The MESH Control Network Hardware Instructions For S-Series Switches

Download as pdf or txt
Download as pdf or txt
You are on page 1of 66

Foxboro Evo™

Process Automation System


The MESH Control Network
Hardware Instructions
for S-Series Switches
(P0973KD/P0973KK/P0973LN)

*B0700CE* *C*

B0700CE

Rev C
January 24, 2014
Invensys, Foxboro, I/A Series, and Invensys logo are trademarks of Invensys plc, its subsidiaries, and affiliates.
All other brand names may be trademarks of their respective owners.

Copyright 2012–2014 Invensys Systems, Inc.


All rights reserved

SOFTWARE LICENSE AND COPYRIGHT INFORMATION


Before using the Invensys Systems, Inc. supplied software supported by this documentation, you
should read and understand the following information concerning copyrighted software.
1. The license provisions in the software license for your system govern your obligations
and usage rights to the software described in this documentation. If any portion of
those license provisions is violated, Invensys Systems, Inc. will no longer provide you
with support services and assumes no further responsibilities for your system or its
operation.
2. All software issued by Invensys Systems, Inc. and copies of the software that you are
specifically permitted to make, are protected in accordance with Federal copyright
laws. It is illegal to make copies of any software media provided to you by
Invensys Systems, Inc. for any purpose other than those purposes mentioned in the
software license.
Contents
Figures..................................................................................................................................... v

Tables.................................................................................................................................... vii

Preface.................................................................................................................................... ix
Purpose .................................................................................................................................... ix
Audience .................................................................................................................................. ix
Revision Information ............................................................................................................... ix
Reference Documents .............................................................................................................. ix
Terms and Definitions .............................................................................................................. x

1. Introduction ...................................................................................................................... 1
S-series Chassis Switches ........................................................................................................... 1
SSA Chassis Managed Switch (P0973KK/LN) ..................................................................... 1
Visual Indicators .............................................................................................................. 2
Auto-Ranging Power Supplies ......................................................................................... 3
Power Supply Replacement ............................................................................................. 3
Chassis Cooling System ................................................................................................... 3
Switch/Uplink Modules .................................................................................................. 4
S4 Chassis Managed Switch (P0973KD) .............................................................................. 5
Visual Indicators .............................................................................................................. 6
Auto-Ranging Power Supplies ......................................................................................... 6
Power Supply Replacement ............................................................................................. 7
Chassis Cooling System ................................................................................................... 7
Switch/Uplink Modules .................................................................................................. 9
Media Converter ................................................................................................................ 10
Switch Management ................................................................................................................ 10

2. Site Planning ................................................................................................................... 11


S-series Chassis Switch Features and Capabilities .................................................................... 11
SSA Chassis Switch (P0973KK/LN) ................................................................................... 11
Site Installation Guidelines for SSA Chassis Switch (P0973KK/LN) ............................. 11
Desktop Installation ...................................................................................................... 12
Rack Mounting the SSA Switch in a Four-Post Rack ..................................................... 12
Rack Mounting the SSA Switch in a Two-Post Rack (18 Cm (7 In) Posts) ................... 15
Rack Mounting the SSA Switch in a Two-Post Rack (7.6 Cm (3 In) Posts) .................. 18
Securing the SSA Switch to the Rear of the Rails ........................................................... 19
SSA Chassis Managed Switch Power Supply Specifications ............................................ 20
S4 Chassis Switch (P0973KD) ........................................................................................... 20
Site Installation Guidelines for S4 Chassis Switch (P0973KD) ...................................... 21

iii
B0700CE – Rev C Contents

Switch and Fiber Cable Budget and Loss ................................................................................. 23


Fiber Cable Budget Cable and Loss .................................................................................... 23
Fiber Optic Budgets for S-Series Chassis Switch Modules .................................................. 23
S-series Chassis Switch Network Cabling ................................................................................ 27
Connector Types for S-series Chassis Switches ................................................................... 27
Overview of S-Series Capabilities ............................................................................................ 28
P0973KG, P0973KG Rev. B, or P0973LP S4 S-series Network I/O Fabric Module .......... 28
P0973KF S4 S-series Network I/O Module ....................................................................... 29
Network Option Module (P0973KH) ............................................................................... 29
Port LEDs .......................................................................................................................... 30
I/O Fabric Module and I/O Module LEDs ........................................................................ 31
SSA Chassis Managed Switch (P0973KK/LN) System LEDs ............................................. 34

3. Installation ...................................................................................................................... 37
Installing S-series Chassis Switches .......................................................................................... 37
Ethernet Switch Installation ............................................................................................... 37
Installing Optional ISL Uplink Modules ....................................................................... 37
Installing Optional Redundant Power Supplies ............................................................. 37
Configuring the Switches ............................................................................................... 38
Connecting The MESH Control Network Components ......................................................... 38

4. Switch Configuration ...................................................................................................... 39


Configuring Ethernet Switches ................................................................................................ 39
The MESH Network Switch Configurator Application Software (SCAS) .......................... 39
Command Line Interface (CLI) Entries .............................................................................. 39
Logging In .......................................................................................................................... 39
Configuration Requirements .............................................................................................. 40
Connecting Ethernet Switch to the PC ................................................................................... 41
Generic Switch Parameters ...................................................................................................... 43
Edge Switches ......................................................................................................................... 44
Configuring the S-series Chassis Switches ............................................................................... 44
Resetting Password .................................................................................................................. 44
Maintenance ........................................................................................................................... 46

Appendix A. Ethernet Switch Interconnection Diagrams .................................................... 47

Index .................................................................................................................................... 51

iv
Figures
1-1. SSA Chassis Managed Switch (P0973KK) ..................................................................... 1
1-2. SSA Chassis Managed Switch (P0973LN) ..................................................................... 2
1-3. S-Series (for P0973KK) SSA Chassis Managed Switch Power Supply (P0973KL) ......... 3
1-4. S-Series (for P0973LN) SSA Chassis Managed Switch Power Supply (P0973LQ) ......... 3
1-5. S4 Chassis Managed Switch (P0973KD) ....................................................................... 5
1-6. S-Series S4 Chassis Managed Switch Power Supply ....................................................... 7
1-7. S4 Chassis Managed Switch Removable Fan Tray (P0973KT) ...................................... 8
2-1. Attaching Rails from SSA Rail Kit to Rack Posts ......................................................... 13
2-2. Securing the SSA Switch to the Four-Post Rack .......................................................... 14
2-3. Removing the Rail Extensions from the Rails .............................................................. 15
2-4. Attaching the Mounting Brackets to the Rails (Left Rail Example) .............................. 16
2-5. Positioning and Attaching the Rails to the 18 cm (7 in) Posts ..................................... 17
2-6. Installation Positions in a Two-Post Rack (7.6 cm (3 in) Posts) .................................. 18
2-7. Screw to Remove If You Plan to Secure the Left Rear of the SSA Switch ..................... 19
2-8. Securing the Rear of the SSA Switch (Four-Post Rack Example) ................................. 19
2-9. Fiber Uplink Mini-GBIC Module’s with LC Connector
(P0972WT, P0972WU, P0972YQ, and P0973FT) .................................................... 24
2-10. Fiber Uplink (ISL) Mini-GBIC Modules with Simplex LC Connector
1000Base-BX (P0973JB and P0973JC) ....................................................................... 24
2-11. P0973KG S-Series Network I/O Fabric Module ......................................................... 28
2-12. P0973KG, Rev. B, S-Series Network I/O Fabric Module ............................................ 29
2-13. P0973LP, S-Series Network I/O Fabric Module ......................................................... 29
2-14. P0973KF S-series Network I/O Module ..................................................................... 29
2-15. Network Option Module (NOM) (P0973KH) ........................................................... 30
2-16. Network I/O Module LEDs (P0973KF, P0973KG, P0973KH and P0973KK) .......... 30
2-17. I/O Fabric Module and I/O Module LEDs ................................................................. 32
2-18. SSA Chassis Managed Switch (P0973KK/LN) System LEDs ...................................... 34
4-1. Connecting PC to Ethernet Switches .......................................................................... 41
4-2. P0973KD Reset Password Jumper Location (P0973KG Network I/O Fabric Module
Slot 2) ......................................................................................................................... 45
4-3. P0973KK Reset Password Jumper Location ................................................................ 45
A-1. SSA Chassis Switch (P0973KK/LN) Uplink Cabling Options .................................... 48
A-2. S4 Chassis Switch (P0973KD) Uplink Cabling Options ............................................. 49

v
B0700CE – Rev C Figures

vi
Tables
1-1. SSA Chassis Managed Switch Modules/Uplink Modules .............................................. 4
1-2. S4 Chassis Managed Switch Modules/Uplink Modules ................................................. 9
2-1. SSA Chassis Managed Switch (P0973KK) Power Supply Specifications ...................... 20
2-2. SSA Chassis Managed Switch (P0973LN) Power Supply Specifications ...................... 20
2-3. SSA Chassis Managed Switch (P0973KK/LN) Environmental Specifications .............. 20
2-4. S4 Chassis Managed Switch (P0973KD) Power Supply Specifications ........................ 21
2-5. S4 Chassis Managed Switch (P0973KD) Environmental Specifications ...................... 21
2-6. Fiber Cable Power Losses ............................................................................................ 23
2-7. Fiber Optic Budgets for S-Series Chassis Switch Mini-GBIC Modules ....................... 25
2-8. Operating Range for Mini-GBIC Modules ................................................................. 26
2-9. P0972YL Mini-GBIC Module (1000Base-T) Specifications ....................................... 26
2-10. Connector Types for S-series Chassis Switches ............................................................ 27
2-11. Port LEDs for S-Series Switch Modules ...................................................................... 31
2-12. I/O Fabric Module and I/O Module System LEDs ..................................................... 33
2-13. SSA Chassis Managed Switch (P0973KK/LN) System LEDs ...................................... 34
4-1. Console Port Pinout .................................................................................................... 42
4-2. Generic Switch Configuration Parameters for V 8.1 and Later Releases ...................... 43

vii
B0700CE – Rev C Tables

viii
Preface

Purpose
This document provides general guidelines and specific requirements for installing and
configuring the S-series Chassis switches for The MESH control network. Topics include:
♦ Site Planning
♦ Installation
♦ Configuration.
This document is a supplement to The MESH Control Network Architecture Guide (B0700AZ) for
workstations connected to The MESH control network.

NOTE
The S-series Chassis switches cannot be used with the I/A Series Control Network,
for use with workstations with I/A Series® software, Version 7.x.

Audience
This book is intended for use by process engineering, operations, installation, and maintenance
personnel. They are expected to have a working knowledge of Ethernet LANs and Foxboro Evo™
Process Automation System configurations.

Revision Information
For this release of this document (B0700CE, Rev. C), the following changes were made:
Global
♦ Updated product names and references to support the release of the Foxboro Evo Pro-
cess Automation System.
♦ Updated to reflect SCAS 3.5.4 release.
♦ Changed all instances of “Mesh” to “MESH”.
Chapter 1 “Introduction”
♦ Added Figure 1-2 “SSA Chassis Managed Switch (P0973LN)” on page 2, and
Figure 1-4 “S-Series (for P0973LN) SSA Chassis Managed Switch Power Supply
(P0973LQ)” on page 3.
Chapter 2 “Site Planning”
♦ Added Figure 2-13 “P0973LP, S-Series Network I/O Fabric Module” on page 29.

Reference Documents
The following documents provide additional or related information:

ix
B0700CE – Rev C Preface

♦ The MESH Control Network Architecture Guide (B0700AZ)


♦ The MESH Control Network Operation, and Switch Installation and Configuration
Guide (B0700CA)
♦ Media Converter Installation and Configuration Guide for Control Networks (B0700CP)
♦ The MESH Control Network Architecture (PSS 21H-7C2 B4)
♦ The MESH Control Network Ethernet Equipment (PSS 21H-7C3 B4)
♦ I/A Series® System and Triconex™ Enclosures and Mounting Structures Site Planning
and Installation User’s Guide (B0700AS)
♦ System Definition: A Step-by-Step Procedure (B0193WQ)
♦ I/A Series Configuration Component (IACC) User's Guide (B0700FE).
These documents may also be available on the Global Customer Support Center web site at
http://support.ips.invensys.com. The MESH control network documents for Foxboro Evo Process
Automation Systems are available on The MESH Network Configuration Tool CD-ROM
(K0173ZU).

Terms and Definitions


10Base-T 10 Mb twisted-pair Ethernet

100Base-TX 100 Mb twisted-pair Fast Ethernet

100Base-FX 100 Mb fiber optic Fast Ethernet

1000Base-LX IEEE 802.3z specification for Gigabit Ethernet over two strands of
50/125 or 62.5/125 micron core MMF or 9/125 micron core SMF fiber
cable using long wavelength optical transmission.

1000Base-SX IEEE 802.3z specification for Gigabit Ethernet over two strands of
50/125 or 62.5/125 micron core MMF fiber cable using short wavelength
optical transmission.

1000Base-X IEEE 802.3z specification for Gigabit Ethernet using fiber cable using
short wavelength optical transmission.

1000Base-BX IEEE 802.3ab specification for Gigabit Ethernet over a single strand of
9/125 micron core SMF fiber cable. The communication over a single
strand of fiber is achieved by separating the transmission wavelength of
the two devices - transmitted data and received data are broadcasted and
received other separate wavelengths.

1000Base-ZX IEEE 802.3ab specification for Gigabit Ethernet over a single strand of
9/125 micron core SMF fiber cable using 1,550 nm wavelength to achieve
distances of at least 70 km (43.5 mi).

ANSI American National Standards Institute

x
Preface B0700CE – Rev C

Auto-Negotiation Signalling method allowing each node to select its optimum operational
mode (e.g., speed and duplex mode) based on the capabilities of the node
to which it is connected.

Backbone Another term for bus - refers to the main link that connects network
nodes. The term is often used to describe the main network connections
composing the network.

Beacon The packet type and packet on the network upon which the port disabling
is enacted.

Bi-directional The Bi-directional Gigabit Interface Converters are deployed as a pair.


GBIC (MGBIC) One of the SFP Mini-GBICs is placed at one end of a single strand of sin-
gle mode fiber (terminated with an LC UPC1 connector) and the second
at the other end of the same fiber, achieving bi-directional transmission on
a single fiber. These Mini-GBICs support the Digital Optical Monitoring
(DOM) extensions to the SFP standard.

BPP Beacon Priority Policy - A role/service that allows for the Beacon packet to
have the highest priority when propagating though the network. This
ensures the Beacon packet will be transmitted back to the PBQ in a
flooded switch.

BootP Bootstrap Protocol

Bridge Priority The range of priority values used to determine which device is selected as
Value the Spanning Tree root. This value can range from 0- 65535 for bridge
priority mode 802.1d (decrement by 1) or from 0-61440 for bridge prior-
ity mode 802.1t (decrement by 4096).

CAT5 Category 5 Twisted Pair Cable - such as 10Base-T, 100Base-TX and


1000Base-T.

CBP (Circuit Breaker Policy) a role/service that disables a port when a Beacon
packet is received from an edge switch or from the tier below.

Circuit Breaker A policy rule that will disable a port that receives an incoming packet of an
outgoing Beacon packet “Loop”.

Circuit Breaker This is used to refer to policy rule that will disable an uplink port that
PBQ/SBQ interfaces two root switches that receives an incoming packet of an outgo-
(CBPBQ/CBSBQ) ing Beacon packet “Loop”. This function is a subset of the Circuit
Breaker.

CLI Command Line Interface

Core Switch Refers to the main body of switches that provide the network with its
backbone connections. A core switch can also be considered an “edge

1.
“UPC” denotes an “ultra” quality polish on the fiber endface of a cable.

xi
B0700CE – Rev C Preface

switch” in reference to the root; however the outer most edge switches
within the network are normally not considered to be core switches.

CRC Cyclic Redundancy Check

CSMA/CD Carrier Sense Multiple Access/Collision Detection

Data Loop or Loop Refers to a condition where data traverses a redundant path with no
Path termination point.

DCE Data Communications Equipment (modem)

DSR Data Set Ready

DTE Data Terminal Equipment

DTR Data Terminal Ready

Edge Switch Refers to an outer switch in a network topology that is linked to the pri-
mary root or backup root bridge switch directly in one to two tier
configurations, and indirectly in three to four tier configurations.

ESD Electrostatic Discharge

FCS Frame Check Sequence

FTM Frame Transfer Matrix

Full Duplex Transmission method that allows two network devices to transmit and
receive concurrently, effectively doubling the bandwidth of that link.

GBIC Gigabit Interface Converter

HTTP Hypertext Transfer Protocol

ICMP Internet Control Message Protocol

IEEE Institute of Electrical and Electronics Engineers

IEEE 802.3 Defines carrier sense multiple access with collision detection (CSMA/CD)
access method and physical layer specifications.

IEEE 802.3ab Defines a media access method and physical layer specifications for
1000Base-T Gigabit Ethernet.

IEEE 802.3u Defines a media access method and physical layer specifications for
100Base-TX Fast Ethernet over CAT5 cable.

IEEE 802.3x Defines Ethernet frame start/stop requests and timers used for paused flow
control on full-duplex links.

IEEE 802.3z Defines a media access method and physical layer specifications for
1000Base Gigabit Ethernet.

xii
Preface B0700CE – Rev C

IGMP Internet Group Management Protocol, used to establish host member-


ships in particular multicast groups on a single network.

IP Internet Protocol

LAN Local Area Network

LDP Loop Detection Policy (Refer to The MESH Control Network Operation,
and Switch Installation and Configuration Guide (B0700CA) for more
information.)

LED Light Emitting Diode

MAC Media Access Control

MDI Media Dependent Interface or Media Device Interface

MIB Management Information Base

MMF Multi-mode Fiber cable

NOM Network Option Module (Invensys P/N P0973KH)

PBQ Primary Beacon Queryer - The switch with the lowest IP address and with
the IGMP “Beacon” enabled.

Policy A group of rules which a network device uses to make forwarding, block-
ing or port-disable decisions.

RFC Request for Comment

RMON Remote Monitoring

Role A collection of services

RPSC Redundant Power Supply Chassis

RPSM Redundant Power Supply Module

RSTP Rapid Spanning-Tree Protocol (IEEE 802.1w standard)

Rule Hit An action when a packet classifier finds the packet.

Rules Packet classifiers that are used to identify packet types on the network.

RXD Receive Data

SBQ Secondary Beacon Query - The switch with the second lowest IP address
and with the IGMP “Beacon” enabled.

Service A collection of Rules

SFP Small Form Factor Pluggable (Type of Mini-GBIC)

xiii
B0700CE – Rev C Preface

SMF Single-mode Fiber cable

SNMP Simple Network Management Protocol

STP Spanning-Tree Protocol (IEEE 802.1d standard)

TCP/IP Transmission Control Protocol/Internet Protocol

TFTP Trivial File Transfer Protocol

The MESH A switched Fast Ethernet network based on IEEE 802.3u (Fast Ethernet)
and IEEE 802.3z (gigabit Ethernet) standards.

TXD Transmit Data

UTP Unshielded Twisted Pair

VLAN Virtual Local Area Network

xiv
1. Introduction
This chapter provides an introduction to the S-series Chassis switches and their equipment used in
The MESH control network.

NOTE
For details about the concepts, architecture and cabling for The MESH, refer to The
MESH Control Network Architecture Guide (B0700AZ).

S-series Chassis Switches


The following S-series Chassis switches have been tested and qualified by Invensys for use with
The MESH and other Foxboro Evo™ Process Automation System products:
♦ SSA Chassis managed switch (P0973KK/LN) provides fifty-two SFP uplink ports.
♦ S4 Chassis managed switch (P0973KD) provides up to one hundred ninety two SFP
uplink ports.
These switches are optimal for use in the star and inverted tree topologies for small to large-sized
networks, as discussed in the introduction of The MESH Control Network Architecture Guide
(B0700AZ).

NOTE
S-series switches, as indicated, must use Revision 3.5.1 or later versions of the
Switch Configurator Application Software, discussed in The MESH Control Network
Operation, and Switch Installation and Configuration Guide (B0700CA).

SSA Chassis Managed Switch (P0973KK/LN)

Figure 1-1. SSA Chassis Managed Switch (P0973KK)

1
B0700CE – Rev C 1. Introduction

Figure 1-2. SSA Chassis Managed Switch (P0973LN)

The SSA Chassis managed switch (P0973KK/LN) provides fifty-two SFP 1000Base-X 1Gb
uplink ports.
The switches allow high-performance, full-featured Ethernet switching in small to medium-sized
network applications, as well as high-performance direct end-station connectivity.
Distributed switching architecture with redundant processors and integral load-sharing redundant
power supplies make the SSA Chassis managed switch extremely reliable.
The chassis utilizes add-on power supplies (ordered separately) that requires one separately fused,
15-amp power circuit within 182 cm (6 ft) of the power supply. For redundancy, a second supply
slot is available.

NOTE
Two separate branch circuits are required for the redundant power supply. Requires
two 15 A ac outlets independently fused within 182 cm (6 ft) of power supply, each
outlet uses a separate 15 A power circuit per power supply.

The features of the SSA Chassis managed switch (P0973KK/LN) are:


♦ 48-port 1000Base-X 1Gb SFP uplink ports
♦ 4-port 10G SFP uplink ports configurable as 1G uplink ports
♦ Rapid Spanning Tree (RSTP), IEEE 802.1w compatible
♦ Monitoring and configuration tasks via local port, or SNMP-based management
application
♦ Distributed switching architecture for maximum uptime
♦ Redundant power supply for increased power security.

NOTE
The DFE-Gold and DFE-Platinum series blades are neither interchangeable nor
compatible with the S-series chassis switch.

For more information on uplink modules, refer to Figure A-1 in Appendix A “Ethernet Switch
Interconnection Diagrams” and the documentation supplied with the switch.

Visual Indicators
Indicators on the front of the chassis indicate: power failure and fan failure. Indicators for each
port and uplink indicate: port enabled and link activity, data collisions and diagnostic failure.

2
1. Introduction B0700CE – Rev C

Auto-Ranging Power Supplies


The SSA managed switch’s chassis power supplies (P0973KL and P0973LQ) automatically adjust
to the input voltage and frequency, which allows for an input voltage of 100 to 240 V ac, and a
frequency between 50 and 60 Hz.

Figure 1-3. S-Series (for P0973KK) SSA Chassis Managed Switch Power Supply (P0973KL)

Figure 1-4. S-Series (for P0973LN) SSA Chassis Managed Switch Power Supply (P0973LQ)

Power Supply Replacement


Power supplies in the SSA Chassis managed switch are removable, and thus may be replaced in the
field.

Chassis Cooling System


The SSA Chassis managed switch supports thirteen individual 12 V fans. In the event of a fan
failure the chassis FAN LED and the output of the CLI show system command will indicate that
a fan has failed.

3
B0700CE – Rev C 1. Introduction

Switch/Uplink Modules
Table 1-1 lists the type of Ethernet switch modules and optional uplink modules which are
compatible with the SSA Chassis managed switch.

Table 1-1. SSA Chassis Managed Switch Modules/Uplink Modules

Uplink Connectors
Switch (add to uplink modules)

Invensys Invensys
Description Part No. Description Part No.

SSA Chassis man- P0973KK/ Uplink module 1000Base-SX with LC connectors P0972WT - MMF1
aged switch with LN
forty-eight Uplink module 1000Base-LX/LH with LC P0972YQ - MMF2
1000Base-X SFP connectors1
with four 10G-T Uplink module 1000Base-LX with LC connectors1 P0972WU - 10 km (6.2 mi)
SFP connectors, with SMF
configurable to
1000Base-X. A Uplink module, 1000Base-ZX with LC connectors P0973FT2 - 80 km (49.6 mi)
total of 52 SFP with SMF
ports.
Uplink module 1000Base-T with RJ-45 connectors1 P0972YL - 100 m (330 ft)

Bi-directional downlink/uplink Mini-GBIC Kit - P0973JD3 - 10Km S-SMF


includes both P0973JB and P0973JC modules Mini-GBIC Kit
100Base-FX with LC connectors1 P0973JE - MMF2

Bi-directional downlink/uplink Mini-GBIC Kit - P0973KP4 - 40 km (25 mi) S-


includes both P0973KM and P0973KN modules SMF Mini-GBIC Kit

Bi-directional downlink/uplink Mini-GBIC Kit - P0973KS5 - 120 km (74.6 mi)


includes both P0973KQ and P0973KR modules S-SMF Mini-GBIC Kit

1.
Refer to Table 2-8 on page 26 to determine the maximum range for your specific application.
2. It is not recommended to use the P0973FT MGBIC over distances less than 8 km (5.0 mi).
3. Kit P0973JD is comprised of two Mini-GBICs (P0973JB and P0973JC). P0973JC transmits
“downstream” (from the core of the network to the edge) uses the 1490 nm wavelength, and the
“edge” P0973JB transmits “upstream” uses the 1310 nm wavelength.
4. Kit P0973KP (40 km (25 mi)) is comprised of two Mini-GBICs (P0973KM and P0973KN).
P0973KN transmits “downstream” (from the core of the network to the edge) uses the 1490 nm
wavelength, and the “edge” P0973KM transmits “upstream” uses the 1310 nm wavelength over
Simplex Single Mode Fiber (S-SMF).
5. Kit P0973KS (120Km) is comprised of two Mini-GBICs (P0973KQ and P0973KR). P0973KR
transmits “downstream” (from the core of the network to the edge) uses the 1590 nm wavelength,
and the “edge” P0973KQ transmits “upstream” uses the 1490 nm wavelength over Simplex Single
Mode Fiber (S-SMF) at a minimum distance of 30 km (19 mi).

4
1. Introduction B0700CE – Rev C

S4 Chassis Managed Switch (P0973KD)

Slot 4

Slot 3
(Not Used)

Slot 2

Slot 1

Power Supplies
(P0973KE or P0973LJ)

Figure 1-5. S4 Chassis Managed Switch (P0973KD)

The S4 Chassis managed switch (P0973KD) (Figure 1-5) consists of three usable slots within a
4-slot chassis with four empty power supply locations and a front mounted fan assembly. The
3-slots can be populated with Ethernet blades/modules, depending on the needs of the user.
Slot 2 in the switch (see Figure 1-5) must be populated with an S4 S-series Network I/O Fabric
module (P0973KG, P0973KG Rev. B, or P0973LP) for switch operations. The I/O Fabric mod-
ule is the master blade for the switch, controlling the other slot locations. To achieve proper
failover in the event of an I/O Fabric module failure, Slot 3 cannot be populated.
The P0973KD switch provides up to one hundred ninety two SFP uplink ports depending on the
number of blades and modules installed.
The switch allows high-performance, full-featured Ethernet switching in medium to large-sized
network applications. Direct end-station connectivity is possible when using the P0973JE 100Mb
GBIC.
The chassis utilizes a 1200/1600 or 930/1600 watt power supplies (ordered separately) that
requires one separately fused, 20-amp power circuit (for P0973KE) or a 15-amp power circuit (for
P0973LJ) within 182 cm (6 ft) of the power supply. For redundancy, four supply slots are
available. The third and fourth supply slots are used for Power over Ethernet (PoE) functionality
(not supported on The MESH control network).
For a list of the switch modules supported by the S4 Chassis managed switch, refer to Table 1-2,
“S4 Chassis Managed Switch Modules/Uplink Modules,” on page 9.

5
B0700CE – Rev C 1. Introduction

NOTE
A redundantly powered S4 Chassis managed switch requires two 20-amp branch
circuits.

The features of the S4 Chassis managed switch (P0973KD) are:


♦ Up to 192 1Gb SFP uplink ports depending on the choice of modules
♦ Selectable switch modules/uplink modules and interfaces (see Table 1-2, “S4 Chassis
Managed Switch Modules/Uplink Modules,” on page 9)
♦ Rapid Spanning Tree (RSTP), IEEE 802.1w compatible
♦ Monitoring and configuration tasks via local port, or SNMP-based management
application.
♦ Distributed switching architecture for maximum uptime
♦ An optional, pluggable, redundant power supply for increased power security.
Distributed switching architecture with redundant processors and power supplies and hot-swap-
pable components make the S4 Chassis managed switch extremely reliable —with no single point
of failure.

Visual Indicators
Indicators on the front of the power supply indicate: ac and dc power status (good or failed).
Indicators on the blades indicate testing and bootup. Indicators for each port and uplink indicate:
port enabled and link activity, data collisions and diagnostic failure. For a full description of these
LEDs, refer to “Overview of S-Series Capabilities” on page 28.

Auto-Ranging Power Supplies


The S4 Chassis managed switch's have two option for its power supplies:
♦ P0973KE - a 20 Amp input source power supply
♦ P0973LJ - a 15 Amp input source power supply.
Both automatically adjust to the input voltage ranges of 100 to 125 V ac, or 200 or 250 V ac,
with a frequency range of 50 to 60 Hz.

6
1. Introduction B0700CE – Rev C

Figure 1-6. S-Series S4 Chassis Managed Switch Power Supply

Power Supply Replacement


To reduce network downtime, redundant power supplies (P0973KE and P0973LJ) are hot swap-
pable and one can be replaced online after it has been powered down. This allows you to remove
one power supply without powering down the chassis and interrupting network traffic.

Chassis Cooling System


The S4 Chassis managed switch features a removable fan tray (P0973KT), which is accessible
from the front of the chassis. The fan tray is hot swappable, which allows you to replace it without
powering down the chassis.

! CAUTION
The fan assembly is hot-swappable. However, do not run the chassis for any
extended periods of time without an operating fan assembly, as the chassis will
quickly overheat and cause damage.

7
B0700CE – Rev C 1. Introduction

Figure 1-7. S4 Chassis Managed Switch Removable Fan Tray (P0973KT)

8
1. Introduction B0700CE – Rev C

Switch/Uplink Modules
Table 1-2 lists the type of Ethernet switch modules and optional uplink modules which are
compatible with the S4 Chassis managed switch. This managed switch has three usable slots for
switch modules (blades).

Table 1-2. S4 Chassis Managed Switch Modules/Uplink Modules

Uplink Modules Uplink Connectors


Switch Modules (add to switch module) (add to uplink modules)

Invensys Invensys Invensys


Description Part No. Description Part No. Description Part No.

(Slot 2 only) P0973KG 1 Gb uplink Net- P0973KH Uplink module 1000Base-SX with P0972WT - MMF2
Plug-in S150 or work Option LC connectors1
I/O P0973KG, Module with
Fabric switch Rev. B 12 SFP ports - Uplink module 1000Base-LX/LH P0972YQ - MMF2
module with 2 or refer to “Net- with LC connectors1
expansion P0973LP work Option Uplink module 1000Base-LX with P0972WU - 10 km
slots Module LC connectors1 (6.2 mi) with SMF
(P0973KH)” on
(Slot 1/4 only) P0973KF page 29 for Uplink module, 1000Base-ZX P0973FT3 - 80 km
Plug-in S130 more informa- with LC connectors (49.6 mi) with SMF
I/O switch tion on this
module with Uplink module 1000Base-T with P0972YL - 100 m
module.
expansion slot RJ-45 connectors1 (330 ft)

Bi-directional downlink/uplink P0973JD4 - 10Km


Mini-GBIC Kit - includes both S-SMF Mini-GBIC
P0973JB and P0973JC modules Kit

100Base-FX with LC connectors1 P0973JE - MMF2

Bi-directional downlink/uplink P0973KP5 - 40 km


Mini-GBIC Kit - includes both (25 mi) S-SMF Mini-
P0973KM and P0973KN modules GBIC Kit
Bi-directional downlink/uplink P0973KS6 - 120 km
Mini-GBIC Kit - includes both (74.6 mi) S-SMF
P0973KQ and P0973KR modules Mini-GBIC Kit

1.
Use uplink connectors with P0973KG/P0973KF/P0973KH switch modules.
2. Refer to Table 2-8 on page 26 to determine the maximum range for your specific application.
3. It is not recommended to use the P0973FT MGBIC over distances less than 8 km (5.0 mi).
4.
Kit P0973JD is comprised of two Mini-GBICs (P0973JB and P0973JC). P0973JC transmits
“downstream” (from the core of the network to the edge) uses the 1490 nm wavelength, and the
“edge” P0973JB transmits “upstream” uses the 1310 nm wavelength.
5. Kit P0973KP (40 km (25 mi)) is comprised of two Mini-GBICs (P0973KM and P0973KN).
P0973KN transmits “downstream” (from the core of the network to the edge) uses the 1490 nm
wavelength, and the “edge” P0973KM transmits “upstream” uses the 1310 nm wavelength over
Simplex Single Mode Fiber (S-SMF).
6.
Kit P0973KS (120Km) is comprised of two Mini-GBICs (P0973KQ and P0973KR). P0973KR
transmits “downstream” (from the core of the network to the edge) uses the 1590 nm wavelength,
and the “edge” P0973KQ transmits “upstream” uses the 1490 nm wavelength over Simplex Single
Mode Fiber (S-SMF) at a minimum distance of 30 km (19 mi).

9
B0700CE – Rev C 1. Introduction

NOTE
The DFE-Gold series blades or DFE-Platinum series blades are neither interchange-
able nor compatible with the S-series chassis.

For more information on uplink modules, refer to Figure A-2 in Appendix A “Ethernet Switch
Interconnection Diagrams” and the documentation supplied with the switch.

Media Converter
The media converter provides a way to connect devices that use 100 Mb CAT5-STP copper cable
(RJ-45 connectors) to a device that uses 100FX multimode fiber optic cable. The media converter
allows connection between copper and fiber devices. A media converter allows you to connect a
workstation or a controller to an Ethernet switch that is not equipped with fiber optic ports, while
gaining the benefits of extended range isolated fiber optic transmission.
Refer to Media Converter Installation and Configuration Guide for Control Networks (B0700CP)
for all information on the media converter types available for use with these switches.

Switch Management
For The MESH control network, the network management module for the Fast Ethernet
switches, provides a menu-driven or Command Line Interface (CLI) system configuration pro-
gram with management capability. See Chapter 4 “Switch Configuration” for further details.
Appendix A “Ethernet Switch Interconnection Diagrams” contains details on expansion and
cabling options.

10
2. Site Planning
This chapter describes the steps that should be taken and the options that should be considered
when planning the inclusion of the S-series Chassis switches in The MESH Control Network.
The design of each implementation of The MESH Control Network is different, and depends on
the needs and requirements of the individual site. The following paragraphs provide the informa-
tion necessary to help network designers to plan the control network that meets the needs of their
specific site.
Refer to The MESH Control Network Architecture Guide (B0700AZ) for details about overall site
planning.

S-series Chassis Switch Features and Capabilities


The following sections describe the features and capabilities of the switches that are offered by
Invensys for use in The MESH Control Network. Use this information to aid in the selection of
equipment to implement the network design plan.
It is recommended to install the SSA Chassis managed switch (P0973KK/LN) and the S4 Chassis
managed switch (P0973KD) into the G50 Server enclosure, discussed in G50 Server Enclosure
(PSS 21H-2X50 B4) and Enclosures and Mounting Structures Site Planning and Installation User’s
Guide (B0700AS).

SSA Chassis Switch (P0973KK/LN)


The SSA switch is a chassis-based Ethernet switch (refer to “SSA Chassis Managed Switch
(P0973KK/LN)” on page 1). The switch consists of a tabletop or rack-mountable chassis contain-
ing a field swappable, load-sharing, redundant power supply with cooling fans.

Site Installation Guidelines for SSA Chassis Switch (P0973KK/LN)


The following guidelines must be observed when a site is selected for the SSA Chassis managed
switch. If the guidelines are not followed, unsatisfactory network performance may result.
♦ To ensure proper ventilation and prevent overheating, leave a minimum clearance
space of 5.1 cm (2.0 in) of clearance on either side and in the rear of the unit.
♦ To install the SSA Chassis managed switch as a freestanding unit on a shelf, the shelf
must be able to adequately support the static weight of the unit.
♦ The power supplies for the SSA Chassis managed switch require two three-pronged
power receptacles capable of delivering the current and voltage specified below. ac out-
lets on independently fused circuits are required for each power supply, and must be
located less than 2 m (6 ft) from the site. The power cord used and type of outlet is
dependent on the country. In the United States, two power cords with NEMA 5-15P
plugs are provided with each power supply.
♦ Ambient temperature at the installation site must be maintained between 5° and 40°C
(41° to 104°F). Temperature changes must be maintained within 10°C (18°F) per
hour.

11
B0700CE – Rev C 2. Site Planning

♦ The SSA Chassis managed switch may be mounted in a 19” rack, such in the G50
Server enclosure.
♦ If the SSA P0973KK is installed in an enclosure other than the G50 Server enclosure,
be aware that the air flow for the S-series switches is left to right, which is different
from other MESH Control Network switches and this may impact the air circulation
in the enclosure.

NOTE
The S-series P0973LN air flow has also changed from front to back to improve the
switch's cooling.

♦ To install the SSA Chassis managed switch as a rack mounted unit using the SSA rail
kit (shipped with the SSA switch), ensure that the rack used will support the unit and
that the rack will remain stable after installation.

! WARNING
DO NOT use the P0973LN rack mount with the P0973KK chassis. This rack
mount will cause the unit to overheat due to airflow restrictions.

The SSA Chassis switch can be mounted in three types of racks:


♦ Four-post rack - See “Rack Mounting the SSA Switch in a Four-Post Rack” below.
♦ Two-post rack (18 cm (7 in) posts) - See “Rack Mounting the SSA Switch in a Two-
Post Rack (18 Cm (7 In) Posts)” on page 15.
♦ Two-post rack (7.6 cm (3 in) posts) - See “Rack Mounting the SSA Switch in a Two-
Post Rack (7.6 Cm (3 In) Posts)” on page 18.
If you are installing the SSA switch in a rack, it is recommended that you install the SSA switch in
a four-post, 48.26 cm (19 in) equipment rack.

Desktop Installation
For desktop installation, you must attach the adhesive rubber feet to the bottom of the SSA
switch.
To attach the rubber feet to the bottom of the SSA switch, proceed as follows:
1. Place the SSA switch upside down on a sturdy, flat surface.
2. Remove the adhesive backing from the four rubber feet.
3. Adhere the rubber feet to the round, recessed areas on the bottom of the SSA switch.

Rack Mounting the SSA Switch in a Four-Post Rack


NOTE
When installing the SSA switch in a G50 Server enclosure, use this procedure to
install it.

12
2. Site Planning B0700CE – Rev C

For a four-post rack installation, the SSA rail kit requires that the front to back spacing of the rack
posts be within the range of 62 cm (24.5 in) to 83 cm (32.5 in).
In a four-post rack, the SSA switch is flush-mounted on the rails supplied in the SSA rail kit and
secured to the front posts of the rack. If desired, you can secure the rear of the SSA switch to the
rails.
To install the SSA switch in a four-post rack:
1. Extend the right and left rails to fit the outside dimensions of the rack posts.
The rails in the SSA rail kit are shipped with the rail extensions attached. If the rails
do not slide easily, loosen the screws that secure the rail extensions to the main rails.
2. Position the right and left rails, which are labeled on the inside of each rail, in the rack
with the bottom lip of the rail facing into the rack.
3. Attach each rail to the rack posts with two screws in the front and two screws in the
back in the top and bottom screw holes. See Figure 2-1.

NOTE
The SSA rail kit does not include screws for attaching the rails to the rack posts.

Tighten these screws securing


the rail extensions to the rails.
Rails (Included in SSA rail kit)

Rack Posts

Tighten these screws securing


the rail extensions to the rails. Note: Screws are customer-supplied.

Figure 2-1. Attaching Rails from SSA Rail Kit to Rack Posts

4. If necessary, tighten the screws that secure the rail extensions to the ends of the rails as
shown in Figure 2-1. These screws must be tight before you place the SSA switch in
the rails.

13
B0700CE – Rev C 2. Site Planning

5. From the front of the rack, slide the SSA switch onto the rails until the mounting ears
of the SSA switch are against the front posts of the rack.
6. Secure the front of the SSA switch to the rack by screwing the customer-supplied rack
screws in the mounting ears on the right and left front of the SSA switch. See
Figure 2-2.

Secure screws as shown

Figure 2-2. Securing the SSA Switch to the Four-Post Rack

7. (Optional) Secure the rear of the SSA to the rails. See “Securing the SSA Switch to the
Rear of the Rails” on page 19.

14
2. Site Planning B0700CE – Rev C

Rack Mounting the SSA Switch in a Two-Post Rack (18 Cm (7 In) Posts)
In a two-post rack with 18 cm (7 in) posts, the SSA switch is flush-mounted in the rack and
secured in the SSA rails to the front and rear of the posts. In this procedure, you need to modify
the rails by removing the rail extensions and attaching the mounting brackets, which are supplied
in the rail kit.
To rack mount the SSA in a two-post rack with 18 cm (7 in) posts:
1. Remove the extensions from each rail by unscrewing the rail clamps. See Figure 2-3.
The rail extensions and rail clamps are not used to install an SSA switch in a two-post
rack. Save the eight 6-32 screws to be used in the next step.

1 - Rails (used in this procedure) 3 - Rail Clamps (must be removed - not used)
2 - Rail Extensions (must be removed - not used) 4 - 6-32 Screws (used in this procedure)
Figure 2-3. Removing the Rail Extensions from the Rails

15
B0700CE – Rev C 2. Site Planning

2. Attach a mounting bracket, included in the SSA rail kit, to the outside of each rail
using the 6-32 screws removed in step 1. See Figure 2-4.
Use the four 6-32 screws to attach each mounting bracket. Leave the 6-32 screws loose
to position the mounting brackets properly against the rack posts.

1 - Mounting Bracket 2 - Rail

Figure 2-4. Attaching the Mounting Brackets to the Rails (Left Rail Example)

16
2. Site Planning B0700CE – Rev C

3. Position the right and left rails, which are labeled on the inside of each rail, in the rack
with the bottom lip of the rail facing into the rack. The front mounting ears of the
rails should be flush against the front screw holes of the rack posts. The mounting
brackets should be flush against the rear screw holes of the rack posts. See Figure 2-5.

Note: Screws are customer-supplied.

Front
Mounting Ears

1 - Securing the left rail to the front of the 18 cm (7 in) post.


2 - Securing the left mounting bracket to the rear of the 18 cm (7 in) post.
Figure 2-5. Positioning and Attaching the Rails to the 18 cm (7 in) Posts

4. Attach the rails to the rack posts using customer-supplied rack screws. See Figure 2-5.

NOTE
The SSA rail kit does not include screws for attaching the rails and mounting brack-
ets to the rack posts.

a. Secure the front of the rail to the front of the rack post with customer-supplied
screws in the top and bottom screw holes.
b. Secure the mounting bracket to the back of the rack post with customer-supplied
screws in the top and bottom screw holes.
5. Tighten the 6-32 screws that secure the mounting brackets to the rails.
6. Slide the SSA switch onto the rails until the front of the SSA switch is against the
front of the rack posts.
7. Secure the front of the SSA switch to the rack by screwing the customer-supplied rack
screws in the mounting ears on the right and left front of the SSA.

17
B0700CE – Rev C 2. Site Planning

8. (Optional) Secure the rear of the SSA switch to the rails. See “Securing the SSA
Switch to the Rear of the Rails” on page 19.

Rack Mounting the SSA Switch in a Two-Post Rack (7.6 Cm (3 In) Posts)
In a two-post rack with 7.6 cm (3 in) posts, three mid-mount positions are possible. See
Figure 2-6 for possible mounting positions, as shown on the right post. The top mid-mount posi-
tion shown in Figure 2-6 is recommended as the best of the three options.

Recommended Position

Optional Positions

Figure 2-6. Installation Positions in a Two-Post Rack (7.6 cm (3 in) Posts)

To rack mount the SSA switch in a two-post rack with 7.6 cm (3 in) posts:
1. Remove the extensions from each rack rail by unscrewing the rail clamps. See
Figure 2-3 on page 15.
The rail extensions and rail clamps are not used to install an SSA switch in a two-post
rack.
2. Using the eight 6-32 screws removed in step 1, attach the mounting bracket to each
rail (four screws for each mounting bracket) in the appropriate orientation for the
mounting option that you have chosen. See Figure 2-6.
3. Secure the mounting brackets to the rack posts with three customer-supplied screws in
each mounting bracket.
Depending on the mounting option, you must secure the mounting brackets to either
the front or back of the rack posts. See Figure 2-6. The SSA rail kit does not include
screws for attaching the mounting brackets to the rack posts.
4. Snap the 10-32 cage nuts, included in the SSA rail kit, into the square screw holes on
the front mounting ears of the rails.

18
2. Site Planning B0700CE – Rev C

5. Slide the SSA switch onto the rails until the front of the SSA switch is against the
mounting ears of the rails.
6. Secure the front of the SSA switch to the rails by screwing the 10-32 screws, included
in the SSA rail kit, into the mounting ears on the right and left front of the SSA
switch.
7. (Optional) Secure the rear of the SSA switch to the rails. See “Securing the SSA
Switch to the Rear of the Rails” below.

Securing the SSA Switch to the Rear of the Rails


This optional procedure for securing the SSA switch to the rear of the SSA rails applies to the
three rack installation scenarios described above - the four-post rack and both two-post rack sce-
narios. Securing the rear of the SSA switch is recommended only if you are shipping the rack in
which the SSA switch is installed.
If you plan to secure the left rear corner of the SSA switch, you must remove the screw from the
left rear corner of the SSA switch before installing the SSA in the rack. See Figure 2-7.

1 - Remove this screw before installing the SSA switch in the rack.

Figure 2-7. Screw to Remove If You Plan to Secure the Left Rear of the SSA Switch

To secure the rear of the SSA switch to the rails, screw the 2-56 screws, included in the SSA rail
kit, into the screw tabs on the right and left rail. See Figure 2?8.

Figure 2-8. Securing the Rear of the SSA Switch (Four-Post Rack Example)

19
B0700CE – Rev C 2. Site Planning

SSA Chassis Managed Switch Power Supply Specifications

Table 2-1. SSA Chassis Managed Switch (P0973KK) Power Supply Specifications

Specification Description
Input (Voltage/Amps) 100 to 240 V AC: 8A at 625 watts

Table 2-2. SSA Chassis Managed Switch (P0973LN) Power Supply Specifications

Specification Description
Input Frequency 50 to 60 Hz
Input (Voltage/Amps) at Output Power 100 to 240 V AC: 5.29 to 2.2A at 450 watts
Environmental
Operating Temperature 5°C to 40°C (41°F to 104°F)
Storage Temperature -30°C to 73°C (-22°F to 164°F)
Operating Relative Humidity 5% to 95% (non-condensing)

Table 2-3. SSA Chassis Managed Switch (P0973KK/LN) Environmental Specifications

Specification Description
Operating Temperature 5°C to 40°C (41°F to 104°F)
Storage Temperature -30°C to 73°C (-22°F to 164°F)
Operating Relative Humidity 5% to 90% (non-condensing)
Regulatory Compliance
Safety Safety: UL 60950, CSA C22.2 No. 60950, EN
60950, IEC 60950.
Modules which support laser connections also
meet the EN 60825 and 21 CFR 1040.10 stan-
dards.
Electromagnetic Compatibility (EMI) FCC 47 CFR Parts 2 and 15, CSA C108.8,
EN 55022, EN 61000-3-2, EN 61000-3-3,
EN 55024, AS/NZS CISPR 22, VCCI V-3

S4 Chassis Switch (P0973KD)


In addition to the discrete switches described above, the S4 chassis-based Ethernet switch (refer to
“S4 Chassis Managed Switch (P0973KD)” on page 5) provides expansion capability. The switch
consists of a tabletop or rack-mountable chassis containing a power supply, cooling fans, and slots
for up to three Ethernet interface cards (blades).
Table 1-2, “S4 Chassis Managed Switch Modules/Uplink Modules” on page 9 lists the Invensys
part numbers for the S4 Chassis switch and optional interface modules. See Appendix A “Ether-
net Switch Interconnection Diagrams” for configuration options.

20
2. Site Planning B0700CE – Rev C

Site Installation Guidelines for S4 Chassis Switch (P0973KD)


The following guidelines must be observed when a site is selected for the S4 Chassis managed
switch. If the guidelines are not followed, unsatisfactory network performance may result.
♦ For proper cooling, there must be a minimum amount of clearance 152 mm (6 in)
behind the chassis and 51 mm (2 in) of clearance on either side of the chassis.
♦ If installing the S4 Chassis managed switch as a freestanding unit on a shelf, ensure
that the shelf can support a minimum weight of approximately 24.7 kg (54.45 lb) per
fully loaded chassis plus the weight of the connected network cables. The weight
includes the chassis, fan tray, two power supplies, and three modules.
♦ The S4 Chassis managed switch may be mounted in a 19” rack such as in the G50
Server enclosure.
♦ If installed in an enclosure other than the G50 Server enclosure, be aware that the air
flow for the S-series switches is different from other The MESH Control Network
switches and this may impact the air circulation in the enclosure.
♦ If installing the S4 Chassis managed switch in an equipment rack, ensure that the rack
can support and remain stable with the chassis installed.
♦ Each P0973KE or P0973LJ ac power supply requires a three-pronged power recepta-
cle capable of delivering the current and voltage specified below. An ac outlet on a
separately fused circuit is required for each P0973KE or P0973LJ supply to provide
power redundancy, and must be located within 1.8 m (6 ft) from the site. The power
cord used and type of outlet is dependent on the country. In the United States, a
power cord with a NEMA 5-20P plug is provided with each P0973KE supply and a
NEMA 5-15P plug is provided with each P0973LJ supply.
♦ Ambient temperature at the installation site must be maintained between 5° and 40°C
(41° to 104°F). Temperature changes must be maintained within 10°C (18°F) per
hour.

Table 2-4. S4 Chassis Managed Switch (P0973KD) Power Supply Specifications

Part Number Specification Description


P0973KE Input (Voltage/Current) 100 to 125 V ac: 16 A at 1200 Watts
at Output Power 200 to 240 V ac: 10 A at 1600 Watts
P0973LJ Input (Voltage/Current) 100 to 125 V ac: 12 A at 930 Watts
at Output Power 200 to 240 V ac: 8 A at 1600 Watts

Table 2-5. S4 Chassis Managed Switch (P0973KD) Environmental Specifications

Specification Description
Operating Temperature 5°C to 40°C (41°F to 104°F)
Storage Temperature -30°C to 73°C (-22°F to 164°F)
Operating Relative Humidity 5% to 90% (non-condensing)

21
B0700CE – Rev C 2. Site Planning

Table 2-5. S4 Chassis Managed Switch (P0973KD) Environmental Specifications (Continued)

Specification Description
Regulatory Compliance
Safety UL 60950, CSA C22.2 No. 60950,
73/23/EEC, EN 60950, IEC 60950
Modules which support laser connections also
meet the EN 60825 and 21 CFR 1040.10 stan-
dards.
Electromagnetic Compatibility (EMI) FCC 47 CFR Parts 2 and 15, CSA C108.8,
89/336/EEC, EN 55022, EN 61000-3-2,
EN 61000-3-3, EN 55024, AS/NZS
CISPR 22, VCCI V-3

22
2. Site Planning B0700CE – Rev C

Switch and Fiber Cable Budget and Loss


Fiber Cable Budget Cable and Loss
The typical power budget for 100FX system of The MESH Control Network with 62.5/125 m
fiber is 11.0 db and worst case (includes aging) is 10.0 db.
Table 2-6 lists some typical and worst case power losses for fiber optic cable, splitter/combiners
and patch cords.

Table 2-6. Fiber Cable Power Losses

Link Element Value Comments


Splitter/Combiner 4.5 db
MT-RJ Patch Cord 0.5 db 0.75 db worst case
LC, SC, and other simi- 0.15 db 0.5 db worst case
lar patch cords
Singlemode fiber cable 0.5 db/km at 1300 nm wavelength
(SMF) 0.275 db/km at 1550 nm wavelength
Simplex-Singlemode 0.33 - 0.35 db/km at 1310 nm wavelength
fiber cable 0.21 - 0.24 db/km at 1490 nm wavelength
(Simplex-SMF)1 0.19 - 0.20 db/km at 1550 nm wavelength
0.20 - 0.23 db/km at 1625 nm wavelength
Multimode fiber cable 1.0 db/km at 1300 nm wavelength
(MMF) 3.5 db/km at 850 nm wavelength
Splice loss 0.25 dB Mechanical splice
50/125 μM mating 5.25 dB -5.0 dB mating loss and a -0.25 dB for
62.5/125 μM loss mechanical splice
Aging reserve 1.0 dB 62.5/125 micron cable
Patch Panel loss 2.0 dB average
1.
These db losses may vary in the S-SMF cables depending on the mandrel diameter due to
macrobend loss.

Fiber Optic Budgets for S-Series Chassis Switch Modules


Table 2-7 lists the fiber optic budgets and Table 2-8 lists the operating range for the fiber-based S-
series Chassis switch modules.
Table 2-9 lists the specifications for the P0972YL copper-based switch module.

23
B0700CE – Rev C 2. Site Planning

Figure 2-9. Fiber Uplink Mini-GBIC Module’s with LC Connector


(P0972WT, P0972WU, P0972YQ, and P0973FT)

The 1000Base-BX Fiber uplink (ISL) Mini-GBIC modules with Simplex LC connectors
(P0973JB/KM/KQ and P0973JC/KN/KR) are shown in Figure 2-10. 1000Base-BX is a version
of Fast Ethernet over a single strand of optical fiber (unlike 1000Base-LX, which uses a pair of
fibers). Simplex single-mode fiber is used, along with a special multiplexer (Mini-GBIC) which
splits the signal into transmit and receive wavelengths. The wavelengths used for transmit and
receive are 1310 nm, 1490 nm or 1590 nm. The Mini-GBIC modules on each side of the fiber
are not the same device, as the one transmitting P0973JC/KN/KR Mini-GBIC module “down-
stream” (from the core of the network to the edge) uses the 1490 nm or 1590 nm wavelengths,
and the “edge” transmitting P0973JB/KM/KQ Mini-GBIC module “upstream” uses the 1310 nm
or 1490 nm wavelengths with a distances of 10 km (6.2 mi), 40 km (24.8 mi) and 1490 nm
wavelength with a distances of 120 km (74.4 mi).

Figure 2-10. Fiber Uplink (ISL) Mini-GBIC Modules with Simplex LC Connector
1000Base-BX (P0973JB and P0973JC)

24
2. Site Planning B0700CE – Rev C

Table 2-7. Fiber Optic Budgets for S-Series Chassis Switch Mini-GBIC Modules

Transmit Transmit
Power Power Optical Power Receiver Sensitivity
Product Part
Number Min(dBm) Max(dBm) Budget(dBm) Min(dBm) Max(dBm)
P0972WT
50/125 -9.5 -4 7.5 -17 0
62.5/125 -9.5 -4 7.5 -17 0
P0972YQ
50/125 -9.5 -3 10.51 -20 -3
62.5/125 -9.5 -3 10.51 -20 -3
P0972WU
50/125 -11.5 -3 8.5 -20 -3
62.5/125 -11.5 -3 8.5 -20 -3
9/125 SMF -9.5 10.5 -20
P0973FT
9/125 SMF -2 +3 7 -9 -30
P0973JE
50/125 -20 -15 10 -30 -14
62.5/125 -20 -15 10 -30 -14
P0973JB/JC2
9/125 S-SMF -9 -3 13 -22 -3
P0973KM/KN2
9/125 S-SMF -5 0 17 -22 0
P0973KQ/KR2
9/125 S-SMF -1 4 31 -32 -7

1. (Multimode only for the P0972YQ) The maximum drive distance (up to 2 km) depends on
the quality of the installed multimode fiber-optic cable segment. Use the Link Power Bud-
get to calculate the maximum cable length of the attached segment. The Link Power Budget
must not exceed those specified in this table. The P0972YQ input power must not exceed -
3 dBm. Otherwise, saturation could occur. Note: The input power is not selectable.
2. P0973JB/JC, P0973KM/KN and P0973KQ/KR are bi-directional Mini-GBICs. Both
upstream and downstream switches transmit on the same fiber but at different frequencies.
When ordering these Mini-GBICs, you must acquire a matching pair, one of each type. For
a matching pair, order kits P0973JD (10 km (6.2 mi)), P0973KP (40 km (25 mi)), or
P0973KS (120 km (74.6 mi)) which include one of each of the required modules.

25
B0700CE – Rev C 2. Site Planning

Table 2-8. Operating Range for Mini-GBIC Modules1

Modal Bandwidth Range


Product Part Light Wavelength
Number2 Cable Type (nm) MHz/km Min (Meters) Max (Meters)
P0972WT 62.5µm 850 160 2 220
62.5µm 200 2 275
50µm 400 2 500
50µm 500 2 550
P0972YQ 62.5µm 1310 160 2 2000
50µm 400 2 1000
P0972WU 9-10µm 1310 - - 10000
P0973FT3 9-10µm 1550 - 8000 80000
P0973JB4 9µm 1310 nm/1490 nm - - 10000
P0973JC4 9µm 1490 nm/1310 nm - - 10000
P0973JE5 62.5µm 1310 nm 160 2 2000
50µm 400 2 1000
P0973KM4 9µm 1310 nm/1490 nm - 5000 40000
P0973KN4 9µm 1490 nm/1310 nm - 5000 40000
P0973KQ4 9µm 1490 nm/1590 nm - 30000 120000
P0973KR4 9µm 1590 nm/1490 nm - 30000 120000

1. Transmission distances are provided as a nominal guide only. Refer to the optical specifications and
the specific characteristics of your fiber installation to determine targeted distances.
2. All listed Mini-GBICs are thermal rated at 5 to +40°C (41 to +104°F).
3.
It is not recommended to use the P0973FT MGBIC over distances less than 8 km (5.0 mi).
4. P0973JB/JC, P0973KM/KN and P0973KQ/KR are bi-directional Mini-GBICs. Both upstream and
downstream switches transmit on the same fiber but at different frequencies. When ordering these
Mini-GBICs, you must acquire a matching pair, one of each type. For a matching pair, order kits
P0973JD (10 km (6.2 mi)), P0973KP (40 km (25 mi)), or P0973KS (120 km (74.6 mi)) which
include one of each of the required modules.
5. This Mini-GBIC (P0973JE) is not to be used as an uplink (ISL) port. This Mini-GBIC has been
qualified to be used for an end device (CP, ATS, FCM, workstation, etc.) 100Mb switch port.

Table 2-9. P0972YL Mini-GBIC Module (1000Base-T) Specifications

Item Specification
Supported Type Copper, Category 5 UTP
Cable Max Length Up to 100 meters
Connector RJ45
Data Rate 1 Gb, IEEE 802.3:2000 compatible 1000BASE-T operation only -
Automatic crossover detection
TX Output impedance 100 ohms, typical at all frequencies between 1 MHz and 125 MHz
RX Input impedance 100 ohms, typical at all frequencies between 1 MHz and 125 MHz

26
2. Site Planning B0700CE – Rev C

S-series Chassis Switch Network Cabling


For the specifications and transmission distance capabilities for the fiber optic, and twisted-pair
cabling used in The MESH Control Network, refer to The MESH Control Network Architecture
Guide (B0700AZ).

Connector Types for S-series Chassis Switches


Table 2-10 summarizes the connector type for S-series Chassis switches (blades) and uplink ports.

Table 2-10. Connector Types for S-series Chassis Switches

SSA Chassis Switch (P0973KK/LN)


S4 Chassis Switch (P0973KD)
Ports/Uplink Connector Type
P0973KK/LN SFP
P0973KG or P0973KG, Rev. B SFP
P0973KH SFP
P0973LP SFP
SFP MGBICs
P0972YL RJ-45 1000Base-TX
P0972YQ LC 1000Base-LX\LH MMF
P0972WT LC 1000Base-SX MMF
P0972WU LC 1000Base-LX SMF
P0973FT LC 1000Base-ZX SMF
Kit P0973JD1 Simplex LC 1000Base-BX (10 km (6.2 mi)) S-SMF
P0973JE2 LC 100Base-FX MMF
Kit P0973KP3 Simplex LC 1000Base-BX (40 km (25 mi)) S-SMF
Kit P0973KS4 Simplex LC 1000Base-BX (120 km (74.6 mi)) S-SMF
1. Kit P0973JD contains both the “upstream” Mini-GBIC (P0973JB) and the “downstream” Mini-
GBIC (P0973JC).
2. P0973JE is a 100Base-FX Mini-GBIC and is for end 100Mb device connectivity which is not
intended to be used as an ISL uplink GBIC.
3.
Kit P0973KP contains both the “upstream” Mini-GBIC (P0973KN) and the “downstream”
Mini-GBIC (P0973KM).
4.
Kit P0973KS contains both the “upstream” Mini-GBIC (P0973KQ) and the “downstream”
Mini-GBIC (P0973KR).

27
B0700CE – Rev C 2. Site Planning

Overview of S-Series Capabilities


The S-series switch is the next generation of Security Enhanced Network switches. The S-series
switch delivers high performance and flexibility to ensure comprehensive switching, Quality of
Service, security, and traffic containment. Key features include:
♦ Superior performance and capacity to support more high-bandwidth and latency sen-
sitive applications
♦ 1 Gigabit SFP Ethernet inter-switch link (ISL) connectivity
♦ Integrated Services Design that reduces the number/type of modules required, simpli-
fies network design, and lowers entry cost
♦ Port- and User-Based Policy and Multilayer Packet Classification that provides granu-
lar control and security for critical process applications
♦ High-availability services with stateful failover for services and management
♦ Self-learning configuration modules with increased reliability and fault tolerance that
reduces configuration time and maximizes uptime
♦ Reduced support and maintenance costs, and decreased configuration time

P0973KG, P0973KG Rev. B, or P0973LP S4 S-series Network I/O


Fabric Module
The P0973KG, P0973KG Rev. B, or P0973LP S-series network fabric module has 48
1000BASE-X compliant front panel ports that support a variety of optional Small Form Factor
Pluggable (SFP) Gigabit connections using optional Mini-Gigabit Interface Cards (MGBICs).
The SFP port slots enable you to install a mix-and-match number of SFPs to meet a need for var-
ious Gigabit Ethernet connections.
There are also two slots for an optional network option module P0973KH (NOM).

NOTE
The P0973KG blade can only be installed in slot 2 of the S4 chassis switch and
must be installed for switch operation. The Fabric module is the master blade for
the chassis.

Figure 2-11. P0973KG S-Series Network I/O Fabric Module

28
2. Site Planning B0700CE – Rev C

Figure 2-12. P0973KG, Rev. B, S-Series Network I/O Fabric Module

Figure 2-13. P0973LP, S-Series Network I/O Fabric Module

P0973KF S4 S-series Network I/O Module


The P0973KF S-series network I/O module has 48 1000Base-X compliant front panel ports that
support a variety of optional Small Form Factor Pluggable (SFP) Gigabit connections using
optional Mini-Gigabit Interface Cards (MGBICs). The SFP port slots enable you to install a mix-
and match number of SFPs to meet a need for various Gigabit or Megabit Ethernet connections.
There is also a slot for an optional network option module P0973KH (NOM).

NOTE
The P0973KF blade can only be installed in slots 1 and 4 of the S4 chassis switch.

Figure 2-14. P0973KF S-series Network I/O Module

Network Option Module (P0973KH)


The Network Option Module (P0973KH) is an optional uplink card that can be installed on an
Invensys-supplied S-series module. It provides twelve SFP ports for MGBICs.

29
B0700CE – Rev C 2. Site Planning

Figure 2-15. Network Option Module (NOM) (P0973KH)

The 100Base-FX M-GBIC (P0973JE) may be installed in the Network Option Module.

Port LEDs
On the S-series modules, you can view the receive and transmit activity on the RX and TX LEDs
for the SFP, and SFP+ ports (P0973KF, P0973KG, P0973KH and P0973KK).

3 - SFP/SFP+ RX LED for bottom port 5 - SFP/SFP+ TX LED for bottom port
4 - SFP/SFP+ RX LED for top port 6 - SFP/SFP+ TX LED for top port

Figure 2-16. Network I/O Module LEDs (P0973KF, P0973KG, P0973KH and P0973KK)

These LEDs allow you to quickly observe network status for diagnosing switch and network prob-
lems, as described in the following tables.

30
2. Site Planning B0700CE – Rev C

Table 2-11. Port LEDs for S-Series Switch Modules

LED Color State Recommended Action


RX (Receive) None No link. No activity. Port None
enabled or disabled.
Green Solid. Link present, port None
enabled, no traffic is being
received by the interface.
Yellow Blinking. Link present, None
port enabled, traffic is
being received by the
interface.
Tx (Transmit) None Port enabled, but no If you know the port should be
activity. active and is not, contact Invensys
for technical support.
Green Blinking. Indicates data None
transmission activity.
Flashing frequency indi-
cates the data rate.
Yellow Solid. Fault or error None, unless activity is high; in
(collision). which case, check for network
configuration problems or a
defective device.

I/O Fabric Module and I/O Module LEDs


On the S-Series I/O Fabric modules and I/O modules, you can view the LEDs for the CPU and
management (MGMT) as shown in Figure 2-17. The Power over Ethernet (POE) feature is not
supported on The MESH Control Network, so its LED can be disregarded.

31
B0700CE – Rev C 2. Site Planning

1 - Power over Ethernet (POE) LED


2 - CPU LED
3 - Management LED
Figure 2-17. I/O Fabric Module and I/O Module LEDs

32
2. Site Planning B0700CE – Rev C

Table 2-12. I/O Fabric Module and I/O Module System LEDs

LED Color State Recommended Action


CPU Off Power off. Ensure chassis has adequate
power.
Amber Blinking. Device in None.
bootup process.

Solid. Testing. If the LED remains amber for


several minutes, contact Invensys
for technical support.
Green Blinking. Image starts None.
running.

Solid. Functional. None.


Red Solid. Processor in reset. None.
Green and Blinking. Indicates that None. This state is activated when
Amber the module is in the pro- the RESET button is pressed for
cess of shutting down. less than one second to start an
orderly shutdown.
Amber and Alternating (67% on, While in this state, you have 60
Off 33% off). Indicates a seconds before the module will
shutdown is complete. reboot.
The indication will hold
for 60 seconds then auto-
matically restart.
MGMT None This module is not the None.
management module.
Green Solid. This module is the None.
designated management
module.
Amber Amber. This is a tempo- None.
rary indication that the
module is saving data.

33
B0700CE – Rev C 2. Site Planning

SSA Chassis Managed Switch (P0973KK/LN) System LEDs


On the SSA Chassis managed switch (P0973KK/LN), you can view the LEDs for managing the
switch as shown in Figure 2-18.
The Power over Ethernet (POE) feature is not supported on The MESH Control Network, so its
LED can be disregarded.

Figure 2-18. SSA Chassis Managed Switch (P0973KK/LN) System LEDs

Table 2-13. SSA Chassis Managed Switch (P0973KK/LN) System LEDs

LED Color State Recommended Action


Fan Off Fans are off or booting up. None.
Green All fans are operating normally. None.
Amber One fan has failed. Replace the failed fan.
Red One or more of the following con- Check the CLI to determine the
ditions has occurred: exact condition of the fans. Use
♦ Temperature is out of range. the show system command.
♦ The fan controller has failed. If the fans have failed, replace the
♦ Two or more fans have failed. fans

34
2. Site Planning B0700CE – Rev C

Table 2-13. SSA Chassis Managed Switch (P0973KK/LN) System LEDs (Continued)

LED Color State Recommended Action


CPU Off Power off. Ensure chassis has adequate
power.
Amber Blinking. Device in bootup process. None.

Solid. Testing.
If the LED remains amber for
several minutes, contact Invensys
for technical support.
Green Blinking. Image starts running. None.

Solid. Functional.
None.
Red Solid. Processor in reset. None.
Green Blinking. Indicates that the SSA None. This state is activated when
and switch is in the process of shutting the RESET button is pressed for
Amber down. less than one second to start an
orderly shutdown.
Amber Alternating (67% on, 33% off). While in this state, you have 60
and Off Indicates a shutdown is complete. seconds before the module will
The indication will hold for 60 sec- reboot.
onds then automatically restart.
PWR Off The SSA is not receiving power Ensure the power cords are
(Cont. from the power supplies. plugged in and power is available
below) at the source. Contact Invensys
for technical support.
Green Functional. Indicates one of the None
following conditions:
♦ A single power supply is pres-
ent and operating normally.
♦ Two power supplies are present
and operating normally.

35
B0700CE – Rev C 2. Site Planning

Table 2-13. SSA Chassis Managed Switch (P0973KK/LN) System LEDs (Continued)

LED Color State Recommended Action


PWR Amber One of the following conditions has Ensure the power cords are
(Cont.) occurred: plugged in and power is available
♦ Two power supplies are present at the source. Contact Invensys
but only one is operating nor- for technical support.
mally while the other is not
connected.
♦ Two power supplies are present
but only one is operating nor-
mally while the other indicates
a fault.
♦ Both power supplies are faulty
but the SSA is still receiving
power.
♦ Power supplies are operating in
additive (non-redundant)
mode.
♦ Other internal fault.
Blue Solid. Indicates, in PoE mode (not None.
supported), that two 625W power
supplies are installed.
Blue/ Indicates, in PoE mode (not sup- None.
Green ported), that one 625W power
supply is installed.
White Solid. Indicates, in PoE mode (not None.
supported), that two 1000W power
supplies are installed.
White/ Indicates, in PoE mode (not sup- None.
Green ported), that one 1000W power
supply is installed.
Blue/ Indicates, in PoE mode (not sup- None.
White ported), that 625W and 1000W
power supplies are installed.

36
3. Installation
This chapter describes the steps necessary to install the S-series Chassis switches as part of The
MESH Control Network.
Installation of the Ethernet switches in The MESH Control Network consists of locating the
individual components and then making connections between them using fiber optic or copper
cable.

Installing S-series Chassis Switches


The following paragraphs provide instructions for installing the S-series Chassis switches as part
of The MESH Control Network.

Ethernet Switch Installation


The S-series Chassis switches are designed to be placed on a flat, level surface. Alternatively, the
switches may be mounted in a rack using the supplied mounting brackets. Make sure that the
environment in which the switch is located meets the switch’s environmental operating specifica-
tions, especially heat and humidity. Refer to the documentation included with the switch for
detailed installation instructions and operating specifications.

Installing Optional ISL Uplink Modules


Optional ISL uplink modules (NOM P0973KH) are available only for the S4 Chassis switch (see
“S4 Chassis Managed Switch (P0973KD)” on page 5) and should be installed before the switch is
connected to The MESH Control Network.
Refer to the documentation included with the uplink modules (P0973KH) and the S4 Chassis
managed switch (P0973KD) for instructions on installing the modules.

! CAUTION
If a blade, uplink expansion module, or GBIC port is to be added or removed from
the switch configuration, a complete software reconfiguration of the switch is neces-
sary after it is installed or removed.

Installing Optional Redundant Power Supplies


Optional redundant power supplies (P0973KL) are available for the SSA Chassis switch
(P0973KL) (see “SSA Chassis Managed Switch (P0973KK/LN)” on page 1) and optional redun-
dant power supplies (P0973KE or P0973LJ) for the S4 Chassis switch (P0973KE) (see “S4 Chas-
sis Managed Switch (P0973KD)” on page 5); redundant power supplies (P0973KE or P0973LJ)
should be installed before the switch is connected to The MESH Control Network.
Refer to the documentation included with the switch for instructions on installing redundant
power supplies.

37
B0700CE – Rev C 3. Installation

Configuring the Switches


All managed switches require configuration before they are added to The MESH Control Net-
work.
Refer to “Switch Configuration” on page 39.

Connecting The MESH Control Network Components


Refer to The MESH Control Network Architecture Guide (B0700AZ) for details on connecting
these Ethernet switches as part of The MESH Control Network.

38
4. Switch Configuration
This chapter describes the steps necessary to configure the S-series Chassis switches as part of The
MESH Control Network.

Configuring Ethernet Switches


There are two methods available to configure these switches:
♦ The MESH Network Switch Configurator Application Software, and
♦ Command Line Interface (CLI).

The MESH Network Switch Configurator Application Software


(SCAS)
The MESH Network Switch Configurator Application Software (SCAS) was created for Invensys
customers as a configuration tool for qualified Ethernet switches in The MESH Control Net-
work. It reduces the repetitive Command Line Interface (CLI) command entries which are
required to configure the control network switches, by allowing users to customize configuration
files that define a set of CLI commands downloadable via the serial port. SCAS supports the S-
series Chassis switches and their uplink modules:
Refer to The MESH Control Network Operation, and Switch Installation and Configuration Guide
(B0700CA) document for information on how to use SCAS. The latest version of the tool and its
documentation are available on the Global Customer Support Center web site at
http://support.ips.invensys.com
After logging in to the web page, go to: Support -> Foxboro -> Product Information ->
Briefs/Product Releases -> then select MESH Network Switches Documentation
Details on downloading SCAS are provided in The MESH Control Network Operation, and Switch
Installation and Configuration Guide (B0700CA) document, in the section “Getting the Latest
Configuration Revision”.
Customers are encouraged to download and use the latest documentation and configurator tools
on the Global Customer Support Center web site.

Command Line Interface (CLI) Entries


This chapter provides instructions and specific CLI entries that must be typed and entered into
the switches for proper operation of the The MESH Control Network.

Logging In
By default, the S-series switches are configured with three user login accounts:
♦ ro for Read-Only access
♦ rw for Read-Write access
♦ admin for superuser access to all modifiable parameters.

39
B0700CE – Rev C 4. Switch Configuration

The default password is set to a blank string. For information on changing these default settings,
refer to The MESH Control Network Operation, and Switch Installation and Configuration Guide
(B0700CA, Rev. H or later) document, in the section “Changing Switch Password and Settings.”

Configuration Requirements
All managed switches require configuration before they are added to The MESH Control Net-
work.

! CAUTION
Switches should be configured off line before they are connected to The MESH
Control Network.

Configuration of managed switches is accomplished by connecting a terminal (or a computer run-


ning terminal emulation software) to the serial console port on the switch and using the switch’s
resident management software to set the parameters. Refer to “Connecting Ethernet Switch to the
PC” on page 41. For customized switch configurations, refer to the documentation that comes
with the switch for command line entry instructions on configuring a specific switch model.
To avoid the possibility of address conflicts, IP addresses for managed switches are automatically
assigned by the system configurator (SysDef or IACC). Once the configurator has selected the IP
addresses, each switch must be configured with its IP address (refer to “The MESH Control Net-
work Addresses” in The MESH Control Network Architecture Guide (B0700AZ)). For information
on using the system configurator, refer to:
♦ System Definition: A Step-by-Step Procedure (B0193WQ) or
♦ I/A Series Configuration Component (IACC) User's Guide (B0700FE).
While using SysDef record the address of the station monitoring the switch. There is a switch
parameter named TRAP under the SNMP Configuration menu that you should set based on this
IP address.

! CAUTION
Do not mirror active ports to other used ports. Doing so results in an excessive
increase in the traffic levels routed by the switches.

NOTE
When adding a switch or blade to the network, clear the NVRAM, or return the
switch to the Factory Default Configuration to obtain default settings before con-
figuring the switch.

NOTE
Uplink ports should be installed and configured first. Otherwise, configured infor-
mation may be lost when the uplink ports are installed.

40
4. Switch Configuration B0700CE – Rev C

This chapter provides generic configuration information that applies to all Ethernet switches and
specific procedures for the switches that have been tested and qualified by Invensys for use with
Foxboro Evo Process Automation Systems. The configuration information is presented as follows:
♦ “Generic Switch Parameters” on page 43
♦ “Connecting Ethernet Switch to the PC” on page 41
♦ “Configuring the S-series Chassis Switches” on page 44.

Connecting Ethernet Switch to the PC


The Network Administrator computer (laptop recommended) needs to be connected to the
switch’s CLI port (for example, serial port) through the computer’s COM port using the serial
cable provided with the switch.
Figure 4-1 shows the connection from a PC to the Ethernet switches.
For the S-series Chassis switches, a CAT 5 cable with RJ-45 plugs is connected to the CLI port on
the blade. A 9-pin D connector to RJ-45 plug adaptor is required to connect the switch to the PC.
The cable and adaptor/connectors are customer-supplied.

SSA and S4 COM Port Connection

SSA Chassis Switch (P0973KK/LN) RJ-45 To


RJ-45 9D Adaptor
Connector
Customer
Supplied
Laptop

RJ-45
Connector

S4 Chassis Switch (P0973KD)


Figure 4-1. Connecting PC to Ethernet Switches

41
B0700CE – Rev C 4. Switch Configuration

The RS-232 console port uses a standard 8-pin RJ-45 connector. The pinout is listed in
Table 4-1. A RJ-45 to DB9 adapter is provided with the switch; a RJ-45 to RJ-45 straight-
through console cable is customer-supplied (not provided with the switch).

Table 4-1. Console Port Pinout

Pin Connection
1 TXD
2 CTS
3 Unused
4 RXD
5 GND
6 RTS
7 Unused
8 Unused

42
4. Switch Configuration B0700CE – Rev C

Generic Switch Parameters


Table 4-2 lists the generic and some specific switch parameters that should be configured for all
Ethernet switches that are used in The MESH Control Network.

Table 4-2. Generic Switch Configuration Parameters for V 8.1 and Later Releases

Parameter Value/Comment
NVRAM for all switches/blades Clear memory prior to conducting a switch configuration.
(parameter for E-series switches only)
IP Address Set the IP address of the switch to the IP address defined
by the system configurator
Subnet Mask Set the subnet mask of the switch to 255.255.0.0
Switch Identification Set the identification of the switch to the letterbug (name)
you assigned to the switch during system configuration
Auto-negotiation mode with no flow For copper ports, set to 100 Mb full duplex with no auto-
control, Copper ports negotiation and with no flow control.
Auto-negotiation mode with no flow For fiber ports, set to 100 Base Full Duplex mode with no
control, Fiber ports flow control.
Flow control Disable full and half-duplex flow control (IEEE 802.3x)
on all the switch ports
Rapid Spanning Tree Protocol Enable RSTP (IEEE 802.1w). It may be enabled by default
(RSTP) on some switches.
Switch Priority For primary root and backup root switches (as defined by
network architecture), set the switch priority to 32000 or
28672. All other edge switches, set switch priority to
32768.
Port Mirroring Disabled, by default, unless you intend to execute specific
diagnostics
Spanning Tree Edge Port All 100 Mb “end device” ports (FCP,ZCP, workstations
AdminEdge set to True (Enabled), all 1 Gb/100 Mb
“uplink” ports AdminEdge set to False (Disabled).
Uplink port Auto-negotiation All 1 Gb/100Mb “uplink” ports set Auto-negotiation to
Enabled.
SNMP Trap Set the SNMP trap to the primary and alternate port
addresses (151.128.152.XXX and 151.128.24.XXX) of
the workstation (System Monitor Host) that is monitoring
the switch.
Broadcast Rate Limit 500 packets per second for 100 Mb ports and 5000 packets
per second for 1 Gb ports.
Link Aggregation Control Protocol Disable LACP
(LACP)
Gigabit Ports Active Mode
Global GVRP State Disabled
Unused Ports Disable all unused ports

43
B0700CE – Rev C 4. Switch Configuration

Edge Switches
An edge switch is a switch which will not be configured as a root or backup bridge. The edge
switch usually interfaces Foxboro Evo devices (Control Processors, FCMs, and so forth) to the
root switches. Multiple root switches can be configured to take over as roots by adjusting the
Bridge Priority Value. However, normally only two roots exist, primary and backup root switch,
all other switches are defined as edge switches.

Configuring the S-series Chassis Switches


The S-series Chassis switches SSA (P0973KK/LN) and S4 (P0973KD) must be booted with a
supported version of Foxboro Evo qualified and compatible firmware. (Refer to the Appendix
“Qualified Switch Firmware Compatibilities Matrix” in The MESH Control Network Operation,
and Switch Installation and Configuration Guide (B0700CA) for supported versions.)
To configure the Chassis switches SSA (P0973KK/LN), and S4 (P0973KD), it is recommended
that you refer to The MESH Control Network Operation, and Switch Installation and Configuration
Guide (B0700CA) and use the latest Switch Configurator Application Software (SCAS) to config-
ure this switch.

Resetting Password
The switch’s Command Line Interface (CLI) locks out after three incorrect password attempts
and remains locked out for 15 minutes. The Reset Password jumper remains non-functional
for those 15 minutes.

NOTE
Power must be applied to the unit before the 15 minute lockout can expire.

If you forget the switch’s login password, use the Reset Password jumper as described in the fol-
lowing procedure.

44
4. Switch Configuration B0700CE – Rev C

1 - Switch 7 2 - Switch 8
Figure 4-2. P0973KD Reset Password Jumper Location (P0973KG Network I/O Fabric Module
Slot 2)

1 - Switch 8 2 - Switch 7
Figure 4-3. P0973KK Reset Password Jumper Location

45
B0700CE – Rev C 4. Switch Configuration

To reset the S-series switch password, proceed as follows:


1. In Figure 4-2 and Figure 4-3, changing the position of jumper switch 8 clears the
admin password and restores the factory default password on the next power-up of the
module. Once the module resets, you can either use the factory default settings or
reenter your own password.
2. Login to the device management (see “Logging In” on page 39). Now, you can login
to the switch via the console port and assign a new password. For information on
changing the password settings, refer to The MESH Control Network Operation, and
Switch Installation and Configuration Guide (B0700CA, Rev. H or later) document, in
the section “Changing Switch Password and Settings.”

Maintenance
For all maintenance information, refer to The MESH Control Network Architecture Guide
(B0700AZ).

46
Appendix A. Ethernet Switch
Interconnection Diagrams
This appendix provides cabling diagrams for interconnecting Ethernet switches.
Multiple options are available for connecting Ethernet switches to each other. The figures in this
chapter illustrate the way in which the switches can be connected and list the parts and cables nec-
essary. The illustrations are as follows:
♦ “SSA Chassis Switch (P0973KK/LN) Uplink Cabling Options” on page 48
(Figure A-1)
♦ “S4 Chassis Switch (P0973KD) Uplink Cabling Options” on page 49 (Figure A-2)

47
B0700CE – Rev C Appendix A. Ethernet Switch Interconnection Diagrams

TO NEXT SWITCH
TO NEXT TO NEXT TO NEXT (Requires matching
P0973JB/JC/KM/K TO NEXT SWITCH'S
SWITCH SWITCH SWITCH
N/KQ/KR MGBIC) UPLINK MODULE TO END DEVICE

LC LC LC LC LC
LC

Simplex Single Mode Fiber (customer supplied)


10 Km, 40 Km, 120 Km (max) w/LC connectors
TO NEXT SWITCH'S
550 meters (max) w/LC connectors

UPLINK PORT

10 Km/0.5 Km (max) w/LC connectors

1000/2000m (max) w/LC connectors


1000Base-LX/LH, MMF

customer supplied

1000Base-BX, S-SMF
1000Base-SX, MMF

1000Base-ZX, SMF
Cable Group D

Cable Group D

1000Base-LX, SMF/MMF
See Note 2

Cable Group B
80 km (max)

customer supplied
2 km (max)

customer supplied

1000Base-T, Cat5 w/RJ-45


100Base-FX, MMF

See Note 2

100 m (max)
LC LC LC LC LC
LC

RJ-45
LC LC LC LC LC LC
P0972WT - See Note 2

Uplink MGBIC Module


Uplink MGBIC Module

Uplink MGBIC Module

1000Base-T w/RJ-45
1000BaseSX/LX w/LC
1000Base-LX/LH w/LC
Uplink MGBIC Module

Uplink MGBIC Module

Uplink MGBIC Module

Uplink MGBIC Module


1000Base-SX w/LC

/KM/KN/KQ/KR

1000Base-BX w/LC
1000Base-LX w/LC

P0973JB/JC

P0972YL
100BaseFXw/LC
P0972WU
P0972YQ

P0973JE
P0973FT

Note 1: The choice of configuration depends upon


OR

GREEN
C OPPER (ie, Cu) ETHERNET CABLE
the uplink cable length or cable type
needed (i.e., copper or fiber). MAGENTA
FIBER (ie, FO) ETHERNET CABLE

Note 2: Refer to the table "Operating Range for


Mini-GBIC Modules" in Chapter 2 for the
allowable ranges for the P0972WT and Cable Group D (Fiber)
P0973JE modules. (w/LC-LC connectors)
P0972UN = 0.5 m (gray)
P0972VG = 0.5 m
(orange)
P0973KK/LN P0972UJ = 1 m
SSA S-Series Switch P0972TN = 3 m
P0972TP = 15 m
P0972TQ = 50 m
User supplied if > 50 m
CHASSIS SLOT Cable Group B (Cu )
(w/RJ-45 connectors)
P0971XK = 3 meters
P0971XL = 15 m
P0972MR = 30 m
P0971XM = 50 m
P0971XN = 100 m

Figure A-1. SSA Chassis Switch (P0973KK/LN) Uplink Cabling Options

48
Appendix A. Ethernet Switch Interconnection Diagrams B0700CE – Rev C

TO NEXT SWITCH
TO NEXT TO NEXT TO NEXT (Requires matching
P0973JB/JC/KM/K TO NEXT SWITCH'S
SWITCH SWITCH SWITCH
N/KQ/KR MGBIC) UPLINK MODULE
TO END DEVICE

LC LC LC LC
LC LC

Simplex Single Mode Fiber (customer supplied)


10 Km, 40 Km, 120 Km (max) w/LC connectors
550 meters (max) w/LC connectors
TO NEXT SWITCH'S
UPLINK PORT

10 Km/0.5 Km (max) w/LC connectors

1000/2000m (max) w/LC connectors


1000Base-LX/LH, MMF

customer supplied
1000Base-SX, MMF

1000Base-ZX, SMF

1000Base-BX, SMF
Cable Group D

Cable Group D
See Note 3

1000Base-LX, SMF/MMF

Cable Group B
80 km (max)
2 km (max)

customer supplied

customer supplied

1000Base-T, Cat5 w/RJ-45


100Base-FX, MMF

See Note 3

100 m (max)
LC LC LC LC LC
LC

P0973JB/JC/KM/KN/KQ/KR
RJ-45
LC LC LC LC LC LC
P0972WT - See Note 3

Uplink MGBIC Module

Uplink MGBIC Module


Uplink MGBIC Module

Uplink MGBIC Module

1000Base-T w/RJ-45
1000BaseSX/LX w/LC
1000Base-LX/LH w/LC

1000Base-BX w/LC
Uplink MGBIC Module

Uplink MGBIC Module

Uplink MGBIC Module


1000Base-SX w/LC

1000Base-LX w/LC

See Note 2

P0972YL
100BaseFXw/LC
P0972WU
P0972YQ

P0973JE
P0973FT

Note 1: The choice of configuration depends upon OR GREEN C OPPER (ie, Cu) ETHERNET CABLE
the uplink cable length or cable type
MAGENTA
needed (i.e., copper or fiber). FIBER (ie, FO) ETHERNET CABLE

Note 2: P0973JB/JC/KM/KN/KQ/KR may also


plug into the P0973KF and P0973KG
blades (shown in the P0973KD S4
Chassis switch). The P0973KG
blade can also support two (2)
P0973KH modules. P0973KH
1GB Uplink Module
Note 3: Refer to the table "Operating Range 12 SFP Module Slots
for Mini-GBIC Modules" in Chapter 2
for the allowable ranges for the
P0972WT and P0973JE modules.

P0973KF SLOT 4
FAN ASSEMBLY P0973KT

NOT USED

P0973KD P0973KG/LP SLOT 2 Cable Group D (Fiber)


(w/LC-LC connectors)
S4 Chassis Switch
Cable Group B (Cu ) P0972UN = 0.5 m (gray)
(w/RJ-45 connectors) P0972VG = 0.5 m (orange)
P0973KF SLOT 1 P0971XK = 3 meters P0972UJ = 1 m
P0971XL = 15 m P0972TN = 3 m
REPAIR FAN P0972MR = 30 m P0972TP = 15 m
ASSY P0971XM = 50 m P0972TQ = 50 m
P0973KT P0971XN = 100 m User supplied if > 50 m

POWER SUPPLY P0973KE or P0973LJ

Figure A-2. S4 Chassis Switch (P0973KD) Uplink Cabling Options

49
B0700CE – Rev C Appendix A. Ethernet Switch Interconnection Diagrams

50
Index
C
Cable
specifications 27
Chassis switch
configuration 44
Configuration
Chassis switch 44
Ethernet switches 38, 39

E
Ethernet switches
configuration 38, 39
installation 37

I
Installation
Ethernet switches 37

N
Network components
connecting 38
installing 37

S
Specifications
cable 27

51
Invensys
10900 Equity Drive
Houston, TX 77041
United States of America
http://www.invensys.com

Global Customer Support


Inside U.S.: 1-866-746-6477
Outside U.S.: 1-508-549-2424 or contact your
local Invensys representative.
Website: http://support.ips.invensys.com

You might also like