EEE20005-week 2 3
EEE20005-week 2 3
and Technology
5
Introduction to transformers (cont.)
• Besides wide applications in power systems for
changing voltage levels, transformers can also be
used in AC/DC adapter,
• Instrument (measuring
high voltage, e.g. 500kV or
high current, e.g. 10kA).
6
The ideal transformer
• An ideal transformer is a lossless device with an input
winding (Np) and an output winding (Ns) as shown in Fig. 2-4.
• The relationship between input voltage and output voltage as
well as input current and output current, are given by two
simple equations:
V p (t ) Np Np
Vs (t ) Ns (2-1) Ns (2-2)
i p (t ) Ns 1
(2-3)
is (t ) N p
7
Fig. 2-4
The ideal transformer (cont.)
-dot convention
• The dot convention is
adopted to identify the
polarity of the voltage
and current on the
secondary side.
Z L' 2 Z L (2-15) 10
Theory of operation of a real
single-phase transformer
• To understand the operation of a real transformer,
refer to Fig. 2-8, it consists of two coils (windings)
wrapped around a transformer core.
• The winding at the primary side of the transformer is
connected to an AC power source, and the winding
at the secondary side is open circuit. The hysteresis
curve of the transformer is shown in Fig. 2-9.
1 (2-18)
VP (t )dt
N
16
The voltage ratio across
a transformer (cont.)
• There is a similar division of flux in the secondary winding
between mutual flux and leakage flux which passes through
the secondary winding but returns through the air,
S M LS (2-20)
where S is total average secondary flux
M is flux component linking both
primary and secondary coils
LS is secondary leakage flux
17
The voltage ratio across
a transformer (cont.)
• With the division of the average primary flux into
mutual and leakage components, Faraday’s law for
the primary circuit can be re-expressed as
d P d M d LP
v p (t ) N p Np Np (2-21)
dt dt dt
v p (t ) e p (t ) eLP (t ) (2-22)
• The voltage on the secondary coil can also be
expressed in terms of Faraday’s law as
d S d M d LS
vs (t ) N s Ns Ns
(2-23)
dt dt dt
vs (t ) es (t ) eLS (t ) (2-24) 18
The voltage ratio across
a transformer (cont.)
• The primary voltage due to the mutual flux is
given by d M
e p (t ) N p (2-25)
dt
and the secondary voltage due to the mutual flux
is given by d M
es (t ) N s (2-26)
dt
• From these two relationships, we have
e p (t ) d M es (t )
Np dt Ns
e p (t ) Np
• Therefore, (2-27)
es (t ) Ns 19
The voltage ratio across
a transformer (cont.)
e p (t ) Np
es (t ) Ns
• This equation means that the ratios of the primary
voltage caused by the mutual flux to the secondary
voltage caused by the mutual flux is equal to the
turn ratio of the transformer. M LP
• Since in the well-designed transformer,
M LS
VM VM
sin t cos(t 900 )(Wb)
N p N p
Fig. 2-11 22
(2-29)
The magnetization current
in a real transformer (cont.)
1 1 VM
Np v p ( t ) dt
Np VM cos tdt
N p
sin t
VM 2Vrms
m
N p N p
N p m 2 fN p m
Vrms 4.44 fN p m
2 2
Fnet N p i p N s is
(2-32) Fig. 2-14 27
The current ratio on
a transformer (cont.)
Fnet N p i p N s is
where is the reluctance of the transformer core. Because
the reluctance of a well-designed transformer core is very
small (nearly zero), the relationship between the primary
and secondary currents is approximately l
Fnet N p i p N s is 0 (2-33) A
as long as the core is unsaturated.
• Thus,
N p i p N s is (2-34)
or ip Ns 1
(2-35)
is Np
28
Assumptions to convert a real
transformer into an ideal transformer
• The assumptions to convert a real transformer into an
ideal transformer described previously are shown as
follows:
1. The core must have no hysteresis or eddy currents.
2. The magnetization curve must have the shape shown in Fig.
2-15. Notice that for an unsaturated core, the net MMF=0,
implying that N p i p N s is
3. The leakage flux in the core must be zero
implying that all the flux in the core
couples both windings.
4. The resistance of the transformer windings
must be zero. Fig. 2-15
29
The equivalent circuit of
a real transformer
• If we want to build a model for a real transformer,
all previous imperfection should be taken into
account in the model to describe behaviors of the
real transformer.
• These major imperfection items to be considered
in the construction of such a model are:
1. Copper (I2R) losses. Copper losses are the
resistive heating losses in the primary and
secondary windings of the transformer.
2. Eddy current (V2/R) losses. Eddy current losses
are resistive heating losses in the core of the
transformer. 30
The equivalent circuit of
a real transformer (cont.)
i p (2-37a) e (t ) N d LP
Np
LP N pi p LP
LP p
dt
iS (2-37b) e (t ) N d LS
NS
LS N S iS LS
LS S
dt 33
The exact equivalent circuit
of a transformer (cont.)
• Substitute eq.(2-37) into eq.(2-36)
d NP N P2 diP
eLP (t ) N p ( iP ) (2-38a)
dt dt
d NS N S2 diS
eLS (t ) N S ( iS ) (2-38b)
dt dt
• The constants in these eqs. can be lumped together,
diP
eLP (t ) LP (2-39a)
dt
diS
eLS (t ) LS (2-39b)
dt 34
The exact equivalent circuit
of a transformer (cont.)
diP diS
eLP (t ) LP eLS (t ) LS
dt dt
where PL N P / is the self-inductance of the
2
Fig. 2-16
36
The exact equivalent circuit
of a transformer (cont.)
• Fig. 2-17a shows the equivalent circuit referred
to its primary side while Fig. 2-17b shows the
equivalent circuit referred to its secondary side.
37
Fig. 2-17
Approximate equivalent circuit
of a transformer
• The transformer models shown below are often more
complex than necessary in order to get good results in
practical engineering applications.
• One of the major problems is that the excitation branch of
the model adds another node to the circuit being analyzed,
making circuit solution more complex than necessary.
• The excitation branch has a very small current compared to
the load current of the transformers. In fact, it is so small
under normal circumstances it causes a completely
negligible voltage drop cross Rp and Xp.
38
Approximate equivalent circuit
of a transformer (cont.)
• Thus, a simplified equivalent circuit can be produced
by moving the excitation branch to the front of the
transformer, and the primary and secondary
impedances are left in series with each other.
39
Approximate equivalent circuit
of a transformer (cont.)
• These impedances are just added, creating the
approximate equivalent circuit in Fig. 2-18a and b.
Fig. 2-18 40
Approximate equivalent circuit
of a transformer (cont.)
• In some applications, the excitation branch may be
neglected entirely without causing serious errors. In
these cases, the equivalent circuit of the transformer
reduces to the simple circuits in Fig. 2-18c and d.
Fig. 2-18
41
Determining the values of
components in transformer model
• We can determine the values of the components in the
equivalent circuit by conducting the open-circuit test (OCT)
and the short-circuit test (SCT) on a transformer.
• In the OCT, a transformer’s secondary winding is open-
circuited, and its primary winding is applied to the rated
voltage of the transformer (see Fig.2-19).
Fig.2-19 42
Determining the values of components
in transformer model (cont.)
• For the OCT, the input voltage, current and real
power to the transformer are measured, Rc and XM
can be found as follows.
• Measured values: Voc, I oc, Poc
Poc Voc2 / Rc
Rc Voc2 / Poc (2-40a)
I Rc Voc / Rc (2-40b)
I X M I oc2 I R2c (2-40c)
X M Voc / I X M (2-40d)
43
Determining the values of components
in transformer model (cont.)
• In the SCT, the transformer’s secondary terminals
are shorted-circuited, and primary terminal is applied
to the voltage until the current is equal to the chosen
current or its rated current (see Fig.2-20).
Fig.2-20
44
Determining the values of components
in transformer model (cont.)
• For the SCT, the input voltage, current and real
power to the transformer are measured too.
Leakage reluctance Xeqp and winding resistance
Reqp can be determined as follows.
• Measured values:
Vsc, I sc, Psc
Psc I sc2 Reqp
Reqp Psc / I sc2 (2-41a)
Z scp Vsc / I sc (2-41b)
X eqp Z scp
2
Reqp
2
(2-41c) 45
Example 2-2
• The equivalent circuit impedances of a 20kVA,
8000/240V, 60Hz transformer are to be determined.
The open-circuited test and the short-circuit test
were performed on the primary side of the
transformer, and the following data were taken:
Open-circuit test (on primary) Short-circuit test (on primary)
Voc=8000V Vsc=489V
Ioc=0.214A Isc=2.5A
Poc=400W Psc=240W
• Find the impedances of the approximate equivalent
circuit referred to the primary side, and sketch that
circuit.
46
Example 2-2 (cont.)
Open-circuit test (on primary)
Voc=8000V
Ioc=0.214A
Poc=400W
I X M I oc
2
I R2c 0.2142 0.052 0.2081A
Vsc=489V
Isc=2.5A
Psc=240W
X eqp Z scp
2
Reqp
2
• A transformer phasor
diagram is just a visual
representation of this Fig. 2-26
equation:
Vp
Vs Reqs I s jX eqs I s
• Fig.2-26 and 2-27
show phasor diagram
under an inductive,
resistive or capacitive
load, respectively.
xVS I S cos
100%
xVS I S cos x Pcu Pcore
2
56
Example 2-5 (cont.)
Open-circuit test (on primary) Short-circuit test (on primary)
Voc=2300V Vsc=47V
Ioc=0.21A Isc=6.0A
Poc=50W Psc=160W
(a). Find the equivalent circuit of this transformer referred to
the high-voltage side.
(b). Find the equivalent circuit of this transformer referred to
the low-voltage side.
(c). Calculate the voltage regulation at 0.8 lagging power
factor, 1.0 power factor and at 0.8 leading power factor.
(e). What is the efficiency of the transformer at a full load
with a power factor of 0.8 lagging?
57
Example 2-5 (cont.)
Solution (a)
Open-circuit test (on primary)
Voc=2300V
Ioc=0.21A
Poc=50W
RC Voc
2
/ Poc 2300 2 / 50 105800
I Rc Voc / Rc 2300 / 105800 0.0217 A
Vsc=47V
Isc=6.0A
Psc=160W
X eqp Z scp
2
Reqp
2
Fig. 2-29b
60
Example 2-5 (cont.)
Solution (c)
• The full load current on the
secondary side of the
transformer is
S rated 15000
I s ,rated 65.3 A
VS ,rated 230 Vp
Vs ( Reqs jX eqs ) I s
• To calculate Vp/, use eq. 2-64
At PF=0.8 lagging, current I S 65.3 36.90 A cos( ) 0.8
VP 36.90
2300 (0.0444 j 0.0645) 65.3 36.9
0 0
23000 2.90 36.90 j 4.2153.10 230 2.32 j1.74 2.52 j 3.36
234.84 j1.62 234.850.400
VP / Vs , fl 234.85 230
• The resulting VR is VR 2.1% 61
Vs , fl 230
Example 2-5 (cont.)
At PF=1.0, current I S 65.300 A
cos( ) 1
VP
23000 (0.0444 j 0.0645) 65.300 00
23000 2.9000 j 4.21900 230 2.9 j1.74 j 4.21
232.9 j 4.21 232.941.040V
VP / Vs, fl 232.94 230
VR 1.28%
Vs, fl 230
At PF=0.8 leading, current I S 65.336.90 A
VP cos( ) 0.8
2300 (0.0444 j 0.0645) 65.336.9
0 0
36.90
23000 2.9036.90 4.21126.90 230 2.32 j1.74 2.52 j3.36
229.80 j5.10 229.851.270V
VP / Vs, fl 229.85 230
VR 0.062% 62
Vs , fl 230
• Example 2-5
(cont.)
Each of these
three phasor
diagrams is
shown in Fig.
2-30.
Fig. 2-30 63
Example 2-5 (cont.)
Solution (d): to find the efficiency of the transformer at
the full load, calculate its losses at this condition. The
copper losses are
PCu ( I s ) 2 Req (65.2) 2 (0.0444) 188.75W
VS I S cos S
100%
and the core losses are VS I S cos S Pcu Pcore
Req Pcore
Pcore I s2 Req (2-68a)
Vs cos Vs I s2 cos
Thus, the conditions to obtain the maximum efficiency of the
transformer is that the copper losses equal core losses,
namely,
Pcore I s Req PCu
2
(2-68b) 65
Example 2-5 (cont.)
• Find the maximum efficiency of the transformer
Pcore I s2 Req PCu 52.5 I s2 0.0444 I s 34.3865 A
69
Transformer ratings and
related problems (cont.)
An inrush current
at starting
Fig.2-48
v(t ) VM sin(t )
Vmax (2-101)
, 90 0
N p
max
/ /
v(t )dt
1
1
(t ) (t ) v(t )dt
Np 0
2Vmax (2-106)
Np 0 , 0 0
max
N p
• For any other phase angles of the applied voltage between
900 and 00, magnetic flux has a normal value at 900 and the
highest value at 00 (the worst case, some excess current
will flow). The phase angle of the applied voltage is not
normally controlled at starting, there can be huge inrush
currents during a first several cycles after transformer is
connected to the line (see Fig.2-48). 70
The per-unit system
• Computations using the actual values of parameters and
variables in power systems may be lengthy and time-
consuming.
• However, if the quantities are expressed in a per-unit (p.u.)
system, computation is much easy, especially in power
systems with a lot of transformers and different ratings of
equipment. The per-unit (p.u.) system is very useful.
• The quantity of p.u. is defined as follows:
Actual value
__________________
Quantity in p.u. = (2-53)
Base value of quantity
where “actual value” is a value in volts, amperes, ohms and etc.
71
The per-unit system (cont.)
• There are two major advantages in using per-unit
system.
1. the parameters and variables fall in a narrow
numerical range when they are expressed in a
per-unit system.
2. There is no need to refer circuit quantities from
one side to another; therefore a common source
of mistakes is removed.
• To establish a per-unit system, it is necessary to
select two base quantities. These commonly
selected two quantities are voltage and power
(or apparent power).
72
The per-unit system (cont.)
• Once voltage and power are selected, all the other
base values (current and impedance) can be
determined.
• In a single-phase system, these relationships are
74
Fig. 2-22
Example 2-3 (cont.)
(a). Select base voltage and base apparent power, find base
current and base impedance for every region in power system.
(b). Convert this system into its per-unit equivalent circuit.
(c). Find the power supplied to the load in this system.
(d). Find the power lost in the transmission line.
Solution: in the generator region 1, Vbase=480V and Sbase=10kVA,
so Sbase 10000 Vbase1 480
I base1 20.83 A Z base1 23.04
Vbase1 480 I base1 20.83
75
Example 2-3 (cont.)
• The turns ratio of transformer T1 is 1 / 10 0.1,
so the base voltage in the transmission line region
2 is
Vbase2
Vbase1
480
4800V
Sbase2 10000VA
0.1
Sbase2 10000 Vbase2 4800
I base2 2.083 A Z base2 2304
Vbase2 4800 I base2 2.083
76
Example 2-3 (cont.)
• The turns ratio of transformer T2 is 20 / 1 20,
so the base voltage in the load region 3 is
Vbase3
Vbase2
4800
240V Sbase3 10000VA
20
Sbase3 10000 Vbase3 240
I base3 41.67 A Z base3 5.76
Vbase3 240 I base3 41.67
77
Example 2-3 (cont.)
• To convert a power system to a per-unit system,
each component must be divided by the base value
in its region of the system.
• First, we convert the generator’s voltage into the
per-unit voltage by using its actual value divided by
its base value: 48000
VG , pu 0
10 pu
480
Vbase1 480V
78
Example 2-3 (cont.)
• Second, we convert the line impedance into the per
unit impedance by using its actual value divided by
its base value, 20 60 j
Z line, pu 0.0087 j 0.0260
2304
5.76
Zbase3 5.76
Zbase 2 2304
79
Example 2-3 (cont.)
• The per-unit
equivalent circuit of
the power system is
shown in Fig. 2-23
Fig. 2-23
80
Example 2-3 (cont.)
81
Autotransformer
82
Autotransformer-step up (cont.)
• Fig. 2-32 show a step-up autotransformer, the
voltage at the output of the whole transformer is the
sum of the voltage on the first winding (Nc) and the
voltage on the second winding (Nse).
• The first winding is also called the common winding,
and the secondary winding is called the series
winding. Their voltage and current relationships are
shown as follows:
VL Nc
(2-76)
VH N c N SE
IL N c N SE
(2-79)
IH Nc 83
Fig. 2-32
Autotransformer-step up (cont.)
• Apparent power rating advantage of autotransformers
It is interesting to note that if a conventional transformer is
reconnected as an autotransformer, it can handle much more
power than it was originally rated for.
• To understand this idea, refer to the following Fig., we will
have Sin VL I L Sout VH I H SIO
SW VC I C VL ( I L I H ) (2-82)
NC
VL I L VL I H VL I L VL I L
N SE NC (2-85)
N SE N SE
VL I L S IO
N SE NC N SE NC
S IO N SE NC
SW N SE (2-86) 84
Autotransformer-step down (cont.)
• Fig. 2-33 shows the step-down autotransformer,
where the voltage at the input is the sum of the
voltage on the series winding and the common
winding, while the voltage at the output is just the
voltage on the common winding.
• Their voltage, current and power relationships are
the same as those in the step-up transformer.
VL Nc
VH N c N SE (2-76)
IL N N SE
c
IH Nc
(2-79)
S IO N SE NC
SW N SE (2-86)
Fig. 2-33 85
Autotransformer (cont.)
• The advantages of the autotransformer are
summarized as follows:
1. Less copper will be used to construct
autotransformer.
2. The power rating is increased.
3. Using a slide over exposed turns
can get continuously variable
turn ratio and thus output
voltage (Variac).
• The disadvantage: no insulation between
the primary winding and the second winding. 86
Instrument transformer
• Two special-purpose transformers are used in power systems
for taking measurements of high voltage and high current.
One is the potential transformer, the other is the current
transformer.
1. Potential transformer is a specially wound transformer
with a high-voltage primary and a low-voltage
secondary, providing a sample of the power system’s
high voltage to the instruments monitoring it. Since its
main purpose is the voltage sampling, it must be accurate
as required for a given application.
Potential
transformer
87
Instrument transformer (cont.)
• Potential transformer has the following features:
1. Same equivalent circuit as normal transformer.
2. Same equations as normal transformer
3. Used to step down voltage to be measured
4. Tends to operate at no load condition
5. Not allowed short circuit.
6. Used widely in protection circuit in power systems.
88
Instrument transformer (cont.)
2. Current transformers sample
high current in a line and reduce it to a
safe and measurable level. Fig. 2-50
shows a typical current transformer. It
consists of a secondary winding
wrapped around a ferromagnetic ring
with the single primary line running Fig. 2-50
through the center of the ring.
The current transformer differs from other transformers in that
its windings are loosely coupled. Unlike all other transformers,
mutual flux in the current transformer is smaller than the
leakage flux due to loose coupling, the voltage and current
ratios of equations for normal transformer do not apply to a
current transformer.
89
Instrument transformer (cont.)
However, the secondary current in the
current transformer is directly proportional
to much larger primary current, and the
device can provide an accurate samples of
a line current for measurement purposes.
VLP 3VP
(2-87)
VLS 3VS
Fig. 2-38a