G4 Digital DC Input Modules

Features
4000 volts transient optical isolation
Built-in LED status indicator
Small footprint design, reducing mounting space by
approximately 50 percent
Built-in filtering for transient suppression and noise
rejection

G4 Digital DC Input Modules


Operating temperature: -30 °C to 70 °C
UL recognized, CSA certified, CE approved
Passes NEMA Showering Arc Test (ICS 2-230)
Meets IEEE Surge Withstand Specification (IEEE-472)
Opto 22 G4 digital input modules include the
G4IDC5B high-speed module and the G4IDC5MA
Description module with manual-on/manual-off/automatic
switch for diagnostic testing.
Opto 22’s G4 DC input modules are used to detect on/off DC
voltage levels. Each module provides up to 4000 volts
(transient) of optical isolation between field inputs and the
logic output of the circuit.
All DC input modules except the G4IDC5K and G4IDC5D are
designed with filtering on the input and a hysteresis amplifier,
providing high noise rejection and transient-free, “clean”
switching. The G4IDC5K is a fast-switching module used to
detect signals produced by photoelectric switches and TTL
devices. The low-cost G4IDC5D is used for data acquisition.
Part Numbers
The G4IDC5MA is a special module featuring a manual-on/
manual-off/automatic switch, ideal for diagnostic testing of Part Description
control applications.
G4IDC5 G4 DC Input 10–32 VDC, 5 VDC Logic
The G4IDC5-SW and G4IDC5-SWNC modules supply power to
G4 DC Input 4–16 VDC, 5 VDC Logic
an external dry contact switch and sense switch closure (SW) G4IDC5B
High Speed
or opening (SWNC).
G4IDC5D G4 DC Input 2.5–28 VDC, 5 VDC Logic
Typical applications for DC input modules include sensing the G4IDC5G G4 DC Input 35–60 VDC, 5 VDC Logic
presence or absence of voltage and sensing contact closure
G4 DC Input 2.5–16 VDC, 5 VDC Logic
from sources such as proximity switches, limit switches, G4IDC5K
Very High Speed
selector switches, push buttons, photoelectric switches, and
TTL-compatible devices. G4 DC Input 10–32 VDC, 5 VDC Logic
G4IDC5MA
With Manual/Auto Switch
G4 Switch Status Input, Self-powered,
G4IDC5-SW
Normally Open
G4 Switch Status Input, Self-powered,
G4IDC5-SWNC
Normally Closed
DATA SHEET
Form 0253-150501

G4IDC15 G4 DC Input 10–32 VDC, 15 VDC Logic


G4IDC24 G4 DC Input 10–32 VDC, 24 VDC Logic

Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • www.opto22.com PAGE


SALES 800-321-6786 • 951-695-3000 • FAX 951-695-3095 • [email protected] • SUPPORT 800-835-6786 • 951-695-3080 • FAX 951-695-3017 • [email protected]
© 2012–2015 Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations. 1
G4 Digital DC Input Modules
Specifications

Units G4IDC5 G4IDC5B G4IDC5D G4IDC5G

VDC 10–32 4–16 2.5–28 35–60


Input voltage range
VAC 12–32 4–16 — 35–60
Key feature — Higher speed High speed —
Input current at maximum line mA 25 45 30 6
G4 Digital DC Input Modules

Isolation, input-to-output (transient):


1 ms V 4000 4000 4000 4000
1 minute V 1500 1500 1500 1500
Turn-on time ms 5 0.05 1 10
Turn-off time ms 5 0.1 1.5 10
Input allowed for off-state mA, V 1, 3 0.7, 1 0.2, 1 0.7, 7
Nominal output supply voltage VDC 5 5 5 5
Output supply voltage range VDC 4.5–6 4.5–6 4.5–6 4.5–6
Output supply current at
mA 12 12 12 12
nominal logic voltage
Input resistance (R1 in schematic) ohms 1.5 K 300 900 10 K
Control resistance (Rc in schematic) ohms 220 220 470 220
Output voltage drop V @ 50 mA 0.4 0.4 0.4 0.4
Output current (sinking) mA 50 50 50 50
microamps @
Output leakage with no input 100 100 10 100
30 VDC
Transistor V breakdown 30 30 30 30
Temperature:
Operating °C –30 to +70 –30 to +70 –30 to +70 –30 to +70
Storage °C –30 to +85 –30 to +85 –30 to +85 –30 to +85

G4IDC5-SW and G4IDC5-SWNC modules


See page 2 for specifications and other information for the
G4IDC5-SW and G4IDC5-SWNC self-powered modules.
Form 0253-150501
DATA SHEET

PAGE Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • www.opto22.com


SALES 800-321-6786 • 951-695-3000 • FAX 951-695-3095 • [email protected] • SUPPORT 800-835-6786 • 951-695-3080 • FAX 951-695-3017 • [email protected]
2 © 2012–2015 Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations.
G4 Digital DC Input Modules
Specifications (cont.)

Units G4IDC5K G4IDC5MA G4IDC15** G4IDC24**

VDC 2.5–16 10–32 10–32 10–32


Input voltage range
VAC — 12–32 12–32 12–32
Highest Diagnostic
Key feature — —
speed switch

G4 Digital DC Input Modules


Input current at maximum line mA 30 25 25 25
Isolation, input-to-output (transient):
1 ms V 4000 4000 4000 4000
1 minute V 1500 1500 1500 1500
Turn-on time ms 0.025* 5 5 5
Turn-off time ms 0.025* 5 5 5
Input allowed for off-state mA, V 0.2, 1 1, 3 1, 3 1,3
Nominal output supply voltage VDC 5 5 15 24
Output supply voltage range VDC 4.5–6 4.5–6 12–18 20–30
Output supply current at
mA 12 12 15 18
nominal logic voltage
Input resistance (R1 in schematic) ohms 500 1.5 K 1.5 K 1.5 K
Control resistance (Rc in schematic) ohms 220 220 1K 2.2 K
Output voltage drop V @ 50 mA 0.4 0.4 0.4 0.4
Output current (sinking) mA 50 50 50 50
microamps @
Output leakage with no input 100 100 100 100
30 VDC
Transistor V breakdown 30 30 30 30
Temperature:
Operating °C –30 to +70 –30 to +70 –30 to +70 –30 to +70
Storage °C –30 to +85 –30 to +85 –30 to +85 –30 to +85
* At 5Vp-p square wave input, 50% duty cycle.
** Not for use with Opto 22 brains.

DATA SHEET
Form 0253-150501

Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • www.opto22.com PAGE


SALES 800-321-6786 • 951-695-3000 • FAX 951-695-3095 • [email protected] • SUPPORT 800-835-6786 • 951-695-3080 • FAX 951-695-3017 • [email protected]
© 2012–2015 Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations. 3
G4 Digital DC Input Modules
G4IDC5-SW and G4IDC5-SWNC Modules

Description Typical switches for use with these modules are switched
status sensors (level sensors, pressure indicators, etc.),
Each G4IDC5-SW and G4IDC5-SWNC module provides one
magnetic reed switches (used on doors or windows for
isolated channel of contact status input. Each module supplies
burglar alarms), snap-action micro switches, the auxiliary
13 volts of power to an external dry contact switch. The
switches on motor starters, and most relay contacts.
G4IDC5-SW senses switch closure; the G4IDC5-SWNC senses
switch opening. Each user-supplied switch is connected with CAUTION: G4IDC5-SW and G4IDC5-SWNC inputs are not
G4 Digital DC Input Modules

two wires. Because these modules include power for the intended to be used with contacts that are connected to any
switch, they are particularly cost-effective when labor costs for external user-supplied voltage or currents.
wiring external power are high.

Specifications

Field Side Ratings


Open Circuit Voltage (Switch Open) 11 VDC min., 13 VDC typical, 15 VDC max.
Short Circuit Current (Switch Closed) 6 milliamps nominal
Minimum Off Resistance ≥20 K ohms
Maximum Allowable On Resistance
500 ohms
(Wire + Contact Resistance)
Logic Side Ratings
Logic Output Voltage for G4IDC5-SW <0.5 V max. (switch closed; LED on) @ 2 mA sinking
(normally open) 2.7 V min. (switch open; LED off) @ 0.4 mA sourcing
Logic Output Voltage for G4IDC5-SWNC <0.5 V max. (switch open; LED on) @ 2 mA sinking
(normally closed) 2.7 V min. (switch closed; LED off) @ 0.4 mA sourcing
Maximum Operating Common Mode
250 V
Voltage (Field Term to Logic Connector)
Power Requirements: 5 VDC (±0.25) @ 25 mA nom.
Module Ratings
Number of Channels Per Module 1
Turn-on Time 8 msec typical
Turn-off Time 8 msec typical
Input-to-output Isolation (transient) 4000 V AC/DC
0 °C to 70 °C, operating
Temperature
–30 °C to 85 °C, storage

Schematic
Form 0253-150501
DATA SHEET

PAGE Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • www.opto22.com


SALES 800-321-6786 • 951-695-3000 • FAX 951-695-3095 • [email protected] • SUPPORT 800-835-6786 • 951-695-3080 • FAX 951-695-3017 • [email protected]
4 © 2012–2015 Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations.
G4 Digital DC Input Modules
Dimensions

G4 Digital DC Input Modules


Schematics

DATA SHEET
Form 0253-150501

Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • www.opto22.com PAGE


SALES 800-321-6786 • 951-695-3000 • FAX 951-695-3095 • [email protected] • SUPPORT 800-835-6786 • 951-695-3080 • FAX 951-695-3017 • [email protected]
© 2012–2015 Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations. 5
More About Opto 22
Products Professional, available for separate purchase, adds one SoftPAC,
OptoOPCServer, OptoDataLink, options for controller redundancy
Opto 22 develops and manufactures reliable, flexible, easy-to-use or segmented networking, and support for legacy Opto 22 serial
hardware and software products for industrial automation, mistic™ I/O units.
energy management, remote monitoring, and data acquisition
applications. SNAP PAC Brains
While SNAP PAC controllers provide central control and data
groov distribution, SNAP PAC brains provide distributed intelligence for
groov puts your system on your mobile device. With zero I/O processing and communications. Brains offer analog, digital,
programming, you can build mobile operator interfaces to and serial functions, including thermocouple linearization; PID
monitor and control systems from Allen-Bradley, Siemens, loop control; and optional high-speed digital counting (up to 20
Schneider Electric, Modicon, and many more. Web-based groov kHz), quadrature counting, TPO, and pulse generation and
puts mobile-ready gadgets at your fingertips. Tag them from your measurement.
existing tag database, and they automatically scale for use on any SNAP I/O
device with a modern web browser. See groov.com for more
I/O provides the local connection to sensors and equipment.
information and your free trial.
Opto 22 SNAP I/O offers 1 to 32 points of reliable I/O per module,
depending on the type of module and your
SNAP PAC System
needs. Analog, digital, and serial modules are
Designed to simplify the typically complex all mixed on the same mounting rack and
process of selecting and applying an controlled by the same processor (SNAP PAC
automation system, the SNAP PAC brain or rack-mounted controller).
System consists of four integrated
components:
Quality
• SNAP PAC controllers
• PAC Project™ Software Suite Founded in 1974, Opto 22 has established a
• SNAP PAC brains worldwide reputation for high-quality products.
• SNAP I/O™ All are made in the U.S.A. at our manufacturing
facility in Temecula, California. Because we
SNAP PAC Controllers
test each product twice before it leaves our
Programmable automation controllers factory, rather than only testing a sample
(PACs) are multifunctional, modular controllers based on open of each batch, we can guarantee most
standards. solid-state relays and optically isolated I/O
Opto 22 has been manufacturing PACs for over two decades. The modules for life.
standalone SNAP PAC S-series, the rack-mounted SNAP PAC R-
series, and the software-based SoftPAC™ all handle a wide range Free Product Support
of digital, analog, and serial functions for data collection, remote
monitoring, process control, and discrete and hybrid Opto 22’s California-based Product Support Group offers free,
manufacturing. comprehensive technical support for Opto 22 products. Our staff
of support engineers represents decades of training and
SNAP PACs are based on open Ethernet and Internet Protocol (IP) experience. Support is available in English and Spanish by phone
standards, so you can build or extend a system easily, without the or email, Monday–Friday, 7 a.m. to 5 p.m. PST.
expense and limitations of proprietary networks and protocols.
Additional support is always available on our website: how-to
Wired+Wireless™ models are also available.
videos, OptoKnowledgeBase, self-training guide, troubleshooting
PAC Project Software Suite and user’s guides, and OptoForums.
Opto 22’s PAC Project Software Suite provides full-featured, cost- In addition, hands-on training is available for free at our Temecula,
effective control programming, HMI (human machine interface) California headquarters, and you can register online.
development and runtime, OPC server, and database connectivity
software for your SNAP PAC System.
Purchasing Opto 22 Products
Control programming includes both easy-to-learn flowcharts and
optional scripting. Commands are in plain English; variables and I/ Opto 22 products are sold directly and through a worldwide
O point names are fully descriptive. network of distributors, partners, and system integrators. For
more information, contact Opto 22 headquarters at 800-321-
PAC Project Basic offers control and HMI tools and is free for 6786 or 951-695-3000, or visit our website at www.opto22.com.
download on our website, www.opto22.com. PAC Project
www.opto22.com
www.opto22.com • Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • Form 1335-131203
SALES 800-321-6786 • 951-695-3000 • FAX 951-695-3095 • [email protected] • SUPPORT 800-835-6786 • 951-695-3080 • FAX 951-695-3017 • [email protected]
© 2014 Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations.