Manual Mitsubishi fx3g
Manual Mitsubishi fx3g
Manual Mitsubishi fx3g
USER'S MANUAL
Before installation, operation, maintenance or inspection of this product, thoroughly read through and
understand this manual and all of the associated manuals. Also, take care to handle the module properly and
safely.
This manual classifies the safety precautions into two categories: and .
Depending on the circumstances, procedures indicated by may also cause severe injury.
It is important to follow all precautions for personal safety.
Store this manual in a safe place so that it can be taken out and read whenever necessary. Always forward it
to the end user.
1. DESIGN PRECAUTIONS
• Make sure to have the following safety circuits outside of the PLC to ensure safe system operation even during
external power supply problems or PLC failure.
Otherwise, malfunctions may cause serious accidents.
1) Most importantly, have the following: an emergency stop circuit, a protection circuit, an interlock circuit for
opposite movements (such as normal vs. reverse rotation), and an interlock circuit (to prevent damage to the
equipment at the upper and lower positioning limits).
2) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all
outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output
control block, output control may be disabled.
External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
3) Note that the output current of the 24V DC service power supply for sensors varies depending on the model
and the absence/presence of extension blocks. If an overload occurs, the voltage automatically drops, inputs
in the PLC are disabled, and all outputs are turned off.
External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
4) Note that when an error occurs in a relay, triac or transistor output device, the output could be held either on or
off.
For output signals that may lead to serious accidents, external circuits and mechanisms should be designed to
ensure safe machinery operation in such a case.
• Do not bundle the control line together with or lay it close to the main circuit or power line.
As a guideline, lay the control line 100mm(3.94") or more away from the main circuit or power line.
Noise may cause malfunctions.
• Make sure to ground the shield wire or shield of the shielded cable connected to an analog input expansion board,
special analog input adapter, or special function block at one point on the PLC.
However, do not use common grounding with heavy electrical systems.
Noise may cause malfunctions.
• Make sure to ground the shield wire or shield of the shielded cable connected to an analog output expansion
board, special analog output adapter, or special function block at one point on the analog device side.
However, do not use common grounding with heavy electrical systems.
Noise may cause malfunctions.
• Install module so that excessive force will not be applied to the power connectors or terminal blocks.
Failure to do so may result in wire damage/breakage or PLC failure.
(1)
Safety Precautions
(Read these precautions before use.)
2. WIRING PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before attempting wiring work.
Failure to do so may cause electric shock or damage to the product.
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn
out.
• Do not wire vacant terminals externally.
Doing so may damage the product.
• Perform class D grounding (grounding resistance: 100Ω or less) to the grounding terminal on the main unit.
Do not use common grounding with heavy electrical systems.
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
• Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise:
- Do not bundle the power line or shield of the analog input/output cable together with or lay it close to the main
circuit, high-voltage line, or load line.
Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
100mm (3.94") or more away from the main circuit, high-voltage line, or load line.
- Ground the shield of the analog input/output cable at one point on the signal receiving side.
However, do not use common grounding with heavy electrical systems.
• Make sure to properly wire to the terminal block (European type) in accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
- The disposal size of the cable end should follow the dimensions described in the manual.
- Tightening torque should follow the specifications in the manual.
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
• Make sure to properly wire the terminal block in accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
- The disposal size of the cable end should follow the dimensions described in the manual.
- Tightening torque should follow the specifications in the manual.
- Tighten the screws using a Phillips-head screwdriver No.2 (shaft diameter 6mm (0.24") or less).
Make sure that the screwdriver does not touch the partition part of the terminal block.
(2)
Safety Precautions
(Read these precautions before use.)
(3)
Safety Precautions
(Read these precautions before use.)
MEMO
(4)
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3S/FX3G/FX3GC/FX3U/FX3UC Series
Programmable Controllers
User's Manual [Analog Control Edition]
Foreword
This manual describes the "analog" function of the MELSEC-F FX Series programmable controllers and
should be read and understood before attempting to install or use the unit.
Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
it to the end user.
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
rights which may occur as a result of using the contents noted in this manual.
1
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition
Outline Precautions
• This manual provides information for the use of the FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programmable
Controllers. The manual has been written to be used by trained and competent personnel. The definition of
such a person or persons is as follows;
1) Any engineer who is responsible for the planning, design and construction of automatic equipment
using the product associated with this manual should be of a competent nature, trained and qualified
to the local and national standards required to fulfill that role. These engineers should be fully aware of
all aspects of safety with regards to automated equipment.
2) Any commissioning or service engineer must be of a competent nature, trained and qualified to the
local and national standards required to fulfill that job. These engineers should also be trained in the
use and maintenance of the completed product. This includes being completely familiar with all
associated documentation for the said product. All maintenance should be carried out in accordance
with established safety practices.
3) All operators of the completed equipment should be trained to use that product in a safe and
coordinated manner in compliance to established safety practices. The operators should also be
familiar with documentation which is connected with the actual operation of the completed equipment.
Note: The term 'completed equipment' refers to a third party constructed device which contains or uses
the product associated with this manual
• This product has been manufactured as a general-purpose part for general industries, and has not been
designed or manufactured to be incorporated in a device or system used in purposes related to human life.
• Before using the product for special purposes such as nuclear power, electric power, aerospace, medicine
or passenger movement vehicles, consult with Mitsubishi Electric.
• This product has been manufactured under strict quality control. However when installing the product
where major accidents or losses could occur if the product fails, install appropriate backup or failsafe
functions in the system.
• When combining this product with other products, please confirm the standard and the code, or regulations
with which the user should follow. Moreover, please confirm the compatibility of this product to the system,
machine, and apparatus with which a user is using.
• If in doubt at any stage during the installation of the product, always consult a professional electrical
engineer who is qualified and trained to the local and national standards. If in doubt about the operation or
use, please consult your local Mitsubishi Electric representative.
• Since the examples indicated by this manual, technical bulletin, catalog, etc. are used as a reference,
please use it after confirming the function and safety of the equipment and system. Mitsubishi Electric will
accept no responsibility for actual use of the product based on these illustrative examples.
• This manual content, specification etc. may be changed without a notice for improvement.
• The information in this manual has been carefully checked and is believed to be accurate; however, if you
have noticed a doubtful point, a doubtful error, etc., please contact your local Mitsubishi Electric
representative.
Registration
• Phillips is a registered trademark of Phillips Screw Company.
• The company name and the product name to be described in this manual are the registered trademarks or
trademarks of each company.
2
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition Table of Contents
Table of Contents
SAFETY PRECAUTIONS .................................................................................................. (1)
A. Common Items
1. Introduction A-1
3
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition Table of Contents
4
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition Table of Contents
1. Outline B-3
2. Specifications B-6
3. Wiring B-9
5
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition Table of Contents
8. Troubleshooting B-61
6
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition Table of Contents
1. Outline C-3
2. Specifications C-7
3. Wiring C-12
4. Programming C-17
6. Troubleshooting C-31
7
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition Table of Contents
1. Outline D-3
2. Specifications D-7
3. Wiring D-11
4. Programming D-15
6. Troubleshooting D-23
8
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition Table of Contents
1. Outline E-3
2. Specifications E-6
3. Wiring E-9
9
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition Table of Contents
9. Troubleshooting E-64
10
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition Table of Contents
1. Outline F-3
2. Specifications F-7
3. Wiring F-12
4. Programming F-17
6. Troubleshooting F-29
11
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition Table of Contents
1. Outline G-3
2. Specifications G-7
3. Wiring G-11
4. Programming G-15
6. Troubleshooting G-21
12
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition Table of Contents
H. FX3U-3A-ADP
(2-channel Analog Input, 1-channel Analog Output)
1. Outline H-3
2. Specifications H-7
3. Wiring H-12
4. Programming H-18
13
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition Table of Contents
6. Troubleshooting H-37
14
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition Table of Contents
I. FX3U-4AD-PT-ADP
(4-channel Platinum Resistance Thermometer Data Input)
1. Outline I-3
2. Specifications I-7
3. Wiring I-12
4. Programming I-17
5. Troubleshooting I-27
15
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition Table of Contents
J. FX3U-4AD-PTW-ADP
(4-channel Platinum Resistance Thermometer Data Input)
1. Outline J-3
2. Specifications J-7
3. Wiring J-12
4. Programming J-17
5. Troubleshooting J-27
16
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition Table of Contents
K. FX3U-4AD-PNK-ADP
(4-channel Resistance Thermometer Data Input)
1. Outline K-3
2. Specifications K-7
3. Wiring K-12
4. Programming K-17
5. Troubleshooting K-29
17
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition Table of Contents
1. Outline L-3
2. Specifications L-7
3. Wiring L-12
4. Programming L-18
5. Troubleshooting L-30
18
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition Table of Contents
1. Outline M-3
3. Parameter M-7
4. Auto-Tuning M-18
6. Troubleshooting M-28
Warranty...................................................................................................................................... i
Revised History ......................................................................................................................... ii
19
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition Table of Contents
20
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Introduction
Common Items 1.1 Outline and Features of Analog Control
Common Items
1. Introduction
This manual describes the analog products for the FX3S/FX3G/FX3GC/FX3U/FX3UC Series PLC. B
This chapter describes the analog control methods and applications.
FX3UC-4AD
FX3U-4AD
1.1 Outline and Features of Analog Control
For the FX Series, there are 3 types of analog control: Voltage/Current input, Voltage/Current output, and
Temperature Sensor input.
C
FX3U-4AD-ADP
It is important to select products that are optimum for the purpose of use.
FX3S Series FX3G Series FX3GC Series FX3U Series FX3UC Series
PLC PLC PLC PLC PLC
FX3G-2AD-BD
E
FX3U-4DA
Voltage/current input Voltage/current Temperature sensor
control type output control type input control type
FX3U-4AD FX3U-4DA FX3U-4AD-PT-ADP
FX3UC-4AD FX3U-4DA-ADP FX3U-4AD-PTW-ADP
FX3U-4AD-ADP FX3U-3A-ADP FX3U-4AD-PNK-ADP
FX3U-4AD-TC-ADP
F
FX3U-3A-ADP FX3G-1DA-BD
FX3U-4DA-ADP
FX3G-2AD-BD
Refer to Subsection Refer to Subsection Refer to Subsection
1.1.1. 1.1.2. 1.1.3.
FX3G-1DA-BD
Flowmeter, Inverter, etc. Thermocouple,
pressure sensor, etc. platinum resistance
thermometer
sensor
H
FX3U-3A-ADP
In addition to the above applications, the FX3S/FX3G/FX3GC/FX3U/FX3UC Series PLC can be used for various
purposes.
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
A-1
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Introduction
Common Items 1.1 Outline and Features of Analog Control
FX3S/FX3G/FX3GC/FX3U/FX3UC
Series PLC
Voltage or A/D conversion
Analog input data
current
special function
block, special
adapter,
expansion board
A-2
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Introduction
Common Items 1.1 Outline and Features of Analog Control
A
1.1.2 Analog output control
Common Items
Output the voltage/current signal from the PLC to an inverter, etc. to control the inverter frequency, etc.
Inverter, etc.
FX3S/FX3G/FX3GC/FX3U/FX3UC
Series PLC
Analog output Voltage or
B
D/A conversion
FX3UC-4AD
FX3U-4AD
data special function current
block, special
adapter,
expansion board
FX3U-4AD-ADP
the input voltage/current.
FX3G-2AD-BD
→ For detailed description, refer to Section G.
FX3U-4DA
→ For detailed description, refer to Section F.
• FX3U-3A-ADP
→ For detailed description, refer to Section H.
FX3U-4DA-ADP
• FX2N-4DA • FX2N-5A
→ For a detailed description of the other analog output products,
refer to the corresponding manuals.
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
A-3
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Introduction
Common Items 1.1 Outline and Features of Analog Control
FX3S/FX3G/FX3GC/FX3U/FX3UC
Series PLC
Temperature data Temperature data
(Analog data) Temperature (Digital value)
sensor input,
special function
block or special
adapter
Measure the
temperature of the Check the temperature
equipment. using the PLC.
A-4
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Description of Analog Products
Common Items 2.1 Types of Analog Products
Common Items
2. Description of Analog Products
B
2.1 Types of Analog Products
FX3UC-4AD
FX3U-4AD
Analog input/output products are required to perform analog control using the FX Series PLC.
There are 3 types of input/output products: the expansion board, special adapter and the special function
block.
Subsequent subsections explain differences among analog products. C
FX3U-4AD-ADP
2.1.1 Expansion board
The analog expansion board uses PLC devices to send/receive data to/from the PLC.
FX3G-2AD-BD
• Only 1*1 expansion board can be connected.
PLC
Expansion board E
FX3U-4DA
F
→ For a detailed description of the system configuration,
FX3U-4DA-ADP
refer to the FX3S Series User’s Manual - Hardware Edition.
*1. When expansion board is connected to FX3S Series PLC, special adapters cannot be connected to
the main unit.
FX3G-1DA-BD
• Up to 2*2 expansion boards can be connected.
PLC
Expansion board
H
FX3U-3A-ADP
I
FX3U-4AD-PT
A-5
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Description of Analog Products
Common Items 2.1 Types of Analog Products
FX3S-CNV-ADP
FX3G-CNV-ADP
A-6
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Description of Analog Products
Common Items 2.1 Types of Analog Products
A
3. FX3GC Series PLC
Common Items
• Connect the special adapter(s) to the left side of the FX3GC Series PLC.
• Up to 2 analog special adapters can be connected.
Analog
PLC
special adapters
B
FX3UC-4AD
FX3U-4AD
C
FX3U-4AD-ADP
Up to 2 analog adapters can be connected.
→ For a detailed description of the system configuration,
refer to the FX3GC Series User’s Manual - Hardware Edition.
FX3G-2AD-BD
• Connect the special adapter(s) to the left side of the FX3U Series PLC.
• An expansion board is needed to connect the special adapter(s).
• Up to 4 analog special adapters can be connected.
• When using the high-speed input/output special adapter(s), be sure to connect the high-speed input/output
special adapter(s) first, and then connect the analog special adapter(s). E
High-speed
FX3U-4DA
Analog input/output
special adapters Expansion board PLC
special adapters
FX3U-4DA-ADP
FX3U-***-BD
FX3G-1DA-BD
→ For a detailed description of the system configuration,
refer to the FX3U Series User’s Manual - Hardware Edition.
Analog
special adapters PLC
I
FX3U-4AD-PT
-ADP
A-7
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Description of Analog Products
Common Items 2.1 Types of Analog Products
6. FX3UC-32MT-LT(-2) PLC
• Connect the special adapter(s) to the left side of the FX3UC-32MT-LT(-2) PLC.
• An expansion board is needed to connect the special adapter(s).
• Up to 4 analog special adapters can be connected.
Analog
special adapters Expansion board PLC
FX3U-***-BD
Up to 4 analog adapters can be connected. "***" represents "422", "232", "485", "8AV", "CNV", or "USB."
A-8
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Description of Analog Products
Common Items 2.1 Types of Analog Products
A
2.1.3 Special function block
Common Items
The special function block uses buffer memory (BFM) to send/receive data to/from the PLC.
FX3UC-4AD
FX3U-4AD
PLC Analog special function block
for FX3U/FX2N
FX3U-4AD-ADP
Up to 8 special function units/blocks can be
connected (excluding the special adapters).
D
→ For a detailed description of the system configuration,
FX3G-2AD-BD
refer to the FX3G Series User's Manual - Hardware Edition.
FX3U-4DA
PLC Analog special function block Analog special function block
FX3UC-1PS-5V
for FX3UC/FX2NC or for FX3U/FX2N
FX2NC-CNV-IF
FX3U-4DA-ADP
G
FX3G-1DA-BD
Up to 8 special function units/blocks can be connected (excluding the special adapters).
• Connect the special function block(s) to the right side of the FX3U Series PLC.
• Up to 8 special function blocks can be connected.
PLC Analog special function block
for FX3U/FX2N/FX0N
I
FX3U-4AD-PT
-ADP
A-9
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Description of Analog Products
Common Items 2.1 Types of Analog Products
Up to 8*1 special function units/blocks can be connected (excluding the special adapters).
Select either FX3UC-1PS-5V or FX2NC-CNV-IF considering the current components consumption.
→ For a detailed description of the system configuration,
refer to the FX3UC Series User’s Manual - Hardware Edition.
*1. Up to 7 special function units/blocks can be connected to the FX3UC-32MT-LT(-2) PLC.
A-10
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Description of Analog Products
Common Items 2.2 List of Analog Product Models
A
2.2 List of Analog Product Models
Common Items
The analog input/output products compatible with the FX3S/FX3G/FX3GC/FX3U/FX3UC Series PLC are
described below:
FX3UC-4AD
FX3U-4AD
• FX3S/FX3G Series PLC
No. of Refer-
Type Range Resolution Function
channels ence
Voltage/current input
Voltage: 0 V to 10 V DC 2.5 mV (12 bits) Combined use of voltage and C
FX3G-2AD-BD 2ch D
FX3U-4AD-ADP
Current: 4 mA to 20 mA DC 8 μA (11 bits) current inputs is possible.
Voltage/current output
Voltage: 0 V to 10 V DC 2.5 mV (12 bits)
FX3G-1DA-BD 1ch Voltage and current output. G
Current: 4 mA to 20 mA DC 8 μA (11 bits)
D
2.2.2 Special adapter
FX3G-2AD-BD
• FX3S/FX3G/FX3GC/FX3U/FX3UC Series PLC
No. of Refer-
Type Range Resolution Function
channels ence
Voltage/current input E
Voltage: 0 V to 10 V DC 2.5 mV (12 bits) Combined use of voltage and
FX3U-4DA
FX3U-4AD-ADP 4ch C
Current: 4 mA to 20 mA DC 10 μA (11 bits) current inputs is possible.
Voltage/current output
Voltage: 0 V to 10 V DC 2.5 mV (12 bits) Combined use of voltage and
FX3U-4DA-ADP 4ch F
Current: 4 mA to 20 mA DC 4 μA (12 bits) current outputs is possible.
F
Voltage/current input/output mixture
FX3U-4DA-ADP
Input Voltage: 0 V to 10 V DC 2.5 mV (12 bits)
2ch Current: 4 mA to 20 mA DC 5 μA (12 bits) Combined use of voltage/
FX3U-3A-ADP current inputs and voltage/ H
Output Voltage: 0 V to 10 V DC 2.5 mV (12 bits) current output is possible.
1ch Current: 4 mA to 20 mA DC 4 μA (12 bits)
G
Temperature sensor input
FX3G-1DA-BD
Compatible with the platinum
resistance thermometer
sensor (Pt100).
FX3U-4AD-PT-ADP 4ch Pt100: -50 °C to +250 °C 0.1 °C I
The product can be switched
between "Centigrade" and
"Fahrenheit." H
FX3U-3A-ADP
"Fahrenheit."
A-11
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Description of Analog Products
Common Items 2.2 List of Analog Product Models
A-12
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Description of Analog Products
Common Items 2.2 List of Analog Product Models
A
No. of Refer-
Common Items
Type Range Resolution Function
channels ence
Voltage/current input/output mixture
Voltage: 0.32 mV
Input -10 V to +10 V DC (with sign, 16 bits) Combined use of voltage and
4ch Current:
-20 mA to +20 mA DC
1.25 μA
(with sign, 15 bits)
current is possible.
The offset/gain can be
B
FX2N-5A*1 *2
FX3UC-4AD
FX3U-4AD
Voltage: 5 mV adjusted.*3
Output -10 V to +10 V DC (with sign, 12 bits) The scaling function is
1ch Current: 20 μA incorporated.
0 mA to 20 mA DC (10 bits)
Voltage: 40 mV
Input 0 V to 10 V DC (8 bits) C
2ch Current: 64 μA
FX3U-4AD-ADP
The input format is common to 2
4 mA to 20 mA DC (8 bits) channels.
FX0N-3A*4 *5 *2
Voltage: 40 mV The offset/gain can be adjusted.
Output 0 V to 10 V DC (8 bits) (Common to 2 input channels)
1ch Current: 64 μA
4 mA to 20 mA DC (8 bits) D
Temperature sensor input
FX3G-2AD-BD
Type K: Combined use of voltage,
-100 °C to +1200 °C current, and thermocouple is
Type J: possible.
-100 °C to +600 °C Compatible with thermocouple
FX2N-8AD*1 8ch 0.1 °C types K, J, and T. *2
Type T:
The unit can be switched between E
"Centigrade" and "Fahrenheit."
FX3U-4DA
-100 °C to +350 °C The sampling function is
incorporated.
Type K: Compatible with thermocouple
0.4 °C
-100 °C to +1200 °C types K and J.
FX2N-4AD-TC*1 4ch *2
Type J:
-100 °C to +600 °C
0.3 °C
The unit can be switched between
"Centigrade" and "Fahrenheit." F
FX3U-4DA-ADP
Compatible with the platinum
resistance thermometer sensor
Pt100:
FX2N-4AD-PT*1 4ch 0.2 °C to 0.3 °C (Pt100 or JPt100). *2
-100 °C to +600 °C
The unit can be switched between
"Centigrade" and "Fahrenheit."
Compatible with thermocouple G
types K, J, R, S, E, T, B, N, PL II,
FX3G-1DA-BD
W5Re/W26Re, U, and L.
Compatible with the platinum
resistance thermometer sensor
(Pt1000, Pt100, and JPt100).
Example:
The unit can be switched between
Type K:
-100 °C to +1300 °C
0.1 °C or 1 °C "Centigrade" and "Fahrenheit." H
FX3U-4LC*1 4ch (Depends on the Compatible with the micro *2
FX3U-3A-ADP
Example:
sensor input range.) voltage input.
Pt100:
The temperature adjustment
-200 °C to +600 °C
function (PID operation, etc.) is
incorporated.
The peak disconnection
detection function is I
incorporated.
FX3U-4AD-PT
(A CT sensor is needed.)
*1. To connect this block to the FX3GC/FX3UC Series PLC, either the FX2NC-CNV-IF or FX3UC-1PS-5V is
required.
-ADP
A-13
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Description of Analog Products
Common Items 2.2 List of Analog Product Models
No. of Refer-
Type Range Resolution Function
channels ence
Temperature sensor input
Example: Compatible with thermocouple
Type K: types K, J, R, S, E, T, B, N, PL II,
-600 °C to +1300 °C W5Re/W26Re, U, and L.
Compatible with the platinum
resistance thermometer sensor
(Pt100, JPt100).
0.1 °C or 1 °C The unit can be switched between
FX2N-2LC*1 2ch (Depends on the "Centigrade" and "Fahrenheit." *2
Example: sensor input range.) The temperature adjustment
Pt100: function (PID operation, etc.) is
-200 °C to +600 °C incorporated.
The peak disconnection
detection function is
incorporated.
(A CT sensor is needed.)
*1. To connect this block to the FX3GC/FX3UC Series PLC, either the FX2NC-CNV-IF or FX3UC-1PS-5V is
required.
*2. Refer to the instruction manual of the respective product.
A-14
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 System Configuration Drawings of Analog Products
Common Items 3.1 FX3S Series PLC
Common Items
3. System Configuration Drawings of Analog Products
This section shows drawings to describe the configuration of analog units for the FX3S/FX3G/FX3GC/FX3U/ B
FX3UC Series PLC.
FX3UC-4AD
FX3U-4AD
3.1 FX3S Series PLC
3.1.1 Connection of expansion boards, special adapters
FX3U-4AD-ADP
and represent the connecting positions.
(For a detailed description of installation, refer to the
FX3S Series User’s Manual - Hardware Edition.)
D
Analog input
FX3G-2AD-BD
Flowmeter
European terminal block
Pressure sensor
Only one analog expansion board or one analog special adapter can be connected.
FX3U-4DA
European terminal block Analog output
Inverter, etc.
FX3G-1DA-BD
Analog input
F
FX3U-4DA-ADP
Flowmeter
European terminal block
Pressure sensor
Signal converter, etc.
FX3S-CNV-ADP FX3U-4AD-ADP
FX3G-1DA-BD
Analog output
European terminal block
Inverter, etc.
FX3U-4DA-ADP
Analog input
H
FX3U-3A-ADP
Flowmeter
European terminal block Pressure sensor
Signal converter, etc.
Temperature sensor
input
Thermocouple
European terminal block
-ADP
(types K and J)
Resistance
FX3U-4AD-TC-ADP
FX3U-4AD-PNK-ADP
thermometer sensor
(Pt1000 and Ni1000)
J
FX3U-4AD-PTW
A-15
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 System Configuration Drawings of Analog Products
Common Items 3.2 FX3G Series PLC
Board A
Analog input
Flowmeter
European terminal block
Pressure sensor
Only one analog expansion board or one analog special adapter can be connected.
Board A
FX3G-1DA-BD
1st
adapter Analog input
Flowmeter
European terminal block
Pressure sensor
Signal converter, etc.
FX3G-CNV-ADP FX3U-4AD-ADP
1st
adapter
Analog output
European terminal block
Inverter, etc.
FX3U-4DA-ADP
1st
Analog input
adapter
Flowmeter
European terminal block Pressure sensor
Signal converter, etc.
Temperature sensor
1st
input
adapter
Thermocouple
European terminal block (types K and J)
Resistance
thermometer sensor
FX3U-4AD-TC-ADP (Pt1000 and Ni1000)
FX3U-4AD-PNK-ADP
Platinum resistance
FX3U-4AD-PT-ADP
thermometer
FX3U-4AD-PTW-ADP
sensor (Pt100)
A-16
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 System Configuration Drawings of Analog Products
Common Items 3.2 FX3G Series PLC
A
2. FX3G Series PLC (40-point, 60-point type)
Common Items
A , B , and C represent the connecting positions.
A B C (For a detailed description of installation, refer to the
FX3G Series User’s Manual - Hardware Edition.)
FX3UC-4AD
FX3U-4AD
Only either A or C
can be used as 2nd.
European
B Board A terminal Analog input
C Board B block Flowmeter
European
Pressure sensor C
Signal converter,
terminal
FX3U-4AD-ADP
block etc.
FX3G-2AD-BD
FX3G-2AD-BD
B Board A European
terminal
Up to 2 analog expansion boards, analog special adapters can be connected.
C Board B
block
Analog output D
Inverter, etc.
FX3G-2AD-BD
European
terminal
FX3G-1DA-BD block
FX3G-1DA-BD
E
Any one can be
FX3U-4DA
selected.
A 2nd European
adapter terminal Analog input
B A 1st
block Flowmeter
adapter
European
Pressure sensor
Signal converter, F
FX3U-4DA-ADP
FX3U-4AD-ADP terminal etc.
block
FX3G-CNV-ADP FX3U-4AD-ADP A 2nd
adapter European
terminal
A 1st Analog output
adapter
block
Inverter, etc. G
European
FX3G-1DA-BD
FX3U-4DA-ADP terminal
block
FX3U-4DA-ADP Analog input
A 2nd Flowmeter
adapter European Pressure sensor
A 1st
terminal Signal converter, H
block etc.
FX3U-3A-ADP
adapter
(types K and J)
A 1st
European Resistance
adapter
terminal thermometer
-ADP
FX3U-4AD-PNK-ADP
FX3U-4AD-PT-ADP block thermometer
FX3U-4AD-PTW-ADP
sensor (Pt100)
-ADP
A-17
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 System Configuration Drawings of Analog Products
Common Items 3.2 FX3G Series PLC
Analog input
C Flowmeter
Pressure sensor
Signal converter,
etc.
Terminal block
Analog output
Special function Inverter, etc.
block for
FX3U/FX2N
Temperature sensor
input
Thermocouple
• For a detailed description of the connectable special function blocks and system configuration:
→ Refer to the FX3G Series User's Manual - Hardware Edition.
The analog special function blocks shown in the table below can be connected to the FX3G Series PLC:
FX Series Type
Analog special function blocks for
FX3U-4AD, FX3U-4DA, FX3U-4LC
the FX3U
Analog special function blocks for FX2N-8AD, FX2N-4AD, FX2N-2AD, FX2N-4DA, FX2N-2DA, FX2N-5A,
the FX2N FX2N-4AD-PT, FX2N-4AD-TC, FX2N-2LC
A-18
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 System Configuration Drawings of Analog Products
Common Items 3.3 FX3GC Series PLC
A
3.3 FX3GC Series PLC
Common Items
3.3.1 Connection of special adapters
FX3UC-4AD
FX3U-4AD
C1 D C2 To connect the special function blocks C or the conversion adapters D ,
A refer to Subsection 3.3.2.
FX3U-4AD-ADP
A
Analog input
Flowmeter
European terminal block
Pressure sensor
Signal converter, etc. D
FX3U-4AD-ADP
FX3G-2AD-BD
A
Analog output
Up to 2 analog special adapters can be connected.
FX3U-4DA
FX3U-4DA-ADP
A
Analog input
Flowmeter
European terminal block Pressure sensor F
Signal converter, etc.
FX3U-4DA-ADP
FX3U-3A-ADP Analog output
Inverter, etc.
A Temperature sensor
input
G
FX3G-1DA-BD
Thermocouple
European terminal block
(types K and J)
Resistance
thermometer
FX3U-4AD-TC-ADP sensor (Pt1000 and
FX3U-4AD-PNK-ADP
FX3U-4AD-PT-ADP
Ni1000)
Platinum resistance H
FX3U-4AD-PTW-ADP thermometer
FX3U-3A-ADP
sensor (Pt100)
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
A-19
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 System Configuration Drawings of Analog Products
Common Items 3.3 FX3GC Series PLC
C1
FX3UC-4AD
C1
Up to 8 special function blocks can be connected.
FX3UC-1PS-5V
C2
Terminal block
Special function
block for
FX2NC-CNV-IF FX3U/FX2N
• For a detailed description of special function block connectability and system configuration:
→ Refer to the FX3GC Series User's Manual - Hardware Edition.
• Use the FX3UC-1PS-5V (extension power supply unit) if the capacity of the 5 V DC power supply unit
incorporated in the FX3GC Series PLC is deteriorated.
→ Refer to the FX3GC Series User's Manual - Hardware Edition.
The analog special function blocks shown in the table below can be connected to the FX3GC Series PLC:
FX Series Type
Analog special function blocks for the FX3U FX3U-4AD, FX3U-4DA, FX3U-4LC
Analog special function blocks for the FX3UC FX3UC-4AD
FX2N-8AD, FX2N-4AD, FX2N-2AD, FX2N-4DA, FX2N-2DA,
Analog special function blocks for the FX2N
FX2N-5A, FX2N-4AD-PT, FX2N-4AD-TC, FX2N-2LC
Analog special function blocks for the FX2NC FX2NC-4AD, FX2NC-4DA
A-20
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 System Configuration Drawings of Analog Products
Common Items 3.4 FX3U Series PLC
A
3.4 FX3U Series PLC
Common Items
3.4.1 Connection of special adapters
FX3UC-4AD
FX3U-4AD
A C To connect special function blocks C , refer to the next page.
B
FX3U-4AD-ADP
B A
Analog input
RDA
• Flowmeter
RD
SDA
SD SDB
• Pressure sensor
SG
FX3G-2AD-BD
A
Up to 4 analog special adapters can be connected.
Analog output
European terminal block
• Inverter, etc.
FX3U-4DA-ADP
E
FX3U-4DA
A Analog input
• Flowmeter
European terminal block • Pressure sensor
• Signal converter, etc.
Analog output
F
FX3U-3A-ADP
FX3U-4DA-ADP
• Inverter, etc.
A Temperature sensor
input
European terminal block
• Thermocouple
(types K and J)
G
FX3G-1DA-BD
• Resistance
thermometer
FX3U-4AD-TC-ADP
sensor (Pt1000 and
FX3U-4AD-PNK-ADP
Ni1000)
FX3U-4AD-PT-ADP • Platinum resistance
FX3U-4AD-PTW-ADP thermometer
sensor (Pt100) H
FX3U-3A-ADP
J
FX3U-4AD-PTW
-ADP
A-21
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 System Configuration Drawings of Analog Products
Common Items 3.4 FX3U Series PLC
Analog input
C Flowmeter
Pressure sensor
Signal converter,
etc.
Terminal block
Analog output
Special function Inverter, etc.
block for
FX3U/FX2N/FX0N
Temperature sensor
input
Thermocouple
Platinum resistance
thermometer
sensor (Pt100)
• For a detailed description of the connectable special function blocks and system configuration:
→ Refer to the FX3U Series User's Manual - Hardware Edition.
The analog special function blocks shown in the table below can be connected to the FX3U Series PLC:
FX Series Type
Analog special function blocks for
FX3U-4AD, FX3U-4DA, FX3U-4LC
the FX3U
Analog special function blocks for FX2N-8AD, FX2N-4AD, FX2N-2AD, FX2N-4DA, FX2N-2DA, FX2N-5A,
the FX2N FX2N-4AD-PT, FX2N-4AD-TC, FX2N-2LC
Analog special function blocks for
FX0N-3A
the FX0N
A-22
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 System Configuration Drawings of Analog Products
Common Items 3.5 FX3UC Series PLC
A
3.5 FX3UC Series PLC
Common Items
3.5.1 Connection of special adapters
FX3UC-4AD
FX3U-4AD
C1 D C2 To connect the special function blocks C or the conversion adapters D ,
A refer to Subsection 3.5.2-1.
FX3U-4AD-ADP
A
Analog input
Flowmeter
European terminal block
Pressure sensor
Signal converter, etc.
D
FX3G-2AD-BD
FX3U-4AD-ADP
Analog output
Up to 4 analog special adapters can be connected.
FX3U-4DA
FX3U-4DA-ADP
A
Analog input
FX3U-4DA-ADP
Signal converter, etc.
FX3U-3A-ADP Analog output
Inverter, etc.
A Temperature sensor
G
FX3G-1DA-BD
input
Thermocouple
European terminal block
(types K and J)
Resistance
thermometer
FX3U-4AD-TC-ADP
FX3U-4AD-PNK-ADP
sensor (Pt1000 and
Ni1000) H
FX3U-4AD-PT-ADP Platinum resistance
FX3U-3A-ADP
FX3U-4AD-PTW-ADP thermometer
sensor (Pt100)
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
A-23
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 System Configuration Drawings of Analog Products
Common Items 3.5 FX3UC Series PLC
2. FX3UC-32MT-LT(-2) PLC
B A
RD
RDA
Analog input
European terminal block
RDB
Flowmeter
SDA
SD SDB
SG
Pressure sensor
FX3U-***-BD*1 FX3U-4AD-ADP Signal converter, etc.
Analog output
Up to 4 analog special adapters can be connected.
FX3U-4DA-ADP
A Analog input
Flowmeter
Pressure sensor
European terminal block
Signal converter, etc.
Analog output
FX3U-3A-ADP
Inverter, etc.
A Temperature sensor
input
Thermocouple
European terminal block
(types K and J)
Resistance
thermometer
FX3U-4AD-TC-ADP sensor (Pt1000 and
FX3U-4AD-PNK-ADP Ni1000)
FX3U-4AD-PT-ADP Platinum resistance
FX3U-4AD-PTW-ADP thermometer
sensor (Pt100)
A-24
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 System Configuration Drawings of Analog Products
Common Items 3.5 FX3UC Series PLC
A
3.5.2 Connection of special function blocks
Common Items
1. FX3UC (D, DS, DSS) Series PLC
A , C , and D represent the connecting positions.
A C1 D C2
(For a detailed description of installation, refer to the
FX3UC Series User’s Manual - Hardware Edition.) B
FX3UC-4AD
FX3U-4AD
To connect the special adapters A , refer to Subsection 3.5.1-1.
C1
FX3U-4AD-ADP
European terminal block
FX3UC-4AD
D
C1
FX3G-2AD-BD
Up to 8 special function blocks can be connected.
FX3U-4DA
Analog output
Inverter, etc.
FX3UC-4AD
Temperature sensor
C1 input
Thermocouple
F
FX3U-4DA-ADP
D Platinum resistance
European terminal block
thermometer
sensor (Pt100)
C1 or C2
Special function
block for FX2NC
FX3UC-1PS-5V G
FX3G-1DA-BD
C2
Terminal block
Special function H
block for
FX3U-3A-ADP
FX2NC-CNV-IF FX3U/FX2N/FX0N
• For a detailed description of special function block connectability and system configuration:
→ Refer to the FX3UC Series User's Manual - Hardware Edition.
• Use the FX3UC-1PS-5V (extension power supply unit) if the capacity of the 5 V DC power supply unit
incorporated in the FX3UC Series PLC is deteriorated.
→ Refer to the FX3UC Series User's Manual - Hardware Edition.
I
FX3U-4AD-PT
The analog special function blocks shown in the table below can be connected to the FX3UC Series PLC:
FX Series Type
Analog special function blocks for the FX3U FX3U-4AD, FX3U-4DA, FX3U-4LC
-ADP
A-25
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 System Configuration Drawings of Analog Products
Common Items 3.5 FX3UC Series PLC
2. FX3UC-32MT-LT(-2) PLC
A , B , C , and D represent the connecting positions.
(For a detailed description of installation, refer to the
A C1 D C2 FX3UC Series User’s Manual - Hardware Edition.)
B
C1
FX3UC-4AD
C1
Up to 7 special function blocks can be connected.
FX3UC-1PS-5V
C2
Terminal block
Special function
block for
FX2NC-CNV-IF FX3U/FX2N/FX0N
• For a detailed description of special function block connectability and system configuration:
→ Refer to the FX3UC Series User's Manual - Hardware Edition.
• Use the FX3UC-1PS-5V (extension power supply unit) if the capacity of the 5 V DC power supply unit
incorporated in the FX3UC Series PLC is deteriorated.
→ Refer to the FX3UC Series User's Manual - Hardware Edition.
The analog special function blocks shown in the table below can be connected to the FX3UC Series PLC:
FX Series Type
Analog special function blocks for the FX3U FX3U-4AD, FX3U-4DA, FX3U-4LC
Analog special function blocks for the FX3UC FX3UC-4AD
FX2N-8AD, FX2N-4AD, FX2N-2AD, FX2N-4DA, FX2N-2DA,
Analog special function blocks for the FX2N
FX2N-5A, FX2N-4AD-PT, FX2N-4AD-TC, FX2N-2LC
Analog special function blocks for the FX2NC FX2NC-4AD, FX2NC-4DA
Analog special function blocks for the FX0N FX0N-3A
A-26
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.1 Analog Input
Common Items
4. Comparison of Performance Specifications
The analog product performance specifications are shown in the following tables. Select the optimal product B
for your equipment.
FX3UC-4AD
FX3U-4AD
4.1 Analog Input
4.1.1 FX3U-4AD-ADP C
FX3U-4AD-ADP
FX3U-4AD-ADP
Specifications
Voltage input Current input
Number of input points 4ch
FX3G-2AD-BD
Absolute maximum input -0.5V, +15V -2mA, +30mA
Offset
Impossible to change Impossible to change
Gain
Digital output 12 bits, binary 11 bits, binary
E
Resolution 2.5mV (10V × 1/4000) 10μA (16mA × 1/1600)
FX3U-4DA
Overall accuracy
Ambient temperature:
±0.5% (±50mV) for 10V full scale ±0.5% (±80μA) for 16mA full scale
25±5°C
Ambient temperature:
0 to 55°C
±1.0% (±100mV) for 10V full scale ±1.0% (±160μA) for 16mA full scale F
FX3U-4DA-ADP
Time required for A/D • FX3U/FX3UC Series PLC : 200μs (Data updated every scan time.)
conversion • FX3S/FX3G/FX3GC Series PLC : 250μs (Data updated every scan time.)
4080 1640
4000 1600 G
FX3G-1DA-BD
Digital output
Digital output
Input characteristics
20.4mA
10.2V
0 10V
Analog input
0 4mA
Analog input
20mA H
FX3U-3A-ADP
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply from the analog inputs.
• Channels are not insulated from each other.
Number of I/O points
occupied
0 point (This number is not related to the maximum I/O points of the PLC.) I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
A-27
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.1 Analog Input
4.1.2 FX2N-2AD
FX2N-2AD
Specifications
Voltage input Current input
Number of input points 2ch
0V to 5V DC
4mA to 20mA DC
Analog input range*1 0V to 10V DC
(Input resistance: 250 Ω)
(Input resistance: 200 kΩ)
Absolute maximum input -0.5V, +15V -2mA, +60mA
*2*3
Offset If the digital value is "0": 0V to 1V If the digital value is "0": 0mA to 4mA*2*3
If the digital value is "4000":
Gain If the digital value is "4000": 20mA*2*3
5V to 10V*2*3
Digital output 12 bits, binary
*3
Resolution 2.5mV (10V × 1/4000) 4.00μA (16mA × 1/4000)*3
Overall accuracy
Ambient temperature:
- -
25±5°C
Ambient temperature:
±1.0% (±100mV) for 10V full scale ±1.0% (±160μA) for 16mA full scale
0 to 55°C
4095 4095
4000 4000
Digital output
Digital input
20.380mA
Input characteristics
10.238V
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method
• Channels are not insulated from each other.
Number of I/O points
8 points (Taken from either the input or output points of the PLC.)
occupied
*1. For FX2N-2AD, combined use of the voltage and current inputs is not possible.
*2. Use the adjustment volume to adjust FX2N-2AD.
*3. Adjustment of the offset or gain value will change the resolution.
A-28
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.1 Analog Input
A
4.1.3 FX3U-4AD
Common Items
FX3U-4AD
Specifications
Voltage input Current input
Number of input points 4ch
-20mA to +20mA DC
B
-10V to +10V DC
FX3UC-4AD
FX3U-4AD
Analog input range 4mA to 20mA DC
(Input resistance: 200 kΩ)
(Input resistance: 250 Ω)
Absolute maximum input ±15V ±30mA
Offset -10V to +9V*1*2 -20mA to +17mA*1*3
Gain -9V to +10V*1*2 -17mA to +30mA*1*3 C
FX3U-4AD-ADP
Digital output With sign, 16 bits, binary With sign, 15 bits, binary
0.32mV (20V × 1/64000) 1.25μA (40mA × 1/32000)
Resolution*4 2.5mV (20V × 1/8000) 5.00μA (40mA × 1/8000)
Overall accuracy
FX3G-2AD-BD
Ambient temperature: ±1.0% (±400μA) for 40mA full scale
±0.5% (±100mV) for 20V full scale
0 to 55°C Same accuracy for 4mA to 20mA input
FX3U-4DA
+32640 +16320
+32000 +16000
+20.4mA
+10.2V
-10V 0 -20mA 0
+10V +20mA F
-20.4mA
-10.2V
FX3U-4DA-ADP
Input characteristics*4 -32000 -16000
-32640 -16320
zWhen the input mode is set to "3":
16400
16000
G
20.4mA
FX3G-1DA-BD
0 4mA 20mA
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply from the analog inputs. H
FX3U-3A-ADP
*1. Adjustment of the offset or gain value will not affect the resolution. In the direct indication mode, however, the
*2.
offset/gain cannot be adjusted.
The offset and the gain should satisfy the following condition:
I
FX3U-4AD-PT
*4. The resolution and the input/output characteristics depend on the selected mode.
*5. If 1 or more channels use the digital filter(s), the time required for A/D conversion will be
"5 ms × number of selected channels." J
FX3U-4AD-PTW
-ADP
A-29
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.1 Analog Input
4.1.4 FX2N-4AD
FX2N-4AD
Specifications
Voltage input Current input
Number of input points 4ch
-20mA to +20mA DC
-10V to +10V DC
Analog input range 4mA to 20mA DC
(Input resistance: 200 kΩ)
(Input resistance: 250 Ω)
Absolute maximum input ±15V ±32mA
*1*2
Offset -5V to +5V -20mA to +20mA*1*3
Gain -4V to +15V*1*2 -16mA to +32mA*1*3
Digital output With sign, 12 bits, binary With sign, 11 bits, binary
*1
Resolution 5mV (20V × 1/4000) 20μA (40mA × 1/2000)*1
Overall accuracy
Ambient temperature:
- -
25±5°C
Time required for A/D Normal conversion mode:15ms × number of selected channels
conversion High-speed conversion mode: 6ms × number of selected channels
+2000 +1600
+1000
+32mA
-10V 0
+10V -20mA 0
-10.240V
+20mA
-32mA
-2000
Input characteristics -2048 -1000
-1600
zWhen the input is set from 4 mA to 20 mA:
1750
1000
32mA
0 4mA 20mA
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply from the analog inputs.
• Channels are not insulated from each other.
Number of I/O points
8 points (Taken from either the input or output points of the PLC.)
occupied
*1. Adjustment of the offset or gain value will not affect the resolution.
*2. The offset and the gain should satisfy the following condition:
1V ≤ (Gain - Offset) ≤ 15V
*3. The offset and the gain should satisfy the following condition:
4mA ≤ (Gain - Offset) ≤ 32mA
A-30
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.1 Analog Input
A
4.1.5 FX3UC-4AD
Common Items
FX3UC-4AD
Specifications
Voltage input Current input
Number of input points 4ch
-20mA to +20mA DC
B
-10V to +10V DC
FX3UC-4AD
FX3U-4AD
Analog input range 4mA to 20mA DC
(Input resistance: 200 kΩ)
(Input resistance: 250 Ω)
Absolute maximum input ±15V ±30mA
Offset -10V to +9V*1*2 -20mA to +17mA*1*3
Gain -9V to +10V*1*2 -17mA to +30mA*1*3 C
FX3U-4AD-ADP
Digital output With sign, 16 bits, binary With sign, 15 bits, binary
0.32mV (20V × 1/64000) 1.25μA (40mA × 1/32000)
Resolution*4 2.5mV (20V × 1/8000) 5.00μA (40mA × 1/8000)
Overall accuracy
FX3G-2AD-BD
Ambient temperature: ±1.0% (±400μA) for 40mA full scale
±0.5% (±100mV) for 20V full scale
0 to 55°C Same accuracy for 4mA to 20mA input
FX3U-4DA
+32640 +16320
+32000 +16000
+20.4mA
+10.2V
-10V 0 -20mA 0
+10V +20mA F
-20.4mA
-10.2V
FX3U-4DA-ADP
Input characteristics*4 -32000 -16000
-32640 -16320
zWhen the input mode is set to "3":
16400
16000
G
20.4mA
FX3G-1DA-BD
0 4mA 20mA
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply from the analog inputs. H
FX3U-3A-ADP
*1. Adjustment of the offset or gain value will not affect the resolution. In the direct indication mode, however, the
*2.
offset/gain cannot be adjusted.
The offset and the gain should satisfy the following condition:
I
FX3U-4AD-PT
*4. The resolution and the input/output characteristics depend on the selected mode.
*5. If 1 or more channels use the digital filter(s), the time required for A/D conversion will be
"5 ms × number of selected channels." J
FX3U-4AD-PTW
-ADP
A-31
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.1 Analog Input
4.1.6 FX2NC-4AD
FX2NC-4AD
Specifications
Voltage input Current input
Number of input points 4ch
-20mA to +20mA DC
-10V to +10V DC
Analog input range 4mA to 20mA DC
(Input resistance: 200 kΩ)
(Input resistance: 250 Ω)
Absolute maximum input ±15V ±30mA
Offset -10V to +9V*1*2 -20mA to +17mA*1*3
Gain -9V to +10V*1*2 -17mA to +30mA*1*3
Digital output With sign, 16 bits, binary With sign, 15 bits, binary
0.32mV (20V × 1/64000) 1.25μA (40mA × 1/32000)
Resolution*4 2.5mV (20V × 1/8000) 5.00μA (40mA × 1/8000)
Overall accuracy
zWhen the input mode is set to "0": zWhen the input mode is set to "6":
+32640 +16320
+32000 +16000
+20.4mA
+10.2V
-10V 0 -20mA 0
+10V 20mA
-20.4mA
-10.2V
0 4mA 20mA
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply from the analog inputs.
• Channels are not insulated from each other.
Number of I/O points
8 points (Taken from either the input or output points of the PLC.)
occupied
*1. Adjustment of the offset or gain value will not affect the resolution. In the direct indication mode, however, the
offset/gain cannot be adjusted.
*2. The offset and the gain should satisfy the following condition:
1V ≤ (Gain - Offset)
*3. The offset and the gain should satisfy the following condition:
3mA ≤ (Gain - Offset) ≤ 30mA
*4. The resolution and the input/output characteristics depend on the selected mode.
*5. If 1 or more channels use the digital filter(s), the time required for A/D conversion will be
"5 ms × number of selected channels."
A-32
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.1 Analog Input
A
4.1.7 FX2N-8AD
Common Items
FX2N-8AD
Specifications
Voltage input Current input
Number of input points 8ch
B
-20mA to +20mA DC
FX3UC-4AD
FX3U-4AD
-10V to +10V DC
Analog input range 4mA to 20mA DC
(Input resistance: 200 kΩ)
(Input resistance: 250 Ω)
Absolute maximum input ±15V ±30mA
Offset -10V to +9V*1*2 -20mA to +17mA*1*3
Gain -9V to +10V*1*2 -17mA to +30mA*1*3
C
FX3U-4AD-ADP
Digital output With sign, 15 bits, binary With sign, 14 bits, binary
0.63mV (20V × 1/32000) 2.50μA (40mA × 1/16000)
Resolution*4 2.5mV (20V × 1/8000) 2.00μA (16mA × 1/8000)
Overall accuracy
FX3G-2AD-BD
Ambient temperature: ±0.5% (±200μA) for 40mA full scale
±0.5% (±100mV) for 20V full scale
0 to 55°C Same accuracy for 4mA to 20mA input
FX3U-4DA
zWhen the input mode is set to "0": zWhen the input mode is set to "6":
+16320 +8160
+16000 +8000
+20.4mA
+10.2V
-10V 0
+10V
-20mA 0
+20mA
F
-20.4mA
-10.2V
FX3U-4DA-ADP
Input characteristics*4 -16000 -8000
-16320 Approx.-8160
zWhen the input mode is set to "3":
8200
G
FX3G-1DA-BD
8000
20.4mA
0 4mA 20mA
• The photocoupler is used to insulate the analog input area from the PLC.
H
FX3U-3A-ADP
Insulation method • The DC/DC converter is used to insulate the power supply from the analog inputs.
• Channels are not insulated from each other.
Number of I/O points
8 points (Taken from either the input or output points of the PLC.)
occupied
*1. Adjustment of the offset or gain value will not affect the resolution. In the direct indication mode, however, the
offset/gain cannot be adjusted.
I
FX3U-4AD-PT
*2. The offset and the gain should satisfy the following condition:
1V ≤ (Gain - Offset)
*3. The offset and the gain should satisfy the following condition:
-ADP
A-33
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.1 Analog Input
4.1.8 FX3G-2AD-BD
FX3G-2AD-BD
Specifications
Voltage input Current input
Number of input points 2ch
0V to 10V DC 4mA to 20mA DC
Analog input range
(Input resistance: 198.7 kΩ) (Input resistance: 250 Ω)
Absolute maximum input -0.5V, +15V -2mA, +30mA
Offset
Impossible to change Impossible to change
Gain
Digital output 12 bits, binary 11 bits, binary
Resolution 2.5mV (10V × 1/4000) 8μA (16mA × 1/2000)
Overall accuracy
Ambient temperature:
±0.5% (±50mV) for 10V full scale ±0.5% (±80μA) for 16mA full scale
25±5°C
Ambient temperature:
±1.0% (±100mV) for 10V full scale ±1.0% (±160μA) for 16mA full scale
0 to 55°C
4080 2040
4000
2000
Digital output
Digital output
Input characteristics
A-34
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.2 Analog Output
A
4.2 Analog Output
Common Items
4.2.1 FX3U-4DA-ADP
FX3U-4DA-ADP
B
FX3UC-4AD
FX3U-4AD
Specifications
Voltage output Current output
Number of output points 4ch
0V to 10V DC 4mA to 20mA DC
Analog output range
(External load: 5 k to 1 MΩ) (External load: 500 Ω or less)
Offset C
Impossible to change Impossible to change
FX3U-4AD-ADP
Gain
Digital input 12 bits, binary
Resolution 2.5mV (10V × 1/4000) 4μA (16mA × 1/4000)
Ambient temperature:
±0.5% (±50mV) for 10V full scale ±0.5% (±80μA) for 16mA full scale
25±5°C D
Ambient temperature:
FX3G-2AD-BD
Overall accuracy
±1.0% (±100mV) for 10V full scale ±1.0% (±160μA) for 16mA full scale
0 to 55°C
If the external load resistance (Rs) is less than
5 kΩ, the accuracy increases as shown in the
following formula: (Increase: 100 mV per 1%)
Reference 47100
-0.9 %
-
E
Rs+47
FX3U-4DA
for 10 V full scale
Time required for D/A • FX3U/FX3UC Series PLC : 200μs (Data updated every scan time.)
conversion • FX3S/FX3G/FX3GC Series PLC : 250μs (Data updated every scan time.)
F
10V 20mA
FX3U-4DA-ADP
Analog output
Analog output
Output characteristics
4080
4080
4mA G
0 4000 0 4000
FX3G-1DA-BD
Digital input Digital input
• The photocoupler is used to insulate the analog output area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply from the analog inputs.
• Channels are not insulated from each other.
Number of I/O points
H
0 point (This number is not related to the maximum I/O points of the PLC.)
FX3U-3A-ADP
occupied
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
A-35
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.2 Analog Output
4.2.2 FX2N-2DA
FX2N-2DA
Specifications
Voltage output Current output
Number of output points 2ch
0V to 10V DC
4mA to 20mA DC
Analog output range 0V to 5V DC
(External load: 400 Ω or less)
(External load: 2 k to 1 MΩ)
If the digital value is "0": If the digital value is "0":
Offset*1*2 0V to 1V 4mA
If the digital value is "4000": If the digital value is "4000":
Gain*1*2 5V to 10V 20mA
Digital output 12 bits, binary
Resolution 2.5mV (10V × 1/4000)*2 4μA (16mA × 1/4000)*2
±0.1V ±0.16mA
Overall accuracy
Does not include any load fluctuation. -
Time required for D/A 4ms × number of selected channels
conversion (Operation synchronized with sequence program)
10V 20mA
Analog output
Analog output
Output characteristics
4095
4095
4mA
0 4000 0 4000
Digital input Digital input
If the input data consists of 13 bits or more, only the lower 12 bits will be valid, and the other bits will
be ignored.
• The photocoupler is used to insulate the analog output area from the PLC.
Insulation method
• Channels are not insulated from each other.
Number of I/O points
8 points (Taken from either the input or output points of the PLC.)
occupied
A-36
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.2 Analog Output
A
4.2.3 FX3U-4DA
Common Items
FX3U-4DA
Specifications
Voltage output Current output
Number of output points 4ch B
0mA to 20mA DC
FX3UC-4AD
FX3U-4AD
-10V to +10V DC
Analog output range 4mA to 20mA DC
(External load: 1 k to 1 MΩ)
(External load: 500 Ω or less)
Offset -10V to +9V*1*2 0mA to 17mA*1*3
Gain -9V to +10V*1*2 3mA to 30mA*1*3
Digital input With sign, 16 bits, binary 15 bits, binary
C
FX3U-4AD-ADP
Resolution 0.32mV (20V × 1/64000)*4 0.63μA (20mA × 1/32000)*4
Ambient temperature: ±0.3% (±60μA) for 20mA full scale
Overall accuracy
FX3G-2AD-BD
Reference Includes corrective function by load fluctuation. -
zWhen the output mode is set to "0": zWhen the output mode is "2":
(The dotted line is for mode 3.) E
+10.2V
FX3U-4DA
20.4mA
+10V
+32640
20mA
0
output
+32000
F
-32640
32640
FX3U-4DA-ADP
4mA
-10V
-10.2V 0 32000
Digital input
• The photocoupler is used to insulate the analog output area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply from the analog output.
• Channels are not insulated from each other.
G
FX3G-1DA-BD
Number of I/O points
8 points (Taken from either the input or output points of the PLC.)
occupied
*1. Adjustment of the offset or gain value will not affect the resolution. In the analog value specification
mode, however, the offset/gain cannot be adjusted.
*2. The offset and the gain should satisfy the following condition: H
1V ≤ (Gain - Offset) ≤ 10V
FX3U-3A-ADP
*3. The offset and the gain should satisfy the following condition:
3mA ≤ (Gain - Offset) ≤ 30mA
*4. Adjustment of the offset or gain value will not affect the resolution.
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
A-37
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.2 Analog Output
4.2.4 FX2N-4DA
FX2N-4DA
Specifications
Voltage output Current output
Number of output points 4ch
0mA to 20mA DC
-10V to +10V DC
Analog output range 4mA to 20mA DC
(External load: 2 k to 1 MΩ)
(External load: 500 Ω or less)
Offset -5V to +5V*1*2 -20mA to +20mA*1*3
15 V or less, and 32 mA or less, and
Gain
Gain - Offset ≥ 1V Gain - Offset ≥ 4mA
Digital output With sign, 12 bits, binary 10 bits, binary
Resolution 5mV (10V × 1/2000)*1 20μA (20mA × 1/1000)*1
±1.0% (±200μA) for 20mA full scale
±1.0% (±200mV) for 20V full scale
Overall accuracy Same accuracy for 4mA to 20mA output
Does not include any load fluctuation. -
Time required for D/A
2.1 ms (The number of selected channels will not affect this value.)
conversion
When the output mode is set to "0": When the output mode is "2":
(The dotted line is for mode 1.)
+10V 20mA
Analog output
+2047
1023
4mA
-10V 0 1000
Digital input
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply from the analog output.
• Channels are not insulated from each other.
Number of I/O points
8 points (Taken from either the input or output points of the PLC.)
occupied
*1. Adjustment of the offset or gain value will not affect the resolution.
*2. The offset and the gain should satisfy the following condition:
1V ≤ (Gain - Offset) ≤ 15V
*3. The offset and the gain should satisfy the following condition:
4mA ≤ (Gain - Offset) ≤ 32mA
A-38
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.2 Analog Output
A
4.2.5 FX2NC-4DA
Common Items
FX2NC-4DA
Specifications
Voltage output Current output
Number of output points 4ch B
0mA to 20mA DC
FX3UC-4AD
FX3U-4AD
-10V to +10V DC
Analog output range 4mA to 20mA DC
(External load: 2 k to 1 MΩ)
(External load: 500 Ω or less)
Offset -5V to +5V*1*2 -20mA to +20mA*1*3
Gain -4V to +15V*1*2 -16mA to +32mA*1*3
Digital input With sign, 12 bits, binary 10 bits, binary
C
FX3U-4AD-ADP
Resolution*1 5mV (20V × 1/4000) 20μA (20mA × 1/1000)
Ambient temperature: ±0.5% (±100μA) for 20mA full scale
Overall accuracy
FX3G-2AD-BD
Reference Does not include any load fluctuation. -
zWhen the output mode is set to "0": zWhen the output mode is "2":
(The dotted line is for mode 1.) E
FX3U-4DA
+10V
20mA
+2047
0
output
+2000
F
-2048
1023
FX3U-4DA-ADP
4mA
-10V
0 1000
Digital input
• The photocoupler is used to insulate the analog output area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply from the analog output.
• Channels are not insulated from each other.
G
FX3G-1DA-BD
Number of I/O points
8 points (Taken from either the input or output points of the PLC.)
occupied
*1. Adjustment of the offset or gain value will not affect the resolution.
*2. The offset and the gain should satisfy the following condition:
1V ≤ (Gain - Offset) ≤ 15V H
FX3U-3A-ADP
*3. The offset and the gain should satisfy the following condition:
4mA ≤ (Gain - Offset) ≤ 32mA
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
A-39
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.2 Analog Output
4.2.6 FX3G-1DA-BD
FX3G-1DA-BD
Specifications
Voltage output Current output
Number of output points 1ch
0V to 10V DC 4mA to 20mA DC
Analog output range
(External load: 2 k to 1 MΩ) (External load: 500 Ω or less)
Offset
Impossible to change Impossible to change
Gain
Digital input 12 bits, binary 11 bits, binary
Resolution 2.5mV (10V × 1/4000) 8μA (16mA × 1/2000)
Ambient temperature:
±0.5% (±50mV) for 10V full scale ±0.5% (±80μA) for 16mA full scale
25±5°C
Ambient temperature:
Overall accuracy
±1.0% (±100mV) for 10V full scale ±1.0% (±160μA) for 16mA full scale
0 to 55°C
Shipment adjustment is carried out by external
load resistance 2 kΩ.
If external load resistance becomes larger than
Reference -
2 kΩ, the output voltage will increase slightly.
When the load is 1 MΩ, the output voltage is
about 2% higher than the correct value.
Time required for D/A
60μs (Data updated every scan time.)
conversion
10V 20mA
Analog output
Analog output
Output characteristics
4mA
Caution:
An area of dead band is located in the region of
0V. Therefore the output analog value may not
represent the digital value accurately.
Insulation method • The analog output area is not insulated from the PLC.
Number of I/O points
0 point (This number is not related to the maximum I/O points of the PLC.)
occupied
A-40
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.3 Mixed Analog Input/Output
A
4.3 Mixed Analog Input/Output
Common Items
4.3.1 FX3U-3A-ADP
FX3U-3A-ADP B
Specifications
FX3UC-4AD
FX3U-4AD
Voltage input Current input Voltage output Current output
Number of input/
2ch 1ch
output points
0V to 10V DC 0V to 10V DC 4mA to 20mA DC
Analog input/ 4mA to 20mA DC
(Input resistance: (External load: (External load:
output range
198.7 kΩ)
(Input resistance: 250 Ω)
5 k to 1 MΩ) 500 Ω or less) C
FX3U-4AD-ADP
Absolute -0.5V, -2mA,
- -
maximum input +15V +30mA
Digital input/
12 bits, binary
output
Resolution 2.5mV (10V × 1/4000) 5μA (16mA × 1/3200) 2.5mV (10V × 1/4000) 4μA (16mA × 1/4000)
Ambient D
±0.5% (±50mV) ±0.5% (±80μA) ±0.5% (±50mV) ±0.5% (±80μA)
temperature:
FX3G-2AD-BD
for 10V full scale for 16mA full scale for 10V full scale for 16mA full scale
25±5°C
Ambient
±1.0% (±100mV) ±1.0% (±160μA) ±1.0% (±100mV) ±1.0% (±160μA)
temperature:
for 10V full scale for 16mA full scale for 10V full scale for 16mA full scale
0 to 55°C
Overall accuracy
FX3U-4DA
than 5 kΩ, the accuracy
increases as shown in the
following formula:
Reference - - (Increase: 100 mV per -
1%)
47100
F
-0.9 %
FX3U-4DA-ADP
Rs+47
for 10 V full scale
• FX3U/FX3UC Series PLC :
80μs for each selected input channel + 40μs for each selected output channel
Time required (Operation synchronized with sequence program)
for conversion • FX3S/FX3G/FX3GC Series PLC : G
90μs for each selected input channel + 50μs for each selected output channel
FX3G-1DA-BD
(Operation synchronized with sequence program)
4080 3280
4000 3200 10V 20mA
H
Analog output
Analog output
Digital output
Digital output
I/O
FX3U-3A-ADP
characteristics
20.4mA
10.2V
4080
4080
4mA
0 10V 0 4mA 20mA 0 4000 0 4000
Analog input Analog input Digital input Digital input
I
• The photocoupler is used to insulate the analog input and output area from the PLC.
FX3U-4AD-PT
Insulation
• The DC/DC converter is used to insulate the power supply from the analog input and output.
method
• Channels are not insulated from each other.
-ADP
A-41
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.3 Mixed Analog Input/Output
4.3.2 FX2N-5A
1. Analog input
FX2N-5A
Specifications
Voltage input Current input
Number of input points 4ch
-10V to +10V DC -20mA to +20mA DC
Analog input range -100mV to +100mV DC 4mA to 20mA DC
(Input resistance: 200 kΩ) (Input resistance: 250 Ω)
Absolute maximum input ±15V ±30mA
• -10V to +10V DC:
-32V to +5V DC
Offset -32mA to +10mA
• -100mV to +100mV DC:
-320mV to +50mV DC
• -10V to +10V DC:
-5V to +32V, and Gain - Offset > 1V -10mA to +32mA, and
Gain
• -100mV to +100mV DC: Gain - Offset > 1 mA
-50mV to +320mV, and Gain - Offset > 10mA
• -10V to +10V DC:
With sign, 16 bits, binary
Digital input/output With sign, 15 bits, binary
• -100mV to +100mV DC:
With sign, 12 bits, binary
312.5μV (20V × 1/64000) 1.25μA (40mA × 1/32000)
Resolution
50μV (200mV × 1/4000) 10μA (40mA × 1/4000)
• -10V to +10V DC:
Ambient temperature: ±0.3% (±60mV) for 20V full scale ±0.3% (±120μA) for 40mA full scale
Overall accuracy
25±5°C • -100mV to +100mV DC: Same accuracy for 4mA to 20mA input
±0.5% (±1mV) for 200mV full scale
• -10V to +10V DC:
Ambient temperature: ±0.5% (±100mV) for 20V full scale ±0.5% (±200μA) for 40mA full scale
0±55°C • -100mV to +100mV DC: Same accuracy for 4mA to 20mA input
±1.0% (±2mV) for 200mV full scale
Time required for
1ms × number of selected channels
conversion
zWhen the input mode is set to "0": zWhen the input mode is set to "2":
+32767 +32767 +20.480mA
+32000
+10.240V
+32000
-10V 0 -20mA 0
+20mA
-20.480mA
+10V
-10.240V
-32000 -32000
I/O characteristics
-32768 -32768
zWhen the input mode is set to "1":
+32767
+32000
20.383mA
2mA
0 4mA 20mA
-4000
2. Analog output
FX2N-5A
Specifications
Voltage output Current output
Number of output points 1ch
A-42
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.3 Mixed Analog Input/Output
A
FX2N-5A
Common Items
Specifications
Voltage output Current output
0mA to 20mA DC
-10V to +10V DC
Analog output range 4mA to 20mA DC
(External load: 5 k to 1 MΩ)
(External load: 500 Ω or less)
Offset -10V to +5V 0mA to 10mA B
-9V to +10V, and 3 mA to 30 mA or less, and
FX3UC-4AD
FX3U-4AD
Gain
Gain - Offset ≥ 1V Gain - Offset ≥ 3mA
Digital input/output With sign, 12 bits, binary 10 bits, binary
Resolution 5mV (10V × 1/4000) 20μA (20mA × 1/1000)
C
Overall accuracy
FX3U-4AD-ADP
Ambient temperature: ±1.0% (±400μA) for 40mA full scale
±1.0% (±200mV) for 20V full scale
0±55°C Same accuracy for 4mA to 20mA output
zWhen the output mode is set to "0": zWhen the output mode is "4":
D
FX3G-2AD-BD
(The dotted line is for mode 2.)
Analog output
-32000 0
I/O characteristics
+32000 E
-32768
32767
FX3U-4DA
4mA
-10V
0 32000
Digital input
3. Other
F
FX3U-4DA-ADP
Specifications FX2N-5A
• The photocoupler is used to insulate the analog input and output area from the
PLC.
Insulation method • The DC/DC converter is used to insulate the power supply from the analog input
and output.
• Channels are not insulated from each other. G
FX3G-1DA-BD
Number of I/O points
8 points (Taken from either the input or output points of the PLC.)
occupied
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
A-43
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.3 Mixed Analog Input/Output
4.3.3 FX0N-3A
FX0N-3A
Specifications
Voltage input Current input Voltage output Current output
Number of
input/output 2ch 1ch
points
0V to 10V DC 0V to 10V DC
Analog input/ 4mA to 20mA DC 4mA to 20mA DC
0V to 5V DC 0V to 5V DC
output range*1 (Input resistance: 250 Ω) (External load: 500 Ω)
(Input resistance: 200 kΩ) (External load: 1 k to 1 MΩ)
Absolute
-0.5V, -2mA,
maximum - -
+15V +60mA
input
If the digital value is "0": If the digital value is "0": If the digital value is "0": If the digital value is "0":
Offset*2*3 0V to 1V 0mA to 4mA 0V to 1V 4mA
If the digital value is "250": If the digital value is "250": If the digital value is "250": If the digital value is "250":
Gain*2*3 5V to 10V 20mA 5V to 10V 20mA
Digital input/ 0 to 250 0 to 250
output 8 bits, binary 8 bits, binary
Resolution*3 40mV (10V × 1/250) 64μA (16mA × 1/250) 40mV (10V × 1/250) 64μA (16mA × 1/250)
Overall
±0.1V ±0.16mA ±0.1V ±0.16mA
accuracy
Time required TO instruction processing time × 2 + FROM instruction processing time
for conversion (operation synchronized with sequence program)
255 255
250 250 10V 20mA
Analog output
Digital output
Digital output
Analog output
20.320mA
10.200V
I/O
characteristics
255
255
4mA
0 10V 0 4mA 20mA 0 250 0 250
Analog input Analog input Digital input Digital input
A-44
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.4 Temperature Sensor Input
A
4.4 Temperature Sensor Input
Common Items
4.4.1 FX3U-4AD-PT-ADP
FX3U-4AD-PT-ADP
B
Specifications
FX3UC-4AD
FX3U-4AD
Centigrade (°C) Fahrenheit (°F)
Number of input points 4ch
3-wire platinum resistance thermometer sensor(s)
Input signal
JIS C 1604-1997
Rated temperature range -50°C to +250°C -58°F to +482°F C
FX3U-4AD-ADP
Digital output -500 to +2500 -580 to +4820
Resolution 0.1°C 0.18°F
• Ambient temperature: 25°C±5°C ±0.5% for full scale
Overall accuracy
• Ambient temperature: 0°C to 55°C ±1.0% for full scale
Time required for
conversion
• FX3U/FX3UC Series PLC : 200μs (Data updated every scan time.) D
• FX3S/FX3G/FX3GC Series PLC : 250μs (Data updated every scan time.)
FX3G-2AD-BD
+2550 +4910
+2500 +4820
Digital
output
Digital
output
+491°F
+255°C
Input characteristics
FX3U-4DA
-50°C -58°F
0 0
-67°F
-55°C
+250°C +482°F
-500 Temperature -580 Temperature
-550 -670
• The photocoupler is used to insulate the analog input area from the PLC. F
Insulation method • The DC/DC converter is used to insulate the power supply from the analog inputs.
FX3U-4DA-ADP
• Channels are not insulated from each other.
Number of I/O points 0 points
occupied (This number of points is not related to the maximum number of input/output points of the PLC.)
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
A-45
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.4 Temperature Sensor Input
4.4.2 FX3U-4AD-PTW-ADP
FX3U-4AD-PTW-ADP
Specifications
Centigrade (°C) Fahrenheit (°F)
Number of input points 4ch
3-wire platinum resistance thermometer sensor(s)
Input signal
JIS C 1604-1997
Rated temperature range -100°C to +600°C -148°F to +1112°F
Digital output -1000 to +6000 -1480 to +11120
Resolution 0.2°C to 0.3°C 0.4°F to 0.5°F
• Ambient temperature: 25°C±5°C ±0.5% for full scale
Overall accuracy
• Ambient temperature: 0°C to 55°C ±1.0% for full scale
Time required for • FX3U/FX3UC Series PLC : 200μs (Data updated every scan time.)
conversion • FX3S/FX3G/FX3GC Series PLC : 250μs (Data updated every scan time.)
+6150 +11390
+6000 +11120
Digital
output
Digital
output
+1139°F
+615°C
Input characteristics
-100°C -148°F
-175°F
-115°C
0 +600°C 0 +1112°F
-1000Temperature -1480Temperature
-1150 -1750
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply from the analog inputs.
• Channels are not insulated from each other.
Number of I/O points 0 points
occupied (This number of points is not related to the maximum number of input/output points of the PLC.)
A-46
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.4 Temperature Sensor Input
A
4.4.3 FX3U-4AD-PNK-ADP
Common Items
FX3U-4AD-PNK-ADP
Specifications
Centigrade (°C) Fahrenheit (°F)
Number of input points 4ch B
Platinum resistance thermometer sensor (2-wire or 3-wire) Pt1000
FX3UC-4AD
FX3U-4AD
JIS C 1604-1997
Input signal
Nickel resistance thermometer sensor (2-wire or 3-wire) Ni1000
DIN 43760-1987
Pt1000 -50°C to +250°C Pt1000 -58°F to +482°F
Rated temperature range
Ni1000 -40°C to +110°C Ni1000 -40°F to +230°F C
Pt1000 -500 to +2500 Pt1000 -580 to +4820
FX3U-4AD-ADP
Digital output
Ni1000 -400 to +1100 Ni1000 -400 to +2300
Pt1000 Pt1000
Resolution 0.1°C 0.2°F
Ni1000 Ni1000
Overall accuracy
• Ambient temperature : 25°C±5°C ±0.5% for full scale D
• Ambient temperature : 0°C to 55°C ±1.0% for full scale
FX3G-2AD-BD
Time required for • FX3U/FX3UC Series PLC : 200μs (Data updated every scan time.)
conversion • FX3S/FX3G/FX3GC Series PLC : 250μs (Data updated every scan time.)
• Pt1000 • Pt1000
+2560 +4920
+2500 +4820 E
FX3U-4DA
+492.8F
Approx.
+256C
Approx.
-50C 0 -58F 0
Approx.
Approx.
+250C +482F
-55C
F
-67F
-500 -580
-550 -670
FX3U-4DA-ADP
Input characteristics
• Ni1000 • Ni1000
+1150 +2390
+1100 +2300
G
Approx.
Approx.
+115C
+239F
FX3G-1DA-BD
-40C 0 -40F 0
Approx.
Approx.
+110C +230F
-45C
-49F
-400 -400
-450 -490
• The photocoupler is used to insulate the analog input area from the PLC. H
Insulation method • The DC/DC converter is used to insulate the power supply line from the analog input area.
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
A-47
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.4 Temperature Sensor Input
4.4.4 FX3U-4AD-TC-ADP
FX3U-4AD-TC-ADP
Specifications
Centigrade (°C) Fahrenheit (°F)
Number of input points 4ch
Thermocouple type K or J
Input signal
JIS C 1602-1995
• Type K: -100°C to +1000°C • Type K: -148°F to +1832°F
Rated temperature range
• Type J: -100°C to +600°C • Type J: -148°F to +1112°F
• Type K: -1000 to +10000 • Type K: -1480 to +18320
Digital output
• Type J: -1000 to +6000 • Type J: -1480 to +11120
• Type K: 0.4°C • Type K: 0.72°F
Resolution
• Type J: 0.3°C • Type J: 0.54°F
Overall accuracy ± (0.5% for full scale +1°C)
Time required for • FX3U/FX3UC Series PLC : 200μs (Data updated every scan time.)
conversion • FX3S/FX3G/FX3GC Series PLC : 250μs (Data updated every scan time.)
• Type K • Type K
+10100 +18500
+10000 +18320
Digital
output
Digital
output
+1010°C
+1850°F
-110°C -148°F
0 -166°F 0
-110°C
+1000°C +1832°F
Temperature Temperature
-1000 -1480
-1100 -1660
Input characteristics
• Type J • Type J
+6100
+6000 +11300
+11120
Digital
output
Digital
output
+1130°F
+610°C
-100°C -148°F
-110°C
0 0
-166°F
+600°C +1112°F
Temperature Temperature
-1000 -1480
-1100 -1660
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply from the analog inputs.
• Channels are not insulated from each other.
Number of I/O points 0 points
occupied (This number of points is not related to the maximum number of input/output points of the PLC.)
A-48
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.4 Temperature Sensor Input
A
4.4.5 FX2N-4AD-PT
Common Items
FX2N-4AD-PT
Specifications
Centigrade (°C) Fahrenheit (°F)
Number of input points 4ch B
3-wire platinum resistance thermometer sensor(s)
FX3UC-4AD
FX3U-4AD
DIN43760
Input signal
Pt100 JIS C 1604-1997
JPt100 JIS C 1604-1981
Input signal current 1mA(Constant current system)
Rated temperature range -100°C to +600°C -148°F to +1112°F C
Digital output -1000 to +6000 -1480 to +11120
FX3U-4AD-ADP
Resolution 0.2°C to 0.3°C 0.36°F to 0.54°F
Overall accuracy ±1.0% for full scale
Time required for
60ms (15ms × 4ch)
conversion
D
FX3G-2AD-BD
+6000 +11120
Digital
output
Digital
output
Input characteristics
E
-100°C -148°F
FX3U-4DA
0 +600°C 0 +1112°F
Temperature Temperature
-1000 -1480
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply from the analog inputs. F
• Channels are not insulated from each other.
FX3U-4DA-ADP
Number of I/O points
8 points (Count either the input or output points of the PLC.)
occupied
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
A-49
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.4 Temperature Sensor Input
4.4.6 FX2N-4AD-TC
FX2N-4AD-TC
Specifications
Centigrade (°C) Fahrenheit (°F)
Number of input points 4ch
Thermocouple type K or J
Input signal
JIS C 1602-1995
• Type K: -100°C to +1200°C • Type K: -148°F to +2192°F
Rated temperature range
• Type J: -100°C to +600°C • Type J: -148°F to +1112°F
• Type K: -1000 to +12000 • Type K: -1480 to +21920
Digital output
• Type J: -1000 to +6000 • Type J: -1480 to +11120
• Type K: 0.4°C • Type K: 0.72°F
Resolution
• Type J: 0.3°C • Type J: 0.54°F
Overall accuracy ± (0.5% for full scale +1°C)
Time required for
(240ms±2%) × number of selected channels
conversion
+12000 +21920
(Type K) (Type K)
Digital
output
Digital
output
+6000 +11120
(Type J) (Type J)
Input characteristics
-100°C -148°F
0 +600°C +1200°C 0 +1112°F +2192°F
(Type J) (Type K) (Type J) (Type K)
-1000 -1480
Temperature Temperature
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply from the analog inputs.
• Channels are not insulated from each other.
Number of I/O points
8 points (Taken from either the input or output points of the PLC.)
occupied
A-50
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.4 Temperature Sensor Input
A
4.4.7 FX2N-8AD
Common Items
FX2N-8AD
Specifications
Centigrade (°C) Fahrenheit (°F)
Number of input points 8ch
Thermocouple type K, J, and T
B
Input signal
FX3UC-4AD
FX3U-4AD
JIS C 1602-1995
• Type K • Type K
-100°C to +1200°C -148°F to +2192°F
• Type J • Type J
Rated temperature range
-100°C to +600°C -148°F to +1112°F
• Type T • Type T C
-100°C to +350°C -148°F to +662°F
FX3U-4AD-ADP
• Type K • Type K
-1000 to +12000 -1480 to +21920
• Type J • Type J
Digital output
-1000 to +6000 -1480 to +11120
• Type T • Type T D
-1000 to +3500 -1480 to +6620
FX3G-2AD-BD
Resolution 0.1°C 0.1°F
• Type K: • Type K:
Overall accuracy
±0.5% (±6.5°C) for full scale ±0.5% (±11.7°F) for full scale
Ambient temperature: • Type J: • Type J:
0 to 55°C ±0.5% (±3.5°C) for full scale ±0.5% (±6.3°F) for full scale E
• Type T: • Type T:
FX3U-4DA
±0.7% (±3.15°C) for full scale ±0.7% (±5.67°F) for full scale
Time required for
40ms × number of selected channels
conversion
+12000
(Type K)
+21920
(Type K) F
FX3U-4DA-ADP
Digital
output
Digital
output
+6000 +11120
(Type J) (Type J)
+3500 +6620
Input characteristics (Type T) (Type T)
+600°C +1112°F
-100°C (Type J) -148°F (Type J)
0 +350°C +1200°C 0 +662°F
(Type T)
+2192°F
(Type K)
G
(Type T) (Type K)
FX3G-1DA-BD
-1000 -1480
Temperature Temperature
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply from the analog inputs.
• Channels are not insulated from each other. H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
A-51
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.4 Temperature Sensor Input
4.4.8 FX2N-2LC
FX2N-2LC*1*2
Specifications
Centigrade (°C) Fahrenheit (°F)
Number of input points 2ch
Thermocouple type K, J, R, S, E, T, B, N, PL II, W5Re/W26Re, U, and L
JIS C 1602-1995
Input signal
3-wire platinum resistance thermometer sensor(s)
Pt100 JIS C 1604-1997, JPt100 JIS C 1604-1981
Examples: Examples:
• Type K • Type K
Rated temperature range -100°C to +1300°C -100°F to +2400°F
• Type J • Type J
-100.0°C to +800.0°C -100°F to +2100°F
Examples: Examples:
• Type K • Type K
Digital output -100 to +1300 -100 to +2400
• Type J • Type J
-1000 to +8000 -100 to +2100
Resolution 1°C or 0.1°C 1°F or 0.1°F
Overall accuracy
Ambient temperature:
±0.3°C (±1digit) for full scale
23±5°C
Ambient temperature:
±0.7°C (±1digit) for full scale
0 to 55°C
±1.0°C
Cold junction temperature
±2.0°C if the input value is in the range from -150°C to -100°C
compensation error
±3.0°C if the input value is in the range from -200°C to -150°C
Time required for
500ms (Sampling period)
conversion
Digital
output
Input characteristics
-100°C -100°F
0 +1300°C 0 +2400°F
Temperature Temperature
-100 -100
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply from the analog inputs.
• Channels are insulated from each other.
Number of I/O points
8 points (Taken from either the input or output points of the PLC.)
occupied
*1. For FX2N-2LC, the rated temperature range, digital output value, and resolution depend on the selected sensor
and mode.
*2. Accuracy is not guaranteed for the temperature range of 0°C to 399°C (0°F to 799°F) of the thermocouple -B input
and for the temperature range of 0°F to 32°F of the PL II and WRe5-26 inputs.
A-52
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.4 Temperature Sensor Input
A
4.4.9 FX3U-4LC
Common Items
FX3U-4LC*1*2
Specifications
Centigrade (°C) Fahrenheit (°F)
Number of input points 4ch
Thermocouple type K, J, R, S, E, T, B, N JIS C 1602-1995
B
FX3UC-4AD
FX3U-4AD
PL II, W5Re/W26Re, U, and L
3-wire platinum resistance thermometer sensor(s)
Input signal Pt100 JIS C 1604-1997, JPt100 JIS C 1604-1981
2-wire/3-wire platinum resistance thermometer sensor(s)
Pt1000 JIS C 1604-1997
micro voltage input C
Examples: Examples:
FX3U-4AD-ADP
• Type K • Type K
Rated temperature range -100°C to +1300°C -100°F to +2400°F
• Type J • Type J
-100.0°C to +800.0°C -100°F to +2100°F
Examples: Examples: D
• Type K • Type K
FX3G-2AD-BD
Digital output -100 to +1300 -100 to +2400
• Type J • Type J
-1000 to +8000 -100 to +2100
Resolution 1°C or 0.1°C 1°F or 0.1°F
E
Overall accuracy
Ambient temperature: Measurement accuracy differs depending on the type of input, and the input range.
FX3U-4DA
25±5°C For specification details, refer to the FX3U-4LC User's Manual.
Ambient temperature: Measurement accuracy differs depending on the type of input, and the input range.
0 to 55°C For specification details, refer to the FX3U-4LC User's Manual.
FX3U-4DA-ADP
±3.0°C if the input value is in the range from -200°C to -150°C
Time required for
250ms (Sampling period)
conversion
FX3G-1DA-BD
Digital
output
Digital
output
Input characteristics
-100°C -100°F H
0 0
FX3U-3A-ADP
+1300°C +2400°F
Temperature Temperature
-100 -100
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply from the analog inputs.
• Channels are insulated from each other. I
FX3U-4AD-PT
*1. For FX3U-4LC, the rated temperature range, digital output value, and resolution depend on the selected sensor
-ADP
and mode.
*2. For a detailed description of the micro voltage input, refer to the FX3U-4LC User's Manual. J
FX3U-4AD-PTW
-ADP
A-53
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Version Number
Common Items 5.1 PLC Main Unit
5. Version Number
Right side
9 Z 0 0 0 1 1 0 1 0 0 0 1
A-54
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Version Number
Common Items 5.1 PLC Main Unit
A
2. Checking the front of the product
Common Items
The year and month of production of the PLC main unit can be checked from the manufacturer's serial
number "LOT" on the front (at the bottom) of the product.
The "LOT" indication is adopted for products manufactured at the following times.
Main unit "LOT" indication adoption time
FX3S Series PLC March 2013 and later (From first product) B
FX3UC-4AD
FX3U-4AD
FX3G Series PLC October 2008 and later
FX3GC Series PLC January 2012 and later (From first product)
FX3U Series PLC January 2009 and later
FX3UC Series PLC January 2009 and later
C
Example: FX3U-48MR/ES
FX3U-4AD-ADP
D
FX3G-2AD-BD
<Product during December, 2009 or earlier> <Product from January, 2010>
9 Z 1 0 1
E
FX3U-4DA
Month (Example: Dec.): Month (Example: Jan.):
1 to 9 = January to September, 1 to 9 = January to September,
X = October, Y = November, Z = December X = October, Y = November, Z = December
Year (Example: 2009): Last digit of year Year (Example: 2010): Last two digit of year
FX3U-4DA-ADP
The PLC version can be checked by reading the last three digits of device D8001 or D8101.
D8001/D8101 2 4 1 0 0
PLC type and
Version data (Example: Ver. 1.00)
version number
PLC type (Example: 24 = FX3U/FX3UC series)
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
A-55
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Version Number
Common Items 5.2 Special adapter
Left side
9 Z 0 0 0 1 1 0 1 0 0 0 1
A-56
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Manual Introduction (Types, Contents, and Obtainment)
Common Items 6.1 How to Use the Manuals
Common Items
6. Manual Introduction (Types, Contents, and Obtainment)
This chapter describes the FX3S/FX3G/FX3GC/FX3U/FX3UC Series PLC main unit instruction manual and the B
various manuals of analog products.
FX3UC-4AD
FX3U-4AD
6.1 How to Use the Manuals
Various analog products can be connected to the FX Series PLC to control the analog inputs and outputs.
C
FX3U-4AD-ADP
PLC
FX3G-2AD-BD
For sequence programs:
Programming manual Supplied separately
FX3U-4DA
Analog products
Depending on the product type, the "Installation Manual" or the "User's Manual" is supplied with the
product.
For a detailed description, refer to the separate manual "User's Manual - Analog Control Edition" as F
described below:
FX3U-4DA-ADP
For installation and parts identification:
FX3G-1DA-BD
(Necessary information is in the user's manual, but for a detailed description,
refer to the separate manual.)
Analog control H
FX3U-3A-ADP
Voltage input Current input Voltage output Current output Temperature input
J
FX3U-4AD-PTW
-ADP
A-57
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Manual Introduction (Types, Contents, and Obtainment)
Common Items 6.2 Description of Related Manuals
Supplied with
Document product or
Manual type Description
number supplied
separately
FX3S/FX3G/FX3GC/FX3U/FX3UC Series PLC
FX3S/FX3G/FX3GC/FX3U/ Supplied
This manual describes the details of the FX3S/FX3G/
FX3UC Series User’s Manual JY997D16701 separately
FX3GC/FX3U/FX3UC Series PLC analog products.
- Analog Control Edition (This manual)
Supplied with
Document product or
Manual type Description
number supplied
separately
FX3S Series PLC
I/O specifications, wiring and installation of the PLC main
FX3S Series Supplied with unit FX3S extracted from the FX3S Series User’s Manual -
JY997D48301
HARDWARE MANUAL product Hardware Edition. For detailed explanation, refer to the
FX3S Series User’s Manual - Hardware Edition.
I/O specifications, wiring and installation of the PLC main
unit FX3S-30M/E-2AD extracted from the FX3S
FX3S-30M/E-2AD Supplied with
JY997D51701 Series User’s Manual - Hardware Edition. For detailed
HARDWARE MANUAL product
explanation, refer to the FX3S Series User’s Manual -
Hardware Edition.
Details about the hardware including I/O specifications,
FX3S Series User’s Manual Supplied
JY997D48601 wiring, installation and maintenance of the FX3S PLC
- Hardware Edition separately
main unit.
FX3G Series PLC
I/O specifications, wiring and installation of the PLC main
FX3G Series Supplied with unit FX3G extracted from the FX3G Series User’s Manual
JY997D46001
HARDWARE MANUAL product - Hardware Edition. For detailed explanation, refer to the
FX3G Series User’s Manual - Hardware Edition.
Details about the hardware including I/O specifications,
FX3G Series User’s Manual Supplied
JY997D31301 wiring, installation and maintenance of the FX3G PLC
- Hardware Edition separately
main unit.
A-58
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Manual Introduction (Types, Contents, and Obtainment)
Common Items 6.2 Description of Related Manuals
A
Supplied with
Common Items
Document product or
Manual type Description
number supplied
separately
FX3GC Series PLC
I/O specifications, wiring and installation of the PLC main
unit FX3GC extracted from the FX3GC Series User’s
B
FX3GC Series Supplied with
FX3UC-4AD
FX3U-4AD
JY997D45201 Manual - Hardware Edition. For detailed explanation,
HARDWARE MANUAL product
refer to the FX3GC Series User’s Manual - Hardware
Edition.
Details about the hardware including I/O specifications,
FX3GC Series User’s Manual Supplied
JY997D45401 wiring, installation and maintenance of the FX3GC PLC
- Hardware Edition separately
main unit. C
FX3U-4AD-ADP
FX3U Series PLC
I/O specifications, wiring and installation of the PLC main
FX3U Series Supplied with unit FX3U extracted from the FX3U Series User’s Manual
JY997D50301
HARDWARE MANUAL product - Hardware Edition. For detailed explanation, refer to the
FX3U Series User’s Manual - Hardware Edition.
Details about the hardware including I/O specifications, D
FX3U Series User’s Manual Supplied
FX3G-2AD-BD
JY997D16501 wiring, installation and maintenance of the FX3U PLC
- Hardware Edition separately
main unit.
FX3UC Series PLC
I/O specifications, wiring and installation of the PLC main
unit FX3UC (D, DS, DSS) extracted from the FX3UC
FX3UC (D, DS, DSS) Series
HARDWARE MANUAL
JY997D50501
Supplied with
product
Series User’s Manual - Hardware Edition. For detailed E
explanation, refer to the FX3UC Series User’s Manual -
FX3U-4DA
Hardware Edition.
I/O specifications, wiring and installation of the PLC main
unit FX3UC-32MT-LT-2 extracted from the FX3UC Series
FX3UC-32MT-LT-2 Supplied with
JY997D31601 User’s Manual - Hardware Edition. For detailed
HARDWARE MANUAL product
explanation, refer to the FX3UC Series User’s Manual -
Hardware Edition. F
FX3U-4DA-ADP
Details about the hardware including I/O specifications,
FX3UC Series User’s Manual Supplied
JY997D28701 wiring, installation and maintenance of the FX3UC PLC
- Hardware Edition separately
main unit.
FX3S/FX3G/FX3GC/FX3U/FX3UC Series PLC
FX3S/FX3G/FX3GC/FX3U/
FX3UC Series Programming Supplied
This manual describes the basic and application G
JY997D16601 commands necessary for the FX3S/FX3G/FX3GC/FX3U/
FX3G-1DA-BD
Manual - Basic & Applied separately
FX3UC Series PLC.
Instruction Edition
MELSEC-Q/L/F
Supplied Programming methods, specifications, functions, etc.
Structured Programming SH-080782
separately required to create structured programs.
Manual (Fundamentals)
FXCPU Structured
Supplied Devices, parameters, etc. provided in structured projects
H
Programming Manual JY997D26001
FX3U-3A-ADP
separately of GX Works2.
[Device & Common]
FXCPU Structured
Supplied Sequence instructions provided in structured projects of
Programming Manual JY997D34701
separately GX Works2.
[Basic & Applied Instruction]
FXCPU Structured
Supplied Application functions provided in structured projects of
I
Programming Manual JY997D34801
FX3U-4AD-PT
separately GX Works2.
[Application Functions]
-ADP
J
FX3U-4AD-PTW
-ADP
A-59
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Manual Introduction (Types, Contents, and Obtainment)
Common Items 6.2 Description of Related Manuals
Supplied with
Document product or
Manual type Description
number supplied
separately
Analog input unit
This manual describes the FX3G-2AD-BD analog input
FX3G-2AD-BD Supplied with
JY997D33501 expansion board hardware, such as specifications and
INSTALLATION MANUAL product
installation.
This manual describes the FX3U-4AD analog input
FX3U-4AD Supplied with
JY997D20701 special function block hardware, such as specifications
INSTALLATION MANUAL product
and installation, and also describes various programs.
This manual describes the FX3U-4AD-ADP analog input
FX3U-4AD-ADP Supplied with
JY997D13901 special adapter hardware, such as specifications and
USER’S MANUAL product
installation.
This manual describes the FX2N-8AD analog input
FX2N-8AD Supplied with
JY992D86001 special function block hardware, such as specifications
USER’S MANUAL product
and installation, and also describes various programs.
This manual describes the FX2N-4AD analog input
FX2N-4AD Supplied with
JY992D65201 special function block hardware, such as specifications
USER’S GUIDE product
and installation, and also describes various programs.
This manual describes the FX2N-2AD analog input
FX2N-2AD Supplied with
JY992D74701 special function block hardware, such as specifications
USER’S GUIDE product
and installation, and also describes various programs.
This manual describes the FX2NC-4AD analog input
FX2NC-4AD Supplied with
JY997D07801 special function block hardware, such as specifications
USER’S MANUAL product
and installation, and also describes various programs.
Analog output unit
This manual describes the FX3G-1DA-BD analog output
FX3G-1DA-BD Supplied with
JY997D33601 expansion board hardware, such as specifications and
INSTALLATION MANUAL product
installation.
This manual describes the FX3U-4DA analog output
FX3U-4DA Supplied with
JY997D20801 special function block hardware, such as specifications
INSTALLATION MANUAL product
and installation.
This manual describes the FX3U-4DA-ADP analog output
FX3U-4DA-ADP Supplied with
JY997D14001 special adapter hardware, such as specifications and
USER’S MANUAL product
installation.
This manual describes the FX2NC-4DA analog output
FX2NC-4DA Supplied with
JY997D07601 special function block hardware, such as specifications
USER’S MANUAL product
and installation, and also describes various programs.
This manual describes the FX2N-4DA analog output
FX2N-4DA Supplied with
JY992D65901 special function block hardware, such as specifications
USER’S GUIDE product
and installation, and also describes various programs.
This manual describes the FX2N-2DA analog output
FX2N-2DA Supplied with
JY992D74901 special function block hardware, such as specifications
USER’S GUIDE product
and installation, and also describes various programs.
Analog input/output unit
This manual describes the FX3U-3A-ADP analog input/
FX3U-3A-ADP Supplied with
JY997D35601 output special adapter hardware, such as specifications
USER’S MANUAL product
and installation.
This manual describes the FX2N-5A analog input/output
FX2N-5A Supplied with
JY997D11401 special function block hardware, such as specifications
USER’S MANUAL product
and installation, and also describes various programs.
This manual describes the FX0N-3A analog input/output
FX0N-3A Supplied with
JY992D49001 special function block hardware, such as specifications
USER’S GUIDE product
and installation, and also describes various programs.
A-60
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Manual Introduction (Types, Contents, and Obtainment)
Common Items 6.2 Description of Related Manuals
Common Items
Supplied with
Document product or
Manual type Description
number supplied
separately
Temperature sensor unit
B
FX3UC-4AD
FX3U-4AD
This manual describes the FX3U-4AD-PT-ADP platinum
FX3U-4AD-PT-ADP Supplied with
JY997D14701 resistance thermometer input special adapter hardware,
USER’S MANUAL product
such as specifications and installation.
This manual describes the FX3U-4AD-PTW-ADP
FX3U-4AD-PTW-ADP Supplied with
JY997D29101 platinum resistance thermometer input special adapter
USER’S MANUAL product
hardware, such as specifications and installation. C
FX3U-4AD-ADP
This manual describes the FX3U-4AD-PNK-ADP
FX3U-4AD-PNK-ADP Supplied with
JY997D29201 resistance thermometer input special adapter hardware,
USER’S MANUAL product
such as specifications and installation.
This manual describes the FX3U-4AD-TC-ADP
FX3U-4AD-TC-ADP Supplied with
JY997D14801 thermocouple input special adapter hardware, such as
USER’S MANUAL product
specifications and installation. D
FX3G-2AD-BD
This manual describes the FX3U-4LC temperature
FX3U-4LC Supplied with
JY997D38901 adjustment special function block hardware, such as
INSTALLATION MANUAL product
specifications and installation.
This manual describes the FX3U-4LC temperature
FX3U-4LC Supplied adjustment special function block hardware, such as
USER’S MANUAL
JY997D39101
separately specifications and installation, and also describes various E
programs.
FX3U-4DA
This manual describes the FX2N-4AD-PT platinum
FX2N-4AD-PT Supplied with resistance thermometer input special function block
JY992D65601
USER’S GUIDE product hardware, such as specifications and installation, and
also describes various programs.
FX3U-4DA-ADP
USER’S GUIDE product specifications and installation, and also describes various
programs.
This manual describes the FX2N-2LC temperature
FX2N-2LC Supplied with
JY992D85601 adjustment special function block hardware, such as
USER’S GUIDE product
specifications and installation.
This manual describes the FX2N-2LC temperature
G
FX3G-1DA-BD
FX2N-2LC Supplied adjustment special function block hardware, such as
JY992D85801
USER’S MANUAL separately specifications and installation, and also describes various
programs.
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
A-61
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 7 Generic Names and Abbreviations in This Manual
Common Items 6.2 Description of Related Manuals
A-62
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 7 Generic Names and Abbreviations in This Manual
Common Items 6.2 Description of Related Manuals
A
Abbreviation, generic name Description
Common Items
High-speed input/output special Generic name for high-speed input special adapter and high-speed output
adapter special adapter.
2HSY-ADP FX3U-2HSY-ADP
4HSX-ADP FX3U-4HSX-ADP
Communication special adapter Generic name for communication special adapter.
B
FX3UC-4AD
FX3U-4AD
232ADP FX3U-232ADP(-MB), FX2NC-232ADP, FX0N-232ADP, FX-232ADP
485ADP FX3U-485ADP(-MB), FX2NC-485ADP, FX0N-485ADP, FX-485ADP
ENET-ADP FX3U-ENET-ADP
CF card special adapter Generic name for CF card special adapter.
CF-ADP FX3U-CF-ADP C
Analog special adapter Generic name for analog special adapter.
FX3U-4AD-ADP
4AD-ADP FX3U-4AD-ADP
4DA-ADP FX3U-4DA-ADP
3A-ADP FX3U-3A-ADP
PT-ADP FX3U-4AD-PT-ADP
D
PTW-ADP FX3U-4AD-PTW-ADP
FX3G-2AD-BD
PNK-ADP FX3U-4AD-PNK-ADP
TC-ADP FX3U-4AD-TC-ADP
Special adapter connection
conversion adapter or connection Generic name for CNVADP
conversion adapter E
CNVADP FX3S-CNV-ADP, FX3G-CNV-ADP
FX3U-4DA
3. Extension unit
Abbreviation, generic name Description
Generic name for the FX3U Series extension unit, FX3UC Series extension unit,
FX2N Series extension unit, FX2NC Series extension unit, and FX0N Series F
extension unit.
Extension unit
FX3U-4DA-ADP
The number of connectable units, however, depends on the type of the main
unit. To check the number of connectable units, refer to the User’s Manual -
Hardware Edition of the main unit to be used for your system.
FX3U Series extension unit Generic name for FX3U Series special function block.
FX3UC Series extension unit Generic name for FX3UC Series special function block.
Generic name for FX2N Series input/output powered extension unit, FX2N Series
G
FX3G-1DA-BD
FX2N Series extension unit input/output extension block, FX2N Series special function unit, and FX2N Series
special function block.
Generic name for FX2NC Series input/output extension block and FX2NC Series
FX2NC Series extension unit
special function block.
Generic name for FX0N Series input/output extension block and FX0N Series
FX0N Series extension unit
special function block. H
FX3U-3A-ADP
Generic name for FX3U Series special function block, FX3UC Series special
function block, FX2N Series special function unit, FX2N Series special function
Special function unit/block
block, FX2NC Series special function block, and FX0N Series special function
block.
FX3U Series special FX3U-4AD, FX3U-4DA, FX3U-4LC, FX3U-2HC, FX3U-1PG, FX3U-20SSC-H,
function block FX3U-64CCL I
FX3UC Series special
FX3U-4AD-PT
FX3UC-4AD
function block
FX2N Series special
FX2N-10GM, FX2N-20GM, FX2N-1RM-E-SET, FX2N-1RM-SET
function unit
-ADP
J
FX3U-4AD-PTW
-ADP
A-63
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 7 Generic Names and Abbreviations in This Manual
Common Items 6.2 Description of Related Manuals
4. Peripheral unit
Abbreviation, generic name Description
Peripheral unit
Generic name for programming software, handy programming panel,
Peripheral unit
and display units.
Programming tool
Programming tool Generic name for programming software, and handy programming panel.
Programming software Generic name for Programming software.
Generic name for SWDNC-GXW2-J and SWDNC-GXW2-E programming
GX Works2
software packages.
Generic name for SWD5C-GPPW-J and SWD5C-GPPW-E programming
GX Developer
software packages.
Handy programming panels Generic name for the following models
(HPP) FX-30P, FX-20P(-E)-SET0, FX-20P(-E), FX-10P-SET0, FX-10P(-E)
A-64
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)
Common Items
B
FX3UC-4AD
FX3U-4AD
FX3S/FX3G/FX3GC/FX3U/FX3UC Series
Programmable Controllers C
FX3U-4AD-ADP
User's Manual [Analog Control Edition]
FX3G-2AD-BD
E
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
Foreword
This manual describes the specifications, wiring, and operation methods for the FX3U-4AD/FX3UC-4AD
special extension block (4-channel analog input) and should be read and understood before attempting to
I
FX3U-4AD-PT
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
J
FX3U-4AD-PTW
rights which may occur as a result of using the contents noted in this manual.
B-1
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)
B-2
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 1.1 Outline of Functions
Common Items
1. Outline
This chapter outlines the FX3U-4AD/FX3UC-4AD. B
For common descriptions of the FX3U-4AD and FX3UC-4AD, these model names are referred to as the 4AD.
FX3UC-4AD
FX3U-4AD
1.1 Outline of Functions
The FX3U-4AD is an analog special function block which is connectable with the FX3G/FX3GC/FX3U/FX3UC
Series PLC used to capture 4-ch voltage/current data. The FX3UC-4AD cannot be connected to the FX3G/
C
FX3U-4AD-ADP
FX3U Series PLC.
1) Up to 8*1 units can be connected to the FX3G/FX3GC/FX3U/FX3UC Series PLC.
(including the other special function blocks).
2) Either "voltage input" or "current input" can be specified for each channel.
3) The A/D conversion values will be stored in the 4AD buffer memory (BFM). D
FX3G-2AD-BD
4) Set the digital filter to read out stable A/D conversion values.
5) For each channel, up to 1,700 A/D conversion values can be stored as history data.
FX3U-4DA
(including other types of special function blocks)
Number of connectable units
FX3G/FX3U Series PLC
To check the connectable PLC F
model number, refer to
FX3U-4DA-ADP
Section 1.3.
FX3G-1DA-BD
For a detailed description of
analog data reading programs,
refer to Chapter 4, 6, and 7.
For a detailed description of
Program
Transmission direction Buffer memory the buffer memory, refer to
Section 5.3, and Section 5.4. H
FROM (FNC 78) BFM#0
FX3U-3A-ADP
Refer to the system configuration shown in the User's Manual - Hardware Edition to check the number of
connectable units and to configure the entire system. I
FX3U-4AD-PT
J
FX3U-4AD-PTW
-ADP
B-3
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 1.2 Setup Procedure Before Starting Operation
FX3U-4AD/FX3UC-4AD
Refer to Chapter 1.
Wiring Wiring:
• Power supply line
• Analog input line
Refer to Chapter 4.
Refer to Chapter 7.
B-4
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 1.3 Connectable PLC and Version Numbers
A
1.3 Connectable PLC and Version Numbers
Common Items
FX3U-4AD is compatible with the following PLC.
Compatible PLC Version number Date of production
FX3G Series PLC Ver. 1.00 or later After June 2008 (From first product)
FX3GC Series PLC Ver. 1.40 or later After January 2012 (From first product) B
FX3U Series PLC Ver. 2.20 or later After May 2005 (From first product)
FX3UC-4AD
FX3U-4AD
FX3UC Series PLC Ver. 1.30 or later After August 2004
FX3UC-4AD is compatible with the following PLC.
Compatible PLC Version number Date of production
FX3GC Series PLC Ver. 1.40 or later After January 2012 (From first product)
FX3UC Series PLC Ver. 1.30 or later After August 2004
C
FX3U-4AD-ADP
1. Version check
The PLC version can be checked by reading the last three digits of device D8001 or D8101.
→ For a detailed description of the version check,
refer to A. Common Items Subsection 5.1.2.
2. How to check the manufacturer's serial number
The year and month of production of the product can be checked on the nameplate, and on the front of the
D
FX3G-2AD-BD
product.
→ For a detailed description of how to check the manufacturer's serial number,
refer to A. Common Items Subsection 5.1.1.
FX3U-4DA
The following programming tools and versions are applicable for the FX3G/FX3GC/FX3U/FX3UC series.
1. English versions
Model name Media model name Applicable version Remarks
FX3G PLC
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later F
GX Developer SWD5C-GPPW-E Ver. 8.72A or later -
FX3U-4DA-ADP
FX-30P Ver. 1.00 or later
FX3GC PLC
GX Works2 SWDNC-GXW2-E Ver. 1.77F or later
-
FX-30P Ver. 1.30 or later
FX3U and FX3UC PLCs G
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
FX3G-1DA-BD
GX Developer SWD5C-GPPW-E Ver. 8.18U or later -
FX-30P Ver. 1.00 or later
2. Japanese versions
Model name
FX3G PLC
Media model name Applicable version Remarks
H
FX3U-3A-ADP
Point
• It is possible to create programs in FX3GC PLC using programming tools of inapplicable versions by
-ADP
B-5
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 2.1 Generic Specifications
2. Specifications
This chapter describes the general, power supply, and performance specifications for the 4AD.
Item Specifications
Ambient 0 to 55 °C (32 to 131 °F) when operating
temperature -25 to 75 °C (-13 to 167 °F) when stored
Relative
5 to 95 %RH (no condensation) when operating
humidity
Frequency Acceleration Half amplitude
(Hz) (m/s2) (mm)
10 times of testing in
Vibration 10 to 57 - 0.035 each direction (X-, Y-,
DIN Rail Mounting
resistance*1 57 to 150 4.9 - and Z-axis directions)
(Total: 80 min, each)
10 to 57 - 0.075
Direct Mounting*2
57 to 150 9.8 -
Shock
147 m/s2 Acceleration, Action time: 11 ms, 3 times by half-sine pulse in each direction X, Y, and Z
resistance*1
Noise Using noise simulator of:
resistance Noise voltage: 1,000 Vp-p / Noise width: 1 μs / Rise: 1 ns / Cycle: 30 to 100 Hz
Dielectric
withstand 500 V AC, for 1 min
voltage Between all terminals and ground terminal
Insulation 5 MΩ or more using 500 V DC
resistance insulation resistance meter
Class D grounding (grounding resistance: 100 Ω or less)
Grounding
<Common grounding with a heavy electrical system is not allowed.>*3
Working
Free from corrosive or flammable gas and excessive conductive dust
atmosphere
Working
altitude < 2000 m*4
B-6
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 2.2 Power Supply Specifications
A
2.2 Power Supply Specifications
Common Items
FX3U-4AD
Item Specifications
A/D conversion 24V DC ±10%, 90mA B
circuit drive power (It is necessary to supply 24V DC from the terminal block.)
FX3UC-4AD
FX3U-4AD
5V DC, 110mA
CPU drive power (Since the internal power is supplied from the main unit, it is not necessary to supply power
externally.)
FX3UC-4AD C
FX3U-4AD-ADP
Item Specifications
A/D conversion 24V DC ±10%, 80mA
circuit drive power (It is necessary to supply 24V DC from the power connector.)
5V DC, 100mA
CPU drive power
(Since the internal power is supplied from the main unit, it is not necessary to supply the power.)
D
FX3G-2AD-BD
2.3 Performance Specifications
Specifications
Item
Voltage input Current input E
FX3U-4DA
-10V to +10V DC -20mA to +20mA DC, 4mA to 20mA DC
Analog input range
(Input resistance: 200 kΩ) (Input resistance: 250 Ω)
Offset*1 -10V to +9V*2 -20mA to +17mA*3
Gain*1 -9V to +10V*2 -17mA to +30mA*3
Absolute maximum
±15V ±30mA
F
input
FX3U-4DA-ADP
Digital output With sign, 16bits, binary With sign, 15bits, binary
0.32mV (20V × 1/ 64,000) 1.25μA (40mA × 1/ 32,000)
Resolution*4 2.5mV (20V × 1/8000) 5.00μA (40mA × 1/8000)
• Ambient temperature: 25°C±5°C
• Ambient temperature: 25°C±5°C ±0.5% (±200μA) for 40mA full scale G
±0.3% (±60mV) for 20V full scale Same accuracy (±200μA) for 4mA to 20mA input
FX3G-1DA-BD
Overall accuracy
• Ambient temperature: 0°C to 55°C • Ambient temperature: 0°C to 55°C
±0.5% (±100mV) for 20V full scale ±1% (±400μA) for 40mV full scale
Same accuracy (±400μA) for 4mA to 20mA input
Time required for 500μs × number of selected channels
A/D conversion (If 1 or more channels use the digital filter(s): 5ms × number of selected channels) H
• The photocoupler is used to insulate the analog input area from the PLC.
FX3U-3A-ADP
Insulation method • The DC/DC converter is used to insulate the analog input area from the power supply unit.
• Channels are not insulated from each other.
Number of I/O
8 points (Taken from either the input or output points of the PLC.)
points occupied
*1. Adjustment of the offset or gain value will not affect the resolution. In the direct indication mode,
I
FX3U-4AD-PT
*3. The offset and the gain should satisfy the following condition:
3 mA ≤ (Gain - Offset) ≤ 30 mA J
*4. If 1 or more channels use the digital filter(s), the time required for A/D conversion will be
FX3U-4AD-PTW
B-7
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 2.4 Input Mode (Characteristics) BFM#0
+10.2V
+10.2V
Input Input Input
voltage -10V 0 voltage -10V 0 voltage -10V 0
+10V +10V +10V
-10.2V
-10.2V
-10.2V
20.4 mA
20.4 mA
4000
+20.4mA
+20.4mA
-20.4mA
-20.4mA
B-8
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 2.4 Input Mode (Characteristics) BFM#0
Common Items
3. Wiring
This chapter describes the 4AD wiring. B
Observe the following cautions when wiring the 4AD.
FX3UC-4AD
FX3U-4AD
WIRING PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before attempting wiring work.
Failure to do so may cause electric shock or damage to the product. C
FX3U-4AD-ADP
WIRING PRECAUTIONS
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn
out.
D
FX3G-2AD-BD
• Do not wire vacant terminals externally.
Doing so may damage the product.
• Perform class D grounding (grounding resistance: 100Ω or less) to the grounding terminal on the main unit.
Do not use common grounding with heavy electrical systems.
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions. E
• Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise:
FX3U-4DA
- Do not bundle the power line or shield of the analog input/output cable together with or lay it close to the main
circuit, high-voltage line, or load line.
Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
100mm (3.94") or more away from the main circuit, high-voltage line, or load line.
- Ground the shield of the analog input/output cable at one point on the signal receiving side.
However, do not use common grounding with heavy electrical systems. F
• Make sure to properly wire to the terminal block (European type) in accordance with the following precautions.
FX3U-4DA-ADP
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
- The disposal size of the cable end should follow the dimensions described in the manual.
- Tightening torque should follow the specifications in the manual.
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends. G
- Do not connect more than the specified number of wires or electric wires of unspecified size.
FX3G-1DA-BD
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
• Make sure to properly wire the terminal block in accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
- The disposal size of the cable end should follow the dimensions described in the manual.
- Tightening torque should follow the specifications in the manual. H
FX3U-3A-ADP
- Tighten the screws using a Phillips-head screwdriver No.2 (shaft diameter 6mm (0.24") or less).
Make sure that the screwdriver does not touch the partition part of the terminal block.
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
B-9
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 3.1 Terminal Layout
FX3U-4AD
Signal Application
24+
24V DC power supply
24-
Ground terminal
V+
VI- Channel-1 analog input
I+
FG
V+ Channel-2 analog input
VI-
I+
FG
V+ Channel-3 analog input
VI-
I+
FG
V+ Channel-4 analog input
VI-
I+
FX3UC-4AD
Signal Application
V1+
I1+
Channel-1 analog input
COM1
SLD
V2+
I2+
Channel-2 analog input
COM2
SLD
• Do not connect any lines.
•
V3+
I3+
Channel-3 analog input
COM3
SLD
V4+
I4+
Channel-4 analog input
COM4
SLD
Ground terminal
B-10
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 3.2 Cable and Terminal Tightening Torque
A
3.2 Cable and Terminal Tightening Torque
Common Items
3.2.1 Power cable (FX3UC-4AD)
Supply the 24 V DC power to FX3UC-4AD via the power supply connector. B
The power crossover cable (type "C" shown in the following table) is supplied with the FX3UC-4AD.
FX3UC-4AD
FX3U-4AD
To connect the power cable, refer to the User's Manual - Hardware Edition of the PLC main unit.
There are 3 types of power cables as shown in the following table. Types "A" and "B" are supplied with the
main unit, and type "C" is supplied with the input extension blocks for FX2NC Series or the special function
blocks for FX3UC/FX2NC Series.
Type Application Model Length Cable supplied with C
1m
FX3U-4AD-ADP
A Power cable for main unit FX2NC-100MPCB
(3’ 3")
FX3GC/FX3UC Series PLC main unit
Input power cable for input 1m
B FX2NC-100BPCB
extension block (3’ 3")
Input power crossover cable 0.1 m • Input extension block for FX2NC Series
C FX2NC-10BPCB1
for input extension block (0’ 3") • Special function block for FX3UC/FX2NC Series D
FX3G-2AD-BD
The crossover cable (type "C") can skip up to 4 16-point output blocks to connect units.
If more blocks should be skipped to supply power to an input extension block, use cable type "B".
FX3U-4DA
The end disposal of the cable shows blow.
Tighten the terminal to a torque of 0.5 to 0.8 N•m.
Do not tighten terminal screws with a torque outside the above-mentioned range.
Failure to do so may cause equipment failures or malfunctions.
• When one wire is connected to one terminal F
Terminal Crimp
FX3U-4DA-ADP
3.2 (0.13") screw terminal
6.2 mm (0.24")
or less
3.2 (0.13")
6.2 mm (0.24") Terminal G
or less
FX3G-1DA-BD
• When two wires are connected to one terminal
3.2 (0.13")
6.2 mm (0.24") Terminal Crimp
screw terminal
or less
6.3 mm (0.25") H
or more
FX3U-3A-ADP
3.2 (0.13")
6.2 mm (0.24") Terminal
or less 6.3 mm (0.25")
or more I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
B-11
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 3.2 Cable and Terminal Tightening Torque
1. Cable
Applicable cable and tightening torque
Wire size Tightening
Termination
(stranded wire/solid wire) torque
0.3 mm2 to 0.5 mm2 • To connect a stranded cable, peel the cover off the cable
Single wire and then twist the core before connection.
(AWG22 to 20)
• To connect a single-wire cable, peel the cover off the
Double wire 0.3 mm2 (AWG22)×2 cable before connection.
0.22 to • Ferrule with insulation sleeve
0.3 mm2 to 0.5 mm2 0.25 N•m (recommended terminal)
Ferrule with (AWG22 to 20) AI 0.5-8WH : Manufactured by Phoenix Contact
insulation (Refer to the external • Caulking tool
sleeve view of ferrule shown in
CRIMPFOX 6*1 : Manufactured by Phoenix Contact
the following figure.)
(or CRIMPFOX 6T-F*2 : Manufactured by Phoenix Contact)
• To terminate cable end using ferrule with insulation sleeve: • Ferrule with insulation sleeve
If the cable sheath is too thick, it may be difficult to insert the cable Insulation sleeve Contact area
into the insulation sleeve. For this reason, select an appropriate cable (Crimp area)
while referring to the external view.
<Reference> 8mm (0.31")
Manufacturer Model Caulking tool 2.6mm 14mm
(0.1")
CRIMPFOX 6*3 (0.55")
Phoenix Contact AI 0.5-8WH
(or CRIMPFOX 6T-F*4)
3. Tool
For tightening the terminal, use a commercially available small screwdriver
The head
having a straight form that is not widened toward the end as shown right. should be
straight.
Note:
If the diameter of screwdriver grip is too small, tightening torque will not be
able to be achieved. To achieve the appropriate tightening torque shown in 0.4mm 2.5mm
the table above, use the following screwdriver or an appropriate (0.01") (0.09")
replacement (grip diameter: approximately 25 mm (0.98")).
<Reference>
Manufacturer Model
Phoenix Contact SZS 0.4×2.5
B-12
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 3.3 Examples of Power Supply Circuit
A
3.3 Examples of Power Supply Circuit
Common Items
3.3.1 FX3U-4AD
Below are shown examples of circuits for using the 24V DC service power supply of the FX3G/FX3U Series B
PLC.
FX3UC-4AD
FX3U-4AD
1) Sink input [- common] wiring
AC power
100 to 240 V
C
FX3U-4AD-ADP
Class-D
grounding
L N S/S 0V 24V 24+ 24-
D
FX3G-2AD-BD
+15V
FX3U-4DA
2) Source input [+ common] wiring
AC power
F
100 to 240 V
FX3U-4DA-ADP
Class-D
grounding G
FX3G-1DA-BD
L N S/S 0V 24V 24+ 24-
+15V
FX3U-4AD
Connect the "S/S" terminal of the main unit to the "0V" terminal.
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
B-13
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 3.3 Examples of Power Supply Circuit
3.3.2 FX3UC-4AD
+15V +15V
-15V -15V
Power
Power Power crossover Power
crossover crossover
connector connector connector connector
Power connector
24- 24+ 24- 24+ 24- 24+ 24- 24+ 24- 24+ 24- 24+ 24- 24+
Power Power
connector connector
Black Red Green Black Red Black Red
Black Red Black Red Black Red
24V DC
Fuse FX2NC-100BPCB
Power cable*1
For wiring example of FX3GC Series PLC, refer to the following manual.
→ Refer to the FX3GC Series User’s Manual - Hardware Edition
"Section 4.2 Example External wiring".
*1. The FX3UC-MT/D and FX3UC-32MT-LT(-2) are supplied together with power cable.
*2. The FX2NC-EX-DS and FX2NC-16EX-T-DS do not have a power connector, and receive power
from the input connector.
• Ground the " " terminal and " " terminal to the Class - D grounding line (100 Ω or less) together
with the ground terminal of the main unit.
• To perform crossover wiring to connect the power line from FX3UC-4AD to a succeeding extension block,
remove the resin cover from the power crossover connector using nippers.
• For the timing of power-on/off when using an external power supply, see the following manual of the
connected PLC.
→ Refer to the FX3G Series User’s Manual - Hardware Edition.
→ Refer to the FX3GC Series User’s Manual - Hardware Edition.
→ Refer to the FX3U Series User’s Manual - Hardware Edition.
→ Refer to the FX3UC Series User’s Manual - Hardware Edition.
B-14
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 3.4 Analog Input Line
A
3.4 Analog Input Line
Common Items
The analog input type, "voltage input "or "current input", can be selected for each channel.
3.4.1 FX3U-4AD
B
FX3UC-4AD
FX3U-4AD
External power supply FX3U-4AD
wiring
24+ +15V
24V DC
*1 24- -15V
Class-D grounding
C
*2
FX3U-4AD-ADP
If current input is
selected
ch 6.8kΩ
*3 ch
V+
*4 250Ω
I+ D
VI-
FX3G-2AD-BD
200kΩ
FG
If voltage input is *2
selected
ch
*3 6.8kΩ ch
V+
*5
I+
250Ω E
FX3U-4DA
VI-
200kΩ
FG
*2
FX3U-4DA-ADP
*1. For FX3G/FX3U Series PLC (AC power type), the 24V DC service power supply is also available.
*2. The [FG] terminal and the [ ] terminal are connected internally.
There is no “FG” terminal for ch1. When using ch1, connect directly to the [ ] terminal.
*3. Use a 2-core twisted shield wire for analog input line, and separate it from other power lines or
inductive lines.
G
FX3G-1DA-BD
*4. For the current input, short-circuit the [V+] terminal and the [I+] terminal.
*5. If there is voltage ripple in the input voltage or there is noise in the external wiring, connect a capacitor
of approximately 0.1 to 0.47μF 25 V.
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
B-15
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 3.5 Grounding
3.4.2 FX3UC-4AD
*4 •
Class-D
grounding
*1. Use the 2-core shielded twisted pair cable for the analog input lines, and separate the analog input
lines from the other motive power lines or inductive lines.
*2. To use the current input, be sure to short circuit the line between the V + terminal and the I
+ terminal ( : channel number).
*3. The SLD and " " terminals are connected to each other inside.
*4. Do not connect any lines to the "•" terminal.
3.5 Grounding
Grounding should be performed as stated below.
• The grounding resistance should be 100 Ω or less.
• Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" as shown in the following
figure.
→ For details, refer to the User’s Manual - Hardware Edition of each Series.
• The PLC grounding point should be close, and all grounding wires should be as short as possible.
B-16
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Analog Input
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 4.1 Analog Input Procedures
Common Items
4. Analog Input
This chapter describes the minimum programming necessary to readout the 4AD analog data. B
Follow the procedure below to confirm that the analog data can be properly read out.
FX3UC-4AD
FX3U-4AD
4.1 Analog Input Procedures
FX3U-4AD-ADP
Unit numbers from 0 to 7 will be assigned to the special function units/blocks starting from the left.
When units/blocks are connected to the FX3UC-32MT-LT(-2) PLC, unit numbers from 1 to 7 are
assigned. Check the unit number assigned to the 4AD.
Unit
number: 0
Unit
number: 1
Unit
number: 2 D
FX3G-2AD-BD
Main unit Input/output Input/output
Special Special Special
(FX3U Series extension extension
function block function block function unit
PLC) block block
FX3U-4DA
2 Input mode (BFM#0) setting
Depending on the analog signal generator to be connected, set the input mode (BFM#0) for each
channel. F
FX3U-4DA-ADP
Use hexadecimal numbers for input mode setting. Set the corresponding channel digit to the input
mode setting value specified in the following table:
H
ch4
ch3
ch1
ch2
G
FX3G-1DA-BD
Setting Analog input
Input mode Digital output range
value range
0 Voltage input mode -10V to +10V -32000 to +32000
1 Voltage input mode -10V to +10V -4000 to +4000 H
Voltage input
FX3U-3A-ADP
5
Current input mode
Analog value direct indication mode
4mA to 20mA 4000 to 20000 I
FX3U-4AD-PT
→ For a detailed description of the standard input characteristics, refer to Section 2.4.
→ For a detailed description of the input mode (BFM#0), refer to Subsection 5.4.1.
-ADP
B-17
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Analog Input
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 4.1 Analog Input Procedures
B-18
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.1 Assignment of Unit Numbers and Outline of Buffer Memory
Common Items
5. Buffer Memory (BFM)
This chapter describes the buffer memory incorporated in 4AD. B
FX3UC-4AD
FX3U-4AD
5.1 Assignment of Unit Numbers and Outline of Buffer Memory
FX3U-4AD-ADP
When connected to the FX3G/FX3GC/FX3U/FX3UC (D, DS, DSS) Series PLC
Unit Unit Unit
number: 0 number: 1 number: 2
D
FX3G-2AD-BD
Input/output Special Special Input/output Special
Main unit extension function block function block extension function unit
block block
E
When connected to the FX3UC-32MT-LT(-2) PLC
FX3U-4DA
Unit number: 0
(Incorporated Unit Unit Unit
CC-Link/LT) number: 1 number: 2 number: 3
FX3U-4DA-ADP
(FX3UC-32MT extension extension
-LT(-2)) block function block function block block function unit
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
B-19
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.1 Assignment of Unit Numbers and Outline of Buffer Memory
*1. Since buffer memory direct specification (U\G) can directly specify the buffer memory in the source or
destination area of an applied instruction, programs can be created efficiently. (This function is supported
only in FX3U/FX3UC PLCs.)
→ For a detailed description of buffer memory reading/writing, refer to Section 5.2.
→ For a detailed description of the buffer memory, refer to Section 5.4.
B-20
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.2 Buffer Memory Reading/Writing Method
A
5.2 Buffer Memory Reading/Writing Method
Common Items
To read or write to the 4AD buffer memory, use the FROM/TO instructions or buffer memory direct
specifications*1.
However, to use buffer memory direct specification*1, software compatible with FX3U/FX3UC Series PLCs is
required. B
FX3UC-4AD
FX3U-4AD
*1. This function is supported only in FX3U/FX3UC PLCs.
→ For a detailed description of software compatible with the FX3U/FX3UC Series PLC,
refer to Section 1.4.
FX3U-4AD-ADP
the applied instruction as follows:
FX3G-2AD-BD
If the following program is created, data in buffer memory (BFM#10) of unit 1 will be multiplied by the data
(K10), and then the multiplication result will be output to data registers (D10, D11).
READ command
FNC 22 U1\G10 K10 D10
MUL
E
Multiplication result
FX3U-4DA
Unit number
Buffer memory number Multiplier
2. Example 2
If the following program is created, the value in data register (D20) is added to K10 and written to buffer
memory (BFM#6) of unit 1. F
WRITE command
FX3U-4DA-ADP
FNC 20 D20 K10 U1\G6
ADD
(
Addition Unit number
result Buffer memory number )
Augend Addend
G
5.2.2 FROM/TO instruction (FX3G/FX3GC/FX3U/FX3UC PLC)
FX3G-1DA-BD
1. FROM instruction (Reading out BFM data to PLC)
Use the FROM instruction to read the data from the buffer memory.
In a sequence program, use this instruction as follows:
READ command
FNC 78
H
K1 K10 D10 K1
FX3U-3A-ADP
FROM
Number of transfer
Unit number data points
Buffer memory number Destination register
If the above program is created, 1 point of data will be read out from the buffer memory BFM#10 of unit No.1
to data register D10. I
FX3U-4AD-PT
WRITE command
FNC 79
TO
K1 K0 H3300 K1
J
Number of transfer
FX3U-4AD-PTW
If the above program is created, 1 point of data (H3300) will be written to buffer memory BFM#0 of unit No.1.
B-21
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.3 Buffer Memory List (BFM)
BFM number Description Setting range Initial value Data type Reference
Hexadeci- Subsection
#0*1 Input mode setting for channels 1 to 4 *2 H0000 at delivery
mal 5.4.1
#1 Not used - - - -
#2 Averaging time units for channel 1 1 to 4095 K1 Decimal
#3 Averaging time units for channel 2 1 to 4095 K1 Decimal Subsection
#4 Averaging time units for channel 3 1 to 4095 K1 Decimal 5.4.2
*1. If power failure occurs, the EEPROM will retain its data.
*2. To specify the input mode of each channel, set each digit using hexadecimal numbers 0 to 8 and F.
*3. Use b0 to b3.
B-22
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.3 Buffer Memory List (BFM)
Common Items
BFM number Description Setting range Initial value Data type Reference
Convenient function setting:
Convenient functions: Automatic send
Hexadeci- Subsection
#22*1 function, data addition, upper/lower limit
detection, abrupt change detection, peak
*2 H0000 at delivery
mal 5.4.8 B
FX3UC-4AD
FX3U-4AD
value holding
#23 to #25 Not used - - - -
Upper/lower limit value error status (Valid if b1 Hexadeci- Subsection
#26 - H0000
of BFM#22 is set to ON) mal 5.4.9
#27
Abrupt change detection status (Valid if b2 of
BFM#22 is set to ON)
- H0000
Hexadeci-
mal
Subsection
5.4.10 C
FX3U-4AD-ADP
Hexadeci- Subsection
#28 Over-scale status - H0000
mal 5.4.11
Hexadeci- Subsection
#29 Error status - H0000
mal 5.4.12
Subsection
#30 Model code K2080 - K2080 Decimal
5.4.13 D
FX3G-2AD-BD
#31 to #40 Not used - - - -
#41*1 Channel-1 offset data (Unit: mV or μA) • Voltage input: K0 at delivery Decimal
BFM#21 -10000 to
#42*1 Channel-2 offset data (Unit: mV or μA) will be
+9000*3
K0 at delivery Decimal
Subsection
used for
#43 *1 Channel-3 offset data (Unit: mV or μA) • Current input: K0 at delivery Decimal 5.4.14
writing
#44*1 Channel-4 offset data (Unit: mV or μA)
data.
-20000 to
+17000*4 K0 at delivery Decimal
E
FX3U-4DA
#45 to #50 Not used - - - -
#51 *1 Channel-1 gain data (Unit: mV or μA) • Voltage input: K5000 at delivery Decimal
BFM#21 -9000 to
#52*1 Channel-2 gain data (Unit: mV or μA) will be
+10000*3
K5000 at delivery Decimal
Subsection
used for
#53*1 Channel-3 gain data (Unit: mV or μA) writing
data.
• Current input:
-17000 to
K5000 at delivery Decimal 5.4.14
F
#54*1 Channel-4 gain data (Unit: mV or μA) *4 K5000 at delivery Decimal
FX3U-4DA-ADP
+30000
#55 to #60 Not used - - - -
Channel-1 addition data (Valid if b0 of BFM#22
#61 -16000 to +16000 K0 Decimal
is set to ON)
Channel-2 addition data (Valid if b0 of BFM#22
#62
is set to ON)
-16000 to +16000 K0 Decimal
Subsection G
FX3G-1DA-BD
Channel-3 addition data (Valid if b0 of BFM#22 5.4.15
#63 -16000 to +16000 K0 Decimal
is set to ON)
Channel-4 addition data (Valid if b0 of BFM#22
#64 -16000 to +16000 K0 Decimal
is set to ON)
#65 to #70 Not used - - - -
#73
Channel-3 lower limit value error setting (Valid if upper limit value
Minimum digital
value in input Decimal
5.4.16
I
b1 of BFM#22 is set to ON) error setting value
FX3U-4AD-PT
range
Minimum digital
Channel-4 lower limit value error setting (Valid if
#74 value in input Decimal
b1 of BFM#22 is set to ON)
-ADP
range
#75 to #80 Not used - - - -
*1. If power failure occurs, the EEPROM will retain its data.
J
FX3U-4AD-PTW
B-23
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.3 Buffer Memory List (BFM)
BFM number Description Setting range Initial value Data type Reference
Channel-1 upper limit value error setting Maximum digital
#81 Decimal
(Valid if b1 of BFM#22 is set to ON) value in input range
Channel-2 upper limit value error setting From lower limit Maximum digital
#82 value error setting value in input range Decimal
(Valid if b1 of BFM#22 is set to ON) Subsection
value to maximum
Channel-3 upper limit value error setting Maximum digital 5.4.16
#83 digital value in Decimal
(Valid if b1 of BFM#22 is set to ON) input range value in input range
Channel-4 upper limit value error setting Maximum digital
#84 Decimal
(Valid if b1 of BFM#22 is set to ON) value in input range
#85 to #90 Not used - - - -
Channel-1 abrupt change detection value From 1 to 50% of
#91 5% of full scale Decimal
(Valid if b2 of BFM#22 is set to ON) full scale
Channel-2 abrupt change detection value From 1 to 50% of
#92 5% of full scale Decimal
(Valid if b2 of BFM#22 is set to ON) full scale Subsection
Channel-3 abrupt change detection value From 1 to 50% of 5.4.17
#93 5% of full scale Decimal
(Valid if b2 of BFM#22 is set to ON) full scale
Channel-4 abrupt change detection value From 1 to 50% of
#94 5% of full scale Decimal
(Valid if b2 of BFM#22 is set to ON) full scale
#95 to #98 Not used - - - -
Clear of upper/lower limit error data or abrupt Subsection
#99 *1 H0000 -
change error data 5.4.18
#100 Not used - - - -
Channel-1 minimum peak value (Valid if b3 of
#101 - - Decimal
BFM#22 is set to ON)
Channel-2 minimum peak value (Valid if b3 of
#102 - - Decimal
BFM#22 is set to ON) Subsection
Channel-3 minimum peak value (Valid if b3 of 5.4.19
#103 - - Decimal
BFM#22 is set to ON)
Channel-4 minimum peak value (Valid if b3 of
#104 - - Decimal
BFM#22 is set to ON)
#105 to #108 Not used - - - -
Hexadeci- Subsection
#109 Minimum peak value resetting *3 H0000
mal 5.4.20
#110 Not used - - - -
Channel-1 maximum peak value (Valid if b3
#111 - - Decimal
of BFM#22 is set to ON)
Channel-2 maximum peak value (Valid if b3
#112 - - Decimal
of BFM#22 is set to ON) Subsection
Channel-3 maximum peak value (Valid if b3 5.4.19
#113 - - Decimal
of BFM#22 is set to ON)
Channel-4 maximum peak value (Valid if b3
#114 - - Decimal
of BFM#22 is set to ON)
#115 to #118 Not used - - - -
Hexadeci- Subsection
#119 Maximum peak value resetting *3 H0000
mal 5.4.20
#120 to #124 Not used - - - -
Peak values (Minimum: BFM#101 to #104 /
Maximum: #111 to #114) automatic transfer-
Subsection
#125*2 to first data register specification (Valid if b4 of 0 to 7992 K200 at delivery Decimal
5.4.21
BFM#22 is set to ON / Occupies of 8
consecutive points)
*1. Use b0 to b2.
*2. If power failure occurs, the EEPROM will retain its data.
*3. Use b0 to b3.
B-24
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.3 Buffer Memory List (BFM)
A
BFM number Description Setting range Initial value Data type Reference
Common Items
Upper/lower limit error status data (BFM#26)
Subsection
#126*1 automatic transfer-to data register specification 0 to 7999 K208 at delivery Decimal
5.4.22
(Valid if b5 of BFM#22 is set to ON)
Abrupt change detection status data (BFM#27)
Subsection
#127*1 automatic transfer-to data register specification
(Valid if b6 of BFM#22 is set to ON)
0 to 7999 K209 at delivery Decimal
5.4.23 B
FX3UC-4AD
FX3U-4AD
Over-scale status data (BFM#28) automatic
Subsection
#128*1 transfer-to data register specification (Valid if b7 0 to 7999 K210 at delivery Decimal
5.4.24
of BFM#22 is set to ON)
Error status data (BFM#29) automatic transfer-
Subsection
#129*1 to data register specification (Valid if b8 of 0 to 7999 K211 at delivery Decimal
BFM#22 is set to ON)
5.4.25
C
FX3U-4AD-ADP
#130 to #196 Not used - - - -
Selection of cyclic data update function (function Hexadeci- Subsection
#197 *2 H0000
for data history) mal 5.4.26
Subsection
#198*1 Data history sampling time setting (Unit: ms) 0 to 30000 K15000 Decimal
5.4.27
FX3G-2AD-BD
#200 Channel-1 data history (initial value) - K0 Decimal
Decimal
~
~
#1899 Channel-1 data history (1,700th value) - K0 Decimal
#1900 Channel-2 data history (initial value) - K0 Decimal
Decimal
E
~
FX3U-4DA
#3599 Channel-2 data history (1,700th value) - K0 Decimal Subsection
#3600 Channel-3 data history (initial value) - K0 Decimal 5.4.29
Decimal
~
FX3U-4DA-ADP
Decimal
~
*1. If power failure occurs, the EEPROM will retain its data.
*2. Use b0 to b3. G
*3. Use b0 to b3 and b8 to b11.
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
B-25
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
H
ch4 ch1
ch3 ch2
The different types of input modes are shown in the following table:
→ For a detailed description of input characteristics, refer to Section 2.4.
B-26
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
A
5.4.2 BFM#2 to #5: Averaging time
Common Items
Setting range: 1 to 4095
Initial value: K1
Numeric data type: Decimal (K)
To change the channel data type from the immediate data (channels 1 to 4: BFM#10 to #13) to the average B
FX3UC-4AD
FX3U-4AD
data, set the desired averaging time (channels 1 to 4 : BFM#2 to 5).
The relation between the set averaging time and the corresponding operation is shown in the following table.
→ For a detailed description of channel data update timing, refer to Subsection 5.4.4.
Averaging
time (BFM#2
to #5)
Channel data (BFM#10 to #13) type Error descriptions C
FX3U-4AD-ADP
Immediate data K0 will be set, and the averaging time
0 or less (Each time the A/D conversion is performed, the channel setting error (b10 of BFM#29) will
data will be updated.) occur.
Immediate data
1 (initial
value)
(Each time the A/D conversion is performed, the channel
data will be updated.)
-
D
FX3G-2AD-BD
Average data
(Each time the A/D conversion is performed, the average
2 to 400 -
value will be calculated and the channel data will be
updated.)
Average data
(Each time the A/D conversion data reaches the averaging E
401 to 4095 -
FX3U-4DA
time, the average data will be calculated and the channel
data will be updated.)
Average data
4096 will be set, and the averaging
(Each time the A/D conversion data reaches the averaging
4096 or more time setting error (b10 of BFM#29) will
time, the average data will be calculated and the channel
occur.
data will be updated.) F
FX3U-4DA-ADP
1. Application
If the measurement signal contains comparatively reduced ripple noise, such as supply voltage frequency,
averaging will result in obtaining of stable data.
FX3G-1DA-BD
• To use the averaging function, be sure to set the digital filter of the corresponding channel to "0". (Digital
filter setting: BFM#6 to #9 for channels 1 to 4)
To use the digital filter function, be sure to set the averaging time of the corresponding channel to "1".
(Averaging time: BFM#2 to #5 for channels 1 to 4)
If the averaging time is set to a value other than "1" and the digital filter (BFM#6 to #9 for channels 1 to 4)
is set to a value other than "0", the digital filter setting error (b11 of BFM#29) will occur. H
FX3U-3A-ADP
• If one of the channels uses the digital filter, the A/D conversion time will be set to 5 ms for all the channels.
• If the averaging time is out of the setting range, the averaging time setting error (b10 of BFM#29) will occur.
• If the averaging time is set, the data history function cannot be used.
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
B-27
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
To use the digital filter for channel data (BFM#10 to #13 for channels 1 to 4), set the digital filter value in the
corresponding buffer memory (BFM#6 to #9 for channels 1 to 4).
→ For a detailed description of channel data update timing, refer to Subsection 5.4.4.
If the digital filter function is used, the relation between the analog input value and the set digital filter value or
the digital output value (channel data) will be as follows:
• Digital filter value (BFM#6 to #9 for channels 1 to 4) > Fluctuation of analog signal (fluctuation
width: less than 10 times of sampling)
If the fluctuation of the analog signal (input value) is less than the set digital filter value, the analog input
value will be converted into a stabilized digital output value and stored in the corresponding buffer memory
(BFM#10 to #13 for channels 1 to 4).
• Digital filter value (BFM#6 to #9 for channels 1 to 4) < Fluctuation of analog signal
If the fluctuation of the analog signal (input value) is more than the set digital filter value, the digital output
value will follow the analog input value, and the digital output value equal to the analog input value will be
stored in the corresponding buffer memory (BFM#10 to #13 for channels 1 to 4).
The relation between the set value and the corresponding operation is shown in the following table:
1. Application
If the measurement signal contains steep spike noise, use the digital filter instead of the averaging function.
The digital filter produces more stabilized data results.
B-28
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
A
5.4.4 BFM#10 to #13: Channel data
Common Items
Numeric data type: Decimal (K)
Use these buffer memories to store the A/D converted digital values.
The channel data (BFM#10 to #13 for channels 1 to 4) and the data update timing will depend on the set
averaging time (BFM#2 to #5 for channels 1 to 4) or the digital filter setting condition (BFM#6 to #9 for B
FX3UC-4AD
FX3U-4AD
channels 1 to 4) as shown in the following table.
→ For a detailed description of the averaging time, refer to Subsection 5.4.2.
→ For a detailed description of digital filter functions, refer to Subsection 5.4.3.
FX3U-4AD-ADP
Immediate data Each time the A/D conversion is performed, the
0 (The digital filter "0" will be set, and the data will be updated.
0 or less
will not be used.) averaging time setting error The update timing will be as follows:
(b10 of BFM#29) will occur.
0 (The digital filter
Immediate data
Update time = 500μs*1 × Number of
selected channels
D
will not be used.)
FX3G-2AD-BD
Each time the A/D conversion is performed, the
1 1 to 1600 Immediate data data will be updated.
(The digital filter The digital filter function will The update timing will be as follows:
will be used.) be used. Update time = 5ms × Number of selected
channels E
FX3U-4DA
Each time the A/D conversion is performed, the
data will be updated.
2 to 400 Average data The update timing will be as follows:
FX3U-4DA-ADP
the set averaging time, the data will be updated.
Average data
The update timing will be as follows:
"4096" will be set, and the
4096 or more
averaging time setting error Update time = 500μs*1 × Number of
(b10 of BFM#29) will occur. selected channels × Averaging time
FX3G-1DA-BD
all the channels.
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
B-29
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
Setting range: K0 or K1
Initial value: K0
Numeric data type: Decimal (K)
Use this function to initialize all data in BFM#0 to #6999, to the factory default status.
Set value Description
K0 Normal
K1 Initializes all data
Set "K1" to initialize all data. When initialization is complete, "K0" will be set automatically.
Channel numbers are assigned to the 4 lower bits of BFM#21. If any of these bits are turned on, the offset
data (BFM#41 to #44) and gain data (BFM#51 to #54) of the corresponding channel will be written to the
internal memory (EEPROM). When written to the internal memory, the data will become valid.
B-30
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
A
5.4.8 BFM#22: Convenient function setting
Common Items
Initial value: H0000
Numeric data type: Hexadecimal (H)
Turn on each bit (b0 to b8) of BFM#22 to enable the function assigned to each bit (refer to the following table).
Turn off each bit to disable the function of each bit.
B
FX3UC-4AD
FX3U-4AD
1. Function assigned to each bit of BFM#22
Bit No. Function Description Reference
The channel data (BFM#10 to #13), peak data (BFM#101 to
#104, #111 to #114), and data history (BFM#200 to #6999) will
be subject to change (the addition data (BFM#61 to #64) will be C
Subsection
b0 Data addition function added to the measurement data).
FX3U-4AD-ADP
5.4.15
When setting the lower limit error data (BFM#71 to #74) or the
upper limit error data (BFM#81 to #84), add the addition data
(BFM#61 to #64) to the error data to be set.
If the A/D conversion data of a channel is outside the range set
b1
Upper/lower limit
detection function
by the lower limit error data (BFM#71 to #74) and the upper limit
error data (BFM#81 to #84), the result will be written to BFM#26
Subsection
5.4.16
D
FX3G-2AD-BD
as the upper/lower limit error status data.
When channel data (BFM#10 to #13) is updated, if the
difference between the previous value and the new value is
Abrupt change Subsection
b2 larger than the set abrupt change detection value (value set in
detection function 5.4.17
BFM#91 to #94), the result will be written to BFM#27 as the
abrupt change detection status data. E
FX3U-4DA
The minimum value of channel data written to BFM#10 to #13
will be written to BFM#101 to #104 as the minimum peak value,
Peak value holding Subsection
b3 and the maximum value of channel data written to BFM#10 to
function 5.4.19
#13 will be written to BFM#111 to #114 as the maximum peak
value.
If the automatic transfer-to first data register is specified in
Subsection
F
BFM#125, the minimum peak value (BFM#101 to #104) and the
FX3U-4DA-ADP
Peak value automatic 5.4.19
b4 maximum peak value (BFM#111 to #114) will be automatically
transfer function Subsection
written to the specified data registers (8 points (registers)
5.4.21
starting from the first data register specified).
If the upper/lower limit error status data automatic transfer-to Subsection
Upper/lower limit error
b5 status data automatic
data register is specified in BFM#126, the upper/lower limit error
status data (BFM#26) will be automatically written to the
5.4.16
Subsection
G
transfer function
FX3G-1DA-BD
specified data register. 5.4.22
Abrupt change If the abrupt change detection status data automatic transfer-to Subsection
detection status data data register is specified in BFM#127, the abrupt change 5.4.17
b6
automatic transfer detection status data (BFM#27) will be automatically written to the Subsection
function specified data register. 5.4.23
Over-scale status If the over-scale status data automatic transfer-to data register is
Subsection
H
b7 data automatic specified in BFM#128, the over-scale status data (BFM#28) will
FX3U-3A-ADP
5.4.24
transfer function be automatically written to the specified data register.
Error status data If the error status data automatic transfer to data register is
Subsection
b8 automatic transfer specified in BFM#129, the error status data (BFM#29) will be
5.4.25
function automatically written to the specified data register.
b9 to b15 - Not used. - I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
B-31
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
B-32
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
A
5.4.9 BFM#26: Upper/lower limit error status
Common Items
Initial value: H0000
Numeric data type: Hexadecimal (H)
If channel data (BFM#10 to #13) is out of the range set by the lower limit error data (BFM#71 to #74) and the
upper limit error data (BFM#81 to #84), the following operation will be performed: B
FX3UC-4AD
FX3U-4AD
• If "channel data < lower limit error set value":
The lower limit error bit will turn on.
• If "channel data > upper limit error set value":
The upper limit error bit will turn on.
→ For a detailed description of upper/lower limit error status data resetting,
refer to Subsection 5.4.18. C
FX3U-4AD-ADP
1. BFM#26 bit assignment
The upper and lower limit error values of each channel are assigned as shown in the following table:
FX3G-2AD-BD
b2 Lower limit error value
ch2
b3 Upper limit error value
b4 Lower limit error value
ch3
b5 Upper limit error value E
b6 Lower limit error value
FX3U-4DA
ch4
b7 Upper limit error value
b8 to b15 Not used.
FX3U-4DA-ADP
of BFM#22).
• Perform one of the following operations to turn off the previously turned on bit:
- Turn the power off and on.
- Turn on b0 or b1 of BFM#99 to reset the upper/lower limit error status.
- Write "H0000" in BFM#26 as the upper/lower limit error status data. G
FX3G-1DA-BD
• Even if an error is detected, channel data (BFM#10 to #13) will be continuously updated.
• The upper/lower limit error status data automatic transfer function is not supported when connected and
used with the FX5U or FX5UC CPU module.
3. Upper/lower limit error status data automatic transfer function (b5 of BFM#22)
If the upper/lower limit error status data automatic transfer-to data register is specified in BFM#126, the data H
in BFM#26 can be transferred to the specified data register.
FX3U-3A-ADP
When the upper/lower error is detected, data will be automatically transferred from the 4AD to the PLC. For
this reason, the PLC does not need the program for reading data, and the scanning time of the PLC can be
shortened.
: Represents a numeric value.
Convenient function
Automatic data transfer function
I
setting
FX3U-4AD-PT
BFM#22 b1:ON
BFM#26 → D
BFM#22 b5:ON
J
FX3U-4AD-PTW
-ADP
B-33
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
B-34
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
A
5.4.11 BFM#28: Over-scale status
Common Items
Initial value: H0000
Numeric data type: Hexadecimal (H)
If the input analog value is out of the A/D conversion range, the following operation will be performed:
• If "(analog input value) < (lower limit value in A/D conversion range)": B
FX3UC-4AD
FX3U-4AD
The over-scale lower limit bit will turn on.
• If "(analog input value) < (upper limit value in A/D conversion range)":
The over-scale upper limit bit will turn on.
FX3U-4AD-ADP
Voltage input -10.2V to +10.2V
Current input -20.4mA to +20.4mA
FX3G-2AD-BD
Bit No. Channel number Description
b0 Over-scale (lower limit)
ch1
b1 Over-scale (upper limit)
b2 Over-scale (lower limit)
ch2
b3 Over-scale (upper limit) E
b4 Over-scale (lower limit)
FX3U-4DA
ch3
b5 Over-scale (upper limit)
b6 Over-scale (lower limit)
ch4
b7 Over-scale (upper limit)
b8 to b15 Not used. F
FX3U-4DA-ADP
3. Caution regarding use of over-scale status data
• Perform one of the following operations to turn off the previously turned on bit:
- Turn the power off and on.
- Write "H0000" in BFM#28 as the over-scale status data.
• Even if over scale is detected, channel data (BFM#10 to #13) will continuously be updated.
G
FX3G-1DA-BD
• The over-scale status data automatic transfer function is not supported when connected and used with the
FX5U or FX5UC CPU module.
When over-scale is detected, data will be automatically transferred from the 4AD to the PLC. For this reason,
the PLC does not need any program for reading the data, and the scan time of the PLC can be shortened.
: Represents a numeric value.
Convenient function
Automatic data transfer function
setting
Transfer-to data register specification
I
ON = Valid Transfer-from memory
FX3U-4AD-PT
(BFM#128: K)
BFM#22 b7:ON BFM#28 → D
-ADP
J
FX3U-4AD-PTW
-ADP
B-35
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
B-36
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
A
5.4.13 BFM#30: Model code
Common Items
Initial value: K2080
Numeric data type: Decimal (K)
FX3UC-4AD
FX3U-4AD
5.4.14 BFM#41 to #44: Offset data / BFM#51 to #54: Gain data
FX3U-4AD-ADP
stored. The initial offset data and gain data are set for each mode as shown in the following table:
• Offset data: Analog input value when the digital value is "0" (reference offset value)
• Gain data: Analog input value when the digital value is equal to the reference gain value (The
reference gain value depends on the set input mode.)
D
1. Reference offset/gain value and initial value set at delivery
FX3G-2AD-BD
Offset Gain
Input mode (BFM#0) (Channels 1 to 4: BFM#41 to (Channels 1 to 4: BFM#51 to
#44) #54)
Set Reference Reference
value
Description
value
Initial value
value
Initial value E
FX3U-4DA
Voltage input
0 0 0mV 16000 5000mV
(-10V to +10V: -32000 to +32000)
Voltage input
1 0 0mV 2000 5000mV
(-10V to +10V: -4000 to +4000)
2
Voltage input
Analog value direct indication mode
0
(Data change
0mV
(Data change
5000
(Data change
5000mV
(Data change F
FX3U-4DA-ADP
(-10V to +10V: -10000 to +10000) impossible) impossible) impossible) impossible)
3 Current input (4mA to 20mA: 0 to 16000) 0 4000μA 16000 20000μA
4 Current input (4mA to 20mA: 0 to 4000) 0 4000μA 4000 20000μA
Current input 4000 4000μA 20000 20000μA
5 Analog value direct indication mode
(4mA to 20mA: 4000 to 20000)
(Data change
impossible)
(Data change
impossible)
(Data change
impossible)
(Data change
impossible)
G
FX3G-1DA-BD
Current input
6 0 0μA 16000 20000μA
(-20mA to +20mA: -16000 to +16000)
Current input
7 0 0μA 4000 20000μA
(-20mA to +20mA: -4000 to +4000)
8
Current input
Analog value direct indication mode
0
(Data change
0μA
(Data change
20000
(Data change
20000μA
(Data change
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
B-37
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
*1. The offset and gain values should meet the following condition:
7500 ≥ Gain value - Offset value ≥ 1000
*2. The offset and gain values should meet the following condition:
30000 ≥ Gain value - Offset value ≥ 3000
If the addition data (BFM#61 to #64) is set, the set data will be added before storing the channel data
(BFM#10 to #13), peak data (BFM#101 to #104, BFM#111 to #114), or data history (BFM#200 to #6999).
B-38
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
A
5.4.16 BFM#71 to #74: Lower limit error setting / BFM#81 to #84: Upper limit error setting
Common Items
Setting range: See below.
Initial value: See below.
Numeric data type: Decimal (K)
Set the upper/lower limit error data so that the upper/lower limit error status (BFM#26) can be detected.
B
FX3UC-4AD
FX3U-4AD
The data setting range depends on the input mode set in BFM#0.
The following table shows the data setting range for each input mode:
FX3U-4AD-ADP
Voltage input
0 -32768 to +32767 -32768 32767
(-10 V to +10 V: -32000 to +32000)
Voltage input
1 -4095 to +4095 -4095 4095
(-10 V to +10 V: -4000 to +4000)
Voltage input D
2 Analog value direct indication mode -10200 to +10200 -10200 10200
FX3G-2AD-BD
(-10 V to +10 V: -10000 to +10000)
Current input
3 -1 to +16383 -1 16383
(4 mA to 20 mA: 0 to 16000)
4 Current input (4 mA to 20 mA: 0 to 4000) -1 to +4095 -1 4095
Current input E
5 Analog value direct indication mode 3999 to 20400 3999 20400
FX3U-4DA
(4 mA to 20 mA: 4000 to 20000)
Current input
6 -16384 to +16383 -16384 16383
(-20 mA to +20 mA: -16000 to +16000)
Current input
7
(-20 mA to +20 mA: -4000 to +4000)
-4096 to +4095 -4096 4095
F
FX3U-4DA-ADP
Current input
8 Analog value direct indication mode -20400 to +20400 -20400 20400
(-20 mA to +20 mA: -20000 to +20000)
FX3G-1DA-BD
• To use the data addition function (b0 of BFM#22) together with this function, be sure to add the addition
data (channels 1 to 4: BFM#61 to #64) to the upper/lower limit values to be set. In addition, observe the
data setting range.
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
B-39
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
When channel data (BFM#10 to #13) is updated, if the difference between the previous value and the new
value is larger than the set abrupt change detection value (value set in BFM#91 to #94), the system will judge
that the channel data is changed abruptly.
The result of abrupt change detection will be written to BFM#27 as the abrupt change detection status data.
The abrupt change detection value setting range depends on the set input mode (BFM#0) as shown in the
following table:
Input mode (BFM#0)
Set Setting range Initial value
Description
value
Voltage input
0 1 to 32767 3200
(-10 V to +10 V: -32000 to +32000)
Voltage input
1 1 to 4095 400
(-10 V to +10 V: -4000 to +4000)
Voltage input
2 Analog value direct indication mode 1 to 10000 1000
(-10 V to +10 V: -10000 to +10000)
3 Current input (4 mA to 20 mA: 0 to 16000) 1 to 8191 800
4 Current input (4 mA to 20 mA: 0 to 4000) 1 to 2047 200
Current input
5 Analog value direct indication mode 1 to 8191 800
(4 mA to 20 mA: 4000 to 20000)
Current input
6 1 to 16383 1600
(-20 mA to +20 mA: -16000 to +16000)
Current input
7 1 to 4095 400
(-20 mA to +20 mA: -4000 to +4000)
Current input
8 Analog value direct indication mode 1 to 20000 2000
(-20 mA to +20 mA: -20000 to +20000)
B-40
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
A
5.4.18 BFM#99: Clearance of upper/lower limit error data and abrupt change detection data
Common Items
Initial value: H0000
Numeric data type: Hexadecimal (H)
Three error data clearance commands (lower limit error data clearance command, upper limit error data
clearance command, and abrupt change detection data clearance command) are respectively assigned to the B
3 lower bits of BFM#99.
FX3UC-4AD
FX3U-4AD
Turning on each bit (batch turning on for all channels) will reset the corresponding error status flag (#26 or
#27 of BFM).
FX3U-4AD-ADP
BFM#26
b1 Upper limit error data clearance command
b2 Abrupt change detection data clearance command BFM#27
b3 to b15 Not used. -
Two or more data clearance commands can be turned on at the same time. D
FX3G-2AD-BD
2. Operation after resetting BFM#26, #27
Each bit will turn off automatically.
5.4.19 BFM#101 to #104: Minimum peak value / BFM#111 to #114: Maximum peak value E
FX3U-4DA
Numeric data type: Decimal (K)
The minimum channel data (channels 1 to 4) value written to BFM#10 to #13 will be written to BFM#101 to
#104 as the minimum peak value, and the maximum channel data value will be written to BFM#111 to #114
as the maximum peak value.
F
1. Caution regarding peak value
FX3U-4DA-ADP
To use the minimum peak value and the maximum peak value, be sure to turn on the peak value holding
function (b3 of BFM#22).
Note:
• If the data addition function (b0 of BFM#22) is used together with this function, the addition data will be
added to the measurement data.
G
FX3G-1DA-BD
• If the value holding function is not used, the peak value will be "K0".
• The peak value automatic transfer function is not supported when connected and used with the FX5U or
FX5UC CPU module.
maximum peak value will be automatically written to the specified data registers (8 points (registers) starting
from the first data register specified).
When the peak value is updated, data will be automatically transferred from the 4AD to the PLC. For this
reason, the PLC does not need any program for reading the data, and the scan time of the PLC can be
shortened.
: Represents a numeric value. I
Convenient function
FX3U-4AD-PT
(BFM#125: K)
ON = Valid Transfer-from buffer memory
(8 points (registers) starting from the
specified data register) J
BFM#22 b4: ON BFM#101 to 104 D to D+3
FX3U-4AD-PTW
→
BFM#22 b3: ON BFM#111 to 114 D+4 to D+7
-ADP
B-41
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
5.4.20 BFM#109: Minimum peak value resetting / BFM#119: Maximum peak value resetting
Description
Bit No.
BFM#109 BFM#119
b0 Channel-1 minimum peak value (BFM#101) resetting Channel-1 maximum peak value (BFM#111) resetting
b1 Channel-2 minimum peak value (BFM#102) resetting Channel-2 maximum peak value (BFM#112) resetting
b2 Channel-3 minimum peak value (BFM#103) resetting Channel-3 maximum peak value (BFM#113) resetting
b3 Channel-4 minimum peak value (BFM#104) resetting Channel-4 maximum peak value (BFM#114) resetting
b4 to b15 Not used.
Two or more bits can be turned on at a time.
5.4.21 BFM#125: Peak value automatic transfer to first data register specification
If the automatic transfer to first data register is specified in BFM#125, the minimum peak value (BFM#101 to
#104) and the maximum peak value (BFM#111 to #114) will be automatically transferred to the specified data
registers (8 points (registers) starting from the first data register specified).
When the peak value is updated, data will be automatically transferred from the 4AD to the PLC. For this
reason, the PLC does not need any program for reading the data, and the scan time of the PLC can be
shortened.
→ For a detailed description of the minimum peak value (BFM#101 to #104) and the maximum peak
value (BFM#111 to #114), refer to Subsection 5.4.19.
2. Caution regarding peak value automatic transfer-to first data register specification
• If data registers are already specified for the other automatic transfer functions, do not specify the same
data registers.
• Be sure to turn on the peak value automatic transfer function (b4 of BFM#22) and the peak value holding
function (b3 of BFM#22).
• The data written to BFM#125 will be retained in the EEPROM.
B-42
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
A
3. Caution regarding EEPROM writing
Common Items
If data is written to BFM#0, #19, #21, #22, #125 to #129, or #198, the data will also be written to the 4AD
EEPROM.
→ For a detailed description of caution regarding EEPROM writing, refer to Subsection 5.4.1.
5.4.22 BFM#126: Upper/lower error status data automatic transfer-to data register B
specification
FX3UC-4AD
FX3U-4AD
Setting range: 0 to 7999
Initial value (at delivery) : K208
Numeric data type: Decimal (K)
Use this function to automatically transfer the upper/lower limit error status data (BFM#26) to the data register
C
FX3U-4AD-ADP
specified in BFM#126.
When the upper/lower limit error is detected, data will be automatically transferred from the 4AD to the PLC.
For this reason, the PLC does not need any program for reading the data, and the scanning time of the PLC
can be shortened.
→ For a detailed description of the upper/lower limit error status data (BFM#26),
refer to Subsection 5.4.9. D
FX3G-2AD-BD
1. If "BFM#126 = K208 (initial value)"
Specified data register Description
D208 Upper/lower limit error status data in BFM#26
2. Cautions regarding upper/lower limit error status data automatic transfer-to data register E
specification
FX3U-4DA
• If a data register is already specified for the other automatic transfer functions, do not specify the same
data register.
• Be sure to turn on the upper/lower limit error status data automatic transfer function (b5 of BFM#22) and
the upper/lower limit detection function (b1 of BFM#22).
F
• The data written to BFM#126 will be retained in the EEPROM.
FX3U-4DA-ADP
3. Caution regarding EEPROM writing
If data is written to BFM#0, #19, #21, #22, #125 to #129, or #198, the data will also be written to the 4AD
EEPROM.
→ For a detailed description of caution regarding EEPROM writing, refer to Subsection 5.4.1.
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
B-43
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
5.4.23 BFM#127: Abrupt change detection status data automatic transfer-to data register
specification
Use this function to automatically transfer the abrupt change detection status data (BFM#27) to the data
register specified in BFM#127.
When abrupt change is detected, data will be automatically transferred from the 4AD to the PLC. For this
reason, the PLC does not need any program for reading the data, and the scan time of the PLC can be
shortened.
→ For a detailed description of the abrupt change detection status data (BFM#27),
refer to Subsection 5.4.10.
2. Caution regarding abrupt change detection status data automatic transfer to data register
specification
• If a data register is already specified for the other automatic transfer functions, do not specify the same
data register.
• Be sure to turn on the abrupt change detection status data automatic transfer function (b6 of BFM#22) and
the abrupt change detection function (b2 of BFM#22).
• The data written to BFM#127 will be retained in the EEPROM.
B-44
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
A
5.4.24 BFM#128: Over-scale status data automatic transfer-to data register specification
Common Items
Setting range: 0 to 7999
Initial value (at delivery) : K210
Numeric data type: Decimal (K)
Use this function to automatically transfer the over-scale status data (BFM#28) to the data register specified
B
FX3UC-4AD
FX3U-4AD
in BFM#128.
When over-scale is detected, data will be automatically transferred from the 4AD to the PLC. For this reason,
the PLC does not need any program for reading the data, and the scan time of the PLC can be shortened.
→ For a detailed description of the over-scale status data (BFM#28), refer to Subsection 5.4.11.
FX3U-4AD-ADP
Specified data register Description
D210 Over-scale status data in BFM#28
2. Cautions regarding over-scale status data automatic transfer-to data register specification
• If a data register is already specified for the other automatic transfer functions, do not specify the same
data register.
D
FX3G-2AD-BD
• Be sure to turn on the over-scale status data automatic transfer function (b7 of BFM#22).
• The data written to BFM#128 will be retained in the EEPROM.
FX3U-4DA
→ For a detailed description of caution regarding EEPROM writing, refer to Subsection 5.4.1.
5.4.25 BFM#129: Error status data automatic transfer-to data register specification
FX3U-4DA-ADP
Numeric data type: Decimal (K)
Use this function to automatically transfer the error status data (BFM#29) to the data register specified in
BFM#129.
When an error is detected, data will be automatically transferred from the 4AD to the PLC. For this reason,
the PLC does not need any program for reading the data, and the scan time of the PLC can be shortened. G
→ For a detailed description of the error status data (BFM#29), refer to Subsection 5.4.12.
FX3G-1DA-BD
1. If "BFM#129 = K211 (initial value)"
Specified data register Description
D211 Error status data in BFM#29
H
2. Cautions regarding error status data automatic transfer-to data register specification
FX3U-3A-ADP
• If a data register is already specified for the other automatic transfer functions, do not specify the same
data register.
• Be sure to turn on the error status data automatic transfer function (b8 of BFM#22).
• The data written to BFM#129 will be retained in the EEPROM.
I
3. Caution regarding EEPROM writing
FX3U-4AD-PT
If data is written to BFM#0, #19, #21, #22, #125 to #129, or #198, the data will also be written to the 4AD
EEPROM.
-ADP
→ For a detailed description of caution regarding EEPROM writing, refer to Subsection 5.4.1.
J
FX3U-4AD-PTW
-ADP
B-45
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
5.4.26 BFM#197: Selection of cyclic data update function (function for data history)
1. Sampling cycle
As shown in the following table, the sampling cycle depends on whether the digital filter function is used.
Value set in
Whether digital filter function is used Sampling cycle
BFM#198
0.5 ms × number of selected channels (number of
0
channels using the digital filter function)
None of the channels use the digital filter
function. Set value (ms) in BFM#198 × number of selected
1 or more channels (number of channels using the digital filter
function)
5 ms × number of selected channels (number of
9 or less
channels using the digital filter function)
One or more channels use the digital filter
function. Set value (ms)*1 in BFM#198 × number of selected
10 or more channels (number of channels using the digital filter
function)
B-46
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
A
5.4.28 BFM#199: Data history resetting/stoppage
Common Items
Initial value: H0000
Numeric data type: Hexadecimal (H)
The data history resetting function and the data history stoppage function are assigned to the bits of BFM#199.
B
1. Data history resetting function (b0 to b3)
FX3UC-4AD
FX3U-4AD
The sampled history data can be reset for each channel.
Turn on a bit to reset all the history data (1st to 1,700th) of the corresponding channel. (Note that two or more
bits can be turned on at a time.)
When the data reset is complete, the corresponding bit will turn off automatically.
FX3U-4AD-ADP
Data sampling can be temporarily stopped for each channel.
Turn on a bit to temporarily stop sampling history data for the corresponding channel. (Note that two or more
bits can be turned on at a time.)
Turn off the bit to restart sampling of history data.
FX3G-2AD-BD
b0 ch1
b1 ch2
Data history resetting function
b2 ch3
b3 ch4
E
b4 to b7 Not used.
FX3U-4DA
b8 ch1
b9 ch2
Data history stoppage function
b10 ch3
b11 ch4
b12 to b15 Not used. F
FX3U-4DA-ADP
4. Caution regarding data history resetting
• When a bit is turned on, the corresponding data history will be reset.
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
B-47
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
…
1,700th #1899 #3599 #5299 #6999
B-48
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Changing Input Characteristics
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 6.1 Procedure for Changing Input Characteristics
Common Items
6. Changing Input Characteristics
For the 4AD, the standard input characteristics are provided for each input mode (BFM#0) at the time of B
factory shipment.
FX3UC-4AD
FX3U-4AD
Changing the offset data (BFM#41 to #44) or gain data (BFM#51 to #54), however, can change the input
characteristics of each channel. This chapter describes how to change the input characteristics.
FX3U-4AD-ADP
1 Determine the input mode (BFM#0)
Determine the optimum input mode (BFM#0) for the selected channels and the voltage/current
specifications.
D
Set value
FX3G-2AD-BD
Input mode Analog input range Digital output range
(HEX)
0 Voltage input mode -10V to +10V -32000 to +32000
1 Voltage input mode -10V to +10V -4000 to +4000
2
Voltage input analog value direct indication
mode
The offset and the gain cannot be adjusted. E
FX3U-4DA
3 Current input mode 4mA to 20mA 0 to 16000
4 Current input mode 4mA to 20mA 0 to 4000
Current input analog value direct indication
5 The offset and the gain cannot be adjusted.
mode
6 Current input mode -20mA to +20mA -16000 to +16000 F
FX3U-4DA-ADP
7 Current input mode -20mA to +20mA -4000 to +4000
Current input analog value direct indication
8 The offset and the gain cannot be adjusted.
mode
9 to E Not used. - -
F Channel not used - - G
Example: Enter "HFF00" in BFM#0 to set input mode 0 for channels 1 and 2 and prevent use channels 3 and
FX3G-1DA-BD
4.
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
B-49
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Changing Input Characteristics
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 6.1 Procedure for Changing Input Characteristics
Input mode 0 Input characteristics provided at the time Input characteristics newly provided
of factory shipment
Digital value Digital value
+32640 +32000
+32000
-32000
-32640
Numeric
Input mode Analog input range Gain standard value Initial value
value
0 Voltage input mode -10V to +10V 16000 5000mV
1 Voltage input mode -10V to +10V 2000 5000mV
3 Current input mode 4mA to 20mA 16000 20000μA
4 Current input mode 4mA to 20mA 4000 20000μA
6 Current input mode -20mA to +20mA 16000 20000μA
7 Current input mode -20mA to +20mA 4000 20000μA
Set the analog input value in mV for the voltage input mode, and set the analog input value in μA
for the current input mode.
Example: To set the gain value of 3 V, set 3000 mV.
→ For a detailed description of gain data, refer to Subsection 5.4.14.
B-50
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Changing Input Characteristics
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 6.1 Procedure for Changing Input Characteristics
A
5
Common Items
Create a sequence program.
To change the input characteristics, write the offset data (BFM#41 to #44) and the gain data
(BFM#51 to #54) in the sequence program, and then turn on the corresponding bit of BFM#21 for
the corresponding channel. The following example shows a program for the unit number 0.
B
Example: Program for changing the input characteristics of channels 1 and 2 (For FX3U/FX3UC Series
FX3UC-4AD
FX3U-4AD
PLCs):
FX3U-4AD-ADP
SET M0
T0 K50 *1
T0
FNC 16 K1000 U0\G41 K2
Offset value of
channels 1 and 2
D
FMOV P
FX3G-2AD-BD
FNC 16 Gain value of
K3000 U0\G51 K2 channels 1 and 2
FMOV P
FX3U-4DA
RST M0
*1. It takes approximately 5 seconds to change the input mode (BFM#0). This is because all the set
values should be changed.
After changing the input mode, be sure to wait for 5 seconds or more before setting other data. F
FX3U-4DA-ADP
The input characteristics of each channel can be written in BFM#21. It is also possible to perform
batch writing of input characteristics for two or more channels.
FX3G-1DA-BD
Start the PLC, and turn on the command (X000) to write the input characteristics. In approx. 5 sec-
onds, the offset data and the gain data will be written.
Since the offset data and the gain data are stored in the 4AD EEPROM, it is possible to delete the
sequence program. H
7
FX3U-3A-ADP
J
FX3U-4AD-PTW
-ADP
B-51
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 7 Examples of Practical Programs
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 7.1 Program That Uses Averaging Time
1. Conditions
The sequence program described in this section is created under the following conditions.
1) System configuration
The FX3U-4AD (unit No.0) should be connected to the FX3U Series PLC.
2) Input mode
Channels 1 and 2 should be set to mode 0 (voltage input, -10V to +10V → -32000 to +32000).
Channels 3 and 4 should be set to mode 3 (current input, 4mA to 20mA → 0 to 16000).
3) Averaging time
For channels 1 to 4, the averaging time should be set to "10".
4) Digital filter function
For channels 1 to 4, the digital filter function should be disabled (default).
5) Device assignment
Device Description
D0 A/D converted digital value for channel 1
D1 A/D converted digital value for channel 2
D2 A/D converted digital value for channel 3
D3 A/D converted digital value for channel 4
T0
FNC 16 For channels 1 to 4, the averaging time
K10 U0\G2 K4 will be set to "10".
FMOV P
*1. After setting the input mode, set the data writing time (waiting time) to 5 seconds or more for each
setting.
The specified input mode will be retained even if power failure occurs. After specifying the input mode,
if the same input mode is used, it is not necessary to set the input mode and waiting time (T0 K50).
*2. To use the default value set for the digital filter function, it is not necessary to set the digital filter
function in the sequence program.
B-52
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 7 Examples of Practical Programs
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 7.1 Program That Uses Averaging Time
A
• For FX3G/FX3GC/FX3U/FX3UC Series PLCs
Common Items
Initial pulse
M8002
FNC 79 Input modes of channels 1
K0 K0 H3300 K1 to 4 will be specified.*1
RUN monitor TO P
M8000
T0 K50 *1
B
FX3UC-4AD
FX3U-4AD
T0
FNC 79 For channels 1 to 4, the averaging time
K0 K2 K10 K4 will be set to "10".
TO P
FNC 78 K0 K10 D0 K4
The digital values set for channels C
1 to 4 will be read out to D0 to D3.
FX3U-4AD-ADP
FROM
*1. After setting the input mode, set the data writing time (waiting time) to 5 seconds or more for each
setting.
The specified input mode will be retained even if power failure occurs. After specifying the input mode,
if the same input mode is used, it is not necessary to set the input mode and waiting time (T0 K50). D
*2. To use the default value set for the digital filter function, it is not necessary to set the digital filter
FX3G-2AD-BD
function in the sequence program.
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
B-53
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 7 Examples of Practical Programs
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 7.2 Program That Uses Convenient Functions
1. Conditions
The sequence program described in this section is created under the following conditions.
1) System configuration
The FX3U-4AD (unit No.0) should be connected to the FX3U Series PLC.
2) Input mode
Channels 1 and 2 should be set to mode 0 (voltage input, -10V to +10V → -32000 to +32000).
Channels 3 and 4 should be set to mode 3 (current input, 4mA to 20mA → 0 to 16000).
3) Averaging time
For all the channels, the averaging time should be set to "1" (default).
(To use the default value, it is not necessary to set the averaging time in the sequence program.)
4) Digital filter function
For all channels, the digital filter function should be disabled (default).
(To use the default value, it is not necessary to set the digital filter function in the sequence program.)
5) Convenient functions
The upper/lower limit detection function, upper/lower limit error status data automatic transfer function,
over-scale status data automatic transfer function, and error status data automatic transfer function
should be used.
Caution:
The upper/lower limit error status data automatic transfer function, the over-scale status data automatic
transfer function, and the error status data automatic transfer function are not supported when connected
and used with the FX5U or FX5UC CPU module.
6) Device assignment
Device Description
X000 Clearance of upper/lower limit error data
Input
X001 Clearance of over-scale data
Y000 Output of channel-1 lower limit error data
Y001 Output of channel-1 upper limit error data
Y002 Output of channel-2 lower limit error data
Y003 Output of channel-2 upper limit error data
Y004 Output of channel-3 lower limit error data
Y005 Output of channel-3 upper limit error data
Y006 Output of channel-4 lower limit error data
Y007 Output of channel-4 upper limit error data
Y010 Output of channel-1 over-scale (lower limit) data
Y011 Output of channel-1 over-scale (upper limit) data
Y012 Output of channel-2 over-scale (lower limit) data
Y013 Output of channel-2 over-scale (upper limit) data
Output Y014 Output of channel-3 over-scale (lower limit) data
Y015 Output of channel-3 over-scale (upper limit) data
Y016 Output of channel-4 over-scale (lower limit) data
Y017 Output of channel-4 over-scale (upper limit) data
Y020 Output of error detection signal
Y021 Output of setting error detection signal
D0 A/D converted digital value of channel 1
D1 A/D converted digital value of channel 2
D2 A/D converted digital value of channel 3
D3 A/D converted digital value of channel 4
D100 Upper/lower limit error status data automatic transfer-to data register
D101 Over-scale status data automatic transfer-to data register
D102 Error status data automatic transfer-to data register
B-54
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 7 Examples of Practical Programs
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 7.2 Program That Uses Convenient Functions
A
2. Example of sequence program
Common Items
• For FX3U/FX3UC Series PLCs
Initial pulse
M8002
FNC 12 Input modes of channels 1 to 4 will be
RUN monitor MOV P
H3300 U0\G0 specified.*2 B
M8000
FX3UC-4AD
FX3U-4AD
T0 K50 *1
T0
FNC 12 H01A2 U0\G22 The convenient functions will be set.*2
MOV P
FX3U-4AD-ADP
FNC 12 The over-scale status data automatic transfer-to data
K101 U0\G128 register will be set to D101.*2
MOV P
FX3G-2AD-BD
BMOV to #13 into D0 to D3.
Clearance of upper/lower
limit error data
X000
FNC 12 H0003 U0\G99 Clearance of upper/lower limit error data
MOV P
Clearance of over-scale
data
E
FX3U-4DA
X001
FNC 12 K0 U0\G28 Clearance of over-scale data
MOV P
RUN monitor
M8000
FNC 12
MOV
D100 K2Y000
The upper/lower limit error status data of each channel
will be output to Y000 to Y007. F
FX3U-4DA-ADP
FNC 12 The over-scale status data of each channel will be output
D101 K2Y010 to Y010 to Y017.
MOV
Error detection
D102.0
FX3G-1DA-BD
D102.8
Y021 The setting error detection signal will be output to Y021.
*1. After setting the input mode, set the data writing time (waiting time) to 5 seconds or more for each
setting.
H
FX3U-3A-ADP
After this, if the same input mode is used, it is not necessary to set the input mode and waiting time
(T0 K50) again.
*2. The set input mode, convenient functions, upper/lower limit error status data automatic transfer-to
data register number, over-scale status data automatic transfer-to data register number, and error
status data automatic transfer-to data register number are retained in the 4AD EEPROM. For this
reason, even if the sequence program is deleted, the previously set functions will still be valid.
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
B-55
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 7 Examples of Practical Programs
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 7.2 Program That Uses Convenient Functions
Initial pulse
M8002
FNC 79 Input modes of channels 1 to 4 will be
K0 K0 H3300 K1 specified.*2
RUN monitor TO P
M8000
T0 K50 *1
T0
FNC 79 K0 K22 H01A2 K1 The convenient functions will be set. *2
TO P
RUN monitor
M8000
FNC 12 The upper/lower limit error status data of each
D100 K2Y000 channel will be output to Y000 to Y007.
MOV
*1. After setting the input mode, set the data writing time (waiting time) to 5 seconds or more for each
setting.
After this, if the same input mode is used, it is not necessary to set the input mode and waiting time
(T0 K50) again.
*2. The set input mode, convenient functions, upper/lower limit error status data automatic transfer-to
data register number, over-scale status data automatic transfer-to data register number, and error
status data automatic transfer-to data register number are retained in the 4AD EEPROM. For this
reason, even if the sequence program is deleted, the previously set functions will still be valid.
B-56
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 7 Examples of Practical Programs
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 7.3 Program That Uses Data History Function
A
7.3 Program That Uses Data History Function
Common Items
This section describes a program that uses the data history function of the 4AD.
1. Conditions
The sequence program described in this section is created under the following functions. B
1) System configuration
FX3UC-4AD
FX3U-4AD
The FX3U-4AD (unit No.0) should be connected to the FX3U Series PLC.
2) Input mode
Channels 1 and 2 should be set to mode 0 (voltage input, -10V to +10V → -32000 to +32000).
Channels 3 and 4 should be set to mode 3 (current input, 4mA to 20mA → 0 to 16000).
3) Averaging time C
FX3U-4AD-ADP
For all the channels, the averaging time should be set to "1" (default).
(To use the default value, it is not necessary to set the averaging time in the sequence program.)
4) Digital filter function
For all channels, the digital filter function should be disabled (default).
(To use the default value, it is not necessary to set the digital filter function in the sequence program.)
5) Data history function
D
FX3G-2AD-BD
For all channels, the data sampling time should be set to 100 ms.
The sampling cycle should be 100 ms × 4 (number of selected channels) = 400 ms.
For all channels, data will be sampled 100 times, and the sampled data will be stored as data history in
the data registers.
6) Device assignment
Device Description
E
FX3U-4DA
X000 Clearance of data history
Input
X001 Temporarily stoppage of data history
D0 A/D converted digital value of channel 1
D1 A/D converted digital value of channel 2
D2 A/D converted digital value of channel 3 F
FX3U-4DA-ADP
D3 A/D converted digital value of channel 4
Data register
D100 to D199 Channel-1 data history(100 data samples)
D200 to D299 Channel-2 data history(100 data samples)
D300 to D399 Channel-3 data history(100 data samples)
D400 to D499 Channel-4 data history(100 data samples) G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
B-57
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 7 Examples of Practical Programs
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 7.3 Program That Uses Data History Function
Initial pulse
M8002
FNC 12 Input modes of channels 1 to 4 will be
H3300 U0\G0 specified.*2
RUN monitor MOV P
M8000
T0 K50 *1
T0
FNC 12 K100 U0\G198 The sampling time will be set to 100 ms.*2
MOV P
T0
FNC 15 Channel-1 history data (100 data samples)
U0\G200 D100 K100 will be read out to D100 to D199.
BMOV
*1. After setting the input mode, set the data writing time (waiting time) to 5 seconds or more for each
setting.
After this, if the same input mode is used, it is not necessary to set the input mode and waiting time
(T0 K50) again.
*2. The set input mode and the sampling time are retained in the 4AD EEPROM. Therefore, even if the
sequence program is deleted, the previously set functions will still be valid.
*3. If a large amount of history data is read out, the scan time of the PLC will be become longer. If the
scan time exceeds 200 ms, the CPU error indicator lamp will illuminate, and the PLC will stop.
Insert WDT instruction (watchdog timer refresh) between BMOV instructions.
B-58
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 7 Examples of Practical Programs
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 7.3 Program That Uses Data History Function
A
• For FX3G/FX3GC/FX3U/FX3UC Series PLCs
Common Items
Initial pulse
M8002
FNC 79 K0 K0 H3300 K1 Input modes of channels 1 to 4 will be
TO P specified.*2
RUN monitor
M8000
T0 K50 *1 B
FX3UC-4AD
FX3U-4AD
T0
FNC 79 K0 K198 K100 K1 The sampling time will be set to 100 ms.*2
TO P
FX3U-4AD-ADP
FNC 79 K0 K199 H000F K1 Data history of all the channels will be
TO P erased.
Temporarily stop
data history
X001
FNC 79 K0 K199 H0F00 K1 Data history of all the channels will be
TO P temporarily stopped.
Temporarily stop
data history
D
FX3G-2AD-BD
X001
FNC 79 K199 H0000 K1 Temporary stoppage of data history will be
K0 canceled for all the channels.
TO P
T0
FNC 79 Channel-1 history data (100 data samples)
TO
K0 K200 D100 K100
will be read out to D100 to D199. E
FX3U-4DA
FNC 07 The watchdog timer will be refreshed.*3
WDT
FX3U-4DA-ADP
WDT
FX3G-1DA-BD
FNC 79 K0 K5300 D400 K100 Channel-4 history data (100 data samples)
TO will be read out to D400 to D499.
setting.
After this, if the same input mode is used, it is not necessary to set the input mode and waiting time
(T0 K50) again.
*2. The set input mode and the sampling time are retained in the 4AD EEPROM. Therefore, even if the
sequence program is deleted, the previously set functions will still be valid. I
*3. If a large amount of history data is read out, the scan time of the PLC will be become longer. If the
FX3U-4AD-PT
scan time exceeds 200 ms, the CPU error indicator lamp will illuminate, and the PLC will stop.
Insert WDT instruction (watchdog timer refresh) between BMOV instructions.
-ADP
J
FX3U-4AD-PTW
-ADP
B-59
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 7 Examples of Practical Programs
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 7.4 Initialization Program for 4AD (Factory Default)
1. Conditions
The sequence program described in this section runs under the following conditions.
1) System configuration
The FX3U-4AD (unit No.0) should be connected to the FX3U Series PLC.
2) Device assignment
Device Description
X000 4AD initialization command
3. Cautions
• It takes approximately 5 seconds to complete initialization.
Do not write any data to the buffer memory in this time.
• When initialization is complete, the value of BFM#20 will be reset to "K0".
• Priority is given to the data change disable (BFM#19). To initialize, write K2080 to BFM#19.
B-60
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 8 Troubleshooting
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 8.1 PLC Version Number Check
Common Items
8. Troubleshooting
This chapter describes troubleshooting methods and error codes. B
If the A/D conversion data is not input, or if the proper digital value is not input, check the following items:
FX3UC-4AD
FX3U-4AD
• PLC version number
• Wiring
• Program
• Error status
C
FX3U-4AD-ADP
8.1 PLC Version Number Check
Verify that the PLC being used is of the following version or later.
FX3U-4AD
Compatible PLC Version number
D
FX3G-2AD-BD
FX3G Series PLC Ver. 1.00 or later
FX3GC Series PLC Ver. 1.40 or later
FX3U Series PLC Ver. 2.20 or later
FX3UC Series PLC Ver. 1.30 or later
FX3UC-4AD
E
FX3U-4DA
Compatible PLC Version number
FX3GC Series PLC Ver. 1.40 or later
FX3UC Series PLC Ver. 1.30 or later
FX3U-4DA-ADP
8.2 Wiring Check
Check the wiring as follows:
1. Power G
FX3G-1DA-BD
The 4AD needs driving power. Verify that the power supply line is properly connected. Also check that the 24
V indicator lamp of the 4AD is on.
1. Storage devices
Check whether the device holding digital values contains any values written by other programs. J
FX3U-4AD-PTW
B-61
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 8 Troubleshooting
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 8.4 Error Status Check
B-62
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 8 Troubleshooting
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 8.5 4AD Initialization and Test Program
A
8. Digital filter setting error (b11)
Common Items
1) Description of error
The digital filter value (BFM#6 to #9) is not set correctly.
2) Remedy
Set the digital filter value again in the range from 0 to 1600.
Also check that the averaging is not set for the selected channel. B
FX3UC-4AD
FX3U-4AD
9. Abrupt change detection value setting error (b12)
1) Description of error
The abrupt change detection value (BFM#91 to #94) is not set correctly.
2) Remedy
Check that the abrupt change detection value is in the range specified for the selected input mode. If the C
value is out of the range, correct it.
FX3U-4AD-ADP
10. Upper/lower limit detection setting error (b13)
1) Description of error
The lower limit error detection value (BFM#71 to #74) or the upper limit error detection value (BFM#81 to
#84) is not set correctly. D
2) Remedy
FX3G-2AD-BD
Check that the upper/lower limit error detection value is in the range specified for the selected input
mode. If the value is out of the range, correct it.
FX3U-4DA
2) Remedy
Set the addition data again in the range from -16000 to +16000.
FX3U-4DA-ADP
If the remedies above cannot solve the problem, initialize and then check the conditions of the 4AD using the
test program.
→ For a detailed description of 4AD initialization program, refer to Section 7.4.
→ For a detailed description of the test program, refer to Chapter 4.
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
B-63
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 8 Troubleshooting
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 8.5 4AD Initialization and Test Program
MEMO
B-64
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4AD-ADP (4-channel Analog Input)
Common Items
B
FX3UC-4AD
FX3U-4AD
FX3S/FX3G/FX3GC/FX3U/FX3UC Series
Programmable Controllers C
FX3U-4AD-ADP
User's Manual [Analog Control Edition]
FX3G-2AD-BD
E
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
Foreword
This manual describes the specifications, wiring, and operation methods for the FX3U-4AD-ADP special
adapter (4-channel analog input) and should be read and understood before attempting to install or use the I
unit.
FX3U-4AD-PT
Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
it to the end user.
-ADP
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
rights which may occur as a result of using the contents noted in this manual.
J
FX3U-4AD-PTW
C-1
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4AD-ADP (4-channel Analog Input)
C-2
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD-ADP (4-channel Analog Input) 1.1 Outline of Functions
Common Items
1. Outline
This chapter outlines the FX3U-4AD-ADP (referred to as the 4AD-ADP). B
FX3UC-4AD
FX3U-4AD
1.1 Outline of Functions
The FX3U-4AD-ADP is an analog special adapter. Connect the FX3U-4AD-ADP to the FX3S/FX3G/FX3GC/
FX3U/FX3UC Series PLC to read 4 channels of voltage/current data.
1) Only 1 4AD-ADP unit can be connected to the FX3S Series PLC. C
Up to 2*1 4AD-ADP units can be connected to the FX3G/FX3GC Series PLC.
FX3U-4AD-ADP
Up to 4 4AD-ADP units can be connected to the FX3U/FX3UC Series PLC.
(including the other analog expansion boards, analog special adapters).
2) Either "voltage input" or "current input" can be specified for each channel.
3) A/D conversion data of each channel will be automatically written to the special data register of the FX3S/
FX3G/FX3GC/FX3U/FX3UC Series PLC. D
FX3G-2AD-BD
System Point and section to be
referred to
FX3S Series PLC : Only 1
FX3G/FX3GC Series PLC : 2*1 maximum
Number of connectable
FX3U/FX3UC Series PLC : 4 maximum units
including the other analog expansion
boards, analog special adapters
E
FX3U-4DA
FX3S/FX3G/FX3GC/FX3U/FX3UC
Series PLC
To check the connectable
PLC model number, refer
+ +
to Section 1.3.
FX3U-4DA-ADP
*2
4th 3rd 2nd 1st Expansion board
adapter adapter adapter adapter
For a detailed
Analog data description of wiring,
FX3G-1DA-BD
For FX3S/FX3G/FX3GC/FX3U/
FX3UC Series PLC
Contents
Transfer direction
Special devices*3 For a detailed description
of special devices, refer to H
Analog data 1st adapter M/D8260 to M/D8269 Chapter 4.
FX3U-3A-ADP
Refer to the system configuration shown in the User's Manual - Hardware Edition to check the number of I
connectable units and to configure the entire system.
FX3U-4AD-PT
*1. Only 1 analog special adapter can be connected to the FX3G Series PLC (14-point and 24-point type).
*2. The expansion board is not required when connecting with the FX3GC/FX3UC (D, DS, DSS) Series PLC.
-ADP
C-3
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD-ADP (4-channel Analog Input) 1.2 Setup Procedure Before Starting Operation
FX3U-4AD-ADP
Refer to Chapter 1.
Wiring Wiring:
• Selection of sensor cable
• Power supply line
Refer to Chapter 4. • Analog input line
Programming Programming:
• Details of special devices
• Examples of basic programs
Refer to Chapter 5.
C-4
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD-ADP (4-channel Analog Input) 1.3 Connectable PLCs and Version Number
A
1.3 Connectable PLCs and Version Number
Common Items
The 4AD-ADP is compatible with the following PLCs.
FX3UC-4AD
FX3U-4AD
FX3G Series PLC Ver. 1.00 or later*1 After June 2008 (From first product)
FX3GC Series PLC Ver. 1.40 or later*1 After January 2012 (From first product)
FX3U Series PLC Ver. 2.20 or later*1 After May 2005 (From first product)
FX3UC Series PLC Ver. 1.20 or later*1 After April 2004
*1. The FX3U/FX3UC Series PLC Ver. 2.70 or later and FX3S Series PLC supports the under-scale C
FX3U-4AD-ADP
detection. The FX3G/FX3GC Series PLC are not supported.
1. Version check
The PLC version can be checked by reading the last three digits of device D8001 or D8101.
→ For a detailed description of the version check,
refer to A. Common Items Subsection 5.1.2. D
FX3G-2AD-BD
2. How to check the manufacturer's serial number
The year and month of production of the product can be checked on the nameplate, and on the front of the
product.
→ For a detailed description of how to check the manufacturer's serial number,
refer to A. Common Items Subsection 5.1.1.
E
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
C-5
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD-ADP (4-channel Analog Input) 1.4 Compatible Programming Tool Version Number
1. English versions
Model name Media model name Applicable version Remarks
FX3S PLC
GX Works2 SWDNC-GXW2-E Ver. 1.492N or later
-
FX-30P Ver. 1.50 or later
FX3G PLC
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer SWD5C-GPPW-E Ver. 8.72A or later -
FX-30P Ver. 1.00 or later
FX3GC PLC
GX Works2 SWDNC-GXW2-E Ver. 1.77F or later
-
FX-30P Ver. 1.30 or later
FX3U and FX3UC PLCs
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer SWD5C-GPPW-E Ver. 8.18U or later -
FX-30P Ver. 1.00 or later
2. Japanese versions
Model name Media model name Applicable version Remarks
FX3S PLC
GX Works2 SWDNC-GXW2-J Ver. 1.492N or later
-
FX-30P Ver. 1.50 or later
FX3G PLC
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
GX Developer SWD5C-GPPW-J Ver. 8.72A or later -
FX-30P Ver. 1.00 or later
FX3GC PLC
GX Works2 SWDNC-GXW2-J Ver. 1.77F or later
-
FX-30P Ver. 1.30 or later
FX3U and FX3UC PLCs
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
GX Developer SWD5C-GPPW-J Ver. 8.13P or later -
FX-30P Ver. 1.00 or later
Point
• It is possible to create programs in FX3GC PLC using programming tools of inapplicable versions by
selecting "FX3G" as the alternative model.
• It is possible to create programs in FX3S PLC using programming tools of inapplicable versions by
selecting "FX3G" as the alternative model. However, memory capacity setting of the PLC parameter must
be set to 4000 steps or less.
C-6
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-ADP (4-channel Analog Input) 2.1 Generic Specifications
Common Items
2. Specifications
This chapter describes the general, power supply, and performance specifications for the 4AD-ADP. B
FX3UC-4AD
FX3U-4AD
2.1 Generic Specifications
Item Specifications C
FX3U-4AD-ADP
Ambient 0 to 55 °C (32 to 131 °F) when operating
temperature -25 to 75 °C (-13 to 167 °F) when stored
Relative
5 to 95 %RH (no condensation) when operating
humidity
Frequency Acceleration Half amplitude D
(Hz) (m/s2) (mm)
FX3G-2AD-BD
Tests 10 times in each
Vibration 10 to 57 - 0.035 direction (X-, Y-, and Z-
DIN Rail Mounting
resistance*1 57 to 150 4.9 - axis directions) (Total:
80 min, each)
10 to 57 − 0.075
Direct Mounting*2
−
Shock
57 to 150 9.8
E
m/s2
FX3U-4DA
147 Acceleration, Action time: 11 ms, 3 times by half-sine pulse in each direction X, Y, and Z
resistance*1
Noise Using noise simulator of:
resistance Noise voltage: 1,000 Vp-p / Noise width: 1 μs / Rise: 1 ns / Cycle: 30 to 100 Hz
Dielectric
withstand
voltage
500 V AC, for 1 min F
Between all terminals and ground terminal
FX3U-4DA-ADP
Insulation 5 MΩ or more using 500 V DC
resistance insulation resistance meter
Class D grounding (grounding resistance: 100 Ω or less)
Grounding
<Common grounding with a heavy electrical system is not allowed.>*3
Working
Free from corrosive or flammable gas and excessive conductive dusts
G
environment
FX3G-1DA-BD
Working
altitude < 2000 m*4
*4. If the pressure is higher than the atmospheric pressure, do not use the 4AD-ADP.
The 4AD-ADP may malfunction.
-ADP
J
FX3U-4AD-PTW
-ADP
C-7
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-ADP (4-channel Analog Input) 2.2 Power Supply Specifications
Item Specifications
A/D conversion circuit 24V DC +20%-15%, 40mA
driving power (It is necessary to connect a 24V DC power supply to the terminal block.)
5V DC, 15mA
Interface driving power (Since the internal power is supplied from the FX Series main unit, it is not
necessary to supply the power.)
Specifications
Item
Voltage input Current input
Analog input 0V to 10V DC 4mA to 20mA DC
range (Input resistance: 194 kΩ) (Input resistance: 250 Ω)
Absolute input
-0.5V, +15V -2mA, +30mA
maximum
Digital output 12 bits, binary 11 bits, binary
Resolution 2.5mV (10V/4000) 10μA (16mA/1600)
• ±0.5% (±50mV) for 10V full scale • ±0.5% (±80μA) for 16mA full scale
(when ambient temperature is 25°C ± 5°C) (when ambient temperature is 25°C ± 5°C)
Total accuracy
• ±1.0% (±100mV) for 10V full scale • ±1.0% (±160μA) for 16mA full scale
(when ambient temperature is 0°C to 55°C) (when ambient temperature is 0°C to 55°C)
• FX3U/FX3UC Series PLC : 200μs (The data will be updated at every scan time.)
A/D conversion
• FX3S/FX3G/FX3GC Series PLC : 250μs (The data will be updated at every scan time.)
time
→ For a detailed description of data update, refer to Section 2.4.
4080 1640
4000 1600
Input
Digital output
Digital output
characteristics
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply line from the analog input area.
• Channels are not insulated from each other.
Number of I/O
0 point (This number is not related to the maximum number of input/output points of the PLC.)
points occupied
C-8
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-ADP (4-channel Analog Input) 2.4 A/D Conversion Time
A
2.4 A/D Conversion Time
Common Items
This section describes the A/D conversion time.
FX3UC-4AD
FX3U-4AD
1. A/D conversion and special data register update timing
A/D conversion is performed at every scan time of the PLC.
During execution of END instruction, the PLC performs A/D conversion, reads out the A/D converted data,
and then writes the data in the special data registers.
FX3U-4AD-ADP FX3S Series PLC C
FX3U-4AD-ADP
Sequence
program
A/D conversion start
command
A/D
conversion D
Digital value reading END instruction
FX3G-2AD-BD
250 s/4ch
FX3U-4DA
3. A/D conversion speed (data update time)
During execution of the END instruction, the A/D converted data of all 4 channels will be read out in 250 μs,
and the data read out will be written to the special data registers.
END instruction execution time will be 250 μs.
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
C-9
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-ADP (4-channel Analog Input) 2.4 A/D Conversion Time
Sequence
program
A/D conversion start
A/D command
conversion
Digital value reading
250 s/4ch
A/D conversion start END instruction
A/D command
conversion
Digital value reading
250 s/4ch
C-10
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-ADP (4-channel Analog Input) 2.4 A/D Conversion Time
A
2.4.3 When connected to a FX3U/FX3UC PLC
Common Items
1. A/D conversion and special data register update timing
A/D conversion is performed at every scan time of the PLC.
During execution of END instruction, the PLC performs A/D conversion, reads out the A/D converted data,
and then writes the data in the special data registers. B
FX3UC-4AD
FX3U-4AD
FX3U-4AD-ADP FX3U-4AD-ADP
n'th 1st FX3U/FX3UC Series PLC
Sequence
FX3U-4AD-ADP
A/D command
conversion
Digital value reading
200 s/4ch
A/D conversion start END instruction
A/D
conversion
command
D
FX3G-2AD-BD
Digital value reading
200 s/4ch
FX3U-4DA
3. If two or more analog special adapters are connected
During execution of the END instruction, data will be read out from all the connected adapters (in the order of
1st adapter → 2nd adapter... 4th adapter).
FX3U-4DA-ADP
and the data read out will be written to the special data registers.
END instruction execution time will be "200 μs × number of connected analog adapters."
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
C-11
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-ADP (4-channel Analog Input)
3. Wiring
This chapter describes the 4AD-ADP wiring.
Observe the following caution to wire the 4AD-ADP.
WIRING PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before attempting wiring work.
Failure to do so may cause electric shock or damage to the product.
WIRING PRECAUTIONS
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn
out.
• Do not wire vacant terminals externally.
Doing so may damage the product.
• Perform class D grounding (grounding resistance: 100Ω or less) to the grounding terminal on the main unit.
Do not use common grounding with heavy electrical systems.
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
• Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise:
- Do not bundle the power line or shield of the analog input/output cable together with or lay it close to the main
circuit, high-voltage line, or load line.
Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
100mm (3.94") or more away from the main circuit, high-voltage line, or load line.
- Ground the shield of the analog input/output cable at one point on the signal receiving side.
However, do not use common grounding with heavy electrical systems.
• Make sure to properly wire to the terminal block (European type) in accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
- The disposal size of the cable end should follow the dimensions described in the manual.
- Tightening torque should follow the specifications in the manual.
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
C-12
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-ADP (4-channel Analog Input) 3.1 Terminal Layout
A
3.1 Terminal Layout
Common Items
The terminals of the 4AD-ADP are arranged as follows:
FX3UC-4AD
FX3U-4AD
Signal Application
24+
24-
External power
C
Grounding terminal
FX3U-4AD-ADP
V1+
I1+ Channel 1 analog input
COM1
V2+
I2+
COM2
Channel 2 analog input
D
FX3G-2AD-BD
V3+
I3+ Channel 3 analog input
COM3
V4+
I4+ Channel 4 analog input
COM4 E
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
C-13
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-ADP (4-channel Analog Input) 3.2 Applicable Cables and Terminal Tightening Torque
1. Cables
Applicable cable and tightening torque
Wire size Tightening
Termination
(stranded wire/solid wire) torque
0.3 mm2 to 0.5 mm2 • To connect a stranded cable, peel the cover off the cable
Single-wire and then twist the core before connection.
(AWG22 to 20)
• To connect a single-wire cable, just strip the cover off the
2-wire 0.3 mm2 (AWG22)×2 cable before connection.
0.22 to • Ferrule with insulation sleeve
0.3 mm2 to 0.5 mm2 0.25 N•m (recommended terminal)
Ferrule with (AWG22 to 20) AI 0.5-8WH : Manufactured by Phoenix Contact
insulation (Refer to the external view • Caulking tool
sleeve of ferrule shown in the
CRIMPFOX 6*1 : Manufactured by Phoenix Contact
following figure.)
(or CRIMPFOX 6T-F*2 : Manufactured by Phoenix Contact)
3. Tool
For tightening the terminal, use a commercially available small screwdriver
The head
having a straight form that is not widened toward the end as shown right. should be
straight.
Note:
If the diameter of screwdriver grip is too small, tightening torque will not be
able to be achieved. To achieve the appropriate tightening torque shown in 0.4mm 2.5mm
the table above, use the following screwdriver or an appropriate (0.01") (0.09")
replacement (grip diameter: approximately 25 mm (0.98")).
<Reference>
Manufacturer Model
Phoenix Contact SZS 0.4×2.5
C-14
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-ADP (4-channel Analog Input) 3.3 Power Supply Line
A
3.3 Power Supply Line
Common Items
Connect the 24 V DC power supply line of the 4AD-ADP to the 24+ and 24- terminals of the terminal block.
FX3UC-4AD
FX3U-4AD
4AD-ADP FX3S/FX3G/FX3U 4AD-ADP FX3S/FX3G/FX3U
Series Series
+15V +15V
PLC (Main unit) PLC (Main unit)
FX3U-4AD-ADP
24+ 24- 24+ 24- 24V 0V D
FX3G-2AD-BD
Terminal Terminal
block block
Fuse
Class-D Class-D
24V DC grounding grounding
Caution regarding connection of the power supply line: E
FX3U-4DA
• Ground the " " terminal to a class-D grounded power supply line (100 Ω or less) together with the
grounding terminal of the PLC main unit.
• When using an external power supply, turn it ON at the same time with the main unit or earlier than the
main unit. When turning OFF the power, confirm the safety of the system, and then turn OFF the power of
the PLC (including special adapter) at the same time.
F
3.3.2 To connect to the FX3GC/FX3UC Series PLC
FX3U-4DA-ADP
Example of wiring of FX3UC Series PLC
4AD-ADP FX3UC Series PLC
(Main unit)
+15V
G
FX3G-1DA-BD
Power
connector H
FX3U-3A-ADP
I
Fuse
FX3U-4AD-PT
Class-D
24V DC grounding
For example of wiring of FX3GC Series PLC, refer to the following manual.
-ADP
• Ground the " " terminal to a class-D grounded power supply line (100 Ω or less) together with the
grounding terminal of the PLC main unit.
-ADP
C-15
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-ADP (4-channel Analog Input) 3.4 Analog Input Line
*1 147kΩ ch
V+
250Ω
I+
47kΩ
COM
Class-D
grounding
*1. Use the 2-core shielded twisted pair cable for the analog input lines, and separate the analog input
lines from other power lines or inductive lines.
*2. If "current input" is selected, be sure to short the line between the V+ terminal and the I+ terminal.
(: Channel number).
*3. For FX3S/FX3G/FX3U Series PLC (AC power type), the 24 V DC service power supply is also
available.
3.5 Grounding
Grounding should be performed as stated below.
• The grounding resistance should be 100 Ω or less.
• Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" as shown in the following
figure.
→ For details, refer to the User’s Manual - Hardware Edition of each PLC Series.
C-16
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-ADP (4-channel Analog Input) 4.1 Loading of A/D Conversion Data
Common Items
4. Programming
This chapter describes how to create programs that can read analog data using the 4AD-ADP. B
FX3UC-4AD
FX3U-4AD
4.1 Loading of A/D Conversion Data
1) The input analog data will be converted into digital data and then stored in the special devices of the
FX3S/FX3G/FX3GC/FX3U/FX3UC Series PLC.
C
2) If the data is stored in the special devices, the averaging time can be set, and the input mode can be
FX3U-4AD-ADP
specified.
3) Special auxiliary relays (10 points) and special data registers (10 points) are assigned automatically
starting from the adapter nearest to the main unit.
→ For a detailed description of special device assignment, refer to Section 4.2.
• FX3S Series PLC D
FX3G-2AD-BD
Communi-
cation
FX3U-4AD special FX3S-CNV
-ADP adapter -ADP FX3S Series PLC
Special devices
Special auxiliary relays: E
A/D M8280 to M8289 Sequence
FX3U-4DA
Special data registers: program
D8280 to D8289
FX3U-4DA-ADP
cation
FX3U-4AD special FX3U-4AD
-ADP adapter -ADP FX3G/FX3GC Series PLC*2
*1
2nd 1st
Special devices
A/D
Special auxiliary relays:
M8280 to M8289 G
Special data registers:
FX3G-1DA-BD
D8280 to D8289.
Sequence
program
Special auxiliary relays:
M8290 to M8299
A/D Special data registers:
D8290 to D8299.
H
FX3U-3A-ADP
The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
next adapter as the 2nd analog special adapter. However, in this case, do not include the connector
conversion adapter and the communication special adapter.
*1. The second special adapter is not available in the FX3G Series PLC (14-point and 24-point type).
*2. A connector conversion adapter is required to connect the FX3U-4AD-ADP to the FX3G Series PLC. I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
C-17
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-ADP (4-channel Analog Input) 4.2 List of Special Devices
The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
next adapter as the 2nd analog special adapter, and so on. However, in this case, do not include the high-
speed input/output special adapter, communication special adapter, and the CF card special adapter.
*3. An expansion board is required to connect the FX3U-4AD-ADP to the FX3U/FX3UC-32MT-LT(-2) PLC.
C-18
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-ADP (4-channel Analog Input) 4.2 List of Special Devices
A
• FX3G/FX3GC Series PLC
Common Items
R: Read / W: Write
Special Device number
Description Attribute Reference
device 1st 2nd
M8280 M8290 Switches the input mode of channel 1 R/W
M8281 M8291 Switches the input mode of channel 2 R/W
B
Special Section 4.3
FX3UC-4AD
FX3U-4AD
M8282 M8292 Switches the input mode of channel 3 R/W
auxiliary
relay M8283 M8293 Switches the input mode of channel 4 R/W
M8284 to M8294 to
Unused (Do not use.) - -
M8289 M8299
D8280 D8290 Channel-1 input data R C
D8281 D8291 Channel-2 input data R
FX3U-4AD-ADP
Section 4.4
D8282 D8292 Channel-3 input data R
D8283 D8293 Channel-4 input data R
Averaging time for channel-1
D8284 D8294 R/W
(Setting range: 1 to 4095)
Special
data Averaging time for channel-2 D
D8285 D8295 R/W
(Setting range: 1 to 4095)
FX3G-2AD-BD
register Section 4.5
Averaging time for channel-3
D8286 D8296 R/W
(Setting range: 1 to 4095)
Averaging time for channel-4
D8287 D8297 R/W
(Setting range: 1 to 4095)
D8288 D8298 Error status R/W Section 4.6 E
FX3U-4DA
D8289 D8299 Model code = 1 R Section 4.7
FX3U-4DA-ADP
Switches the input mode of
M8260 M8270 M8280 M8290 R/W
channel 1
Switches the input mode of
M8261 M8271 M8281 M8291 R/W
channel 2
Special Section 4.3
Switches the input mode of
auxiliary
relay
M8262 M8272 M8282 M8292
channel 3
R/W G
FX3G-1DA-BD
Switches the input mode of
M8263 M8273 M8283 M8293 R/W
channel 4
M8264 to M8274 to M8284 to M8294 to
Unused (Do not use.) - -
M8269 M8279 M8289 M8299
D8260 D8270 D8280 D8290 Channel-1 input data R
D8261 D8271 D8281 D8291 Channel-2 input data R
H
Section 4.4
FX3U-3A-ADP
Section 4.5
Averaging time for channel-3
D8266 D8276 D8286 D8296 R/W
(Setting range: 1 to 4095)
Averaging time for channel-4
-ADP
C-19
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-ADP (4-channel Analog Input) 4.3 Switching of Input Mode
C-20
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-ADP (4-channel Analog Input) 4.4 Input Data
A
4.4 Input Data
Common Items
Numeric data type: Decimal (K)
The data converted by the 4AD-ADP will be stored in the special data registers.
The special data registers that store the input data are shown in the following table:
B
• FX3S Series PLC
FX3UC-4AD
FX3U-4AD
Special data register Description
D8280 Stores the channel-1 input data
D8281 Stores the channel-2 input data
D8282
D8283
Stores the channel-3 input data
Stores the channel-4 input data
C
FX3U-4AD-ADP
• FX3G/FX3GC Series PLC
Special data register
Description
1st 2nd
D8280 D8290 Stores the channel-1 input data D
D8281 D8291 Stores the channel-2 input data
FX3G-2AD-BD
D8282 D8292 Stores the channel-3 input data
D8283 D8293 Stores the channel-4 input data
FX3U-4DA
D8260 D8270 D8280 D8290 Stores the channel-1 input data
D8261 D8271 D8281 D8291 Stores the channel-2 input data
D8262 D8272 D8282 D8292 Stores the channel-3 input data
D8263 D8273 D8283 D8293 Stores the channel-4 input data F
FX3U-4DA-ADP
The converted A/D immediate data or averaged data (data average conforming to the specified averaging
time) will be stored in the above data registers as the input data.
→ For a detailed description of the averaging time, refer to Section 4.5.
FX3G-1DA-BD
Do not change (rewrite) the input data using sequence program, indicator, or device monitor of the
programming tool.
Even if the input data is not stored in D100 or D101, data registers D8260 or D8261 can be directly used in
I
FX3U-4AD-PT
J
FX3U-4AD-PTW
-ADP
C-21
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-ADP (4-channel Analog Input) 4.5 Averaging Time
C-22
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-ADP (4-channel Analog Input) 4.6 Error Status
A
4.6 Error Status
Common Items
If an error is detected in the 4AD-ADP, the error status data will be stored in the corresponding special data
register.
The following table shows the special data registers that store the error status data:
• FX3S Series PLC B
FX3UC-4AD
FX3U-4AD
Special data register Description
D8288 Stores the error status data.
FX3U-4AD-ADP
D8288 D8298 Stores the error status data.
FX3G-2AD-BD
Check the ON/OFF status of each bit of the error status data register to check the description of the error.
Errors are assigned to the bits as shown in the following table. Create a program to detect errors.
→ For a detailed description of the error status, refer to Section 6.5.
FX3U-4DA
b0 Channel-1 over-scale detection b7 4AD-ADP communication data error
b1 Channel-2 over-scale detection b8 Channel-1 under-scale detection*1
b2 Channel-3 over-scale detection b9 Channel-2 under-scale detection*1
b3 Channel-4 over-scale detection b10 Channel-3 under-scale detection*1
F
b4 EEPROM error b11 Channel-4 under-scale detection*1
FX3U-4DA-ADP
b5 Averaging time setting error b12 to b15 Unused
4AD-ADP hardware error
b6 - -
(Power supply error included)
*1. The FX3U/FX3UC Series PLC Ver. 2.70 or later and FX3S Series PLC in applicable.
The under-scale detection function is valid only for current input mode. G
FX3G-1DA-BD
The FX3G/FX3GC Series PLC are not supported.
M8000
FNC 12 D8288 K4M0
Normally ON MOV
M8002
RST M6
*2
Error status of 3rd analog special adapter
b6 = OFF (4AD-ADP hardware error)
I
Initial pulse
FX3U-4AD-PT
*2
RST M7 Error status of 3rd analog status register
b7 = OFF (4AD-ADP communication data error)
-ADP
FNC 12
K4M0 D8288
MOV
J
FX3U-4AD-PTW
C-23
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-ADP (4-channel Analog Input) 4.6 Error Status
M8000
FNC 12
D8288 K4M0
Normally ON MOV
M0
Y000 Detects over-scale in channel 1 of
the 3rd*1 adapter.
M1
Y001 Detects over-scale in channel 2 of
the 3rd*1 adapter.
M2
Y002 Detects over-scale in channel 3 of
the 3rd*1 adapter.
M3
Y003 Detects over-scale in channel 4 of
the 3rd*1 adapter.
M4
Y004 EEPROM error in 3rd*1 adapter.
M5
Y005 Averaging time setting error in
3rd*1 adapter.
M6
Y006 4AD-ADP hardware error in
3rd*1 adapter.
M7
Y007 4AD-ADP communication data
error in 3rd*1 adapter.
*1. "1st" for the FX3S/FX3G/FX3GC PLC.
D8268.2
Y002 Detects over-scale in channel 3 of
the 1st adapter.
D8268.3
Y003 Detects over-scale in channel 4 of
the 1st adapter.
D8268.4
Y004 EEPROM error in 1st adapter.
D8268.5
Y005 Averaging time setting error in
1st adapter.
D8268.6
Y006 4AD-ADP hardware error in 1st adapter.
D8268.7
Y007 4AD-ADP communication data error
in 1st adapter.
C-24
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-ADP (4-channel Analog Input) 4.7 Model Code
A
4.7 Model Code
Common Items
Initial value: K1
Numeric data type: Decimal (K)
When the 4AD-ADP is connected, model code "1" is stored in the corresponding special data register.
The following table shows the special data registers that store the model code: B
FX3UC-4AD
FX3U-4AD
• FX3S Series PLC
Special data register Description
D8289 Model code
FX3U-4AD-ADP
Description
1st 2nd
D8289 D8299 Model code
FX3G-2AD-BD
1st 2nd 3rd 4th
D8269 D8279 D8289 D8299 Model code
Use the special data registers above to check whether a 4AD-ADP is connected or not.
E
1. Program Example (For FX3U/FX3UC Series PLC)
FX3U-4DA
FNC224 D8269 K1 Y007 Checks the model code of the 1st
LD= analog special adapter
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
C-25
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-ADP (4-channel Analog Input) 4.8 Basic Program Example
FNC 12
K4M0 D8288
MOV
M8000
FNC 12 Sets the averaging time to "5"
K5 D8284 for channel-1 data.
Normally MOV
ON
FNC 12 Sets the averaging time to "5"
K5 D8285 for channel-2 data.
MOV
M8000
FNC 12 D8280 D100 Stores the A/D converted
Normally MOV channel-1 digital data into D100.
ON
FNC 12 D8281 D101 Stores the A/D converted
MOV channel-2 digital data into D101.
Even if the input data is not stored into D100 or D101, the data registers D8280 or D8281 can be directly
used in the timer/counter setting value or in a PID instruction.
*1. "1st" for the FX3S/FX3G/FX3GC PLC.
C-26
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-ADP (4-channel Analog Input) 4.8 Basic Program Example
A
• For FX3U/FX3UC Series PLC
Common Items
The following program will set channel 1 of the 1st adapter to voltage input mode and channel 2 to current
input mode, and will store the converted A/D value of channel-1 data into D100 and that of channel-2 data
into D101.
M8001 Sets the input mode of channel
Normally
M8260 1 to the voltage input mode
(0 V to 10 V).
B
OFF
FX3UC-4AD
FX3U-4AD
M8000 Sets the input mode of channel
M8261 2 to the current input mode
Normally (4 mA to 20 mA).
ON
M8002
RST D8268.6 Error status: b6 = OFF C
Initial
FX3U-4AD-ADP
pulse
RST D8268.7 Error status: b7 = OFF
M8000
FNC 12 Sets the averaging time to "5"
K5 D8264 for channel-1 data.
MOV
Normally
ON
Sets the averaging time to "5"
D
FNC 12 K5 D8265
FX3G-2AD-BD
MOV for channel-2 data.
M8000
FNC 12 D8260 D100 Stores the A/D converted
Normally MOV channel-1 digital data into D100.
ON
FNC 12
MOV
D8261 D101 Stores the A/D converted
channel-2 digital data into D101. E
FX3U-4DA
Even if the input data is not stored into D100 or D101, the data registers D8260 or D8261 can be directly
used in the timer/counter setting value or in a PID instruction.
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
C-27
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Changing of Input Characteristics
FX3U-4AD-ADP (4-channel Analog Input) 5.1 Example: Changing of Voltage Input Characteristics
1. Input characteristics
Voltage input characteristics Digital output value to be changed
(product specifications) Y-axis
Digital output
4000 10000
Digital output to
be calculated
(D110)
2000
400
0 X-axis
1V 5V 10V 0 400(1V) 2000(5V)
Analog input
Digital value actually obtained
by A/D conversion
C-28
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Changing of Input Characteristics
FX3U-4AD-ADP (4-channel Analog Input) 5.1 Example: Changing of Voltage Input Characteristics
A
2. Example of program 1 (For FX3U/FX3UC Series PLC)
Common Items
For example, create the following program to change the digital input data of the 1st analog special adapter:
M8001
M8260 Sets the input mode of channel 1 to the voltage input mode
Normally (0 V to 10 V)
OFF
M8002
B
FX3UC-4AD
FX3U-4AD
RST D8268.6 Error status: b6 = OFF
Initial
pulse
RST D8268.7 Error status: b7 = OFF
M8000
FNC 12
MOV
K1 D8264 Sets the averaging time to "1" for the channel-1 data C
Normally
FX3U-4AD-ADP
ON
M8002 FNC 12 K2 D50 Program for setting scaling instruction data table
Initial MOV
pulse Item Description Value Device
FNC 12
MOV
K400 D51 Number of points
X-
Sets the number of points
A/D converted digital value
2 D50
D
400 D51
FX3G-2AD-BD
Start coordinate start point data
FNC 12 K0 D52 point Y- Digital output value of changed
MOV coordinate X-axis value start point 0 D52
FX3U-4DA
M8000 FNC259
D8260 D50 D100 The scaling instruction operation results will be stored in D100.
Normally SCL
ON
F
Cautions regarding use of the SCL instruction
FX3U-4DA-ADP
If the A/D converted digital value is out of the data table range specified by the SCL instruction, the PLC will
detect an operation error (error code: K6706).
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
C-29
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Changing of Input Characteristics
FX3U-4AD-ADP (4-channel Analog Input) 5.1 Example: Changing of Voltage Input Characteristics
C-30
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
FX3U-4AD-ADP (4-channel Analog Input) 6.1 PLC Version Number Check
Common Items
6. Troubleshooting
This chapter describes troubleshooting methods and error statuses. B
If the A/D conversion data is not input, or if the proper digital value is not input, check the following items:
FX3UC-4AD
FX3U-4AD
• PLC version number
• Wiring
• Special devices
• Programs C
• Error status
FX3U-4AD-ADP
6.1 PLC Version Number Check
• Any versions (from Ver. 1.00 (initial version) to the latest version) of the FX3S Series are compatible. D
• Any versions (from Ver. 1.00 (initial version) to the latest version) of the FX3G Series are compatible.
FX3G-2AD-BD
• Any versions (from Ver. 1.40 (initial version) to the latest version) of the FX3GC Series are compatible.
• Any versions (from Ver. 2.20 (initial version) to the latest version) of the FX3U Series are compatible.
• Check the version number of the FX3UC Series PLC. The version number should be 1.20 or later.
→ For a detailed description of the version check method,
refer to A. Common Items Subsection 5.1.2.
E
FX3U-4DA
6.2 Wiring Check
Check the following items for wiring:
F
1. Power
FX3U-4DA-ADP
The 4AD-ADP needs driving power. Verify that the power supply line is properly connected. Also check that
the POWER indicator lamp of the 4AD-ADP is on.
FX3G-1DA-BD
3. Use of current input mode
To use the current input mode for a channel, be sure to shortcircuit the line between the V+ terminal and the
I+ terminal ( : channel number) of the channel. If the line is not shortcircuited, data will not be converted
into proper digital data.
→ For a detailed description of wiring, refer to Chapter 3. H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
C-31
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
FX3U-4AD-ADP (4-channel Analog Input) 6.3 Special Device Check
2. Input data
Verify that the special device of the selected channel is correctly selected. This special device should be
selected depending on the connecting position and the channel.
3. Averaging time
Check that the set averaging time is within the specified range. The averaging time should be set in the range
from 1 to 4095. If the set averaging time is outside the specified range, an error occurs.
4. Error status
Check that no error is detected in the 4AD-ADP.
If an error is detected, check the details of the error, and then check the wiring and programs.
→ For a detailed description of special devices, refer to Chapter 4.
C-32
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
FX3U-4AD-ADP (4-channel Analog Input) 6.5 Error Status Check
A
6.5 Error Status Check
Common Items
If an error occurs in the 4AD-ADP, the corresponding bit will turn ON.
The bit which is turned ON due to the error status is held ON until overwritten to OFF by the program or the
power is cycled. If b6 or b7 is turned ON, then it is necessary to clear the error status using the program the
next time the power of the PLC is cycled. B
FX3UC-4AD
FX3U-4AD
Bit Description Bit Description
b0 Channel-1 over-scale detection b7 4AD-ADP communication data error
b1 Channel-2 over-scale detection b8 Channel-1 under-scale detection*1
b2 Channel-3 over-scale detection b9 Channel-2 under-scale detection*1
b3 Channel-4 over-scale detection b10 Channel-3 under-scale detection*1
C
FX3U-4AD-ADP
b4 EEPROM error b11 Channel-4 under-scale detection*1
b5 Averaging time setting error b12 to b15 Unused
4AD-ADP hardware error
b6 - -
(Power supply error included)
*1. The FX3U/FX3UC Series PLC Ver. 2.70 or later and FX3S Series PLC in applicable.
D
FX3G-2AD-BD
The under-scale detection function is valid only for current input mode.
The FX3G/FX3GC Series PLC are not supported.
FX3U-4DA
The input analog value (voltage or current value) is outside the specified range.
Voltage input mode : The input voltage value is over the specified upper limit of 10.2 V.
Current input mode : The input current value is over the specified upper limit of 20.4 mA.
2) Remedy
Check that the input analog value is within the specified range. Also check the wiring. F
FX3U-4DA-ADP
2. EEPROM error (b4)
1) Description of error
The adjustment data which was set in the EEPROM before delivery from our factory cannot be read out
properly or has been destroyed.
2) Remedy G
Please contact your local Mitsubishi Electric representative.
FX3G-1DA-BD
3. Averaging time setting error (b5)
1) Description of error
The averaging time set for one of the channels (channels 1 to 4) is outside the specified range: 1 to 4095.
2) Remedy H
Check that the averaging time is set correctly for each channel.
FX3U-3A-ADP
J
FX3U-4AD-PTW
-ADP
C-33
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
FX3U-4AD-ADP (4-channel Analog Input) 6.5 Error Status Check
C-34
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3G-2AD-BD (2-channel Analog Input)
Common Items
B
FX3UC-4AD
FX3U-4AD
FX3S/FX3G/FX3GC/FX3U/FX3UC Series
Programmable Controllers C
FX3U-4AD-ADP
User's Manual [Analog Control Edition]
FX3G-2AD-BD
E
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
Foreword
This manual describes the specifications, wiring, and operation methods for the FX3G-2AD-BD analog input
expansion board (2-channel analog input) and should be read and understood before attempting to install or I
use the unit.
FX3U-4AD-PT
Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
it to the end user.
-ADP
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property J
rights which may occur as a result of using the contents noted in this manual.
FX3U-4AD-PTW
D-1
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3G-2AD-BD (2-channel Analog Input)
D-2
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3G-2AD-BD (2-channel Analog Input) 1.1 Outline of Functions
Common Items
1. Outline
This chapter outlines the FX3G-2AD-BD (referred to as the 2AD-BD). B
FX3UC-4AD
FX3U-4AD
1.1 Outline of Functions
The FX3G-2AD-BD is an analog expansion board. Connect the FX3G-2AD-BD to the FX3S/FX3G Series PLC
to read 2 channels of voltage/current data.
C
1) Only 1 2AD-BD unit can be connected to the FX3S Series PLC.
FX3U-4AD-ADP
Up to 2 2AD-BD units can be connected to the FX3G Series PLC (40-point and 60-point type).
Only 1 2AD-BD unit can be connected to the FX3G Series PLC (14-point and 24-point type).
(including other analog expansion boards, analog special adapters)
2) Either "voltage input" or "current input" can be specified for each channel.
3) A/D conversion data of each channel will be automatically written to the special data register of the FX3S/ D
FX3G Series PLC.
FX3G-2AD-BD
• FX3S Series PLC
Only 1
including other analog expansion boards, Number of connectable
E
analog special adapters. FX3S Series PLC
FX3U-4DA
units
FX3U-4DA-ADP
Connected to the option connector
Analog data
For a detailed
description of wiring,
FX3G-1DA-BD
Contents
Transfer direction For FX3S Series PLC
H
Analog data
FX3U-3A-ADP
J
FX3U-4AD-PTW
-ADP
D-3
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3G-2AD-BD (2-channel Analog Input) 1.1 Outline of Functions
2*1 maximum
including other analog expansion boards, Number of connectable
analog special adapters. FX3G Series PLC units
Board B Board A
To check the connectable
PLC model number, refer
to Section 1.3.
Refer to the system configuration shown in the User's Manual - Hardware Edition to check the number of
connectable units and to configure the entire system.
*1. Only 1 analog board can be connected to the FX3G Series PLC (14-point and 24-point type).
D-4
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3G-2AD-BD (2-channel Analog Input) 1.2 Setup Procedure Before Starting Operation
A
1.2 Setup Procedure Before Starting Operation
Common Items
Before starting analog input using the 2AD-BD, follow the procedure below to set up the system:
FX3G-2AD-BD B
FX3UC-4AD
FX3U-4AD
Refer to Chapter 1.
FX3U-4AD-ADP
• Operation environment
• Performance specifications
Refer to the • Input characteristics
common pages.
FX3G-2AD-BD
• Selection of units
Refer to Chapter 3.
Wiring Wiring:
• Selection of sensor cable
• Analog input line E
Refer to Chapter 4.
FX3U-4DA
Programming Programming:
• Details of special devices
• Examples of basic programs
Refer to Chapter 5.
FX3U-4DA-ADP
If the error status data or the input analog value is G
abnormal, refer to Chapter 6 "Troubleshooting."
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
D-5
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3G-2AD-BD (2-channel Analog Input) 1.3 Connectable PLCs and Version Number
1. Version check
The PLC version can be checked by reading the last three digits of device D8001 or D8101.
→ For a detailed description of the version check,
refer to A. Common Items Subsection 5.1.2.
1. English versions
Model name Media model name Applicable version Remarks
FX3S PLC
GX Works2 SWDNC-GXW2-E Ver. 1.492N or later -
FX-30P Ver. 1.50 or later -
FX3G PLC
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer SWD5C-GPPW-E Ver. 8.72A or later -
FX-30P Ver. 1.00 or later
2. Japanese versions
Model name Media model name Applicable version Remarks
FX3S PLC
GX Works2 SWDNC-GXW2-J Ver. 1.492N or later
-
FX-30P Ver. 1.50 or later
FX3G PLC
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
GX Developer SWD5C-GPPW-J Ver. 8.72A or later -
FX-30P Ver. 1.00 or later
Point
• It is possible to create programs in FX3S PLC using programming tools of inapplicable versions by
selecting "FX3G" as the alternative model. However, memory capacity setting of the PLC parameter must
be set to 4000 steps or less.
D-6
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3G-2AD-BD (2-channel Analog Input) 2.1 Generic Specifications
Common Items
2. Specifications
This chapter describes the general and performance specifications for the 2AD-BD. B
FX3UC-4AD
FX3U-4AD
2.1 Generic Specifications
Item Specifications C
FX3U-4AD-ADP
Ambient 0 to 55 °C (32 to 131 °F) when operating
temperature -25 to 75 °C (-13 to 167 °F) when stored
Relative
5 to 95%RH (no condensation) when operating
humidity
Frequency Acceleration Half amplitude D
(Hz) (m/s2) (mm)
FX3G-2AD-BD
Tests 10 times in each
Vibration 10 to 57 - 0.035 direction (X-, Y-, and Z-
DIN Rail Mounting
resistance*1 57 to 150 4.9 - axis directions) (Total:
80 min, each)
10 to 57 − 0.075
Direct Mounting
−
*1
57 to 150 9.8
E
Shock
m/s2
FX3U-4DA
147 Acceleration, Action time: 11 ms, 3 times by half-sine pulse in each direction X, Y, and Z
resistance
Noise Using noise simulator of:
resistance Noise voltage: 1,000 Vp-p / Noise width: 1 μs / Rise: 1 ns / Cycle: 30 to 100 Hz
Class D grounding (grounding resistance: 100 Ω or less)
Grounding
<Common grounding with a heavy electrical system is not allowed.>*2 F
Working
FX3U-4DA-ADP
Free from corrosive or flammable gas and excessive conductive dusts
environment
Working
altitude < 2000 m*3
FX3G-1DA-BD
PLC Other PLC Other PLC Other
equipment equipment equipment
*3. If the pressure is higher than the atmospheric pressure, do not use the 2AD-BD.
The 2AD-BD may malfunction.
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
D-7
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3G-2AD-BD (2-channel Analog Input) 2.2 Performance Specifications
Specifications
Item
Voltage input Current input
Analog input 0V to 10V DC 4mA to 20mA DC
range (Input resistance: 198.7 kΩ) (Input resistance: 250 Ω)
Absolute input
-0.5V, +15V -2mA, +30mA
maximum
Digital output 12 bits, binary 11 bits, binary
Resolution 2.5mV (10V/4000) 8μA (16mA/2000)
• ±0.5% (±50mV) for 10V full scale • ±0.5% (±80μA) for 16mA full scale
(when ambient temperature is 25°C ± 5°C) (when ambient temperature is 25°C ± 5°C)
Total accuracy
• ±1.0% (±100mV) for 10V full scale • ±1.0% (±160μA) for 16mA full scale
(when ambient temperature is 0°C to 55°C) (when ambient temperature is 0°C to 55°C)
A/D conversion 180 μs (The data will be updated at every scan time.)
time → For a detailed description of data update, refer to Section 2.3.
4080 2040
4000 2000
characteristics
D-8
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3G-2AD-BD (2-channel Analog Input) 2.3 A/D Conversion Time
A
2.3 A/D Conversion Time
Common Items
This section describes the A/D conversion time.
FX3UC-4AD
FX3U-4AD
1. A/D conversion and special data register update timing
A/D conversion is performed at every scan time of the PLC.
During execution of END instruction, the PLC performs A/D conversion, reads out the A/D converted data,
and then writes the data in the special data registers.
FX3S Series PLC C
FX3U-4AD-ADP
Sequence Program
END instruction
D
FX3G-2AD-BD
A/D conversion Digital value
start command reading
E
FX3U-4DA
A/D
conversion
180 s
/2ch
F
FX3U-4DA-ADP
FX3G-2AD-BD
FX3G-1DA-BD
the data read out will be written to the special data registers.
END instruction execution time will be 180 μs.
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
D-9
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3G-2AD-BD (2-channel Analog Input) 2.3 A/D Conversion Time
Sequence Program
END instruction
A/D A/D
conversion conversion
180 s 180 s
/2ch /2ch
FX3G-2AD-BD FX3G-2AD-BD
Board A Board B
D-10
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3G-2AD-BD (2-channel Analog Input)
Common Items
3. Wiring
This chapter describes the 2AD-BD wiring. B
Observe the following caution to wire the 2AD-BD.
FX3UC-4AD
FX3U-4AD
WIRING PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before attempting wiring work.
Failure to do so may cause electric shock or damage to the product. C
FX3U-4AD-ADP
WIRING PRECAUTIONS
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn
out.
D
FX3G-2AD-BD
• Do not wire vacant terminals externally.
Doing so may damage the product.
• Perform class D grounding (grounding resistance: 100Ω or less) to the grounding terminal on the main unit.
Do not use common grounding with heavy electrical systems.
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions. E
• Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise:
FX3U-4DA
- Do not bundle the power line or shield of the analog input/output cable together with or lay it close to the main
circuit, high-voltage line, or load line.
Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
100mm (3.94") or more away from the main circuit, high-voltage line, or load line.
- Ground the shield of the analog input/output cable at one point on the signal receiving side.
However, do not use common grounding with heavy electrical systems. F
• Make sure to properly wire to the terminal block (European type) in accordance with the following precautions.
FX3U-4DA-ADP
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
- The disposal size of the cable end should follow the dimensions described in the manual.
- Tightening torque should follow the specifications in the manual.
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends. G
- Do not connect more than the specified number of wires or electric wires of unspecified size.
FX3G-1DA-BD
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
D-11
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3G-2AD-BD (2-channel Analog Input) 3.1 Terminal Layout
D-12
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3G-2AD-BD (2-channel Analog Input) 3.2 Applicable Cables and Terminal Tightening Torque
A
3.2 Applicable Cables and Terminal Tightening Torque
Common Items
Use the following cables to connect with the counterpart equipment. Terminate the cable ends as shown
below.
1. Cables B
Applicable cable and tightening torque
FX3UC-4AD
FX3U-4AD
Wire size Tightening
Termination
(stranded wire/solid wire) torque
0.3 mm2 to 0.5 mm2 • To connect a stranded cable, peel the cover off the cable
Single-wire and then twist the core before connection.
(AWG22 to 20)
• To connect a single-wire cable, just strip the cover off the C
2-wire 0.3 mm2 (AWG22)×2 cable before connection.
FX3U-4AD-ADP
0.22 to • Ferrule with insulation sleeve
0.3 mm2 to 0.5 mm2 0.25 N•m (recommended terminal)
Ferrule with (AWG22 to 20) AI 0.5-8WH : Manufactured by Phoenix Contact
insulation (Refer to the external view • Caulking tool
sleeve of ferrule shown in the
following figure.)
CRIMPFOX 6*1 : Manufactured by Phoenix Contact
(or CRIMPFOX 6T-F*2 : Manufactured by Phoenix Contact)
D
FX3G-2AD-BD
*1. Old model name : CRIMPFOX ZA 3
*2. Old model name : CRIMPFOX UD 6
FX3U-4DA
Do not tighten terminal screws with a torque outside the above-mentioned range. Failure to do so may cause
equipment failures or malfunctions.
• To directly terminate the end of a stranded/single-wire cable: • Stranded wire/solid wire
- Twist the end of the stranded cable so that the "barbed wires"
cannot protrude. F
- Do not solder-plate the end of the cable.
FX3U-4DA-ADP
9mm
(0.35")
• To terminate cable end using a ferrule with insulation sleeve: • Ferrule with insulation sleeve
If the cable sheath is too thick, it may be difficult to insert the cable into Insulation sleeve Contact area
the insulation sleeve. For this reason, select an appropriate cable while (Crimp area) G
referring to the external view.
FX3G-1DA-BD
<Reference> 8mm (0.31")
Manufacturer Model Caulking tool 2.6mm 14mm
(0.1")
CRIMPFOX 6*3 (0.55")
Phoenix Contact AI 0.5-8WH
(or CRIMPFOX 6T-F*4)
H
*3. Old model name : CRIMPFOX ZA 3
FX3U-3A-ADP
3. Tool
For tightening the terminal, use a commercially available small screwdriver
The head
having a straight form that is not widened toward the end as shown right. should be
straight.
I
FX3U-4AD-PT
Note:
If the diameter of screwdriver grip is too small, tightening torque will not be
able to be achieved. To achieve the appropriate tightening torque shown in 0.4mm 2.5mm
-ADP
the table above, use the following screwdriver or an appropriate (0.01") (0.09")
replacement (grip diameter: approximately 25 mm (0.98")).
<Reference> J
Manufacturer Model
FX3U-4AD-PTW
D-13
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3G-2AD-BD (2-channel Analog Input) 3.3 Analog Input Line
*1 110kΩ ch
V +
250Ω
I + 88.7kΩ
Class-D
grounding
VI-
*3
*1. Use the 2-core shielded twisted pair cable for the analog input lines, and separate the analog input
lines from other power lines or inductive lines.
*2. If "current input" is selected, be sure to short the line between the V+ terminal and the I+ terminal.
(: Channel number).
*3. Make sure to short-circuit the "V+" and "VI-" terminals when ch is not used.
3.4 Grounding
Grounding should be performed as stated below.
• The grounding resistance should be 100 Ω or less.
• Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" as shown in the following
figure.
→ For details, refer to the User’s Manual - Hardware Edition of each PLC Series.
D-14
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3G-2AD-BD (2-channel Analog Input) 4.1 Loading of A/D Conversion Data
Common Items
4. Programming
This chapter describes how to create programs that can read analog data using the 2AD-BD. B
FX3UC-4AD
FX3U-4AD
4.1 Loading of A/D Conversion Data
1) The input analog data will be converted into digital data and then stored in the special devices of the
FX3S/FX3G Series PLC.
C
2) If the data is stored in the special devices, the averaging time can be set, and the input mode can be
FX3U-4AD-ADP
specified.
3) In the FX3G Series PLC (40-point or 60-point type), special auxiliary relays (10 points) and special data
registers (10 points) are assigned to each analog expansion board, board A and B connected to option
connector 1 and 2 respectively, in that order.
In the FX3G Series PLC (14-point or 24-point type) and FX3S Series PLC, special auxiliary relays (10
points) and special data registers (10 points) are assigned.
D
FX3G-2AD-BD
→ For a detailed description of special device assignment, refer to Section 4.2.
• FX3S Series PLC
FX3S Series PLC
Sequence Program
E
FX3U-4DA
Special auxiliary relays:
M8260 to M8269
Special data register:
D8260 to D8269
Option connector
F
FX3U-4DA-ADP
A/D
FX3G-2AD-BD
FX3G-1DA-BD
FX3G Series PLC
Sequence Program
A/D
FX3G-2AD-BD
A/D
FX3G-2AD-BD
I
FX3U-4AD-PT
The analog expansion board connected to option connector 1 is regarded as the "board A", and the analog
-ADP
D-15
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3G-2AD-BD (2-channel Analog Input) 4.2 List of Special Devices
D-16
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3G-2AD-BD (2-channel Analog Input) 4.3 Switching of Input Mode
A
4.3 Switching of Input Mode
Common Items
Turn the special auxiliary relay on/off to switch the input mode of 2AD-BD between the current input mode
and the voltage input mode. To switch the input mode, use the following special auxiliary relays:
• FX3S Series PLC
Special auxiliary relay Description
B
FX3UC-4AD
FX3U-4AD
M8260 Switches the input mode of channel 1 OFF: Voltage input
M8261 Switches the input mode of channel 2 ON: Current input
FX3U-4AD-ADP
M8260 M8270 Switches the input mode of channel 1 OFF: Voltage input
M8261 M8271 Switches the input mode of channel 2 ON: Current input
FX3G-2AD-BD
M8001 M8000
M8260 M8261
Normally OFF Normally ON
E
4.4 Input Data
FX3U-4DA
Numeric data type: Decimal (K)
The data converted by the 2AD-BD will be stored in the special data registers.
The special data registers that store the input data are shown in the following table:
• FX3S Series PLC F
FX3U-4DA-ADP
Special data register Description
D8260 Stores the channel-1 input data
D8261 Stores the channel-2 input data
FX3G-1DA-BD
Board A Board B
D8260 D8270 Stores the channel-1 input data
D8261 D8271 Stores the channel-2 input data
The converted A/D immediate data or averaged data (data average conforming to the specified averaging
time) will be stored in the above data registers as the input data. H
→ For a detailed description of the averaging time, refer to Section 4.5.
FX3U-3A-ADP
M8000
FNC 12 Stores the channel-1 input data
D8260 D100 of the board A in the D100.
Normally MOV
-ADP
ON
FNC 12
MOV
D8261 D101
Stores the channel-2 input data
of the board A in the D101. J
FX3U-4AD-PTW
Even if the input data is not stored in D100 or D101, data registers D8260 or D8261 can be directly used in
the timer/counter set value or in a PID instruction.
-ADP
D-17
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3G-2AD-BD (2-channel Analog Input) 4.5 Averaging Time
D-18
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3G-2AD-BD (2-channel Analog Input) 4.6 Error Status
A
4.6 Error Status
Common Items
If an error is detected in the 2AD-BD, the error status data will be stored in the corresponding special data
register.
The following table shows the special data registers that store the error status data:
• FX3S Series PLC B
FX3UC-4AD
FX3U-4AD
Special data register Description
D8268 Stores the error status data.
FX3U-4AD-ADP
D8268 D8278 Stores the error status data.
Check the ON/OFF status of each bit of the error status data register to check the description of the error.
Errors are assigned to the bits as shown in the following table. Create a program to detect errors.
→ For a detailed description of the error status, refer to Section 6.6. D
FX3G-2AD-BD
Bit Description Bit Description
b0 Channel-1 over-scale detection b6 2AD-BD hardware error
b1 Channel-2 over-scale detection b7 2AD-BD communication data error
b2 Unused b8 Channel-1 under-scale detection*1
E
b3 Unused b9 Channel-2 under-scale detection*1
FX3U-4DA
b4 EEPROM error b10 to b15 Unused
b5 Averaging time setting error - -
FX3U-4DA-ADP
1. Caution regarding use of error status data
If a 2AD-BD hardware error (b6) or 2AD-BD communication data error (b7) is detected, it is necessary to clear
the error status with a program at the next power-on of the PLC.
For this reason, be sure to create the following program:
• For FX3G Series PLC
G
FX3G-1DA-BD
M8000
FNC 12 D8268 K4M0
Normally ON MOV
M8002
Error status of board A
RST M6 b6 = OFF (2AD-BD hardware error)
Initial pulse H
FX3U-3A-ADP
FNC 12
K4M0 D8268
MOV
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
D-19
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3G-2AD-BD (2-channel Analog Input) 4.6 Error Status
M8000
FNC 12
D8268 K4M0
MOV
Normally
ON
M0
Y000 Detects over-scale in channel 1 of
the board A.
M1
Y001 Detects over-scale in channel 2 of
the board A.
M4
Y004 EEPROM error in board A.
M5
Y005 Averaging time setting error in
board A.
M6
Y006 2AD-BD hardware error in board A.
M7
Y007 2AD-BD communication data error in
board A.
D-20
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3G-2AD-BD (2-channel Analog Input) 4.7 Model Code
A
4.7 Model Code
Common Items
Initial value: K3
Numeric data type: Decimal (K)
When the 2AD-BD is connected, model code "3" is stored in the corresponding special data register.
The following table shows the special data registers that store the model code: B
• FX3S Series PLC
FX3UC-4AD
FX3U-4AD
Special data register Description
D8269 Model code
FX3U-4AD-ADP
Board A Board B
D8269 D8279 Model code
Use the special data registers above to check whether a 2AD-BD is connected or not.
1. Program Example (For FX3G Series PLC)
D
FNC224 Checks the model code of the
FX3G-2AD-BD
D8269 K3 Y007
LD= board A
FX3U-4DA
• For FX3G Series PLC
The following program will set the board A to voltage input mode and channel 2 to current input mode, and
will store the converted A/D value of channel-1 data into D100 and that of channel-2 data into D101.
M8001 Sets the input mode of the channel 1
M8260 to the voltage input mode
(0 V to 10 V).
F
Normally
FX3U-4DA-ADP
OFF
M8000 Sets the input mode of the channel 2
M8261 to the current input mode
Normally (4 mA to 20 mA).
ON
M8000 G
FNC 12 D8268 K4M0
FX3G-1DA-BD
Normally MOV
ON
M8002
RST M6 Error status: b6 = OFF
Initial
pulse H
RST M7 Error status: b7 = OFF
FX3U-3A-ADP
D8260 D100
Normally MOV channel-1 digital data into D100.
ON
FNC 12
MOV
D8261 D101 Stores the A/D converted J
channel-2 digital data into D101.
FX3U-4AD-PTW
Even if the input data is not stored into D100 or D101, the data registers D8260 or D8261 can be directly
used in the timer/counter setting value or in a PID instruction.
-ADP
D-21
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Changing of Input Characteristics
FX3G-2AD-BD (2-channel Analog Input) 5.1 Example: Changing of Voltage Input Characteristics
1. Input characteristics
Voltage input characteristics Digital output value to be changed
(product specifications) Y-axis
Digital output
4000 10000
Digital output to
be calculated
(D110)
2000
400
0 X-axis
1V 5V 10V 0 400(1V) 2000(5V)
Analog input
Digital value actually obtained
by A/D conversion
D-22
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
FX3G-2AD-BD (2-channel Analog Input) 6.1 PLC Version Number Check
Common Items
6. Troubleshooting
This chapter describes troubleshooting methods and error statuses. B
If the A/D conversion data is not input, or if the proper digital value is not input, check the following items:
FX3UC-4AD
FX3U-4AD
• PLC version number
• Installation
• Wiring
• Special devices
• Programs C
FX3U-4AD-ADP
• Error status
FX3G-2AD-BD
→ For a detailed description of the version check method,
refer to A. Common Items Subsection 5.1.2.
FX3U-4DA
the 2AD-BD is lit correctly.
For installation details, refer to the following manual.
→ Refer to FX3S Series User’s Manual - Hardware Edition.
→ Refer to FX3G Series User’s Manual - Hardware Edition.
F
6.3 Wiring Check
FX3U-4DA-ADP
Check the following items for wiring:
1. Analog input line
Use 2-core twisted shielded pair cable for the analog input line. In addition, be sure to separate the analog
input line from other power lines or inductive lines.
G
FX3G-1DA-BD
2. Use of current input mode
To use the current input mode for a channel, be sure to shortcircuit the line between the V+ terminal and the
I+terminal (: channel number) of the channel. If the line is not shortcircuited, data will not be converted
into proper digital data.
→ For a detailed description of wiring, refer to Chapter 3. H
FX3U-3A-ADP
Turn off the device to set the input mode to the voltage input mode. Turn on the device to set the input mode
to the current input mode.
2. Input data
-ADP
Verify that the special device of the selected channel is correctly selected. This special device should be
selected depending on the connecting position and the channel. J
3. Averaging time
FX3U-4AD-PTW
Check that the set averaging time is within the specified range. The averaging time should be set in the range
from 1 to 4095. If the set averaging time is outside the specified range, an error occurs.
-ADP
D-23
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
FX3G-2AD-BD (2-channel Analog Input) 6.5 Program Check
4. Error status
Check that no error is detected in the 2AD-BD.
If an error is detected, check the details of the error, and then check the wiring and programs.
→ For a detailed description of special devices, refer to Chapter 4.
D-24
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
FX3G-2AD-BD (2-channel Analog Input) 6.6 Error Status Check
A
4. 2AD-BD hardware error (b6)
Common Items
1) Description of error
The 2AD-BD is not operating properly.
2) Remedy
Check that the 2AD-BD is correctly connected to the PLC.
If the problem cannot be solved even after the above check, please contact your local Mitsubishi Electric B
representative.
FX3UC-4AD
FX3U-4AD
5. 2AD-BD communication data error (b7)
1) Description of error
A communication error is detected between the 2AD-BD and the PLC.
2) Remedy C
Check that the 2AD-BD is correctly connected to the PLC.
FX3U-4AD-ADP
If the problem cannot be solved even after the above check, please contact your local Mitsubishi Electric
representative.
FX3G-2AD-BD
This error is only detected for the current input mode, and indicates the input current is less than 2 mA.
2) Remedy
Check that the input analog value is within the specified range. Also check the wiring.
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
D-25
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
FX3G-2AD-BD (2-channel Analog Input) 6.6 Error Status Check
MEMO
D-26
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4DA (4-channel Analog Output)
Common Items
B
FX3UC-4AD
FX3U-4AD
FX3S/FX3G/FX3GC/FX3U/FX3UC Series
Programmable Controllers C
FX3U-4AD-ADP
User's Manual [Analog Control Edition]
FX3G-2AD-BD
E
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
Foreword
This manual describes the specifications, wiring, and operation methods for the FX3U-4DA special extension
block (4-channel analog output) and should be read and understood before attempting to install or use the I
FX3U-4AD-PT
unit.
Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
it to the end user.
-ADP
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property J
rights which may occur as a result of using the contents noted in this manual.
FX3U-4AD-PTW
E-1
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4DA (4-channel Analog Output)
E-2
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4DA (4-channel Analog Output) 1.1 Outline of Functions
Common Items
1. Outline
This chapter outlines the FX3U-4DA. B
FX3UC-4AD
FX3U-4AD
1.1 Outline of Functions
FX3U-4DA is an analog special function block which is connectable to the FX3G/FX3GC/FX3U/FX3UC Series
PLC to convert 4-channel digital signal from the PLC to analog signal (voltage/current).
C
1) Up to 8*1 units can be connected to the FX3G/FX3GC/FX3U/FX3UC Series PLC.
FX3U-4AD-ADP
(including the other special function blocks).
2) Each channel has either voltage output or current output specification.
3) The block converts the digital values stored in the FX3U-4DA buffer memory (BFM) in FX3U-4DA to
analog signals (voltage/current).
4) A predetermined output pattern is set as data table, and analog signal can be output according to the
D
FX3G-2AD-BD
data table.
FX3U-4DA
FX3G/FX3U Series PLC
24V
FX3U -4DA
24V
Section 1.3. F
FX3U-4DA-ADP
D/A D/A
FX3G-1DA-BD
For a detailed description of
analog data output programs,
refer to Chapter 4, 7, and 8.
For a detailed description of
Program
Transmission direction Buffer memory the buffer memory, refer to
Section 5.3, and Section 5.4.
FROM (FNC 78)
TO (FNC 79) BFM#0
To use FROM/TO instruction
H
Refer to the system configuration shown in the FX3G/FX3GC/FX3U/FX3UC User's Manual - Hardware Edition to
check the number of connectable units and to configure the entire system.
*1. Up to 7 units can be connected to the FX3UC-32MT-LT(-2) PLC. I
FX3U-4AD-PT
J
FX3U-4AD-PTW
-ADP
E-3
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4DA (4-channel Analog Output) 1.2 Setup Procedure Before Starting Operation
FX3U-4DA
Refer to Chapter 1.
Wiring Wiring:
Power supply line
Analog output line
Refer to Chapter 4.
Refer to Chapter 8.
E-4
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4DA (4-channel Analog Output) 1.3 Connectable PLCs and Version Number
A
1.3 Connectable PLCs and Version Number
Common Items
FX3U-4DA is compatible with the following PLC.
Compatible PLC Version number Date of production
FX3G Series PLC Ver. 1.00 or later After June 2008 (From first product)
B
FX3GC Series PLC Ver. 1.40 or later After January 2012 (From first product)
FX3UC-4AD
FX3U-4AD
FX3U Series PLC Ver. 2.20 or later After May 2005 (From first product)
FX3UC Series PLC Ver. 1.30 or later After August 2004
1. Version check
The PLC version can be checked by reading the last three digits of device D8001 or D8101. C
→ For a detailed description of the version check,
FX3U-4AD-ADP
refer to A. Common Items Subsection 5.1.2.
FX3G-2AD-BD
1.4 Compatible Programming Tool Version Number
The following programming tools and versions are applicable for the FX3G/FX3GC/FX3U/FX3UC series.
E
FX3U-4DA
1. English versions
Model name Media model name Applicable version Remarks
FX3G PLC
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer SWD5C-GPPW-E Ver. 8.72A or later -
F
FX-30P Ver. 1.00 or later
FX3U-4DA-ADP
FX3GC PLC
GX Works2 SWDNC-GXW2-E Ver. 1.77F or later
-
FX-30P Ver. 1.30 or later
FX3U and FX3UC PLCs
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later G
GX Developer SWD5C-GPPW-E Ver. 8.18U or later -
FX3G-1DA-BD
FX-30P Ver. 1.00 or later
2. Japanese versions
Model name Media model name Applicable version Remarks
FX3G PLC H
FX3U-3A-ADP
Point
• It is possible to create programs in FX3GC PLC using programming tools of inapplicable versions by
-ADP
E-5
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4DA (4-channel Analog Output) 2.1 Generic Specifications
2. Specifications
This chapter describes the general, power supply, and performance specifications for the FX3U-4DA.
Item Specifications
Ambient 0 to 55 °C (32 to 131 °F) when operating
temperature -25 to 75 °C (-13 to 167 °F) when stored
Relative
5 to 95 %RH (no condensation) when operating
humidity
Frequency Acceleration Half amplitude
(Hz) (m/s2) (mm)
Tests 10 times in each
Vibration 10 to 57 - 0.035 direction (X-, Y-, and Z-
DIN Rail Mounting
resistance*1 57 to 150 4.9 - axis directions) (Total:
80 min, each)
10 to 57 - 0.075
Direct Mounting*2
57 to 150 9.8 -
Shock
147 m/s2 Acceleration, Action time: 11 ms, 3 times by half-sine pulse in each direction X, Y, and Z
resistance*1
Noise Using noise simulator of:
resistance Noise voltage: 1,000 Vp-p / Noise width: 1 μs / Rise: 1 ns / Cycle: 30 to 100 Hz
Dielectric
withstand 500 V AC, for 1 min
voltage Between batch of all terminals and ground terminal
Insulation 5 MΩ or more using 500 V DC
resistance insulation resistance meter
Class D grounding (grounding resistance: 100 Ω or less)
Grounding
<Common grounding with a heavy electrical system is not allowed.>*3
Working
Free from corrosive or flammable gas and excessive conductive dusts
environment
Working
altitude < 2000 m*4
E-6
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4DA (4-channel Analog Output) 2.2 Power Supply Specifications
A
2.2 Power Supply Specifications
Common Items
Item Specifications
D/A conversion 24 V DC ±10 %, 160 mA B
circuit drive power (It is necessary to supply 24 V DC from the terminal block.)
FX3UC-4AD
FX3U-4AD
5 V DC, 120 mA
CPU drive power (Since the internal power is supplied from the main unit, it is not necessary to supply power
externally.)
FX3U-4AD-ADP
2.3 Performance Specifications
Item
Specifications
D
Voltage output Current output
FX3G-2AD-BD
Analog output -10 V to +10 V DC 0 mA to 20 mA DC, 4 mA to 20 mA DC
range (External load: 1 kΩ to 1 MΩ) (External load: 500 Ω or less)
Offset*1 -10 V to +9 V*2 0 mA to 17 mA*3
Gain*1 -9 V to +10 V*2 3 mA to 30 mA*3
E
Digital input With sign, 16bits, binary 15bits, binary
FX3U-4DA
Resolution 0.32 mV (20 V / 64,000) 0.63 μA (20 mA / 32,000)
• Ambient temperature: 25 °C±5 °C • Ambient temperature: 25 °C±5 °C
±0.3 % (±60 mV) for 20 V full scale ±0.3 % (±60 μA) for 20 mA full scale
Overall accuracy*4
• Ambient temperature: 0 °C to 55 °C • Ambient temperature: 0 °C to 55 °C
±0.5 % (±100 mV) for 20 V full scale ±0.5 % (±100 μA) for 20 mA full scale F
Time required for
FX3U-4DA-ADP
1 ms (The number of selected channels will not affect this value.)
D/A conversion
• The photocoupler is used to insulate the analog output area from the PLC.
Insulation method • The DC/DC converter is used to insulate the analog output area from the power supply unit.
• Channels are not insulated from each other.
Number of I/O
8 points (Taken from either the input or output points of the PLC.)
G
points occupied
FX3G-1DA-BD
*1. Adjustment of the offset or gain value will not affect the resolution. In output mode 1 or 4, however, the
offset/gain cannot be adjusted.
*2. The offset and the gain should satisfy the following condition:
1 V ≤ (Gain - Offset) ≤ 10 V
H
*3. The offset and the gain should satisfy the following condition:
FX3U-3A-ADP
3 mA ≤ (Gain - Offset) ≤ 30 mA
*4. When the external load is less than 30 kΩ, please use the output corrective function by load resistance.
→ For a detailed description of the output corrective function by load resistance,
refer to Subsection 5.4.17.
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
E-7
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4DA (4-channel Analog Output) 2.4 Output Mode (Characteristics) BFM#0
10200
-32000 0 -10000 0
-32640
-10200
32000 10000
-10 -10
-10.2 -10.2
Current Current
output (mA) output (mA)
20.4 20.4
20 20
Current
output (mA)
20.32
20
4
0 32000 32640
Digital value
E-8
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4DA (4-channel Analog Output)
Common Items
3. Wiring
This chapter describes wiring of the FX3U-4DA. B
Observe the following cautions wiring the FX3U-4DA.
FX3UC-4AD
FX3U-4AD
WIRING PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before attempting wiring work.
Failure to do so may cause electric shock or damage to the product. C
FX3U-4AD-ADP
WIRING PRECAUTIONS
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn
out.
D
FX3G-2AD-BD
• Do not wire vacant terminals externally.
Doing so may damage the product.
• Perform class D grounding (grounding resistance: 100Ω or less) to the grounding terminal on the main unit.
Do not use common grounding with heavy electrical systems.
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions. E
• Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise:
FX3U-4DA
- Do not bundle the power line or shield of the analog input/output cable together with or lay it close to the main
circuit, high-voltage line, or load line.
Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
100mm (3.94") or more away from the main circuit, high-voltage line, or load line.
- Ground the shield of the analog input/output cable at one point on the signal receiving side.
However, do not use common grounding with heavy electrical systems. F
• Make sure to properly wire the terminal block in accordance with the following precautions.
FX3U-4DA-ADP
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
- The disposal size of the cable end should follow the dimensions described in the manual.
- Tightening torque should follow the specifications in the manual.
- Tighten the screws using a Phillips-head screwdriver No.2 (shaft diameter 6mm (0.24") or less).
Make sure that the screwdriver does not touch the partition part of the terminal block. G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
E-9
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4DA (4-channel Analog Output) 3.1 Terminal Layout
Signal Application
24+
24 V DC power supply
24-
Ground terminal
V+
VI- Channel-1 analog output
I+
Do not connect any lines.
V+
VI- Channel-2 analog output
I+
Do not connect any lines.
V+
VI- Channel-3 analog output
I+
Do not connect any lines.
V+
VI- Channel-4 analog output
I+
φ3.2 (0.13")
6.2 mm (0.24") Terminal
or less
E-10
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4DA (4-channel Analog Output) 3.3 Wiring to Power Supply Terminals
A
3.3 Wiring to Power Supply Terminals
Common Items
3.3.1 Examples of Power Supply Circuit
Below are examples of circuits for using the 24 V DC service power supply of the FX3G/FX3U Series PLC. B
1) Sink input [- common] wiring
FX3UC-4AD
FX3U-4AD
AC power
100 to 240 V
FX3U-4AD-ADP
Class-D
grounding
L N S/S 0V 24V 24+ 24-
+15V
D
FX3G-2AD-BD
FX3G/FX3U Series PLC
(main unit) -15V
FX3U-4DA
Connect the "S/S" terminal of the main unit to the "24V" terminal. E
FX3U-4DA
2) Source input [+ common] wiring
AC power
100 to 240 V F
FX3U-4DA-ADP
Class-D
grounding
L N S/S 0V 24V 24+ 24-
G
FX3G-1DA-BD
+15V
Connect the "S/S" terminal of the main unit to the "0V" terminal.
• Ground the " " terminal and " " terminal to the Class - D grounding line (100 Ω or less) together
with the ground terminal of the main unit.
-ADP
• For the timing of power-on/off when using an external power supply, see the following manual of the
connected PLC.
→ Refer to the FX3G Series User's Manual - Hardware Edition. J
→ Refer to the FX3GC Series User's Manual - Hardware Edition.
FX3U-4AD-PTW
E-11
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4DA (4-channel Analog Output) 3.4 Analog Output Wiring
Class-D grounding
*2
If voltage output is
selected
ch
Shield *3
V+
I+ ch
Class-D VI-
*4 grounding *5
If current output is
selected ch
Shield *3 V+
I+ ch
VI-
Class-D
grounding *5
ch : represents the channel number.
*1. For FX3G/FX3U Series PLC (AC power type), the 24 V DC service power supply is also available.
*2. Do not connect any wires to the " • " terminal.
*3. Use a 2-core twisted shield wire for analog output wire, and separate it from other power lines or
inductive lines.
*4. If there is ripple or noise in the output voltage, connect a capacitor of approximately 0.1 to 0.47 μF
25 V in the vicinity of the signal receiving side.
*5. Ground the shielded wire at one point on the signal receiving side.
3.5 Grounding
Grounding should be performed as stated below.
• The grounding resistance should be 100 Ω or less.
• Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" as shown in the following
figure.
→ For details, refer to the User’s Manual - Hardware Edition of each PLC Series.
E-12
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Analog Output
FX3U-4DA (4-channel Analog Output) 4.1 Analog Output Procedures
Common Items
4. Analog Output
This chapter describes the minimum programming necessary for analog output by the FX3U-4DA. B
Follow the procedure below to confirm that correct analog values can be output.
FX3UC-4AD
FX3U-4AD
4.1 Analog Output Procedures
FX3U-4AD-ADP
Unit numbers from 0 to 7 will be assigned to the special function units/blocks starting from the left.
When the units/blocks are connected to the FX3UC-32MT-LT(-2) PLC, the unit numbers from 1 to 7
are assigned. Check the unit number assigned to the FX3U-4DA.
FX3G-2AD-BD
Main unit Input/output Special Special Input/output Special
(FX3U Series extension function block function block extension function unit
PLC) block block
E
FX3U-4DA
2 Output mode (BFM#0) setting
Depending on the analog signal generator to be connected, set the output mode (BFM#0) for each
channel.
F
FX3U-4DA-ADP
Use hexadecimal numbers for output mode setting. Set the corresponding channel digit to the
output mode setting value specified in the following table:
H G
ch4 ch1
FX3G-1DA-BD
ch3 ch2
Setting
Output mode Analog output range Digital input range
value
0 Voltage output mode -10 V to +10 V -32000 to +32000 H
FX3U-3A-ADP
Voltage output
1 -10 V to +10 V -10000 to +10000
analog value mV specification mode
2 Current output mode 0 mA to 20 mA 0 to 32000
3 Current output mode 4 mA to 20 mA 0 to 32000
4
Current output
0 mA to 20 mA 0 to 20000
I
analog value μA specification mode
FX3U-4AD-PT
→ For a detailed description of the output mode (BFM#0), refer to Subsection 5.4.1.
J
FX3U-4AD-PTW
-ADP
E-13
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Analog Output
FX3U-4DA (4-channel Analog Output) 4.1 Analog Output Procedures
T0
FNC 15 Data (BFM#1 to 4) to be output to channels 1
D0 U\G1 K4 to 4 are transferred from D0 to D3.
BMOV
E-14
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.1 Assignment of Unit Numbers and Outline of Buffer Memory
Common Items
5. Buffer Memory (BFM)
This chapter describes the buffer memory incorporated in FX3U-4DA. B
FX3UC-4AD
FX3U-4AD
5.1 Assignment of Unit Numbers and Outline of Buffer Memory
FX3U-4AD-ADP
When connected to the FX3G/FX3GC/FX3U/FX3UC (D, DS, DSS) Series PLC
Unit Unit Unit
number: 0 number: 1 number: 2
D
FX3G-2AD-BD
Input/output Special Special Input/output Special
Main unit extension function block function block extension function unit
block block
E
When connected to the FX3UC-32MT-LT(-2) PLC
FX3U-4DA
Unit number: 0
(Incorporated Unit Unit Unit
CC-Link/LT) number: 1 number: 2 number: 3
F
Main unit Input/output Input/output
FX3U-4DA-ADP
(FX3UC-32MT extension Special Special extension Special
-LT(-2)) block function block function block block function unit
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
E-15
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.1 Assignment of Unit Numbers and Outline of Buffer Memory
*1. Since buffer memory direct specification (U\G) can directly specify the buffer memory in the
source or destination area of an applied instruction, programs can be created efficiently. (This function
is supported only in FX3U/FX3UC PLCs.)
→ For a detailed description of buffer memory reading/writing, refer to Section 5.2.
→ For a detailed description of the buffer memory, refer to Section 5.4.
E-16
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.2 Buffer Memory Reading/Writing Method
A
5.2 Buffer Memory Reading/Writing Method
Common Items
To read or write the buffer memory of FX3U-4DA, use FROM/TO instructions or the buffer memory direct
specification function*1.
To use the buffer memory direct specification function*1, however, it is necessary to adopt the software
compatible with the PLC. B
*1. This function is supported only in FX3U/FX3UC PLCs.
FX3UC-4AD
FX3U-4AD
→ For a detailed description of the software compatible with the PLC,
refer to Section 1.4.
FX3U-4AD-ADP
U\G Enter a numeric value in
Unit number (0 to 7) Buffer memory number (0 to 32766)
1. Example 1 D
If the following program is created, data in buffer memory (BFM#10) of unit 1 will be multiplied by the data
FX3G-2AD-BD
(K10), and then the multiplication result will be output to the data registers (D10, D11).
READ command
FNC 22 U1\G10 K10 D10
MUL
Unit number
Multiplication result E
FX3U-4DA
Buffer memory number Multiplier
2. Example 2
If the following program is created, the value in the data register (D20) is added to K10 and written to buffer
memory (BFM#6) of unit 1.
WRITE command
FNC 20
F
D20 K10 U1\G6
FX3U-4DA-ADP
ADD
Addition Unit number
result Buffer memory number
Augend Addend
FX3G-1DA-BD
1. FROM instruction (Reading out BFM data to PLC)
Use FROM instruction to read out the data from the buffer memory.
In a sequence program, use this instruction as follows:
READ command
FNC 78 K1 K10 D10 K1 H
FROM
FX3U-3A-ADP
Number of transfer
Unit number data points
Buffer memory number Transfer-to register
If the above program is created, 1 point of data will be read out from the buffer memory BFM#10 of unit No.1
to the data register (D10). I
2. TO instruction (Writing PLC data into BFM)
FX3U-4AD-PT
WRITE command
FNC 79 K1 K0 H3300 K1
TO J
Number of transfer
FX3U-4AD-PTW
E-17
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.3 Buffer Memory List (BFM)
BFM number Description Setting range Initial value Data type Reference
Hexadeci- Subsection
#0*1 Output mode setting for channels 1 to 4 *2 H0000 at delivery
mal 5.4.1
#1 Channel 1 output data K0 Decimal
#2 Channel 2 output data Depending on the K0 Decimal Subsection
#3 Channel 3 output data mode used K0 Decimal 5.4.2
#11*1 Channel-2 offset data (Unit: mV or μA) Depending on the Depending on Decimal Subsection
mode used the mode used 5.4.6
#12*1 Channel-3 offset data (Unit: mV or μA) Decimal
*1. If power failure occurs, the EEPROM will retain the data.
*2. Specify the output mode of each channel setting one of hex code 0 to 4 and F in each digit.
*3. Specify the data to be output from each channel upon PLC stop setting one of hex code 0 to 2 in each
digit.
*4. Use b0 to b3.
E-18
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.3 Buffer Memory List (BFM)
Common Items
BFM number Description Setting range Initial value Data type Reference
Data to be output from channel 1 upon PLC stop Depending on the
#32*1 (Valid only if BFM#5 = H2) mode used
K0 Decimal
#33*1
Data to be output from channel 2 upon PLC stop Depending on the
K0 Decimal B
(Valid only if BFM#5 = H2) mode used Subsection
FX3UC-4AD
FX3U-4AD
Data to be output from channel 3 upon PLC stop Depending on the 5.4.12
#34*1 (Valid only if BFM#5 = H2) mode used
K0 Decimal
FX3U-4AD-ADP
#38 Upper/lower limit function setting *2 H0000
mal 5.4.13
Hexadeci- Subsection
#39 Upper/lower limit function status - H0000
mal 5.4.14
Hexadeci- Subsection
#40 Clear of upper/lower limit function status *3 H0000
FX3G-2AD-BD
#42 Channel-2 lower limit of upper/lower limit function Depending on the K-32640 Decimal Subsection
#43 Channel-3 lower limit of upper/lower limit function mode used K-32640 Decimal 5.4.16
FX3U-4DA
#47 Channel-3 upper limit of upper/lower limit function mode used K32640 Decimal 5.4.16
#48 Channel-4 upper limit of upper/lower limit function K32640 Decimal
#49 Not used - - - -
Corrective function setting by load resistance Hexadeci- Subsection
#50*1 *4 H0000
(Valid only in voltage output mode) mal 5.4.17
F
#51*1 Load resistance value for channel 1 (Unit: Ω) K1000 to K30000 K30000 Decimal
FX3U-4DA-ADP
#52*1 Load resistance value for channel 2 (Unit: Ω) K1000 to K30000 K30000 Decimal Subsection
5.4.17
#53*1 Load resistance value for channel 3 (Unit: Ω) K1000 to K30000 K30000 Decimal
#54*1 Load resistance value for channel 4 (Unit: Ω) K1000 to K30000 K30000 Decimal
#55 to #59 Not used - - - - G
Subsection
FX3G-1DA-BD
#60*1 Status automatic transfer function setting *5 K0 Decimal
5.4.18
Error status data (BFM#29) automatic transfer-
Subsection
#61*1 to data register specification (Valid if b0 of K200 Decimal
5.4.19
BFM#60 is set to ON)
K0 to 7999
#62 *1
Upper/lower limit function status data (BFM#39)
automatic transfer-to data register specification
(BFM#61, #62 and
K201 Decimal
Subsection H
#63 must have 5.4.20
FX3U-3A-ADP
*1. If power failure occurs, the EEPROM will retain the data.
I
FX3U-4AD-PT
*2. Specify the use of the upper/lower limit function for each channel setting one of hex code 0 to 2 in
each digit.
*3. Use b0 to b1.
-ADP
*4. Specify the use of the corrective function by load resistance for each channel setting a hex code 0 or
1 in each digit. J
FX3U-4AD-PTW
E-19
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.3 Buffer Memory List (BFM)
BFM number Description Setting range Initial value Data type Reference
Hexadeci-
#80 Start/stop of table output function *1 H0000
mal
#81 Channel-1 output pattern K1 to K10 K1 Decimal
#82 Channel-2 output pattern K1 to K10 K1 Decimal
#83 Channel-3 output pattern K1 to K10 K1 Decimal
#84 Channel-4 output pattern K1 to K10 K1 Decimal
Number of times of output execution of table
#85 K0 to K32767 K0 Decimal
from channel 1
Number of times of output execution of table Chapter 6
#86 K0 to K32767 K0 Decimal
from channel 2
Number of times of output execution of table
#87 K0 to K32767 K0 Decimal
from channel 3
Number of times of output execution of table
#88 K0 to K32767 K0 Decimal
from channel 4
Hexadeci-
#89 Output completion flag of table output function - H0000
mal
#90 Table output error code - K0 Decimal
#91 Table output error occurrence number - K0 Decimal
#92 to #97 Not used - - - -
#98 Head device number in data table K0 to K32767 K1000 Decimal
Hexadeci-
#99 Data table transfer command *2 H0000 Chapter 6
mal
#100 to #398 Data table in pattern 1 - K0 Decimal
#399 Not used - - - -
#400 to #698 Data table in pattern 2 - K0 Decimal Chapter 6
#699 Not used - - - -
#700 to #998 Data table in pattern 3 - K0 Decimal Chapter 6
#999 Not used - - - -
#1000 to
Data table in pattern 4 - K0 Decimal Chapter 6
#1298
#1299 Not used - - - -
#1300 to
Data table in pattern 5 - K0 Decimal Chapter 6
#1598
#1599 Not used - - - -
#1600 to
Data table in pattern 6 - K0 Decimal Chapter 6
#1898
#1899 Not used - - - -
#1900 to
Data table in pattern 7 - K0 Decimal Chapter 6
#2198
#2199 Not used - - - -
#2200 to
Data table in pattern 8 - K0 Decimal Chapter 6
#2498
#2499 Not used - - - -
#2500 to
Data table in pattern 9 - K0 Decimal Chapter 6
#2798
#2799 Not used - - - -
#2800 to
Data table in pattern 10 - K0 Decimal Chapter 6
#3098
*1. Specify whether to start or stop the table output function for each channel setting a hex code 0 or 1
in each digit.
*2. Specify the data table transfer command and the register type setting 0 or 1 in the last two digits of
the hex code.
E-20
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.4 Buffer Memory Details
A
5.4 Buffer Memory Details
Common Items
5.4.1 BFM#0: Output mode specification
FX3UC-4AD
FX3U-4AD
Specify the output modes of channel 1 to 4.
4 hexadecimal digits are assigned to specify the output modes of the 4 channels.
Change the value of each digit to change the output mode of each channel. 0 to 4 and F can be set for each
digit.
C
H
FX3U-4AD-ADP
ch4 ch1
ch3 ch2
The different types of output modes are shown in the following table:
→ For a detailed description of output characteristics, refer to Section 2.4. D
FX3G-2AD-BD
Set value
Output mode Analog output range Digital input range
[HEX]
0 Voltage output mode -10 V to +10 V -32000 to +32000
Voltage output
1*1 -10 V to +10 V -10000 to +10000
analog value mV specification mode E
2 Current output mode 0 mA to 20 mA 0 to 32000
FX3U-4DA
3 Current output mode 4 mA to 20 mA 0 to 32000
Current output
4*1 analog value μA specification mode
0 mA to 20 mA 0 to 20000
5 to E
F
Invalid (setting values unchanged)
Channel not used
- -
F
FX3U-4DA-ADP
*1. The offset/gain values cannot be changed.
1. Cautions regarding output mode setting
• While the output mode is being changed, the output is stopped, and H0000 is automatically written in the
output status (BFM#6).
At the completion of change of the output mode, the output status (BFM#6) will automatically change to G
FX3G-1DA-BD
H1111, and the output is restarted.
• It takes approximately 5 seconds to determine the output mode.
For this reason, after changing the output mode, be sure to wait for 5 seconds or more, and then write the
other data.
• When the output mode is changed, the settings in the following buffer memory are initialized according to
the new output mode. H
- BFM#5 (output setting upon PLC stop)*2
FX3U-3A-ADP
*4 These settings are initialized only when the output mode is changed from current output mode
(mode 2, 3 or 4) to voltage output mode (mode 0 or 1).
-ADP
E-21
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.4 Buffer Memory Details
Initial value: K0
Numeric data type: Decimal (K)
Input the digital values corresponding to the analog signals to be output in BFM#1 to #4.
It is possible to set the output conditions from channel 1 to 4 when the PLC is in the stopped state.
H
ch4 ch1
ch3 ch2
E-22
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.4 Buffer Memory Details
A
5.4.4 BFM#6: Output status
Common Items
Initial value: H0000
Numeric data type: Hexadecimal (H)
FX3UC-4AD
FX3U-4AD
H
ch4 ch1
ch3 ch2
C
FX3U-4AD-ADP
Value status (HEX) Description
0 Output updating is stopped.*1
1 Under output updating
*1. The output conditions conform to the output setting upon PLC stop (BFM#5). D
FX3G-2AD-BD
1. Cautions regarding use of output status
• The output status setting is valid only if the PLC is running.
When the PLC is stopped, H0000 is automatically written.
• When the setting in any of the following buffer memory areas is changed, output updating is stopped.
H0000 is automatically written in BFM#6. E
- BFM#0 (Output mode setting)
FX3U-4DA
- BFM#5 (Output setting upon PLC stop)
- BFM#9 (Offset/gain setting value write command)
- BFM#19 (Setting change prohibition)
- BFM#20 (Initialization function)
- BFM#32 to #35 (Data to be output from each channel upon PLC stop) F
FX3U-4DA-ADP
- BFM#50 (Corrective function setting by load resistance)
- BFM#51 to #54 (Load resistance for each channel)
- BFM#60 (Status automatic transfer function Setting)
- BFM#61 (Error status data automatic transfer-to data register specification)
- BFM#62 (Upper/lower limit function status with automatic transfer to specified data register) G
- BFM#63 (Disconnection detection status with automatic transfer to data register specification)
FX3G-1DA-BD
- BFM#99 (Data table transfer command)
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
E-23
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.4 Buffer Memory Details
The WRITE command can be given to two or more channels at the same time. (Set "H000F" to write the data
of all the channels in the EEPROM.)
On completion of writing, "H0000" (b0 to b3: OFF) will be set automatically.
E-24
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.4 Buffer Memory Details
A
5.4.6 BFM#10 to #13: Offset data/BFM#14 to #17: Gain data
Common Items
Setting range: See below
Initial value: See below
Numeric data type: Decimal (K)
If the output mode is specified in BFM#0, the initial value of the offset data and gain data of each channel will
B
FX3UC-4AD
FX3U-4AD
be automatically stored.
The initial offset data and the gain data are set for each mode as shown in the following table:
• Offset data: Analog output value when the output data in BFM#1 to #4 are 0 (reference offset value)
• Gain data: Analog output value when the output data in BFM#1 to #4 are the reference gain values (The
reference gain value depends on the set output mode.) C
FX3U-4AD-ADP
1. Reference offset/gain value and initial value set
Offset (channels 1 to 4: Gain (channels 1 to 4:
Output mode (BFM#0)
BFM#10 to #13) BFM#14 to #17)
Reference Reference
Set value Description Initial value Initial value
value value D
Voltage output
FX3G-2AD-BD
0 0 0 mV 16000 5000 mV
(-10 V to +10 V: -32000 to +32000)
Voltage output Analog value mV 0 0 mV 5000 5000 mV
1 specification mode (Data change (Data change (Data change (Data change
(-10 V to +10 V: -10000 to +10000) impossible) impossible) impossible) impossible)
2
Current output
0 0 μA 16000 10000 μA E
(0 mA to 20 mA: 0 to 32000)
FX3U-4DA
Current output
3 0 4000 μA 16000 12000 μA
(4 mA to 20 mA: 0 to 32000)
Current output Analog value μA 0 0 μA 10000 10000 μA
4 specification mode (Data change (Data change (Data change (Data change
(0 mA to 20 mA: 0 to 20000) impossible) impossible) impossible) impossible) F
FX3U-4DA-ADP
2. Offset/gain data change
Set offset data and gain data to change the output characteristics.
The offset and gain data can be set for each channel. If the voltage output mode is set, write the offset and
gain data in mV. If the current output mode is set, write the offset and gain data in μA.
To change the offset or gain data, execute the offset/gain setting value write command (BFM#9).
The setting range is shown in the following table. G
FX3G-1DA-BD
Voltage output (mV) Current output (μA)
Offset data -10000 to +9000*1 0 to 17000*2
Gain data -9000 to +10000*1 3000 to 30000*2
*1. The offset and gain values should meet the following conditions:
H
FX3U-3A-ADP
• The offset and gain data should be set before the value write command BFM#9 is executed.
• The resolution cannot be increased by changing the output characteristics.
-ADP
• When the value specified as the output mode (BFM#0) is changed, the initial value of offset and gain data
in each output mode will be automatically written.
• Even if the output characteristics are changed, the actual valid output range will not be changed:
J
FX3U-4AD-PTW
-10 V to +10 V for the voltage output mode, and 0 mA to 20 mA in the current output mode.
→ For a detailed description of output characteristics change, refer to Chapter 7.
-ADP
E-25
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.4 Buffer Memory Details
Specify the following value as the setting change prohibition mode (BFM#19).
E-26
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.4 Buffer Memory Details
A
5.4.8 BFM#20: Initialization function (resetting to factory default status)
Common Items
Setting range: K0 or K1
Initial value: K0
Numeric data type: Decimal (K)
When K1 is set in BFM#20, all functions and all buffer memory (BFM#0 to #3098) will be initialized to the B
default status.
FX3UC-4AD
FX3U-4AD
When BFM#20 is not K0 or K1, this function is invalid. (The settings will not be changed, and the functions will
not be initialized.)
FX3U-4AD-ADP
output will be restarted.
• It takes approximately 5 seconds to initialize all the data. Do not set (write) data in the buffer memory
during this period.
• Priority is given to the setting of the value change prohibition mode (BFM#19).
• At the completion of initialization, the value of BFM#20 will automatically change to K0. D
FX3G-2AD-BD
5.4.9 BFM#28: Disconnection detection status (only in current output mode)
Initial value: H0000
Numeric data type: Hexadecimal (H) E
When a wire-break is detected, the bit corresponding to the relevant channel will turn on.
FX3U-4DA
1. Assignment to each bit of BFM#28
FX3U-4DA-ADP
b2 Wire-break in channel 3
b3 Wire-break in channel 4
b4 to b15 Not used
FX3G-1DA-BD
• When any of b0 to b3 is turned on, b11 of the error status (BFM#29) is turned on.
• The disconnection detection status is valid only if the output mode (BFM#0) is the current output mode
(mode 2 to 4). In other output modes, each corresponding bit of BFM#28 stays off.
• The disconnection detection status data automatic transfer function is not supported when connected and
used with the FX5U or FX5UC CPU module. H
FX3U-3A-ADP
J
FX3U-4AD-PTW
-ADP
E-27
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.4 Buffer Memory Details
E-28
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.4 Buffer Memory Details
A
5.4.11 BFM#30: Model code
Common Items
Initial value (at delivery): K3030
Numeric data type: Decimal (K)
K3030 (fixed value) is stored as the model code.
B
FX3UC-4AD
FX3U-4AD
5.4.12 BFM#32 to #35: Data to be output upon PLC stop
Initial value: K0
Numeric data type: Decimal (K)
To enable the output data set when the PLC stops, Set "2" for any digit in the output data (H0000) at PLC's C
stop. Set the BFM values as follows.
FX3U-4AD-ADP
BFM number Description
#32 Data in channel 1
#33 Data in channel 2
#34 Data in channel 3 D
#35 Data in channel 4
FX3G-2AD-BD
The setting range depends on the output mode.
FX3U-4DA
2, 3 0 to 32640
4 0 to 20400
F
1. Cautions regarding data output setting when PLC is in stop
FX3U-4DA-ADP
• While changing the settings, the output is stopped, and H0000 is automatically written in the output status
(BFM#6).
After the completion of writing, the output status (BFM#6) will automatically change to H1111, and output
will be restarted.
• The analog values to be output depend on the output mode. G
FX3G-1DA-BD
• When a value out of any of the above ranges is set, b5 of the error status (BFM#29) is turned on.
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
E-29
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.4 Buffer Memory Details
H
ch4 ch1
ch3 ch2
*1. When any value becomes less than the lower limit (BFM#41 to #44) or more than the upper limit
(BFM#45 to #48), the relevant bit of the upper/lower limit function status is turned on.
Upper limit
Lower limit
The value is output even if it is
below the lower limit.
*2. When any value becomes less than the lower limit (BFM#41 to #44) or more than the upper limit
(BFM#45 to #48), the relevant bit of the upper/lower limit function status is turned on.
In this setting, analog values more than the upper limit and less than the lower limit are not output.
Analog value Values more than the upper limit are not
output.
Upper limit
Lower limit
Values less than the lower limit are
not output.
E-30
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.4 Buffer Memory Details
A
5.4.14 BFM#39: Upper/lower limit function status
Common Items
Initial value: H0000
Numeric data type: Hexadecimal (H)
When any of the output data (BFM#1 to #4) is out of range between the lower limit and the upper limit
(BFM#41 to #48), the relevant bit is turned on. B
FX3UC-4AD
FX3U-4AD
1. Assignment to each bit of BFM#39
Bit Description
b0 Data output from channel 1 < Lower limit (BFM#41)
b1 Data output from channel 1 > Upper limit (BFM#45) C
b2 Data output from channel 2 < Lower limit (BFM#42)
FX3U-4AD-ADP
b3 Data output from channel 2 > Upper limit (BFM#46)
b4 Data output from channel 3 < Lower limit (BFM#43)
b5 Data output from channel 3 > Upper limit (BFM#47)
b6 Data output from channel 4 < Lower limit (BFM#44) D
b7 Data output from channel 4 > Upper limit (BFM#48)
FX3G-2AD-BD
b8 to b15 Not used
FX3U-4DA
• The upper/lower limit function status can be reset by the following methods.
- Use the upper/lower limit function status reset function (BFM#40).
- Turn the power supply off then on.
• The upper/lower limit value automatic transfer function is not supported when connected and used with the
FX5U or FX5UC CPU module. F
FX3U-4DA-ADP
3. Upper/lower limit automatic transfer function (b1 of BFM#60)
If the upper/lower limit automatic transfer data register is specified in BFM#62, the data in BFM#39 can be
transferred to a specified data register.
Only when an error is detected, data will be automatically transferred from the FX3U-4DA to the PLC. For this
reason, the PLC does not need the program for reading data, and the scan time of the PLC can be shortened.
→ For a detailed description of the status automatic transfer function, refer to Subsection 5.4.18.
G
FX3G-1DA-BD
5.4.15 BFM#40: Clearance of upper/lower limit function status
Initial value: H0000
Numeric data type: Hexadecimal (H) H
The flags can be reset by turning on the following bits of BFM#40.
FX3U-3A-ADP
Bit Description
b0 Clearance of lower limit status I
b1 Clearance of upper limit status
FX3U-4AD-PT
b2 to b15 Invalid
-ADP
E-31
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.4 Buffer Memory Details
E-32
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.4 Buffer Memory Details
A
5.4.17 BFM#50: Setting of output corrective function by load resistance
Common Items
(only in voltage output mode)/BFM#51 to #54: Load resistance values
The output characteristics of FX3U-4DA have been adjusted at 30 kΩ load resistance as a factory default.
B
FX3UC-4AD
FX3U-4AD
When the load resistance is 1 kΩ, the output deviation is approx. -4.3 % to 20 V in full scale, whereas the
output deviation is approx. 0.15 % to 20 V in full scale when the load resistance is 1 MΩ. When the load
resistance is 30 kΩ or less (1 kΩ to 30 kΩ), the deviation of the output characteristics can be corrected by
specifying the output corrective function (BFM#50) and the load resistance values (BFM#51 to #54).
Analog value C
FX3U-4AD-ADP
The deviation of output characteristics is
corrected by the corrective function by load
+10V resistance.
-32000 D
32000 Digital value
FX3G-2AD-BD
: Output characteristics after correction
FX3U-4DA
1. Setting of output corrective function (BFM#50)
The corrective function by load resistance is valid or invalid by writing a 4-digit hexadecimal number,
H, in the output corrective function setting (BFM#50).
F
H
FX3U-4DA-ADP
ch4 ch1
ch3 ch2
FX3G-1DA-BD
0 Corrective function by load resistance is invalid.
1 Corrective function by load resistance is valid.
Other than above values Invalid (setting values unchanged)
BFM
Description Setting range (Ω) Initial value (Ω)
number
#51 Load resistance value for channel 1
#52
#53
Load resistance value for channel 2
Load resistance value for channel 3
1000 to 30000 30000 I
FX3U-4AD-PT
J
FX3U-4AD-PTW
-ADP
E-33
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.4 Buffer Memory Details
When the bits, b0 to b2, of BFM#60 are turned on, the assigned functions (see the table below) are valid.
When the bits are turned off, the functions are invalid.
E-34
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.4 Buffer Memory Details
A
5.4.19 BFM#61: Error status data automatic transfer-to data register specification
Common Items
Setting range: 0 to 7999
Initial value: K200
Numeric data type: Decimal (K)
Use this function to automatically transfer the error status data (BFM#29) to the data register specified in
B
FX3UC-4AD
FX3U-4AD
BFM#61.
When an error is detected, data will be automatically transferred from FX3U-4DA to the PLC. For this reason,
the PLC does not need a program for reading data, and the scan time of the PLC can be shortened.
→ For a detailed description of the error status (BFM#29), refer to Subsection 5.4.12.
FX3U-4AD-ADP
Specified data
Description
register
D200 Value of error status (BFM#29)
FX3G-2AD-BD
register.
• This function is valid by turning on b0 of the status automatic transfer function setting (BFM#60).
• When a value out of the above setting range is set, b9 of the error status BFM#29 is turned on.
• The data set in BFM#61 will be retained in the EEPROM.
E
3. Cautions regarding EEPROM writing
FX3U-4DA
If data is set in BFM#0, #5, #10 to #17, #32 to #35, #50 to #54 or #60 to #63, the data will be written in the
EEPROM of FX3U-4DA.
Do not turn off the power immediately after writing values in these buffer memories.
The maximum number of EEPROM rewritable times is 10,000. Therefore, when creating a program, do not
frequently write data in the above buffer memories (BFM). F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
E-35
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.4 Buffer Memory Details
5.4.20 BFM#62: Upper/lower limit function status data automatic transfer-to data register
specification
Use this function to automatically transfer the upper/lower limit function status data (BFM#39) to the data
register specified in BFM#62.
Only when the value becomes more than the upper limit or less than the lower limit, data will be automatically
transferred from FX3U-4DA to the PLC. For this reason, the PLC does not need the program to read data, and
the scan time of the PLC can be shortened.
→ For a detailed description of the upper/lower limit function status (BFM#39),
refer to Subsection 5.4.14.
Specified data
Description
register
D201 Value of upper/lower limit function status (BFM#39)
2. Cautions regarding upper/lower limit function status automatic transfer function setting
• If a data is already specified for the other automatic transfer functions, do not specify the same data
register.
• This function is valid by turning on b1 of the status automatic transfer function setting (BFM#60).
• When a value out of the above setting range is set, b9 of the error status BFM#29 is turned on.
• The data set in BFM#62 will be retained in the EEPROM.
E-36
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.4 Buffer Memory Details
A
5.4.21 BFM#63: Specification of data register for automatic transfer at disconnection
Common Items
detection
FX3UC-4AD
FX3U-4AD
Use this function to automatically transfer the disconnection detection status data (BFM#28) to the data
register specified in BFM#63.
Only when wire-break is detected, data will be automatically transferred from FX3U-4DA to the PLC. For this
reason, the PLC does not need the program for reading data, and the scan time of the PLC can be shortened.
→ For a detailed description of the disconnection detection status (BFM#28),
refer to Subsection 5.4.9. C
FX3U-4AD-ADP
1. If "BFM#63 = K202 (initial value)"
Specified data
Description
register
D202 Value of disconnection detection status (BFM#28)
D
FX3G-2AD-BD
2. Cautions regarding disconnection detection status automatic transfer function setting
• If a data is already specified for the other automatic transfer functions, do not specify the same data
register.
• This function is valid by turning on b2 of the status automatic transfer function setting (BFM#60).
• When a value out of the above setting range is set, b9 of the error status BFM#29 is turned on. E
FX3U-4DA
• The data set in BFM#63 will be retained in the EEPROM.
FX3U-4DA-ADP
frequently write data in the above buffer memories (BFM).
FX3G-1DA-BD
BFM#80 (start/stop command of table output function)
BFM#81 to #84 (output pattern setting of channels)
BFM#85 to #88 (output execution cycle number of channels)
BFM#89 (completion flag of table output function)
BFM#90 (table output error code)
BFM#91 (table output error source number) H
BFM#98 (data table head device number)
FX3U-3A-ADP
J
FX3U-4AD-PTW
-ADP
E-37
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Table Output Function
FX3U-4DA (4-channel Analog Output) 6.1 Outline of Table Output Function
Transfer of data table*1 The data table is transferred from the PLC main
unit to the relevant buffer memory of FX3U-4DA.
Refer to Section 6.4
*1. It is possible to write the data table directly in FX3U-4DA using a program (TO instruction, etc.).
Caution:
The data table transfer command is not supported when connected and used with the FX5U or FX5UC CPU
module.
Directly write to the FX3U-4DA by the PLC program (TO instruction, etc.)
E-38
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Table Output Function
FX3U-4DA (4-channel Analog Output) 6.2 Preparation of data table
A
6.2 Preparation of data table
Common Items
1. Outline of data table
The data table to be prepared in the PLC consists of the following items.
(1) Number of patterns (1 to 10 patterns)
(2) Each pattern
B
FX3UC-4AD
FX3U-4AD
(3) Number of points in each pattern (1 to 99 points)
(4) Condition after output at final point in each pattern
(5) Points in each pattern
(6) Data to be output at each point
(7) Output update time at each point
(8) Unit of output update time at each point, and point-to-point interpolation method C
FX3U-4AD-ADP
2. Preparation of data table
Prepare the data table consisting of the following items in the data registers (D1000 to D7999) in the PLC
main unit or the expansion registers (R0 to R32767).
It is convenient to prepare the data table on spreadsheet software and copy and paste the data to the device
memory of GX Works2 or GX Developer.
D
FX3G-2AD-BD
Setting item Device number in PLC assignment
(1) Number of patterns (x) Device number specified in BFM#98
(3) Number of points in pattern 1 (n) Device number+1 specified in BFM#98
(2) Pattern 1
(4) Condition after output at final point in pattern Device number+2 specified in BFM#98
(6) Output data Device number+3 specified in BFM#98 E
(7) Output update time Device number+4 specified in BFM#98
FX3U-4DA
(5) Point 1
(8) Unit of output update time at each point,
Device number+5 specified in BFM#98
and point-to-point interpolation method
. . .
. . .
. . . F
(6) Output data
FX3U-4DA-ADP
(7) Output update time
(5) Point n
(8) Unit of output update time at each point,
and point-to-point interpolation method
. .
. . G
. .
FX3G-1DA-BD
(3) Number of points in pattern X (m)
(2) Pattern X
(8) Unit of output update time at each point, Device specified in BFM#98 + total number
and point-to-point interpolation method of data tables -1*1
-ADP
E-39
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Table Output Function
FX3U-4DA (4-channel Analog Output) 6.2 Preparation of data table
(4) Condition after output at final point in pattern (number of data items: 1)
The condition after output at the final point in a pattern can be set to continue to output the output signal at
the final point or output the offset signal.
The setting is shown in the following table.
*1. When a value out of the setting range is set, the error code is stored in the table output error code
BFM#90, the device number or the buffer memory that has developed the table output error is stored
in BFM#91, and b8 of the error status BFM#29 is turned on.
E-40
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Table Output Function
FX3U-4DA (4-channel Analog Output) 6.2 Preparation of data table
A
(8) Output update time unit and point-to-point interpolation method (number of data items: 1)
Common Items
Set the unit of the output update time and the point-to-point interpolation method for each point.
The output update time unit and the point-to-point interpolation method for the n-th point are applied
between the n-th point and the (n+1)-th point.
When the pattern is repeated, the output update time unit and the point-to-point interpolation method are
applied between the final point and the first point.
When the pattern is not repeated, the output update time unit and the point-to-point interpolation method
B
FX3UC-4AD
FX3U-4AD
for the final point are ignored.
A 4-digit hexadecimal number, H, is allocated as shown below.
H
Invalid*1 Output updating time unit
C
FX3U-4AD-ADP
Invalid*1 Point-to-point interpolation method
FX3G-2AD-BD
1 100 ms
2 1s
3 1 min
Other than above values Invalid*1
E
FX3U-4DA
• Interpolation method
Data output between points are interpolated every 1 ms and automatically updated.
FX3U-4DA-ADP
interpolated in the shape of a straight line.)
S-shaped interpolation (Data output between points are
2 interpolated in the shape of an S-shaped as shown
below.)
Invalid*1
Other than above values
G
FX3G-1DA-BD
• S-shaped interpolation
Output data
D/8
Point n+1
H
FX3U-3A-ADP
D/2 D/8
Point n
Time I
FX3U-4AD-PT
T
-ADP
*1. When a value out of the setting range is set, the error code is stored in the table output error code
BFM#90, the device number or the buffer memory that has developed the table output error is stored
J
FX3U-4AD-PTW
E-41
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Table Output Function
FX3U-4DA (4-channel Analog Output) 6.2 Preparation of data table
Data
Set value Description
register
D5000 K2 Number of patterns 2 patterns
D5001 K3 Number of points in pattern 1 3 points
Pattern 1
Holding of value
D5002 K0 Setting of condition after output at final point in pattern 1
output at final point
D5003 K3000 Data to be output at point 1 in pattern 1 3V
D5004 K18 Point 1 Output update time at point 1 in pattern 1 1800 ms
Output update time unit at point 1 in pattern 1 100 ms
D5005 H0021
Point-to-point interpolation method S-shaped interpolation
D5006 K8000 Data to be output at point 2 in pattern 1 8V
Point 2
D5013 K1 Setting of condition after output at final point in pattern 2 Output of offset value
D5014 K2000 Data to be output at point 1 in pattern 2 2V
Point 1
E-42
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Table Output Function
FX3U-4DA (4-channel Analog Output) 6.2 Preparation of data table
A
5. Example of pattern output
Common Items
Data can be output in a predetermined pattern as shown below. (Example of pattern 1 in output mode 1
shown on the previous page)
FX3UC-4AD
FX3U-4AD
are set to 0 or 2 or
Output higher.)
value
Point 2
8V
Linear
S-shaped
interpolation
C
interpolation
FX3U-4AD-ADP
5V
Point 3
Point 1
3V
D
FX3G-2AD-BD
Time
Output update Output update Output update
time at point 1
(1800 ms)
time at point 2
(2600 ms)
time at point 3
(500 ms)
E
FX3U-4DA
6. Caution when preparing the data table
• Prepare the data table in continuous data registers in the PLC main unit or continuous expansion registers.
(Prepare data without spaces between patterns or points.)
If data has spaces, the data cannot be transferred normally to the buffer memory in FX3U-4DA. F
→ For a detailed description of data table errors, refer to Section 6.5.
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
E-43
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Table Output Function
FX3U-4DA (4-channel Analog Output) 6.3 Procedures for transferring data table to buffer memory
1. Specify the head device number of the data table to be transferred. (BFM#98, initial value:
K1000)
Specify the head device number of the data table in BFM#98.
The setting range is K1000 to K7994 for the data registers (D1000 to D7999) (because at least six points are
occupied) or K0 to K32762 for the expansion registers (R0 to R32767) (because at least six points are
occupied).
Example) When the data table is set starting from D1000, set K1000 in BFM#98.
When a value out of the setting range is set, the error code K21 is stored in the table output error code
BFM#90, the number of the buffer memory, K98, that has developed the table output error is stored in
BFM#91, and b8 of the error status BFM#29 is turned on.
H
Invalid*1 Data table transfer command
Invalid*1 Register type
• Register type
*1. When a value out of the setting range is set, the error code is stored in the table output error code
BFM#90, the number of the buffer memory, K99, that has developed the table output error is stored in
BFM#91, and b8 of the error status BFM#29 is turned on.
Example) When K1000 is written in the head device number of data table (BFM#98) and H0001 is written in
the data table transfer command (BFM#99), the data table will be transferred from the data
register D1000.
Caution:
When connected and used with the FX5U or FX5UC CPU module, do not use the data table transfer
command.
Directly write to the FX3U-4DA by the PLC program (TO instruction, etc.)
E-44
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Table Output Function
FX3U-4DA (4-channel Analog Output) 6.3 Procedures for transferring data table to buffer memory
A
3. Buffer memory contents in FX3U-4DA after transfer
Common Items
The transferred data table is stored in the following buffer memory areas.
BFM
Description
number
#100
Pattern 1
Number of points B
#101 Condition after output at final point in pattern
FX3UC-4AD
FX3U-4AD
#102 Output data
#103 Output update time
Point 1
Unit of output update time at each point, and point-to-
#104
point interpolation method
. . . C
. . .
FX3U-4AD-ADP
. . .
#396 Output data
#397 Output update time
Point 99
Unit of output update time at each point, and point-to-
#398
point interpolation method D
FX3G-2AD-BD
#399 Not used
. . .
. . .
. . .
#2800 Number of points
#2801 Condition after output at final point in pattern
E
FX3U-4DA
#2802 Output data
#2803 Output update time
Point 1
Unit of output update time at each point, and point-to-
#2804
Pattern 10
FX3U-4DA-ADP
. . .
#3096 Output data
#3097 Output update time
Point 99
Unit of output update time at each point, and point-to-
#3098
point interpolation method G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
E-45
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Table Output Function
FX3U-4DA (4-channel Analog Output) 6.3 Procedures for transferring data table to buffer memory
E-46
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Table Output Function
FX3U-4DA (4-channel Analog Output) 6.3 Procedures for transferring data table to buffer memory
A
5. Cautions regarding data table transfer
Common Items
• While the table output function is executed, it is impossible to start transferring the data table.
• The number of patterns is not transferred to the buffer memory in FX3U-4DA.
• The transferred data table is stored in the buffer memory in FX3U-4DA. The data table stored in FX3U-4DA
will be erased when power is turned off. Therefore, it is necessary to transfer the data table after rebooting
the power.
B
FX3UC-4AD
FX3U-4AD
• At completion of transfer, BFM#99 will automatically change to H0000. Also when transfer is stopped due
to an error, BFM#99 will automatically change to H0000. When BFM#99 changes to H0000, check the
error flag.
→ For a detailed description of errors related to table output, refer to Section 6.5.
• If an error occurs during transfer of the data table, the data up to the error is transferred. Subsequent data C
is not transferred.
FX3U-4AD-ADP
• It is possible to write the data table directly in the buffer memory without using the data table transfer
command (BFM#99).
In this case, the correctness of the data table is not evaluated until the table is output by the table output
start/stop function (BFM#80).
If a data table with incorrect data is output, the data up to the point where incorrect data occurs is output.
At the point where incorrect data occurs, an error is registered and only the data output just before the
D
FX3G-2AD-BD
occurrence of the error is held.
• Execute the data table transfer command (BFM#99) as a pulse execution type instruction.
• During transfer of the data table, the scan time increases by up to about 10 ms.
• The standard data table transfer time is obtained by the following formula.
E
Number of *1
FX3U-4DA
data table items
Transfer time = (Scan time) (number of FX3U-4DA units connected to main unit)
64
FX3U-4DA-ADP
Number of data table items to be transferred: 2991 items (when the number of patterns is 10
and the number of points in each pattern is 99)
Number of units connected to FX3U-4DA: 8 units
2991
G
Transfer time = (50 ms) (8 units)
FX3G-1DA-BD
64
= 18800 ms
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
E-47
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Table Output Function
FX3U-4DA (4-channel Analog Output) 6.4 Procedures for executing table output function
1. Set the output patterns for the channels. (BFM#81 to #84, initial value: K1)
Set the output patterns for the channels in BFM#81 to #84.
The output pattern can be changed in the middle of outputting the table.
Setting range for BFM#81 to #84: 1 to 10
When a value out of the setting range is set, the error code K31 is stored in the table output error code
BFM#90, the number of the buffer memory (K81 to K84) that has developed the table output error is stored in
BFM#91, and b8 of the error status BFM#29 is turned on.
2. Set the number of table outputs for the channels. (BFM#85 to #88, initial value: K0)
Set the number of table outputs for the channels in BFM#85 to #88.
The number of outputs can be changed even during outputting the table.
Setting range for BFM#85 to #88: 0 to 32767
When 0 is set, output of the table will be repeated until the table output is stopped by BFM#80.
When a value out of the setting range is set, the error code K32 is stored in the table output error code
BFM#90, the number of the buffer memory (K85 to K88) that has developed the table output error is stored in
BFM#91, and b8 of the error status BFM#29 is turned on.
H
ch4 ch1
ch3 ch2
*1. When a value out of the setting range is set, the error code K33 is stored in the table output error code
BFM#90, the number of the buffer memory (K80) that has developed the table output error is stored in
BFM#91, and b8 of the error status BFM#29 is turned on.
E-48
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Table Output Function
FX3U-4DA (4-channel Analog Output) 6.4 Procedures for executing table output function
A
4. Cautions regarding table output
Common Items
• When BFM#99 (data table transfer command) is not H0000, the table output function cannot be started.
• When an error occurs during transfer of data table, start the table output after setting the correct data table.
• While the table output completion flag BFM#89 is ON, output of a new table cannot be started.
• The table output function is valid only while the PLC is in RUN mode. B
• While even a single channel is outputting data table (BFM#80 is not H0000), it is prohibited to change
FX3UC-4AD
FX3U-4AD
BFM#0, #5, #9 to #17, #19, #20, #32 to #35, #38, #41 to 48, #50 to #54 and #60 to #63.
• The pattern can be changed during output as shown below. (The change is invalid while the table output
completion flag BFM#89 is ON.)
Output
value Pattern 5
C
FX3U-4AD-ADP
Pattern 1
FX3G-2AD-BD
Time
Table output start Change from output pattern
1 to output pattern 5 E
FX3U-4DA
5. Check the table output completion flag. (BFM#89, initial value: H0000)
The value in BFM#89 indicates whether the table output from each channel has been completed.
After data is output at the final point in the last cycle of a pattern, the table output completion flag is turned on.
When the table output (BFM#80) is set to be stopped, the table output completion flag is turned off. F
FX3U-4DA-ADP
H
ch4 ch1
ch3 ch2
G
FX3G-1DA-BD
Value for each
Table output completion flag
channel
0 Table output uncompleted
1 Table output completed
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
E-49
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Table Output Function
FX3U-4DA (4-channel Analog Output) 6.5 Details of table output error
E-50
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Table Output Function
FX3U-4DA (4-channel Analog Output) 6.5 Details of table output error
A
2. Cautions regarding table output errors
Common Items
• Errors in data table
When the data table in the PLC contains an error, the error can be detected during transfer of the data to
the buffer memory in FX3U-4DA. In this case, the error code (BFM#90) is K11, and the device number is
written as the error source (BFM#91).
If an error is caused in the data table by directly rewriting the data in BFM after the data table is transferred, B
the error can be detected when the table is output using incorrect data. In this case, the error code
FX3UC-4AD
FX3U-4AD
(BFM#90) is K12, and the BFM number is written as the error source (BFM#91).
• Error during transfer of the data table
While transferring of the data table, an error (error codes K31 to K33) does not occur even when the
BFM#80 (table output function start/stop) is set to a value out of the setting range. An error occurs after the
completion of the transfer of the data table. C
• Error during output of the table
FX3U-4AD-ADP
Even if the output value is scaled over during output of the table, the output of the table will not be stopped.
However, while the output value is scaled over, b10 (scale over) of the error status BFM#29 stays on.
When an error (error codes K122 to K172, K31 to K33) occurs during output of the table, the output of the
table is cancelled and the analog output value just before the occurrence of the error is retained.
• Table output errors (BFM#90) and table output error source numbers (BFM#91) are not retained. They will D
be cleared when the next data table transfer command is given or the table output start function is
FX3G-2AD-BD
executed.
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
E-51
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Table Output Function
FX3U-4DA (4-channel Analog Output) 6.6 Examples uses of table output function
Output
frequency
(Hz)
60
30
0
5 10V
Analog signal
To control the frequency as shown below, where control the analog signal is proportional to the frequency use
the table output function.
Output
frequency
(Hz)
60
30
0
Time
Output
voltage (V)
Point 2 Point 3
10
No interpolation
S-shaped S-shaped
interpolation interpolation
5
Point 4
0 Point 1
Time
Output update Output update Output update
time at point 1 time at point 2 time at point 3
E-52
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 7 Changing Output Characteristics
FX3U-4DA (4-channel Analog Output) 7.1 Procedure for Changing Output Characteristics
Common Items
7. Changing Output Characteristics
For FX3U-4DA, the standard output characteristics are provided for each output mode (BFM#0)at the time of B
factory shipment.
FX3UC-4AD
FX3U-4AD
Changing the offset data (BFM#10 to #13) and gain data (BFM#14 to #17) can change the output
characteristics of each channel. This chapter describes how to change the output characteristics.
FX3U-4AD-ADP
1 Cancel the setting change prohibition mode.
If setting change is prohibited, write K3030 in BFM#19. The setting change prohibition mode will be
canceled.
D
2
FX3G-2AD-BD
Determine the output mode (BFM#0).
Determine the output mode (BFM#0) optimum for the selected channels and the voltage/current
specifications.
Set value (HEX) Output mode Analog output range Digital input range E
FX3U-4DA
0 Voltage output mode -10 V to +10 V -32000 to +32000
Voltage output analog value mV
1 The characteristic cannot be changed.
specification mode
2 Current output mode 0 mA to 20 mA 0 to 32000
3 Current output mode
Current output analog value μA
4 mA to 20 mA 0 to 32000
F
4 The characteristic cannot be changed.
FX3U-4DA-ADP
specification mode
5 to E Setting not allowed - -
F Channel not used - -
Example: Enter "HFF00" in BFM to set output mode 0 for channels 1 and 2 and prevent use chan- G
nels 3 and 4
FX3G-1DA-BD
Cautions regarding data setting
• If a value "1" or "4" is set for a channel, the output characteristics of the channel cannot be changed.
• Set the optimum output mode for the analog signal to be output.
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
E-53
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 7 Changing Output Characteristics
FX3U-4DA (4-channel Analog Output) 7.1 Procedure for Changing Output Characteristics
Output mode: 0
Output characteristics provided at the time Output characteristics newly provided
of factory shipment
+10.2V
+10V 5V
Digital 1V Digital
-32000 0 value value
+32000 0 32000
-10V
-10.2V
E-54
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 7 Changing Output Characteristics
FX3U-4DA (4-channel Analog Output) 7.1 Procedure for Changing Output Characteristics
A
6
Common Items
Create a sequence program.
To change the output characteristics, write the offset data (BFM#10 to #13) and the gain data
(BFM#14 to #17) in the sequence program, and then turn on the corresponding bit of BFM#9 for
the corresponding channel.
B
Example: Program for changing the output characteristics of channels 1 and 2 (For FX3U/FX3UC Series
FX3UC-4AD
FX3U-4AD
PLCs):
X000
FNC 12 Cancellation of setting change
K3030 U0\G19 prohibition mode
MOV P
FX3U-4AD-ADP
MOV P channels 1 to 4
SET M0
M0
K50
T0
D
T0
FX3G-2AD-BD
FNC 16 K1000 U0\G10 K2 Setting of offset data (channels 1 and 2)
FMOV P
FX3U-4DA
FNC224 FNC 12 K0 U0\G19 Setting change prohibition
K0 U0\G9
LD= MOV P
F
7 Transfer the sequence program to change the output characteristics.
FX3U-4DA-ADP
Transfer the sequence program, and start the PLC.
After the PLC is started and the output characteristic write command (X000) is turned on, the offset
data and gain data will be written.
Since the offset data and gain data are stored in the EEPROM incorporated in FX3U-4DA, it is pos-
G
FX3G-1DA-BD
sible to delete the pre-written sequence program.
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
E-55
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 8 Examples of Practical Programs
FX3U-4DA (4-channel Analog Output) 8.1 Example of Program for Analog Output Operation (Regular Operation)
1. Conditions
The sequence program described in this section is under the following conditions.
1) System configuration
FX3U-4DA (unit No.0) should be connected to the FX3U Series PLC.
2) Output mode
Channels 1 and 2 should be set to mode 0 (voltage output, -10 V to +10 V).
Channel 3 should be set to mode 3 (current output, 4 mA to 20 mA).
Channel 4 should be set to mode 2 (current output, 0 mA to 20 mA).
- For FX3U/FX3UC Series PLCs
Initial pulse
Transfer H2300 to BFM#0 (output modes of
M8002 channels 1 to 4).
FNC 12 H2300 U0\G0 ch1 and ch2: Voltage output (-10 to +10 V),
MOV P output mode 0
RUN monitor ch3: Current output (4 mA to 20 mA), output
M8000 mode 3
K50 *1 ch4: Current output (0 mA to 20 mA), output
T0 mode 2
Data to be output to channel 1 is written in D0. Store the data to be output to channels 1 to 4
Data to be output to channel 2 is written in D1. in D0 to D3 in the following ranges.
Data to be output to channel 3 is written in D2. D0 and D1: -32000 to +32000
Data to be output to channel 4 is written in D3. D2 and D3: 0 to 32000
Data to be output to channel 1 is written in D0. Store the data to be output to channels 1 to 4
Data to be output to channel 2 is written in D1. in D0 to D3 in the following ranges.
Data to be output to channel 3 is written in D2. D0 and D1: -32000 to +32000
Data to be output to channel 4 is written in D3. D2 and D3: 0 to 32000
E-56
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 8 Examples of Practical Programs
FX3U-4DA (4-channel Analog Output) 8.2 Example of Program using Useful Functions
A
8.2 Example of Program using Useful Functions
Common Items
This section describes a practical program that uses the disconnection detection function (BFM#28), upper/
lower limit function (BFM#38 to #48), corrective function by load resistance (BFM#50 to #54) and status
automatic transfer function (BFM#60 to #63) of FX3U-4DA.
1. Conditions
B
FX3UC-4AD
FX3U-4AD
The sequence program described in this section is created under the following conditions.
1) System configuration
FX3U-4DA (unit No.0) should be connected to the FX3U Series PLC.
2) Output mode
Channels 1 and 2 should be set to mode 0 (voltage output, -10 V to +10 V). C
Channels 3 and 4 should be set to mode 2 (current output, 0 mA to 20 mA).
FX3U-4AD-ADP
3) Convenient functions
The disconnection detection function, upper/lower limit function, corrective function by load resistance
and status automatic transfer function are used.
Caution:
The status automatic transfer function is not supported when connected and used with the FX5U or D
FX5UC CPU module.
FX3G-2AD-BD
4) Device assignment
Device Description
X000 Clearance of upper/lower limit function status data
X001
D10
Clearance of disconnection detection status data
Data to be output from channel 1
E
FX3U-4DA
Input
D11 Data to be output from channel 2
D12 Data to be output from channel 3
D13 Data to be output from channel 4
Y000 Output of channel-1 lower limit error data
Y001 Output of channel-1 upper limit error data F
FX3U-4DA-ADP
Y002 Output of channel-2 lower limit error data
Y003 Output of channel-2 upper limit error data
Y004 Output of channel-3 lower limit error data
Y005 Output of channel-3 upper limit error data
Y006 Output of channel-4 lower limit error data G
Output Y007 Output of channel-4 upper limit error data
FX3G-1DA-BD
Y010 Output of disconnection detection signal
Y011 Output of error detection signal
D200 Data register at destination of automatic transfer of error status
D201
Data register at destination of automatic transfer of upper/lower limit
function error status
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
E-57
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 8 Examples of Practical Programs
FX3U-4DA (4-channel Analog Output) 8.2 Example of Program using Useful Functions
Initial pulse
M8002
FNC 12 H2200 U0\G0 Output modes of channels 1 to 4 will be specified*1
RUN monitor MOV P
M8000
T0 K50*2
T0
FNC 12 H1122 U0\G38 Upper/lower limit function setting
MOV P
FNC 16 K-3200 U0\G41 K2 Setting of lower limit values for channels 1 and 2
FMOV P
FNC 16 K6400 U0\G43 K2 Setting of lower limit values for channels 3 and 4
FMOV P
FNC 16 K28800 U0\G45 K2 Setting of upper limit values for channels 1 and 2
FMOV P
FNC 16 K25600 U0\G47 K2 Setting of upper limit values for channels 3 and 4
FMOV P
FNC 16 K5000 U0\G51 K2 Setting of load resistance values for channels 1 and 2*1
FMOV P
D202.2
Disconnection detected in channels 3 and 4
Y010 Output to Y010
D202.3
D200.0
Y011 Error detected Output to Y011
*1. The output mode setting, setting of corrective function by load characteristics and status automatic
transfer function setting are retained in the EEPROM of FX 3U -4DA. For this reason, even if the
sequence program is deleted, the previously set functions will still be valid.
*2. After setting the output mode, set the data writing time (waiting time) to 5 seconds or more for each
setting. After the output mode is specified, and the same output mode is used, it is not necessary to
set the output mode and the waiting time (T0 K50).
E-58
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 8 Examples of Practical Programs
FX3U-4DA (4-channel Analog Output) 8.2 Example of Program using Useful Functions
A
• For FX3G/FX3GC/FX3U/FX3UC Series PLCs
Common Items
Initial pulse
M8002
FNC 79 K0 K0 H2200 K1 Output modes of channels 1 to 4 will be specified*1
RUN monitor TO P
M8000
K50*2
B
T0
FX3UC-4AD
FX3U-4AD
T0
FNC 79 K0 K38 H1122 K1 Upper/lower limit function setting
TO P
FNC 79 K0 K41 K-3200 K2 Setting of lower limit values for channels 1 and 2
TO P C
FX3U-4AD-ADP
FNC 79 K0 K43 K6400 K2 Setting of lower limit values for channels 3 and 4
TO P
FNC 79 K0 K45 K28800 K2 Setting of upper limit values for channels 1 and 2
TO P
FNC 79
TO P
K0 K47 K25600 K2 Setting of upper limit values for channels 3 and 4 D
FX3G-2AD-BD
FNC 79 K0 K50 H0011 K1 Corrective function setting by load resistance*1
TO P
FNC 79 K0 K51 K5000 K2 Setting of load resistance values for channels 1 and 2*1
TO P
FX3U-4DA
TO P and the sequence program for this function is omitted.)
X000
FNC 79 K0 K40 H0003 K1 Clearance of upper/lower limit function status data
TO P
X001
FNC 79
TO P
K0 K29 K0 K1 Clearance of error status data
F
X002
FX3U-4DA-ADP
FNC 79 K0 K28 K0 K1 Clearance of disconnection detection status data
TO P
RUN monitor
M8000
FNC 79 K0 K1 D10 K4 Transfer of data that will be output from channels 1 to 4
TO
FX3G-1DA-BD
FNC 12 D200 K4M0
MOV
M0
Y011 Error detected Output to Y011
I
FX3U-4AD-PT
*1. The output mode setting, setting of corrective function by load characteristics and status automatic
transfer function setting are retained in the EEPROM of FX 3U -4DA. For this reason, even if the
sequence program is deleted, the previously set functions will still be valid.
-ADP
*2. After setting the output mode, set the data writing time (waiting time) to 5 seconds or more for each
setting. After the output mode is specified, and the same output mode is used, it is not necessary to J
set the output mode and the waiting time (T0 K50).
FX3U-4AD-PTW
-ADP
E-59
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 8 Examples of Practical Programs
FX3U-4DA (4-channel Analog Output) 8.3 Example of Program for Table Output Operation (Pattern Output Operation)
1. Conditions
The sequence program described in this section is under the following conditions.
1) System configuration
FX3U-4DA (unit No.0) should be connected to the FX3U Series PLC.
2) Output mode
Channel 1 should be set to mode 0 (voltage output, -10 V to +10 V).
Channel 3 should be set to mode 2 (current output, 0 mA to 20 mA).
Channels 2 and 4 are out of use.
3) Convenient function
The table output function is used.
4) Device assignment
Device Description
X000 Start of table output function for channels 1 and 3
X001 Stop of table output function
X002 Restart of table output function for channel 3
D10 Data to be output from channel 1
Input
D11 Data to be output from channel 2
D12 Data to be output from channel 3
D13 Data to be output from channel 4
D5000 or more Data table*1
Y000 Completion of output of table from channel 1
Y001 Table output error
M0 Data table transfer complete
Output
M1 During output of table from channel 3
D100 Data table transfer command
D101 Table output completion flag
Initial pulse
M8002
FNC 12 HF2F0 U0\G0 Specification of output modes of channels 1 to 4*2
MOV P
RUN monitor
M8000
T0 K50*3
Continued
*2. The output mode setting is retained in the EEPROM of the FX3U-4DA. For this reason, even if the
sequence program is deleted, the previously set functions will still be valid.
*3. After setting the output mode, set the data writing time (waiting time) to 5 seconds or more for each
setting. After the output mode is specified, and the same output mode is used, it is not necessary to
set the output mode and the waiting time (T0 K50).
E-60
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 8 Examples of Practical Programs
FX3U-4DA (4-channel Analog Output) 8.3 Example of Program for Table Output Operation (Pattern Output Operation)
Common Items
T0
FNC 12 K1 U0\G81 Channel-1 output pattern
MOV P
FX3UC-4AD
FX3U-4AD
FNC 12 Number of repetitions of output of table
K5 U0\G85 from channel 1
MOV P
FX3U-4AD-ADP
K5000 U0\G98 Number of head device in data table
MOV P
FNC 78
FROM
K0 K99 D100 K1 Readout of data table transfer command D
FX3G-2AD-BD
D100.0
Turning-on of M0 At the completion of transfer
SET M0 of data table
X000
FNC 12 H0100 U0\G80 Start table output function (channel 3)
MOV P
Turning-on of M1 when table is output from E
SET M1 channel 3
FX3U-4DA
X000 M1
FNC 12 H0101 U0\G80 Start table output function (channel 1)
MOV P
X001 M1
FNC 12 H0000 U0\G80 Stop table output function
MOV P F
FX3U-4DA-ADP
Turning-off of M1 when output of table from
RST M1 channel 3 is stopped
X002 M1
FNC 12 H0100 U0\G80 Restart of table output function (channel 3)
MOV P
FX3G-1DA-BD
M1
FNC 78 K0 K89 D101 K2 Readout table output completion flag and table
FROM output error
D101.0
Y000 Completion of table output from channel 1
Output to Y000
FNC228
H
K0 D102 Y001 Output to Y001 when table output error occurs
FX3U-3A-ADP
LD<>
*1. Execute the data table transfer command as a pulse execution type instruction.
Caution: I
The data table transfer command is not supported when connected and used with the FX5U or FX5UC CPU
FX3U-4AD-PT
module.
Directly write to the FX3U-4DA by the PLC program (TO instruction, etc.)
-ADP
J
FX3U-4AD-PTW
-ADP
E-61
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 8 Examples of Practical Programs
FX3U-4DA (4-channel Analog Output) 8.3 Example of Program for Table Output Operation (Pattern Output Operation)
Initial pulse
M8002
FNC 79 K0 K0 HF2F0 K1 Specification of output modes of channels 1 to 4*1
TO P
RUN monitor
M8000
T0 K50*2
T0
FNC 79 K0 K81 K1 K1 Channel-1 output pattern
TO P
*1. The output mode setting is retained in the EEPROM of the FX3U-4DA. For this reason, even if the
sequence program is deleted, the previously set functions will still be valid.
*2. After setting the output mode, set the data writing time (waiting time) to 5 seconds or more for each
setting. After the output mode is specified, and the same output mode is used, it is not necessary to
set the output mode and the waiting time (T0 K50).
*3. Execute the data table transfer command as a pulse execution type instruction.
E-62
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 8 Examples of Practical Programs
FX3U-4DA (4-channel Analog Output) 8.4 Program to Initialize FX3U-4DA (Factory Default)
Common Items
M1
FNC 78 K0 K89 D101 K2 Readout table output completion flag and table
FROM output error
FNC 12
MOV
D101 K4M30
B
M30
FX3UC-4AD
FX3U-4AD
Y000 Completion of table output from channel 1
Output to Y000
FNC228 K0 D102 Y001 Output to Y001 when table output error occurs
LD<>
FX3U-4AD-ADP
8.4 Program to Initialize FX3U-4DA (Factory Default)
To initialize FX3U-4DA, execute the following program.
This will return the output mode (BFM#0), the offset data (BFM#10 to #13) and the gain data (BFM#14 to #17)
will be to the factory default status state. D
FX3G-2AD-BD
1. Conditions
The sequence program described in this section is under the following conditions.
1) System configuration
FX3U-4DA (unit No.0) should be connected to the FX3U Series PLC.
2) Device assignment E
Device Description
FX3U-4DA
X000 4DA initialization command
FX3U-4DA-ADP
X000
FNC 12 K1 U0\G20 The 4DA will be initialized.
MOV P (BFM#0 to #3098 will be cleared.)
FX3G-1DA-BD
4DA initialization command
X000
FNC 79 K0 K20 K1 K1 The 4DA will be initialized.
TO P (BFM#0 to #3098 will be cleared.)
H
3. Cautions regarding initializing
FX3U-3A-ADP
• During initialization, output is stopped, and H0000 is automatically written in the output status (BFM#6).
At the completion of initialization, the output status (BFM#6) will automatically change to H1111, and the
output will be restarted.
• It takes approximately 5 seconds to complete initialization. Do not set (write) data in the buffer memory
during the period. I
• Priority is given to the setting of the change prohibition mode (BFM#19).
FX3U-4AD-PT
• Once initialization is completed, the value in BFM#20 will automatically change to "K0".
-ADP
J
FX3U-4AD-PTW
-ADP
E-63
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 9 Troubleshooting
FX3U-4DA (4-channel Analog Output) 9.1 PLC Version Number Check
9. Troubleshooting
This chapter describes the troubleshooting methods and error codes.
If the D/A conversion data is not output, or if the proper digital value is not output, check the following items:
• Wiring
• Program
• Error status
1. Power
FX3U-4DA needs driving power. Verify that the power supply line is properly connected. Also check that the
24 V indicator lamp of FX3U-4DA is on.
E-64
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 9 Troubleshooting
FX3U-4DA (4-channel Analog Output) 9.4 Error Status Check
A
9.4 Error Status Check
Common Items
When an error occurs in FX3U-4DA, the bit appropriate to the error is turned on in the error status (BFM#29).
Take measures, referring to the following table.
FX3UC-4AD
FX3U-4AD
b1 O/G error
b2 Power supply error
b3 Hardware error
b4 - C
b5 Error in setting of function for setting output upon PLC stop
FX3U-4AD-ADP
b6 Upper/lower limit function setting error
Error in corrective function setting by load resistance
b7
(Valid only in voltage output mode)
b8 Table output function setting error
b9 Status automatic transfer setting error
D
FX3G-2AD-BD
b10 Over-scale
b11 Disconnection detection (Valid only in current output mode)
b12 Setting data change prohibited
b13 to b15 -
E
1. Error detection (b0)
FX3U-4DA
1) Description of error
If any of b1 is turned on, this bit (b11) will turn on.
FX3U-4DA-ADP
2) Remedy
Check the output mode (BFM#0) and the offset and gain data (BFM#10 to #17).
FX3G-1DA-BD
24 V power is not correctly supplied.
2) Remedy
Check the wiring condition or the supply voltage.
5. Error when setting the function for output upon PLC stop (b5)
1) Description of error I
FX3U-4AD-PT
The bit will turn on when the functions setting value for setting output upon PLC stop is not correctly set.
2) Remedy
Check the output mode (BFM#0) and the setting value of output data upon PLC stop (BFM#32 to #35).
-ADP
J
FX3U-4AD-PTW
-ADP
E-65
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 9 Troubleshooting
FX3U-4DA (4-channel Analog Output) 9.5 FX3U-4DA Initialization and Test Program
E-66
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4DA-ADP (4-channel Analog Output)
Common Items
B
FX3UC-4AD
FX3U-4AD
FX3S/FX3G/FX3GC/FX3U/FX3UC Series
Programmable Controllers C
FX3U-4AD-ADP
User's Manual [Analog Control Edition]
FX3G-2AD-BD
E
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
Foreword
This manual describes the specifications, wiring, and operation method for the FX3U-4DA-ADP special
adapter (4-channel analog output) and should be read and understood before attempting to install or use the
unit.
I
FX3U-4AD-PT
Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
it to the end user.
-ADP
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
rights which may occur as a result of using the contents noted in this manual. J
FX3U-4AD-PTW
F-1
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4DA-ADP (4-channel Analog Output)
F-2
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4DA-ADP (4-channel Analog Output) 1.1 Outline of Functions
Common Items
1. Outline
This chapter outlines the FX3U-4DA-ADP (referred to as 4DA-ADP). B
FX3UC-4AD
FX3U-4AD
1.1 Outline of Functions
The FX3U-4DA-ADP is an analog special adapter. Which is connectable with the FX3S/FX3G/FX3GC/FX3U/
FX3UC Series PLC to output the voltage/current data for up to 4 channels.
1) Only 1 4DA-ADP unit can be connected to the FX3S Series PLC. C
Up to 2*1 4DA-ADP units can be connected to the FX3G/FX3GC Series PLC.
FX3U-4AD-ADP
Up to 4 4DA-ADP units can be connected to the FX3U/FX3UC Series PLC.
(including the other analog expansion boards, analog special adapters)
2) Either "voltage output" or "current output" can be specified for each channel.
3) The D/A conversion results will be automatically output as the values to the special data register of the
FX3S/FX3G/FX3GC/FX3U/FX3UC Series PLC.
D
FX3G-2AD-BD
System Point and section to be
referred to
FX3U-4DA
Series PLC
To check the connectable
PLC model number, refer
+ + to Section 1.3.
FX3U-4DA-ADP
Expansion
4th 3rd 2nd 1st
adapter adapter adapter adapter board*2
For a detailed
description of wiring,
Analog data refer to Chapter 3.
G
Inverter, etc.
Refer to the system configuration shown in the User's Manual - Hardware Edition to check the number of I
connectable units and to configure the entire system.
FX3U-4AD-PT
*1. Only 1 analog special adapter can be connected to the FX3G Series PLC (14-point and 24-point type).
*2. The expansion board is not required when connecting with the FX3GC/FX3UC (D, DS, DSS) PLC.
-ADP
F-3
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4DA-ADP (4-channel Analog Output) 1.2 Setup Procedure Before Starting Operation
FX3U-4DA-ADP
Refer to Chapter 1.
Wiring Wiring:
• Power supply line
• Analog output line
Refer to Chapter 4.
Programming:
Programming
• Details of special devices
• Examples of basic programs
Refer to Chapter 5.
F-4
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4DA-ADP (4-channel Analog Output) 1.3 Connectable PLCs and Version Number
A
1.3 Connectable PLCs and Version Number
Common Items
The 4DA-ADP is compatible with the following PLCs.
FX3UC-4AD
FX3U-4AD
FX3GC Series PLC Ver. 1.40 or later*1 After January 2012 (From first product)
FX3U Series PLC *1 After May 2005 (From first product)
Ver. 2.20 or later
FX3UC Series PLC Ver. 1.20 or later*1 After April 2004
*1. For versions that support 4DA-ADP hardware error status check, refer to Section 6.5. C
FX3U-4AD-ADP
1. Version check
The PLC version can be checked by reading the last three digits of device D8001 or D8101.
→ For a detailed description of the version check,
refer to A. Common Items Subsection 5.1.2.
FX3G-2AD-BD
product.
→ For a detailed description of how to check the manufacturer's serial number,
refer to A. Common Items Subsection 5.1.1.
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
F-5
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4DA-ADP (4-channel Analog Output) 1.4 Compatible Programming Tool Version Number
1. English versions
Model name Media model name Applicable version Remarks
FX3S PLC
GX Works2 SWDNC-GXW2-E Ver. 1.492N or later
-
FX-30P Ver. 1.50 or later
FX3G PLC
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer SWD5C-GPPW-E Ver. 8.72A or later -
FX-30P Ver. 1.00 or later
FX3GC PLC
GX Works2 SWDNC-GXW2-E Ver. 1.77F or later
-
FX-30P Ver. 1.30 or later
FX3U and FX3UC PLCs
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer SWD5C-GPPW-E Ver. 8.18U or later -
FX-30P Ver. 1.00 or later
2. Japanese versions
Model name Media model name Applicable version Remarks
FX3S PLC
GX Works2 SWDNC-GXW2-J Ver. 1.492N or later
-
FX-30P Ver. 1.50 or later
FX3G PLC
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
GX Developer SWD5C-GPPW-J Ver. 8.72A or later -
FX-30P Ver. 1.00 or later
FX3GC PLC
GX Works2 SWDNC-GXW2-J Ver. 1.77F or later
-
FX-30P Ver. 1.30 or later
FX3U and FX3UC PLCs
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
GX Developer SWD5C-GPPW-J Ver. 8.13P or later -
FX-30P Ver. 1.00 or later
Point
• It is possible to create programs in FX3GC PLC using programming tools of inapplicable versions by
selecting "FX3G" as the alternative model.
• It is possible to create programs in FX3S PLC using programming tools of inapplicable versions by
selecting "FX3G" as the alternative model. However, memory capacity setting of the PLC parameter must
be set to 4000 steps or less.
F-6
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4DA-ADP (4-channel Analog Output) 2.1 Generic Specifications
Common Items
2. Specifications
This chapter describes the general, power supply, and performance specifications for 4DA-ADP. B
FX3UC-4AD
FX3U-4AD
2.1 Generic Specifications
Item Specifications C
FX3U-4AD-ADP
Ambient 0 to 55 °C (32 to 131 °F) when operating
temperature -25 to 75 °C (-13 to 167 °F) when stored
Relative
5 to 95 %RH (no condensation) when operating
humidity
Frequency Acceleration Half amplitude D
(Hz) (m/s2) (mm)
FX3G-2AD-BD
10 times of testing in
Vibration 10 to 57 - 0.035 each direction (X-, Y-,
DIN Rail Mounting
resistance*1 57 to 150 4.9 - and Z-axis directions)
(Total: 80 min, each)
10 to 57 − 0.075
Direct Mounting*2
−
Shock
57 to 150 9.8
E
147 m/s2 Acceleration, Action time: 11 ms, 3 times by half-sine pulse in each direction X, Y, and Z
FX3U-4DA
resistance*1
Noise Using noise simulator of:
resistance Noise voltage: 1,000 Vp-p / Noise width: 1 μs / Rise: 1 ns / Cycle: 30 to 100 Hz
Dielectric
withstand
voltage
500 V AC, for 1 min F
Between all terminals and ground terminal
FX3U-4DA-ADP
Insulation 5 MΩ or more using 500 V DC
resistance insulation resistance meter
Class D grounding (grounding resistance: 100 Ω or less)
Grounding
<Common grounding with a heavy electrical system is not allowed.>*3
Working
Free from corrosive or flammable gas and excessive conductive dusts G
environment
FX3G-1DA-BD
Working
< 2000 m*4
altitude
*4. If the pressure is higher than the atmospheric pressure, do not use 4DA-ADP.
The 4DA-ADP may malfunction.
-ADP
J
FX3U-4AD-PTW
-ADP
F-7
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4DA-ADP (4-channel Analog Output) 2.2 Power Supply Specifications
Item Specifications
D/A conversion circuit 24 V DC +20 %-15 %, 150 mA
driving power (It is necessary to connect a 24 V DC power line to the terminal block.)
5 V DC, 15 mA
Interface driving power (Since the internal power is supplied from the main unit of the FX Series, it is not
necessary to supply the power.)
Specifications
Item
Voltage output Current output
Analog output 0 V to 10 V DC 4 mA to 20 mA DC
range (External load: 5 kΩ to 1 MΩ) (External load: 500 Ω or less)
Digital input 12 bits, binary
Resolution 2.5 mV (10 V/4000) 4 μA (16 mA/4000)
• ±0.5 % (±50 mV) for 10 V full scale
(when ambient temperature is 25 °C±5 °C)
• ±1.0 % (±100 mV) for 10 V full scale
(when ambient temperature is 0 °C to 55
°C)
• ±0.5 % (±80 μA) for 16 mA full scale
(when ambient temperature is 25 °C±5 °C)
If the external load resistance (Rs) is less than
Total accuracy • ±1.0 % (±160 μA) for 16 mA full scale
5 kΩ, the value calculated from the following
(when ambient temperature is 0 °C to 55
formula will be added:
°C)
(Addition will be 100 mV per 1%.)
47100
-0.9 %
Rs+47
for 10 V full scale
• FX3U/FX3UC Series PLC : 200 μs (The data will be updated at every scan time.)
D/A conversion
• FX3S/FX3G/FX3GC Series PLC : 250 μs (The data will be updated at every scan time.)
time
→ For a detailed description of data update, refer to Section 2.4.
10V 20mA
Analog output
Analog output
Output
characteristics
4mA
• The photocoupler is used to insulate the analog output area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply line from the analog output area.
• Channels are not insulated from each other.
Numbers of I/O
0 point (This number is not related to the maximum number of input/output points of the PLC.)
points occupied
F-8
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4DA-ADP (4-channel Analog Output) 2.4 D/A Conversion Time
A
2.4 D/A Conversion Time
Common Items
This section describes the D/A conversion time.
FX3UC-4AD
FX3U-4AD
1. D/A conversion and special data register update timing
D/A conversion is performed at every scan time of the PLC.
During execution of the END instruction, the PLC writes the output setting data of the special data registers,
performs D/A conversion of the data, and updates the analog output data.
FX3U-4AD-ADP
Sequence
program
Digital value
D/A
conversion
writing
D
D/A conversion
FX3G-2AD-BD
250 s start command END instruction
/4ch
E
2. D/A conversion during PLC stop
FX3U-4DA
If the output holding function cancellation setting is enabled by the special device, the offset value will be
output.
If the output holding function cancellation setting is disabled, the output at switching from RUN to STOP will
be latched.
Just after power-on, however, the offset value will be output until operation begins.
F
3. D/A conversion speed (data update time)
FX3U-4DA-ADP
During execution of END instruction, the output setting digital data per of 4 channel will be subject to D/A
conversion which takes 250 μs, after which the analog data will be output.
END instruction execution time will be 250 μs.
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
F-9
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4DA-ADP (4-channel Analog Output) 2.4 D/A Conversion Time
FX3U-4DA-ADP FX3U-4DA-ADP
2nd 1st FX3G/FX3GC Series PLC
Sequence
program
Digital value
D/A writing
conversion
D/A conversion
250 s start command
/4ch
END instruction
D/A Digital value writing
conversion
D/A conversion
250 s/4ch start command
F-10
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4DA-ADP (4-channel Analog Output) 2.4 D/A Conversion Time
A
2.4.3 When connected to a FX3U/FX3UC PLC
Common Items
1. D/A conversion and special data register update timing
D/A conversion is performed at every scan time of the PLC.
During execution of the END instruction, the PLC writes the output setting data of the special data registers,
performs D/A conversion of the data, and updates the analog output data. B
FX3UC-4AD
FX3U-4AD
FX3U-4DA-ADP FX3U-4DA-ADP
FX3U/FX3UC Series PLC
n'th 1st
Sequence
program C
Digital value
FX3U-4AD-ADP
D/A writing
conversion
D/A conversion
200 s start command
/4ch
END instruction
D/A
conversion
Digital value writing D
D/A conversion
FX3G-2AD-BD
200 s/4ch start command
FX3U-4DA
output.
If the output holding function cancellation setting is disabled, the output at switching from RUN to STOP will
be latched.
Just after power-on, however, the offset value will be output until operation begins.
FX3U-4DA-ADP
During execution of the END instruction, data in all the connected adapters will be subject to D/A conversion
and then output (in the order of 1st adapter → 2nd adapter... 4th adapter).
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
F-11
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4DA-ADP (4-channel Analog Output)
3. Wiring
This chapter describes the 4DA-ADP wiring.
Observe the following caution to wire the 4DA-ADP.
WIRING PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before attempting wiring work.
Failure to do so may cause electric shock or damage to the product.
WIRING PRECAUTIONS
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn
out.
• Do not wire vacant terminals externally.
Doing so may damage the product.
• Perform class D grounding (grounding resistance: 100Ω or less) to the grounding terminal on the main unit.
Do not use common grounding with heavy electrical systems.
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
• Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise:
- Do not bundle the power line or shield of the analog input/output cable together with or lay it close to the main
circuit, high-voltage line, or load line.
Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
100mm (3.94") or more away from the main circuit, high-voltage line, or load line.
- Ground the shield of the analog input/output cable at one point on the signal receiving side.
However, do not use common grounding with heavy electrical systems.
• Make sure to properly wire to the terminal block (European type) in accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
- The disposal size of the cable end should follow the dimensions described in the manual.
- Tightening torque should follow the specifications in the manual.
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
F-12
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4DA-ADP (4-channel Analog Output) 3.1 Terminal Layout
A
3.1 Terminal Layout
Common Items
The terminals of the 4DA-ADP are arranged as follows:
FX3UC-4AD
FX3U-4AD
Signal Application
24+
C
External power
FX3U-4AD-ADP
24-
Grounding terminal
V1+
I1+ Channel 1 analog output
COM1
V2+ D
I2+ Channel 2 analog output
FX3G-2AD-BD
COM2
V3+
I3+ Channel 3 analog output
COM3
V4+
I4+ Channel 4 analog output E
FX3U-4DA
COM4
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
F-13
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4DA-ADP (4-channel Analog Output) 3.2 Applicable Cables and Terminal Tightening Torque
1. Cable
Applicable cable and tightening torque
Wire size Tightening
Termination
(stranded wire/solid wire) torque
0.3 mm2 to 0.5 mm2 • To connect a stranded cable, peel the cover off the cable
Single-wire and then twist the core before connection.
(AWG22 to 20)
• To connect a single-wire cable, just peel the cover off the
2-wire 0.3 mm2 (AWG22)×2 cable before connection.
0.22 to • Ferrule with insulation sleeve
0.3 mm2 to 0.5 mm2 0.25 N•m (recommended terminal)
Ferrule with (AWG22 to 20) AI 0.5-8WH : Manufactured by Phoenix Contact
insulation (Refer to the external • Caulking tool
sleeve view of ferrule shown in
CRIMPFOX 6*1 : Manufactured by Phoenix Contact
the following figure.)
(or CRIMPFOX 6T-F*2 : Manufactured by Phoenix Contact)
3. Tool
For tightening the terminal, use a commercially available small screwdriver
The head
having a straight form that is not widened toward the end as shown right. should be
straight.
Note:
If the diameter of screwdriver grip is too small, tightening torque will not be
able to be achieved. To achieve the appropriate tightening torque shown in 0.4mm 2.5mm
the table above, use the following screwdriver or an appropriate (0.01") (0.09")
replacement (grip diameter: approximately 25 mm (0.98")).
<Reference>
Manufacturer Model
Phoenix Contact SZS 0.4×2.5
F-14
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4DA-ADP (4-channel Analog Output) 3.3 Power Supply Line
A
3.3 Power Supply Line
Common Items
Connect the 24 V DC power supply line of the 4DA-ADP to the 24+ and 24- terminals of the terminal block.
FX3UC-4AD
FX3U-4AD
4DA-ADP FX3S/FX3G/FX3U 4DA-ADP FX3S/FX3G/FX3U
Series Series
+15V PLC (Main unit) +15V PLC (Main unit)
FX3U-4AD-ADP
24+ 24- 24V 0V
24+ 24-
Terminal
D
Terminal
FX3G-2AD-BD
block block
Fuse
Class-D Class-D
24V DC grounding grounding
FX3U-4DA
• Ground the "
grounding terminal of the PLC main unit.
• When using an external power supply, turn it ON at the same time with the main unit or earlier than the
main unit. When turning OFF the power, confirm the safety of the system, and then turn OFF the power of
the PLC (including special adapter) at the same time.
F
3.3.2 To connect to the FX3GC/FX3UC Series PLC
FX3U-4DA-ADP
Example of wiring of FX3UC Series PLC
4DA-ADP FX3UC Series PLC
(Main unit)
+15V
G
FX3G-1DA-BD
Power
connector H
FX3U-3A-ADP
I
Fuse
FX3U-4AD-PT
Class-D
24V DC grounding
For example of wiring of FX3GC Series PLC, refer to the following manual.
-ADP
• Ground the " " terminal to a class-D grounded power supply line (100 Ω or less) together with the
grounding terminal of the PLC main unit.
-ADP
F-15
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4DA-ADP (4-channel Analog Output) 3.4 Analog Output Line
Class-D
grounding
*1. Use 2-core shielded twisted pair cable for the analog output lines, and separate the analog output
lines from other power lines or inductive lines.
*2. For FX3S/FX3G/FX3U Series PLC (AC power type), the 24 V DC service power supply is also available.
*3. Ground the shielded wire at one point on the signal receiving side.
3.5 Grounding
Grounding should be performed as stated below.
• The grounding resistance should be 100 Ω or less.
• Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" as shown in the following
figure.
→ For details, refer to User’s Manual - Hardware Edition of the each PLC Series.
F-16
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4DA-ADP (4-channel Analog Output) 4.1 Writing of D/A Conversion Data
Common Items
4. Programming
This chapter describes how to create programs that can output the analog data using the 4DA-ADP. B
FX3UC-4AD
FX3U-4AD
4.1 Writing of D/A Conversion Data
1) The input digital data will be converted into analog data and then output to the terminals.
2) If data is stored in the special devices, the averaging time can be set, and the output mode can be C
specified.
FX3U-4AD-ADP
3) Special auxiliary relays (10 points) and special data registers (10 points) are assigned automatically
starting from the adapter nearest the main unit.
→ For a detailed description of special device assignment, refer to Section 4.2.
• FX3S Series PLC
Communi-
D
FX3G-2AD-BD
cation
FX3U-4DA special FX3S-CNV
-ADP adapter -ADP FX3S Series PLC
Special devices
Special auxiliary relays:
D/A
M8280 to M8289
Special data registers:
Sequence E
Program
FX3U-4DA
D8280 to D8289
FX3U-4DA-ADP
FX3U-4DA special FX3U-4DA
-ADP adapter -ADP FX3G/FX3GC Series PLC*2
2nd*1 1st
Special devices
Special auxiliary relays:
D/A
M8280 to M8289 G
Special data registers:
FX3G-1DA-BD
D8280 to D8289 Sequence
Program
Special auxiliary relays:
M8290 to M8299
D/A Special data registers:
D8290 to D8299
H
FX3U-3A-ADP
The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
next adapter as the 2nd analog special adapter. However, in this case, do not include the connector
conversion adapter and the communication special adapter.
*1. The second special adapter is not available in the FX3G Series PLC (14-point and 24-point type).
*2. A connector conversion adapter is required to connect the FX3U-4DA-ADP to the FX3G Series PLC. I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
F-17
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4DA-ADP (4-channel Analog Output) 4.1 Writing of D/A Conversion Data
The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
next adapter as the 2nd analog special adapter, and so on. In this case, however, do not include the high-
speed input/output special adapter, communication special adapter, and the CF card special adapter.
*1. An expansion board is required to connect the FX3U-4DA-ADP to the FX3U/FX3UC-32MT-LT(-2) PLC.
F-18
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4DA-ADP (4-channel Analog Output) 4.2 List of Special Devices
A
4.2 List of Special Devices
Common Items
If 4DA-ADP is connected, special devices will be assigned automatically as shown in the following table:
• FX3S Series PLC
R: Read / W: Write
Special
B
Device number Description Attribute Reference
FX3UC-4AD
FX3U-4AD
device
M8280 Switches the output mode of channel 1. R/W
M8281 Switches the output mode of channel 2. R/W Section
M8282 Switches the output mode of channel 3. R/W 4.3
FX3U-4AD-ADP
relay M8285 Sets the cancel of the channel-2 output holding function. R/W Section
M8286 Sets the cancel of the channel-3 output holding function. R/W 4.4
M8287 Sets the cancel of the channel-4 output holding function. R/W
M8288 to M8289
D8280
Unused (Do not use.)
Channel-1 output setting data
-
R/W
-
D
FX3G-2AD-BD
D8281 Channel-2 output setting data R/W Section
D8282 Channel-3 output setting data R/W 4.5
Special D8283 Channel-4 output setting data R/W
data D8284 to D8287 Unused (Do not use.) - -
register
Section E
D8288 Error status R/W
4.6
FX3U-4DA
Section
D8289 Model code = 2 R
4.7
FX3U-4DA-ADP
Description Attribute Reference
device 1st 2nd
M8280 M8290 Switches the output mode of channel 1. R/W
M8281 M8291 Switches the output mode of channel 2. R/W Section
M8282 M8292 Switches the output mode of channel 3. R/W 4.3
M8283 M8293 Switches the output mode of channel 4. R/W
G
Special
FX3G-1DA-BD
M8284 M8294 Sets the cancel of the channel-1 output holding function. R/W
auxiliary
relay M8285 M8295 Sets the cancel of the channel-2 output holding function. R/W Section
M8286 M8296 Sets the cancel of the channel-3 output holding function. R/W 4.4
M8287 M8297 Sets the cancel of the channel-4 output holding function. R/W
M8288 to M8298 to
Unused (Do not use.) - -
H
M8289 M8299
FX3U-3A-ADP
Special
D8283
D8284 to
D8293 Channel-4 output setting data
D8294 to
R/W
I
data Unused (Do not use.) - -
FX3U-4AD-PT
Section
D8289 D8299 Model code = 2 R
4.7
J
FX3U-4AD-PTW
-ADP
F-19
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4DA-ADP (4-channel Analog Output) 4.2 List of Special Devices
F-20
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4DA-ADP (4-channel Analog Output) 4.3 Switching of Output Mode
A
4.3 Switching of Output Mode
Common Items
Turn the special auxiliary relay on/off to switch the output mode of 4DA-ADP between the current output
mode and the voltage output mode.
To switch the output mode, use the following special auxiliary relays:
• FX3S Series PLC B
FX3UC-4AD
FX3U-4AD
Special auxiliary
Description
relay
M8280 Switches the output mode of channel 1
M8281 Switches the output mode of channel 2 OFF:Voltage output
M8282 Switches the output mode of channel 3 ON :Current output C
FX3U-4AD-ADP
M8283 Switches the output mode of channel 4
FX3G-2AD-BD
M8280 M8290 Switches the output mode of channel 1
M8281 M8291 Switches the output mode of channel 2 OFF:Voltage output
M8282 M8292 Switches the output mode of channel 3 ON :Current output
M8283 M8293 Switches the output mode of channel 4
FX3U-4DA
Special auxiliary relay
Description
1st 2nd 3rd 4th
M8260 M8270 M8280 M8290 Switches the output mode of channel 1
M8261 M8271 M8281 M8291 Switches the output mode of channel 2 OFF:Voltage output
F
M8262 M8272 M8282 M8292 Switches the output mode of channel 3 ON :Current output
FX3U-4DA-ADP
M8263 M8273 M8283 M8293 Switches the output mode of channel 4
FX3G-1DA-BD
1) To switch the channel output mode of 2) To switch the output mode of channel 2
channel 1 of the 1st analog special of the 1st analog special adapter to the
adapter to the voltage output mode: current output mode:
M8001 M8000
M8260 M8261
Normally OFF Normally ON H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
F-21
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4DA-ADP (4-channel Analog Output) 4.4 Output Holding Function Cancellation Setting
F-22
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4DA-ADP (4-channel Analog Output) 4.5 Output Setting Data
A
4.5 Output Setting Data
Common Items
Numeric data type: Decimal (K)
The 4DA-ADP performs D/A conversion on the output setting data (digital data) into analog data, and outputs
the analog data.
Use the special data registers shown in the following table for the output setting data: B
FX3UC-4AD
FX3U-4AD
• FX3S Series PLC
Special data register Description
D8280 Channel-1 output setting data
D8281 Channel-2 output setting data
D8282 Channel-3 output setting data
C
FX3U-4AD-ADP
D8283 Channel-4 output setting data
FX3G-2AD-BD
D8281 D8291 Channel-2 output setting data
D8282 D8292 Channel-3 output setting data
D8283 D8293 Channel-4 output setting data
FX3U-4DA
Special data register
Description
1st 2nd 3rd 4th
D8260 D8270 D8280 D8290 Channel-1 output setting data
D8261 D8271 D8281 D8291 Channel-2 output setting data
D8262 D8272 D8282 D8292 Channel-3 output setting data F
FX3U-4DA-ADP
D8263 D8273 D8283 D8293 Channel-4 output setting data
FX3G-1DA-BD
Normally ON the 1st analog special adapter.
H
Using the indicator or the sequence program, input the digital data to be subject to D/A conversion (to be
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
F-23
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4DA-ADP (4-channel Analog Output) 4.6 Error Status
1. Description of setting
If an error is detected on 4DA-ADP, the error status data will be stored in the corresponding special data
register.
The following table shows the special data registers that store the error status data:
• FX3S Series PLC
Special data register Description
D8288 Stores the error status data.
Bit Description
b0 Channel-1 output data setting error
b1 Channel-2 output data setting error
b2 Channel-3 output data setting error
b3 Channel-4 output data setting error
b4 EEPROM error
b5 Unused
b6 4DA-ADP hardware error (Power supply error included)*1
b7 to b15 Unused
F-24
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4DA-ADP (4-channel Analog Output) 4.6 Error Status
A
2. Program Example 1 (For FX3S/FX3G/FX3GC/FX3U/FX3UC Series PLC)
Common Items
M8000 FNC 12 D8288 K4M0
MOV
Normally
ON
M0
Y000 Channel-1 output data setting error in
B
FX3UC-4AD
FX3U-4AD
3rd*1 adapter.
M1
Y001 Channel-2 output data setting error in
3rd*1 adapter.
M2
Y002 Channel-3 output data setting error in
C
FX3U-4AD-ADP
3rd*1 adapter.
M3
Y003 Channel-4 output data setting error in
3rd*1 adapter.
M4
Y004 EEPROM error in the 3rd*1 adapter. D
FX3G-2AD-BD
*1. "1st" for the FX3S/FX3G/FX3GC PLC.
FX3U-4DA
Y000 Channel-1 output data setting error in
1st adapter.
D8268.1
Y001 Channel-2 output data setting error in
1st adapter.
F
D8268.2
FX3U-4DA-ADP
Y002 Channel-3 output data setting error in
1st adapter.
D8268.3
Y003 Channel-4 output data setting error in
1st adapter.
G
D8268.4
FX3G-1DA-BD
Y004 EEPROM error in 1st adapter.
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
F-25
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4DA-ADP (4-channel Analog Output) 4.7 Model Code
Initial value: K2
Numeric data type: Decimal (K)
1. Description of setting
When the 4DA-ADP is connected, model code "2" is stored in the corresponding special data register.
The following table shows the special data registers that store the model code:
• FX3S Series PLC
Special data register Description
D8289 Model code
M8000
M8281 Sets the output mode of channel 2 to the current
output mode (4 mA to 20 mA).
Normally
ON
M8285 Cancels the output holding function for channel 2.
M8000
FNC 12 D100 D8280 Performs D/A conversion with the digital data stored
Normally MOV in D100 for channel 1.
ON
FNC 12 D101 D8281 Performs D/A conversion with the digital data stored
MOV in D101 for channel 2.
Using the indicator or the sequence program, input the digital data to be subject to D/A conversion (to be
output as analog data) in D100 and D101.
*1. "1st" for the FX3S/FX3G/FX3GC PLC.
F-26
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Changing of Output Characteristics
FX3U-4DA-ADP (4-channel Analog Output) 5.1 Example: Changing of Voltage Output Characteristics
Common Items
5. Changing of Output Characteristics
Use the scaling instruction (SCL/FNC259) for the FX3U/FX3UC Series PLC to change the output B
characteristics.
FX3UC-4AD
FX3U-4AD
FX3S/FX3G/FX3GC Series PLCs do not support the scaling instruction. Use sequence programs to change the
output characteristics.
→ For a detailed description of scaling instruction, refer to the FX3S/FX3G/FX3GC/FX3U/FX3UC Series
Programming Manual - Basic & Applied Instruction.
FX3U-4AD-ADP
This section describes an example of a program that can change the digital value range from 400 to 2000
(when analog output range is 1 to 5 V) to 0 to 10000.
A specified digital value is inputted into D100.
1. Output characteristics
Voltage output characteristics
D
subject to D/A conversion
Digital value characteristics
FX3G-2AD-BD
(product specifications) Specified digital output
to be changed
value to be actually
10V
Analog output
Y-axis
E
5V 2000
FX3U-4DA
(5V)
1V 400
(1V)
X-axis
0 400 2000 4000
Digital value input
0 10000
Desired digital value (D100)
F
FX3U-4DA-ADP
2. Example of program 1 (For FX3U/FX3UC Series PLC)
For example, create the following program to change the digital output of the 1st analog special adapter.
M8001
M8260 Sets the output mode of channel 1 to the voltage output
Normally
OFF
mode. G
FX3G-1DA-BD
M8264 Sets the output holding function for channel 1.
M8002
FNC 12 Program for setting scaling instruction data table
K2 D50
Initial MOV
pulse
FNC 12
Item
Number of points
Description
Sets the number of points.
Value Device
2 D50
H
K0 D51
FX3U-3A-ADP
If the input digital value for the D/A conversion is out of the data table range specified by the SCL instruction
the PLC will detect an operation error (error code: K6706).
-ADP
F-27
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Changing of Output Characteristics
FX3U-4DA-ADP (4-channel Analog Output) 5.1 Example: Changing of Voltage Output Characteristics
FNC230 D100 K0 FNC237 D100 K10000 M10 Check to make sure the digital
LD>= AND<= value (D100) is in range.
M10
FNC 22 D100 K1600 D101
MUL
F-28
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
FX3U-4DA-ADP (4-channel Analog Output) 6.1 PLC Version Number Check
Common Items
6. Troubleshooting
This chapter describes the troubleshooting methods and error status. B
If analog data is not output, or if the proper analog value is not output, check the following items:
FX3UC-4AD
FX3U-4AD
• Version number of PLC
• Wiring
• Special devices
• Programs C
• Error status
FX3U-4AD-ADP
6.1 PLC Version Number Check
• Any versions (from Ver. 1.00 (initial version) to the latest version) of the FX3S Series are compatible. D
• Any versions (from Ver. 1.00 (initial version) to the latest version) of the FX3G Series are compatible.
FX3G-2AD-BD
• Any versions (from Ver. 1.40 (initial version) to the latest version) of the FX3GC Series are compatible.
• Any versions (from Ver. 2.20 (initial version) to the latest version) of the FX3U Series are compatible.
• Check the version number of FX3UC Series. The version number should be 1.20 or later.
→ For a detailed description of the version check method,
refer to A. Common Items Subsection 5.1.2.
E
FX3U-4DA
6.2 Wiring Check
Check the following items for wiring:
F
1. Power
FX3U-4DA-ADP
The 4DA-ADP needs driving power. Verify that the power supply line is properly connected. Also check that
the POWER indicator lamp of the 4DA-ADP is on.
FX3G-1DA-BD
→ For a detailed description of wiring, refer to Chapter 3.
3. Error status
-ADP
F-29
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
FX3U-4DA-ADP (4-channel Analog Output) 6.4 Program Check
Bit Description
b0 Channel-1 output data setting error
b1 Channel-2 output data setting error
b2 Channel-3 output data setting error
b3 Channel-4 output data setting error
b4 EEPROM error
b5 Unused
b6 4DA-ADP hardware error (Power supply error included)*1
b7 to b15 Unused
F-30
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
FX3U-4DA-ADP (4-channel Analog Output) 6.5 Error Status Check
A
3. 4DA-ADP hardware error (b6)
Common Items
1) Description of error
The 4DA-ADP is not operating properly.
2) Remedy
Check that the 24 V DC power is properly supplied to the 4DA-ADP. Also check that the 4DA-ADP is
correctly connected to the PLC. B
If the problem cannot be solved even after the above check, please contact your local Mitsubishi Electric
FX3UC-4AD
FX3U-4AD
representative.
FX3U-4AD-ADP
D
FX3G-2AD-BD
E
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
F-31
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
FX3U-4DA-ADP (4-channel Analog Output) 6.5 Error Status Check
MEMO
F-32
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3G-1DA-BD (1-channel Analog Output)
Common Items
B
FX3UC-4AD
FX3U-4AD
FX3S/FX3G/FX3GC/FX3U/FX3UC Series
Programmable Controllers C
FX3U-4AD-ADP
User's Manual [Analog Control Edition]
FX3G-2AD-BD
E
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
Foreword
This manual describes the specifications, wiring, and operation method for the FX3G-1DA-BD analog output
expansion board (1-channel analog output) and should be read and understood before attempting to install or
use the unit.
I
FX3U-4AD-PT
Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
it to the end user.
-ADP
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
rights which may occur as a result of using the contents noted in this manual.
J
FX3U-4AD-PTW
G-1
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3G-1DA-BD (1-channel Analog Output)
G-2
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3G-1DA-BD (1-channel Analog Output) 1.1 Outline of Functions
Common Items
1. Outline
This chapter outlines the FX3G-1DA-BD (referred to as 1DA-BD). B
FX3UC-4AD
FX3U-4AD
1.1 Outline of Functions
The FX3G-1DA-BD is an analog expansion board. Which is connectable with the FX3S/FX3G Series PLC to
output the voltage/current data for up to 1 channel.
C
1) Only 1 1DA-BD unit can be connected to the FX3S Series PLC.
FX3U-4AD-ADP
Up to 2 1DA-BD units can be connected to the FX3G Series PLC (40-point and 60-point type).
Only 1 1DA-BD unit can be connected to the FX3G Series PLC (14-point and 24-point type).
(Including other analog expansion boards, analog special adapters).
2) Either "voltage output" or "current output" can be specified.
3) The D/A conversion results will be automatically output as the values to the special data register of the D
FX3S/FX3G Series PLC.
FX3G-2AD-BD
• FX3S Series PLC
Only 1
Number of connectable E
including other analog expansion units
FX3U-4DA
boards, analog special adapters. FX3S Series PLC
FX3U-4DA-ADP
Connected to the option connector
FX3G-1DA-BD
Contents H
Output mode Transfer direction
FX3U-3A-ADP
J
FX3U-4AD-PTW
-ADP
G-3
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3G-1DA-BD (1-channel Analog Output) 1.1 Outline of Functions
Inverter, etc.
Refer to the system configuration shown in the User's Manual - Hardware Edition to check the number of connectable
units and to configure the entire system.
*1. Only 1 analog board can be connected to the FX3G Series PLC (14-point and 24-point type).
G-4
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3G-1DA-BD (1-channel Analog Output) 1.2 Setup Procedure Before Starting Operation
A
1.2 Setup Procedure Before Starting Operation
Common Items
Before starting analog output using the 1DA-BD, follow the procedure below to set up the system:
FX3G-1DA-BD B
FX3UC-4AD
FX3U-4AD
Refer to Chapter 1.
FX3U-4AD-ADP
Specifications check Specifications:
• Operation environment
• Performance specifications
Refer to the common • Output characteristics
pages.
FX3G-2AD-BD
(Refer to the common pages for analog control.)
• Selection of units
Refer to Chapter 3.
Wiring Wiring:
• Power supply line
• Analog output line E
FX3U-4DA
Refer to Chapter 4.
Programming:
Programming
• Details of special devices
• Examples of basic programs
Refer to Chapter 5.
F
Changing of output characteristics Method of output characteristics change
FX3U-4DA-ADP
If the error status data or the output analog value G
is abnormal, refer to Chapter 6 "Troubleshooting."
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
G-5
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3G-1DA-BD (1-channel Analog Output) 1.3 Connectable PLCs and Version Number
1. Version check
The PLC version can be checked by reading the last three digits of device D8001 or D8101.
→ For a detailed description of the version check,
refer to A. Common Items Subsection 5.1.2.
1. English versions
Model name Media model name Applicable version Remarks
FX3S PLC
GX Works2 SWDNC-GXW2-E Ver. 1.492N or later -
FX-30P Ver. 1.50 or later -
FX3G PLC
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer SWD5C-GPPW-E Ver. 8.72A or later -
FX-30P Ver. 1.00 or later
2. Japanese versions
Model name Media model name Applicable version Remarks
FX3S PLC
GX Works2 SWDNC-GXW2-J Ver. 1.492N or later
-
FX-30P Ver. 1.50 or later
FX3G PLC
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
GX Developer SWD5C-GPPW-J Ver. 8.72A or later -
FX-30P Ver. 1.00 or later
Point
• It is possible to create programs in FX3S PLC using programming tools of inapplicable versions by
selecting "FX3G" as the alternative model. However, memory capacity setting of the PLC parameter must
be set to 4000 steps or less.
G-6
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3G-1DA-BD (1-channel Analog Output) 2.1 Generic Specifications
Common Items
2. Specifications
This chapter describes the general and performance specifications for 1DA-BD. B
FX3UC-4AD
FX3U-4AD
2.1 Generic Specifications
Item Specifications C
FX3U-4AD-ADP
Ambient 0 to 55 °C (32 to 131 °F) when operating
temperature -25 to 75 °C (-13 to 167 °F) when stored
Relative
5 to 95 %RH (no condensation) when operating
humidity
Frequency Acceleration Half amplitude D
(Hz) (m/s2) (mm)
FX3G-2AD-BD
10 times of testing in
Vibration 10 to 57 - 0.035 each direction (X-, Y-,
DIN Rail Mounting
resistance*1 57 to 150 4.9 - and Z-axis directions)
(Total: 80 min, each)
10 to 57 − 0.075
Direct Mounting
−
Shock
57 to 150 9.8
E
m/s2
FX3U-4DA
147 Acceleration, Action time: 11 ms, 3 times by half-sine pulse in each direction X, Y, and Z
resistance*1
Noise Using noise simulator of:
resistance Noise voltage: 1,000 Vp-p / Noise width: 1 μs / Rise: 1 ns / Cycle: 30 to 100 Hz
Class D grounding (grounding resistance: 100 Ω or less)
Grounding
<Common grounding with a heavy electrical system is not allowed.>*2 F
Working
FX3U-4DA-ADP
Free from corrosive or flammable gas and excessive conductive dusts
environment
Working
altitude < 2000 m*3
FX3G-1DA-BD
PLC Other PLC Other PLC Other
equipment equipment equipment
*3. If the pressure is higher than the atmospheric pressure, do not use 1DA-BD.
The 1DA-BD may malfunction.
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
G-7
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3G-1DA-BD (1-channel Analog Output) 2.2 Performance Specifications
Specifications
Item
Voltage output Current output
Analog output 0 V to 10 V DC 4 mA to 20 mA DC
range (External load: 2 kΩ to 1 MΩ) (External load: 500 Ω or less)
Digital input 12 bits, binary 11 bits, binary
Resolution 2.5 mV (10 V/4000) 8 μA (16 mA/2000)
• ±0.5 % (±50 mV) for 10 V full scale
(when ambient temperature is 25 °C±5 °C)
• ±1.0 % (±100 mV) for 10 V full scale
(when ambient temperature is 0 °C to 55 °C)
• ±0.5 % (±80 μA) for 16 mA full scale
Shipment adjustment is carried out by external (when ambient temperature is 25 °C±5 °C)
Total accuracy load resistance 2 kΩ. • ±1.0 % (±160 μA) for 16 mA full scale
If external load resistance becomes larger (when ambient temperature is 0 °C to 55
than 2 kΩ, the output voltage will increase °C)
slightly.
When the load is 1 MΩ, the output voltage
becomes about 2 % higher than the correct
value.
D/A conversion 60 μs (The data will be updated at every scan time.)
time → For a detailed description of data update, refer to Section 2.3.
10V 20mA
Analog output
Analog output
Output
characteristics
4mA
Caution:
An area of dead band is located in the region
of 0 V. Therefore the output analog value may
not represent the digital value accurately.
Insulation method • The analog output area is not insulated from the PLC.
Numbers of I/O
0 point (This number is not related to the maximum number of input/output points of the PLC.)
points occupied
G-8
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3G-1DA-BD (1-channel Analog Output) 2.3 D/A Conversion Time
A
2.3 D/A Conversion Time
Common Items
This section describes the D/A conversion time.
FX3UC-4AD
FX3U-4AD
1. D/A conversion and special data register update timing
D/A conversion is performed at every scan time of the PLC.
During execution of the END instruction, the PLC writes the output setting data of the special data registers,
performs D/A conversion of the data, and updates the analog output data.
FX3U-4AD-ADP
Sequence Program
D
END instruction
FX3G-2AD-BD
D/A conversion Digital value
start command writing E
FX3U-4DA
D/A
conversion
60 s
/1ch
F
FX3U-4DA-ADP
FX3G-1DA-BD
FX3G-1DA-BD
be latched.
Just after power-on, however, the offset value will be output until operation begins.
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
G-9
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3G-1DA-BD (1-channel Analog Output) 2.3 D/A Conversion Time
Sequence Program
END instruction
D/A D/A
conversion conversion
60 s 60 s
/1ch /1ch
FX3G-1DA-BD FX3G-1DA-BD
Board A Board B
G-10
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3G-1DA-BD (1-channel Analog Output)
Common Items
3. Wiring
This chapter describes the 1DA-BD wiring. B
Observe the following caution to wire the 1DA-BD.
FX3UC-4AD
FX3U-4AD
WIRING PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before attempting wiring work.
Failure to do so may cause electric shock or damage to the product. C
FX3U-4AD-ADP
WIRING PRECAUTIONS
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn
out.
D
FX3G-2AD-BD
• Do not wire vacant terminals externally.
Doing so may damage the product.
• Perform class D grounding (grounding resistance: 100Ω or less) to the grounding terminal on the main unit.
Do not use common grounding with heavy electrical systems.
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions. E
• Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise:
FX3U-4DA
- Do not bundle the power line or shield of the analog input/output cable together with or lay it close to the main
circuit, high-voltage line, or load line.
Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
100mm (3.94") or more away from the main circuit, high-voltage line, or load line.
- Ground the shield of the analog input/output cable at one point on the signal receiving side.
However, do not use common grounding with heavy electrical systems. F
• Make sure to properly wire to the terminal block (European type) in accordance with the following precautions.
FX3U-4DA-ADP
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
- The disposal size of the cable end should follow the dimensions described in the manual.
- Tightening torque should follow the specifications in the manual.
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends. G
- Do not connect more than the specified number of wires or electric wires of unspecified size.
FX3G-1DA-BD
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
G-11
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3G-1DA-BD (1-channel Analog Output) 3.1 Terminal Layout
Signal • • V+ I+ VI-
Unused Output COM
Application
terminal terminal terminal
G-12
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3G-1DA-BD (1-channel Analog Output) 3.2 Applicable Cables and Terminal Tightening Torque
A
3.2 Applicable Cables and Terminal Tightening Torque
Common Items
Use the following cables to connect with the counterpart equipment. Terminate the cable end as shown below.
1. Cable
Applicable cable and tightening torque
B
FX3UC-4AD
FX3U-4AD
Wire size Tightening
Termination
(stranded wire/solid wire) torque
0.3 mm2 to 0.5 mm2 • To connect a stranded cable, peel the cover off the cable
Single-wire and then twist the core before connection.
(AWG22 to 20)
2-wire 0.3 mm2 (AWG22)×2
• To connect a single-wire cable, just peel the cover off the
cable before connection.
C
FX3U-4AD-ADP
0.22 to • Ferrule with insulation sleeve
0.3 mm2 to 0.5 mm2 0.25 N•m (recommended terminal)
Ferrule with (AWG22 to 20) AI 0.5-8WH : Manufactured by Phoenix Contact
insulation (Refer to the external • Caulking tool
sleeve view of ferrule shown in
CRIMPFOX 6*1 : Manufactured by Phoenix Contact
the following figure.)
(or CRIMPFOX 6T-F*2 : Manufactured by Phoenix Contact) D
FX3G-2AD-BD
*1. Old model name : CRIMPFOX ZA 3
*2. Old model name : CRIMPFOX UD 6
FX3U-4DA
Do not tighten terminal screws with a torque outside the above-mentioned range. Failure to do so may cause
equipment failures or malfunctions.
• To directly terminate the end of a stranded/single-wire cable: • Stranded wire/solid wire
- Twist the end of the stranded cable so that the "barbed wires"
cannot protrude.
- Do not solder-plate the end of the cable.
F
FX3U-4DA-ADP
9mm
(0.35")
• To terminate cable end using a ferrule with insulation sleeve: • Ferrule with insulation sleeve
If the cable sheath is too thick, it may be difficult to insert the cable into Insulation sleeve Contact area
the insulation sleeve. For this reason, select an appropriate cable while
referring to the external view.
(Crimp area)
G
FX3G-1DA-BD
<Reference> 8mm (0.31")
Manufacturer Model Caulking tool 2.6mm 14mm
(0.1")
CRIMPFOX 6*3 (0.55")
Phoenix Contact AI 0.5-8WH
(or CRIMPFOX 6T-F*4)
3. Tool
For tightening the terminal, use a commercially available small screwdriver
The head
having a straight form that is not widened toward the end as shown right. should be
straight. I
Note:
FX3U-4AD-PT
If the diameter of screwdriver grip is too small, tightening torque will not be
able to be achieved. To achieve the appropriate tightening torque shown in 0.4mm 2.5mm
the table above, use the following screwdriver or an appropriate (0.01") (0.09")
-ADP
G-13
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3G-1DA-BD (1-channel Analog Output) 3.3 Analog Output Line
*1. Use 2-core shielded twisted pair cable for the analog output lines, and separate the analog output
lines from other power lines or inductive lines.
*2. Ground the shielded wire at one point on the signal receiving side.
3.4 Grounding
Grounding should be performed as stated below.
• The grounding resistance should be 100 Ω or less.
• Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" as shown in the following
figure.
→ For details, refer to User’s Manual - Hardware Edition of the each PLC Series.
G-14
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3G-1DA-BD (1-channel Analog Output) 4.1 Writing of D/A Conversion Data
Common Items
4. Programming
This chapter describes how to create programs that can output the analog data using the 1DA-BD. B
FX3UC-4AD
FX3U-4AD
4.1 Writing of D/A Conversion Data
1) The input digital data will be converted into analog data and then output to the terminals.
2) If data is stored in the special devices, the averaging time can be set, and the output mode can be C
specified.
FX3U-4AD-ADP
3) In the FX3G Series PLC (40-point or 60-point type), special auxiliary relays (10 points) and special data
registers (10 points) are assigned to each analog expansion board, board A and B connected to option
connector 1 and 2 respectively, in that order.
In the FX3G Series PLC (14-point or 24-point type) and FX3S Series PLC, special auxiliary relays (10
points) and special data registers (10 points) are assigned.
→ For a detailed description of special device assignment, refer to Section 4.2.
D
FX3G-2AD-BD
• FX3S Series PLC
FX3S Series PLC
Sequence Program
E
FX3U-4DA
Special auxiliary relays:
M8260 to M8269
Special data register:
D8260 to D8269
Option connector F
FX3U-4DA-ADP
D/A
FX3G-1DA-BD
FX3G-1DA-BD
Sequence Program
The analog expansion board connected to option connector 1 is regarded as the "board A", and the analog
expansion board connected to option connector 2 is regarded as the "board B".
-ADP
*1. Board B is not available in the FX3G Series PLC (14-point and 24-point type).
J
FX3U-4AD-PTW
-ADP
G-15
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3G-1DA-BD (1-channel Analog Output) 4.2 List of Special Devices
G-16
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3G-1DA-BD (1-channel Analog Output) 4.4 Output Holding Function Cancellation Setting
A
4.4 Output Holding Function Cancellation Setting
Common Items
This setting can hold the analog data output or to output the offset data (0 V for voltage output mode, 4 mA for
current output mode) when the PLC stops.
To cancel or set the output holding function, use the following special auxiliary relays:
• FX3S Series PLC B
FX3UC-4AD
FX3U-4AD
Special auxiliary relay Description
OFF: Holds the analog data output just before
Cancel output holding function
M8264 stop of the PLC.
setting.
ON : Outputs the offset data at stop of the PLC.
FX3U-4AD-ADP
Special auxiliary relay
Description
Board A Board B
OFF: Holds the analog data output just before
Cancel output holding function
M8264 M8274 stop of the PLC.
setting.
ON : Outputs the offset data at stop of the PLC.
D
FX3G-2AD-BD
1. Program Example (For FX3G Series PLC)
To set or cancel the output holding function, create a sequence program as follows:
FX3U-4DA
Normally OFF
FX3U-4DA-ADP
The 1DA-BD performs D/A conversion on the output setting data (digital data) into analog data, and outputs
the analog data.
Use the special data registers shown in the following table for the output setting data:
• FX3S Series PLC
Special data register Description G
FX3G-1DA-BD
D8260 Output setting data
Using the indicator or the sequence program, input the digital data to be subject to D/A conversion (to be
output as analog data) in D100 and D101. J
FX3U-4AD-PTW
-ADP
G-17
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3G-1DA-BD (1-channel Analog Output) 4.6 Error Status
1. Description of setting
If an error is detected on 1DA-BD, the error status data will be stored in the corresponding special data
register.
The following table shows the special data registers that store the error status data:
• FX3S Series PLC
Special data register Description
D8268 Stores the error status data.
Bit Description
b0 Output data setting error
b1 to b3 Unused
b4 EEPROM error
b5 to b15 Unused
Initial value: K4
Numeric data type: Decimal (K)
1. Description of setting
When the 1DA-BD is connected, model code "4" is stored in the corresponding special data register.
The following table shows the special data registers that store the model code:
• FX3S Series PLC
Special data register Description
D8269 Model code
G-18
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3G-1DA-BD (1-channel Analog Output) 4.8 Basic Program Example
A
4.8 Basic Program Example
Common Items
Create the following basic program example to output D/A converted analog data.
• For FX3G Series PLC
The following program will set the board A to the voltage output mode and board B to current output mode,
and will set digital data in D100 and D101 for D/A conversion. B
FX3UC-4AD
FX3U-4AD
M8001
M8260 Sets the output mode of the board A to the voltage
output mode (0 V to 10 V).
Normally
OFF
M8264 Sets the output holding function for the board A.
M8000
Sets the output mode of the board B to the current
C
M8270
FX3U-4AD-ADP
Normally output mode (4 mA to 20 mA).
ON
M8274 Cancels the output holding function for the board B.
M8000
FNC 12 Performs D/A conversion with the digital data stored
Normally MOV
D100 D8260
in D100 for the board A. D
ON
FX3G-2AD-BD
FNC 12 D101 D8270 Performs D/A conversion with the digital data stored
MOV in D101 for the board B.
Using the indicator or the sequence program, input the digital data to be subject to D/A conversion (to be
output as analog data) in D100 and D101.
E
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
G-19
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Changing of Output Characteristics
FX3G-1DA-BD (1-channel Analog Output) 5.1 Example: Changing of Voltage Output Characteristics
1. Output characteristics
Voltage output characteristics
Y-axis
5V 2000
(5V)
1V 400
(1V)
0 400 2000 4000 X-axis
0 10000
Digital value input
Desired digital value (D100)
M8001
M8260 Sets the output mode of 1st board
Normally to the voltage output mode (0 V to 10 V).
OFF
FNC230 D100 K0 FNC237 D100 K10000 M10 Check to make sure the digital
LD>= AND<= value (D100) is in range.
M10
FNC 22
D100 K1600 D101
MUL
FNC 23
D101 K10000 D103
DDIV Calculation for changing output
characteristics.
FNC 20 Stores the operation result in D8260.
D103 K400 D107
ADD
G-20
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
FX3G-1DA-BD (1-channel Analog Output) 6.1 PLC Version Number Check
Common Items
6. Troubleshooting
This chapter describes the troubleshooting methods and error status. B
If analog data is not output, or if the proper analog value is not output, check the following items:
FX3UC-4AD
FX3U-4AD
• Version number of PLC
• Installation
• Wiring
• Special devices C
• Programs
FX3U-4AD-ADP
• Error status
FX3G-2AD-BD
• Check the version number of the FX3G Series PLC. The version number should be 1.10 or later.
→ For a detailed description of the version check method,
refer to A. Common Items Subsection 5.1.2.
FX3U-4DA
Confirm that the 1DA-BD is attached correctly to the main unit. Confirm also that the POW indicator lamp of
the 1DA-BD is lit correctly.
For installation details, refer to the following manual.
→ Refer to FX3S User’s Manual-Hardware Edition.
→ Refer to FX3G User’s Manual-Hardware Edition. F
FX3U-4DA-ADP
6.3 Wiring Check
Check the following items for wiring:
FX3G-1DA-BD
Use the 2-core twisted shielded pair cable for the analog output line. In addition, be sure to separate the
analog output line from other power lines or inductive lines.
→ For a detailed description of wiring, refer to Chapter 3.
Check whether the special devices for the 1DA-BD are being used correctly:
3. Error status J
Check that no error is detected in the 1DA-BD.
FX3U-4AD-PTW
If an error is detected, check the details of the error, and then check the wiring and programs.
→ For a detailed description of special devices, refer to Chapter 4.
-ADP
G-21
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
FX3G-1DA-BD (1-channel Analog Output) 6.5 Program Check
Bit Description
b0 Output data setting error
b1 to b3 Unused
b4 EEPROM error
b5 to b15 Unused
To solve the problem, refer to the troubleshooting method described below:
G-22
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output)
Common Items
B
FX3UC-4AD
FX3U-4AD
FX3S/FX3G/FX3GC/FX3U/FX3UC Series
Programmable Controllers C
FX3U-4AD-ADP
User's Manual [Analog Control Edition]
FX3G-2AD-BD
E
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
Foreword
This manual describes the specifications, wiring, and operation methods for the FX3U-3A-ADP analog special
adapter (2-channel analog input, 1-channel analog output) and should be read and understood before I
attempting to install or use the unit.
FX3U-4AD-PT
Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
it to the end user.
-ADP
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property J
rights which may occur as a result of using the contents noted in this manual.
FX3U-4AD-PTW
H-1
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output)
H-2
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output) 1.1 Outline of Functions
Common Items
1. Outline
This chapter outlines the FX3U-3A-ADP (referred to as the 3A-ADP). B
FX3UC-4AD
FX3U-4AD
1.1 Outline of Functions
The analog special adapter FX3U-3A-ADP receives voltage/current data from 2 channels and outputs voltage/
current data from 1 channel when connected to a FX3S/FX3G/FX3GC/FX3U/FX3UC Series PLC.
1) Only 1 3A-ADP unit can be connected to the FX3S Series PLC.
Up to 2*1 3A-ADP units can be connected to the FX3G/FX3GC Series PLC.
C
FX3U-4AD-ADP
Up to 4 3A-ADP units can be connected to the FX3U/FX3UC Series PLC.
(including the other analog expansion boards, analog special adapters)
2) The 3A-ADP receives and outputs voltage/current data.
3) A/D conversion data of each channel will be automatically written to the special data register of the FX3S/
FX3G/FX3GC/FX3U/FX3UC Series PLC.
4) D/A conversion results will be automatically output as the values to the special data register of the FX3S/
FX3G/FX3GC/FX3U/FX3UC Series PLC.
D
FX3G-2AD-BD
System Point and section to be
referred to
FX3S Series PLC : Only 1
FX3G/FX3GC Series PLC : 2*1 maximum
FX3U/FX3UC Series PLC : 4 maximum
including the other analog expansion
boards, analog special adapters
Number of connectable E
units
FX3U-4DA
FX3S/FX3G/FX3GC/FX3U/FX3UC
Series PLC
To check the connectable
PLC model number, refer
+ +
to Section 1.3.
FX3U-4DA-ADP
*2
4th 3rd 2nd 1st Expansion board
adapter adapter adapter adapter
For a detailed
Analog data description of wiring,
refer to Chapter 3. G
Flowmeter, Inverter, etc.
FX3G-1DA-BD
pressure sensor, etc
For FX3S/FX3G/FX3GC/
Contents
FX3U/FX3UC Series PLC
Special devices*3 For a detailed description
H
of special devices, refer to
FX3U-3A-ADP
Refer to the system configuration shown in the User's Manual - Hardware Edition to check the number of
connectable units and to configure the entire system.
*1. Only 1 analog special adapter can be connected to the FX3G Series PLC (14-point and 24-point type).
-ADP
*2. The expansion board is not required when connecting with the FX3GC/FX3UC (D, DS, DSS) Series PLC.
For the FX3S/FX3G Series PLC a connector conversion adapter is used.
*3. FX3S/FX3G/FX3GC PLCs use the following special devices. J
For FX3S Series PLC For FX3G/FX3GC Series PLC
FX3U-4AD-PTW
H-3
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output) 1.2 Setup Procedure Before Starting Operation
FX3U-3A-ADP
Refer to Chapter 1.
Wiring Wiring:
• Selection of sensor cable
• Power supply line
Refer to Chapter 4. • Analog input/output line
Programming Programming:
• Details of special devices
• Examples of basic programs
Refer to Chapter 5.
H-4
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output) 1.3 Connectable PLCs and Version Number
A
1.3 Connectable PLCs and Version Number
Common Items
The 3A-ADP is compatible with the following PLC.
Compatible PLC Version number Date of production
FX3S Series PLC Ver. 1.00 or later*1 After March 2013 (From first product) B
FX3G Series PLC Ver. 1.20 or later*1 After June 2009
FX3UC-4AD
FX3U-4AD
FX3GC Series PLC Ver. 1.40 or later*1 After January 2012 (From first product)
FX3U Series PLC Ver. 2.61 or later*1 After July 2009
FX3UC Series PLC Ver. 2.61 or later*1 After July 2009
*1. The FX3U/FX3UC Series PLC Ver. 2.70 or later and FX3S Series PLC supports the under-scale C
detection. The FX3G/FX3GC Series PLC are not supported.
FX3U-4AD-ADP
1. Version check
The PLC version can be checked by reading the last three digits of device D8001 or D8101.
→ For a detailed description of the version check,
refer to A. Common Items Subsection 5.1.2.
D
2. How to check the manufacturer's serial number
FX3G-2AD-BD
The year and month of production of the product can be checked on the nameplate, and on the front of the
product.
→ For a detailed description of how to check the manufacturer's serial number,
refer to A. Common Items Subsection 5.1.1.
E
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
H-5
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output) 1.4 Compatible Programming Tool Version Number
1. English versions
Model name Media model name Applicable version Remarks
FX3S PLC
GX Works2 SWDNC-GXW2-E Ver. 1.492N or later
-
FX-30P Ver. 1.50 or later
FX3G PLC
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer SWD5C-GPPW-E Ver. 8.72A or later -
FX-30P Ver. 1.00 or later
FX3GC PLC
GX Works2 SWDNC-GXW2-E Ver. 1.77F or later
-
FX-30P Ver. 1.30 or later
FX3U and FX3UC PLCs
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer SWD5C-GPPW-E Ver. 8.18U or later -
FX-30P Ver. 1.00 or later
2. Japanese versions
Model name Media model name Applicable version Remarks
FX3S PLC
GX Works2 SWDNC-GXW2-J Ver. 1.492N or later
-
FX-30P Ver. 1.50 or later
FX3G PLC
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
GX Developer SWD5C-GPPW-J Ver. 8.72A or later -
FX-30P Ver. 1.00 or later
FX3GC PLC
GX Works2 SWDNC-GXW2-J Ver. 1.77F or later
-
FX-30P Ver. 1.30 or later
FX3U and FX3UC PLCs
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
GX Developer SWD5C-GPPW-J Ver. 8.13P or later -
FX-30P Ver. 1.00 or later
Point
• It is possible to create programs in FX3GC PLC using programming tools of inapplicable versions by
selecting "FX3G" as the alternative model.
• It is possible to create programs in FX3S PLC using programming tools of inapplicable versions by
selecting "FX3G" as the alternative model. However, memory capacity setting of the PLC parameter must
be set to 4000 steps or less.
H-6
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output) 2.1 Generic Specifications
Common Items
2. Specifications
This chapter describes the general, power supply, and performance specifications for the 3A-ADP. B
FX3UC-4AD
FX3U-4AD
2.1 Generic Specifications
Item Specifications C
Ambient 0 to 55 °C (32 to 131 °F) when operating
FX3U-4AD-ADP
temperature -25 to 75 °C (-13 to 167 °F) when stored
Relative humidity 5 to 95 %RH (no condensation) when operating
Frequency Acceleration Half amplitude
(Hz) (m/s2) (mm)
Vibration 10 to 57 - 0.035
Tests 10 times in each
direction (X-, Y-, and Z-
D
DIN Rail Mounting
FX3G-2AD-BD
resistance*1 57 to 150 4.9 - axis directions) (Total:
80 min, each)
10 to 57 - 0.075
Direct Mounting*2
57 to 150 9.8 -
*1 2
Shock resistance 147 m/s Acceleration, Action time: 11 ms, 3 times by half-sine pulse in each direction X, Y, and Z
Using noise simulator of:
E
Noise resistance
FX3U-4DA
Noise voltage: 1,000 Vp-p / Noise width: 1 μs / Rise: 1 ns / Cycle: 30 to 100 Hz
Dielectric withstand
500 V AC, for 1 min
voltage
Between all terminals and ground terminal
Insulation 5 MΩ or more using 500 V DC
resistance insulation resistance meter
F
Class D grounding (grounding resistance: 100 Ω or less)
FX3U-4DA-ADP
Grounding
<Common grounding with a heavy electrical system is not allowed.>*3
Working
Free from corrosive or flammable gas and excessive conductive dusts
environment
Working altitude < 2000 m*4
*1. The criterion is shown in IEC61131-2.
G
FX3G-1DA-BD
*2. If 3A-ADP is connected to the FX3GC/FX3UC Series PLC, direct installation is not possible.
*3.
PLC Other PLC Other PLC Other
equipment equipment equipment
Item Specifications
Conversion circuit driving 24 V DC +20 %-15 %, 90 mA
power (It is necessary to connect a 24 V DC power line to the terminal block.) J
FX3U-4AD-PTW
5 V DC, 20 mA
Interface driving power (Since the internal power is supplied from the main unit of the FX Series, it is not
necessary to supply the power.)
-ADP
H-7
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output) 2.3 Performance Specifications
Specifications
Item
Voltage input Current input Voltage output Current output
Number of input/
2ch 1ch
output points
4 mA to 20 mA DC
Analog input/ 0 V to 10 V DC 4 mA to 20 mA DC 0 V to 10 V DC
(External load:
output range (Input resistance:198.7 kΩ) (Input resistance:250 Ω) (External load:5 k to 1 MΩ)
500 Ω or less)
Absolute -0.5 V, -2 mA,
- -
maximum input +15 V +30 mA
Digital input/
12 bits, binary
output
Resolution 2.5 mV (10 V × 1/4000) 5 μA (16 mA × 1/3200) 2.5 mV (10 V × 1/4000) 4 μA (16 mA × 1/4000)
Ambient
±0.5 % (±50 mV) ±0.5 % (±80 μA) ±0.5 % (±50 mV) ±0.5 % (±80 μA)
temperature:
for 10 V full scale for 16 mA full scale for 10 V full scale for 16 mA full scale
25±5 °C
Ambient
±1.0 % (±100 mV) ±1.0 % (±160 μA) ±1.0 % (±100 mV) ±1.0 % (±160 μA)
temperature:
for 10 V full scale for 16 mA full scale for 10 V full scale for 16 mA full scale
0 to 55 °C
Overall accuracy
4080 3280
4000 3200 10V 20mA
Analog output
Analog output
Digital output
Digital output
I/O
characteristics
20.4mA
10.2V
4080
4080
4mA
0 10V 0 4mA 20mA 0 4000 0 4000
Analog input Analog input Digital input Digital input
• The photocoupler is used to insulate the analog input and output area from the PLC.
Insulation
• The DC/DC converter is used to insulate the power supply from the analog input and output area.
method
• Channels are not insulated from each other.
Number of I/O 0 points
points occupied (This number of points is not related to the maximum number of input/output points of the PLC.)
H-8
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output) 2.4 Conversion Time
A
2.4 Conversion Time
Common Items
This section describes the conversion time.
FX3UC-4AD
FX3U-4AD
1. Conversion and special data register update timing
A/D and D/A conversion is performed at every scan time of the PLC.
During execution of END instruction, the PLC performs A/D conversion, reads out the A/D converted data,
and then writes the data in the special data registers.
The PLC writes output setting data to special data registers, performs D/A conversion, and updates analog
output values. C
FX3U-4AD-ADP
FX3U-3A-ADP FX3S Series PLC
FX3G-2AD-BD
D/A conversion
50 s for each End instruction
Digital value reading
selected output
channel
FX3U-4DA
2. Conversion during PLC STOP
1) A/D conversion
Even if the PLC is stopped, A/D conversion will be performed and the special data registers will be
updated.
2) D/A conversion F
If the output holding function cancellation setting is enabled by the special device, the offset value will be
FX3U-4DA-ADP
output.
If the output holding function cancellation setting is disabled, the output at switching from RUN to STOP
will be latched.
Just after power-on, however, the offset value will be output until operation begins.
FX3G-1DA-BD
1) A/D conversion
During execution of END instruction, the A/D converted data of "90 μs for each selected input channel",
and the data read out will be written to the special data registers.
END instruction execution time will be 90 μs for each selected input channel.
2) D/A conversion
During execution of END instruction, the output setting digital data per of "50 μs for each selected output H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
H-9
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output) 2.4 Conversion Time
H-10
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output) 2.4 Conversion Time
A
2.4.3 When connected to a FX3U/FX3UC PLC
Common Items
1. Conversion and special data register update timing
A/D and D/A conversion is performed at every scan time of the PLC.
During execution of END instruction, the PLC performs A/D conversion, reads out the A/D converted data,
and then writes the data in the special data registers. B
The PLC writes output setting data to special data registers, performs D/A conversion, and updates analog
FX3UC-4AD
FX3U-4AD
output values.
FX3U-3A-ADP FX3U-3A-ADP
n'th 1st FX3U/FX3UC Series PLC
FX3U-4AD-ADP
start command program
selected input
channel Digital value writing
+
D/A conversion
A/D conversion 40 s for each Digital value reading
80 s for each selected output
selected input channel A/D,D/A conversion
start command
End instruction D
channel
FX3G-2AD-BD
+
D/A conversion Digital value writing
40 s for each
selected output Digital value reading
channel
FX3U-4DA
1) A/D conversion
Even if the PLC is stopped, A/D conversion will be performed and the special data registers will be
updated.
2) D/A conversion
If the output holding function cancellation setting is enabled by the special device, the offset value will be F
output.
FX3U-4DA-ADP
If the output holding function cancellation setting is disabled, the output at switching from RUN to STOP
will be latched.
Just after power-on, however, the offset value will be output until operation begins.
FX3G-1DA-BD
During execution of the END instruction, data will be read out from all the connected adapters (in the
order of 1st adapter → 2nd adapter... 4th adapter).
2) D/A conversion
During execution of the END instruction, data in all the connected adapters will be subject to D/A
conversion and then output (in the order of 1st adapter → 2nd adapter... 4th adapter).
H
4. Conversion speed (data update time)
FX3U-3A-ADP
1) A/D conversion
During execution of END instruction, the A/D converted data of "80 μs for each selected input channel",
and the data read out will be written to the special data registers.
END instruction execution time will be "80 μs for each selected input channel × number of connected
analog adapters." I
FX3U-4AD-PT
2) D/A conversion
During execution of END instruction, the output setting digital data per of "40 μs for each selected output
channel", after which the analog data will be output.
-ADP
END instruction execution time will be "40 μs for each selected output channel × number of connected
adapters."
J
FX3U-4AD-PTW
-ADP
H-11
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output)
3. Wiring
This chapter describes the 3A-ADP wiring.
Observe the following caution to wire the 3A-ADP.
WIRING PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before attempting wiring work.
Failure to do so may cause electric shock or damage to the product.
WIRING PRECAUTIONS
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn
out.
• Do not wire vacant terminals externally.
Doing so may damage the product.
• Perform class D grounding (grounding resistance: 100Ω or less) to the grounding terminal on the main unit.
Do not use common grounding with heavy electrical systems.
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
• Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise:
- Do not bundle the power line or shield of the analog input/output cable together with or lay it close to the main
circuit, high-voltage line, or load line.
Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
100mm (3.94") or more away from the main circuit, high-voltage line, or load line.
- Ground the shield of the analog input/output cable at one point on the signal receiving side.
However, do not use common grounding with heavy electrical systems.
• Make sure to properly wire to the terminal block (European type) in accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
- The disposal size of the cable end should follow the dimensions described in the manual.
- Tightening torque should follow the specifications in the manual.
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
H-12
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output) 3.1 Terminal Layout
A
3.1 Terminal Layout
Common Items
The terminals of the 3A-ADP are arranged as follows:
FX3UC-4AD
FX3U-4AD
Signal Application
24+
24-
External power
C
Grounding terminal
FX3U-4AD-ADP
• Do not connect any lines.
V1+
I1+ Channel 1 analog input
COM1
V2+
I2+ Channel 2 analog input
D
FX3G-2AD-BD
COM2
V0
I0 Analog output
COM
•
•
Do not connect any lines.
E
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
H-13
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output) 3.2 Applicable Cables and Terminal Tightening Torque
1. Cables
Applicable cable and tightening torque
Wire size Tightening
Termination
(stranded wire/solid wire) torque
0.3 mm2 to 0.5 mm2 • To connect a stranded cable, peel the cover off the cable
Single-wire and then twist the core before connection.
(AWG22 to 20)
• To connect a single-wire cable, just strip the cover off the
2-wire 0.3 mm2 (AWG22)×2 cable before connection.
0.22 to • Ferrule with insulation sleeve
0.3 mm2 to 0.5 mm2 0.25 N•m (recommended terminal)
Ferrule with (AWG22 to 20) AI 0.5-8WH : Manufactured by Phoenix Contact
insulation (Refer to the external view • Caulking tool
sleeve of ferrule shown in the
CRIMPFOX 6*1 : Manufactured by Phoenix Contact
following figure.)
(or CRIMPFOX 6T-F*2 : Manufactured by Phoenix Contact)
3. Tool
For tightening the terminal, use a commercially available small screwdriver
The head
having a straight form that is not widened toward the end as shown right. should be
straight.
Note:
If the diameter of screwdriver grip is too small, tightening torque will not
be able to be achieved. To achieve the appropriate tightening torque 0.4mm 2.5mm
shown in the table above, use the following screwdriver or an appropriate (0.01") (0.09")
replacement (grip diameter: approximately 25 mm (0.98")).
<Reference>
Manufacturer Model
Phoenix Contact SZS 0.4×2.5
H-14
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output) 3.3 Power Supply Line
A
3.3 Power Supply Line
Common Items
Connect the 24 V DC power supply line of the 3A-ADP to the 24+ and 24- terminals of the terminal block.
FX3UC-4AD
FX3U-4AD
3A-ADP FX3S/FX3G/FX3U 3A-ADP FX3S/FX3G/FX3U
Series PLC Series PLC
+15V +15V
(Main unit) (Main unit)
FX3U-4AD-ADP
24+ 24- 24+ 24- 24V 0V
D
Terminal Terminal
FX3G-2AD-BD
block block
Fuse
Class-D Class-D
24V DC grounding grounding
Caution regarding connection of the power supply line: E
FX3U-4DA
• Ground the " " terminal to a class-D grounded power supply line (100 Ω or less) together with the
grounding terminal of the PLC main unit.
• When using an external power supply, turn it ON at the same time with the main unit or earlier than the
main unit. When turning OFF the power, confirm the safety of the system, and then turn OFF the power of
the PLC (including special adapter) at the same time.
F
3.3.2 To connect to the FX3GC/FX3UC Series PLC
FX3U-4DA-ADP
Example of wiring of FX3UC Series PLC
3A-ADP FX3UC Series PLC
(Main unit)
+15V
G
FX3G-1DA-BD
Power
connector
H
FX3U-3A-ADP
I
Fuse
FX3U-4AD-PT
Class-D
24V DC grounding
For example of wiring of FX3GC Series PLC, refer to the following manual.
-ADP
• Ground the " " terminal to a class-D grounded power supply line (100 Ω or less) together with the
grounding terminal of the PLC main unit.
-ADP
H-15
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output) 3.4 Analog Input / output Line
*1 110k ch
V +
250
I +
COM
88.7k
Connection of external
power supply line +15V
24+
24V DC *3 24-
Class-D
grounding
V +,I +,ch : represents the channel number.
*1. Use the 2-core shielded twisted pair cable for the analog input lines, and separate the analog input
lines from other power lines or inductive lines.
*2. If "current input" is selected, be sure to short the line between the V+ terminal and the I+ terminal.
(: Channel number).
*3. For FX3S/FX3G/FX3U Series PLC (AC power type), the 24 V DC service power supply is also
available.
*1. Use 2-core shielded twisted pair cable for the analog output lines, and separate the analog output
lines from other power lines or inductive lines.
*2. Ground the shielded wire at one point on the signal receiving side.
H-16
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output) 3.5 Grounding
A
3.5 Grounding
Common Items
Grounding should be performed as stated below.
• The grounding resistance should be 100 Ω or less.
• Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" as shown in the following
B
FX3UC-4AD
FX3U-4AD
figure.
→ For details, refer to the User's Manual - Hardware Edition of the each PLC Series.
FX3U-4AD-ADP
Best condition Good condition Not allowed
FX3G-2AD-BD
E
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
H-17
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output) 4.1 Loading/Writing of Conversion Data
4. Programming
This chapter explains how to create programs for inputting and outputting analog data using the 3A-ADP.
Special devices
Communi-
cation
FX3U-3A special FX3U-3A
-ADP adapter -ADP FX3G/FX3GC Series PLC *2
*1
2nd 1st
Special devices
Special auxiliary relays:
A/D M8280 to M8289
or Special data registers:
D/A D8280 to D8289.
Sequence
program
Special auxiliary relays:
A/D M8290 to M8299
or Special data registers:
D/A D8290 to D8299.
The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
next adapter as the 2nd analog special adapter. However, in this case, do not include the connecter
conversion adapter and the communication special adapter.
*1. The second special adapter is not available in the FX3G Series PLC (14-points and 24-points type).
*2. A connector conversion adapter is required to connect the FX3U-3A-ADP to the FX3G Series PLC.
H-18
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output) 4.2 List of Special Devices
A
• FX3U/FX3UC Series PLC
Common Items
Communic
FX3U-3A FX3U-3A FX3U-3A -ation FX3U-3A
-ADP -ADP -ADP special -ADP
adapter FX3U/FX3UC Series PLC*1
FX3UC-4AD
FX3U-4AD
M8260 to M8269
or Special data registers:
D/A D8260 to D8269
FX3U-4AD-ADP
program
A/D Special auxiliary relays:
M8280 to M8289
or Special data registers:
D/A D8280 to D8289.
A/D
Special auxiliary relays:
M8290 to M8299
D
or
FX3G-2AD-BD
Special data registers:
D/A D8290 to D8299
The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
next adapter as the 2nd analog special adapter, and so on. However, in this case, do not include the high-
speed input/output special adapter, communication special adapter, and the CF card special adapter. E
*1. An expansion board is required to connect the FX3U-3A-ADP to the FX3U/FX3UC-32MT-LT(-2) PLC.
FX3U-4DA
4.2 List of Special Devices
If the 3A-ADP is connected, special devices will be assigned automatically as shown in the following table:
F
• FX3S Series PLC
FX3U-4DA-ADP
R: Read / W: Write
Special
Device number Description Attribute Reference
device
M8280 Switches the input mode of channel 1 R/W
Section 4.3
M8281 Switches the input mode of channel 2 R/W G
M8282 Switches the output mode. R/W Section 4.4
FX3G-1DA-BD
M8283 to M8285 Unused (Do not use.) - -
Special M8286 Sets the cancel of output holding function. R/W Section 4.5
auxiliary Sets whether or not the input channel 1 is
relay M8287 R/W
used.
M8288
Sets whether or not the input channel 2 is
R/W Section 4.6
H
used.
FX3U-3A-ADP
H-19
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output) 4.2 List of Special Devices
H-20
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output) 4.3 Switching of Input Mode
A
4.3 Switching of Input Mode
Common Items
Turn the special auxiliary relay on/off to switch the input mode of 3A-ADP between the current input mode
and the voltage input mode.
To switch the input mode, use the following special auxiliary relays:
• FX3S Series PLC B
FX3UC-4AD
FX3U-4AD
Special auxiliary
Description
relay
M8280 Switches the input mode of channel 1 OFF:Voltage input
M8281 Switches the input mode of channel 2 ON :Current input
FX3U-4AD-ADP
Special auxiliary
relay Description
1st 2nd
M8280 M8290 Switches the input mode of channel 1 OFF:Voltage input
ON :Current input
M8281 M8291 Switches the input mode of channel 2
D
• FX3U/FX3UC Series PLC
FX3G-2AD-BD
Special auxiliary relay
Description
1st 2nd 3rd 4th
M8260 M8270 M8280 M8290 Switches the input mode of channel 1 OFF:Voltage input
ON :Current input
M8261 M8271 M8281 M8291 Switches the input mode of channel 2
E
1. Program Example (For FX3U/FX3UC Series PLC)
FX3U-4DA
To switch the channel input mode, create a sequence program as follows:
1) To switch the input mode of channel 1 2) To switch the input mode of channel 2
of the 1st analog special adapter to the of the 1st analog special adapter to the
voltage input mode: current input mode:
M8001
M8260
M8000
M8261
F
FX3U-4DA-ADP
Normally OFF Normally ON
FX3G-1DA-BD
To switch the output mode, use the following special auxiliary relays:
• FX3S Series PLC
Special auxiliary relay Description
Description
1st 2nd 3rd 4th
H-21
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output) 4.5 Output Holding Function Cancellation Setting
H-22
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output) 4.6 Setting whether or not a channel is used
A
4.6 Setting whether or not a channel is used
Common Items
The 3A-ADP sets to ON or OFF special auxiliary relays to set whether or not each channel is used.
This setting can be used to disable or enable the input or output channels of the 3A-ADP.
• FX3S Series PLC
Special auxiliary relay Description
B
FX3UC-4AD
FX3U-4AD
Sets whether or not input
M8287
channel 1 is used.
Sets whether or not input OFF: Channel is used.
M8288
channel 2 is used. ON: Channel is not used.
M8289
Sets whether or not output
channel is used.
C
FX3U-4AD-ADP
• FX3G/FX3GC Series PLC
Special auxiliary relay
Description
1st 2nd
M8287 M8297
Sets whether or not input
channel 1 is used.
D
FX3G-2AD-BD
Sets whether or not input OFF: Channel is used.
M8288 M8298
channel 2 is used. ON: Channel is not used.
Sets whether or not output
M8289 M8299
channel is used.
FX3U-4DA
Description
1st 2nd 3rd 4th
Sets whether or not input
M8267 M8277 M8287 M8297
channel 1 is used.
Sets whether or not input OFF: Channel is used.
M8268 M8278 M8288 M8298
channel 2 is used. ON: Channel is not used. F
FX3U-4DA-ADP
Sets whether or not output
M8269 M8279 M8289 M8299
channel is used.
POINT
When the setting whether or not the output channel is used is changed from "Used (OFF)" to "Not used (ON)",
the last output before the change is held. G
FX3G-1DA-BD
1. Program Example (For FX3U/FX3UC Series PLCs)
Set whether or not each channel is used in a sequence program.
1) To set that input channel 2 in the 1st unit
is not used:
M8000
M8268 H
Normally ON
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
H-23
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output) 4.7 Input Data
The converted A/D immediate data or averaged data (data average conforming to the specified averaging
time) will be stored in the above data registers as the input data.
When the channel is not used, "0" will be stored.
→ For a detailed description of the averaging time, refer to Section 4.9.
Even if the input data is not stored in D100 or D101, data registers D8260 or D8261 can be directly used in
the timer/counter set value or in a PID instruction.
H-24
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output) 4.8 Output Setting Data
A
4.8 Output Setting Data
Common Items
Numeric data type: Decimal (K)
The 3A-ADP performs D/A conversion on the output setting data (digital data) into analog data, and outputs
the analog data.
Use the special data registers shown in the following table for the output setting data: B
FX3UC-4AD
FX3U-4AD
• FX3S Series PLC
Special data register Description
D8282 Output setting data
FX3U-4AD-ADP
Description
1st 2nd
D8282 D8292 Output setting data
FX3G-2AD-BD
1st 2nd 3rd 4th
D8262 D8272 D8282 D8292 Output setting data
FX3U-4DA
Normally ON special adapter.
Using the indicator or the sequence program, input the digital data to be subject to D/A conversion (to be
output as analog data) in D102.
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
H-25
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output) 4.9 Averaging Time
H-26
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output) 4.10 Error Status
A
4.10 Error Status
Common Items
If an error is detected in the 3A-ADP, the error status data will be stored in the corresponding special data
register.
The following table shows the special data registers that store the error status data:
• FX3S Series PLC B
FX3UC-4AD
FX3U-4AD
Special data register Description
D8288 Stores the error status data.
FX3U-4AD-ADP
D8288 D8298 Stores the error status data.
FX3G-2AD-BD
Check the ON/OFF status of each bit of the error status data register to check the description of the error.
Errors are assigned to the bits as shown in the following table. Create a program to detect errors.
→ For a detailed description of the error status, refer to Section 6.5.
FX3U-4DA
3A-ADP hardware error
b0 Channel-1 over-scale detection b6
(Power supply error included)*1
b1 Channel-2 over-scale detection b7 3A-ADP communication data error*2
b2
b3
Output data setting error
Unused
b8
b9
Channel-1 under-scale detection*3
F
Channel-2 under-scale detection*3
FX3U-4DA-ADP
b4 EEPROM error b10 to b15 Unused
b5 Averaging time setting error - -
*1. A 3A-ADP hardware error (b6) is valid only when the use of analog input is set.
Detection of power supply error is valid only when the use of analog input channel 2 is set.
*2. A 3A-ADP communication data error (b7) is valid only when the use of analog input is set.
G
FX3G-1DA-BD
*3. Applicable for FX3U/FX3UC Series PLC Ver. 2.70 or later and FX3S Series PLC.
The under-scale detection function is valid only for current input mode.
The FX3G/FX3GC Series PLC are not supported.
1. Caution regarding use of error status data
If a 3A-ADP hardware error (b6) or 3A-ADP communication data error (b7) is detected, it is necessary to clear H
the error status with a program at the next power-on of the PLC.
FX3U-3A-ADP
M8000
FNC 12
Normally ON MOV
D8288 K4M0
I
FX3U-4AD-PT
M8002 *1
Error status of 3rd analog special adapter
RST M6 b6 = OFF (3A-ADP hardware error)
Initial pulse
-ADP
*1
RST M7 Error status of 3rd analog status register
b7 = OFF (3A-ADP communication data error)
FNC 12 J
K4M0 D8288
FX3U-4AD-PTW
MOV
H-27
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output) 4.10 Error Status
M2
Y002 Output data setting error of the 3rd*1
adapter.
M4
Y004 EEPROM error in 3rd*1 adapter.
M5
Y005 Averaging time setting error in
3rd*1 adapter.
M6
Y006 3A-ADP hardware error in 3rd*1 adapter.
M7
Y007 3A-ADP communication data error in 3rd*1 adapter.
D8268.2
Y002 Output data setting error of the 1st
adapter.
D8268.4
Y004 EEPROM error in 1st adapter.
D8268.5
Y005 Averaging time setting error in
1st adapter.
D8268.6
Y006 3A-ADP hardware error in 1st adapter.
D8268.7
Y007 3A-ADP communication data error in 1st adapter.
H-28
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output) 4.11 Model Code
A
4.11 Model Code
Common Items
Initial value: K50
Numeric data type: Decimal (K)
When the 3A-ADP is connected, model code "50" is stored in the corresponding special data register.
The following table shows the special data registers that store the model code: B
FX3UC-4AD
FX3U-4AD
• FX3S Series PLC
Special data register Description
D8289 Model code
FX3U-4AD-ADP
Description
1st 2nd
D8289 D8299 Model code
FX3G-2AD-BD
D8269 D8279 D8289 D8299 Model code
Use the special data registers above to check whether a 3A-ADP is connected or not.
E
FX3U-4DA
1. Program Example (FX3U/FX3UC Series PLC)
FNC224 D8269 K50 Y007 Checks the model code of the 1st
LD= analog special adapter.
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
H-29
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output) 4.12 Basic Program Example
M8002
RST M6 Error status: b6 = OFF
Initial
pulse
RST M7 Error status: b7 = OFF
Even if the input data is not stored into D100 or D101, the data registers D8280 or D8281 can be directly
used in the timer/counter setting value or in a PID instruction.
Using the indicator or the sequence program, input the digital data to be subject to D/A conversion (to be
output as analog data) in D102.
*1. "1st" for the FX3S/FX3G/FX3GC PLC.
H-30
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output) 4.12 Basic Program Example
A
• FX3U/FX3UC Series PLC
Common Items
The following program will set channel 1 of the 1st adapter to voltage input mode and channel 2 to current
input mode, and will store the converted A/D value of channel-1 data into D100 and that of channel-2 data
into D101. The program will also set "voltage output" for output channels, and set the digital D/A
conversion output to D102.
M8001
M8260 Set the input mode of channel 1 to the voltage
B
FX3UC-4AD
FX3U-4AD
Normally OFF input mode (0 V to 10 V).
M8000
M8261 Set the input mode of channel 2 to the current
Normally ON input mode (4 mA to 20 mA).
M8001
M8262 Set the output mode to the voltage output mode
Normally
OFF
(0 V to 10 V). C
FX3U-4AD-ADP
M8266 Set the output holding function.
M8002
RST D8268.6 Error status: b6 = OFF
Initial
pulse
RST D8268.7 Error status: b7 = OFF D
FX3G-2AD-BD
M8000
FNC 12 K5 D8264 Set the averaging time to "5" for channel-1 data.
Normally MOV
ON
FNC 12 K5 D8265 Set the averaging time to "5" for channel-2 data.
MOV
M8000
FNC 12 Stores the A/D converted channel-1 digital data
E
D8260 D100
FX3U-4DA
Normally MOV into D100.
ON
FNC 12 D8261 D101 Stores the A/D converted channel-2 digital data
MOV into D101.
M8000
FNC 12 Performs D/A conversion with the digital data
Normally MOV
D102 D8262
stored in D102. F
ON
FX3U-4DA-ADP
Even if the input data is not stored into D100 or D101, the data registers D8260 or D8261 can be directly
used in the timer/counter setting value or in a PID instruction.
Using the indicator or the sequence program, input the digital data to be subject to D/A conversion (to be
output as analog data) in D102.
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
H-31
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Changing of Input/output Characteristics
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output) 5.1 Example: Changing of Voltage Input Characteristics
1. Input characteristics
Voltage input characteristics Digital output value to be changed
(product specifications) Y-axis
Digital output
4000 10000
Digital output to
be calculated
(D110)
2000
400
0 X-axis
1V 5V 10V 0 400 (1V) 2000 (5V)
Analog input
Digital value actually obtained
by A/D conversion
H-32
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Changing of Input/output Characteristics
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output) 5.1 Example: Changing of Voltage Input Characteristics
A
2. Example of program 1 (FX3U/FX3UC Series PLC)
Common Items
For example, create the following program to change the digital input data of the 1st analog special adapter:
M8001
M8260 Sets the input mode of channel 1 to the voltage input mode
Normally OFF (0 V to 10 V)
M8002
RST D8268.6 Error status: b6 = OFF B
Initial
FX3UC-4AD
FX3U-4AD
pulse
RST D8268.7 Error status: b7 = OFF
M8000
FNC 12 K1 D8264 Sets the averaging time to "1" for the channel-1 data
Normally ON MOV
C
M8002 FNC 12
FX3U-4AD-ADP
K2 D50 Program for setting scaling instruction data table
Initial MOV
pulse Item Description Value Device
FNC 12 K400 D51 Number of points Sets the number of points 2 D50
MOV X- A/D converted digital value 400 D51
Start coordinate start point data
FNC 12
MOV
K0 D52 point Y- Digital output value of changed
0 D52
D
coordinate X-axis value start point
FX3G-2AD-BD
FNC 12 X- A/D converted digital value end 2000 D53
K2000 D53 End coordinate point data
MOV
point Y- Digital output value of changed 10000
coordinate X-axis value end point D54
FNC 12 K10000 D54
MOV
M8000 FNC259
E
D8260 D50 D100 The scaling instruction operation results will be stored in D100.
FX3U-4DA
Normally SCL
ON
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
H-33
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Changing of Input/output Characteristics
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output) 5.1 Example: Changing of Voltage Input Characteristics
H-34
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Changing of Input/output Characteristics
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output) 5.2 Example: Changing of Voltage Output Characteristics
A
5.2 Example: Changing of Voltage Output Characteristics
Common Items
This section describes an example of a program that can change the digital value range from 400 to 2000
(when analog output range is 1 to 5 V) to 0 to 10000.
A specified digital value is inputted into D120.
1. Output characteristics
B
FX3UC-4AD
FX3U-4AD
Voltage output characteristics
Y-axis
C
FX3U-4AD-ADP
5V 2000
(5V)
1V 400
0 400
(1V)
X-axis
D
2000 4000 0 10000
FX3G-2AD-BD
Digital value input
Desired digital value (D120)
FX3U-4DA
Normally mode.
OFF
M8266 Sets the output holding function for channel 1.
M8002
FNC 12 K2 D50
Program for setting scaling instruction data table F
MOV
FX3U-4DA-ADP
Initial Item Description Value Device
pulse Number of points Sets the number of points. 2 D50
FNC 12 K0 D51
MOV X- Digital value of specified 0 D51
Start coordinate start point on X-axis
FNC 12 point Y- Digital value of desired D/A
K400 D52 400 D52
MOV coordinate
X-
conversion start point
Digital value of specified end 10000
G
FNC 12 D53
End coordinate point on X-axis
FX3G-1DA-BD
K10000 D53
MOV point Y- Digital value of desired D/A 2000
coordinate conversion end point D54
FNC 12 K2000 D54
MOV
M8000
Normally
FNC259
SCL
D120 D50 D8262
The result of operation by scaling instruction will be stored
in the D8262. H
FX3U-3A-ADP
ON
J
FX3U-4AD-PTW
-ADP
H-35
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Changing of Input/output Characteristics
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output) 5.2 Example: Changing of Voltage Output Characteristics
FNC230 D120 K0 FNC237 D120 K10000 M20 Check to make sure the digital
LD>= AND<= value (D120) is in range.
M20
FNC 22 D120 K1600 D121
MUL
H-36
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output) 6.1 PLC Version Number Check
Common Items
6. Troubleshooting
This chapter describes troubleshooting methods and error statuses. B
Refer to the following items when conversion data is not input or output, or when proper digital values are not
FX3UC-4AD
FX3U-4AD
input or output.
• PLC version number
• Installation
• Wiring
• Special devices C
FX3U-4AD-ADP
• Programs
• Error status
FX3G-2AD-BD
• Check the version number of the FX3G Series PLC. The version number should be 1.20 or later.
• Any versions (from Ver. 1.40 (initial version) to the latest version) of the FX3GC Series are compatible.
• Check the version number of the FX3U/FX3UC Series PLC. The version number should be 2.61 or later.
→ For a detailed description of the version check method,
refer to A. Common Items Subsection 5.1.2. E
FX3U-4DA
6.2 Wiring Check
Check the following items for wiring:
1. Power F
The 3A-ADP needs driving power. Verify that the power supply line is properly connected. Also check that the
FX3U-4DA-ADP
POWER indicator lamp of the 3A-ADP is on.
2. Analog input/output line
Use 2-core twisted shielded pair cable for the analog input/output line. In addition, be sure to separate the
analog input line from other power lines or inductive lines.
3. Use of current input mode
G
FX3G-1DA-BD
To use the current input mode for a channel, be sure to shortcircuit the line between the V+ terminal and the
I+terminal (: channel number) of the channel. If the line is not shortcircuited, data will not be converted
into proper digital data.
→ For a detailed description of wiring, refer to Chapter 3.
H
6.3 Special Device Check
FX3U-3A-ADP
Check whether the special devices for the 3A-ADP are being used correctly:
1. Input mode switching
Check that the special device for switching the input mode is set correctly.
Turn off the device to set the input mode to the voltage input mode. Turn on the device to set the input mode I
to the current input mode.
FX3U-4AD-PT
Turn off the device to set the output mode to the voltage output mode. Turn on the device to set the output
mode to the current output mode.
J
3. Input data
FX3U-4AD-PTW
Verify that the special device of the selected channel is correctly selected. This special device should be
selected depending on the connecting position and the channel.
-ADP
H-37
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output) 6.4 Program Check
5. Averaging time
Check that the set averaging time is within the specified range. The averaging time should be set in the range
from 1 to 4095. If the set averaging time is outside the specified range, an error occurs.
7. Error status
Check that no error is detected in the 3A-ADP.
If an error is detected, check the details of the error, and then check the wiring and programs.
→ For a detailed description of special devices, refer to Chapter 4.
*1. A 3A-ADP hardware error (b6) is valid only when use of analog input is set.
Detection of power supply error is valid only when use of the analog input channel 2 is set.
*2. A 3A-ADP communication data error (b7) is valid only when use of analog input is set.
*3. Applicable for FX3U/FX3UC Series PLC Ver. 2.70 or later and FX3S Series PLC.
The under-scale detection function is valid only for current input mode.
The FX3G/FX3GC Series PLC are not supported.
H-38
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output) 6.5 Error Status Check
A
To solve the problem, refer to the troubleshooting method described below:
Common Items
1. Over-scale detection (b0, b1)
1) Description of error
The input analog value (voltage or current value) is outside the specified range.
Voltage input mode : The input voltage value is over the specified upper limit of 10.2 V.
Current input mode : The input current value is over the specified upper limit of 20.4 mA.
B
FX3UC-4AD
FX3U-4AD
2) Remedy
Check that the input analog value is within the specified range. Also check the wiring.
FX3U-4AD-ADP
Analog data will not be correctly output.
2) Remedy
Check that the specified digital value is within the specified range.
FX3G-2AD-BD
The adjustment data which was set in the EEPROM before delivery from our factory cannot be read out
properly or has been destroyed.
2) Remedy
Please contact your local Mitsubishi Electric representative.
FX3U-4DA
1) Description of error
The averaging time set for one of the channels (channels 1 to 2) is outside the specified range: 1 to 4095.
2) Remedy
Check that the averaging time is set correctly for each channel.
FX3U-4DA-ADP
1) Description of error
The 3A-ADP is not operating properly.
2) Remedy
Check that the 3A-ADP is correctly connected to the PLC.
If the problem cannot be solved even after the above check, please contact your local Mitsubishi Electric
representative.
G
FX3G-1DA-BD
6. 3A-ADP communication data error (b7)
1) Description of error
A communication error is detected between the 3A-ADP and the PLC.
2) Remedy
Check that the 3A-ADP is correctly connected to the PLC.
H
FX3U-3A-ADP
If the problem cannot be solved even after the above check, please contact your local Mitsubishi Electric
representative.
2) Remedy
Check that the input analog value is within the specified range. Also check the wiring.
-ADP
J
FX3U-4AD-PTW
-ADP
H-39
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
FX3U-3A-ADP (2-channel Analog Input, 1-channel Analog Output) 6.5 Error Status Check
MEMO
H-40
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input)
Common Items
B
FX3UC-4AD
FX3U-4AD
FX3S/FX3G/FX3GC/FX3U/FX3UC Series
Programmable Controllers C
FX3U-4AD-ADP
User's Manual [Analog Control Edition]
FX3G-2AD-BD
E
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
Foreword
This manual describes the specifications, wiring, and operation methods for the FX3U-4AD-PT-ADP special
adapter (4-channel platinum resistance thermometer input) and should be read and understood before I
attempting to install or use the unit.
FX3U-4AD-PT
Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
it to the end user.
-ADP
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property J
rights which may occur as a result of using the contents noted in this manual.
FX3U-4AD-PTW
I-1
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input)
I-2
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 1.1 Outline of Functions
Common Items
1. Outline
This chapter describes the outline of FX3U-4AD-PT-ADP (referred to as PT-ADP). B
FX3UC-4AD
FX3U-4AD
1.1 Outline of Functions
The FX3U-4AD-PT-ADP is an analog special adapter. Connect the FX3U-4AD-PT-ADP to the FX3S/FX3G/
FX3GC/FX3U/FX3UC Series PLC to read the temperature data from the 4-channel platinum resistance
thermometers.
C
FX3U-4AD-ADP
1) Only 1 PT-ADP unit can be connected to the FX3S Series PLC.
Up to 2*1 PT-ADP units can be connected to the FX3G/FX3GC Series PLC.
Up to 4 PT-ADP units can be connected to the FX3U/FX3UC Series PLC.
(including the other analog expansion boards, analog special adapters)
2) After connection of the platinum resistance thermometer (Pt100), measurement of temperature will be
possible. D
3) The temperature measurement data will be automatically written to the special data registers of the FX3S/
FX3G-2AD-BD
FX3G/FX3GC/FX3U/FX3UC Series PLC.
FX3U-4DA
including the other analog expansion Number of connectable
units
boards, analog special adapters
FX3S/FX3G/FX3GC/FX3U/FX3UC
Series PLC
FX3U-4DA-ADP
Expansion
4th 3rd 2nd 1st
board*2
adapter adapter adapter adapter For a detailed
description of wiring, G
Analog data refer to Chapter 3.
FX3G-1DA-BD
Platinum resistance thermometer
sensor (Pt100)
For FX3S/FX3G/FX3GC/
FX3U/FX3UC Series PLC For a detailed description
H
of special devices, refer to
FX3U-3A-ADP
*2. The expansion board is not required when connecting with the FX3GC/FX3UC (D, DS, DSS) Series PLC.
For the FX3S/FX3G Series PLC a connector conversion adapter is used.
*3. FX3S/FX3G/FX3GC PLCs use the following special devices.
For FX3S Series PLC For FX3G/FX3GC Series PLC
J
FX3U-4AD-PTW
I-3
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 1.2 Setup Procedure Before Starting Operation
FX3U-4AD-PT-ADP
Refer to Chapter 1.
I-4
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 1.3 Connectable PLC and Its Version Number
A
1.3 Connectable PLC and Its Version Number
Common Items
PT-ADP is compatible with the following PLC.
Compatible PLC Version number Date of production
FX3S Series PLC Ver. 1.00 or later After March 2013 (From first product)
B
FX3G Series PLC Ver. 1.00 or later After June 2008 (From first product)
FX3UC-4AD
FX3U-4AD
FX3GC Series PLC Ver. 1.40 or later After January 2012 (From first product)
FX3U Series PLC Ver. 2.20 or later After May 2005 (From first product)
FX3UC Series PLC Ver. 1.30 or later After August 2004
1. Version check C
The PLC version can be checked by reading the last three digits of device D8001 or D8101.
FX3U-4AD-ADP
→ For a detailed description of the version check,
refer to A. Common Items Subsection 5.1.2.
FX3G-2AD-BD
→ For a detailed description of how to check the manufacturer's serial number,
refer to A. Common Items Subsection 5.1.1.
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
I-5
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 1.4 Compatible Programming Tool Version Number
1. English versions
Model name Media model name Applicable version Remarks
FX3S PLC
GX Works2 SWDNC-GXW2-E Ver. 1.492N or later
-
FX-30P Ver. 1.50 or later
FX3G PLC
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer SWD5C-GPPW-E Ver. 8.72A or later -
FX-30P Ver. 1.00 or later
FX3GC PLC
GX Works2 SWDNC-GXW2-E Ver. 1.77F or later
-
FX-30P Ver. 1.30 or later
FX3U and FX3UC PLCs
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer SWD5C-GPPW-E Ver. 8.18U or later -
FX-30P Ver. 1.00 or later
2. Japanese versions
Model name Media model name Applicable version Remarks
FX3S PLC
GX Works2 SWDNC-GXW2-J Ver. 1.492N or later
-
FX-30P Ver. 1.50 or later
FX3G PLC
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
GX Developer SWD5C-GPPW-J Ver. 8.72A or later -
FX-30P Ver. 1.00 or later
FX3GC PLC
GX Works2 SWDNC-GXW2-J Ver. 1.77F or later
-
FX-30P Ver. 1.30 or later
FX3U and FX3UC PLCs
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
GX Developer SWD5C-GPPW-J Ver. 8.13P or later -
FX-30P Ver. 1.00 or later
Point
• It is possible to create programs in FX3GC PLC using programming tools of inapplicable versions by
selecting "FX3G" as the alternative model.
• It is possible to create programs in FX3S PLC using programming tools of inapplicable versions by
selecting "FX3G" as the alternative model. However, memory capacity setting of the PLC parameter must
be set to 4000 steps or less.
I-6
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 2.1 Generic Specifications
Common Items
2. Specifications
This chapter describes the general, power supply, and performance specifications for the PT-ADP. B
FX3UC-4AD
FX3U-4AD
2.1 Generic Specifications
Item Specifications C
FX3U-4AD-ADP
Ambient 0 to 55 °C (32 to 131 °F) when operating
temperature -25 to 75 °C (-13 to 167 °F) when stored
Relative
5 to 95 %RH (no condensation) when operating
humidity
Frequency Acceleration Half amplitude D
(Hz) (m/s2) (mm)
FX3G-2AD-BD
Tested 10 times in each
Vibration 10 to 57 - 0.035 direction (X-, Y-, and Z-
DIN Rail Mounting
resistance*1 57 to 150 4.9 - axis directions) (Total:
80 min, each)
10 to 57 − 0.075
Direct Mounting*2
−
Shock
57 to 150 9.8
E
m/s2
FX3U-4DA
147 Acceleration, Action time: 11 ms, 3 times by half-sine pulse in each direction X, Y, and Z
resistance*1
Noise Using noise simulator of:
resistance Noise voltage: 1,000 Vp-p / Noise width: 1 μs / Rise: 1 ns / Cycle: 30 to 100 Hz
Dielectric
withstand
voltage
500 V AC, for 1 min F
Between all terminals and ground terminal
FX3U-4DA-ADP
Insulation 5 MΩ or more using 500 V DC
resistance insulation resistance meter
Class D grounding (grounding resistance: 100 Ω or less)
Grounding
<Common grounding with a heavy electrical system is not allowed.>*3
Working
Free from corrosive or flammable gas and excessive conductive dusts
G
environment
FX3G-1DA-BD
Working
altitude < 2000 m*4
*4. If the pressure is higher than the atmospheric pressure, do not use the PT-ADP.
The PT-ADP may malfunction.
-ADP
J
FX3U-4AD-PTW
-ADP
I-7
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 2.2 Power Supply Specifications
Items Specification
A/D conversion circuit 24 V DC +20 % -15 %, 50 mA
driving power (It is necessary to connect a 24 V DC power supply to the terminal block.)
5 V DC, 15 mA
Interface driving power (Since the internal power is supplied from the FX Series main unit, it is not necessary
to supply the power.)
Specifications
Items
Centigrade (°C) Fahrenheit (°F)
3-wire platinum resistance thermometer sensor
Input signal
Pt100 JIS C 1604-1997
Rated temperature
-50 °C to +250 °C -58 °F to +482 °F
range
Digital output -500 to +2500 -580 to +4820
Resolution 0.1 °C 0.18 °F
• ±0.5 % for full scale (when ambient temperature is 25 °C±5 °C)
Total accuracy
• ±1.0 % for full scale (when ambient temperature is in the range from 0 to 55 °C)
• FX3U/FX3UC Series PLC : 200 μs (The data will be updated at every scan time.)
A/D conversion
• FX3S/FX3G/FX3GC Series PLC : 250 μs (The data will be updated at every scan time.)
time
→For a detailed description of data update, refer to Section 2.4.
+2550 +4910
+2500 +4820
+255°C
+491°F
Input
characteristics -50°C 0 -58°F 0
+250°C +482°F
-55°C
-67°F
-500 -580
-550 -670
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply line from the analog input area.
• Channels are not insulated from each other.
Number of I/O 0 points
points occupied (This number is not related to the maximum number of input/output points of the PLC.)
I-8
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 2.4 A/D Conversion Time
A
2.4 A/D Conversion Time
Common Items
This section describes the A/D conversion time.
FX3UC-4AD
FX3U-4AD
1. A/D conversion and special data register update timing
A/D conversion is performed at every scan time of the PLC.
During execution of END instruction, the PLC performs A/D conversion, reads out the A/D converted data,
and then writes the data in the special data registers.
FX3U-4AD-PT-ADP FX3S Series PLC C
FX3U-4AD-ADP
Sequence
program
A/D conversion start
command
A/D
conversion D
Digital value reading END instruction
FX3G-2AD-BD
250 s/4ch
FX3U-4DA
3. A/D conversion speed (data update time)
During execution of the END instruction, the A/D converted data of all 4 channels will be read out in 250 μs,
and the data read out will be written to the special data registers.
END instruction execution time will be 250 μs.
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
I-9
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 2.4 A/D Conversion Time
Sequence
program
A/D conversion start
A/D command
conversion
Digital value reading
250 s/4ch
A/D conversion start END instruction
A/D command
conversion
Digital value reading
250 s/4ch
I-10
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 2.5 Temperature Measurement
A
2.4.3 When connected to a FX3U/FX3UC PLC
Common Items
1. A/D conversion and special data register update timing
A/D conversion is performed at every scan time of the PLC.
During execution of END instruction, the PLC performs A/D conversion, reads out the A/D converted data,
and then writes the data in the special data registers. B
FX3UC-4AD
FX3U-4AD
FX3U-4AD-PT-ADP FX3U-4AD-PT-ADP
n'th 1st FX3U/FX3UC Series PLC
Sequence
FX3U-4AD-ADP
A/D command
conversion
Digital value reading
200 s/4ch
A/D conversion start END instruction
A/D
conversion
command
D
Digital value reading
FX3G-2AD-BD
200 s/4ch
FX3U-4DA
3. If two or more analog special adapters are connected
During execution of the END instruction, data will be read out from all the connected adapters (in the order of
1st adapter → 2nd adapter … 4th adapter).
FX3U-4DA-ADP
and the data read out will be written to the special data registers.
END instruction execution time will be "200 μs × number of connected adapters."
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
I-11
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input)
3. Wiring
This chapter describes the PT-ADP wiring.
Observe the following caution to wire the PT-ADP.
WIRING PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before attempting wiring work.
Failure to do so may cause electric shock or damage to the product.
WIRING PRECAUTIONS
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn
out.
• Do not wire vacant terminals externally.
Doing so may damage the product.
• Perform class D grounding (grounding resistance: 100Ω or less) to the grounding terminal on the main unit.
Do not use common grounding with heavy electrical systems.
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
• Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise:
- Do not bundle the power line or shield of the analog input/output cable together with or lay it close to the main
circuit, high-voltage line, or load line.
Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
100mm (3.94") or more away from the main circuit, high-voltage line, or load line.
- Ground the shield of the analog input/output cable at one point on the signal receiving side.
However, do not use common grounding with heavy electrical systems.
• Make sure to properly wire to the terminal block (European type) in accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
- The disposal size of the cable end should follow the dimensions described in the manual.
- Tightening torque should follow the specifications in the manual.
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
I-12
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 3.1 Terminal Layout
A
3.1 Terminal Layout
Common Items
The terminals of the PT-ADP are arranged as follows:
FX3UC-4AD
FX3U-4AD
Signal Application
C
24+ External power
FX3U-4AD-ADP
24-
Ground terminal
L1+ Channel-1 platinum
L1- resistance thermometer
I1- sensor input
L2+ Channel-2 platinum
D
resistance thermometer
FX3G-2AD-BD
L2-
I2- sensor input
L3+ Channel-3 platinum
L3- resistance thermometer
I3- sensor input
L4+
L4-
Channel-4 platinum
resistance thermometer
E
FX3U-4DA
I4- sensor input
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
I-13
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 3.2 Applicable Cable and Terminal Tightening Torque
1. Cables
Applicable cable and tightening torque
Wire size Tightening
Termination
(stranded wire/solid wire) torque
2 2 • To connect a stranded cable, peel the cover off the cable
Single-wire 0.3 mm to 0.5 mm and then twist the core before connection.
(AWG22 to 20)
• To connect a single-wire cable, just strip the cover off the
2-wire 0.3 mm2 (AWG22)×2 cable before connection.
0.22 to • Ferrule with insulation sleeve
0.3 mm2 to 0.5 mm2 0.25 N•m (recommended terminal)
Ferrule with (AWG22 to 20) AI 0.5-8WH : Manufactured by Phoenix Contact
insulation (Refer to the external • Caulking tool
sleeve view of ferrule shown in
CRIMPFOX 6*1 : Manufactured by Phoenix Contact
the following figure.)
(or CRIMPFOX 6T-F*2 : Manufactured by Phoenix Contact)
*1. Old model name : CRIMPFOX ZA 3
*2. Old model name : CRIMPFOX UD 6
3. Tool
For tightening the terminal, use a commercially available small screwdriver
The head
having a straight form that is not widened toward the end as shown right. should be
straight.
Note:
If the diameter of screwdriver grip is too small, tightening torque will not be
able to be achieved. To achieve the appropriate tightening torque shown in 0.4mm 2.5mm
the table above, use the following screwdriver or an appropriate (0.01") (0.09")
replacement (grip diameter: approximately 25 mm (0.98")).
<Reference>
Manufacturer Type
Phoenix Contact SZS 0.4 × 2.5
I-14
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 3.3 Power Supply Line
A
3.3 Power Supply Line
Common Items
Connect the 24 V DC power supply line of the PT-ADP to the 24+ and 24- terminals of the terminal block.
FX3UC-4AD
FX3U-4AD
PT-ADP FX3S/FX3G/FX3U PT-ADP FX3S/FX3G/FX3U
Series PLC Series PLC
+5V +5V (Main unit)
(Main unit)
FX3U-4AD-ADP
24+ 24- 24+ 24- 24V 0V
D
Terminal Terminal
FX3G-2AD-BD
block block
Fuse
Class-D Class-D
24V DC grounding grounding
Caution regarding connection of the power supply line: E
• Ground the " " terminal to a class-D grounding power supply line (100 Ω or less) together with the
FX3U-4DA
ground terminal of the PLC main unit.
• When using an external power supply, turn it ON at the same time with the main unit or earlier than the
main unit. When turning OFF the power, confirm the safety of the system, and then turn OFF the power of
the PLC (including special adapter) at the same time.
F
3.3.2 To connect to the FX3GC/FX3UC Series PLC
FX3U-4DA-ADP
Example of wiring of FX3UC Series PLC
PT-ADP FX3UC Series PLC
(Main unit)
+5V
G
FX3G-1DA-BD
Power
connector H
FX3U-3A-ADP
Fuse
I
Class-D
FX3U-4AD-PT
24V DC grounding
For example of wiring of FX3GC Series PLC, refer to the following manual.
→ Refer to the FX3GC Series User’s Manual - Hardware Edition
-ADP
• Ground the " " terminal to a class-D grounding power supply line (100 Ω or less) together with the
grounding terminal of the PLC main unit.
-ADP
I-15
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 3.4 Selection of the Platinum Resistance Thermometer Sensor
PT-ADP
+5V
Shield +5V
+5V
24+
24V DC*2
24-
Class-D grounding
L+, L-, I-, ch: represents the channel number.
*1. Separate the cable of the platinum resistance thermometer sensor from the other power cables or
areas easily affected by inductive noise (of the commercial power, etc.).
*2. For FX3S/FX3G/FX3U Series PLC (AC power type), the 24 V DC service power supply is also
available.
3.6 Grounding
Grounding should be performed as stated below.
• The grounding resistance should be 100 Ω or less.
• Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" as shown in the following
figure.
→ For details, refer to the User’s Manual - Hardware Edition of the each PLC Series.
I-16
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.1 Loading of A/D Conversion Data
Common Items
4. Programming
This chapter describes how to create programs that can read analog data using the PT-ADP. B
FX3UC-4AD
FX3U-4AD
4.1 Loading of A/D Conversion Data
1) The input analog data will be converted into digital data and then stored in the special devices of the
FX3S/FX3G/FX3GC/FX3U/FX3UC Series PLC.
C
2) If data is stored in the special devices, the averaging time can be set, and the input mode can be
FX3U-4AD-ADP
specified.
3) Special auxiliary relays (10 points) and special data registers (10 points) are assigned automatically
starting from the adapter nearest to the main unit.
→ For a detailed description of special device assignment, refer to Section 4.2.
• FX3S Series PLC D
FX3G-2AD-BD
Communi-
cation
FX3U-4AD special FX3S-CNV
-PT-ADP adapter -ADP FX3S Series PLC
Special devices
Special auxiliary relays: E
A/D M8280 to M8289 Sequence
FX3U-4DA
Special data registers: program
D8280 to D8289
FX3U-4DA-ADP
cation
FX3U-4AD FX3U-4AD
special
-PT-ADP -PT-ADP FX3G/FX3GC Series PLC*2
adapter
2nd*1 1st
Special devices
Special auxiliary relays:
M8280 to M8289 G
A/D Special data registers:
FX3G-1DA-BD
D8280 to D8289 Sequence
Program
Special auxiliary relays:
M8290 to M8299
A/D Special data registers:
D8290 to D8299
H
FX3U-3A-ADP
The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
next adapter as the 2nd analog special adapter. However, in this case, do not include the connector
conversion adapter and the communication special adapter.
*1. The second special adapter is not available in the FX3G Series PLC (14-point and 24-point type).
*2. A connector conversion adapter is required to connect the FX3U-4AD-PT-ADP to the FX3G Series I
PLC.
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
I-17
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.2 List of Special Devices
The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
next adapter as the 2nd analog special adapter, and so on. However, in this case, do not include the high-
speed input/output special adapter, communication special adapter, and the CF card special adapter.
*1. An expansion board is required to connect the FX3U-4AD-PT-ADP to the FX3U/FX3UC-32MT-LT(-2)
PLC.
I-18
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.2 List of Special Devices
A
• FX3G/FX3GC Series PLC
Common Items
R: Read / W: Write
Special Device number
Description Attribute Reference
device 1st 2nd
Section
Special M8280 M8290 Selects the temperature unit. R/W
4.3 B
auxiliary
FX3UC-4AD
FX3U-4AD
relay M8281 to M8291 to
Unused (Do not use.) - -
M8289 M8299
D8280 D8290 Channel-1 temperature measurement data R
D8281 D8291 Channel-2 temperature measurement data R Section
4.4
D8282
D8283
D8292
D8293
Channel-3 temperature measurement data
Channel-4 temperature measurement data
R
R
C
FX3U-4AD-ADP
D8284 D8294 Averaging time for channel 1 (Setting range: 1 to 4095) R/W
Special
data D8285 D8295 Averaging time for channel 2 (Setting range: 1 to 4095) R/W Section
register D8286 D8296 Averaging time for channel 3 (Setting range: 1 to 4095) R/W 4.5
D8287 D8297 Averaging time for channel 4 (Setting range: 1 to 4095) R/W
Section D
D8288 D8298 Error status R/W
4.6
FX3G-2AD-BD
Section
D8289 D8299 Model code = 20 R
4.7
FX3U-4DA
Special Device number
Description Attribute Reference
device 1st 2nd 3rd 4th
Section
Special M8260 M8270 M8280 M8290 Selects the temperature unit. R/W
4.3
auxiliary
relay M8261 to M8271 to M8281 to M8291 to F
Unused (Do not use.) - -
FX3U-4DA-ADP
M8269 M8279 M8289 M8299
Channel-1 temperature
D8260 D8270 D8280 D8290 R
measurement data
Channel-2 temperature
D8261 D8271 D8281 D8291 R
measurement data Section
Channel-3 temperature 4.4 G
D8262 D8272 D8282 D8292 R
FX3G-1DA-BD
measurement data
Channel-4 temperature
D8263 D8273 D8283 D8293 R
measurement data
Averaging time for channel 1
Special D8264 D8274 D8284 D8294 R/W
(Setting range: 1 to 4095)
data
register Averaging time for channel 2 H
D8265 D8275 D8285 D8295 R/W
(Setting range: 1 to 4095)
FX3U-3A-ADP
Section
Averaging time for channel 3 4.5
D8266 D8276 D8286 D8296 R/W
(Setting range: 1 to 4095)
Averaging time for channel 4
D8267 D8277 D8287 D8297 R/W
(Setting range: 1 to 4095)
Section I
D8268 D8278 D8288 D8298 Error status R/W
4.6
FX3U-4AD-PT
Section
D8269 D8279 D8289 D8299 Model code = 20 R
4.7
-ADP
J
FX3U-4AD-PTW
-ADP
I-19
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.3 Selection of Temperature Unit
I-20
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.4 Temperature Measurement
A
4.4 Temperature Measurement
Common Items
The temperature data input in the PT-ADP will be stored in the special data registers.
The special data registers that store the temperature data are shown in the following table:
• FX3S Series PLC
Special data register Description
B
FX3UC-4AD
FX3U-4AD
D8280 Stores the channel-1 temperature measurement data.
D8281 Stores the channel-2 temperature measurement data.
D8282 Stores the channel-3 temperature measurement data.
D8283 Stores the channel-4 temperature measurement data.
C
FX3U-4AD-ADP
• FX3G/FX3GC Series PLC
Special data register
Description
1st 2nd
D8280
D8281
D8290
D8291
Stores the channel-1 temperature measurement data.
Stores the channel-2 temperature measurement data.
D
FX3G-2AD-BD
D8282 D8292 Stores the channel-3 temperature measurement data.
D8283 D8293 Stores the channel-4 temperature measurement data.
FX3U-4DA
Description
1st 2nd 3rd 4th
D8260 D8270 D8280 D8290 Stores the channel-1 temperature measurement data.
D8261 D8271 D8281 D8291 Stores the channel-2 temperature measurement data.
D8262 D8272 D8282 D8292 Stores the channel-3 temperature measurement data.
D8263 D8273 D8283 D8293 Stores the channel-4 temperature measurement data.
F
FX3U-4DA-ADP
The immediate data or the average data (data averaged in accordance with the specified averaging time) will
be stored in the above data registers as the temperature measurement data.
→ For a detailed description of the averaging time, refer to Section 4.5.
FX3G-1DA-BD
The special data registers for temperature measurement data are for reading only.
Do not change (rewrite) the current data using the sequence program, indicator, or device monitor of the
programming tool.
J
FX3U-4AD-PTW
-ADP
I-21
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.5 Averaging Time
I-22
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.6 Error Status
A
4.6 Error Status
Common Items
If an error is detected in the PT-ADP, the error status data will be stored in the corresponding special data
register.
The following table shows the special data registers that store the error status data:
• FX3S Series PLC B
FX3UC-4AD
FX3U-4AD
Special data register Description
D8288 Stores the error status data.
FX3U-4AD-ADP
D8288 D8298 Stores the error status data.
FX3G-2AD-BD
Check the ON/OFF status of each bit of the error status data register to determine the error. Errors are
assigned to the bits as shown in the following table. Create a program to detect errors.
b0
The temperature measurement data
of channel 1 is outside the specified b5 Averaging time setting error
E
FX3U-4DA
range, or disconnection is detected.
The temperature measurement data
b1 of channel 2 is outside the specified b6 PT-ADP hardware error
range, or disconnection is detected.
b2
The temperature measurement data
of channel 3 is outside the specified b7 PT-ADP communication data error F
FX3U-4DA-ADP
range, or disconnection is detected.
The temperature measurement data
b3 of channel 4 is outside the specified b8 to b15 Unused
range, or disconnection is detected.
b4 EEPROM error - -
G
1. Caution regarding use of error status data
FX3G-1DA-BD
If a PT-ADP hardware error (b6) or PT-ADP communication data error (b7) is detected, it is necessary to clear
the error status with a program at the next power-on of the PLC.
For this reason, be sure to create the following program:
• For FX3S/FX3G/FX3GC/FX3U/FX3UC Series PLC
H
M8000
FX3U-3A-ADP
FNC 12
D8288 K4M0
MOV
Normally
ON
M8002
RST M6 Error status of 3rd*1 analog special adapter
Initial pulse
b6 = OFF (PT-ADP hardware error)
I
FX3U-4AD-PT
FNC 12
K4M0 D8288
MOV J
FX3U-4AD-PTW
I-23
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.6 Error Status
M8002
RST D8268.6 Error status of 1st analog special adapter
b6 = OFF (PT-ADP hardware error)
Initial pulse
M8000
FNC 12
D8288 K4M0
Normally ON MOV
M0
Y000 The temperature measurement data
of channel 1 is outside the specified
range, or disconnection is detected.
M1
Y001 The temperature measurement data
of channel 2 is outside the specified
range, or disconnection is detected.
M2
Y002 The temperature measurement data
of channel 3 is outside the specified
range, or disconnection is detected.
M3
Y003 The temperature measurement data
of channel 4 is outside the specified
range, or disconnection is detected.
M4
Y004 EEPROM error in 3rd*1 adapter.
M5
Y005 Averaging time setting error in 3rd*1
adapter.
M6
Y006 PT-ADP hardware error in 3rd*1
adapter.
M7
Y007 PT-ADP communication data error in
3rd*1 adapter.
I-24
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.7 Model Code
A
3. Program Example 2 (For FX3U/FX3UC Series PLC)
Common Items
D8268.0
Y000 The temperature measurement data
of channel 1 is outside the specified
D8268.1
range, or disconnection is detected.
B
Y001 The temperature measurement data
FX3UC-4AD
FX3U-4AD
of channel 2 is outside the specified
range, or disconnection is detected.
D8268.2
Y002 The temperature measurement data
of channel 3 is outside the specified
D8268.3
range, or disconnection is detected.
C
Y003 The temperature measurement data
FX3U-4AD-ADP
of channel 4 is outside the specified
range, or disconnection is detected.
D8268.4
Y004 EEPROM error in 1st adapter.
D8268.5
D
Averaging time setting error in 1st
FX3G-2AD-BD
Y005
adapter.
D8268.6
Y006 PT-ADP hardware error in 1st
adapter.
D8268.7 E
Y007 PT-ADP communication data error in
FX3U-4DA
1st adapter.
FX3U-4DA-ADP
Initial value: K20
Numeric data type: Decimal (K)
When the PT-ADP is connected, model code "20" will be stored in the corresponding special data register.
The following table shows the special data registers that store the model code:
• FX3S Series PLC G
Special data register Description
FX3G-1DA-BD
D8289 Model code
Use the special data registers above to check whether PT-ADP is connected or not.
-ADP
I-25
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.8 Basic Program Example
M8000
FNC 12 D8280 D100 Stores the current value of the channel-1
Normally MOV temperature measurement data in the D100.
ON
FNC 12 D8281 D101 Stores the average value of the channel-2
MOV temperature measurement data in the D101.
Even if the temperature measurement data is not stored in D100 or D101, data register D8280 or D8281
can be directly used in the arithmetic operation instruction or a PID instruction.
*1. "1st" for the FX3S/FX3G/FX3GC PLC.
• For FX3U/FX3UC Series PLC
The following program will store the temperature measurement data (°C) from channels 1 and 2 of the 1st
adapter to D100 and D101, respectively. The averaging time is set to "1" (immediate data) for channel 1,
and "5" for channel 2.
M8000
FNC 12 D8260 D100 Stores the current value of the channel-1
Normally MOV temperature measurement data in the D100.
ON
FNC 12 D8261 D101 Stores the average value of the channel-2
MOV temperature measurement data in the D101.
Even if the temperature measurement data is not stored in D100 or D101, data register D8260 or D8261
can be directly used in the arithmetic operation instruction or a PID instruction.
I-26
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Troubleshooting
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 5.1 PLC Version Number Check
Common Items
5. Troubleshooting
This chapter describes the troubleshooting methods and error status. B
If the temperature measurement data is not input, or if the proper digital value is not input, check the following
FX3UC-4AD
FX3U-4AD
items:
• Version number of the PLC
• Wiring
• Special devices
C
• Programs
FX3U-4AD-ADP
• Error status
FX3G-2AD-BD
• Any versions (from Ver. 1.00 (initial version) to the latest version) of the FX3G Series are compatible.
• Any versions (from Ver. 1.40 (initial version) to the latest version) of the FX3GC Series are compatible.
• Any versions (from Ver. 2.20 (initial version) to the latest version) of the FX3U Series are compatible.
• Check the version number of the FX3UC Series. The version number should be 1.30 or later.
→ For a detailed description of the version check method,
E
FX3U-4DA
refer to A. Common Items Subsection 5.1.2.
FX3U-4DA-ADP
1. Power
The PT-ADP needs driving power. Verify that the power supply line is properly connected. Also check that the
POWER indicator lamp of the PT-ADP is on.
FX3G-1DA-BD
→ For a detailed description of wiring, refer to Chapter 3.
1. Temperature measurement
Verify that the special device for the selected channel is correctly selected. This special device should be
selected depending on the connecting position and the channel.
2. Averaging time
Check that the set averaging time is within the specified range. The averaging time should be set in the range I
from 1 to 4095. If the set averaging time is outside the specified range, an error occurs.
FX3U-4AD-PT
3. Error status
Check that no error is detected in the PT-ADP.
-ADP
If an error is detected, check the details of the error, and then check the wiring and programs.
→ For a detailed description of special devices, refer to Chapter 4.
J
FX3U-4AD-PTW
-ADP
I-27
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Troubleshooting
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 5.4 Program Check
I-28
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Troubleshooting
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 5.5 Error Status Check
A
4. PT-ADP hardware error (b6)
Common Items
1) Description of error
The PT-ADP does not operate properly.
2) Remedy
Check that the 24 V DC power is properly supplied to the PT-ADP. Also check that the PT-ADP is
correctly connected to the PLC. B
If the problem cannot be solved even after the above check, please contact your local Mitsubishi Electric
FX3UC-4AD
FX3U-4AD
representative.
FX3U-4AD-ADP
Check that the PT-ADP is correctly connected to the PLC.
If the problem cannot be solved even after the above check, please contact your local Mitsubishi Electric
representative.
FX3G-2AD-BD
E
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
I-29
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Troubleshooting
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 5.5 Error Status Check
MEMO
I-30
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input)
Common Items
B
FX3UC-4AD
FX3U-4AD
FX3S/FX3G/FX3GC/FX3U/FX3UC Series
Programmable Controllers C
FX3U-4AD-ADP
User's Manual [Analog Control Edition]
J. FX3U-4AD-PTW-ADP D
(4-channel Platinum Resistance
FX3G-2AD-BD
Thermometer Data Input)
E
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
Foreword
This manual describes the specifications, wiring, and operation methods for the FX3U-4AD-PTW-ADP special I
adapter (4-channel platinum resistance thermometer input) and should be read and understood before
FX3U-4AD-PT
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
J
FX3U-4AD-PTW
rights which may occur as a result of using the contents noted in this manual.
J-1
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input)
J-2
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 1.1 Outline of Functions
Common Items
1. Outline
This chapter describes the outline of FX3U-4AD-PTW-ADP (referred to as PTW-ADP). B
FX3UC-4AD
FX3U-4AD
1.1 Outline of Functions
The FX3U-4AD-PTW-ADP is an analog special adapter. Connect the FX3U-4AD-PTW-ADP to the FX3S/FX3G/
FX3GC/FX3U/FX3UC Series PLC to read the temperature data from the 4-channel platinum resistance
thermometers. C
FX3U-4AD-ADP
1) Only 1 PTW-ADP unit can be connected to the FX3S Series PLC.
Up to 2*1 PTW-ADP units can be connected to the FX3G/FX3GC Series PLC.
Up to 4 PTW-ADP units can be connected to the FX3U/FX3UC Series PLC.
(including the other analog expansion boards, analog special adapters)
2) After connection of the platinum resistance thermometer (Pt100), measurement of temperature will be
possible. D
3) The temperature measurement data will be automatically written to the special data registers of the FX3S/
FX3G-2AD-BD
FX3G/FX3GC/FX3U/FX3UC Series PLC.
FX3U-4DA
including the other analog expansion Number of connectable
units
boards, analog special adapters FX3S/FX3G/FX3GC/FX3U/FX3UC
Series PLC
FX3U-4DA-ADP
Expansion
4th 3rd 2nd 1st
board*2
adapter adapter adapter adapter For a detailed
description of wiring,
G
Analog data
FX3G-1DA-BD
refer to Chapter 3.
For FX3S/FX3G/FX3GC/
FX3U/FX3UC Series PLC For a detailed description
H
of special devices, refer to
FX3U-3A-ADP
*2. The expansion board is not required when connecting with the FX3GC/FX3UC (D, DS, DSS) Series PLC.
For the FX3S/FX3G Series PLC a connector conversion adapter is used.
*3. FX3S/FX3G/FX3GC PLCs use the following special devices. J
For FX3S Series PLC For FX3G/FX3GC Series PLC
FX3U-4AD-PTW
J-3
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 1.2 Setup Procedure Before Starting Operation
FX3U-4AD-PTW-ADP
Refer to Chapter 1.
J-4
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 1.3 Connectable PLC and Its Version Number
A
1.3 Connectable PLC and Its Version Number
Common Items
PTW-ADP is compatible with the following PLC.
FX3UC-4AD
FX3U-4AD
FX3G Series PLC Ver. 1.00 or later After June 2008 (From first product)
FX3GC Series PLC Ver. 1.40 or later After January 2012 (From first product)
FX3U Series PLC Ver. 2.20 or later After May 2005 (From first product)
FX3UC Series PLC Ver. 1.30 or later After August 2004
C
1. Version check
FX3U-4AD-ADP
The PLC version can be checked by reading the last three digits of device D8001 or D8101.
→ For a detailed description of the version check,
refer to A. Common Items Subsection 5.1.2.
FX3G-2AD-BD
→ For a detailed description of how to check the manufacturer's serial number,
refer to A. Common Items Subsection 5.1.1.
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
J-5
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 1.4 Compatible Programming Tool Version Number
1. English versions
Model name Media model name Applicable version Remarks
FX3S PLC
GX Works2 SWDNC-GXW2-E Ver. 1.492N or later
-
FX-30P Ver. 1.50 or later
FX3G PLC
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer SWD5C-GPPW-E Ver. 8.72A or later -
FX-30P Ver. 1.00 or later
FX3GC PLC
GX Works2 SWDNC-GXW2-E Ver. 1.77F or later
-
FX-30P Ver. 1.30 or later
FX3U and FX3UC PLCs
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer SWD5C-GPPW-E Ver. 8.18U or later -
FX-30P Ver. 1.00 or later
2. Japanese versions
Model name Media model name Applicable version Remarks
FX3S PLC
GX Works2 SWDNC-GXW2-J Ver. 1.492N or later
-
FX-30P Ver. 1.50 or later
FX3G PLC
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
GX Developer SWD5C-GPPW-J Ver. 8.72A or later -
FX-30P Ver. 1.00 or later
FX3GC PLC
GX Works2 SWDNC-GXW2-J Ver. 1.77F or later
-
FX-30P Ver. 1.30 or later
FX3U and FX3UC PLCs
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
GX Developer SWD5C-GPPW-J Ver. 8.13P or later -
FX-30P Ver. 1.00 or later
Point
• It is possible to create programs in FX3GC PLC using programming tools of inapplicable versions by
selecting "FX3G" as the alternative model.
• It is possible to create programs in FX3S PLC using programming tools of inapplicable versions by
selecting "FX3G" as the alternative model. However, memory capacity setting of the PLC parameter must
be set to 4000 steps or less.
J-6
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 2.1 Generic Specifications
Common Items
2. Specifications
This chapter describes the general, power supply, and performance specifications for the PTW-ADP. B
FX3UC-4AD
FX3U-4AD
2.1 Generic Specifications
Item Specifications C
FX3U-4AD-ADP
Ambient 0 to 55 °C (32 to 131 °F) when operating
temperature -25 to 75 °C (-13 to 167 °F) when stored
Relative
5 to 95 %RH (no condensation) when operating
humidity
Frequency Acceleration Half amplitude D
(Hz) (m/s2) (mm)
FX3G-2AD-BD
Tested 10 times in each
Vibration 10 to 57 - 0.035 direction (X-, Y-, and Z-
DIN Rail Mounting
resistance*1 57 to 150 4.9 - axis directions) (Total:
80 min, each)
10 to 57 − 0.075
Direct Mounting*2
−
Shock
57 to 150 9.8
E
m/s2
FX3U-4DA
147 Acceleration, Action time: 11 ms, 3 times by half-sine pulse in each direction X, Y, and Z
resistance*1
Noise Using noise simulator of:
resistance Noise voltage: 1,000 Vp-p / Noise width: 1 μs / Rise: 1 ns / Cycle: 30 to 100 Hz
Dielectric
withstand
voltage
500 V AC, for 1 min F
Between all terminals and ground terminal
FX3U-4DA-ADP
Insulation 5 MΩ or more using 500 V DC
resistance insulation resistance meter
Class D grounding (grounding resistance: 100 Ω or less)
Grounding
<Common grounding with a heavy electrical system is not allowed.>*3
Working
Free from corrosive or flammable gas and excessive conductive dusts
G
environment
FX3G-1DA-BD
Working
altitude < 2000 m*4
*4. If the pressure is higher than the atmospheric pressure, do not use the PTW-ADP.
The PTW-ADP may malfunction.
-ADP
J
FX3U-4AD-PTW
-ADP
J-7
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 2.2 Power Supply Specifications
Items Specification
A/D conversion circuit 24 V DC +20 % -15 %, 50 mA
driving power (It is necessary to connect a 24 V DC power supply to the terminal block.)
5 V DC, 15 mA
Interface driving power (Since the internal power is supplied from the FX Series main unit, it is not necessary
to supply the power.)
Specifications
Items
Centigrade (°C) Fahrenheit (°F)
3-wire platinum resistance thermometer sensor
Input signal
Pt100 JIS C 1604-1997
Rated temperature
-100 °C to +600 °C -148 °F to +1112 °F
range
Digital output -1000 to +6000 -1480 to +11120
Resolution 0.2 °C to 0.3 °C 0.4 °F to 0.5 °F
• ±0.5 % for full scale (when ambient temperature is 25 °C±5 °C)
Total accuracy
• ±1.0 % for full scale (when ambient temperature is in the range from 0 to 55 °C)
• FX3U/FX3UC Series PLC : 200 μs (The data will be updated at every scan time.)
A/D conversion
• FX3S/FX3G/FX3GC Series PLC : 250 μs (The data will be updated at every scan time.)
time
→For a detailed description of data update, refer to Section 2.4.
+6150 +11390
+6000 +11120
+1139°F
+615°C
Input
characteristics -100°C 0 -148°F 0
-115°C
+600°C +1112°F
-175°F
-1000 -1480
-1150 -1750
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply line from the analog input area.
• Channels are not insulated from each other.
Number of I/O 0 points
points occupied (This number is not related to the maximum number of input/output points of the PLC.)
J-8
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 2.4 A/D Conversion Time
A
2.4 A/D Conversion Time
Common Items
This section describes the A/D conversion time.
FX3UC-4AD
FX3U-4AD
1. A/D conversion and special data register update timing
A/D conversion is performed at every scan time of the PLC.
During execution of END instruction, the PLC performs A/D conversion, reads out the A/D converted data,
and then writes the data in the special data registers.
FX3U-4AD-PTW-ADP FX3S Series PLC C
FX3U-4AD-ADP
Sequence
program
A/D conversion start
command
A/D
conversion D
END instruction
FX3G-2AD-BD
Digital value reading
250 s/4ch
FX3U-4DA
3. A/D conversion speed (data update time)
During execution of the END instruction, the A/D converted data of all 4 channels will be read out in 250 μs,
and the data read out will be written to the special data registers.
END instruction execution time will be 250 μs
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
J-9
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 2.4 A/D Conversion Time
Sequence
program
A/D conversion start
A/D command
conversion
Digital value reading
250 s/4ch
A/D conversion start END instruction
A/D command
conversion
Digital value reading
250 s/4ch
J-10
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 2.5 Temperature Measurement
A
2.4.3 When connected to a FX3U/FX3UC PLC
Common Items
1. A/D conversion and special data register update timing
A/D conversion is performed at every scan time of the PLC.
During execution of END instruction, the PLC performs A/D conversion, reads out the A/D converted data,
and then writes the data in the special data registers. B
FX3UC-4AD
FX3U-4AD
FX3U-4AD-PTW-ADP FX3U-4AD-PTW-ADP
n'th 1st FX3U/FX3UC Series PLC
Sequence
FX3U-4AD-ADP
A/D command
conversion
Digital value reading
200 s/4ch
A/D conversion start END instruction
A/D
conversion
command
D
Digital value reading
FX3G-2AD-BD
200 s/4ch
FX3U-4DA
3. If two or more analog special adapters are connected
During execution of the END instruction, data will be read out from all the connected adapters (in the order of
1st adapter → 2nd adapter … 4th adapter).
FX3U-4DA-ADP
and the data read out will be written to the special data registers.
END instruction execution time will be "200 μs × number of connected adapters."
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
J-11
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input)
3. Wiring
This chapter describes the PTW-ADP wiring.
Observe the following caution to wire the PTW-ADP.
WIRING PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before attempting wiring work.
Failure to do so may cause electric shock or damage to the product.
WIRING PRECAUTIONS
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn
out.
• Do not wire vacant terminals externally.
Doing so may damage the product.
• Perform class D grounding (grounding resistance: 100Ω or less) to the grounding terminal on the main unit.
Do not use common grounding with heavy electrical systems.
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
• Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise:
- Do not bundle the power line or shield of the analog input/output cable together with or lay it close to the main
circuit, high-voltage line, or load line.
Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
100mm (3.94") or more away from the main circuit, high-voltage line, or load line.
- Ground the shield of the analog input/output cable at one point on the signal receiving side.
However, do not use common grounding with heavy electrical systems.
• Make sure to properly wire to the terminal block (European type) in accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
- The disposal size of the cable end should follow the dimensions described in the manual.
- Tightening torque should follow the specifications in the manual.
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
J-12
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 3.1 Terminal Layout
A
3.1 Terminal Layout
Common Items
The terminals of the PTW-ADP are arranged as follows:
FX3UC-4AD
FX3U-4AD
Signal Application
C
24+ External power
FX3U-4AD-ADP
24-
Ground terminal
L1+ Channel-1 platinum
L1- resistance thermometer
I1- sensor input
L2+ Channel-2 platinum
D
resistance thermometer
FX3G-2AD-BD
L2-
I2- sensor input
L3+ Channel-3 platinum
L3- resistance thermometer
I3- sensor input
L4+
L4-
Channel-4 platinum
resistance thermometer
E
FX3U-4DA
I4- sensor input
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
J-13
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 3.2 Applicable Cable and Terminal Tightening Torque
1. Cables
Applicable cable and tightening torque
Wire size Tightening
Termination
(stranded wire/solid wire) torque
2 2 • To connect a stranded cable, peel the cover off the cable
Single-wire 0.3 mm to 0.5 mm and then twist the core before connection.
(AWG22 to 20)
• To connect a single-wire cable, just strip the cover off the
2-wire 0.3 mm2 (AWG22)×2 cable before connection.
0.22 to • Ferrule with insulation sleeve
0.3 mm2 to 0.5 mm2 0.25 N•m (recommended terminal)
Ferrule with (AWG22 to 20) AI 0.5-8WH : Manufactured by Phoenix Contact
insulation (Refer to the external • Caulking tool
sleeve view of ferrule shown in
CRIMPFOX 6*1 : Manufactured by Phoenix Contact
the following figure.)
(or CRIMPFOX 6T-F*2 : Manufactured by Phoenix Contact)
3. Tool
For tightening the terminal, use a commercially available small screwdriver
The head
having a straight form that is not widened toward the end as shown right. should be
straight.
Note:
If the diameter of screwdriver grip is too small, tightening torque will not be
able to be achieved. To achieve the appropriate tightening torque shown in 0.4mm 2.5mm
the table above, use the following screwdriver or an appropriate (0.01") (0.09")
replacement (grip diameter: approximately 25 mm (0.98")).
<Reference>
Manufacturer Type
Phoenix Contact SZS 0.4 × 2.5
J-14
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 3.3 Power Supply Line
A
3.3 Power Supply Line
Common Items
Connect the 24 V DC power supply line of the PTW-ADP to the 24+ and 24- terminals of the terminal block.
FX3UC-4AD
FX3U-4AD
PTW-ADP FX3S/FX3G/FX3U PTW-ADP FX3S/FX3G/FX3U
Series PLC Series PLC
+5V (Main unit) +5V (Main unit)
FX3U-4AD-ADP
24+ 24- 24V 0V
24+ 24-
D
Terminal Terminal
FX3G-2AD-BD
block block
Fuse
Class-D Class-D
24V DC grounding grounding
Caution regarding connection of the power supply line: E
• Ground the " " terminal to a class-D grounding power supply line (100 Ω or less) together with the
FX3U-4DA
ground terminal of the PLC main unit.
• When using an external power supply, turn it ON at the same time with the main unit or earlier than the
main unit. When turning OFF the power, confirm the safety of the system, and then turn OFF the power of
the PLC (including special adapter) at the same time.
F
3.3.2 To connect to the FX3GC/FX3UC Series PLC
FX3U-4DA-ADP
Example of wiring of FX3UC Series PLC
PTW-ADP FX3UC Series PLC
(Main unit)
+5V
G
FX3G-1DA-BD
Power
connector H
FX3U-3A-ADP
Fuse
I
Class-D
FX3U-4AD-PT
24V DC grounding
For example of wiring of FX3GC Series PLC, refer to the following manual.
→ Refer to the FX3GC Series User’s Manual - Hardware Edition
-ADP
• Ground the " " terminal to a class-D grounding power supply line (100 Ω or less) together with the
grounding terminal of the PLC main unit.
-ADP
J-15
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 3.4 Selection of the Platinum Resistance Thermometer Sensor
PTW-ADP
+5V
Shield +5V
+5V
24+
24V DC*2
24-
Class-D grounding
L+, L-, I-, ch: represents the channel number.
*1. Separate the cable of the platinum resistance thermometer sensor from the other power cables or
areas easily affected by inductive noise (of the commercial power, etc.).
*2. For FX3S/FX3G/FX3U Series PLC (AC power type), the 24 V DC service power supply is also
available.
3.6 Grounding
Grounding should be performed as stated below.
• The grounding resistance should be 100 Ω or less.
• Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" as shown in the following
figure.
→ For details, refer to the User’s Manual - Hardware Edition of the each PLC Series.
J-16
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.1 Loading of A/D Conversion Data
Common Items
4. Programming
This chapter describes how to create programs that can read analog data using the PTW-ADP. B
FX3UC-4AD
FX3U-4AD
4.1 Loading of A/D Conversion Data
1) The input analog data will be converted into digital data and then stored in the special devices of the
FX3S/FX3G/FX3GC/FX3U/FX3UC Series PLC.
C
2) If data is stored in the special devices, the averaging time can be set, and the input mode can be
FX3U-4AD-ADP
specified.
3) Special auxiliary relays (10 points) and special data registers (10 points) are assigned automatically
starting from the adapter nearest to the main unit.
→ For a detailed description of special device assignment, refer to Section 4.2.
• FX3S Series PLC D
FX3G-2AD-BD
Communi-
cation
FX3U-4AD special FX3S-CNV
-PTW-ADP adapter -ADP FX3S Series PLC
Special devices
Special auxiliary relays: E
A/D M8280 to M8289 Sequence
FX3U-4DA
Special data registers: program
D8280 to D8289
FX3U-4DA-ADP
Communi-
cation
FX3U-4AD FX3U-4AD
special
-PTW-ADP -PTW-ADP FX3G/FX3GC Series PLC*2
adapter
2nd*1 1st
Special devices
Special auxiliary relays:
G
FX3G-1DA-BD
M8280 to M8289
A/D Special data registers:
D8280 to D8289 Sequence
Program
Special auxiliary relays:
M8290 to M8299
A/D Special data registers:
D8290 to D8299 H
FX3U-3A-ADP
The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
next adapter as the 2nd analog special adapter. However, in this case, do not include the connector
conversion adapter and the communication special adapter.
*1. The second special adapter is not available in the FX3G Series PLC (14-point and 24-point type).
*2. A connector conversion adapter is required to connect the FX3U-4AD-PTW-ADP to the FX3G Series
I
FX3U-4AD-PT
PLC.
-ADP
J
FX3U-4AD-PTW
-ADP
J-17
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.2 List of Special Devices
The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
next adapter as the 2nd analog special adapter, and so on. However, in this case, do not include the high-
speed input/output special adapter, communication special adapter, and the CF card special adapter.
*1. An expansion board is required to connect the FX3U-4AD-PTW-ADP to the FX3U/FX3UC-32MT-LT(-2)
PLC.
J-18
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.2 List of Special Devices
A
• FX3G/FX3GC Series PLC
Common Items
R: Read / W: Write
Special Device number
Description Attribute Reference
device 1st 2nd
Section
Special M8280 M8290 Selects the temperature unit. R/W
4.3 B
auxiliary
FX3UC-4AD
FX3U-4AD
relay M8281 to M8291 to
Unused (Do not use.) - -
M8289 M8299
D8280 D8290 Channel-1 temperature measurement data R
D8281 D8291 Channel-2 temperature measurement data R Section
4.4
D8282
D8283
D8292
D8293
Channel-3 temperature measurement data
Channel-4 temperature measurement data
R
R
C
FX3U-4AD-ADP
D8284 D8294 Averaging time for channel 1 (Setting range: 1 to 4095) R/W
Special
data D8285 D8295 Averaging time for channel 2 (Setting range: 1 to 4095) R/W Section
register D8286 D8296 Averaging time for channel 3 (Setting range: 1 to 4095) R/W 4.5
D8287 D8297 Averaging time for channel 4 (Setting range: 1 to 4095) R/W
Section D
D8288 D8298 Error status R/W
4.6
FX3G-2AD-BD
Section
D8289 D8299 Model code = 21 R
4.7
FX3U-4DA
Description Attribute Reference
device 1st 2nd 3rd 4th
Section
Special M8260 M8270 M8280 M8290 Selects the temperature unit. R/W
4.3
auxiliary
relay M8261 to M8271 to M8281 to M8291 to
M8269 M8279 M8289 M8299
Unused (Do not use.) - -
F
Channel-1 temperature
FX3U-4DA-ADP
D8260 D8270 D8280 D8290 R
measurement data
Channel-2 temperature
D8261 D8271 D8281 D8291 R
measurement data Section
Channel-3 temperature 4.4
D8262 D8272 D8282 D8292
measurement data
R
G
Channel-4 temperature
FX3G-1DA-BD
D8263 D8273 D8283 D8293 R
measurement data
Averaging time for channel 1
Special D8264 D8274 D8284 D8294 R/W
(Setting range: 1 to 4095)
data
register Averaging time for channel 2
D8265 D8275 D8285 D8295
(Setting range: 1 to 4095)
R/W
Section H
Averaging time for channel 3 4.5
FX3U-3A-ADP
J
FX3U-4AD-PTW
-ADP
J-19
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.3 Selection of Temperature Unit
J-20
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.4 Temperature Measurement
A
4.4 Temperature Measurement
Common Items
The temperature data input in the PTW-ADP will be stored in the special data registers.
The special data registers that store the temperature data are shown in the following table:
• FX3S Series PLC
Special data register Description
B
FX3UC-4AD
FX3U-4AD
D8280 Stores the channel-1 temperature measurement data.
D8281 Stores the channel-2 temperature measurement data.
D8282 Stores the channel-3 temperature measurement data.
D8283 Stores the channel-4 temperature measurement data.
C
• FX3G/FX3GC Series PLC
FX3U-4AD-ADP
Special data register
Description
1st 2nd
D8280 D8290 Stores the channel-1 temperature measurement data.
D8281 D8291 Stores the channel-2 temperature measurement data.
D8282 D8292 Stores the channel-3 temperature measurement data.
D
FX3G-2AD-BD
D8283 D8293 Stores the channel-4 temperature measurement data.
FX3U-4DA
D8261 D8271 D8281 D8291 Stores the channel-2 temperature measurement data.
D8262 D8272 D8282 D8292 Stores the channel-3 temperature measurement data.
D8263 D8273 D8283 D8293 Stores the channel-4 temperature measurement data.
The immediate data or the average data (data averaged in accordance with the specified averaging time) will
F
FX3U-4DA-ADP
be stored in the above data registers as the temperature measurement data.
→ For a detailed description of the averaging time, refer to Section 4.5.
FX3G-1DA-BD
2. Program Example (For FX3U/FX3UC Series PLC)
M8000
FNC 12 D8260 D100 Stores the channel-1 temperature measurement
MOV data of the 1st analog special adapter in D100.
Normally
ON H
FX3U-3A-ADP
Even if the temperature measurement data is not stored in the D100 or the D101, the D8260 or the D8261
can be directly used in the arithmetic operation instruction or a PID instruction.
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
J-21
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.5 Averaging Time
J-22
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.6 Error Status
A
4.6 Error Status
Common Items
If an error is detected in the PTW-ADP, the error status data will be stored in the corresponding special data
register.
The following table shows the special data registers that store the error status data:
• FX3S Series PLC B
FX3UC-4AD
FX3U-4AD
Special data register Description
D8288 Stores the error status data.
FX3U-4AD-ADP
D8288 D8298 Stores the error status data.
FX3G-2AD-BD
Check the ON/OFF status of each bit of the error status data register to determine the error. Errors are
assigned to the bits as shown in the following table. Create a program to detect errors.
FX3U-4DA
b0 of channel 1 is outside the specified b5 Averaging time setting error
range, or disconnection is detected.
The temperature measurement data
b1 of channel 2 is outside the specified b6 PTW-ADP hardware error
range, or disconnection is detected.
The temperature measurement data
F
FX3U-4DA-ADP
b2 of channel 3 is outside the specified b7 PTW-ADP communication data error
range, or disconnection is detected.
The temperature measurement data
b3 of channel 4 is outside the specified b8 to b15 Unused
range, or disconnection is detected.
b4 EEPROM error - - G
FX3G-1DA-BD
1. Caution regarding use of error status data
If a PTW-ADP hardware error (b6) or PTW-ADP communication data error (b7) is detected, it is necessary to
clear the error status with a program at the next power-on of the PLC.
For this reason, be sure to create the following program:
• For FX3S/FX3G/FX3GC/FX3U/FX3UC Series PLC H
FX3U-3A-ADP
M8000 FNC 12
D8288 K4M0
MOV
Normally
ON
M8002
Initial pulse
RST M6 Error status of 3rd*1 analog special adapter
b6 = OFF (PTW-ADP hardware error) I
FX3U-4AD-PT
FNC 12
K4M0 D8288 J
MOV
FX3U-4AD-PTW
J-23
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.6 Error Status
M8002
RST D8268.6 Error status of 1st analog special adapter
b6 = OFF (PTW-ADP hardware error)
Initial pulse
M8000
FNC 12
D8288 K4M0
Normally ON MOV
M0
Y000 The temperature measurement data
of channel 1 is outside the specified
range, or disconnection is detected.
M1
Y001 The temperature measurement data
of channel 2 is outside the specified
range, or disconnection is detected.
M2
Y002 The temperature measurement data
of channel 3 is outside the specified
range, or disconnection is detected.
M3
Y003 The temperature measurement data
of channel 4 is outside the specified
range, or disconnection is detected.
M4
Y004 EEPROM error in 3rd*1 adapter.
M5
Y005 Averaging time setting error in 3rd*1
adapter.
M6
Y006 PTW-ADP hardware error in 3rd*1
adapter.
M7
Y007 PTW-ADP communication data error
in 3rd*1 adapter.
J-24
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.7 Model Code
A
3. Program Example 2 (For FX3U/FX3UC Series PLC)
Common Items
D8268.0
Y000 The temperature measurement data
of channel 1 is outside the specified
D8268.1
range, or disconnection is detected. B
Y001
FX3UC-4AD
FX3U-4AD
The temperature measurement data
of channel 2 is outside the specified
range, or disconnection is detected.
D8268.2
Y002 The temperature measurement data
of channel 3 is outside the specified
D8268.3
range, or disconnection is detected. C
Y003 The temperature measurement data
FX3U-4AD-ADP
of channel 4 is outside the specified
range, or disconnection is detected.
D8268.4
Y004 EEPROM error in 1st adapter.
D8268.5
D
FX3G-2AD-BD
Y005 Averaging time setting error in 1st
adapter.
D8268.6
Y006 PTW-ADP hardware error in 1st
adapter.
D8268.7
E
PTW-ADP communication data error
FX3U-4DA
Y007
in 1st adapter.
FX3U-4DA-ADP
Initial value: K21
Numeric data type: Decimal (K)
When the PTW-ADP is connected, model code "21" will be stored in the corresponding special data register.
The following table shows the special data registers that store the model code:
• FX3S Series PLC
G
FX3G-1DA-BD
Special data register Description
D8289 Model code
Use the special data registers above to check whether PTW-ADP is connected or not.
-ADP
J-25
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.8 Basic Program Example
Even if the temperature measurement data is not stored in D100 or D101, data register D8280 or D8281
can be directly used in the arithmetic operation instruction or a PID instruction.
*1. "1st " for the FX3S/FX3G/FX3GC PLC.
• For FX3U/FX3UC Series PLC
The following program will store the temperature measurement data (°C) from channels 1 and 2 of the 1st
adapter to D100 and D101, respectively. The averaging time is set to "1" (immediate data) for channel 1,
and "5" for channel 2.
M8002 Error status of 1st analog special
RST D8268.6 adapter
Initial b6 = OFF (PTW-ADP hardware error)
pulse
RST D8268.7 Error status of 1st analog special
adapter
b7 = OFF (PTW-ADP communication data error)
M8001 Sets the temperature unit to centigrade
M8260 (C).
Normally OFF
M8002 Sets the averaging time to "1" for
FNC 12 K1 D8264
MOV channel-1 data.
Initial
pulse
FNC 12 K5 D8265 Sets the averaging time to "5" for
MOV channel-2 data.
M8000
FNC 12 D8260 D100 Stores the current value of the channel-1
Normally MOV temperature measurement data in the D100.
ON
FNC 12 D8261 D101 Stores the average value of the channel-2
MOV temperature measurement data in the D101.
Even if the temperature measurement data is not stored in D100 or D101, data register D8260 or D8261
can be directly used in the arithmetic operation instruction or a PID instruction.
J-26
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Troubleshooting
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 5.1 PLC Version Number Check
Common Items
5. Troubleshooting
This chapter describes the troubleshooting methods and error status. B
If the temperature measurement data is not input, or if the proper digital value is not input, check the following
FX3UC-4AD
FX3U-4AD
items:
• Version number of the PLC
• Wiring
• Special devices
C
• Programs
FX3U-4AD-ADP
• Error status
FX3G-2AD-BD
• Any versions (from Ver. 1.00 (initial version) to the latest version) of the FX3G Series are compatible.
• Any versions (from Ver. 1.40 (initial version) to the latest version) of the FX3GC Series are compatible.
• Any versions (from Ver. 2.20 (initial version) to the latest version) of the FX3U Series are compatible.
• Check the version number of the FX3UC Series. The version number should be 1.30 or later.
→ For a detailed description of the version check method,
E
FX3U-4DA
refer to A. Common Items Subsection 5.1.2.
FX3U-4DA-ADP
1. Power
The PTW-ADP needs driving power. Verify that the power supply line is properly connected. Also check that
the POWER indicator lamp of the PTW-ADP is on.
FX3G-1DA-BD
→ For a detailed description of wiring, refer to Chapter 3.
1. Temperature measurement
Verify that the special device for the selected channel is correctly selected. This special device should be
selected depending on the connecting position and the channel.
2. Averaging time
Check that the set averaging time is within the specified range. The averaging time should be set in the range I
from 1 to 4095. If the set averaging time is outside the specified range, an error occurs.
FX3U-4AD-PT
3. Error status
Check that no error is detected in the PTW-ADP.
-ADP
If an error is detected, check the details of the error, and then check the wiring and programs.
→ For a detailed description of special devices, refer to Chapter 4.
J
FX3U-4AD-PTW
-ADP
J-27
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Troubleshooting
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 5.4 Program Check
J-28
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Troubleshooting
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 5.5 Error Status Check
A
4. PTW-ADP hardware error (b6)
Common Items
1) Description of error
The PTW-ADP does not operate properly.
2) Remedy
Check that the 24 V DC power is properly supplied to the PTW-ADP. Also check that the PTW-ADP is
correctly connected to the PLC. B
If the problem cannot be solved even after the above check, please contact your local Mitsubishi Electric
FX3UC-4AD
FX3U-4AD
representative.
FX3U-4AD-ADP
Check that the PTW-ADP is correctly connected to the PLC.
If the problem cannot be solved even after the above check, please contact your local Mitsubishi Electric
representative.
FX3G-2AD-BD
E
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
J-29
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Troubleshooting
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 5.5 Error Status Check
MEMO
J-30
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)
FX3U-4AD-PNK
-ADP
L
FX3U-4AD-TC
FX3S/FX3G/FX3GC/FX3U/FX3UC Series
-ADP
Programmable Controllers M
PID Instruction
User's Manual [Analog Control Edition]
(FNC 88)
K. FX3U-4AD-PNK-ADP (4-channel Resistance
Thermometer Data Input)
Foreword
This manual describes the specifications, wiring, and operation methods for the FX3U-4AD-PNK-ADP special
adapter (4-channel resistance thermometer data input) and should be read and understood before attempting
to install or use the unit.
Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
it to the end user.
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
rights which may occur as a result of using the contents noted in this manual.
K-1
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)
K-2
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 1.1 Outline of Functions
FX3U-4AD-PNK
1. Outline
-ADP
This chapter describes the outline of FX3U-4AD-PNK-ADP (referred to as PNK-ADP). L
FX3U-4AD-TC
1.1 Outline of Functions
-ADP
The FX3U-4AD-PNK-ADP is an analog special adapter. Connect the FX3U-4AD-PNK-ADP to the FX3S/FX3G/
FX3GC/FX3U/FX3UC Series PLC to read the data from the 4-channel resistance thermometer.
1) Only 1 PNK-ADP unit can be connected to the FX3S Series PLC.
M
PID Instruction
Up to 2*1 PNK-ADP units can be connected to the FX3G/FX3GC Series PLC.
Up to 4 PNK-ADP units can be connected to the FX3U/FX3UC Series PLC.
(FNC 88)
(including the other analog expansion boards, analog special adapters)
2) Thermometer types Pt1000 and Ni1000 can be connected. (However, it's impossible to use both types
Pt1000 and Ni1000 with 1 adapter.)
3) The temperature data will be automatically written to the special data register of the FX3S/FX3G/FX3GC/
FX3U/FX3UC Series PLC.
+ + to Section 1.3.
Expansion
4th 3rd 2nd 1st
adapter adapter adapter adapter board*2
For a detailed
description of wiring,
Analog data refer to Chapter 3.
For FX3S/FX3G/FX3GC/
FX3U/FX3UC Series PLC For a detailed description
Description of special devices, refer to
Transfer direction Special devices*3 Chapter 4.
Temperature measurement 1st adapter M/D8260 to M/D8269
For a detailed description
Setting of temperature unit 2nd adapter M/D8270 to M/D8279 of a basic program, refer to
Switching of types between Section 4.9.
3rd adapter M/D8280 to M/D8289
type Pt1000 and Ni1000
Setting of averaging time 4th adapter M/D8290 to M/D8299
Refer to the system configuration shown in the User's Manual - Hardware Edition to check the number of
connectable units and to configure the entire system.
*1. Only 1 analog special adapter can be connected to the FX3G Series PLC (14-point and 24-point type).
*2. The expansion board is not required when connecting with the FX3GC/FX3UC (D, DS, DSS) Series PLC.
For the FX3S/FX3G Series PLC a connector conversion adapter is used.
*3. FX3S/FX3G/FX3GC PLCs use the following special devices.
For FX3S Series PLC For FX3G/FX3GC Series PLC
• 1st adapter: M/D8280 to M/D8289 • 1st adapter: M/D8280 to M/D8289
• 2nd, 3rd and 4th adapters: Cannot be connected • 2nd adapter: M/D8290 to M/D8299
• 3rd and 4th adapters: Cannot be connected
K-3
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 1.2 Setup Procedure Before Starting Operation
FX3U-4AD-PNK-ADP
Refer to Chapter 1.
Wiring Wiring:
•Selection of sensor cable
•Power supply line
Refer to Chapter 4. •Analog input line
Programming Programming:
•Details of special devices
•Examples of basic programs
K-4
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 1.3 Connectable PLC and Its Version Number
K
1.3 Connectable PLC and Its Version Number
FX3U-4AD-PNK
PNK-ADP is compatible with the following PLC.
-ADP
Compatible PLC Version number Date of production
FX3S Series PLC Ver. 1.00 or later After March 2013 (From first product) L
FX3U-4AD-TC
FX3G Series PLC Ver. 1.00 or later After June 2008 (From first product)
FX3GC Series PLC Ver. 1.40 or later After January 2012 (From first product)
FX3U Series PLC Ver. 2.20 or later After May 2005 (From first product)
-ADP
FX3UC Series PLC Ver. 1.30 or later After August 2004
M
1. Version check
PID Instruction
The PLC version can be checked by reading the last three digits of device D8001 or D8101.
→ For a detailed description of the version check,
(FNC 88)
refer to A. Common Items Subsection 5.1.2.
K-5
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 1.4 Compatible Programming Tool Version Number
1. English versions
Model name Media model name Applicable version Remarks
FX3S PLC
GX Works2 SWDNC-GXW2-E Ver. 1.492N or later
-
FX-30P Ver. 1.50 or later
FX3G PLC
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer SWD5C-GPPW-E Ver. 8.72A or later -
FX-30P Ver. 1.00 or later
FX3GC PLC
GX Works2 SWDNC-GXW2-E Ver. 1.77F or later
-
FX-30P Ver. 1.30 or later
FX3U and FX3UC PLCs
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer SWD5C-GPPW-E Ver. 8.18U or later -
FX-30P Ver. 1.00 or later
2. Japanese versions
Model name Media model name Applicable version Remarks
FX3S PLC
GX Works2 SWDNC-GXW2-J Ver. 1.492N or later
-
FX-30P Ver. 1.50 or later
FX3G PLC
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
GX Developer SWD5C-GPPW-J Ver. 8.72A or later -
FX-30P Ver. 1.00 or later
FX3GC PLC
GX Works2 SWDNC-GXW2-J Ver. 1.77F or later
-
FX-30P Ver. 1.30 or later
FX3U and FX3UC PLCs
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
GX Developer SWD5C-GPPW-J Ver. 8.13P or later -
FX-30P Ver. 1.00 or later
Point
• It is possible to create programs in FX3GC PLC using programming tools of inapplicable versions by
selecting "FX3G" as the alternative model.
• It is possible to create programs in FX3S PLC using programming tools of inapplicable versions by
selecting "FX3G" as the alternative model. However, memory capacity setting of the PLC parameter must
be set to 4000 steps or less.
K-6
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 2.1 Generic Specifications
FX3U-4AD-PNK
2. Specifications
-ADP
This chapter describes the general, power supply, and performance specifications for the PNK-ADP. L
FX3U-4AD-TC
2.1 Generic Specifications
-ADP
Item Specifications
Ambient temperature
0 to 55 °C (32 to 131 °F) when operating M
-25 to 75 °C (-13 to 167 °F) when stored
PID Instruction
Relative humidity 5 to 95 %RH (no condensation) when operating
(FNC 88)
Frequency Acceleration Half amplitude
(Hz) (m/s2) (mm)
Tested 10 times in
Vibration 10 to 57 - 0.035 each direction (X-, Y-,
DIN Rail Mounting
resistance*1 57 to 150 4.9 - and Z-axis directions)
(Total: 80 min, each)
10 to 57 − 0.075
Direct Mounting*2
57 to 150 9.8 −
147 m/s2 Acceleration, Action time: 11 ms, 3 times by half-sine pulse in each direction X, Y,
Shock resistance*1
and Z
Using noise simulator of:
Noise resistance
Noise voltage: 1,000 Vp-p / Noise width: 1 μs / Rise: 1 ns / Cycle: 30 to 100 Hz
Dielectric withstand
500 V AC, for 1 min
voltage
Between batch of all terminals and ground terminal
5 MΩ or more using 500 V DC
Insulation resistance
insulation resistance meter
Class D grounding (grounding resistance: 100 Ω or less)
Grounding
<Common grounding with a heavy electrical system is not allowed.>*3
Working
Free from corrosive or flammable gas and excessive conductive dusts
environment
Working altitude < 2000 m*4
Item Specifications
A/D conversion circuit 24 V DC +20 % -15 %, 45 mA
driving power (It is necessary to connect a 24 V DC power supply to the terminal block.)
5 V DC, 15 mA
Interface driving power (Since the internal power is supplied from the FX Series main unit, it is not
necessary to supply the power.)
K-7
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 2.3 Performance Specifications
Specifications
Item
Centigrade (°C) Fahrenheit (°F)
Platinum resistance thermometer sensor (2-wire or 3-wire) Pt1000
JIS C 1604-1997
Input signal
Nickel resistance thermometer sensor (2-wire or 3-wire) Ni1000
DIN 43760-1987
-Pt1000 -Pt1000
+2560 +4920
+2500 +4820
+492.8°F
Approx.
+256°C
Approx.
-50°C 0 -58°F 0
Approx.
Approx.
+250°C +482°F
-55°C
-67°F
-500 -580
Input -550 -670
characteristics
-Ni1000 -Ni1000
+1150 +2390
+1100 +2300
Approx.
Approx.
+115°C
+239°F
-40°C 0 -40°F 0
Approx.
Approx.
+110°C +230°F
-45°C
-49°F
-400 -400
-450 -490
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply line from the analog input area.
• Channels are not insulated from each other.
Number of I/O 0 points
points occupied (This number is not related to the maximum number of input/output points of the PLC.)
K-8
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 2.4 A/D Conversion Time
K
2.4 A/D Conversion Time
FX3U-4AD-PNK
This section describes the A/D conversion time.
-ADP
2.4.1 When connected to a FX3S PLC
L
FX3U-4AD-TC
1. A/D conversion and special data register update timing
A/D conversion is performed at every scan time of the PLC.
During execution of END instruction, the PLC performs A/D conversion, reads out the A/D converted data,
-ADP
and then writes the data in the special data registers.
PID Instruction
(FNC 88)
Sequence
program
A/D conversion start
A/D command
conversion
Digital value reading END instruction
250 s/4ch
K-9
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 2.4 A/D Conversion Time
FX3U-4AD-PNK-ADP FX3U-4AD-PNK-ADP
2nd 1st FX3G/FX3GC Series PLC
Sequence
program
A/D conversion start
A/D command
conversion
Digital value reading
250 μs/4ch
A/D conversion start END instruction
A/D command
conversion
Digital value reading
250 μs/4ch
K-10
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 2.5 Temperature Measurement
K
2.4.3 When connected to a FX3U/FX3UC PLC
FX3U-4AD-PNK
1. A/D conversion and special data register update timing
-ADP
A/D conversion is performed at every arithmetic operation of the PLC.
During execution of END instruction, the PLC performs A/D conversion, reads out the A/D converted data,
and then writes the data in the special data registers. L
FX3U-4AD-TC
FX3U-4AD-PNK-ADP FX3U-4AD-PNK-ADP
n'th 1st FX3U/FX3UC Series PLC
-ADP
Sequence
program M
A/D conversion start
PID Instruction
A/D command
conversion
(FNC 88)
Digital value reading
200 μs/4ch
A/D conversion start END instruction
A/D command
conversion
Digital value reading
200 μs/4ch
K-11
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)
3. Wiring
This chapter describes the PNK-ADP wiring.
Observe the following caution to wire the PNK-ADP.
WIRING PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before attempting wiring work.
Failure to do so may cause electric shock or damage to the product.
WIRING PRECAUTIONS
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn
out.
• Do not wire vacant terminals externally.
Doing so may damage the product.
• Perform class D grounding (grounding resistance: 100Ω or less) to the grounding terminal on the main unit.
Do not use common grounding with heavy electrical systems.
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
• Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise:
- Do not bundle the power line or shield of the analog input/output cable together with or lay it close to the main
circuit, high-voltage line, or load line.
Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
100mm (3.94") or more away from the main circuit, high-voltage line, or load line.
- Ground the shield of the analog input/output cable at one point on the signal receiving side.
However, do not use common grounding with heavy electrical systems.
• Make sure to properly wire to the terminal block (European type) in accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
- The disposal size of the cable end should follow the dimensions described in the manual.
- Tightening torque should follow the specifications in the manual.
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
K-12
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 3.1 Terminal Layout
K
3.1 Terminal Layout
FX3U-4AD-PNK
The terminals of the PNK-ADP are arranged as follows:
-ADP
L
FX3U-4AD-TC
-ADP
Signal Application M
PID Instruction
24+ External power
24-
(FNC 88)
Ground terminal
L1+
Channel-1 Pt1000/Ni1000
L1-
sensor input
l1-
L2+
Channel-2 Pt1000/Ni1000
L2- sensor input
l2-
L3+
Channel-3 Pt1000/Ni1000
L3-
sensor input
l3-
L4+
Channel-4 Pt1000/Ni1000
L4-
sensor input
l4-
K-13
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 3.2 Applicable Cables and Terminal Tightening Torque
1. Cables
Applicable cable and tightening torque
Wire size Tightening
Termination
(stranded wire/solid wire) torque
0.3 mm2 to 0.5 mm2 • To connect a stranded cable, peel the cover off the cable
Single-wire and then twist the core before connection.
(AWG22 to 20)
• To connect a single-wire cable, just strip the cover off the
2-wire 0.3 mm2(AWG22)×2 cable before connection.
0.22 to 0.25 • Ferrule with insulation sleeve
0.3 mm2 to 0.5 mm2 N•m (recommended terminal)
Ferrule with (AWG22-20) AI 0.5-8WH : Manufactured by Phoenix Contact
insulation (Refer to the external view • Caulking tool
sleeve of ferrule shown in the
CRIMPFOX 6*1 : Manufactured by Phoenix Contact
following figure.)
(or CRIMPFOX 6T-F*2 : Manufactured by Phoenix Contact)
3. Tool
For tightening the terminal, use a commercially available small screwdriver
The head
having a straight form that is not widened toward the end as shown right. should be
straight.
Note:
If the diameter of screwdriver grip is too small, tightening torque will not be
able to be achieved. To achieve the appropriate tightening torque shown in 0.4mm 2.5mm
the table above, use the following screwdriver or an appropriate (0.01") (0.09")
replacement (grip diameter: approximately 25 mm (0.98")).
<Reference>
Manufacturer Model
Phoenix Contact SZS 0.4×2.5
K-14
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 3.3 Power Supply Line
K
3.3 Power Supply Line
FX3U-4AD-PNK
Connect the 24 V DC power supply line of the PNK-ADP to the 24+ and 24- terminals of the terminal block.
-ADP
3.3.1 To connect to the FX3S/FX3G/FX3U Series PLC
L
1. To use an external power 2. To use the 24 V DC power of the PLC
FX3U-4AD-TC
PNK-ADP FX3S/FX3G/FX3U PNK-ADP FX3S/FX3G/FX3U
Series PLC Series PLC
+5V +5V
-ADP
(Main unit) (Main unit)
PID Instruction
(FNC 88)
24+ 24- 24+ 24- 24V 0V
Terminal Terminal
block block
Fuse
Class-D Class-D
24V DC grounding grounding
Power
connector
24+ 24- 24+ 24-
Terminal Red Black Green
block
Fuse
Class-D
24V DC grounding
For example of wiring of FX3GC Series PLC, refer to the following manual.
→ Refer to the FX3GC Series User’s Manual - Hardware Edition
"Section 4.2 Example External Wiring".
Cautions regarding connection of the power supply line:
• For the 24 V DC power supply line, be sure to use the same power as the FX3GC/FX3UC Series PLC.
• Ground the " " terminal to a class-D grounding power supply line (100 Ω or less) together with the
ground terminal of the PLC main unit.
K-15
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 3.4 Selection of the Resistance Thermometer Sensor
+5V
2-wire
sensors 47k 47k
type
1M ch
L+
L-
*2 1M
I-
24+
24V DC*1
24-
Class-D grounding
L+, L-, I-, ch: represents the channel number.
*1. For FX3S/FX3G/FX3U Series PLC (AC power type), the 24 V DC service power supply is also
available.
*2. When using a 2-wire temperature sensor type, short-circuit the [L -] terminal and the [I -] terminal.
For the lead wire use a 10 Ω resistance or less per line.
*3. Separate the cable of the platinum resistance thermometer sensor from the other power cables or
areas easily affected by inductive noise (of the commercial power, etc.).
3.7 Grounding
Grounding should be performed as stated below.
• The grounding resistance should be 100 Ω or less.
• Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" as shown in the following
figure.
→ For details, refer to the User’s Manual - Hardware Edition of the each PLC Series.
K-16
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 4.1 Loading of A/D Conversion Data
FX3U-4AD-PNK
4. Programming
-ADP
This chapter describes how to create programs that can read out the analog data using the PNK-ADP. L
FX3U-4AD-TC
4.1 Loading of A/D Conversion Data
-ADP
1) The input analog data will be converted into digital data and then stored in the special devices of the
FX3S/FX3G/FX3GC/FX3U/FX3UC Series PLC.
M
2) If data is stored in the special devices, the averaging time can be set, and the input mode can be
PID Instruction
specified.
(FNC 88)
3) Special auxiliary relays (10 points) and special data registers (10 points) are assigned automatically
starting from the adapter nearest to the main unit.
→ For a detailed description of special device assignment, refer to Section 4.2.
• FX3S Series PLC
Communi-
cation
FX3U-4AD special FX3S-CNV
-PNK-ADP adapter -ADP FX3S Series PLC
Special devices
Special auxiliary relays:
A/D M8280 to M8289 Sequence
Special data registers: program
D8280 to D8289
2nd*1 1st
Special devices
Special auxiliary relays:
M8280 to M8289
A/D Special data registers:
D8280 to D8289 Sequence
Program
Special auxiliary relays:
M8290 to M8299
A/D Special data registers:
D8290 to D8299
The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
next adapter as the 2nd analog special adapter. However, in this case, do not include the connector
conversion adapter and the communication special adapter.
*1. The second special adapter is not available in the FX3G Series PLC (14-point and 24-point type).
*2. A connector conversion adapter is required to connect the FX3U-4AD-PNK-ADP to the FX3G Series
PLC.
K-17
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 4.2 List of Special Devices
The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
next adapter as the 2nd analog special adapter, and so on. However, in this case, do not include the high-
speed input/output special adapter, communication special adapter, and the CF card special adapter.
*1. An expansion board is required to connect the FX3U-4AD-PNK-ADP to the FX3U/FX3UC-32MT-LT(-2)
PLC.
K-18
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 4.2 List of Special Devices
K
• FX3G/FX3GC Series PLC
FX3U-4AD-PNK
R: Read / W: Write
Special Device number
Description Attribute Reference
-ADP
device 1st 2nd
Section
M8280 M8290 Selects the temperature unit R/W
4.3 L
Special
FX3U-4AD-TC
Section
auxiliary M8281 M8291 Input sensor selection R/W
4.4
relay
M8282 to M8292 to
Unused (Do not use.) - -
-ADP
M8289 M8299
D8280 D8290 Channel-1 temperature measurement data R
D8281 D8291 Channel-2 temperature measurement data R Section
M
PID Instruction
D8282 D8292 Channel-3 temperature measurement data R 4.5
D8283 D8293 Channel-4 temperature measurement data R
(FNC 88)
D8284 D8294 Averaging time for channel 1 (Setting range: 1 to 4095) R/W
Special
data D8285 D8295 Averaging time for channel 2 (Setting range: 1 to 4095) R/W Section
register D8286 D8296 Averaging time for channel 3 (Setting range: 1 to 4095) R/W 4.6
D8287 D8297 Averaging time for channel 4 (Setting range: 1 to 4095) R/W
Section
D8288 D8298 Error status R/W
4.7
Section
D8289 D8299 Model code = 11 R
4.8
K-19
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 4.3 Selection of Temperature Unit
K-20
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 4.4 Input sensor selection
K
4.4 Input sensor selection
FX3U-4AD-PNK
Turn on the Pt1000 type or off the Ni1000 type selection special auxiliary relay to select the Pt1000 or Ni1000
-ADP
for PNK-ADP.
The input sensor type will be selected for all the channels at the same time.
To select the input sensor type, use the following special auxiliary relays: L
• FX3S Series PLC
FX3U-4AD-TC
Special auxiliary relay Description
Input sensor selection:
-ADP
M8281 OFF: Pt1000
ON: Ni1000
PID Instruction
Special auxiliary relay
Description
1st 2nd
(FNC 88)
Input sensor selection:
M8281 M8291 OFF: Pt1000
ON: Ni1000
K-21
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 4.5 Temperature Measurement
The immediate data or the average data (data averaged in accordance with the specified averaging time) will
be stored in the above data registers as the temperature measurement data.
→ For a detailed description of the averaging time, refer to Section 4.6.
Even if the temperature measurement data is not stored in D100 or D101, data registers D8260 or D8261 can
be directly used in the arithmetic operation instruction or a PID instruction.
K-22
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 4.6 Averaging Time
K
4.6 Averaging Time
FX3U-4AD-PNK
Setting range: 1 to 4095
-ADP
Initial value: K64
Numeric data type: Decimal (K)
If the averaging time is set for the PNK-ADP, the averaged temperature measurement data will be stored in L
FX3U-4AD-TC
the D8260 to D8263, D8270 to D8273, D8280 to D8283, and D8290 to D8293. The averaging time can be set
for each channel.
Set the averaging time in the following special data registers:
-ADP
• FX3S Series PLC
Special data register Description M
D8284 Averaging time for channel-1 data
PID Instruction
D8285 Averaging time for channel-2 data
(FNC 88)
D8286 Averaging time for channel-3 data
D8287 Averaging time for channel-4 data
FNC 12 K128 D8265 Sets the averaging time to "128" for the channel-2
MOV data of the 1st analog special adapter.
K-23
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 4.7 Error Status
Check the ON/OFF status of each bit of the error status data register to determine the error. Errors are
assigned to the bits as shown in the following table. Create a program to detect errors.
FNC 12
K4M0 D8288
MOV
K-24
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 4.7 Error Status
K
• For FX3U/FX3UC Series PLC
FX3U-4AD-PNK
M8002 Error status in the 1st analog special adapter
RST D8268.6 b6 = OFF (PNK-ADP hardware error)
-ADP
Initial pulse
FX3U-4AD-TC
2. Program Example 1 (For FX3S/FX3G/FX3GC/FX3U/FX3UC Series PLC)
-ADP
M8000 FNC 12
D8288 K4M0 M
MOV
PID Instruction
Normally ON
M0
(FNC 88)
Y000 The temperature measurement data
of channel 1 is outside the specified
range, or disconnection is detected.
M1
Y001 The temperature measurement data
of channel 2 is outside the specified
range, or disconnection is detected.
M2
Y002 The temperature measurement data
of channel 3 is outside the specified
range, or disconnection is detected.
M3
Y003 The temperature measurement data
of channel 4 is outside the specified
range, or disconnection is detected.
M4
Y004 EEPROM error in 3rd*1 adapter.
M5
Y005 Averaging time setting error in 3rd*1
adapter.
M6
Y006 PNK-ADP hardware error in 3rd*1
adapter.
M7
Y007 PNK-ADP communication data error
in the 3rd*1 adapter.
K-25
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 4.8 Model Code
D8268.0
Y000 The temperature measurement data
of channel 1 is outside the specified
range, or disconnection is detected.
D8268.1
Y001 The temperature measurement data
of channel 2 is outside the specified
range, or disconnection is detected.
D8268.2
Y002 The temperature measurement data
of channel 3 is outside the specified
range, or disconnection is detected.
D8268.3
Y003 The temperature measurement data
of channel 4 is outside the specified
range, or disconnection is detected.
D8268.4
Y004 EEPROM error in 1st adapter.
D8268.5
Y005 Averaging time setting error in 1st
adapter.
D8268.6
Y006 PNK-ADP hardware error in 1st
adapter.
D8268.7
Y007 PNK-ADP communication data error
in the 1st adapter.
Use the above special data registers to check whether PNK-ADP is connected or not.
K-26
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 4.9 Basic Program Example
K
4.9 Basic Program Example
FX3U-4AD-PNK
Create the following basic program to read out the temperature measurement data.
-ADP
• For FX3S/FX3G/FX3GC/FX3U/FX3UC Series PLC
The following program will select Pt1000 and will store the temperature measurement data (°C) of
channels 1 and 2 of the 3rd*1 adapter in the D100 and the D101, respectively. The averaging time will be
L
FX3U-4AD-TC
set to "32" for channel 1, and "128" for channel 2.
M8000 FNC 12
-ADP
D8288 K4M0
Normally MOV
ON
M8002 Error status of 3rd*1 analog special
M
adapter
PID Instruction
RST M6
b6 = OFF (PNK-ADP hardware error)
Initial
(FNC 88)
pulse Error status of 3rd*1 analog special
RST M7 adapter
b7 = OFF (PNK-ADP communication data error)
FNC 12
K4M0 D8288
MOV
M8001
M8280 Sets the temperature unit to
centigrade (C)
Normally
OFF
M8281 Selects Pt1000
M8002
FNC 12 K32 D8284 Sets the averaging time to "32" for
MOV channel-1 data.
Initial
pulse
FNC 12 K128 D8285 Sets the averaging time to "128" for
MOV channel-2 data.
M8000 Stores the current value of the
FNC 12 D8280 D100 channel-1 measurement
Normally MOV temperature data to D100.
ON Stores the current value of the
FNC 12 D8281 D101 channel-2 measurement
MOV temperature data to D101.
Even if the temperature measurement data is not stored to D100 or D101, data registers D8280 or D8281
can be directly used in the arithmetic operation instruction or a PID instruction.
*1. "1st" for the FX3S/FX3G/FX3GC PLC.
K-27
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 4.9 Basic Program Example
M8002
FNC 12 K32 D8264 Sets the averaging time to "32" for
MOV channel-1 data.
Initial
pulse
FNC 12 K128 D8265 Sets the averaging time to "128" for
MOV channel-2 data.
M8000 Stores the current value of the
FNC 12 D8260 D100 channel-1 measurement
Normally MOV temperature data to D100.
ON Stores the current value of the
FNC 12 D8261 D101 channel-2 measurement
MOV temperature data to D101.
Even if the temperature measurement data is not stored to D100 or D101, data registers D8260 or D8261
can be directly used in the arithmetic operation instruction or a PID instruction.
K-28
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Troubleshooting
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 5.1 PLC Version Number Check
FX3U-4AD-PNK
5. Troubleshooting
-ADP
This chapter describes the troubleshooting methods and error status. L
If the temperature measurement data is not input, or if the proper digital value is not input, check the following
FX3U-4AD-TC
items:
• Version number of the PLC
-ADP
• Wiring
• Special devices
• Programs M
PID Instruction
• Error status
(FNC 88)
5.1 PLC Version Number Check
• Any versions (from Ver. 1.00 (initial version) to the latest version) of the FX3S Series are compatible.
• Any versions (from Ver. 1.00 (initial version) to the latest version) of the FX3G Series are compatible.
• Any versions (from Ver. 1.40 (initial version) to the latest version) of the FX3GC Series are compatible.
• Any versions (from Ver. 2.20 (initial version) to the latest version) of the FX3U Series are compatible.
• Check the version number of FX3UC Series. The version number should be 1.30 or later.
→ For a detailed description of the version check method,
refer to A. Common Items Subsection 5.1.2.
1. Power
The PNK-ADP needs driving power. Verify that the power supply line is properly connected. Also check that
the POWER indicator lamp of the PNK-ADP is on.
2. Temperature measurement
Check if the special device of the selected channel is correctly set.
This special device should be selected depending on the connecting position and the channel.
3. Averaging time
Verify if the set averaging time is within the specified range. The averaging time should be set in the range
from 1 to 4095. If the set averaging time is outside the specified range, an error occurs.
4. Error status
Check that no error is detected in the PNK-ADP.
If an error is detected, check the details of the error, and then check the wiring and programs.
→ For a detailed description of special devices, refer to Chapter 4.
K-29
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Troubleshooting
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 5.4 Program Check
K-30
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Troubleshooting
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 5.5 Error Status Check
K
4. PNK-ADP hardware error (b6)
FX3U-4AD-PNK
1) Description of error
The PNK-ADP does not operate properly.
-ADP
2) Remedy
Check that the 24 V DC power is properly supplied to the PNK-ADP.
Also check that the PNK-ADP is correctly connected to the PLC. L
If the problem cannot be solved even after the above check, please contact your local Mitsubishi Electric
FX3U-4AD-TC
representative.
-ADP
1) Description of error
A communication error is detected between the PNK-ADP and the PLC. M
2) Remedy
PID Instruction
Check that the PNK-ADP is correctly connected to the PLC.
(FNC 88)
If the problem cannot be solved even after the above check, please contact your local Mitsubishi Electric
representative.
K-31
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Troubleshooting
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 5.5 Error Status Check
MEMO
K-32
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)
FX3U-4AD-PNK
-ADP
L
FX3U-4AD-TC
FX3S/FX3G/FX3GC/FX3U/FX3UC Series
-ADP
Programmable Controllers M
PID Instruction
User's Manual [Analog Control Edition]
(FNC 88)
L. FX3U-4AD-TC-ADP (4-channel Thermocouple
Data Input)
Foreword
This manual describes the specifications, wiring, and operation methods for the FX3U-4AD-TC-ADP special
adapter (4-channel thermocouple input) and should be read and understood before attempting to install or
use the unit.
Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
it to the end user.
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
rights which may occur as a result of using the contents noted in this manual.
L-1
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)
L-2
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 1.1 Outline of Functions
FX3U-4AD-PNK
1. Outline
-ADP
This chapter describes the outline of FX3U-4AD-TC-ADP (referred to as TC-ADP). L
FX3U-4AD-TC
1.1 Outline of Functions
-ADP
The FX3U-4AD-TC-ADP is an analog special adapter. Connect the FX3U-4AD-TC-ADP to the FX3S/FX3G/
FX3GC/FX3U/FX3UC Series PLC to read the data from the 4-channel thermocouple.
1) Only 1 TC-ADP unit can be connected to the FX3S Series PLC.
M
PID Instruction
Up to 2*1 TC-ADP units can be connected to the FX3G/FX3GC Series PLC.
Up to 4 TC-ADP units can be connected to the FX3U/FX3UC Series PLC.
(FNC 88)
(including the other analog expansion boards, analog special adapters)
2) Thermocouple types K and J can be connected. (However, it's impossible to use both types K and J with
1 adapter.)
3) A/D conversion data will be automatically written to the special data register of the FX3S/FX3G/FX3GC/
FX3U/FX3UC Series PLC.
+ + to Section 1.3.
Expansion
4th 3rd 2nd 1st
adapter adapter adapter adapter board*2
For a detailed
For FX3S/FX3G/FX3GC/
FX3U/FX3UC Series PLC For a detailed description
Description Transfer direction Special devices*3 of special devices, refer to
Chapter 4.
Temperature measurement 1st adapter M/D8260 to M/D8269
For a detailed description
Setting of temperature unit 2nd adapter M/D8270 to M/D8279 of a basic program, refer to
Switching of types between Section 4.9.
3rd adapter M/D8280 to M/D8289
type K and type J
Setting of averaging time 4th adapter M/D8290 to M/D8299
Refer to the system configuration shown in the User's Manual - Hardware Edition to check the number of
connectable units and to configure the entire system.
*1. Only 1 analog special adapter can be connected to the FX3G Series PLC (14-point and 24-point type).
*2. The expansion board is not required when connecting with the FX3GC/FX3UC (D, DS, DSS) Series PLC.
For the FX3S/FX3G Series PLC a connector conversion adapter is used.
*3. FX3S/FX3G/FX3GC PLCs use the following special devices.
For FX3S Series PLC For FX3G/FX3GC Series PLC
• 1st adapter: M/D8280 to M/D8289 • 1st adapter: M/D8280 to M/D8289
• 2nd, 3rd and 4th adapters: Cannot be connected • 2nd adapter: M/D8290 to M/D8299
• 3rd and 4th adapters: Cannot be connected
L-3
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 1.2 Setup Procedure Before Starting Operation
FX3U-4AD-TC-ADP
Refer to Chapter 1.
Wiring Wiring:
•Selection of sensor cable
•Power supply line
Refer to Chapter 4. •Analog input line
Programming Programming:
•Details of special devices
•Examples of basic programs
L-4
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 1.3 Connectable PLC and Its Version Number
K
1.3 Connectable PLC and Its Version Number
FX3U-4AD-PNK
TC-ADP is compatible with the following PLC.
-ADP
Compatible PLC Version number Date of production
FX3S Series PLC Ver. 1.00 or later After March 2013 (From first product) L
FX3U-4AD-TC
FX3G Series PLC Ver. 1.00 or later After June 2008 (From first product)
FX3GC Series PLC Ver. 1.40 or later After January 2012 (From first product)
FX3U Series PLC Ver. 2.20 or later After May 2005 (From first product)
-ADP
FX3UC Series PLC Ver. 1.30 or later After August 2004
M
1. Version check
PID Instruction
The PLC version can be checked by reading the last three digits of device D8001 or D8101.
→ For a detailed description of the version check,
(FNC 88)
refer to A. Common Items Subsection 5.1.2.
L-5
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 1.4 Compatible Programming Tool Version Number
1. English versions
Model name Media model name Applicable version Remarks
FX3S PLC
GX Works2 SWDNC-GXW2-E Ver. 1.492N or later
-
FX-30P Ver. 1.50 or later
FX3G PLC
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer SWD5C-GPPW-E Ver. 8.72A or later -
FX-30P Ver. 1.00 or later
FX3GC PLC
GX Works2 SWDNC-GXW2-E Ver. 1.77F or later
-
FX-30P Ver. 1.30 or later
FX3U and FX3UC PLCs
GX Works2 SWDNC-GXW2-E Ver. 1.08J or later
GX Developer SWD5C-GPPW-E Ver. 8.18U or later -
FX-30P Ver. 1.00 or later
2. Japanese versions
Model name Media model name Applicable version Remarks
FX3S PLC
GX Works2 SWDNC-GXW2-J Ver. 1.492N or later
-
FX-30P Ver. 1.50 or later
FX3G PLC
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
GX Developer SWD5C-GPPW-J Ver. 8.72A or later -
FX-30P Ver. 1.00 or later
FX3GC PLC
GX Works2 SWDNC-GXW2-J Ver. 1.77F or later
-
FX-30P Ver. 1.30 or later
FX3U and FX3UC PLCs
GX Works2 SWDNC-GXW2-J Ver. 1.07H or later
GX Developer SWD5C-GPPW-J Ver. 8.13P or later -
FX-30P Ver. 1.00 or later
Point
• It is possible to create programs in FX3GC PLC using programming tools of inapplicable versions by
selecting "FX3G" as the alternative model.
• It is possible to create programs in FX3S PLC using programming tools of inapplicable versions by
selecting "FX3G" as the alternative model. However, memory capacity setting of the PLC parameter must
be set to 4000 steps or less.
L-6
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 2.1 Generic Specifications
FX3U-4AD-PNK
2. Specifications
-ADP
This chapter describes the general, power supply, and performance specifications for the TC-ADP. L
FX3U-4AD-TC
2.1 Generic Specifications
-ADP
Item Specifications
Ambient temperature
0 to 55 °C (32 to 131 °F) when operating M
-25 to 75 °C (-13 to 167 °F) when stored
PID Instruction
Relative humidity 5 to 95 %RH (no condensation) when operating
(FNC 88)
Frequency Acceleration Half amplitude
(Hz) (m/s2) (mm)
Tested 10 times in
Vibration 10 to 57 - 0.035 each direction (X-, Y-,
DIN Rail Mounting
resistance*1 57 to 150 4.9 - and Z-axis directions)
(Total: 80 min, each)
10 to 57 − 0.075
Direct Mounting*2
57 to 150 9.8 −
147 m/s2 Acceleration, Action time: 11 ms, 3 times by half-sine pulse in each direction X, Y,
Shock resistance*1
and Z
Using noise simulator of:
Noise resistance
Noise voltage: 1,000 Vp-p / Noise width: 1 μs / Rise: 1 ns / Cycle: 30 to 100 Hz
Dielectric withstand
500 V AC, for 1 min
voltage
Between batch of all terminals and ground terminal
5 MΩ or more using 500 V DC
Insulation resistance
insulation resistance meter
Class D grounding (grounding resistance: 100 Ω or less)
Grounding
<Common grounding with a heavy electrical system is not allowed.>*3
Working
Free from corrosive or flammable gas and excessive conductive dusts
environment
Working altitude < 2000 m*4
Item Specifications
A/D conversion circuit 24 V DC +20 % -15 %, 45 mA
driving power (It is necessary to connect a 24 V DC power supply to the terminal block.)
5 V DC, 15 mA
Interface driving power (Since the internal power is supplied from the FX Series main unit, it is not
necessary to supply the power.)
L-7
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 2.3 Performance Specifications
Specifications
Item
Centigrade (°C) Fahrenheit (°F)
Thermocouple type K or J
Input signal
JIS C 1602-1995
• Type K •Type K
+10100 +18500
+10000 +18320
+1010°C
+1850° F
-100°C 0 -148° F 0
+1000°C +1832° F
-110°C
-166° F
-1000 -1480
-1100 -1660
Input
characteristics
•Type J •Type J
+6100 +11300
+6000 +11120
+1130°F
+610°C
-100°C 0 -148°F 0
+600°C +1112°F
-110°C
-166°F
-1000 -1480
-1100 -1660
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply line from the analog input area.
• Channels are not insulated from each other.
Number of I/O 0 points
points occupied (This number is not related to the maximum number of input/output points of the PLC.)
L-8
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 2.4 A/D Conversion Time
K
2.4 A/D Conversion Time
FX3U-4AD-PNK
This section describes the A/D conversion time.
-ADP
2.4.1 When connected to a FX3S PLC
L
FX3U-4AD-TC
1. A/D conversion and special data register update timing
A/D conversion is performed at every scan time of the PLC.
During execution of END instruction, the PLC performs A/D conversion, reads out the A/D converted data,
-ADP
and then writes the data in the special data registers.
PID Instruction
(FNC 88)
Sequence
program
A/D conversion start
A/D command
conversion
Digital value reading END instruction
250 s/4ch
L-9
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 2.4 A/D Conversion Time
FX3U-4AD-TC-ADP FX3U-4AD-TC-ADP
2nd 1st FX3G/FX3GC Series PLC
Sequence
program
A/D conversion start
A/D command
conversion
Digital value reading
250 μs/4ch
A/D conversion start END instruction
A/D command
conversion
Digital value reading
250 μs/4ch
L-10
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 2.5 Temperature Measurement
K
2.4.3 When connected to a FX3U/FX3UC PLC
FX3U-4AD-PNK
1. A/D conversion and special data register update timing
-ADP
A/D conversion is performed at every scan time of the PLC.
During execution of END instruction, the PLC performs A/D conversion, reads out the A/D converted data,
and then writes the data in the special data registers. L
FX3U-4AD-TC
FX3U-4AD-TC-ADP FX3U-4AD-TC-ADP
n'th 1st FX3U/FX3UC Series PLC
-ADP
Sequence
program M
A/D conversion start
PID Instruction
A/D command
conversion
(FNC 88)
Digital value reading
200 μs/4ch
A/D conversion start END instruction
A/D command
conversion
Digital value reading
200 μs/4ch
L-11
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)
3. Wiring
This chapter describes the TC-ADP wiring.
Observe the following caution to wire the TC-ADP.
WIRING PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before attempting wiring work.
Failure to do so may cause electric shock or damage to the product.
WIRING PRECAUTIONS
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn
out.
• Do not wire vacant terminals externally.
Doing so may damage the product.
• Perform class D grounding (grounding resistance: 100Ω or less) to the grounding terminal on the main unit.
Do not use common grounding with heavy electrical systems.
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
• Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise:
- Do not bundle the power line or shield of the analog input/output cable together with or lay it close to the main
circuit, high-voltage line, or load line.
Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
100mm (3.94") or more away from the main circuit, high-voltage line, or load line.
- Ground the shield of the analog input/output cable at one point on the signal receiving side.
However, do not use common grounding with heavy electrical systems.
• Make sure to properly wire to the terminal block (European type) in accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
- The disposal size of the cable end should follow the dimensions described in the manual.
- Tightening torque should follow the specifications in the manual.
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
L-12
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 3.1 Terminal Layout
K
3.1 Terminal Layout
FX3U-4AD-PNK
The terminals of the TC-ADP are arranged as follows:
-ADP
L
FX3U-4AD-TC
-ADP
Signal Application M
PID Instruction
24+ External power
24-
(FNC 88)
Ground terminal
• Unused
• (Do not connect any lines.)
J-type Switches the type between
J-type type K and type J.
L1+ Channel-1 thermocouple
L1- sensor input
L2+ Channel-2 thermocouple
L2- sensor input
L3+ Channel-3 thermocouple
L3- sensor input
L4+ Channel-4 thermocouple
L4- sensor input
L-13
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 3.2 Applicable Cables and Terminal Tightening Torque
1. Cables
Applicable cable and tightening torque
Wire size Tightening
Termination
(stranded wire/solid wire) torque
0.3 mm2 to 0.5 mm2 • To connect a stranded cable, peel the cover off the cable
Single-wire and then twist the core before connection.
(AWG22 to 20)
• To connect a single-wire cable, just strip the cover off the
2-wire 0.3 mm2(AWG22)×2 cable before connection.
0.22 to 0.25 • Ferrule with insulation sleeve
0.3 mm2 to 0.5 mm2 N•m (recommended terminal)
Ferrule with (AWG22-20) AI 0.5-8WH : Manufactured by Phoenix Contact
insulation (Refer to the external view • Caulking tool
sleeve of ferrule shown in the
CRIMPFOX 6*1 : Manufactured by Phoenix Contact
following figure.)
(or CRIMPFOX 6T-F*2 : Manufactured by Phoenix Contact)
3. Tool
For tightening the terminal, use a commercially available small screwdriver
The head
having a straight form that is not widened toward the end as shown right. should be
straight.
Note:
If the diameter of screwdriver grip is too small, tightening torque will not be
able to be achieved. To achieve the appropriate tightening torque shown in 0.4mm 2.5mm
the table above, use the following screwdriver or an appropriate (0.01") (0.09")
replacement (grip diameter: approximately 25 mm (0.98")).
<Reference>
Manufacturer Model
Phoenix Contact SZS 0.4×2.5
L-14
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 3.3 Power Supply Line
K
3.3 Power Supply Line
FX3U-4AD-PNK
Connect the 24 V DC power supply line of the TC-ADP to the 24+ and 24- terminals of the terminal block.
-ADP
3.3.1 To connect to the FX3S/FX3G/FX3U Series PLC
1. To use an external power 2. To use the 24 V DC power of the PLC
L
FX3U-4AD-TC
TC-ADP FX3S/FX3G/FX3U TC-ADP FX3S/FX3G/FX3U
Series PLC Series PLC
+5V +5V
-ADP
(Main unit) (Main unit)
PID Instruction
(FNC 88)
24+ 24- 24+ 24- 24V 0V
Terminal Terminal
block block
Fuse
Class-D Class-D
24V DC grounding grounding
Power
connector
24+ 24- 24+ 24-
Terminal Red Black Green
block
Fuse
Class-D
24V DC grounding
For example of wiring of FX3GC Series PLC, refer to the following manual.
→ Refer to the FX3GC Series User’s Manual - Hardware Edition
"Section 4.2 Example External Wiring".
Cautions regarding connection of the power supply line:
• For the 24 V DC power supply line, be sure to use the same power as the FX3GC/FX3UC Series PLC.
• Ground the " " terminal to a class-D grounding power supply line (100 Ω or less) together with the
ground terminal of the PLC main unit.
L-15
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 3.4 Selection of the Thermocouple
• There are 2 types of thermocouples: K type and J type. When selecting the thermocouple type, make sure
that the same type of thermocouple is connection to all the channels.
• Be sure to use a non-grounded thermocouple type.
• The compensating lead wire indicates a temperature value of approximately 0.12 °C higher than that of the
wire resistor (10 Ω). Use the appropriate compensating lead wire when considering this difference.
• If the compensating lead wire is very long, the wire may be easily affected by noise, etc. It is, therefore,
recommended for the length of the compensating lead wire to be 100 m or less.
Shield
Temperature
compensating circuit
3k ch
L+
L-
+5V
24+
24V DC*3
24-
Class-D
grounding
*1. It is not necessary to connect lines to the J-type terminals. Leave these terminals disconnected.
*2. Keep the thermocouple away from inductive noise (commercial power, etc.).
*3. For FX3S/FX3G/FX3U Series PLC (AC power type), the 24 V DC service power supply is also
available.
L-16
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 3.6 Caution Regarding Wiring
K
3.5.2 Wiring of the thermocouple type J
FX3U-4AD-PNK
Terminal block
-ADP
TC-ADP
type J
*1
Thermocouple Compensating
type J Temperature
compensating circuit L
type J*2 lead wire
FX3U-4AD-TC
3k ch
L+
L-
-ADP
Shield
Temperature
compensating circuit M
3k
ch
PID Instruction
L+
L-
(FNC 88)
+5V
24+
24V DC*3
24-
Class-D
grounding
*1. To use a J thermocouple type, be sure to connect the thermocouple to these terminals. In addition,
select J type by turning on the type K/J selection special auxiliary relay.
*2. Keep the thermocouple away from inductive noise (commercial power, etc.).
*3. For FX3S/FX3G/FX3U Series PLC (AC power type), the 24 V DC service power supply is also
available.
3.7 Grounding
Grounding should be performed as stated below.
• The grounding resistance should be 100 Ω or less.
• Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" as shown in the following
figure.
→ For details, refer to the User’s Manual - Hardware Edition of the each PLC Series.
L-17
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 4.1 Loading of A/D Conversion Data
4. Programming
This chapter describes how to create programs that can read out the analog data using the TC-ADP.
Special devices
Special auxiliary relays:
A/D M8280 to M8289 Sequence
Special data registers: program
D8280 to D8289
2nd*1 1st
Special devices
Special auxiliary relays:
M8280 to M8289
A/D Special data registers:
D8280 to D8289 Sequence
Program
Special auxiliary relays:
M8290 to M8299
A/D Special data registers:
D8290 to D8299
The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
next adapter as the 2nd analog special adapter. However, in this case, do not include the connector
conversion adapter and the communication special adapter.
*1. The second special adapter is not available in the FX3G Series PLC (14-point and 24-point type).
*2. A connector conversion adapter is required to connect the FX3U-4AD-TC-ADP to the FX3G Series
PLC.
L-18
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 4.2 List of Special Devices
K
• FX3U/FX3UC Series PLC
FX3U-4AD-PNK
Communi-
cation
FX3U-4AD FX3U-4AD FX3U-4AD special FX3U-4AD
-TC-ADP -TC-ADP -TC-ADP -TC-ADP FX3U/FX3UC Series PLC*1
-ADP
adapter
FX3U-4AD-TC
M8260 to M8269
A/D Special data registers:
D8260 to D8269
-ADP
Special auxiliary relays:
M8270 to M8279
A/D Special data registers:
D8270 to D8279 M
Sequence
PID Instruction
program
Special auxiliary relays:
(FNC 88)
M8280 to M8289
A/D Special data registers:
D8280 to D8289
The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
next adapter as the 2nd analog special adapter, and so on. However, in this case, do not include the high-
speed input/output special adapter, communication special adapter, and the CF card special adapter.
*1. An expansion board is required to connect the FX3U-4AD-TC-ADP to the FX3U/FX3UC-32MT-LT(-2)
PLC.
L-19
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 4.2 List of Special Devices
L-20
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 4.3 Selection of Temperature Unit
K
4.3 Selection of Temperature Unit
FX3U-4AD-PNK
The state of special auxiliary relays decides the TC-ADP's temperature unit as shown in the table below.
-ADP
To switch the temperature unit, use the following special auxiliary relays:
• FX3S Series PLC
L
Special auxiliary relay Description
FX3U-4AD-TC
Selection of temperature unit:
M8280 OFF: Centigrade (°C)
ON: Fahrenheit (°F)
-ADP
• FX3G/FX3GC Series PLC
M
Special auxiliary relay
PID Instruction
Description
1st 2nd
(FNC 88)
Selection of temperature unit:
M8280 M8290 OFF: Centigrade (°C)
ON: Fahrenheit (°F)
L-21
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 4.4 Selection of Type K or J
L-22
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 4.5 Temperature Measurement
K
4.5 Temperature Measurement
FX3U-4AD-PNK
The temperature data input in the TC-ADP will be stored in the special data registers.
-ADP
The special data registers that store the temperature data are shown in the following table:
• FX3S Series PLC
L
Special data register Description
FX3U-4AD-TC
D8280 Stores the channel-1 temperature measurement data.
D8281 Stores the channel-2 temperature measurement data.
-ADP
D8282 Stores the channel-3 temperature measurement data.
D8283 Stores the channel-4 temperature measurement data.
M
• FX3G/FX3GC Series PLC
PID Instruction
Special data register
(FNC 88)
Description
1st 2nd
D8280 D8290 Stores the channel-1 temperature measurement data.
D8281 D8291 Stores the channel-2 temperature measurement data.
D8282 D8292 Stores the channel-3 temperature measurement data.
D8283 D8293 Stores the channel-4 temperature measurement data.
The immediate data or the average data (data averaged in accordance with the specified averaging time) will
be stored in the above data registers as the temperature measurement data.
→ For a detailed description of the averaging time, refer to Section 4.6.
Even if the temperature measurement data is not stored in D100 or D101, data registers D8260 or D8261 can
be directly used in the arithmetic operation instruction or a PID instruction.
L-23
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 4.6 Averaging Time
FNC 12 K128 D8265 Sets the averaging time to "128" for the channel-2
MOV data of the 1st analog special adapter.
L-24
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 4.7 Error Status
K
4.7 Error Status
FX3U-4AD-PNK
If an error is detected on TC-ADP, the error status data will be stored in the corresponding special data
-ADP
register.
The following table shows the special data registers that store the error status data:
• FX3S Series PLC L
FX3U-4AD-TC
Special data register Description
D8288 Stores the error status data.
-ADP
• FX3G/FX3GC Series PLC
Special data register
Description M
1st 2nd
PID Instruction
D8288 D8298 Stores the error status data.
(FNC 88)
• FX3U/FX3UC Series PLC
Special data register
Description
1st 2nd 3rd 4th
D8268 D8278 D8288 D8298 Stores the error status data.
Check the ON/OFF status of each bit of the error status data register to determine the error. Errors are
assigned to the bits as shown in the following table. Create a program to detect errors.
M8000
FNC 12 D8288 K4M0
MOV
Normally
ON
M8002 Error status in the 3rd*1 analog special adapter
RST M6 b6 = OFF (TC-ADP hardware error)
Initial pulse
FNC 12
K4M0 D8288
MOV
L-25
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 4.7 Error Status
M8000 FNC 12
D8288 K4M0
Normally ON MOV
M0
Y000 The temperature measurement data
of channel 1 is outside the specified
range, or disconnection is detected.
M1
Y001 The temperature measurement data
of channel 2 is outside the specified
range, or disconnection is detected.
M2
Y002 The temperature measurement data
of channel 3 is outside the specified
range, or disconnection is detected.
M3
Y003 The temperature measurement data
of channel 4 is outside the specified
range, or disconnection is detected.
M4
Y004 EEPROM error in 3rd*1 adapter.
M5
Y005 Averaging time setting error in 3rd*1
adapter.
M6
Y006 TC-ADP hardware error in 3rd*1
adapter.
M7
Y007 TC-ADP communication data error
in the 3rd*1 adapter.
L-26
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 4.8 Model Code
K
3. Program Example 2 (For FX3U/FX3UC Series PLC)
FX3U-4AD-PNK
D8268.0
-ADP
Y000 The temperature measurement data
of channel 1 is outside the specified
D8268.1
range, or disconnection is detected. L
Y001 The temperature measurement data
FX3U-4AD-TC
of channel 2 is outside the specified
range, or disconnection is detected.
D8268.2
-ADP
Y002 The temperature measurement data
of channel 3 is outside the specified
D8268.3
range, or disconnection is detected. M
Y003 The temperature measurement data
PID Instruction
of channel 4 is outside the specified
range, or disconnection is detected.
(FNC 88)
D8268.4
Y004 EEPROM error in 1st adapter.
D8268.5
Y005 Averaging time setting error in 1st
adapter.
D8268.6
Y006 TC-ADP hardware error in 1st
adapter.
D8268.7
Y007 TC-ADP communication data error
in the 1st adapter.
Use the above special data registers to check whether TC-ADP is connected or not.
L-27
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 4.9 Basic Program Example
M8000
FNC 12 D8288 K4M0
Normally MOV
ON
M8002 Error status of 3rd*1 analog special
RST M6 adapter
b6 = OFF (TC-ADP hardware error)
Initial
pulse Error status of 3rd*1 analog special
RST M7 adapter
b7 = OFF (TC-ADP communication data error)
FNC 12 K4M0 D8288
MOV
M8001
M8280 Sets the temperature unit to
centigrade (C)
Normally
OFF
M8281 Selects thermocouple type K
M8002
FNC 12 K32 D8284 Sets the averaging time to "32" for
MOV channel-1 data.
Initial
pulse
FNC 12 K128 D8285 Sets the averaging time to "128" for
MOV channel-2 data.
M8000 Stores the current value of the
FNC 12 D8280 D100 channel-1 measurement
Normally MOV temperature data to D100.
ON Stores the current value of the
FNC 12 D8281 D101 channel-2 measurement
MOV temperature data to D101.
Even if the temperature measurement data is not stored to D100 or D101, data registers D8280 or D8281
can be directly used in the arithmetic operation instruction or a PID instruction.
*1. "1st" for the FX3S/FX3G/FX3GC PLC.
L-28
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 4.9 Basic Program Example
K
• For FX3U/FX3UC Series PLC
FX3U-4AD-PNK
The following program will select thermocouple type K and will store the temperature measurement data
(°C) of channels 1 and 2 of the 1st adapter in the D100 and the D101, respectively. The averaging time will
be set to "32" for channel 1, and "128" for channel 2.
-ADP
M8002
RST D8268.6
Error status of 1st analog special
adapter
b6 = OFF (TC-ADP hardware error)
L
Initial
FX3U-4AD-TC
pulse
RST D8268.7 Error status of 1st analog special
adapter
b7 = OFF (TC-ADP communication data error)
M8001
-ADP
M8260 Sets the temperature unit to
centigrade (C)
Normally
OFF M
M8261 Selects thermocouple type K
PID Instruction
M8002
(FNC 88)
FNC 12 K32 D8264 Sets the averaging time to "32" for
MOV channel-1 data.
Initial
pulse
FNC 12 K128 D8265 Sets the averaging time to "128" for
MOV channel-2 data.
M8000 Stores the current value of the
FNC 12 D8260 D100 channel-1 measurement
Normally MOV temperature data to D100.
ON Stores the current value of the
FNC 12 D8261 D101 channel-2 measurement
MOV temperature data to D101.
Even if the temperature measurement data is not stored to D100 or D101, data registers D8260 or D8261
can be directly used in the arithmetic operation instruction or a PID instruction.
L-29
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Troubleshooting
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 5.1 PLC Version Number Check
5. Troubleshooting
This chapter describes the troubleshooting methods and error status.
If the temperature measurement data is not input, or if the proper digital value is not input, check the following
items:
• Version number of the PLC
• Wiring
• Special devices
• Programs
• Error status
L-30
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Troubleshooting
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 5.4 Program Check
K
5.4 Program Check
FX3U-4AD-PNK
Check the following items for the program:
-ADP
1. Cancellation of error status at power-on
When the power is turned off and then on again, the error status should be cleared (the b6 and the b7 should L
turn off) using the program.
FX3U-4AD-TC
2. Check of storage devices
Verify that different values are not being stored in the same device by the other parts of the programs.
-ADP
5.5 Error Status Check M
PID Instruction
If an error occurs in the TC-ADP, the corresponding bit will turn on.
(FNC 88)
The bit which is turned ON due to the error status is held ON until overwritten to OFF by the program or the
power is cycled. If b6 or b7 is turned ON, then it is necessary to clear the error status using the program the
next time the power of the PLC is cycled.
L-31
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Troubleshooting
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 5.5 Error Status Check
L-32
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition
PID Instruction (FNC 88)
FX3U-4AD-PNK
-ADP
L
FX3U-4AD-TC
FX3S/FX3G/FX3GC/FX3U/FX3UC Series
-ADP
Programmable Controllers M
PID Instruction
User's Manual [Analog Control Edition]
(FNC 88)
M. PID Instruction (FNC 88)
Foreword
This manual describes the control methods for using the PID instruction in combination with analog products
and should be read and understood before attempting to install or use the unit.
Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
it to the end user.
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
rights which may occur as a result of using the contents noted in this manual.
M-1
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition
PID Instruction (FNC 88)
M-2
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
PID Instruction (FNC 88) 1.1 Outline of function
FX3U-4AD-PNK
1. Outline
-ADP
This chapter describes the outline of PID instruction (FNC88) for the FX3S/FX3G/FX3GC/FX3U/FX3UC Series
PLC.
L
FX3U-4AD-TC
1.1 Outline of function
-ADP
The PID instruction requires the system to calculate the output (MV) value from the measured (PV) value.
Through combining the P (proportional) action, I (integral) action, and D (derivative) action the target (SV) M
value can be obtained. See diagram below.
PID Instruction
1) Alarm output function
(FNC 88)
The alarm function can be set for input variation (measured value) or output variation (value).
2) Setting limit values
The upper limit and lower limit can be set for the output value.
3) Auto-tuning function
The proportional gain (KP), integral time (TI) and differential time (TD) can be set automatically for both
the limit cycle method and step response method.
4) Operation method of the PID instruction
Both PID speed type operation and measured value differential type operation are executed.
Target value
(SV)
Controlled
PID Instruction object
M-3
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
PID Instruction (FNC 88) 1.2 Basic Operation Expressions in PID Instruction (Reference)
TS
ΔMV = KP{(EVn − EVn-1) + EVn + Dn}
TI
Forward operation EVn = PVnf-SV
(OFF) TD KDTD
Dn = (−2PVnf−1 + PVnf + PVnf−2) + Dn-1
TS + KDTD TS + KDTD
MVn = ΣΔMV
TS
ΔMV = KP{(EVn − EVn−1) + EVn + Dn}
TI
Backward EVn = SV − PVnf
operation (ON) TD KDTD
Dn = (2PVnf−1 − PVnf − PVnf−2) + Dn-1
TS + KDTD TS + KDTD
MVn = ΣΔMV
1) Symbols
EVn : Deviation in sampling at this time Dn : Differential term at this time
EVn-1 : Deviation in previous cycle Dn-1 : Differential term in previous cycle
SV : Target value KP : Proportional gain
PVnf : Measured value in sampling at this time (after filter) TS : Sampling cycle
PVnf-1 : Measured value in previous cycle (after filter) TI : Integral constant
PVnf-2 : Measured value in two cycles before (after filter) TD : Differential constant
ΔMV : Output variation KD : Differential gain
MVn : Operation quantity at this time
2) Expression for calculating the measured value (after the filter) in sampling at this time (PVnf)
The value "PVnf" is obtained from the following expression based on the read measured value.
M-4
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 How to Use PID Instruction
PID Instruction (FNC 88) 2.1 Explanation of function and operation
FX3U-4AD-PNK
2. How to Use PID Instruction
-ADP
1. Instruction format L
FX3U-4AD-TC
16-bit Mnemonic Operation Condition 32-bit Mnemonic Operation Condition
FNC 88 Instruction Instruction
PID 9 steps PID Continuous ⎯
PID
Operation
-ADP
2. Set data M
PID Instruction
Operand type Description Data type
S1 Data register storing the target value (SV) Binary 16-bit
(FNC 88)
S2 Data register storing the measured value (PV) Binary 16-bit
S3 Data register storing PID parameters Binary 16-bit
D Data register storing the output value (MV) Binary 16-bit
3. Target devices
Bit devices Word devices Others
M-5
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 How to Use PID Instruction
PID Instruction (FNC 88) 2.2 Relationship Between Parameter Setting and Auto-Tuning
*1. When auto-tuning is not executed for the limit cycle method, the same number of devices as those
occupied in the step response method become occupied.
M-6
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Parameter
PID Instruction (FNC 88) 3.1 Parameter List: (S3) to (S3) + 28
FX3U-4AD-PNK
3. Parameter
-ADP
This chapter describes various parameters of PID instruction. L
FX3U-4AD-TC
3.1 Parameter List: (S3) to (S3) + 28
-ADP
Set item Setting Remarks Reference
It cannot be shorter than operation Subsection
M
Sampling time (TS) 1 to 32767 (ms)
PID Instruction
S3
cycle of the PLC. 3.2.1
0: Forward operation
(FNC 88)
bit0 Operation direction
1: Backward operation
0: Input variation alarm is invalid.
bit1
1: Input variation alarm is valid.
0: Output variation alarm is invalid. Do not set to ON bit 2 and bit 5 at
bit2
1: Output variation alarm is valid. same time.
bit3 Not available
Operation 0: Auto-tuning is not executed. Subsection
S3 +1 bit4
setting (ACT) 1: Auto-tuning is executed. 3.2.2
0: Upper and lower limits of output
value are not valid. Do not set to ON bit 2 and bit 5 at
bit5
1: Upper and lower limits of output same time.
value are valid.
0: Step response method
bit6 Select auto-tuning mode.
1: Limit cycle method
bit7 to bit15 Not available
When "0" is set, input filter is not Subsection
S3 +2 Input filter constant (α) 0 to 99 (%)
provided. 3.2.3
Subsection
S3 +3 Proportional gain (KP) 1 to 32767 (%)
3.2.4
When "0" is set, it is handled as "∞" Subsection
S3 +4 Integral time (TI) 0 to 32767 (× 100 ms)
(no integration). 3.2.5
When "0" is set, differential gain is Subsection
S3 +5 Differential gain (KD) 0 to 100 (%)
not provided. 3.2.6
When "0" is set, differential is not Subsection
S3 +6 Differential time (TD) 0 to 32767 (× 10 ms)
executed. 3.2.7
S3 +7
: These devices are occupied for internal processing of PID operation. Do not change data. -
S3 +19
M-7
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Parameter
PID Instruction (FNC 88) 3.1 Parameter List: (S3) to (S3) + 28
*1. S3 +20 to +24 become occupied only if bits 1, 2, or 5 are set to "1" to determine the action (ACT) of
S3 +1.
M-8
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Parameter
PID Instruction (FNC 88) 3.2 Details of Parameters
FX3U-4AD-PNK
3.2.1 Sampling time (TS): (S3)
-ADP
Setting range: 1 to 32767 [ms]
Set the cycle time (ms) for the PID operation.
L
FX3U-4AD-TC
• In PID control and auto-tuning (Limit cycle method)
Set the sampling time longer than the operation cycle of the PLC.
• In auto-tuning (Step response method)
-ADP
Set the sampling time to 1,000 ms (= 1 second) or more.
1. Maximum error
M
PID Instruction
The maximum error of the sampling time (TS) is from "-(one operation cycle + 1 ms)" to "+(one operation
cycle)."
(FNC 88)
1) When the sampling time (TS) is a small value
Fluctuation of the maximum error described above may cause a problem.
In such a case, execute the PID instruction in the constant scan mode, or program it in a timer interrupt
routine.
2) When the sampling time (TS) is shorter than one operation cycle of the PLC
A PID operation error (K6740) occurs, however when PID operation is executed, the sampling time (TS) is
equal to the operation cycle of the PLC.
In such a case, use the PID instruction in a timer interrupt (I6 to I8), and clear S3 +7 just before
executing the PID instruction.
→ For a detailed description, refer to FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual
- Basic & Applied Instruction Edition
S3 +7 is reset.
X000 (When the interrupt routine is executed for the
FNC 12 K 0 D107
I610 first time, the register for internal processing is
MOVP
cleared by the pulse generation command.)
M-9
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Parameter
PID Instruction (FNC 88) 3.2 Details of Parameters
Time
Time
Relationship between the forward/backward operation and the output (MV), measured value (PV) and
target value (SV)
The relationship is as follows.
Target value (SV)
Output (MV)
Backward Forward
operation operation
M-10
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Parameter
PID Instruction (FNC 88) 3.2 Details of Parameters
2. Alarm setting (for input variation and output variation): S3 +1, bit 1 and bit 2
K
FX3U-4AD-PNK
Setting range: OFF, ON
The input variation and output variation can be checked arbitrarily.
These parameters can be set in S3 +24.
-ADP
→ For the operation of upper/lower limit alarm output for the input and output values,
refer to Subsection 3.2.8.
L
FX3U-4AD-TC
Input variation: S3 +1, bit 1
When using the input variation alarm, it is necessary to set to ON the following bits and set the values to be
checked.
-ADP
Set item Setting (setting range)
Operation setting
(ACT)
S3 +1 bit1 Input variation alarm
ON: Used
OFF: Not used
M
PID Instruction
Input variation S3 +20 Input variation (incremental) alarm set value 0 to 32767
alarm set value
(FNC 88)
S3 +21 Input variation (decremental) alarm set value 0 to 32767
Output variation S3 +22 Output variation (incremental) alarm set value 0 to 32767
alarm set value S3 Output variation (decremental) alarm set value 0 to 32767
+23
Output value
When the upper limit and lower These values
limit of output value are not set are not output.
S3 +22
Output value
upper limit
S3 +23
Output value
lower limit These values
are not output.
When the upper limit and lower
limit of output value are set
Time
M-11
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Parameter
PID Instruction (FNC 88) 3.2 Details of Parameters
Because the input filter (α) is effective to the target value (SV), all of the proportional operation, integral
operation and differential operation are affected.
Input amplitude
Measured Input amplitude
value (PV) processed by input filter
processed by
input filter
M-12
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Parameter
PID Instruction (FNC 88) 3.2 Details of Parameters
FX3U-4AD-PNK
Setting range: 1 to 32767[%]
PID control: Proportional operation
-ADP
During the proportional operation, the output (MV) increases in proportion to the deviation (difference
between the target value (SV) and the measured value (PV)).
This deviation is called proportional gain (Kp), and expressed in the following relational expression: L
FX3U-4AD-TC
Output (MV) = Proportional gain (KP) × Deviation (EV)
The reciprocal of the proportional gain (KP) is called proportional band.
As the proportional gain (KP) is larger (as shown in the example below), the motion to let the measured value
-ADP
(PV) be nearer to the target value (SV) becomes stronger.
PID Instruction
Target value (SV)
(FNC 88)
Temperature
Time
Output (MV)
Proportional gain
KP3 KP3 > KP2 > KP1
KP2 KP1
Time
Proportional gain
KP3 KP2 KP1 KP3 > KP2 > KP1
Proportional gain
KP3 KP2 KP1 KP3 > KP2 > KP1
Time
Setting range: 0 to 32767 [ × 100 ms] "0" is handled as "∞" (no integration).
PID operation: Integral operation
During the integral operation, the time after deviation is generated until the integral operation output becomes
the proportional operation output. This is called integral time and is expressed as "TI".
As TI becomes smaller, the integral operation becomes stronger.
M-13
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Parameter
PID Instruction (FNC 88) 3.2 Details of Parameters
Time
Time
TI3 TI2
Target TI1
Measured value in proportional operation
value(SV)
Measured value in PI operation
Time
Time
Important point
The integral operation changes the output so that the continuously generated deviation is eliminated.
As a result, the remaining deviation generated in the proportional operation can be eliminated.
Deviation
Deviation (EV)
Time
Output of
"proportional operation + integral operation"
Time
M-14
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Parameter
PID Instruction (FNC 88) 3.2 Details of Parameters
FX3U-4AD-PNK
Setting range: 0 to 100[%]
PID control: Differential operation
-ADP
The filter is applied to the output at the differential operation.
Only the differential operation is affected by the differential gain (KD).
• When the differential gain (KD) is small, the output is immediately given with regard to changes in the
L
FX3U-4AD-TC
measured value (PV) caused by disturbance, etc.
• When the differential gain (KD) is large, the output is given after a long time with respect to changes in the
measured value (PV) caused by disturbance, etc.
-ADP
Important points
Set the differential gain (KD) to "0", and then adjust the operation using the input filter (α). M
If the output response is too close to the disturbance, increase the differential gain (KD).
PID Instruction
(FNC 88)
3.2.7 Differential time (TD): (S3)+6
Disturbance
TD1 (PID operation) Deviation (EV)
TD2 (PID operation)
Time
Time
M-15
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Parameter
PID Instruction (FNC 88) 3.2 Details of Parameters
Time
Output (MV)
Time
Time
Time
M-16
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Parameter
PID Instruction (FNC 88) 3.2 Details of Parameters
FX3U-4AD-PNK
When the input variation [ S3 +1, bit 1] is set to 1
-ADP
Variation
L
Measured value (PV)
FX3U-4AD-TC
-ADP
M
PID Instruction
(FNC 88)
Time
Sampling time (TS)
Alarm flag
ON
S3 +24
bit0
ON
S3 +24
bit1
Variation
Output (MV)
Variation
Time
Sampling time (TS)
Alarm flag
ON
S3 +24
bit2
ON
S3 +24
bit3
M-17
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Auto-Tuning
PID Instruction (FNC 88) 4.1 Limit Cycle Method
4. Auto-Tuning
This chapter describes the auto-tuning function of PID instruction.
The auto-tuning function will automatically set the important constants, such as the proportional gain and the
integral time, to ensure optimum PID control.
There are two auto-tuning methods: limit cycle method and step response method.
M-18
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Auto-Tuning
PID Instruction (FNC 88) 4.1 Limit Cycle Method
FX3U-4AD-PNK
1 Set the forward or backward operation
-ADP
Set the operation direction flag (bit 0) in the operation setting parameter (ACT) S3 +1.
L
2 Select the auto-tuning method (limit cycle method)
FX3U-4AD-TC
Set the auto-tuning method to ON (bit 6) in the operation setting parameter (ACT) S3 +1.
(When bit 6 is set to OFF, the step response method is selected.)
-ADP
3 Set the auto-tuning execution flag to ON M
PID Instruction
Set the auto-tuning execution flag to ON (bit 4) in the operation setting parameter (ACT) S3 +1.
(FNC 88)
Set the input filter
Set the input filter in the operation setting parameter (ACT) S3 +2.
M-19
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Auto-Tuning
PID Instruction (FNC 88) 4.1 Limit Cycle Method
4.1.3 Reference: How to obtain three constants in PID control (limit cycle method)
For acquiring satisfactory control results in PID control, it is necessary to obtain the optimal value of each
constant (parameter) suitable to the control target.
This paragraph explains the limit cycle method to obtain the amplitude (a) and vibration cycle (τ, τon) of the
input value, and then calculate the proportional gain (KP), integral time (TI) and differential time (TD) based on
the expressions shown in the table below.
Output value
ULV
(Output upper
limit value)
LLV
(Output lower
limit value)
Time
Input value
SV+SHPV
SV(target value) a
SV-SHPV
τ
τ on τw
τ0 τ1 τ2 Time(s)
PI control 0.9 (
ULV - LLV) ×100 τ on
(PI operation) a
33 × τ on 1 - ⎯
τ
PID control 1.2 (
ULV - LLV) ×100 τon τon
(PID operation) a 20 × τ on 1 - 50 × τ on 1 -
τ τ
M-20
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Auto-Tuning
PID Instruction (FNC 88) 4.2 Step Response Method
FX3U-4AD-PNK
4.2.1 Parameters to be set by auto-tuning (step response method)
-ADP
Parameter
Operation setting (ACT)
Setting position Parameter
Integral time (TI)
Setting position
L
S3 +1, bit 0 (operation direction) S3 +4
FX3U-4AD-TC
Proportional gain (KP) S3 +3 Differential time (TD) S3 +6
-ADP
4.2.2 Auto-tuning procedure
M
1 Transferring the output value for auto-tuning to the output value D
PID Instruction
Set the output value for auto-tuning to the maximum available output value multiplied by 0.5 to 1 for
(FNC 88)
the output equipment.
2 Setting the parameter S3 , target value (SV), etc. that cannot be set in auto-
tuning according to the system
Note that auto-tuning may not be executed normally if the cautions described below are not fol-
lowed
1. Set items
Set item and parameter Remarks
The difference from the measured value (PV) should be 150 or more.
Target value (SV) S1
(For the details, refer to "2. Cautions on setting" below.)
Sampling time (TS) S3 1,000 ms or more (For the details, refer to "2. Cautions on setting" below.)
Input filter (α) S3 +2
Differential gain (KD) S3 +5 When setting the input filter, set the differential gain to "0" usually.
Others Set other items, as necessary.
2. Cautions on setting
1) Difference between the target value (SV) and the measured value (PV)
If the difference between the target value (SV) and the measured value (PV) is less than 150 when auto-
tuning is started, auto-tuning is not executed normally.
Accordingly, if the difference is less than 150, set the target value for auto-tuning.
Set the target value again when auto-tuning is completed.
Set item Setting in PID instruction
Make sure that the difference from the measured value is 150 or
Target value (SV) S1
more when auto-tuning is started.
1. Important point
Start auto-tuning while the system is stable.
If the system is unstable when auto-tuning is started, auto-tuning may not be executed normally.
M-21
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Auto-Tuning
PID Instruction (FNC 88) 4.3 Cautions on Auto-Tuning Execution
4.2.3 Reference: How to obtain three constants in PID control (step response method)
For acquiring satisfactory control results during PID control, it is necessary to obtain the optimal value of each
constant (parameter) suitable for the control target.
This paragraph explains the step response method to obtain three constants in the PID control (proportional
gain (KP), integral time (TI) and differential time (TD)).
Operation characteristics
100%
Output value Output value (MV)
0%
Time
Input value
variation Maximum ramp (R)
Time (s)
Dead time (L) 1 (s)
[s]
1. Countermeasures with in the program when the input value (PV) does not change
When the input value (PV) does not change normally due to factors such as wire breakage in an analog input
line, auto-tuning is not finished.
Detect and avoid such occurrences by introducing a sequence to monitor the input value or the elapsed time
from the start of auto-tuning.
M-22
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Example of Practical Programs (for Step Response Method)
PID Instruction (FNC 88) 5.1 Example: System and operation
FX3U-4AD-PNK
5. Example of Practical Programs (for Step Response Method)
-ADP
The following is an example of a program for the operation application system shown below. L
FX3U-4AD-TC
5.1 Example: System and operation
System configuration
-ADP
Temperature sensor Shielded compensating
(Thermocouple) conductor
M
PID Instruction
X10 X11
ch2
(FNC 88)
FX3U-32MR/ FX2N-16EYT- FX2N-4AD-
ES ESS/UL*1
TC
COM Y20 Y21
Temperature Error indication
chamber
2000
Output value upper limit S3 +22 2000
(2 seconds)
Output value lower limit S3 +23 0 0
OFF ON ON ON ON ON
1.8 sec (1800 ms) 1.8 sec (1800 ms) 1.8 sec (1800 ms)
M-23
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Example of Practical Programs (for Step Response Method)
PID Instruction (FNC 88) 5.2 Program example of auto-tuning (step response method) and PID control
5.2 Program example of auto-tuning (step response method) and PID control
Initial pulse
M8002
FNC 12 K500 D500 The target value is set (to 50 °C).
MOV
Initial pulse
M8002 The mode of FX2N-4AD-TC is set.
FNC 79 K0 K0 H3303 K1 Ch 1: Unused Ch 3: Unused
TO Ch 2: K type Ch 4: Unused
RUN monitor
M8000
FNC 78 K0 K 10 D501 K1 Data is read from the channel 2 in
FROM FX2N-4AD-TC.
Initial pulse
M8002
RST D502 The PID operation is initialized.
PID control is
started after PID control is started
auto-tuning (without auto-tuning)
X010 X011
M-24
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Example of Practical Programs (for Step Response Method)
PID Instruction (FNC 88) 5.2 Program example of auto-tuning (step response method) and PID control
FX3U-4AD-PNK
Auto-tuning ON flag
M1
-ADP
FNC 12 Auto-tuning operation is
D511 K2M10 confirmed.
MOV
Auto-tuning ON flag L
M14
FX3U-4AD-TC
PLF M2 Auto-tuning is finished.
Auto-tuning is finished
-ADP
M2
RST M1 The normal operation is started.
M
PID operation is executed.
PID Instruction
M3
T246 Heater operation cycle
(FNC 88)
K2000
Heater operation cycle
T246
[ RST T246 ] Preset
PID operation
is executed.
M3
Error flag
M8067
Y020 Error occurs.
END
M-25
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Example of Practical Programs (for Step Response Method)
PID Instruction (FNC 88) 5.3 Program example of auto-tuning (step response method)
Auto-tuning is started.
X010
FNC 12 K500 D500 The target value is set (to 50°C).
MOVP
Auto-tuning is started.
M0
SET M1 PID instruction operation
Initial pulse
M8002 The mode of FX2N-4AD-TC is set.
FNC 79 K0 K0 H3303 K1 Ch 1: Unused Ch 3: Unused
TO Ch 2: K type Ch 4: Unused
RUN monitor
M8000
FNC 78 K0 K 10 D501 K1 Data is read from the channel 2
FROM in FX2N-4AD-TC.
Auto-tuning is started.
X010
RST D502 The PID output is initialized.
PID
operation
M1
PID
operation
M1
FNC 88 D500 D501 D510 D502 PID instruction
PID
Auto-tuning is finished.
M2
RST M1 Auto-tuning is completed.
M-26
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Example of Practical Programs (for Step Response Method)
PID Instruction (FNC 88) 5.3 Program example of auto-tuning (step response method)
FX3U-4AD-PNK
PID operation
M1
Heater operation cycle timer
-ADP
T246 (2 sec)
K2000
L
T246
The heater operation cycle timer
FX3U-4AD-TC
RST T246 is preset.
PID
operation
M1
-ADP
PID operation
M1
M
FNC226
PID Instruction
T246 D502 Y021 Heater output
LD <
(FNC 88)
Error flag
M8067
Y020 Error occurs.
END
M-27
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
PID Instruction (FNC 88) 6.1 Error Codes
6. Troubleshooting
Error
Error description Action
code
6730 Incorrect sampling time (TS) (TS ≤ 0)
Incorrect input filter constant (α)
6732
(α < 0 or 100 ≤ α)
<PID operation is stopped.>
6733 Incorrect proportional gain (KP) (KP < 0) A data error has occurred in the set value in a control parameter
6734 Incorrect integral time (TI) (TI < 0) or in the middle of PID operation.
Check the parameters.
Incorrect derivative gain (KD)
6735
(KD < 0 or 201 ≤ KD)
6736 Incorrect derivative time (TD) (TD < 0)
<Auto-tuning is continued.>
6740 Sampling time (TS) ≤ Operation cycle The operation is continued in the condition "sampling time (TS)
= cyclic time (operation cycle)."
Variation of measured value exceeds limit.
6742
(PV < −32768 or +32767 < PV)
Deviation exceeds limit.
6743
(EV < −32768 or +32767 < EV)
Integral result exceeds limit.
6744 <PID operation is continued.>
(Out of range from −32768 to +32767)
The operation is continued with each parameter set to the
Derivative value exceeds limit due to derivative gain maximum or minimum value.
6745
(KD).
Derivative result exceeds limit.
6746
(Out of range from −32768 to +32767)
PID operation result exceeds limit.
6747
(Out of range from −32768 to +32767)
<Output upper limit value and output lower limit value are
PID output upper limit set value < PID output lower limit
6748 exchanged for each other. → PID operation is continued.>
set value
Check whether the target settings are correct.
Abnormal PID input variation alarm set value or output <Alarm output is not given. → PID operation is continued.>
6749
variation alarm set value (Set value < 0) Check whether the target settings are correct.
<Auto-tuning is finished. → PID operation is started.>
• The deviation at start of auto-tuning is 150 or less.
<Step response method> • The deviation at end of auto-tuning is 1/3 or more of the
6750
Improper auto-tuning result deviation at start of auto-tuning.
Confirm the measured value and target value, and then execute
auto-tuning again.
<Auto-tuning is forced to finish. → PID operation does not
started.>
The operation direction estimated from the measured value at
<Step response method> the start of auto-tuning was different from the actual operation
6751
Auto-tuning operation direction mismatch direction of the output during auto-tuning.
Correct the relationship among the target value, output value
for auto-tuning and measured value, and then execute auto-
tuning again.
M-28
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
PID Instruction (FNC 88) 6.1 Error Codes
Error
K
Error description Action
FX3U-4AD-PNK
code
<Auto-tuning is finished. → PID operation is not started.>
Because the set value fluctuated during auto-tuning, auto-
-ADP
<Step response method> tuning was not executed correctly.
6752
Improper auto-tuning operation Set the sampling time to a value larger than the output change
cycle, or set a larger value to the input filter constant.
After changing the setting, execute auto-tuning again.
L
FX3U-4AD-TC
<Limit cycle method>
6753 Abnormal output set value for auto-tuning
[ULV (upper limit) ≤ LLV (lower limit)] <Auto-tuning is forcibly finished. → PID operation is not
-ADP
started.>
<Limit cycle method> Check whether the target settings are correct.
6754 Abnormal PV threshold (hysteresis) set value for auto-
tuning (SHPV < 0) M
PID Instruction
<Limit cycle method> <Auto-tuning is forcibly finished. → PID operation is not
Abnormal auto-tuning transfer status started.>
6755
(FNC 88)
(Data of device controlling transfer status is abnormally Verify that devices occupied by PID instruction are not
overwritten.) overwritten in the program.
<Auto-tuning is forcibly finished. → PID operation is not
started.>
The auto-tuning time is too long.
<Limit cycle method>
Increase the difference (ULV - LLV) between the upper limit and
6756 Abnormal result due to excessive auto-tuning
the lower limit of the output value for auto-tuning, set a smaller
measurement time (τon > τ, τon < 0, τ < 0)
value to the input filter constant (α), or set a smaller value to the
PV threshold (SHPV) for auto-tuning, and then check whether
the result is improved.
<Auto-tuning is finished (KP = 32767). → PID operation is
started.>
<Limit cycle method>
The variation of the measured value (PV) is small compared
6757 Auto-tuning result exceeds proportional gain. (KP = Out
with the output value. Multiply the measured value (PV) by "10"
of range from 0 to 32767)
so that the variation of the measured value will increase during
auto-tuning.
<Limit cycle method> <Auto-tuning is finished (KP = 32767). → PID operation is
6758 Auto-tuning result exceeds integral time. started.>
(TI = Out of range from 0 to 32767) The auto-tuning time is too long.
Increase the difference (ULV - LLV) between the upper limit and
<Limit cycle method> the lower limit of the output value for auto-tuning, set a smaller
6759 Auto-tuning result exceeds derivative time. value to the input filter constant (α), or set a smaller value to the
(TD = Out of range from 0 to 32767) PV threshold (SHPV) for auto-tuning, and then check whether
the result is improved.
Caution
With regard to the measured value (PV) in PID, normal measurement data should be read before PID
operation begins.
Especially when the PID operation is executed to the input value in an analog input block, pay attention to the
conversion time.
M-29
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
PID Instruction (FNC 88) 6.1 Error Codes
MEMO
M-30
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition Warranty
Warranty
Please confirm the following product warranty details before using this product.
1. Gratis Warranty Term and Gratis Warranty Range 2. Onerous repair term after discontinuation of
If any faults or defects (hereinafter "Failure") found to be production
the responsibility of Mitsubishi occurs during use of the (1) Mitsubishi shall accept onerous product repairs for
product within the gratis warranty term, the product shall be seven (7) years after production of the product is
repaired at no cost via the sales representative or discontinued.
Mitsubishi Service Company. However, if repairs are Discontinuation of production shall be notified with
required onsite at domestic or overseas location, expenses Mitsubishi Technical Bulletins, etc.
to send an engineer will be solely at the customer's (2) Product supply (including repair parts) is not available
discretion. Mitsubishi shall not be held responsible for any after production is discontinued.
re-commissioning, maintenance, or testing on-site that 3. Overseas service
involves replacement of the failed module. Overseas, repairs shall be accepted by Mitsubishi's local
overseas FA Center. Note that the repair conditions at
[Gratis Warranty Term]
each FA Center may differ.
The gratis warranty term of the product shall be for one
year after the date of purchase or delivery to a designated 4. Exclusion of loss in opportunity and secondary
place. Note that after manufacture and shipment from loss from warranty liability
Mitsubishi, the maximum distribution period shall be six (6) Regardless of the gratis warranty term, Mitsubishi shall not
months, and the longest gratis warranty term after be liable for compensation to:
manufacturing shall be eighteen (18) months. The gratis (1) Damages caused by any cause found not to be the
warranty term of repair parts shall not exceed the gratis responsibility of Mitsubishi.
warranty term before repairs. (2) Loss in opportunity, lost profits incurred to the user by
Failures of Mitsubishi products.
[Gratis Warranty Range]
(3) Special damages and secondary damages whether
(1) The range shall be limited to normal use within the foreseeable or not, compensation for accidents, and
usage state, usage methods and usage environment, compensation for damages to products other than
etc., which follow the conditions and precautions, etc., Mitsubishi products.
given in the instruction manual, user's manual and (4) Replacement by the user, maintenance of on-site
caution labels on the product. equipment, start-up test run and other tasks.
(2) Even within the gratis warranty term, repairs shall be 5. Changes in product specifications
charged for in the following cases. The specifications given in the catalogs, manuals or
1. Failure occurring from inappropriate storage or technical documents are subject to change without prior
handling, carelessness or negligence by the user. notice.
Failure caused by the user's hardware or software 6. Product application
design. (1) In using the Mitsubishi MELSEC programmable logic
2. Failure caused by unapproved modifications, etc., controller, the usage conditions shall be that the
to the product by the user. application will not lead to a major accident even if any
3. When the Mitsubishi product is assembled into a problem or fault should occur in the programmable
user's device, Failure that could have been logic controller device, and that backup and fail-safe
avoided if functions or structures, judged as functions are systematically provided outside of the
necessary in the legal safety measures the user's device for any problem or fault.
device is subject to or as necessary by industry (2) The Mitsubishi programmable logic controller has been
standards, had been provided. designed and manufactured for applications in general
4. Failure that could have been avoided if industries, etc. Thus, applications in which the public
consumable parts (battery, backlight, fuse, etc.) could be affected such as in nuclear power plants and
designated in the instruction manual had been other power plants operated by respective power
correctly serviced or replaced. companies, and applications in which a special quality
5. Relay failure or output contact failure caused by assurance system is required, such as for Railway
usage beyond the specified Life of contact companies or Public service purposes shall be
(cycles). excluded from the programmable logic controller
6. Failure caused by external irresistible forces such applications.
as fires or abnormal voltages, and failure caused In addition, applications in which human life or property
by force majeure such as earthquakes, lightning, that could be greatly affected, such as in aircraft,
wind and water damage. medical applications, incineration and fuel devices,
7. Failure caused by reasons unpredictable by manned transportation, equipment for recreation and
scientific technology standards at time of shipment amusement, and safety devices, shall also be
from Mitsubishi. excluded from the programmable logic controller range
8. Any other failure found not to be the responsibility of applications.
of Mitsubishi or that admitted not to be so by the However, in certain cases, some applications may be
user. possible, providing the user consults their local
Mitsubishi representative outlining the special
requirements of the project, and providing that all
parties concerned agree to the special circumstances,
solely at the users discretion.
i
FX3S/FX3G/FX3GC/FX3U/FX3UC PLC User's Manual - Analog Control Edition Revised History
Revised History
Date Revision Description
7/2005 A First Edition
2/2006 B • FX3U-4AD is added to B.
• FX3U-4DA is inserted to D.
• Adding and revising the other descriptions.
3/2006 C • B-8 page, 2.2 The Power Supply Specification for the FX3U-4AD, regarding the
A/D conversion circuit drive power:
Revised from [24V DC ±10%, 80mA] to [24VDC ±10%, 90mA]
3/2007 D • JIS (Japanese Industrial Standards) for temperature sensors are added
• Clerical error correction
12/2007 E • FX3UC (D, DSS) Series PLC added
• FX3U-4AD-PTW-ADP is inserted to G
• Clerical error correction
11/2008 F • FX3G Series PLC added
• FX3G-2AD-BD is added to D.
• FX3G-1DA-BD is added to G.
• FX3U-4AD-PNK-ADP is added to H.
• Adding and revising the other descriptions.
6/2009 G • FX3U-3A-ADP is added to H.
• The hardware error function of FX3U-4DA-ADP is added.
• Explanation corrections for manufacture's serial number.
• Adding and revising the other descriptions.
8/2010 H • Supports the under-scale detection function of the FX3U-4AD-ADP and
FX3U-3A-ADP.
• FX3U-4LC is added.
• Explanation corrections for the manufacture's serial number.
• Addition and revision of other descriptions.
• Clerical error correction
2/2012 J • FX3GC Series PLC added.
• Addition and revision of other descriptions.
• Clerical error correction.
5/2013 K • FX3S Series PLC added.
• Addition and revision of other descriptions.
• Clerical error correction.
8/2014 L • "Self-made power cable" is deleted from B.
• Clerical error correction.
4/2015 M • A part of the cover design is changed.
3/2016 N • Clerical error correction.
8/2016 P • Precautions for connecting the FX5U/FX5UC CPU module and FX3U-4AD/FX3U-
4DA are added.
ii
FX3S/FX3G/FX3GC/FX3U/FX3UC SERIES PROGRAMMABLE CONTROLLERS
USER'S MANUAL
HEAD OFFICE: TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
MODEL FX3U-U-ANALOG-E
MODEL CODE 09R619