ETAP Knowledge Base

TS Calculation Aborted

Description: TS calculation aborted due to voltage exceeding 2000%


Category: Transient Stability
Type: Simulation
Keywords: Voltage Exceeding

TS calculation aborted due to voltage exceeding 2000% and problems with the data file at
t = xxx sec.

If you get this error message, you may check the Simulation Time Step in study case editor >
Event page. Most likely it set to larger than 0.001s.

Work around:
Set the Simulation Time Step to 0.001s or smaller than smallest time constant in that project file.

This document is confidential and proprietary to Operation Technology, Inc. and may not be reproduced, published or disclosed to
others without the written authorization of Operation Technology, Inc., 17 Goodyear, Suite 100, Irvine, CA 92618, USA. © 2010 by
Operation Technology, Inc. All Rights Reserved.

© Operation Technology, Inc. Page 1 of 1 ETAPKB