Technical Specifications
Technical Specifications
Technical Specifications
TECHNICAL SPECIFICATIONS
TABLE OF CONTENTS
I. GENERAL REQUIREMENTS
II. SITE WORKS
III. CONCRETE WORKS
IV. MASONRY WORKS (Including re-bars and plastering)
V. ROOFING SYSTEM WITH ACCESSORIES
VI. CARPENTRY WORKS (Includes ceiling joist, hanger & acrylic painting)
VII. DOORS & WINDOWS (Including jambs)
VIII. TILE WORKS
IX. PLUMBING WORKS
X. ELECTRICAL WORKS
XI. PAINTING WORKS
XII. OTHER WORKS
ANNEX-A: FPA Registered Termiticides
I. GENERAL REQUIREMENTS
A. The Contractor shall conduct thorough inspection of the existing job site conditions.
B. The scope of work shall include all additions necessary in order to implement the whole set
of approved Plans, Working Drawings and Specifications.
C. The Contractor shall construct All Architectural, Structural, Electrical, Sanitary/ Plumbing,
Mechanical / Fire Protection works in accordance with the Plans and Specifications. All
items shown on the Plans but not mentioned in the Specifications shall be included.
Discrepancies shall be verified with the Procuring Entity.
D. The Contractor shall have a licensed surveyor to locate benchmarks. Shop drawings of
stake out plan and actual reference marks shall be verified and approved by the Procuring
Entity prior to any permanent construction.
E. The Contractor shall submit details and shop drawings, templates, and schedules required
for the coordination of the work of the various trades. Drawings should include information
on all working dimensions, arrangement and sectional views, connections and materials.
F. Final Cleaning As Pre-requisite To Final Acceptance: Final cleaning of the work by a
reputable building maintenance company shall be employed by the Contractor prior to the
Procuring Entity’s final inspection for certification of final acceptance.
G. The Contractor shall be responsible for the safety and safe working practices of its
respective employees, servants and agents.
H. The Procuring Entity may at any time without invalidating the Contract changes by altering,
adding to or deducting from the work as covered by the drawings, specifications, and
general scope in written instructions. Provisions under General Conditions of the contract
cover such circumstances.
2.3.1 General
2.3.2 Cement
Concrete shall be Portland cement of a brand conforming to ASTM Specification
C150, Type I or Type II. All cement shall be product of one reputable manufacturer
2.3.4 Admixtures
Coarse aggregate shall consist of washed gravel, crushed stone or rock, or a combination
thereof conforming to ASTM C33. The particle shape of the smallest size of crushed
coarse aggregate shall be generally rounded or cubical and the coarse aggregate shall be
reasonably free from flat and elongated particles. A thin, flat and elongated particle can
be defined as a particle having a maximum dimension greater than five times the
minimum dimension.
Reinforcing steel shall be locally manufactured, deformed billet steel bars conforming to
Philippine Standard, Grade 275, Intermediate Grade (30,000 psi).
2.3.8 Forms
Concrete form shall be wood, plywood, steel or other suitable materials. Form surfaces
requiring standard or special finish shall be plywood or a non-absorptive hand pressed
fiberboard or other suitable materials. Plywood shall not be less than 6mm thick and
shall be free from irregularities, dents and sags. Forms shall be coated with no staining
form coating compound such as form oil of the approved make.
Removal of forms shall be accomplished in such a manner as will prevent injury to the
concrete and will insure the complete safety of the structure. The following removal
times are the minimum and may be increased by the Engineer.
a. Where the structure as a whole is supported on shores, vertical forms for beam and
girder sides, columns and similar vertical forms may be removed twenty-four (24)
hours after completion of the pour, providing the concrete has hardened sufficiently
to sustain its own weight to prevent injury.
b. Wall forms shall not be removed in less that four (4) days after pouring.
c. Supporting forms or shoring must remain in place until the concrete can carry any
loads to be imposed upon it and in no case in less than fourteen days.
d. Form ties requiring any peroration in removal of forms which would tend to destroy
the bond between the tie and the concrete in order to remove the form shall not be
disturbed for seven (7) days after completion proper.
• Materials
Materials shall be Plexibond or Mortaflex brand or approved equivalent.
• Surface Preparation
All surfaces shall be free of dirt, dust oil, grease and other contaminants by solvent
cleaning in accordance to SSPC-SP1.
• Concrete – At least 28 days cured, voids, cracks, holes or concrete irregularities shall resurface
using grouts or mortars. Acid-etched the Surface in texture resembling coarse sandpaper,
concrete must be neutral prior to application.
•Application Equipment
Brush and Roller is acceptable.
• Mixing
Mix 6.5 to 8 kgs. Of cement to 4 liters of Plexibond or Mortaflex.
• Application Procedure
Apply 5 coats by brush or 3 coats by textured roller.
(1) Cement
Cement in bags shall be stored in a suitable weatherproof structure as airtight as
practicable. Floors shall be elevated above the ground, sufficient to prevent the
absorption of moisture. Bags shall be stocked against outside walls. The manner of
storage shall permit easy access for inspection and identification of each shipment.
Cement that has been stored for so long that there may be doubt of its quality shall
be tested by standard mortar tests to determine its suitability for use, and shall not
be used without approval of the Subproject Manager.
(2) Aggregates
Aggregate shall be stored in such a manner as to avoid the inclusion of foreign
materials. Aggregates of different sizes shall be stored in separate piles. Stockpiles of
coarse aggregate shall be built in horizontal layers not exceeding 1200mm in depth
to avoid segregation. Should the coarse aggregate become segregated, it shall be
remixed to conform to the grading requirements here on before. Sufficient stockpiles
shall be maintained at all times to permit continuous placement of concrete at the
rate specified.
(3) Reinforcing Steel
Reinforcing steel shall be stored in a manner to avoid excessive rusting or being
coated with grease, oil, dirt and other objectionable materials.
The proportion of all materials in concrete shall be subject to the approval of the
Subproject Manager. The Contractor shall employ at his own expense an approved
testing laboratory, which shall design the mix, proportions in accordance with ACI
211.01. Strength requirements shall be 20.7 Mpa (3000 psi) for footing columns, beams,
slabs, and stairs, slab on grade, water meter box; grease trap; and 13.8 Mpa (2000 psi) for
lean concrete or as required by the Subproject Manager. The adequacy of this tests shall
be verified by a test on a minimum of 6 cylinders; 3 tested at 7 days, 3 at 28 days, in
accordance with ASTM C39.
If, at any time during construction, the concrete resulting from the approved mix design
proves to be unsatisfactory for any reason such as too much water, lack of sufficient
plasticity to prevent segregation, honeycomb, etc., or insufficient strength the Contractor
shall notify the testing laboratory and the Subproject Manager. The laboratory shall
modify the design, subject to the approval of the Subproject Manager until satisfactory
concrete is obtained.
At least two (2) sets of samples consisting of three (3) concrete cylinder specimen per set
shall be made. Fresh concrete shall be placed inside standard 50 x 300 mm cylindrical
mould in three (3) separate equal layers and rodded separately with 25 strokes with a 16
mm diameter. Surface shall be leveled with trowel and samples are to be labeled to
identify the class, strength of concrete, date taken and part of structure samples are
taken. The samples shall be cured in accordance with ASTM C31.
One set of cylinders shall be tested at the age of seven (7) days and one set at the age of
twenty eight (28) days, in accordance with ASTM C39. Additional cylinder samples may
be molded in reserve for further tests, if the results of the twenty-eight (28) days test do
not meet the requirements.
b. Slump Tests
The slump for vibrated concrete shall be 50-mm minimum and 100 mm maximum,
provided that the required strength of concrete is obtained.
c. Test Reports
The testing laboratory shall submit four (4) copies of its test cylinder which are to
include as far as applicable, the following items: Location of pour in the structure,
concrete design mix number, concrete design strength, type and manufacturer of
cement, amount of any admixture used, slump tests, date of sampling, cylinder
application number, days cured in the filed, days cured in the laboratory, age at time of
testing, crushing stress, type of failure, who made the samples, who shipped the samples
to the laboratory and whether concrete strength meets the specifications.
d. Additional Tests
If, in the opinion of the Subproject Manager, based on test cylinder reports, concrete
with strengths below specification requirements has been placed, the Subproject
Manager, at the expense of the Contractor shall make additional tests. Additional test
may be compression test on cored cylinder, ASTM C42, and/or load tests as outlined in
ACI 318, Sec. 202.
b. Ready-Mixed Concrete
Ready-mixed concrete, when shall be batched, mixed and delivered from a plant
approved by the Subproject Manager, and shall be in strict compliance with the
requirements set forth in ASTM C94.
The rate of delivery of the mixed concrete shall be such that the interval between
placing of successive batches shall not exceed thirty (3) minutes. The elapsed time
between the introduction of mixing water to the cement and aggregate and
completion of discharge shall not exceed one (1) hour, or not more than 1 ½ hours if
a retarder is used. It should be kept constantly agitated during the transit period.
Delivery tickets shall contain data on the weight of sand, gravel and amount of
cement and water added. The Contractor shall keep legible copies available for
examination of the Subproject Manager.
Retempering of concrete shall not be permitted. The Contractor shall mix only
quantities required for immediate use and mixture, which has developed setting,
shall not be used. Concrete, which has partially hardened, shall not be retempered.
Concrete shall be placed only after all formworks, materials to be embedded and
preparation of surface involved in the placing have been inspected and approved
by the Subproject Manager. The Contractor shall provide equipment and shall
employ methods that will minimize separation of aggregates from the concrete
mix.
a. General
Concrete surfaces exposed to conditions causing premature drying shall be
protected as soon as possible with canvas, straw, burlap, sand or other
satisfactory material and kept moist; or if the surfaces are not covered they
shall be kept moist by flushing or sprinkling, as directed by the Subproject
Manager. All concrete shall be moist cured for a period of not less than seven
(7) consecutive days after placing by an approved method or combination of
methods applicable to local conditions.
b. Moist Cutting
The surface of the concrete shall be kept continuously wet water for a period
of seven (7) days, by spraying or by covering with burlap or other approved
material thoroughly saturated with water and keeping the covering wet by
spraying or intermittent hosing. Water for curing shall be generally lean and
free from any element, which might cause objectionable staining or
discoloration of the concrete.
All imperfections on concrete surfaces are corrected to produce concrete surfaces that
conform to the requirements of this section. Unless otherwise approved by the
Subproject Manager, patching with cement mortar shall repair imperfections on formed
surfaces. Cement mortar for patching shall be of the same composition as used in the
concrete, except for exposed surfaces; part of the cement shall be white cement to
provide a finish color matching the surrounding concrete. Honeycombed or otherwise
defective areas shall be cut out from solid concrete to a depth of not less than 25 mm.
The edges of the cut shall be perpendicular to the surface of the concrete. The area to be
patched, at least 15 mm adjacent thereto shall be saturated with water before placing the
mortar. The mortar shall be mixed approximately one (1) hour before placing and shall
be remixed occasionally during this period with a trowel without adding water. A grout
of cement and water, mixed to the consistency of paint, shall then be brushed onto the
surface to which the mortar is to be bonded. The mortar shall be compacted into place
and screened slightly higher that the surrounding surface. Patches shall be cured as
specified for the concrete. Exposed surfaces shall utilize plywood forms, after the
removal of forms, shall not be plastered, unless otherwise directed by the Subproject
Manager. All joint marks on the formwork shall be reworked to a smooth surface to
match adjacent areas and to present a new appearance.
2.4.7 Forms
(1) General
Forms shall be used whenever necessary to confine the concrete and shape it to the
required lines and dimensions, or to protect the concrete from contamination. Forms
shall have sufficient strength to withstand the pressure resulting from placement and
vibration of the concrete and shall be maintained rigidly in correct position. Forms shall
be sufficiently tight to prevent loss of mortar from the concrete. Forms for exposed
surfaces shall be lines with form grade plywood. Bolts and roods used for interval ties
shall be so arranged that when the forms are removed, they shall not less than two (2)
centimeters from the formed surface.
(1) General
Steel reinforcement shall be provided together with all necessary tie wires, chairs,
spacers, support and other necessary devices.
The subproject Manager may require the contractor to prepare and submit bar cutting
schedule prior to fabrication of reinforcing steel bars.
In all cases, the thickness of concrete over the reinforcement shall be at least equal to the
diameter of round bars and one-half times the side dimension of square bars.
Exposed reinforcement bars intended for bonding with future extensions shall be
protected from corrosion by concrete or other adequate covering.
The quantities measured as provided above shall be full compensation for furnishing
and placing all materials, labor, equipment, tools and incidentals necessary to
complete the work.
(1) Sand
Fine aggregates for plastering shall be natural sand and shall be retained between No. 50
and NO. 100 sieves
Masonry walls shall be placed level and plumb all around. One section of the walls shall
not be placed in advance of the others, unless, specifically approved. Unfinished work
shall be stepped back for joining with new work; tooting shall not be permitted. Heights
of masonry shall be checked with an instrument at sills and heads of openings to
maintain the level of the walls. Door and window frames, louvered openings, anchors,
pipes, and conduits shall be installed in carefully and neatly as the masonry work
progresses. Spaces around doorframes shall be filled solidly with mortar. Drilling,
cutting, fitting and patching, to accommodate the work of others, shall be performed by
skilled workers. Bolts, anchors, inserts, plugs, ties and miscellaneous metal work
specified elsewhere shall be placed in position as the work progress. Chases of approved
dimension for pipes and other purposes shall be provided, where indicated or
necessary. Top of exposed walls and partitions, not being worked on, shall be covered
with a waterproof membrane, well secured in place. Walls and partitions shall be
structurally bonded or anchored to each and to concrete wall beams and columns.
Mortar materials shall be measured in approved containers to insure that the specified
proportions of materials are controlled and accurately maintained during the progress of
the work. Unless specified otherwise, mortar shall be mixed in proportions by volume.
The aggregates shall be introduced and mixed in such a manner that the materials will
be distributed uniformly throughout the mass. A sufficient amount of water shall be
added gradually and the mass further mixed, not less than 3 minutes, until a mortar of
the plasticity required for the purpose intended shall be obtained. The mortar shall be
mixed in a manner such that the quality of water can be controlled accurately and
uniformly. Mortar boxes, pans of mixing drums shall be kept clean and free of debris of
dried mortar. The mortar shall be used before the initial setting of the cement has taken
place; retempering of mortar in which cement has started to set shall not be permitted.
Fine grout shall be used in grout spaces less than 50 mm in any horizontal dimension or
when clearance between reinforcement and masonry unit is less than 17 mm. Coarse
grout shall be used in grout spaces more than 50 mm in all horizontal dimensions or
where clearance between the reinforcement and masonry is more than 17 mm.
Mortar joint shall be uniform in thickness and the average thickness of any three
consecutive joints shall be 9.50 mm. “Gage rods” shall be made and approved prior to
starting the work and shall be used throughout the work. Changes in coursing or
bonding after the work has started shall no be permitted. The jointer shall be slightly
larger than the width of the joints, so that complete contact is made along the edge of the
units, compressing and sealing the surface of the joint. Joints in masonry, which will not
be exposed, shall be struck flush. Joints shall be brushed to remove all loose and excess
mortar. All horizontal joints shall be on level and vertical joints shall be plumbed and
aligned from the top to the bottom of the wall with a tolerance of plus or minus 12 mm.
The first coarse of concrete masonry unit shall be laid in full bed of mortar, for the full
width of the unit; the succeeding courses shall be laid with broken joints. Concrete
masonry units with the cells verticals shall have bed-joints formed by applying the
mortar to the entire top surfaces of the entire top surfaces of the inner and outer face
shell, and the head joints formed by applying the mortar of a width of about 25 mm to
the ends of the adjoining units laid previously. The mortar for joints shall be smooth, not
furrowed, and shall be of such thickness that it will be forced out of joints as the units
are being placed in position. Where anchors, bolts, ties and reinforcing bars occur within
the cell of the units, such cells shall be solidly filled with mortar or grout as the work
progresses.
3.4.7 Reinforcement
Unless otherwise shown on the drawings, the size and spacing of bars shall be as
follows:
Masonry walls and partitions shall be accurately anchored or bonded at points where
they intersect and where they about or adjoin the concrete frame of the building. All
anchors shall be completely embedded in mortar.
Grout shall be performed on the interior side of wall, except as approved otherwise,
Sills, ledges, offsets and other surfaces to be left exposed shall be protected form grout
falling on such surfaces and be and shall be removed immediately. Grout shall be stirred
before placing to avoid segregation of the aggregate and shall be sufficiently fluid to
flow into joints and around the reinforcement without leaving any voids. Grout shall be
placed by pumping or pouring from buckets equipped with spouts, in lifts not
exceeding 1.2 meters high. Grout shall be puddle thoroughly to eliminate voids without
displacing the masonry units from its original position. Masonry units displaced by the
grouting operation shall be removed and relayed to its proper alignment using fresh
mortar grout.
(1) General
The work consists of furnishing all materials, labor and performing all operations in
connection with plastering masonry wall surfaces, complete in every respect as shown in
the drawings and as specified herein. Plastering work shall be coordinated properly
with the work of other trades. The work of other trade shall be protected properly from
being damaged during plastering operations. Scaffolding shall be amply strong, well
braced, tied securely and inspected regularly. Overloading of scaffolding shall not be
permitted.
Portland cement plaster shall be a two-coat application, the base and the finish coat.
Each coat shall be proportioned as follows: One part by volume of Portland, to three
parts sand. Hydrated lime may be used as directed by the Consultant.
Surface to receive plaster must be free from structural defects and shall be thoroughly
dampened prior to application of plaster.
Plaster base coats shall be applied with sufficient pressure and the plaster shall be
sufficiently plastic to provide good bond on masonry base. The base coat shall be
compacted and straightened to a true surface without the application of water and the
entire surface shall be floated to receive the finish coat. The finish coat shall be applied to
a thickness approximately 3 mm before the scratch coat has set. Maximum pressure
shall be applied in order to compact the finish coat and to provide smooth finish free
from blemishes or irregularities. Trawling shall be continued until the finish surface sets.
Immediately after setting, the surfaces shall be scoured vigorously with clean burlap or
cement bag paper or brush to remove the sheen finish produced by trawling.
Plaster work shall be finished level, plumb, square and true, within a tolerance of 3mm
in 3 meters without waves, blisters, pits, crazing, discoloration, projections or other
imperfections. Plasterwork shall be formed carefully around angles and contours, and
well up to screens. Special care shall be taken to prevent consequent dropping of
applications. There must be no visible junction marks where one day’s work adjoins
another. Finished work shall be protected in an approved manner to prevent damage.
Upon completion of the work, all loose, cracked, damaged or defective plastering shall
be cut and replastered in a satisfactory and approved manner. All pointing and patching
of plastered surfaces and where plastering abuts or adjoins any other finished works
shall be done in a neat and workmanship manner ready to receive pain or other finish.
Dump curing shall begin as soon as the mortar has hardened sufficiently to prevent
injury and water applied in a fog spray to keep the plaster damp throughout soaking.
The period for damp curing shall be as specified for each coat. Protect the plaster from
uneven and excessive evaporation during hot or drying weather conditions.
(8) Cleaning
After the completion of plastering work, all scaffolding surplus materials, debris and
plaster daubs and stains on floors, windows and other surface shall be removed to the
satisfaction and approval of the Subproject Manager.
In measuring the quantity of masonry units for payments, the dimensions to be used shall be as
shown on the plans or as directed by the Subproject Manager in writing. Projections extended
beyond the faces of the wall shall not be included. The area to be paid for under this section
shall be the number of square meters of concrete masonry wall including plastering and
partition placed and accepted in accordance with the plans and specifications. Payment of
accomplished work shall be deemed to include the cost of mortar grout, reinforcing steel, tie
wires, false work and other necessary works to complete this item.
The quantity of concrete masonry wall with plastering and partition shall be paid for at the
contract unit price shown in the bid schedule, which payment shall be full compensation for
furnishing and placing all materials, labor, equipment, tools and incidentals necessary to
complete the work.
The work includes the furnishing, fabrication, erection or installation of structural steel roof
framing and miscellaneous metal work in accordance with this specification and as shown in
the drawings.
This section also includes the furnishing of all plant, tools, equipment, materials and other in
the installation of waterproofing and roofing, including miscellaneous sheet metal works as
required providing a waterproof installation.
Screw and expansion bolts shall be of standard commercial grade, and of sizes and types
indicated as approved by the Subproject Manager.
4.3.5 Electrodes
4.3.6 Galvanizing
4.4.1 General
Fabrication and erection of structural steel shall be in accordance with AISC specification
for the design, fabrication and erection of structural steel for buildings, except as
specified herein. The Contractor shall submit to the Subproject Manager for approval
shop drawings showing the proposed method of fabrication and installation of all metal
work. No work shall started until the shop drawings have been approved and all work
shall conform to the approved shop drawings.
The work shall be well formed at the shape and size shown and assembled as detailed.
Structural members shall be fabricated and assembled in the shop to the greatest extent
possible. Shearing and punching shall be produced in clean, true lines and surfaces with
burrs removes. Nuts shall be drawn up tight. Joints, which ate to be exposed to the
weather, shall be watertight. Hole shall be cut, drilled or punched at right angles to the
surface of the metal and shall be made or enlarged by burning. Holes in base or bearing
plates shall be drilled.
(1) Welding
Structural steel shall be welded in accordance with the standard code of Are and Gas
Welding in Building Construction of the AWS. Qualified welders shall perform all
welding work only.
4.4.3 Erection
The steel structure shall be erected true to line and grades. Bracings and support shall be
introduced whenever necessary to take care of all the loads to which the structure may
be subjected. Such bracings shall be left in place as may be required for safety. As
erection progresses, the work shall be securely bolted to take care of all the dead loads,
wind and erection stresses. No reaming of undersize bolt holes shall be permitted and
erection bolts shall not be used for lining up members.
(5) Setting Up
Steel shall be erected plumb, level and properly guyed. In setting or erecting structural
steel, the individual piece shall be considered plumb or level where the error does not
exceed 1 to 500.
(6) Inspection
The Contractor shall give the Subproject Manager at least fifteen (15) days notice prior to
the start of work at the mill or shop, so that the required inspection may be made. The
term “mill” means any rolling mil, shop or foundry where material for the work is to be
manufactured or fabricated. No materials shall be rolled or fabricated until said
inspection has been provided.
The Contractor shall furnish the Subproject Manager with copies of the certificate mill
reports of the structural steel structure preferably before but not later than the delivery
of steel structure to the job site.
The Contractor shall furnish all facilities for inspection and the Subproject Manager shall
be given free access to the mill or shop and premises at all times. The Contractor shall
furnish without charge all labor, machinery, materials and tools necessary to prepare
test specimens.
Inspection at the mill or ship is intended as a means of facilitating the work and
avoiding errors. It is expressly understood that it will not relieve the Contractor from
any responsibility for imperfect materials or workmanship and the necessity for
replacing the same. The acceptance of any materials or finished member at the mill or
shop by the Subproject Manager shall be preclude their subsequent rejections if found
defective before final acceptance of the work. Inspection of welding works will be in
accordance with the provision of Section 5 of the “Standard Code for Arc and Gas
Welding in Building Construction” of the AWS.
(1) General
Except as specified otherwise herein, all materials shall be installed in accordance with
the manufacturer’s printed erection instructions. Care shall be exercised in storing,
handling and installing to prevent any damage to roofing sheets. The sheets shall be of
the length indicated or the greatest length to suit the purlins spacing. End laps of roofing
shall be located over purlins. Extreme care shall be exercised in drilling, pilot holes for
fattening to keep drills perpendicularly center valleys or crowns as applicable. After
drilling, all melt fillings and burrs shall be removed from holes prior to installing
fasteners and washers. Sheets deformed or otherwise damaged by over-torque
fastenings, shall be removed and new sheets be installed. Size and spacing, of fasteners
used in erection shall be as recommended by manufacturer subject to the approval of the
consultant. All metal shaving shall be swept from roofs upon completion to prevent
rusting and discoloration. Prior to the installation of roofing, purlins should have been
placed and spaced properly to fit the length of roofing sheets to be used.
2. The quantity for roofing sheets and heat insulator to be paid for shall be the number of
square meters completed and accepted. Payment of this item shall be deemed to include
the cost fasteners, gutter, ridge roll, fascia, flashing, accessories and other works
necessary to complete this work item.
The quantity determined as provided above shall be paid for the contract price for each
for the pay item listed in the bid schedule, which price and payment shall be full
compensation for furnishing and placing all materials, labor, equipment, tools and
incidentals necessary to complete the work.
5. CARPENTRY WORKS
5.1 Scope of Work
These sections include all rough and finish carpentry, aluminum works and joinery
works, as shown in the drawings and in accordance with this specification. (Acoustic
board for interior and hardiflex for exterior ceiling). All specifications of acoustic board ceiling is
specified in the drawing.
5.2 Material Requirements
5.2.1 Lumber
All number shall be in accordance with the accepted commercial standard and shall be
of the approved quality of each kind and shall be of the following spaces and grades as
shown in the drawings:
(2) Substitutions
Any lumber equally for the purpose may be substituted for the kinds specified,
provided that the substitution shall be acceptable to the Subproject Manager.
5.2.2 Hardiflex
Ceiling shall be 6-mm thk hardiflex nailed with galvanize or zinc coated common nail.
5.3.2 Fasteners
Fasteners shall be of the type and size best suited for the purpose as shown in the
drawing, fasteners shall be galvanized or zinc coated, regular commercial size as
indicated and shall conform to ASTM specification A307.
6.0 DOORS & WINDOWS (Includes ceiling joists, hanger and acrylic painting)
(3) Lumber
Lumber for doors shall be commercial grade, of the approved equity of each kind, well
seasoned, thoroughly dry, and free from loose or unsound knots, shakes, pitch, pockets
or other imperfections affecting its strength, durability or appearance.
(a) Door frames in contact with concrete shall be nil, good grade of the design size and
thickness as indicated in the drawings. Application of black coal tar between contact
surfaces shall be provided.
(b) Door studs, nailed and frames shall be nil, S4S and kiln dried with not more than
fourteen percent (14%) moisture content.
(4) Plywood
Plywood for interior flush doors shall be nil, first class and of commercial standard.
Doors with surfaces receive paint or stain finish may be furnished factory primed, and
doors with natural finish may be furnished factory pre-finished. Final furnishing shall be
done in site in accordance with painting and varnishing specifications.
(2) Hinges
Hollow Core Flush type Doors, PVC Doors shall be provided with three (3) butt hinges
(100mm x 100mm loose pin, Brass type). Solid Wood Panel shall be provided with four
(4) butt hinges (100mm x 100mm loose pin, Brass Type). For Aluminum frame Doors,
use hinges specified by manufacturer’s standard.
(2) The quantities accomplished for each type of window shall be paid in square meters
of area and/or number of units completed and accepted for each item of work. Payment
for these items shall be considered to include the cost of steel frames, glass panels, finish
hardware and glazing and incidental works.
The accepted quantities measured as stipulated above, shall be paid for at the contract
unit price for each item, which price and payment shall be full compensation for
furnishing and placing all materials, labor, equipment, tools and incidentals necessary to
complete the work described on this Section.
WINDOWS
(2) The quantities accomplished for each type of window shall be paid in square meters
of area and/or number of units completed and accepted for each item of work. Payment
for these items shall be considered to include the cost of steel frames, glass panels, finish
hardware and glazing and incidental works.
The accepted quantities measured as stipulated above, shall be paid for at the contract
unit price for each item, which price and payment shall be full compensation for
furnishing and placing all materials, labor, equipment, tools and incidentals necessary to
complete the work described on this Section.
7.0 TILEWORKS
(1) General
This work includes plain cement finish with or without red cement, and plain cement
finish as bed for tiles, including all labor, materials, equipment and other facility to
complete the work in accordance with the plans and specifications.
Screened Rough, free from ridges and holes Slab and concrete surfaces
under earth fill
(a) Surfaces exposed to public view shall be smooth form finished. No plastering work
shall be done on exposed surfaces to correct imperfections. Form facing materials
shall be used to produce a smooth, hard and uniform texture on the concrete. Tie
holes and defects shall be patched and all fins shall be completely removed.
(b) Surfaces not exposed to public view shall be rough form finished. Tie holes and
defects be patched and fins exceeding 6 mm in height shall be chipped off or rubbed
off.
(c) Finishing of formed surfaces shall be accomplished after removal and repair of
surface defects.
(1) General
The work consist of furnishing all materials, labor and performing all operations in
connection with tile finishing of floors and walls, complete including mortar beds for the
tile. Tile work shall not be started on portions where embedded lines crossed – over the
area until roughing-ins for plumbing and electrical work has been completed and tested.
The work of all other trades in the areas where the work is to be done shall be protected
from damage in a workmanship manner as directed by the Subproject Manager.
(5) Jointing
Joints shall be parallel and uniform in width, plumb and level and in alignment. End
joints in broken-joint shall be made, as far as practicable, on the centerline of the
adjoining tiles. Joint widths shall be uniform and measured to accommodate the tiles
in the given spaces with a minimum cutting.
(6) Grouting
Grouting shall be done as soon as the mortar beds have sufficiently set. All cement
shall be Portland cement, colored or white, as required. Where light colored mortar
is required in joints, mixture of white cement and non-fading mineral oxide shall be
used to produce the desired colors. The quantity of mineral oxides shall not exceed
10% of the volume of cement in any case.
(7) Cleaning
Upon completion of grouting, the tile shall be thoroughly cleaned and maintained in
this condition in this condition until completion of the contract.
B. Valves for water supply shall be PVC with threaded ends. All valves are gate valves
unless otherwise specified. Gate valves shall have solid wedge body and discs
conforming to specification requirements.
The Contractor before any installation work is started shall carefully examine the Plans and
shall investigate actual structural and finishing work condition affecting all this work. Where
actual condition necessitates a rearrangement of the approved pipe layout, the Contractor shall
prepare Plan(s) of the proposed pipe layout for approval by the Subproject Manager.
A. Horizontal lines shall be secured strongly by hooks to the building frame ands
suitable brackets or chairs shall be provided at the floor from which they start.
B. Vent pipes in roof spaces shall be run as closes possible to under side of roof with
horizontal piping pitched down to stacks without forming traps. Vertical cent pipes
may be connected into one main vent riser above the highest vented fixtures.
C. Where an end or circuit vent pipe from any fixtures is connected to a vent line
serving other fixtures, the connection shall be at least 1.20m above the floor on which
the fixtures are located.
D. Horizontal waste line receiving the discharge from two or more fixtures shall be
provided with end vents unless separate venting of fixtures is noted on the Plans.
E. All changes in pie sizes on soil and waste lines shall be made with reducing fittings
or recessed reducers. All changes in directions shall be made by appropriate use of
45 degrees, wyes, half wyes, quarter bends or elbows may be used in waste lines
where the change in direction of flow is the horizontal to the vertical and on the
discharge from waste closets. Where it becomes necessary to use short radius fittings
in other locations the approval of the Subproject Manager shall be obtained prior to
installation of the same.
F. Vent pipe shall be flashed and made watertight at the roof with ferrule lead.
Flashing shall be turned down into pipes.
C. Drain Cocks
1. Pipe drain indicated on the drawing shall consist of 12-mm globe valve with
renewable disc and installed at low points on the cold water piping so that all piping
shall slope 100 in 30.5m.
8.7 Disinfections
A. The entire water distribution system shall be thoroughly flushed and treated with
chlorine before it is operated for public use.
B. ids-infection materials shall be liquid chlorine or hydrochloride and shall be
introduced in a manner approved as practice or potable water.
C. Valves for the water distribution system shall be opened and closed several times
during the 16 hours chlorinating treatment is done.
The work done under Construction of septic tank, holding tank and water storage tank
(including reservoir and piping) shall be considered to include the cost of excavation
and backfilling, bedding, forms and false work, curing, fasteners and incidentals to
complete each item of work.
SPECIFICATION DIGEST
a. Wires and Cables THW, THHN, Copper Wires, Phelps
Dodge, American Wires & Cables or
approved equivalent
1. Furnishing and installation of service entrance and all items as per policies, rules and in
regulations.
2. Furnishing and installation of Panel boards at location indicated in the plan.
3. Furnishing and installation of feeder and branch circuit conductors with necessary
conduits and fittings.
4. Furnishing and installation of all types of utilization devices, outlets and wall switches
5. Furnishing and installation of conduit rough-in, service entrance ducts, terminal
cabinets, boxes and outlets.
6. Furnishing and installation of all lighting fixtures, both for interior and exterior.
7. Reinstallation and rewiring of all existing lighting fixtures, both for interior and exterior,
portions affected by the construction.
8. Furnishing and installation of all items as stated or specified and shown elsewhere in
these specifications and plans.
The installation of the equipment shall conform to good engineering practice and in particular,
comply with the requirements laid down in the following documents or its equivalent, which
are mandatory and modified only be specific agreement.
In addition to the requirements of the codes and specifications referred to above, local
regulations and supplier’s specifications, if any, shall be followed.
Any apparent conflict between the Drawings and Specifications and any controversial or
unclear points in either shall be referred to the Electrical Engineer in Charge for final decision.
On the plans, keep records showing all deviations occurring during construction. At the
completion of the work, said copy of the plans shall be submitted to the LGU for its copy and
file.
Upon completion of work as described herein the Contractor shall furnish the Owner, at his
own expense, Five (5) copies of the “AS BUILT” plans for future reference and maintenance
purposes.
9.5 CORRELATION OF WORK
The Electrical Contractor shall coordinate with the General Contractor and the LGU/Owner to
determine how and where his work fits with that of other crafts, after familiarizing himself with
the plans and specifications. This shall be done at the beginning of construction. Should there be
any existing doubt at any point, a ruling shall be secured from the LGU/Owner and shall be
given time to inspect the work covering this point and to prepare a detail in the form of
Drawing and written instructions as required.
The Contractor shall obtain, at his own expense, all the necessary permits and Certificate of
Electrical Inspection from the proper government authorities required both for the performance
of his work involved and the operation of the system upon completion of work.
The Contractor shall, at his own expense, reproduce the electrical plans for his work to the
necessary scale and complete them with the necessary information and requirements as
required by the Government approving authorities concerned in issuing permits and Certificate
of Electrical Inspection.
Electrical System layout, indicated on the drawings is generally diagrammatic and locations of
outlets, devices, apparatus and equipment are approximate.
The exact routing of conduits, locations of outlets, devices, apparatus and equipment shall be
governed by structural and architectural conditions and limitations.
Consult the LGU/Owner for exact locations. This is not to be construed to permit redesigning
of system; all outlets are to be interconnected as indicated in the drawings.
Locate and install equipment-requiring maintenance where it will be readily accessible. Any
equipment located without the approval of the LGU or Owner shall be done at the risk of the
Contractor.
The Owner reserves the right to make any reasonable changes in locations of outlets and
equipment prior to roughing-in without involving additional expense.
The Contractor shall be held responsible and pay charges for cutting and patching for piping
where sleeves or slots were not installed or where incorrectly located.
All materials to be installed, brand new and shall conform to the applicable standards.
Only skilled workmen using proper tools and equipment shall be employed during the entire
course of installation work. All workmanship shall be of the best quality and all work shall be
done in accordance with the best practices of the trade involved.
The same job foremen shall be assigned and maintained at the job site during the entire course
of the job.
The Electrical Contractor shall furnish and install the 220-volt, 3-phase, 2-wire service entrance
connection for the proposed building. The service entrance conductors and raceway shall be
thermoplastic and Rigid Steel Conduit, respectively. Sizes are indicated on the plan and
electrical riser diagram.
Circuit breakers shall be molded case with trip mechanism with ratings and number of poles as
indicated in the drawings. It shall be standard factory products of reputable electrical
manufacturer, and shall be of the flush type. The rigidity and gauge of steel is to be as specified
in UL Standard for Cabinets.
Panel boards to be used shall be flush mounted when located in areas that are visible to the
general public.
All panel boards shall be set plumb and symmetrical with surrounding objects. Panel boards
shall be installed in a perfectly fit cabinet of appropriate size provided with a stop-in-door trim
and good quality locks. Provide Cardholder on inside of the door with clear plastic cover and
complete type written schedule of panel branch circuits. Leave spare circuits blank for future
load.
Conduit shall enter knockouts of conduit boxes and cabinets squarely. Locknuts and bushing
shall be used at termination of conduit in outlet boxes, pull boxes and panel board. Install
approved couplings and unions to provide electrically continuous and moisture tight systems.
Bonds and offsets shall be avoided where possible but where necessary they shall be made with
approved hickory or conduit bending apparatus. The use of pipe tool or vise for bending shall
not be permitted. Conduits, which have been deformed or crushed in any manner, shall not be
installed. The contractor shall plug with lead or closed with approved pipe caps to ends of all
conduits, which are to be left empty within the conduit boxes so as to prevent the entrance of
white ants and dirt within the conduit systems. This lead shall be so placed that it can be easily
removed when so desired and at the same time serve the purpose of which it is intended. Full
wires shall be inserted in the empty ducts before they are closed with lead and caps and shall be
left therein for future use.
Wiring for all system shall be PVC or RSC conduits using type “THW OR THHN Conductors.
Minimum sizes of conduits to be used shall be ½” diameter. Size larger than ½” mm diameter
shall be indicated in the drawing. Smallest size of conductor to be used shall be 3.5mm2. dia.
Type “THHN or THW” unless otherwise indicated in the plans. Circuit homeruns for lighting
shall be 3.5mm2 and No. 3.5 mm2 for power or otherwise indicated on the plan.
All splices, tape and junctions for all system using conductors shall be accomplished by using
electrical friction or rubber tapes to provide proper insulation and protection for 600 volts.
Wall switches intended to control lights on the 240-volt system shall be rated 10amp.,
250 VAC. HD receptacles shall be 20A, 2-pole, 250 VAC.
The Contractor shall furnish and install all ground cables, connections, ground rods and
all other materials required to provide a permanent and effective grounding system for
the complete project. Grounding, in general shall conform to the provisions of the
Philippine Electrical Code and as recommended by the equipment manufacturer.
All enclosures for electrical regardless of voltage, shall be grounded, including metal
frames of switchboard, motors, generators and steel poles. Each shall be grounded in a
separate.
Manual Station
Stations shall be Pull-Lever or push button type. Switch ratings shall be a minimum of 3
amperes at 120 VAC. Flush mounted station shall mount on a 2” x 4”” Utility box that
will also serve as splicing box.
Fire Alarm Bells
Fire Alarm Bells shall be installed and provided with 4” x 4” junction box at the location
shown on the plans. Bells shall be non-contact vibration 6” diameter, undertone type,
250V.
Smoke Detector
The Electrical Contractor shall provide and install smoke detectors, wiring and
connection flow switches as shown in the Plan.
Fire Extinguishers
Furnish and install two (2) units of fire extinguishers, stallion brand or approved
equivalent, 10 lbs., mounted at 1.2m high at locations specified by the Subproject
Manager, one (1) unit at the first floor and one (1) unit at the second floor.
Wherever hereafter the word “Approval” or “Approved” (make, type, size, arrangement, etc.)
are used specifically with regard to manufactured items, etc., or wherever its is desired to
substitute a different make or type, all information pertinent to the adequacy and adaptability
of the proposed apparatus, shall be submitted to the Electrical Engineers for their approval
before the apparatus, shall be submitted to the Electrical Engineers for their approval before the
apparatus is ordered or installed.
9.17 WARRANTY
All fixture components shall be covered with a warranty for a period of one year against failure
resulting from normal use and/or factory defects.
The quantities to be paid for under each item shall be measured by the number of items
completed to the satisfaction of the Subproject Manager and shall be paid for at the contract unit
price shown in the bid schedule, which payment shall be full compensation for furnishing and
placing all materials, labor, equipment, tools and incidentals necessary to complete each work
item.
10.1 Painting
(1) General
The work covered by this section consists of furnishing all labor, equipment, tools and
materials in performing all operations in connection with painting and finishing,
including protective coating of metal surfaces, complete in accordance with the
specifications and the applicable drawings.
The Subproject Manager shall in accordance with the color schemes shown in the
drawings or as direct all colors.
Sample panels of selected colors, as least (1) meter square in area shall be prepared for
approval by the Subproject Manager prior to application.
(3) Workmanship
Skilled workers shall do all work in a workmanlike manner. Paints shall be evenly
applied and free from sags, runs, crawls and other defect. All coats shall be of proper
consistency and well brushed out or rolled on so as to show a minimum brush or rolled
marks. Brushes or rollers shall be clean and in good condition.
All coats shall be thoroughly dry before the succeeding coat is applied. Allow at least
twenty-four (24) hours or more between applications of coat. For exterior painting
during rainy season, allow one (1) week drying before the succeeding coat is applied.
Painting coats as specified are intended to cover surfaces perfectly., if surfaces are not
fully covered, further coats shall be applied to attain the desired evenness of the paint
application. All finishes shall be uniform as to sheen, color and texture. Paint may be
applied by spray method, except when, in the opinion of the spraying in any particular
application would produce unsatisfactory results. The Contractor shall provide all drop
cloths and other covering requisite to the protection of floors and other work.
Each surface shall be inspected carefully before applying any finish; and if surface is not
in proper condition, the Subproject Manager shall be notified to that effect in writing.
Otherwise the Contractor shall be held responsible for any defects in the finishes arising
there from. Should a coat of paint be applied to a certain area and defect such as large
cracks, hollow spots or unevenness in plastering are discovered, such defects shall be
knocked out and re-plastered by the Contractor and repainted to the satisfaction of the
Subproject Manager.
The Contractor shall inspect all surfaces to be painted and all defects shall be remedied
before starting the work. No work shall be started unless the Contractor shall have made
certain the dryness of the surfaces. Test shall be made, in the presence of the Subproject
Manager, to verify the dryness of surfaces to be painted.
Before applying paint, concrete and cement surfaces shall be allowed to dry thoroughly.
Clean surfaces of all dirt, alkali and grease before commencing work. Treat all surfaces
with a solution of two (2) kilos of zinc sulfate to four (4) liters of water and sufficient
phenolphthalein to act as color warning. Presence of alkali is indicated when
phenolphthalein turn red and further treatment is required to neutralize it. Allow the
surface to dry at least three (3) days and remove and loose crystals from the surface
before finishing.
(b) Finishing:
For exterior and interior concrete surfaces and all other surface with cement plaster
finish, use flat concrete paint with the specified brand approved by the Subproject
Manager.
First Coat-Apply flat concrete paint thinned with ½ liter water per 4 liters of paint; tint
with latex tinting color to closely match color of topcoat or use premixed paint. Dry for 3
to 6 hours.
Intermediate Coat- Repair all minor surface imperfection with paint putty made by
mixing paint with patching compound powder. Let it dry for 24 hours, and then
smoothen the surface with sandpaper, before applying the intermediate coat.
Final Coat- Apply semi-gloss or gloss paint tinted with latex tinting color to the shade
specified.
Plane the surface of wood with sandpaper to remove roughness, loose edges, slivers,
slingers, then clean to remove dust. All frames in contact with concrete or plaster shall
be treated with an anti-termite solution or solution or equivalent before applying paints.
Set nail heads into the wood, fill holes, cracks and defects. Dry for three (3) hours and
clean surface with sandpaper to smoothen the surface.
(b) Finishing:
For all woodwork, use gloss latex house paint with the specified brand approved by the
Subproject Manager.
First Coat- Apply paint thinned with ½ liter water per 4 liters of paint.
Second Coat – Apply latex paint thinned with latex tinning colors to the shade specified.
Dry for 4 to 6 hours.
The accepted quantities measured as stipulated above shall be paid for at the contract unit price
shown in the bid schedule, which payment shall be full compensation for furnishing and
placing all materials, labor, equipment, tools and incidental necessary to complete each work
item.
11.o OTHER WORKS (Ground Floor Railing, Mirror, Perimeter Fence, Tinsmithry Work, Painting
Work, Concrete Walkway, Driveway Pavement, Burial Pit)
Stair and ramp railings shall be 75mm diameter Stainless Steel Pipe with 50mm
diameter Stainless Steel Pipe horizontal and vertical support, properly welded and
anchored to reinforcement of stair and ramp slab. Wall handrails shall be 50mm
diameter Stainless Steel Pipe with 25mm G.I. pipe support, properly welded and
anchored to reinforcement of wall.
The quantity to be paid for railings or handrails shall be in the number of units placed
and accepted. Payment shall be construed to include the cost of false work, anchors and
other materials used in mounting this item.
11.2 MIRROR
11.1.3. Materials
The facial mirror shall be installed inside the toilet above the lavatory or as shown on
plan. It shall be one-sided clear glass, 3/16mm thick with size as shown on the plan. It
shall be cladded or screwed on four corners or as instructed by the Subproject Manager.
The quantity to be paid for facial mirrors shall be per units or sets, placed and accepted.
Payment shall be construed to include the cost of false work, anchors and other
materials used in mounting this item.
Scope of Work
The work includes of concrete fence structures complete in accordance with the standard
specifications and in conformity with the lines, grades, thickness and typical cross-
section on the plan.
Material Requirement
General
Cement
Water
Water shall be lean and free from injurious amounts of oils, acids, alkali, salts,
organic materials, or other substances that may be deleterious to concrete or steel. The
Contractor shall provide adequate for mixing and a constant pressure supply system to
the mixer.
Admixtures
In addition to the grading limits shown above, the fine aggregates, as delivered to the
mixer, shall have a fineness modulus of not less than 2.3 more than 3.0 and during
normal operations, the grading of the fine aggregate shall be controlled so that the
fineness modulus of at least nine (9) out of ten (10) test samples of fine aggregate as
delivered to the mixer shall not vary by more than 0.20m from the average fineness
modulus can be determined by dividing by 100 the sum of the cumulative percentages
retained on U.S. Standard Sieves No. 4,8,16,50 & 100.
Coarse Aggregate
Coarse aggregate shall consist of washed gravel, crushed stone or rock, or a combination
thereof conforming to ASTM C33. The coarse aggregate, as delivered to the batching
plant, shall have uniform and stable moisture content. The approval of deposits and the
be construed as constituting the approval of all materials taken from the deposits, and
the Contractor shall be held responsible for the specified quality of all such materials
used in the work. Coarse aggregate shall consist of hard, tough, durable, clean and
uncoated particles. All foreign materials and dust shall be removed by adequate
processing. The particle shape of the smallest size of crushed coarse aggregate shall be
generally rounded or cubical, and the coarse aggregate shall be reasonably free from flat
and elongated particles. A thin, flat and elongated particle can be defined as a particle
having a maximum dimension greater than five times the minimum dimension. The
coarse aggregate shall be graded from fine too coarse. It shall be separated into size
groups.
The grading of the aggregate within the separated size groups as delivered to the mixer
shall be as follows:
Sieve Sizes Percent by Weight Passing Individual 1-1/2
Std(MM) U.S. Std. Sq. Mesh ¾ Size Size
50 2” 100
37.5 1-1/2” 90-100
25 1” 100 20-55
19 ¾” 90-100 0-15
9.5 3/8” 20-55 0-5
4.75 No. 4 0-10
Use 19-mm (3/4”) coarse aggregate for slab on grade, columns, beams, suspended slabs,
and tie beams
Reinforcing Steel
Reinforcing steel shall be locally manufactured, deformed billet steel bars conforming to
Philippine Standard, Grade 275, Intermediate Grade (30,000 psi).
Forms
Concrete from shall be wood, plywood, steel or other suitable materials. Form surfaces
requiring standard or special finish shall be plywood or a non-absorptive hand pressed
fiberboard or other suitable materials. Plywood shall not be less than 6mm thick and
shall be free from irregularities, dents and sags. Forms shall be located with no staining
form coating compound such as form oil of the approved make.
Removal of forms shall be accomplished in such a manner as will prevent injury to the
concrete and will insure the complete safety of the structure. The following removal
times are the minimum, and may be increased by the Engineer.
e. Where the structure as a whole is supported on shores, vertical forms for beam and
girder sides, columns and similar vertical forms may be removed twenty-four (24)
hours after completion of the pour, providing the concrete has hardened
sufficiently to sustain its own weight to prevent injury.
f. Wall forms shall not be removed in less than four (4) days after pouring.
g. Supporting forms or shoring must remain in place until the concrete can carry any
loads to be imposed upon it and in no case in less than fourteen days.
h. Form ties requiring the tie and the concrete in order to remove the form shall not be
disturbed for seven (7) days after completion proper.
Storage of Materials
(4) Cement
Cement in bags shall be stored in a suitable weatherproof structure as airtight as
practicable. Floors shall be elevated above the ground, sufficient to prevent the
absorption of moisture. Bags shall be stocked close together to reduce circulation of air
but shall not be stocked against outside walls. The manner of storage shall permit easy
access for inspection and identification of each shipment. Cement that has been stored
for so long that there may be doubt of its quality shall be tested by standard mortar tests
to determine its suitability for use, and shall not be used without approval of the
Subproject Manager.
(5) Aggregates
Aggregate shall be stored in such a manner as to avoid the inclusion of foreign materials.
Aggregates of different sizes shall be stored in separate piles. Stockpiles of coarse
aggregate shall be built in horizontal layers not exceeding 1200mm in depth to avoid
segregation. Should the coarse aggregate become segregated, it shall be remixed to
conform to the grading requirements here on before. Sufficient stockpiles shall be
maintained at all times to permit continuous placement of concrete at the rate specified.
Reinforcing steel shall be stored in a manner to avoid excessive rusting or being coated
with grease, oil, dirt and other objectionable materials.
Construction Requirements
Concrete Proportion
The proportion of all materials in concrete shall be subject to the approval of the
Subproject Manager. The Contractor shall employ at his own expense an approved
testing laboratory, which shall design the mix, proportions in accordance with ACI
211.01. Strength requirements shall be 20.7 Mpa (3000 psi) for footing, columns, beams,
slabs and stairs, suspended ramp, lavatory counter, wash basin; 17.2 Mpa (2500 psi) for
ramp on fill, slab on grade, water meter box; grease trap and 13.8 Mpa (2000 psi) for lean
concrete or as required by the Subproject Manager. The adequacy of this test shall be
verified by a test on a minimum of 6 cylinders; 3 tested at 7 days, 3 at 28 days, in
accordance with ASTM C39.
Sampling and testing concrete shall be done by and at the expense of the Contractor.
Throughout the period that the concrete is being poured into the forms and while
spading operation are being done, sets of test samples in cylinder shall be taken from
fresh concrete from the forms.
The test shall be made for each 10 cu.m. of concrete of fraction thereof for each portion of
structure as may be required by the Subproject Manager as follows:
c. Compression Tests:
At least two (2) sets of samples consisting of three – (3) concrete cylinder specimen per
set shall be made. Fresh concrete shall be placed inside standard 150 x 300 mm
cylindrical mould in three (3) separate equal layers and rodded separately with 25
strokes with a 16 mm diameter. Surface shall be leveled with trowel and samples are to
be labeled to identify the class, strength of concrete, date taken and part of structure
samples are taken. The samples shall be cured in accordance with ASTM C31.
One set of cylinders shall be tested at the age of seven (7) days, and one set at the age of
twenty eight (28) days, in accordance with ASTM C39. Additional cylinder samples may
be molded in reserve for further tests, if the results of the twenty-eight (28)-day-test do
not meet the requirements.
d. Slump Tests
Freshly mixed concrete shall be placed in the slump cone 100 x 200 mm x 300mm in
three (3) equal layers. Each layer shall be rodded with 25 strokes of the 16-mm diameters
tamping rod with the tamping end rounded to a hemispherical tip of the same diameter.
The mould shall be leveled and lifted at once and then measure the slump action
immediately by getting the difference in height of the mould and the top of the slumped
concrete.
The slump for vibrated concrete shall be 50-mm minimum and 100 mm maximum,
provided that the required strength of concrete is obtained.
c. Test Reports
The testing laboratory shall submit four (4) copies of its test cylinder which are to
include as far as applicable, the following items: Location of pour in the structure,
concrete design mix number, concrete design strength, type and manufacturer of
cement, amount of any admixture used, slump tests, date of sampling, cylinder
application number, days cured in the field, days cured in the laboratory, age at time of
testing, crushing stress, type failure, who made the samples, who shipped the samples to
the laboratory and whether concrete strength meets the specifications.
d. Additional Tests
If, in the opinion of the Subproject Manager, based on test cylinder reports, concrete
with strengths below specification requirements has been placed, the Subproject
Manager, at the expense of the Contractor shall make additional tests. Additional test
may be compression test on cored cylinder, ASTM C42 and/or load tests as outlined in
ACI 318, Sec. 202.
Mixing Concrete
Mixing shall be thoroughly mixed in a mixer of an approved size and type to insure a
uniform distribution of the materials throughout the mass:
b. Site Mixed Concrete
All structural concrete shall be machine-mixed for at least 1 ½ minutes after all materials
including water are in the mixing drum. The time elapse between the introduction of the
mixing water to the cement and aggregate and placing of the concrete in final position
shall not exceed 45 minutes. Placing of material in the mixer shall be done in such a way
that the first batch of concrete materials in the mixer shall contain sufficient excess of
cement, sand and water to coat the inside of the drum without reducing the cement
content of the mix to be discharged. The retempering of concrete, placing additional
cement, aggregate or water during mixing period shall not be permitted.
The rate of delivery of the mixed concrete shall be such that the interval between placing
of successive batches shall not exceed thirty (30) minutes. The elapsed time between the
introduction of mixing water top the cement and aggregate and completion of discharge
shall not exceed one (1) hour, or not more than 1 ½ hours if a retarder is used. It should
be kept constantly agitated during the transit period. Delivery tickets shall contain data
on the weight of sand, gravel and amount of cement and water added. The Contractor
shall keep legible copies available for examination of the Subproject Manager.
Retempering of concrete shall not be permitted. The Contractor shall mix only quantities
required for immediate use and mixture, which has developed setting, shall not be used.
Concrete, which has partially hardened, shall not be retempered.
Concrete Placing
Concrete shall be placed only after all formworks, materials to be embedded, and
preparation of surface involved in the placing have been inspected and approved by the
Subproject Manager. The Contractor shall provide equipment and shall employ methods
that will minimize separation of aggregates from the concrete mix.
Water shall be removed from excavation before concrete is deposited. Flow of water
shall be diverted through proper side drains to a pump, or to be removed by other
approved methods to avoid washing over freshly deposited concrete. Hardened
concrete, debris and foreign materials shall be removed from the interior of forms and
from inner surfaces of mixing and conveying equipment. Reinforcements shall be
secured in position, inspected and approved before pouring concrete. Runaways shall
not be provided for wheeled concrete0handling equipment’s, such equipments shall not
be wheeled over reinforcement nor shall runaways be supported by reinforcement.
Concrete shall be handled from the mixer to the place of final deposit as rapidly as
practicable by methods, which shall prevent the segregation or loss of the ingredient. It
shall be deposited in the forms in approximately horizontal layers and as nearly as
practicable in its final position to avoid rehandling.
Conveying or handling of concrete by the use of long inclined chutes or pipes of more
than three (3) meters shall not be permitted. Dumping of concrete into buggies, buckets
or wheelbarrows with a free fall of more than one (1) meter shall not be permitted. When
placing operations would involve dropping concrete more than 1 ½ meters, it shall be
deposited through a sheet metal or other approved conveyor. As for practicability, the
conveyor shall be kept full of concrete during placing and their lower ends shall be kept
buried in the newly placed concrete. After the initial set of concrete, the forms shall not
be jarred and no strain shall be placed on the ends of the reinforcing bar, which are
being projected.
c. General
d. Moist Cutting
All imperfections on concrete surfaces are corrected to produce concrete surfaces that
conform to the requirements of this section. Unless otherwise approved by the
Subproject Manager, patching with cement mortar shall repair imperfections on formed
surfaces.
Cement mortar for patching shall be of the same composition as used in the concrete,
except for exposed surfaces; part of the cement shall be white cement to provide a finish
color matching the surrounding concrete. Honeycombed or otherwise defective areas
shall be cut out from solid concrete to a depth of not less than 25 mm. The edges of the
cut shall be perpendicular to the surface of the concrete. The area to be patched, at least
15 mm adjacent thereto shall be saturated with water before placing the mortar. The
mortar shall be mixed approximately one (1) hour before placing and shall be remixed
occasionally during this period with a trowel, without adding water. A grout of cement
and water, mixed to the consistency of paint, shall then be brushed onto the surface to
which the mortar is to be bonded. The mortar shall be compacted into place and
screened slightly higher than the surrounding surface. Patches on exposed surfaces shall
be finished to match the adjoining surfaces, after they have set for an hour or more.
Patches shall be cured as specified for the concrete. Exposed surfaces shall utilize
plywood forms, after the removal of forms, shall not be plastered, unless otherwise
directed by the Subproject Manager. All joint on the formwork shall be reworked to a
smooth surface to match adjacent areas and to present a new appearance.
Forms
4) General
Forms shall be used whenever necessary to confine the concrete and shape it to the
required lines and dimensions, or to protect the concrete from contamination. Forms
shall have sufficient strength to withstand the pressure resulting from placement and
vibration of the concrete, and to shall be maintained rigidly in correct position. Forms
shall be sufficiently tight to prevent loss of mortar from the concrete. Forms for exposed
surfaces shall be lines with form grade plywood. Bolts and roods used for interval ties
and shall be so arranged that when the forms are removed, they shall not be less than
two (2) centimeters from the formed surface.
Before placing concrete, the contact surfaces, the forms shall be cleaned of incrustations
of mortar, grout, or other foreign material. Forms shall, be coated with standard from oil
that can effectively prevent sticking and will not stain the concrete surfaces.
6) Removal of Forms
Forms shall be removed in a manner, which shall prevent damage to concrete structures.
Forms shall not be removed without prior approval of the Subproject Manager. Any
repairs of surface imperfections shall be performed at once and curing shall be started as
soon as the surface is sufficiently hard to permit it without further damage. The
minimum time period for removal of forms shall be govern where it exceeds the
minimum specified curing period. Where the formwork for one element supports the
formwork for another element, the greater time period shall apply to both elements.
Forms shall not be removed before the expiration of the minimum time specified below:
Reinforcing Steel
4) General
Steel reinforcement shall be provide together with all necessary tie wires, chairs, spacers,
support and other necessary devices.
The Subproject Manager may require the contractor to prepare and submit bar cutting
schedule prior to fabrication of reinforcing steel bars.
6) Placing of Reinforcement
Reinforcing steel shall be accurately placed in accordance with approved detailed
reinforcement drawings and shall be adequately secured against displacement by using
specified tie wires or approved clips at all intersections. After it has been installed,
reinforcing steels shall be inspected by the Subproject Manager for compliance with
requirements as to size, shape, length, splicing, position and number. Reinforcing steel
shall be supported by concrete or metal supports, spacers or metals hangers, except for
surfaces exposed to the ground or to the weather, where supports shall be concrete.
Wooden support spreaders shall not be used. At surfaces where an attractive
appearance is required, the supports shall be of type, which shall not cause subsequent
staining or marring of the exposed surface.
Joints in Concrete
3) Construction Joints
Construction joints shall be provided where indicated in the drawing or as directed by
the Subproject Manager. Joints not indicated on drawings shall be constructed and
located as not to impair the strength of the structures. When a construction joint is to be
made, the surface of the hardened concrete shall be thoroughly cleaned and all laitance
removed. In addition, the joint shall be thoroughly wetted and sloshed with a coat
cement grout immediately prior to placing of new concrete.
Concrete Protection
Unless otherwise noted, the thickness of concrete over reinforcement shall be as follows:
In all cases, the thickness of concrete over the reinforcement shall be at least equal to the
diameter of round bars and one-half times the side dimension of square bars.
Exposed reinforcement bars intended for bonding with future extensions shall be
protected from corrosion by concrete or other adequate covering.
C. The volume to be paid for under this item shall be the number of cubic meters of
concrete placed and accepted. Payment for concrete shall be construed to include the
cost of reinforcements, forms, false works, curing, fasteners and accessories
necessary to complete this item of work.
D. The quantities for reinforcing steel to be paid for shall be deemed to be included in
the final quantity of concrete placed and accepted in the completed structure. No
allowance will be given for tie wires separators, wire chairs and other materials used
in fastening the reinforcing steel in place. No measurement for payment shall be
made for splices added by the Contractor for his convenience. Payment for the
accepted quantities shall be deemed to include the cost of tie wires, separators, wire,
supports, hangers, chairs and other materials necessary to complete the work.
The quantities measured as provided above shall be paid for at the contract price for
each of the pay item, which price and payment shall be full compensation for furnishing
and placing all materials, labor, equipment, tools and incidentals necessary to complete
the work.
Scope of Work
The work includes furnishing and placing of concrete masonry units in conformity with
the lines, grades and cross-sections shown on the drawings and in accordance with the
specifications.
Applicable Documents
The latest edition of the following specifications and standards shall form part of this
specification to the extent required by the references thereto.
Material Requirements
Construction Requirements
Workmanship
Masonry walls shall be placed level and plumb all around. One section of the walls shall
be not placed in advance of the others, unless specifically approved. Unfinished work
shall be stepped back for joining with new work; tooting shall not be permitted. Heights
of masonry shall be checked with an instrument at sills and heads of openings to
maintain the level of the walls. Door and window frames, louvered openings, anchors,
pipes and conduits shall be installed in carefully and neatly as the masonry work
progresses. Spaces and around doorframes shall be filled solidly with mortar. Drilling,
cutting fitting and patching, to accommodate the work of others, shall be performed by
skilled workers. Bolts, anchors, inserts, plugs, ties and miscellaneous metal work
specified elsewhere shall be placed in position as the work progress. Chases of approved
dimensions for pipes and partitions, not being worked on, shall be covered with a
waterproof membrane, well secured in place. Walls and partitions shall be structurally
bonded or anchored to each and to concrete wall beams, and columns.
Mortar Mixing
Mortar materials shall be measured in approved containers to insure that the specified
proportions of materials are controlled and accurately maintained during the progress of
the work. Unless specified otherwise, mortar shall be mixed in proportions by volume.
The aggregates shall be introduced and mixed in such a manner that the materials will
be distributed uniformly throughout the mass. A sufficient amount of water shall be
added gradually and the mass further mixed, not less than 3 minutes, until a mortar of
the plasticity required for the purpose intended shall be obtained. The mortar shall be
mixed in a manner such that the quality of water can be controlled accurately and
uniformly. Mortar boxes, plans of mixing drums shall be kept clean and free of debris or
dried mortar. The mortar shall be used before the initial setting of the cement has taken
place; retempering of mortar in which cement has started to set shall not be permitted.
Mortar Joints
Mortar joint shall be uniform in thickness and the average thickness of any three
consecutive joints shall be 9.50mm. “Gage rods” shall be made and approved prior to
starting the work and shall be used throughout the work. Changes in coursing or
bonding after the work has started shall no be permitted. The jointer shall be slightly
larger than the width of the joints, so that complete contact is made along the edge of the
units, compressing and sealing the surface of the joint. Joints masonry, which will not be
exposed, shall be struck flush. Joints shall be brushed to remove all loose and excess
mortar. All horizontal joints shall be on level and vertical joints shall be plumbed and
aligned from the top to the bottom of the wall with a tolerance of plus or minus 12 mm.
Plaster base coats shall be applied with sufficient pressure and the plaster shall be
sufficiently plastic to provide good bond on masonry base. The base coat shall be
compacted and straightened to a true surface without the application of water and the
entire surface shall be floated to receive the finish coat. The finish coat shall be applied to
a thickness approximately 3 mm before the scratch coat has set. Maximum pressure shall
be applied in order to compact the finish coat and to provide smooth finish free from
blemishes or irregularities. Trawling shall be continued until the finish surface sets.
Immediately after setting the surfaces shall be scoured vigorously with clean burlap or
cement bag paper or brush to remove the sheen finish produced by trawling.
Plaster work shall be finished level, plumb, square and true, within a tolerance of 3mm
in 3 meters without waves, blisters, pits, crazing, discoloration, projections or other
imperfections. Plasterwork shall be formed carefully around angles and contours, and
well up to screens. Special care shall be taken to prevent consequent dropping of
applications. There must be no visible junction marks where one day’s work adjoins
another. Finished work shall be protected in an approved manner to prevent damage.
In measuring the quantity of masonry units for payments, the dimensions to be used
shall be as shown on the plans or as directed by the Subproject Manager in writing.
Projections extended beyond faces of the wall shall not be included. The area to be paid
for under this section shall be the number of square meters of concrete masonry wall
including plastering and partition placed and accepted in accordance with the plans and
specifications. Payment of accomplished work shall be deemed to include the cost of
mortar grout, reinforcing steel, tie wires, false work and other necessary works to
complete this item.
The quantity of concrete masonry wall with plastering and partition shall be paid for at
the contract unit price shown in the bid schedule, which payment shall be full
compensation for furnishing and placing all materials, labor, equipment, tools and
incidentals necessary to complete the work.
ANNEX “A”
List of registered termiticides as of _______________________________
Source: Fertilizers and Pesticide Authority – Department of Agriculture (FDA-DA)