This document summarizes the features of a three-phase thermal plus overcurrent plus earth fault relay suitable for protection of transformers and power systems. The relay provides three-phase fault protection, three levels of earth fault protection, two thermal elements, two levels of negative sequence protection, one I2t protection level, and breaker failure protection. It computes direct and negative sequence currents and has selectable 1A or 5A current ratings. Programming options include settings for current levels, time delays, and operation curves. Real-time measurements and demand recording are provided.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
138 views3 pages

IM30T DataSheet - en 71

This document summarizes the features of a three-phase thermal plus overcurrent plus earth fault relay suitable for protection of transformers and power systems. The relay provides three-phase fault protection, three levels of earth fault protection, two thermal elements, two levels of negative sequence protection, one I2t protection level, and breaker failure protection. It computes direct and negative sequence currents and has selectable 1A or 5A current ratings. Programming options include settings for current levels, time delays, and operation curves. Real-time measurements and demand recording are provided.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

M

LINE

IM30-T NC. N7-R1

THREE-PHASE THERMAL + OVERCURRENT +


EARTH FAULT RELAY

46, 49, 50/51, 50N/51N, 51BF, 68, I2t


T> I>->> I2t Io>->>

· Three Phase-Fault levels PROG/ BLOCK BR. Is>->>


I.R.F. INPUT FAIL.

· Three Earth-Fault levels


MICROELETTRICA SCIENTIFICA I/In 100%
· Two Thermal image elements with prealarm MILANO ITALIA

· Two Negative Sequence current levels MODE SELECT


+

· One I2t level MULTIFUNCTION


THERMAL +
_
· Blocking Output and Blocking Input for pilot wire OVERCURRENT +
EARTH FAULT
PROG.
RELAY TYPE
selectivity coordination IM30-T

· Breaker Failure protection ENTET/RESET

· Modbus Communication Protocol


· UL / CSA listed

Three-phase thermal plus overcurrent plus earth fault relay, suitable for protection of transformers and
HV & MV, power transmission and distribution systems.

The relay computes the direct and the negative sequence components of the current system for effective
negative sequence current protection.

Selectable 1 or 5 A rating for phase as well as neutral inputs.

The neutral current input circuits include a 3rd harmonic active filter.

Real Time Measurements = IA - IB - IC - Io - Tw - Tf - I1 - I2


Maximum Demand and Inrush Recording = IA - IB - IC - Io - Tw - Tf - I2

Programmable Input Quantities


Fn = System frequency : (50 - 60)Hz

In = Rated primary current of phase CTs : (0 - 9999)A, step 1A

On = Rated primary current of earth fault detection CTs : (0 - 9999)A, step 1A

1F - 50/51 (I>): First Overcurrent Element


- Current setting range : I> = (0.25 - 4)In, step 0.01In
- Instantaneous output : £ 0.03s
- Definite trip time delay in the independent time operation mode tI> = (0.05 - 30)s, step 0.01s
- Trip time delay at 10x[I>] in inverse time operation modes }
Operation mode F(I>): F(I>) = D : Independent definite time F(I>) = MI : IEEE moderate inverse time curve
F(I>) = A : IEC curve type A F(I>) = VI : IEEE very inverse time curve
F(I>) = B : IEC curve type B F(I>) = I : IEEE inverse time curve
F(I>) = C : IEC curve type C F(I>) = EI : IEEE extremely inverse time curve
F(I>) = SI : IEEE standard inverse time curve
NC.N7- RI IM30-T

2F - 50/51 (I>>): Second Overcurrent Element


- Current setting range : I>> = (0.5 - 40)In, step 0.1In
- Instantaneous output : £ 0.03s
- Independent time delay : tI>> = (0.05 - 3)s, step 0.01s
- Automatic doubling of level I>> on inrush : I>>x2 = ON/OFF

3F - 50/51 (I>>>): Third Overcurrent Element


- Current setting range : I>>> = (0.5 - 40)In, step 0.1In
- Instantaneous output : £ 0.03s

1F - 50N/51N (O>): First Earth Fault Element


- Current setting range : O> = (0.02 - 0.4)On, step 0.01On
- Instantaneous output : £ 0.04s
}
- Definite trip time delay in the independent time operation mode tO> = (0.05 - 30)s, step 0.01s
- Trip time delay at 10x[O>] in inverse time operation modes
Operation mode F(O>): F(O>) = D : Independent definite time F(O>) = MI : IEEE moderate inverse time curve
F(O>) = A : IEC curve type A F(O>) = VI : IEEE very inverse time curve
F(O>) = B : IEC curve type B F(O>) = I : IEEE inverse time curve
F(O>) = C : IEC curve type C F(O>) = EI : IEEE extremely inverse time curve
F(O>) = SI : IEEE standard inverse time curve

2F - 50N/51N (O>>): Second Earth Fault Element


- Current setting range : O>> = (0.02 - 4)On, step 0.01On
- Instantaneous element : £ 0.04s
- Independent time delay : tO>> = (0.05 - 3)s, step 0.01s

3F - 50N/51N (O>>>): Third Earth Fault Element


- Current setting range : O>>> = (0.02 - 4)On, step 0.01On
- Instantaneous output : £ 0.04s

F49 : Thermal Image


- Rated thermal current : It = (0.5 - 2)In, step 0.01In
- Windings' warming up time constant : tw = (1 - 60)min, step 1min.
- Windings continuous admissible overload : Ibw = (1.05 - 1.5)It, step 0.01It
- Oil/Iron warming up time constant : tf = (10 - 400)min, step 1min.
- Temperature prealarm : Ta/n = (50 - 120)%Tn, step 1%Tn

1F - 46 : First Current Unbalance (Negative Sequence)


- Current setting range : 1Is = (0.1 - 0.8)It, step 0.1It
- Independent time delay : t1Is = (1 - 8)s, step 1s (t1Is = trip time @ Is = It)

2F - 46 : Second Current Unbalance (Negative Sequence)


- Current setting range : 2Is = (0.2 - 2)It, step 0.1It
- Independent time delay : t2Is = (0.05 - 3)s, step 0.01s

F I²t>: Inrush Energy


This element performs a max I²t protection; tripping takes place when I²t > (2It)²t2
- Starting level : I > 2It (It = Rated thermal current, same as for F49)
- Trip time delay @ I=2It : t2 = (0.1 - 10 - Dis)s, step 0.1s

Breaker Failure Element


- Trip time delay : tBF = (0.05 - 0.25)s, step 0.01s
IM30-T NC.N7-RI

Connexion Diagram

IM30-T

RS485 RS485

MS-SCE1358-R3 MS-SCE1434-R1
Standard Output Double Output

Ordering data

Power supply
0 Type 1 : 24 à 100 Vac et 24 à 125 Vdc ± 20 %.
0 Type 2 : 80 à 220 Vac et 90 à 250 Vdc ± 20 %.

Execution
0 Flush mounting
0 Surface mounting
0 Standard rack 19”3U

Rated input
0 In = 1 A
0 In = 5 A

Special request

Quantity

Quartier du Pavé Neuf, 49 rue de l’Université - F-93191 Noisy le Grand


Tél : + 33 1 48 15 09 09 - Fax : +33 1 43 05 08 24 - Email
- : [email protected] http : //www.microelettrica.com