G65QS - Canopy Set: PRIME KVA: 63.00 - STANDBY KVA 71.00 2750mm

This document provides specifications for a G65QS canopy set diesel generator including its electrical ratings, engine details, alternator details, starting system, and fuel system. Key specs include a prime power of 63kVA, standby power of 71kVA, 4 cylinder 4.4L turbocharged diesel engine, 1500RPM and 1800RPM operation, IP23 alternator, and standard 14L fuel tank.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
44 views4 pages

G65QS - Canopy Set: PRIME KVA: 63.00 - STANDBY KVA 71.00 2750mm

This document provides specifications for a G65QS canopy set diesel generator including its electrical ratings, engine details, alternator details, starting system, and fuel system. Key specs include a prime power of 63kVA, standby power of 71kVA, 4 cylinder 4.4L turbocharged diesel engine, 1500RPM and 1800RPM operation, IP23 alternator, and standard 14L fuel tank.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

G65QS | Canopy Set

PRIME KVA: 63.00| STANDBY KVA 71.00

2750mm

1830mm

1140mm

DIESEL GENERATOR FUEL OPTIMISED

ELECTRICAL
Prime Standby
Minimum ATP
Frequency (Hz) Phases Voltage (V) kVA kW kVA kW MCB Rating (A) Rated Speed (RPM)
Rating (A)
50 3 400/230V 63.00 50.40 71.00 56.80 80.00 80.00 1500
60 3 380/220V 63.00 50.40 69.00 55.20 100.00 125.00 1800
60 3 220/127V 71.00 56.80 78.00 62.40 250.00 250.00 1800
60 3 480/277V 75.50 60.40 83.00 66.40 125.00 125.00 1800

POWER FACTOR MAXIMUM LOAD IMPACT*


3 Phase 0.8 kVA 58.70
1 Phase 1 kW 47.00
*With 20% voltage and 10% frequency deviation @ 50Hz, 400V

ALL RATINGS ARE TO STANDARD REFERENCE CONDITIONS ISO 8528

Prime: This rating is for the supply of continuous electrical power, at variable load, in lieu of commercially purchase power. There is no limitation on the annual hours of operation and 10% over load power can be supplied for 1 hour
in 12.
Standby: This rating is for the supply of continuous electrical power, at variable load, in the event of a utility power failure. No overload is permitted.
Stage IIIa models are only emissions compliant at 50Hz Prime Power in accordance with 97-68EC.

JCB GENERATOR TECHNICAL SPECIFICATIONS. Tel: +44 (0)1889 590312. www.jcbgenerators.com. JCB reserves the right to change specifications without notice. Illustrations shown may include optional equipment and accessories.
QS_G65QS_EN - Issued: 29/07/2015 15:10:54
G65QS | Canopy Set
PRIME KVA: 63.00| STANDBY KVA: 71.00

CANOPY/SKID ENGINE
Lockable Maintenance Access Doors ● 1500 RPM
Control Panel Viewing Window ● Output Rating (PRP) kW 62.00
Fork Pockets ∆ Output Rating (Standby) kW 68.20
Single Lift Point ∆ 1800 RPM
Bunding ∆ Output Rating (PRP) kW 75.00
Open Frame x Output Rating (Standby) kW 82.50
High Density Fire Retardant Foam ●
Manufacturer and Model JCB GTC-1 S2
Yellow Paint ●
Fuel Diesel
White Paint ∆
Injection Direct
Standard: ● Not Available: x Optional: ∆
Aspiration Turbo Charged
ALTERNATOR ECO 32 2L/4 Cylinders 4
Bore and Stroke mm 103x 132
Poles 4
Displacement L 4.399
Winding Connections Star
Insulation Class H Cooling Water
Enclosure IP23 Engine Oil Specification API CH4
Exciter System Self-regulating brushless Compression Ratio 17.5 : 1
Engine Oil Capacity L 14.00
Voltage Regulator AVR
Coolant Capacity L 16.00
Steady State Voltage Regulation +/- 1.0%
Bearing Single bearing sealed Governor Mechanical
Two stage with restriction indicatorSingle
Coupling Flexible disc Air Filter
paper element
Cooling Direct drive centrifugal blower fan Engine Oil Consumption 100% Load 0.1% of fuel consumed
Coating Winding Protection Grey FUEL SYSTEM

STARTING SYSTEM Diesel Specification EN590


Standard Fuel Tank Capacity L 285
Starter Motor kW 4.20
Battery Capacity Ah 120120
Number of Batteries 1
Auxiliary Voltage V 12

JCB GENERATOR TECHNICAL SPECIFICATIONS. Tel: +44 (0)1889 590312. www.jcbgenerators.com. JCB reserves the right to change specifications without notice. Illustrations shown may include optional equipment and accessories.
QS_G65QS_EN - Issued: 29/07/2015 15:10:54
G65QS | Canopy Set
PRIME KVA: 63.00| STANDBY KVA 71.00

FUEL CONSUMPTION MECHANICAL FEATURES


100% Load Prime L/h 14.10 Cooling Pack ●
75% Load Prime L/h 10.60 Air Filter ●
50Hz
50% Load Prime L/h 8.20 Mechanical Governor ●
100% Load Standby L/h 15.30 Low Oil Pressure Switch ●
100% Load Prime L/h 17.60 Coolant Temperature Sender ●
75% Load Prime L/h 13.30 Oil Temperature Sender ●
60Hz
50% Load Prime L/h 10.30 Radiator Guards ●
100% Load Standby L/h 19.10 Hot Component Guards ∆
Manual Oil Drain Pump (Canopy) ∆
EXHAUST SYSTEM
Water Jacket Heater ∆
O
Maximum Temperature 100% Standby C 542.00 Pre-Filter with Separator ●
Exhaust Gas Flow 100% Standby m3/min 50Hz 0.50 Fuel Level Sender ●
Maximum Allowed Back Pressure mbar 100.00 Internal Fuel Fill (Belly Tank) ●
O
Maximum Temperature 100% Standby C 478.00 3 Way Fuel Valve ∆
Exhaust Gas Flow 100% Standby m3/min 60Hz 0.50 Residential Silencer ●
Maximum Allowed Back Pressure mbar 100.00 Industrial Silencer x
Exhaust Flange Size mm - Standard: ● Not Available: x Optional: ∆

AIR SYSTEM
Intake Air Flow 100% Standby m3/h 367.00
Total Cooling Air Flow 100% Standby m3/s 50Hz 198.00
Alternator Fan Airflow m3/s -13.00
Intake Air Flow 100% Standby m3/h -410.00
Total Cooling Air Flow 100% Standby m3/s 60Hz 198.00
Alternator Fan Airflow m3/s -13.00

SOUND PRESSURE (CANOPY ONLY)


LpA (7m) 50Hz dB(A) 66
LpA (7m) 60Hz dB(A) -

JCB GENERATOR TECHNICAL SPECIFICATIONS. Tel: +44 (0)1889 590312. www.jcbgenerators.com. JCB reserves the right to change specifications without notice. Illustrations shown may include optional equipment and accessories.
QS_G65QS_EN - Issued: 29/07/2015 15:10:54
G65QS | Canopy Set
PRIME KVA: 63.00| STANDBY KVA 71.00

ELECTRICAL FEATURES JCB COMMUNICATION AND CONTROL


AVR DSR ● 4510 x
AVR DER x 4520 ●
Winding Protection Standard x Standard: ● Not Available: x Optional: ∆
Winding Protection Standard + x
Winding Protection Grey ● WEIGHT AND DIMENSIONS
Winding Protection Total ∆ Length mm 2750
Winding Protection Total + ∆ Width mm 1140
MAUX ● Height mm 1830
PMG ∆ Shipping Volume (sea ready) m3 5.32
Anti-Condensation Heater ∆ Weight* Kg 1590.00
*Standard build with all fluids except fuel
3 Pole Moulded Case Circuit Breaker ●
4 Pole Moulded Case Circuit Breaker ∆ OPTIONAL CE PACK
Earth Leakage Protection (Shunt Trip) ∆ EMC Certification ●
Preparation for Earth Spike ● Hot Guards ●
Optional Voltages ∆ Belt Guards ●
Remote Screen ∆ Earth Leakage Relay ●
Emergency Stop Button ● Sound Power Decal ●
External Emergency Stop Button ● EU Declaration for Engine Emissions ●
Standard: ● Not Available: x Optional: ∆ Complete Machine Declaration of Conformity ●
Standard: ● Not Available: x Optional: ∆
BATTERY FEATURES
Battery Isolator ∆ REFERENCE STANDARDS
Battery Type Lead Acid
JCB Generators are CE certified and conform to the following Directives (subject to a country requiring such standard):
Battery Size (Ah) 120
Number of Batteries 1  EN 12100, EN13857, EN60204
Battery Charger ∆  2006/42/CE Machinery safety
 2006/95/EC Low voltage
Standard: ● Not Available: x Optional: ∆  2004/108/CE Electromagnetic compatibility
 2000/14/EC Sound Power Level (amended by 2005/88/EC)
 97/68/EC Emissions(amended by 2002/88/EC & 2004/26/EC)
 Power according to ISO 8528 and ISO 3046
 Ambient reference conditions 1000mbar, 25°C, 30% relative humidity ISO3046
Information based on standard specification equipment unless otherwise stated.