Data sheet

Insulation monitoring relay CM-IWN.1


For unearthed AC, DC and mixed AC/DC systems up to
Un = 400 V AC and 600 V DC

The CM-IWN.1 serves to monitor insulation resistance in


accordance with IEC 61557-8 in unearthed IT AC systems, IT AC
systems with galvanically connected DC circuits, or unearthed IT
DC systems with a voltage up to 400 V AC and 600 V DC. The
measuring range can be extended up to 690 V AC and 1000 V DC St
by using the coupling unit CM-IVN. It can be configured to
the requirements of the applications and therefore used multi¬
functional.
I K
'
5
Characteristics v
»•
- For monitoring the insulation resistance of unearthed IT systems up
Si HI
to Un = 400 V AC and 600 V DC
- According to IEC/EN 61557-8 “Electrical safety in low voltage
distribution systems up to 1 000 V a.c. and 1 500 V d.c. -
s

Equipment for testing, measuring or monitoring of protective
measures - Part 8: Insulation monitoring devices for IT systems"
- Rated control supply voltage 24-240 V AC/DC Approvals
- Prognostic measuring principle with superimposed square wave
UL 508, CAN/CSA C22.2 No.14
signal
- Two measuring ranges 1-100 kQ and 2-200 kQ
© GL
- One (1x2 c/o) or two (2 x 1 c/o) threshold values Ran1/R1 1> (final 9S. IEC/EN 60947-5-1, CB scheme
switch-off) and Ran2/R21> (prewarning) configurable2) ® GB1 4048.5 - 2001 , CCC
- Precise adjustment of the threshold values in 1 kQ steps (R1) and
© GOST
2 kQ steps (R2)
- Interrupted wire detection configurable
- Non-volatile fault storage configurable
- Open- or closed-circuit principle configurable Marks
- 45 mm (1.77 in) width C€ CE
- 3 LEDs for status indication C C-Tick
1> term acc. to IEC/EN 61557-8
2> R2 only active with 2 x 1 c/o configuration

Order data
Insulation monitoring relay
Type Nominal voltage U„of the distribution system to I Rated control supply System leakage Order code
be monitored voltage capacitance, max.
CM-IWN.1 0-400 V AC / 0-600 V DC 24-240 V AC/DC 20 pF 1SVR 650 660 R0200

Accessories
Type Description Order code
CM-IVN Coupling unit for connection of the CM-IWN.1 to systems with voltages Un up to 690 V AC and 1000 V DC 1SVR 650 669 R9400
ADR 02 Adapter for screw mounting 1 SVR 440 029 R0100
MAR.02 Marker label for devices with DIP switches 1 SVR 430 043 R0000
COV.02 Sealable transparent cover 1SVR 440 005 R0100