAL MODULE FOR AUTOMATIC GENERATOR SYNCHRONISING
Functions: 25
MX3PG2A
INTEGRATED NUMERICAL GENERATOR PROTECTION (ROTOR PROTECTION)
Functions: 64R, 27DC, 59DC, 50/51
Application Measurements
• HV line protection • Phase currents
• Earth current
Protections • Phase and phase-to-phase voltages
• Distance protection: • Power: P, Q
• circular or polygonal curve • Energy: active, reactive
• 6 distance stages
• 7 direction stages Other Functions
• 8 timer stages • Auto-reclosing control:
• start-ups: overcurrent, undervoltage and unde- • (3-phase) – P433
rimpedance • (1/3-phase) – P435
• directional voltage memory • Circuit breaker failure protection
• Time-overcurrent protection: • Switch on to fault protection
• backup (active when measuring circuit failure • Limit values monitoring
is detected) • Interlocking
• DT, 4-stage, separate for phase and residual • 4 setting groups
currents • Measuring circuit monitoring (voltage and
• IDMT, separate for phase and residual currents current)
• Under- / overvoltage protection • Programmable scheme logic
• Earth fault, wattmetric protections • Programmable inputs / outputs / LEDs
• Frequency protection: f /df/dt / Δf/Δt • max 16 x I / 30 x O (P433/P435-40TE)
• Power-directional protection • max 28 x I / 46 x O (P435-84TE)
• Thermal overload protection • Analogue I/O module (option)
• Directional earth fault • 3 communication ports (option)
• PSB Power Swing Blocking • Communication protocols:
IEC 60870-103 / -101 / Modbus / DNP3.0 /
Control Functions IEC61850 (KEMA certified)
• 6 configurable buttons • Recording of:
• Faults – 8x200 signals
• Overload faults – 8x200 signals
• Earth faults – 8x200 signals
• Disturbances – 8 waveforms (1kHz)
• Circuit breaker monitoring
• Synchro-check (option)
• Power swing blocking
Documents
• Catalogue card
• User manual
[ Protection Relays Guide ] Line Distance Protections 25
MiCOM P437
NUMERICAL DISTANCE PROTECTION
Functions: 50/51, 50N/51N, 67N, 49 ,50BF, 79, 27, 59, 59N, 32R/32F (F), 81O, 81U, 81R, 21, 78, 26/38 (R), 25, 74TCS
Application • Power: P, Q
• Line protection for HV systems
Other Functions
Protections • Auto-reclosing control (1/3-phase)
• Distance protection: • Synchro-check (option)
• circular or polygonal curve • Power swing blocking
• 6 distance stages • Mutual compensation (option)
• 7 direction stages • Circuit breaker failure
• 8 timer stages • Switch on to fault protection
• start-ups: overcurrent, undervoltage and unde- • Limit values monitoring
rimpedance • Intertripping for distance protection
• directional voltage memory • Intertripping for earth fault protection
• Time-overcurrent protections: • 4 setting groups
• backup (active when measuring circuit failure • Measuring circuit monitoring (voltage
is detected) and current)
• DT, 4-stage, separate for phase and residual • Programmable scheme logic
currents • Programmable inputs / outputs / LEDs
• IDMT, separate for phase and residual currents • max 28 x I / 46 x O
• Under- / overvoltage • Analogue I/O module (option)
• Frequency protection: f, df/dt, Δf/Δt • 3 communication ports (option)
• Thermal overload protection • Communication protocols: IEC60870-
• Earth fault protection 103 / -101 / Modbus / DNP 3.0 /
IEC61850 (KEMA certified)
Control Functions • Recording of:
• 6 configurable buttons • Faults – 8x200 signals
• Overload faults – 8x200 signals
Measurements • Earth faults – 8x200 signals
• Phase currents • Disturbances – 8 waveforms (1kHz)
• Earth current • CB monitoring
• Phase and phase-to-phase voltages
Documents
• Catalogue card
• User manual
[ Protection Relays Guide ] Line Distance Protections 26
MiCOM P432
DISTANCE PROTECTION AND BAY CONTROL
Functions: 21P, 50/51, 50N/51N, 67, 67N, 46, 46BC, 50BF, 79 (3) (1), 27, 59, 51V, 78, 25, 60/VTS
Application Measurements
• HV line protection • Phase currents
• Earth current
Protections • Phase and phase-to-phase voltages
• Distance protection: • Power P, Q
• circular or polygonal curve
• 6 distance stages Other Functions
• 7 direction stages • Auto-reclosing control (1/3-phase)
• 8 timer stages • Synchro-check (option)
• start-ups: overcurrent, undervoltage and unde- • Power swing blocking
rimpedance • Mutual compensation (option)
• directional voltage memory • Circuit breaker failure
• Time-overcurrent protections: • Switch on to fault protection
• backup (active when measuring circuit failure • Limit values monitoring
is detected) • Intertripping for distance protection
• DT, 4-stage, separate for phase and residual • ntertripping for earth fault protection
currents • 4 setting groups
• IDMT, separate for phase and residual currents • Measuring circuit monitoring (voltage and
• Under- / overvoltage current)
• Frequency protection: f, df/dt, Δf/Δt • Programmable scheme logic
• Thermal overload protection • Programmable inputs / outputs / LEDs
• Earth fault protection • max 28 x I / 46 x O
• Analogue I/O module (option)
Control Functions • 3 communication ports (option)
• Control of 6 switches • Communication protocols: IEC60870-103 / -101
• Monitoring of 10 switches / Modbus / DNP 3.0
• Monitoring of extra signals and measurements • Recording of:
• Mimic diagram • Faults – 8x200 signals (1 kHz)
• Interlocking logic • Overload faults – 8x200 signals
• More than 290 configurable bay types • Earth faults – 8x200 signals
• Disturbances – 8 waveforms (1kHz)
• Circuit breaker monitoring
Documents
• Catalogue card
[ Protection Relays Guide ] Line Distance Protections 27
Documents
• Catalogue card
• User manual
[ Protection Relays Guide ] Line Distance Protections 28
MiCOM P521
CURRENT DIFFERENTIAL PROTECTION
Functions: 87L, 87T, 50/51, 50N/51N, 46, 46BC, 50BF, 37, 74TCS
Documents
• Catalogue card
• User manual
[ Protection Relays Guide ] Line Differential Protections 30
Documents
• Catalogue card
• User manual
[ Protection Relays Guide ] Line Differential Protections 31
Documents
• Catalogue card
• User manual
[ Protection Relays Guide ] Differential Protections for Transformers, Generators and Motors 32
MiCOM P532
LINE DIFFERENTIAL PROTECTION AND CONTROL DEVICE
Functions: 87L, 50/51, 50N/51N, 50BF, 67, 67N, ADMIT, 49, 79 (3), 32N, 27, 59, 47, 27D, 59N, 32R/32F (F), 51V, 26/38 (R), 46, 25, 74TCS, CTS/VTS, FL
Application Measurements
• Selective and sensitive protection of overhead • Differential and restraining current
and cable lines • Angles between local and remote currents
• One-box solution with optional bay controller (separate for each of the 3 phases)
in MV systems • Local and remote phase currents
• Earth current
Protections • Voltages
• Line current differential • Power P, Q, S
Option with graphic HMI • Directional phase-phase overcurrent, 3-stage • Energy: active, reactive
IDMT and 1-stage DT • Thermal state
• Directional earth fault
• Directional, active and reactive power Other Functions
• Unbalance, check of the negative sequence • Autoreclose function
current • 4 setting groups
• Thermal overload with 1 thermal time constant • CB failure scheme
• Admittance earth fault • Circuit breaker monitoring
• Under- / overvoltage • Programmable inputs / outputs / LEDs
• Switch onto fault protection • Max of 46 x I / 30 x O
• Synchro-check (option) • 3 communication ports (option)
• Communication ports: IEC 60870-103 / -101/
Control Functions (IED with graphic HMI) Modbus / DNP 3.0 / IEC 61850 (KEMA certified)
• Control of 6 switches (IED with graphic HMI) • Recording of:
• Monitoring of 10 switches (IED with graphic HMI) • Faults – 8x200 events
Option with text HMI • Control and monitoring of 3 switches (IED with • Overload faults – 8x200 events
text HMI – 6I6O module required) • Ground faults – 8x200 events
• More than 290 pre-defined bay types • Disturbances – 8 waveforms (1kHz)
• Check of extra signals and measurements
• Mimic diagram
• Interlocking logic
[ Protection Relays Guide ] Differential Protections for Transformers, Generators and Motors 33
Application Measurements
• Differential protection with supplementary • Differential and restraining currents
functions for transformers, motors and • Phase currents (separate for each phase and
generators each end of the protected unit)
• Earth current (separate for each end of the
Protections protected unit)
• Differential: • Phase shifts between phases
• amplitude and vector group matching • Phase shifts between the same phases of
• zero-sequence current filtering for user-selec- different ends in the protected unit
ted winding(s) • Voltages (P632/3/4)
• inrush restraint (2nd harmonic)
• overfluxing restraint (5th harmonic) Other Functions
• saturation discriminator • Limit values monitoring
• MiCOM P631: 2 ends • 4 setting groups
• MiCOM P632: 2 ends • Programmable scheme logic
• MiCOM P633: 3 ends • Programmable inputs / outputs / LEDs
• MiCOM P634: 4 ends • Analogue I/O module (option)
• Restricted earth-fault, separate for each end of • 3 communication ports
the protected unit (P632/3/4) • Communication protocols: IEC60870-103 / -101
• Overcurrent: DT or IDMT, 3-stage, separate for / Modbus / Courier / DNP 3.0 / IEC61850
phase and residual currents (KEMA certified)
• Io calculated or measured (P632/3/4) • Recording of:
• Thermal overload (for 2 ends) • Disturbances – 8 waveforms (1kHz)
• Frequency: f, df/dt, Δf/Δt (P632/3/4) • Overload faults – 8x200 signals
• Overfluxing U/f • Faults – 8 x 200 signals
Control Functions
• Control and monitoring of 3 switches
• 6 configurable function keys
• Check of extra signals and measurements
• Interlocking logic
• More than 80 pre-defined bay types
•
Documents
• Catalogue card
• User manual
[ Protection Relays Guide ] Voltage Protections 34
MiCOM P132
VOLTAGE PROTECTION WITH LOAD SHEDDING SCHEME
Functions: 27, 59, 47, 27D, 59, 59N, 81O, 81U, 81R, Δf/Δt
Measurements
Documents • Phase voltages
• Catalogue card • Phase-to-phase voltages
• User manual • Positive, negative and zero-sequence voltages
MiCOM P921
VOLTAGE PROTECTION RELAY
Functions: 27, 59, 59N
Documents
• Catalogue card
• User manual
[ Protection Relays Guide ] Voltage Protections 35
Documents
• Catalogue card
• User manual
Application Measurements
• All application where accurate frequency • Voltages
monitoring is required for system stability • Frequencies
• Load shedding scheme and autoreclose
functionality afterwards Other Functions
• 4 setting groups
Protections • Load shedding scheme, 6-stage
• Under- / overfrequency • Trip statistics
• 6-stage, 4 measuring criteria: • Programmable inputs (logic 250 AND/OR gates
• check of frequency, time-delayed and timers), output relays and LED diodes
• change of frequency rate df/dt, time-delayed • P941: 8 x I / 7 x O
• frequency supervision vs. change of frequency • P943: 16 x I / 14 x O
rate f+df/dt, instantaneous • Communication standards: RS232, RS485
• frequency supervision vs. mean rate of frequ- • Another RS232/RS485 port as an option
ency change f+Δf/Δt, instantaneous • Transmission protocols: Courier, Modbus,
• Abnormal operation of a generator; check of IEC60870-5-103, DNP 3.0
frequency changes within a timeframe, in 4 • Recording of:
bands • Events – 512
• Under- / overvoltage, 2-stage. IDMT and DT. • Faults – 20 (1200Hz, window 10.5s)
• Extra I/O modules Documents
• 6-stage autoreclose after load shedding scheme • Catalogue card
• User manual
[ Protection Relays Guide ] Busbar Protections 36
Documents
• Catalogue card
• User manual
[ Protection Relays Guide ] Busbar Protections 37
MiCOM P746
NUMERICAL BUSBAR PROTECTION RELAYS WITH CB FAILURE PROTECTION - CENTRALISED
Functions: 87BB/P, 87BB/N, 87CZ, 50/51, 50N/51N, CTS, VTS, 50BF
Documents
• Catalogue card
[ Protection Relays Guide ] MV Changeover Automation 38
Hardware
• Changeover scheme utilises programmable logic On the basis of the state of a bus coupler CB,
of MiCOM P132 (or MiCOM P139) relay. For the the P13x selects a type of back-up supply con-
relays description see page 12 and 13 of this figuration. Accordingly, a changeover scheme
Guide. mode and a sequence of control operations are
chosen automatically. The device may be pro-
Principles of Operation grammed to operate both in 1-shot changeover
Two scheme configurations are possible: scheme and in return changeover scheme.
• Information on primary voltage interruption is The scheme can be blocked by:
sent from voltage relays (e.g. MiCOM P921) • external signals, sent to binary inputs from
located in measuring bays to binary inputs of other controllers or functional relays, located in
a P13x relay, which initiates the course of the other bays
changeover scheme. During the course of the • internal signals, sent from an integrated facility
scheme the P13x performs several control which monitors the switching state, or after a
operations (opening and closing CBs), using successfully completed scheme
its auxiliary output relays and binary inputs. A • a system of higher level.
manner to initiate the scheme can be selected by • If no protection relay is required in a bus
a user out of the following options: coupler bay, the P13x utilises its binary inputs
• on energising of a binary input of the device, and output relays only, whereas its protection
assigned to an output relay of undervoltage facilities are disabled.
facility in the measuring bay • There are 2 MiCOM P13x devices installed in
• on tripping of a protection relay in a transfor- parallel in 2 feeder bays. In such a case the
mer bay, having confirmed a change of CB relays perform several protection functions for
Documents state in the primary supply bay feeder lines, apart from the changeover scheme
• Catalogue card • remotely, on sending a system command. features described above.
• User manual
MiCOM E124
CAPACITOR TRIP UNIT
Documents
• Catalogue card
MiCOM P891
CIRCUIT BREAKER TRIP / CLOSE MODULE
Documents
• Catalogue card
[ Protection Relays Guide ] Accessories 40
P993
Documents
• Catalogue card
MiCOM P594
GPS SYNCHRONIZING UNIT
Documents
• Catalogue card
Services
• The services offered constitute a substantial Repairs
part of business activities run by Schneider • Equipment reparations
Electric Energy Poland Sp. z o.o. in the area of • Lending of replacement products for the repair
Protections and Systems. Being a global player period
in the sectors of energy generation, transmission • Efficient troubleshooting
and distribution for power industry and industrial • Modernisation of legacy solutions
power plants, we are offering a servicing scheme
customised to meet individual customers’ Installation Retrofit
requirements. • Maximum efficiency at minimum costs
• Maintenance and Technical Support
Consulting and Expertise • Technical aid and assistance on a customer’s
• Technical support site
• Application counselling • Spare parts stock
• Assistance in selection, input and modification of • Maintenance of equipment
settings
Spare Parts
Installation and Commissioning • Offer of supplies of necessary parts and
• A team of professionals trained in handling our components
products installed on sites
Training Sessions
• Related to products
• Related to commissioning operations
• As per customer’s requests
[ Protection Relays Guide ] MV Network Automation / Easergy Range of Products 42
Easergy T200I
MV AND MV/LV SUBSTATION CONTROL UNIT WITH TELECONTROL INTERFACE TO SCADA SYSTEMS
Flair200C
DIRECTIONAL INDICATOR OF FAULT PASSAGE WITH RTU FUNCTIONALITY
AND REMOTE COMMUNICATION FOR CABLE NETWORKS
SEPAM
SEPAM Range of Protections
SEPAM
SEPAM Range of Protections
Content Application
• The CD Catalogue covers information • MiCOM S1 Studio is a universal
regarding products made by Schneider protection relay support software which
Electric Energy Poland Sp. z o.o. and enables global access to all data stored
offered in Poland by the Automation & in the relays. The program provides
Information Systems Unit in Swiebodzice. easy access to MiCOM protections of
• A complete offer of MiCOM protection Px20, Px30 and Px40 series, as well as
relays, as well as of time, measuring and to other types of devices.
insulation monitoring relays.
• Possibility to search by product or by a Main Functions
range of operating voltage • One, common program for MiCOM
• Special publications for designers present Px20, Px30 and Px40 relays to
potential uses of the relays, application configure devices and record data
models and possibilities of replacement of • The devices and files can be arranged
legacy products with modern solutions. in accordance with a topology system
- Substation / Voltage Level / Bay. A
Documentation graphical representation of the system
• The CD contains digital documents is displayed in the Explorer’s separate
related to the protections. Those can be window and helps a user to navigate
a catalogue card and/or user manual, the system.
depending on a selected device. • Configuration files upload and
download
• Acquisition of events and disturbances
and analysis of the recorded data
• Real-time visualisation of measurements
• PSL Editor to edit programmable
scheme logics
• Menu text editor
• Bay type configurator
• Configurator of IEC 61850 transmission
in the relays
• Possibility to export configuration files
in CSV format (comma-separated
values) to a spreadsheet or an
application such as CAPE
Page No. 11 9 8 7 6 6 6 7 6 10 10 10 17 18 29 34 35 35
Revision A_2011
Function symbols in accordance with
ANSI / IEEE Std C37.2 - 1996 Standards
MiCOM P111
MiCOM P114
MiCOM P115
MiCOM P116
* - the symbol does not appear in the Standard
MiCOM P211
MiCOM P121
MiCOM P122
MiCOM P123
MiCOM P126
MiCOM P127
MiCOM P220
MiCOM P225
MiCOM P521
MiCOM P821
MiCOM P921
MiCOM P922
MiCOM P923
MiCOM P124S
MiCOM P122C
MiCOM P124D
MiCOM P120_1p
MiCOM P125_1p
Main Protection Functions ANSI Code P10 P20
Non-directional phase overcurrent 50/51
Non-directional earth fault 50N/51N
Directional phase overcurrent 67
Directional earth fault 67N
Admittance earth fault 67YN
Phase undercurrent / Loss of load 37
Thermal overload 49/51
Negative phase sequence thermal_I2 / Unbalance load 46
Broken conductor detection 46BC
[ Protection Relays Guide] Product Tables
Revision A_2011
Function symbols in accordance with
ANSI / IEEE Std C37.2 - 1996 Standards
* - the symbol does not appear in the Standard
MiCOM P132
MiCOM P139
MiCOM P433
MiCOM P435
MiCOM P437
MiCOM P439
MiCOM P532
MiCOM P631
MiCOM P632
MiCOM P633
MiCOM P634
MiCOM P130C
MiCOM P430C
MiCOM P530C
MiCOM P630C
Main Protection Functions ANSI Code P30
Revision A_2011
Function symbols in accordance with
ANSI / IEEE Std C37.2 - 1996 Standards
MiCOM
MiCOM
* - the symbol does not appear in the Standard
P741/2/3
P443Mho
MiCOM P141
MiCOM P142
MiCOM P143
MiCOM P145
MiCOM P241
MiCOM P242
MiCOM P243
MiCOM P341
MiCOM P342
MiCOM P343
MiCOM P344
MiCOM P345
MiCOM P441
MiCOM P442
MiCOM P444
MiCOM P446
MiCOM P445
MiCOM P541
MiCOM P542
MiCOM P543
MiCOM P544
MiCOM P545
MiCOM P546
MiCOM P547
MiCOM P746
MiCOM P841
MiCOM P941
MiCOM P943
Główna funkcje zabezpieczeniowe ANSI Code P40
Non-directional phase overcurrent 50/51
Non-directional earth fault 50N/51N
Directional phase overcurrent 67
Directional earth fault 67N
One sensitive earth fault admittance stage 67YN
Phase undercurrent / Loss of load 37
Thermal overload 49
Negative phase sequence thermal_I2 / Unbalance
46
load
Broken conductor detection 46BC
Circuit breaker failure 50BF
Multi-shot autoreclose (3 – 3 phase trip, 1 - 1 &
79 3 3 3 1 1 1 1 3 1
3 phase trip)
Wattmetric earth fault 32N // 67W
Phase undervoltage 27
[ Protection Relays Guide] Product Tables
Phase overvoltage 59
Negative sequence overvoltage _ U2 47
Positive sequence undervoltage _ U1 27D
Residual overvoltage / Neutral displacement _ Uo 59N
100% stator earth fault (3 harm.)_neutral //
27TN // 59TN
terminal
100% stator earth fault (20 Hz generator) 64S
Differential _ current_ G / L / M / T_ phase_PC 87 M G G G L L L L L L L SZ SZ
Reverse power_R // Directional power _ F (3 ph
32R
measure)
Overpower 32O
Low forward power 32L
Overfrequency 81O
Underfrequency 81U
Rate of change of frequency _ df/dt / ROCOF / 81R
Turbine abnormal frequency 81AB
Voltage vector shift _ dU > VVS *
Loss of field 40
Overfuxing_U/Hz 24
Voltage dependent overcurrent 51V
Underimpedance / Impedance / Distance 21
Restricted earth fault (differential) 64 // 87N
Interturn (Split Phase) 50DT
Rotor earth fault 64R
Unintentional energisation at standstill // Dead
50 / 27
machine
Pole slipping_Power swings 78 / 68
Temperature detectors 26 / 38
Excess long start 48
Locked rotor at start // Satalled rotor 51LR // 50S
Start number 66
Out of step 55
Anti Back Spin 25
Check synchronising 74CTS
Trip Circuit Supervision FL*
Fault locator 50HS
51
Manufacturing of
MiCOM Px30, Px40 series.
58-160 Świebodzice time to time, please ask for confirmation of the information
give in this publication.
ul. Strzegomska 23/27
tel. 74 854 84 10
Publishing: Schneider Electric Energy Poland Sp. z o.o.
fax 74 854 86 98
Design: Schneider Electric Energy Poland Sp. z o.o.
[email protected]
Printing: Schneider Electric Energy Poland Sp. z o.o.
www.schneider-energy.pl