Material Properties Effect On Deflection PDF
Material Properties Effect On Deflection PDF
Part 1
36 TheStructuralEngineer Technical
October 2014 Material properties
37
38 TheStructuralEngineer Technical
October 2014 Material properties
BCSA
or demolish the development, and to deal with the resulting site
and materials, completes the lifetime environmental costs of that
Figure 2
Deflection coefficients C for moments of inertia for steel sections development13. Softwood timber is the most sustainable material, with
aluminium the most unsustainable
further noted that the natural frequency f1 of a simply supported • factor of safety — definitions of structural materials fall under
beam may also be obtained from its maximum deflection δ due to ‘ductile’ or ‘brittle’. The various codes of practice note that ductile
the applied load and self-weight in millimetres: materials, such as structural steelwork, have a material factor of
safety tending towards 1. Ductile behaviour sustains excessive local
f1 = 18 / δ1/2 (4) strains by plastic deformation, noted as the flat portion for steel in
Figure 3, thereby giving warning before damage occurs. Concrete,
On-site, a non-intrusive, preliminary, cheap testing plan is useful for on the other hand, with a material factor of safety of 1.5, appears to
characterising the global performance of a floor in terms of human sit on the dividing line between ductile and brittle. Other materials
footfall. A heel drop is generated by an 80kg person arching their with a material factor of safety higher than 1.5 are defined as brittle.
heels up by 60mm on the balls of their feet and then freefalling onto Brittle materials break without advance warning in the elastic range of
the floor. The peak force is about 2.2kN and the duration of the deformation (Fig. 3 shows the stress strain curve for glass)
impulse is 50ms11. The heel drop does not require an assessment of
the flooring damping system, as the (viscous) human body absorbs Although Fig. 3 notes glass as being a very brittle material, Table 2
mechanical energy whenever it is in contact with the floor. notes its E value and density to be similar to aluminium. Thus, although
the same C factor may be utilised for calculating span-to-deflection
EC5 notes that a residential timber floor may be considered to satisfy ratios for both these materials, it is important to note that glass in panes
vibration criteria if the natural frequency of the floor exceeds 8Hz. can deflect by more than its own thickness. This takes designers into
Furthermore, the immediate deflection under a 1kN point, which the realm of large deflection theory (Fig. 3), when the pane deflects by
represents a person walking on the floor, should not exceed the more than half of its thickness14. To avoid causing alarm, acceptable
deflection δ where l is the span given in millimetres12. span-to-deflection ratios for glass are limited to span/65 or should not
exceed 50mm15. In the case of prestressed glass, its strength may not
δ = 16 500 / I1.1 or 18mm if I <4m (5) be fully exploited as the deflection limit can control the design.
The term ‘serviceability’ refers to all structural behaviour, excluding It is noted that the density and the modulus of elasticity E for aluminium
structural collapse which renders a building or construction unfit for are approximately one-third that of steel. Thus, the deflections due to
its intended use. This lack of fitness may relate to human reactions dead loads for these materials are similar, even though the aluminium
(aesthetic, physiological or psychological), ranging from annoyance structure is much lighter. On the other hand, the embodied energy
to medical trauma. It may also hinder the operation of humans or content identifies steelwork as being a more sustainable material, with
equipment. In theory, it is possible to modify an unserviceable building, the production of aluminium having more impact on the environment.
so that it becomes serviceable. Serviceability limits and performance Similarly, for higher grades of steel used at the higher stress levels, the
standards as also influenced by non-structural matters such as deflections will be larger than for mild steel, as the E value is constant
architectural features, auditory and visual stimuli, and building usage, for different types of steelwork.
which militate against a single value; instead,
these should be specified in terms of sets
of limits1.
39
Material selection
The main goal of material selection is to minimise cost while meeting
product performance goals. Of course, cost per kilogram is not the
only important factor in material selection. An important concept is
‘cost per unit of function’. For example, if the key design objective were
the stiffness of a plate of the material, then the designer would need a
material with the optimal combination of density, Young's modulus and
price. A valuable insight into the inherent properties of a wide range of
different materials is given by the series of ‘property charts’ developed
by Ashby16. These charts are plotted on logarithmic scales due to the
large variation in material properties. For example, Young’s modulus of
SEWARD, 1998
elasticity E may vary by 10M times, while the density of various materials
may vary by as little as 2000 times.
Figure 4
Comparison of structural and functional properties of various materials
Figure 4 is based on values in Seward’s textbook on understanding
structures17. One of the properties is the strength of the different
materials per unit of weight — known as specific strength. It is noted
As fatigue performance relates to a material’s E value, the fact that that aluminium and fibre composites are more competitive, with the
aluminium’s E value is only one-third that of steel means that the least competitive being masonry and concrete. The weight of a building
fatigue strength of welded aluminium alloys at a given life is about is usually greater than its contents. Constructing a lighter structure
one-third that of corresponding steel joints. It is therefore important results in smaller structural members. On the other hand, weight can
to determine the natural frequency of vibration of the component be useful to resist wind loads. Steelwork generally requires fireproofing
and take account of the fatigue loading to be encountered3. or a paint treatment to offset corrosion effects, which consequently
reduces its efficiency.
As glass fibre’s E value stands at 1/10 that of steel, and it has
lower bond characteristics, concrete reinforced with such Deflection criteria, not strength, dictate the design of structures,
elements is different from conventional concrete. Essentially, especially where the higher grade of material is applied, unless short
concrete reinforced with glass-reinforced plastic shows larger spans are involved. The stiffness per unit of weight, known as specific
crack widths, larger deformations and lower shear strength than modulus, is a better criterion. Fig. 4 also demonstrates why steel and
conventional concrete reinforced with the same amount of steel3. aluminium appear more advantageous. The previous section, however,
Again, steel reinforcing bars are more sustainable than glass fibre discussed the fatigue weakness of aluminium as opposed to steelwork.
reinforcement.
The most economical structural materials appear to be concrete,
The long-term re-use of materials after demolition of structures also timber and steelwork. It is, however, worth noting that labour costs
needs to be accounted for. Steel is easily recycled, while concrete have been ignored in Fig. 3, while fire protection, as in steelwork,
and masonry are easily re-used as hardcore. Only timber may may also be required at an added cost. Although masonry appears
be regarded as a renewable source; however, to protect the rain expensive as a structural material, the cost also depends on the country
forests, the use of tropical hardwoods should be restricted to those where it is applied. For a country with low labour costs and restricted
obtained from properly managed schemes where timber is replaced. specialisations, it could turn out to be more economical.
40 TheStructuralEngineer Technical
October 2014 Material properties
So
cia
SUSTAINABILITY
Economical
CONFERENCE
tal
2014
en
nm
E n v ir o
Annual Institution Events Conferences & Seminars Special Interest Series Technical Lecture Series
A programme of conferences and seminars
organised by the Institution and industry partners
Early bird rates are available until Friday 3 October. Please visit the events section of the Institution website, www.istructe.org for
more information and to buy your tickets. Ticket sales will end Friday 21 November. If you have any questions, please contact the
Events Team at [email protected]
Technical TheStructuralEngineer 41
Material properties November 2014
Introduction
This article is the second in a three-part series outlining the This signifies that for timber, Equations 1 and 2 in Part 1 have to
serviceability hand calculations to be undertaken in the preliminary be factored by 1.33, after factoring up with the quotient of Young’s
structural design stage. modulus for steel divided by that for timber. This has been accounted
for when computing the timber C values (Table 1).
Structural design incorporating serviceability Reference is then made to Equation 3 in Part 1 for the calculation of
requirements rotation at the support in radians. Figure 1 highlights the relevance of
Further to the five basic serviceability equations outlined in Part 11, this rotation at the base of a simple timber structure supported on a
the following example uses the coefficients of load combinations and masonry pier. This rotation of the lightly loaded canopy also creates a
material characteristic strengths set out in the relevant Eurocodes. vertical distortion to the masonry pier due to the sagged shape of the
It goes beyond strength calculations to examine the effects of timber rafter, which produces a horizontal thrust on the pier.
deflection, vibration and rotation at the supports of an element. The Institution’s Manual for the design of steelwork building
These calculations are also useful when verifying the outputs structures to EC35 notes the following on vibration criteria:
produced from structural analysis and design programs. Although
the simplifications implicit in these formulae make them ideal for • the fundamental frequency of floors in dwellings and offices should
hand calculations, the use of automated calculation tools should not be less than three cycles/second. This may be deemed to be
not be ruled out. Options include creating a spreadsheet for these satisfied when the total deflection is less than 28mm
equations or even inputting them into a programmable calculator. • the fundamental frequency of floors used for dancing and gymnasia
In this calculation, reference is made to Table 1 for calculation should not be less than five cycles/second. This may be deemed to be
of C values, and to Equation 3 in Part 1 for calculation of rotation satisfied when the total deflection is less than 10mm
in radians. Here, Table 1 is an updated version of the table of load
values published in Part 1. Whereas Part 1 referred to a steel E value Earthquake engineers note a rule of thumb whereby ‘soft’ skeleton
of 205kN/mm2, as described by the British Constructional Steel structures have a period of fundamental natural oscillations equal
Association in 19902, here we use a steel E value of 210kN/mm2, as to roughly 1/10 of the number of floors in seconds6. For less ductile
set out more recently in EC33. Adopting the E values of EC3 results structures this constant doubles to 1/5. The period of a 15-storey
in minor savings in section sizings for the serviceability effects.
These savings are augmented in the strength calculation undertaken,
as the partial safety factors cited in EC3 are lower. Table 1: Updated deflection coefficient C for I cm4 calculation for
Note that the timber C values for lightweight timber floors a simple support span condition for UDLs and central point loads
account for a 33% increase in value over the interpolated E values Span-to- Steel E = 210kN/mm2 Timber E = 8kN/mm2
of the materials, to cater for creep effects. To allow for creep, the deflection ratio
Institution’s Technical Guidance Note ‘Design of timber floor joists’4
UDL Point load UDL Point load
states that the instantaneous deflection due to permanent loads
is to be increased by a factor of (1 + kdef), while for imposed loads a 1/200 1.24 1.98 43.3 52.0
reduced factor of (1 + ψ2.1kdef) is applied. Shear deflection can also be
1/360 2.23 3.57 77.9 93.7
accounted for by adding 10% to the calculated deflection.
With kdef given at 0.8 for an internal environment and ψ2.1 taken at 1/500 3.10 4.96 108.2 130.2
0.3, the calculated deflection has to be increased by 33% to cater for 1/800 4.96 7.94 173.2 208.4
all these effects. The effect of the distributed load on the deflection
1/1000 6.20 9.92 216.5 260.4
calculation is considered insignificant.
›
Part 2
42 TheStructuralEngineer Technical
November 2014 Material properties
4
5
= =
•
200 384 Figure 1
Rotation at support of
sagged 45-year-old timber rafter
3
5 × 200 × ×
=
384
5 × 200 × × ( ×1000 ) 3 construction does not disrupt the existing use of the premises.
3
= = The proposed intermediate floor has an effective span of 7.5m between
(384 × × 1000) × 10 4 load-bearing masonry walls, with an overall depth of 6.25m and a storey
height of 3.5m. The structural grid adopted is shown in Figure 2, with
When using I = CwL3, where w is in kN/m and L is in m, secondary steel beams (B1) spanning 6.25m onto a steel main beam (B2)
the moment of inertia I is calculated in cm4 by dividing by with a 7.5m span.
104. This assumes consistent units throughout in mm. In Spanning onto the secondary beams are continuous softwood C18
this case: timber planks on a structural grid of 1.25m centres. The front open façade
of this mezzanine floor is glazed in laminated glass, which reduces the
risk of damage and injury at a cost not much greater than that of normal
5 × 200 × 10 9 annealed glass. Laminated glass prevents glass shards from falling and
= = 1.24
(384 × 210 × 10 7 ) flying through the air, and ensures the fenestration remains sealed, even
during the most severe loading conditions.
where the C value of 1.24 conforms to the value quoted Design of timber flooring on a 1.25m continuous span
in Table 1. The timber floor plank is to be a C18 grade planed softwood with a density
For a timber section on a simply supported span, if we of 3.5kN/m3 and E0.mean of 8kN/mm2. We assume a 25mm thick plank,
restrict the deflection to span/500: continuous across a minimum of three spans. For this condition, a bending
moment (BM) of wl2/10 is used, instead of the simple BM of wl2/8.
3.10 × 1.33 × 210 The floor loading comprises a dead load (DL) of timber planks and a gym
= = 108.2 live load (LL) which is assumed to be 5kN/m2:
8
43
Table 2: I values and relative plank depths d* absolute deflection9. As a continuous span of more than three
bays, the span-to-deflection ratio for a UDL is to be reduced by
Strength Deflection-to- Deflection-to- 0.52:
span/250* span/150*
I (cm⁴) 130.2 280 168
=
d (mm) 25 32.25 27.22 (0.52 × 250 ) 130
* These ratios relate to a simple support condition
where:
1250
= = 9.62 mm
130
Using the C value of 43.3 stated in Table 1:
43.3 × 130
= 28.15
200
3
= = 28.15 × 5.09 × 1.25 3 = 280cm 4 /m
• Figure 2
Details of proposed lightweight
intermediate flooring A similar calculation for span/150 criteria yields I = 168cm4/m.
Vibration performance in timber floors may be a concern3
when spans are in excess of 4.0m. However, if a vibration check
for residential premises is to be undertaken according to EC5,
where the characteristic strength value f for C18 timber is the maximum deflection to limit vibration for a 1.25m span should
18N/mm2, the breadth b is taken per metre and the partial not exceed 1.8mm:
safety factor γm for timber is 1.3. Design of timber floor joists
notes that a factor kmod exists on the duration of the load4. span 1250
For intermediate floors defined as service class 1 and for = = 694.5
1.8
permanent self-weight and medium-term imposed floor
loads, kmod is given as 0.8. Table 1 notes that for a central point load:
It is also important to note that the behaviour of timber is
not ductile and timber design is therefore different to steel 694.5
and concrete design. The EC58 standard for designing = 52 × = 180.75
timber structures is based on a simplified method of limit
200
state, whereby characteristic values of load actions and where C = 52 and span/δ = 200.
material characteristics are adjusted by partial coefficients. As a continuous span of more than three bays, the span-to-
Timber structures are analysed using elastic structural deflection ratio for a central point load is to be reduced by 0.55:
analysis techniques in ULS and SLS states. Thus, while the
2
ULS loading is adopted as per EC5, the section modulus = 0.55 × = 0.55 × 180.75 × 1 × 1.25 2 = 155cm4
applied is the elastic, not the plastic, modulus.
As noted previously, for this rectangular section, the To satisfy vibration criteria for residential premises, this I
elastic modulus bd2/6 — not the plastic modulus bd2/4 — has value varies between a strength of 130.2cm4 and a deflection-to-
been applied. span/150 ratio of 168cm4 (Table 2).
The depth of the timber plank d in mm is calculated as: Thus, for this short span, the deflection criteria are more
onerous than the strength and vibration requirements.
They are further dependent on the type of damage to finishes
tolerated. EC5 states that limiting deflections should be specified
for each project and agreed upon with the client.
3
100 × 2.5 3
( ) = = = 130.2cm 4/ m 7.62 kN / m 2 × 1.25 m = 9.50 kN / m (ULS)
12 12 5.09 kN / m 2 × 1.25 m = 6.36 kN / m (SLS)
Ignoring vibration effects, timber deflection to reduce
2
damage to brittle finishes is to be limited to L/250, otherwise 9.5 × 6.25 2
L/150. The Manual for the design of timber building Mu = = = 46.4kN/ m
8 8
structures to EC5, however, notes that these deflection
ratios are there to limit the curvature, rather than the
›
Part 2
44 TheStructuralEngineer Technical
November 2014 Material properties
Table 3: I values and relative beam depths for secondary steel beam Table 4: I values and relative beam depths for primary steel beam
For a fully restrained condition Zp = M/f, where f = 275N/mm2, for The f1 value of 6.11Hz confirms that this floor is adequate for use in a
grade S275 steel (t<16mm): gym, as it is greater than the required minimum natural frequency of 5Hz.
Table 3 shows that if the structural design is to respect the vibration
46.4 × 10 3 criteria, the amount of steel required is double that required solely to
= = 169cm 3 meet the strength criteria, resulting in a 100% increase in material costs.
275 Similarly, meeting the deflection criteria would result in a 50% cost
For an IPN 180 beam, Zp = 187cm3. increase compared with the strength criteria alone.
Ignoring vibration effects, the deflection of the steel beam is to be Respecting the vibration criteria will create a stiffer grillage. As
limited to span/δ = 360. the steel joist is supported on the main steel girder, this increases
the slope of the steel joist at its end, which in turn exacerbates the
3
= = 2.23 × 6.36 × 6.25 3 = 3462cm 4 deflection of the secondary joist member. A prudent design would add
half the deflection of the main beam to the calculated deflection of the
joist when verifying that its deflection does not exceed the specified
For an IPE 0 240 beam, I = 3892cm4. limits under a UDL9.
To limit vibration effects, the Manual for the design of steelwork
building structures to EC35 recommends a total allowable deflection of Design of primary steel beam B2 with a 7.5m effective span
10mm for dance floors and gyms, with the natural frequency at least 5Hz. The edge loading is to consist of 12.5mm thick laminated glass,
Thus: stiffened with glass fins at 1.25m centres, with a storey height of 3.5m
and the self-weight of the beam:
span 6250
= = 625 0.0125m × 25 kN / m3 × 3.5m + 0.75 kN /m = 1.84kN/m
10
The beam loading is calculated as:
625
= 1.24 × = 3.88
200 6.25m
9.50 kN/m ×
2
+ 1.84 kN/m × 1.35 = 26.23 kN/m (ULS)
1.25m
where C = 1.24 for span/δ = 200 (Table 1).
6.25m
= 3
= 3.88 × 6.36 × 6.253 = 6024cm 4 6.36 kN/ m ×
1.25m
2
+ 1.84 kN/ m = 17.74kN/m (SLS)
where δ is the maximum deflection due to the applied load and self- 184.43 × 10 3
weight in mm. For IPE 0 270: = = 696 cm 3
265
6024
= 10mm × = 8.67mm For an IPE A 330 beam, Zp = 702cm3.
6947 Ignoring vibration effects, the deflection of the steel beam is to be
limited to span/δ = 360 where C = 2.23 (Table 1):
Therefore:
3
= = 2.23 × 17.74 × 7.5 3 = 16 689cm 4
18
1 = 1 = 6.11Hz
(8.67 ) 2 For an IPE 0 360 beam, I = 16 270cm4.
The vibration effect in a gym can be limited by limiting the total
deflection to within 10mm. Thus:
www.thestructuralengineer.org
45
26.23
9.38 0.1913 N
79
46 TheStructuralEngineer Technical
December 2014 Material properties
Material properties:
effect on deflection, rotation
and vibration – Part 3
Denis H. Camilleri Eur Ing, A&CE, BSc (Eng), BA (Arch), CEng, ACIArb, FIStructE, FICE
Managing Partner, dhiPERITI
Introduction the downstand of the steel beam is removed to create valuable stor-
This article is the third in a three-part series outlining the serviceability age height.
hand calculations to be undertaken in the preliminary structural design For the storage of heavy metal, assuming a storey height of 5m, the
stage. live load (LL) on the floor slabs is:
47
PAJARI, 1997
For composite construction, the serviceability requirements entail
the calculation of the short-term, long-term and dynamic modular
ratios. For preliminary sizing, the modular ratio is to be averaged out
at 15 for imposed loads and 30 for dead loads (DLs). To calculate the
natural frequency, the modular ratio is taken as 6, while 10% of the where:
imposed load plus the DL is considered for the dynamic deflection. γs is the partial safety factor for concrete = 1.0
Rackham et al.8 note that, for internal beams in composite con-
struction, the span-to-deflection ratios will be determined by the R s = 134 # 345 # 10 -1 = 4623kN
finishes. These are to be limited to span/360 for imposed loads and 1
span/200 for total loads. For edge beams, the ratios are determined From the two respective stress blocks, it is noted that the plastic neu-
by the cladding. For glazing, these are to be limited to span/500. A tral axis falls within the base of the concrete slab.
minimum limit on natural frequency is proposed as 4 cycles/s for The moment of resistance for this composite section is given by:
most building applications, except where there is vibrating machinery,
^0.55m + 0.12m h
and 3 cycles/s for car parks. The limit may be raised to 5 cycles/s for MR = 4623kN # = 1548kN/m 2 1464kN/m
special buildings such as sport halls. 2
Hicks and Lawson9 note that, for floors subjected to pedestrian Alternative construction options to the solid slab are available. These
traffic, the fundamental frequency is to be at least 3.55 cycles/s. This include hollow-core or solid prestressed panels. If using prestressed
may be reduced to 3 cycles/s for steel-framed car parks. panels, the whole depth of the concrete panel could be used for the
concrete stress block; however, the effective width might be less than
Calculating the section of the the 2.4m adopted (it is generally less than 1.5m)5.
composite steel beam On the other hand, if profiled steel sheeting were adopted, then the
The floor load (which comprises the DL for a 120mm concrete slab overall depth of the overlying in situ concrete would not need to be used
and the storage load or LL of 20kN/m2) is calculated as: in the calculation of the concrete stress block, which could be reduced
from 120mm to 70mm. The steel decking would
also create a limitation on the placement of the
steel shear studs, while there would be less sur-
rounding concrete in the vicinity of the shear
studs, resulting in a reduced shear capacity3.
The SCI has a free composite beam checking
tool available online10, for the use of profiled steel
where the ULS load is obtained by multiplying the serviceability sheeting as decking.
limit state (SLS) load by partial safety factors defined in EC0. The deflection under total load — where span/200 and C = 1.24
The beam bending moment (BM) is calculated as: (Table 1, Part 2) — is calculated as:
48 TheStructuralEngineer Technical
December 2014 Material properties
The fundamental frequency may be calculated by first calculating the higher limit for pedestrian bridges was inspired by a baby being
the deflection given by the DL plus 10% of the imposed load: woken on a bridge by the bridge vibration.
The fundamental frequency of a vehicular bridge is quoted in the
W = (2.88 + 0.1 x 20) x 2.4m = 11.7kN/m range of 3Hz. The natural frequency of the bridge should be outside
the range of 0.5–1.5 times the fundamental frequency, to avoid intoler-
span
= 12000 = 60mm
able dynamic conditions due to resonance.
200 200 US limits on allowable LL deflection appeared in the early 1930s
when a study attempted to link the unpleasant vibrations felt on a
I = CWL3 = 1.24 # 11.7 # 12 3 = 25069cm 4 sample of bridges built during that era. The study concluded that
structures with vibrations deemed unacceptable by a subjective hu-
The actual deflection is: man response had deflections that exceeded L/800. Human reactions
to vibrations are classified as either physiological or psychological.
Psychological discomfort results from unexpected motion, but physio-
60mm # 25069 = 6mm logical discomfort, such as seasickness, results from a low-frequency,
250300
high-amplitude vibration. The limits described here produce beam-to-
where for a modular ratio of 6 SZS charts11 provide: depth ratios varying from L/15 to L/20.
I = 250 300cm4 > 184 965cm4 for an IPE 600 beam and 120mm These recommendations are consistent with the warehouse flooring
concrete slab system adopted in this example, where the span-to-depth ratio is 16.67
The fundamental frequency ft that this floor is subjected to is calcu- and the natural frequency of 7.35Hz lies outside the range of 0.5–1.5
lated by: times the fundamental frequency, so resonance does not occur.
Furthermore, the deflection limit of 1:800 allows for a rotation in ra-
ft = 18 = 7.35Hz 2 3Hz
1 dians (Equation 3, Part 1) of:
6 2
Thus, the vibration criteria are also satisfied. However, to satisfy the 3.2 = 0.004rad
strength and deflection criteria, a 15% increase in material costs has 800
to be incurred, due to an increase in section size from IPE 550 to IPE where 3.2 is the constant for a uniform distributed load (UDL), de-
600. creasing to 3 for a point load.
In addition, to satisfy the strength, deflection and vibration criteria The total rotation at the bearing may be obtained by noting that in
for this warehouse loading scenario, the span-to-depth ratio works out bridge decks the LL:DL ratio lies between approx. 0.5 (for medium
as: spans) and 1.0 (for short spans). In addition, an allowance for thermal
camber at 0.0015rad, together with a value for uncertainty taken at
12000 0.01rad, should be allowed made13. In the simple support condition, this
^600 + 120h
= 16.67
gives a total rotation in radians at the bearing of:
Once the preliminary sizing has been ascertained, the final design 0.01 (uncertainty) + 0.0015 (thermal camber) + 2 × 0.004
must be produced to conform to EC4. (traffic) = 0.02rad
Bridge decks As noted in Part 2, this is not to be considered a small rotation al-
In composite construction of bridge decks, span-to-deflection though it lies within the acceptable range 0.015–0.035rad.
ratios higher than 1:200 are advisable, although US and European
recommendations differ12. US recommendations are for the LL span- Alternative design proposal using hollow-core
to-deflection ratio not to exceed 1:800 for a vehicular bridge, or 1:1000 prestressed slab on a rigid support
for a pedestrian bridge. On the other hand, no ratio restrictions exist For the 12m effective span, a hollow-core prestressed slab with a
in European bridge specifications. It is suggested in the literature that depth of 525mm, acting compositely with a 100mm grade 30/37 con-
crete topping, provides a safe load of 23.9kN/m2 and a shear capacity
of 226.5kN/m. This exceeds the superimposed serviceable load of
22.88kN/m2, thereby satisfying the required strength criteria.
Figure 3
Effective lengths
for sway frames
The upward camber with DL only applied is 14.32mm (δ/span =
1/838).
The resulting downward deflection on application of the full load is
23.07mm (δ/span = 1/522).
The span-to-depth ratio for this scheme is 12 000/525 = 22.85.
High deflection ratios are important in precast, prestressed hol-
low slabs supported on non-rigid supports. Tests show the reduc-
tion in shear resistance to these precast slabs to be in the region of
40–77%14. This is due to the transverse deformation of the slab ends
resulting from the deflection of the supporting beam (Figure 2)15.
Deflection-to-span ratios exceeding 1:1000 are an advantage in these
situations.
This alternative proposal is therefore a workable scheme, which sat-
isfies both the strength and serviceability criteria. In choosing between
the two schemes, the high DL imposed by the prestressed solution
should be taken into account. The DL for these panels with a 12m span
is 50% of the LL, which is comparable to bridge construction. For the
composite construction scheme, the DL only approximates to 14.5% of
49
where:
2.2 # 5m = 0.367m
w is in kN/m 30
L is in m This is greater than the 0.3m noted earlier for sway limitations.
9 Strength calculations should then follow to verify the load-bearing
300 # 10
^8 # 210 # 10 7h
C= = 17.86 capacity of the wall panel.
According to the rule of thumb for the natural frequency of framed
vertical structures described in Part 2, this three-storey structure ap-
The C value of 17.86 conforms to the value quoted in Table 1. pears to have a natural frequency in the range of 2.5Hz. If compared
For a concrete cantilever section, to restrict the deflection to to vibrating table tests performed on various masonry buildings, adobe
span/300: buildings are quoted as having a forcing frequency of 6Hz, with a
six-storey masonry building having a fundamental frequency of 2Hz,
C = 17.86 # 210 = 125 increasing to 5.5Hz for a two-storey masonry building.
30
The C value of 125 conforms to the value quoted in Table 1. Conclusions and recommendations
The method described in Parts 1–3 revolves around Equation 1 in Part
15m high panel structure subjected to wind load of 1kN/m2 118, which calculates the moment of inertia I necessary for deflection
The side sway is to be limited to: criteria to be abided by. This is undertaken in a structural engineer’s
parlance, with the units given in m and kN to give I in cm4. The method
produces coefficients, meaning that it is not restricted to steelwork
Table 1: Updated deflection coefficient C for calculating moment of but can also be applied to other materials. For concrete, this method
inertia for a cantilever span condition is applicable only to establish the requirements of horizontal side
Span-to- Steel Concrete Timber sway, as vertical deflections are based on span-to-depth ratios not
deflection E = 210kN/mm2 E = 30kN/mm2 E = 8kN/mm2 deflection-to-span ratios.
ratio Parts 1–3 move from strength calculations to the SLS, while cover-
1/300 (UDL) 17.86 125 469 ing various structural materials by adopting a universal formula with
a varying constant, which depends on the material. The preliminary
1/300 (point 47.15 330 1238
design outlined with ‘back-of-the-envelope calculations’ also helps the
load)
structural designer to perform further dynamic calculations in addition
50 TheStructuralEngineer Technical
December 2014 Material properties
to the static calculations which are usually performed in the design of- structural elements’, The Structural Engineer, 89 (5), pp. 17–18
fice. The preliminary design stage now allows the rotations and vibra- 8) Rackham J. W., Couchman G. H. and Hicks S. J. (2009) SCI
tions imposed on the structure to be quantified, as it is an easy step Publication P300: Composite Slabs and Beams using Steel Decking:
to move onto rotation and vibration effects once a deflection-to-span Best Practice for Design and Construction (Revised ed.), Ascot,
ratio has been determined. At this stage, the designer and client can UK: Steel Construction Institute and Metal Cladding & Roofing
discuss the serviceability requirements gauged to be important for the Manufacturers Association
final project.
The article then examines interactions between structural materials 9) Hicks S. J. and Lawson R. M. (2003) SCI Publication P287: Design
to limit unsightly secondary failures. The outline of the characteristics of of Composite Beams Using Precast Concrete Slabs, Ascot, UK: Steel
the various structural groups of materials, which is presented in Table 2, Construction Institute
Part 1, helps to establish the values of the important design properties.
This should make it easier for the design engineer to move from one 10) SteelConstruction.info (2015) Composite Beam Checking Tool
structural material to another. Knowledge of material properties will help [Online] Available at: http://bcsatools.steel-sci.org/CompositeBeam
the structural designer to choose the appropriate structural material, (Accessed: November 2014)
based on efficiency criteria and sustainability properties, rather than
simply using the material they feel most comfortable with. 11) Swiss Metal Construction Centre (2012) C1/12 steelwork: Tables
The hand calculations presented in Equations 1–5 in Part 1, in con- de dimensionnement pour la construction mixte, Zurich, Switzerland:
junction with the BCSA deflection coefficients chart17 (Figure 2, Part 1) SZS
should help practices to design constructions that will not suffer unwar-
ranted cracking or unwelcome movement when in use, thus avoiding 12) Roeder C. W., Barth K. and Bergman A. (2002) NCHRP Web
lengthy litigation over serviceability failure. As outlined briefly in the Document 46: Improved live load deflection criteria for steel bridges
introduction to Part 1, crack width may not be the defining factor, al- [Online] Available at: www.inti.gob.ar/cirsoc/pdf/puentes_acero/
though this depends on the length, shape and density of cracks. Cracks nchrp_w46.pdf (Accessed: November 2014)
may have a negative aesthetic impact or they may need to be filled to
reduce penetration of sound and odours or the passage of fire. People 13) Camilleri D. (2011) ‘Rotation of supporting small bearing pads in
are sensitive to distinctly perceptible vibrations in an office or residential buildings’, The Structural Engineer, 89 (9), pp. 16–20
environment, but will accept vibrations approximately 10 times greater in
an active environment, such as when dining beside a dance floor or lift- 14) Pajari M. and Koukkari H. (1998) ‘Shear resistance of PHC slabs
ing weights in a gym. Finally, the age of the building also comes into the supported on beams. I: Tests’, J. Struct. Eng., 124 (9), pp. 1050–1061
equation. The older the building, the less sensitive its users are to exist-
ing cracks, deflections and vibration effects. 15) Pajari M. (1997) ‘Interaction between hollow core slabs and
On the other hand, in bridge works, no evidence of serious structural supporting beams’, IABSE Reports (Composite Construction —
damage is attributable to excessive LL deflection. Human psychological Conventional and Innovative), 999, pp. 831–836
reaction to vibration and deflection is a more significant issue than that
of structural durability. 16) Elliott K. S. (2002) Precast Concrete Structures, Oxford, UK:
Butterworth-Heinemann