Technical Data Sheets: Air Conditioning Unit NCD 12 NCD 12

Download as pdf or txt
Download as pdf or txt
You are on page 1of 10

Technical data sheets

Agent Offer VV*** Revision no


Project HOSPITAL EL ALTO SUR sin FC con Batería de frío User Creation date 20/7/2018
Client CONSULCAD SANTA CRUZ Position UMA-V-M1 -

Air conditioning unit


NCD 12 Airfl. supply air [m³/h] 14182 [m³/s] 3.94 external pressure supply [Pa] 300
NCD 12 Airfl. exhaust air [m³/h] 11345 [m³/s] 3.15 external pressure exhaust [Pa] 250

Specifications

?#LONGTEXT:GENFM_DOC

Unit drawing
L2B
130x1090

TAP TAP
TAP

ODA 930x1090 610x1090

FU ETA

G4
NPA-500-4-4-IE2
290x1090
130x1090

TAP TAP
DN25
TAP

PIE

610x1090 450x1090

SUP
FU
DN25

EHA M6 F7
NPL-500-2-7.5-IE2

L2A

Transport Type CONTAINER LxHxD 1200x257x229 cm Max


CONSTRUCTION FEATURES
Material profiles Aluminium material guides galvanized steel
panel thickness 50.0 mm Material Corners Plastic PVC
Material external panel galvanized prepainted+foil 0.6 insulation type Polyurethane 45 kg/m3
Color RAL9002 bottom insulation type Polyurethane 45 kg/m3
mat. panel inside galvanized steel 0.60 mm Unit base frame galvanized steel
material bottom sh. inside galvanized steel 0.60 mm roof No
Draining Panel No Packing Yes PACK2

Aermec - - Bevilacqua (VR) - - - -


User: Aermec Date 18/6/2018 mod. date 20/7/2018 Revision Date
Program version Aercalc vers. P1_19-D07- 10/05/2018 Page 1 / 10
Technical data sheets

Agent Offer VV*** Revision no


Project HOSPITAL EL ALTO SUR sin FC con Batería de frío User Creation date 20/7/2018
Client CONSULCAD SANTA CRUZ Position UMA-V-M1 -

Information according to Regulation 1253/2014 EU1253/2014 compliance (ERP2018) No


Unit type NRVU - BVU specific fan power internal [W/(m3/s)] 862
internal leakage rate at 200 Pa [%] 0.10 Fan Efficiency for UVU with no filters U1/U2 [%] 53.33 / 53.33
Filter energy classification On request If applicable

air density [kg/m³] 0.74 Mixing ratio (RCA/SUP) [%]


specific fan power [W/(m3/s)] 2,759
Designed outdoor temperature winter [°C] -5.00
ECC Energy efficiency class 2016 C air velocity supply / exhaust [m/s] 1.97 / 1.58
Energy label class designed for wet conditions The fan system effect is taken into account in the fan performances

energy recovery class (EN 13053) H1


Supply air Velocity class V3 Exhaust air Velocity class V1
Power class P3 Power class P2

Leakage class -400 Pa / +400 Pa L1 / L1 Thermal transmittance T2


Mechanical strength D1 Thermal break TB2
Data available on the Eurovent's site referring to the casing ATPGP

Aermec - - Bevilacqua (VR) - - - -


User: Aermec Date 18/6/2018 mod. date 20/7/2018 Revision Date
Program version Aercalc vers. P1_19-D07- 10/05/2018 Page 2 / 10
Technical data sheets

Agent Offer VV*** Revision no


Project HOSPITAL EL ALTO SUR sin FC con Batería de frío User Creation date 20/7/2018
Client CONSULCAD SANTA CRUZ Position UMA-V-M1 -

VF Plug fan L1 Exhaust air Connection/Access side left/left Estimated weight [k 280.00
Fan Comefri Motor
NPA-500-4-4-IE2 0683033
Airfoil backward curved blades
Protection / Insulation class IP55 / F
Air volume [m³/h] 11,345 Density [kg/m³] 0.74 number of poles [no.] 4
Ext. pressure [Pa] 250 Nominal power [kW] 4.000
Internal Pressure [Pa] 304 Nominal speed [1/min] 1,440
Pressure tot. / stat. / dyn. / SEF [Pa] 659 / 589 / 70 / 35 Current +-5% [A] 8.23
Outlet / Inlet sound [dBA] 91.8 / 85.9 voltage / frequency / Connection 3x400 V / 50 Hz / Y/D
Fan shaft power [kW] 2.711 Efficiency +-2 [%] 86.6
total efficiency / static [%] 76.61 / 68.46 Motor efficiency class IE IE2
Speed / Max [1/m] 1,890 / 2,850 Motor protection PTC
Fan octave band sound power level [dB] working point [Hz] 65.6
63 125 250 500 1000 2000 4000 8000 maximal frequency [Hz] 74.6
Inlet [dB] 77.6 77.2 89.4 82.4 78.8 77.5 73.7 69.9 specific fan power [w/(m3/s)] 993
Outlet [dB] 88.7 81.7 90.7 87.7 87.7 83.7 79.7 76.7 K factor 259
System absorbed power (motor + inverter) [kW] 3.227
Motor powered through inverter only
( 13 ) 1 set Measuring socket MSOCKET
Removable panel with turn level Dimensions [mm] 610.0 x 1,090.0

C-connection frame - ? Material galvanized s Type RAU Dimensions [mm] 557.0 x 557.0 x 50.0

frequency inverter ABB ACH 550 efficiency [%] 97


Type ACH550-01-08A8-4+B055 - 6753876 Voltage [V] 3x400
Cabling No Current [A] 8.80 max. motor capacity [kW] 4.000 Protection IP54
For the wiring diagram please refer to the frequency inverter manual
Frequency [Hz] 50
Inverter IP54 placed outside the unit on the fan section, only if wired
Operating range: -15/+40°C Temperature, 1000m MSL Dimensions [mm] 213x449x234
F Filter L1 Exhaust air Connection/Access side left/left Estimated weight [k 48.00

Manufacturer generic brand Bag length 48.0


Type Panel filter Filter surface [m2] 3.48

Cells pcs x size 6 x 6019307 592.0 x 490.0


Medium pressure drop [Pa] 141
Clean dP / Dirty dP [Pa] 32 / 250
Airflow [m³/h] 11,345 1.81 m/s
Class ISO 16890 / EN 779:2012 / EFF. Default / G4 /
Material guides and closures galvanized steel
Quantity of dP considered for the select of fan [Pa] 141
Filter monitoring shall be provided for ErP compliance 2018

( 10 ) 1 set Measuring socket MSOCKET


Removable panel with turn level Dimensions [mm] 130.0 x 1,090.0

Aermec - - Bevilacqua (VR) - - - -


User: Aermec Date 18/6/2018 mod. date 20/7/2018 Revision Date
Program version Aercalc vers. P1_19-D07- 10/05/2018 Page 3 / 10
Technical data sheets

Agent Offer VV*** Revision no


Project HOSPITAL EL ALTO SUR sin FC con Batería de frío User Creation date 20/7/2018
Client CONSULCAD SANTA CRUZ Position UMA-V-M1 -

PTDF Plate exchanger - diagonal + filter L2 Exhaust air Connection/Access side right/right Estimated weight [k 834.00

noise calculation
sound power [dB]
Frq. Hz 63 125 250 500 1000 2000 4000 8000 Sum [dB(A)]
Inlet 77.6 77.2 89.4 82.4 78.8 77.5 73.7 69.9 85.9
Outlet 88.7 77.7 89.7 82.7 76.7 69.7 67.7 58.7 84.6
Out 82.7 72.7 79.7 75.7 75.7 70.7 51.7 41.7 79.3
sound pressure level [dB]
Frq. Hz 63 125 250 500 1000 2000 4000 8000 Sum [dB(A)] measuring point at 2 m Distance
Out 68.7 58.7 65.7 61.7 61.7 56.7 37.7 27.7 65.3

Aermec - - Bevilacqua (VR) - - - -


User: Aermec Date 18/6/2018 mod. date 20/7/2018 Revision Date
Program version Aercalc vers. P1_19-D07- 10/05/2018 Page 4 / 10
Technical data sheets

Agent Offer VV*** Revision no


Project HOSPITAL EL ALTO SUR sin FC con Batería de frío User Creation date 20/7/2018
Client CONSULCAD SANTA CRUZ Position UMA-V-M1 -

PTDF Plate exchanger - diagonal + filter L2 Supply air Connection/Access side right/right Estimated weight [k 834.00
SV-100/AS/1890 air density [kg/m³] 0.74
heating modus Cooling mode
Supply [m³/h] 14,182 Pressure drop/std [Pa] 238/109
Entering [°C] -5.00 Humidity [%] 56.8
Leaving [°C] 14.70 Humidity [%] 13.6

Exhaust [m³/h] 11,345 Pressure drop/std [Pa] 163/74


Entering [°C] 20.00 Humidity [%] 40.0
Leaving [°C] 1.90 Humidity [%] 100.0
Temperature efficiency D/W [%] 69.5 / 78.8
condense water qty. [kg/h] 20.00
Recovery capacity [kW] 58.00
Temperature efficiency (EN308) 69.50 Energy efficiency (EN13053) 72.00
energy recovery class (EN13053) H1
Freezing temperature [°C] -5.00 Max. permitted differential pressure [Pa] 1500
Max internal leakage [%] 2.3
Material frame / plates Aluminium / Aluminium Exchanger Weight [kg] 246.00

Manufacturer Camfil Bag length 98.0


Type Panel filter Filter surface [m2] 4.68
Pleated Panel 98mm - Synthetic - Water resistant cardboard
Cells pcs x size 3 x 60A9346 592.0 x 592.0
Medium pressure drop [Pa] 90
3 x 60A9345 592.0 x 287.0
Clean dP / Dirty dP [Pa] 30 / 150
Airflow [m³/h] 14,182 2.52 m/s
Class ISO 16890 / EN 779:2012 / EFF. Coarse 70% / G4 / NA
Material guides and closures galvanized steel
Quantity of dP considered for the select of fan [Pa] 90
Filter monitoring shall be provided for ErP compliance 2018

( 15 ) 1 set Measuring socket MSOCKET


Removable panel with turn level Dimensions [mm] 930.0 x 1,090.0

C-connection frame - ? Material galvanized s Type RAU Dimensions [mm] 1,890.0 x 450.0 x 50.0

C-connection frame - ? Material galvanized s Type RAU Dimensions [mm] 1,890.0 x 450.0 x 50.0

Drain pan Quality Aluminium Drain connection 1'' - 25.0 mm

Aermec - - Bevilacqua (VR) - - - -


User: Aermec Date 18/6/2018 mod. date 20/7/2018 Revision Date
Program version Aercalc vers. P1_19-D07- 10/05/2018 Page 5 / 10
Technical data sheets

Agent Offer VV*** Revision no


Project HOSPITAL EL ALTO SUR sin FC con Batería de frío User Creation date 20/7/2018
Client CONSULCAD SANTA CRUZ Position UMA-V-M1 -

F Filter L3 Supply air Connection/Access side right/right Estimated weight [k 53.00

Manufacturer generic brand Bag length 48.0


Type Compact bag filter Filter surface [m2] 60.00

Cells pcs x size 6 x 6024403 592.0 x 490.0


Medium pressure drop [Pa] 148.5
Clean dP / Dirty dP [Pa] 47 / 250
Airflow [m³/h] 14,182 2.26 m/s
Class ISO 16890 / EN 779:2012 / EFF. Default / M6 /
Material guides and closures galvanized steel
Quantity of dP considered for the select of fan [Pa] 149
Filter monitoring shall be provided for ErP compliance 2018

( 14 ) 1 set Measuring socket MSOCKET


Removable panel with turn level Dimensions [mm] 130.0 x 1,090.0

L Empty section L3 Supply air Connection/Access side right/right Estimated weight [k 44.00
fixed panel Dimensions [mm] 290.0 x 1,090.0

WTH Heating coil L3 Supply air Connection/Access side right/right Estimated weight [k 102.00
Heating coil Fluid type Water
Airflow [m³/h] 14,182 Density [kg/m³] 0.74
air velocity [m/s] 2.28 Fluid volume [l/s] 0.8400
Air in [°C] 14.70 Humidity [%] 13.6 Fluid velocity [m/s] 0.88
Air out [°C] 38.09 Humidity [%] 3.4 Fluid in - Fluid Out [°C] 70.00 - 50.00
Air press. Drop [Pa] 22 Fluid pres. Drop [kPa] 16.43
Capacity [kW] 69.00 Coil internal volume [dm3] 20.500

Materials:
Cu-Al-FeZn P40AC 2R-25T-1725A-2.5pa 5C 1" ( .11- .4- 1.5 -T6/38) Rows copper
Row [no.] 2 Fins Aluminium
Circuits [no.] 5
Fin space [mm] 2.5 Header copper
Connection in DN 25 mm - 1 " Frames galvanized steel
Connection out DN 25 mm - 1 " Material guides and closures galvanized steel

Aermec - - Bevilacqua (VR) - - - -


User: Aermec Date 18/6/2018 mod. date 20/7/2018 Revision Date
Program version Aercalc vers. P1_19-D07- 10/05/2018 Page 6 / 10
Technical data sheets

Agent Offer VV*** Revision no


Project HOSPITAL EL ALTO SUR sin FC con Batería de frío User Creation date 20/7/2018
Client CONSULCAD SANTA CRUZ Position UMA-V-M1 -

DB Steam humidifier L3 Supply air Connection/Access side right/right Estimated weight [k 199.00
FAST1232088 - 2_3437961

Humidification [kg/h] 72.00


nos. of distributors [no.] 2 nos. of units 1 max. capacity [kg/h] 88.00
Only distributor lance length [mm] 1,232.0 Operating mode
Steam type: dry saturated steam at gauge pressure [1÷4bar] Material guides and closures galvanized steel

The length of the steam pipe must not exceed 4m Operating range: +1/+40°C Temperature, 1000m MSL
Drain pan Quality Aluminium Drain connection 1'' - 25.0 mm

Drip eliminator Model SP111 Frame galvanized steel Pressure drop [Pa] 11
Fins Plastic PVC

Aermec - - Bevilacqua (VR) - - - -


User: Aermec Date 18/6/2018 mod. date 20/7/2018 Revision Date
Program version Aercalc vers. P1_19-D07- 10/05/2018 Page 7 / 10
Technical data sheets

Agent Offer VV*** Revision no


Project HOSPITAL EL ALTO SUR sin FC con Batería de frío User Creation date 20/7/2018
Client CONSULCAD SANTA CRUZ Position UMA-V-M1 -

VF Plug fan L3 Supply air Connection/Access side right/right Estimated weight [k 318.00
Fan Comefri Motor
NPL-500-2-7.5-IE2 0683127
Backward curved blades
Protection / Insulation class IP55 / F
Air volume [m³/h] 14,182 Density [kg/m³] 0.74 number of poles [no.] 2
Ext. pressure [Pa] 300 Nominal power [kW] 7.500
Internal Pressure [Pa] 641 Nominal speed [1/min] 2,910
Pressure tot. / stat. / dyn. / SEF [Pa] 1,081 / 988 / 93 / 47 Current +-5% [A] 13.80
Outlet / Inlet sound [dBA] 100.3 / 97.1 voltage / frequency / Connection 3x400 V / 50 Hz / Y/D
Fan shaft power [kW] 5.946 Efficiency +-2 [%] 88.1
total efficiency / static [%] 71.52 / 65.38 Motor efficiency class IE IE2
Speed / Max [1/m] 2,647 / 2,720 Motor protection PTC
Fan octave band sound power level [dB] working point [Hz] 45.5
63 125 250 500 1000 2000 4000 8000 maximal frequency [Hz] 46.7
Inlet [dB] 84.6 87.8 96.9 94.9 89.9 89.3 87.4 83.9 specific fan power [w/(m3/s)] 1,713
Outlet [dB] 88.5 85.5 99.5 97.5 93.5 91.5 92.5 87.5 K factor 218
System absorbed power (motor + inverter) [kW] 6.958
Motor powered through inverter only
( 12 ) 1 set Measuring socket MSOCKET

(3) 1 set Frequency inverter not configured FUCONF0


Removable panel with turn level Dimensions [mm] 610.0 x 1,090.0

Opening L Fan Dimensions [mm] 557.0 x 557.0

frequency inverter ABB ACH 550 efficiency [%] 97


Type ACH550-01-015A-4+B055 - 6753878 Voltage [V] 3x400
Cabling No Current [A] 15.40 max. motor capacity [kW] 7.500 Protection IP54
For the wiring diagram please refer to the frequency inverter manual
Frequency [Hz] 50
Inverter IP54 placed outside the unit on the fan section, only if wired
Operating range: -15/+40°C Temperature, 1000m MSL Dimensions [mm] 213x549x245

Aermec - - Bevilacqua (VR) - - - -


User: Aermec Date 18/6/2018 mod. date 20/7/2018 Revision Date
Program version Aercalc vers. P1_19-D07- 10/05/2018 Page 8 / 10
Technical data sheets

Agent Offer VV*** Revision no


Project HOSPITAL EL ALTO SUR sin FC con Batería de frío User Creation date 20/7/2018
Client CONSULCAD SANTA CRUZ Position UMA-V-M1 -

F Filter L4 Supply air Connection/Access side right/right Estimated weight [k 257.00

Manufacturer Camfil Thickness 600.0


Type Vertical Synthetic bag filter Filter surface [m2] 20.40
Bag Filter Std F7 600 mm - Synthetic - Galvanised steel
Cells pcs x size 3 x 60A9915 592.0 x 287.0
Medium pressure drop [Pa] 130.5
3 x 60A9917 592.0 x 592.0
Clean dP / Dirty dP [Pa] 61 / 200
Airflow [m³/h] 14,182 2.52 m/s
Class ISO 16890 / EN 779:2012 / EFF. ePM1 50% / F7 / C
system of filter handling Dirty air widthdrawal
Quantity of dP considered for the select of fan [Pa] 131
Filter monitoring shall be provided for ErP compliance 2018
Material guides and closures galvanized steel

( 11 ) 1 set Measuring socket MSOCKET


Removable panel with turn level Dimensions [mm] 450.0 x 1,090.0

C-connection frame - ? Material galvanized s Type RAU Dimensions [mm] 1,890.0 x 450.0 x 50.0

noise calculation
sound power [dB]
Frq. Hz 63 125 250 500 1000 2000 4000 8000 Sum [dB(A)]
Inlet 84.6 81.8 92.9 84.9 72.9 67.3 67.4 61.9 86.6
Outlet 88.5 83.5 97.5 94.5 89.5 85.5 80.5 74.5 95.6
Out 82.5 78.8 88.5 85.5 81.5 78.5 64.5 52.5 87.1
sound pressure level [dB]
Frq. Hz 63 125 250 500 1000 2000 4000 8000 Sum [dB(A)] measuring point at 2 m Distance
Out 68.5 64.8 74.5 71.5 67.5 64.5 50.5 38.5 73.1

Baseframe Z120 Material galvanized steel isolated No


Height [mm] 120.0 Welded No

(5) 1 set Grounding

(6) 1 set Transportable in container CONTAINER

(1) 1 set PACK2 - Base packaging (Nylon) PACK2

(2) 1 Pcs Maintenance manual ENG NCD CENTR-NCD-ENG

Delivery sections
**
no. Extra Del.Sect. * Width [mm] Height [mm] Length [mm] Estimated weight [kgGross dim. for transport LxHxD [mm]

1 1,214.0 1,164.0 2,014.0 328.00 1264x1284x2014


2 1 2,014.0 2,328.0 2,014.0 834.00 2114x2568x2124
3 3,102.0 1,164.0 2,014.0 716.00 3102x1404x2124

Aermec - - Bevilacqua (VR) - - - -


User: Aermec Date 18/6/2018 mod. date 20/7/2018 Revision Date
Program version Aercalc vers. P1_19-D07- 10/05/2018 Page 9 / 10
Technical data sheets

Agent Offer VV*** Revision no


Project HOSPITAL EL ALTO SUR sin FC con Batería de frío User Creation date 20/7/2018
Client CONSULCAD SANTA CRUZ Position UMA-V-M1 -

4 1,182.0 1,164.0 2,014.0 257.00 1232x1404x2014


* Number of additional delivery sections for the heat recovery assembly (height too high)
** Including dampers, packaging, roof, brackets and sticking out elements

Giordano Riello International Group SpA partecipates in the Eurovent programme


for Air Handling Units.

Check ongoing validity of certificate: www.eurovent-certification.com or


www.certiflash.com. AERMEC SpA is a brand name of Giordano Riello International
Group SpA.

Aermec - - Bevilacqua (VR) - - - -


User: Aermec Date 18/6/2018 mod. date 20/7/2018 Revision Date
Program version Aercalc vers. P1_19-D07- 10/05/2018 Page 10 / 10