DG SPEC D275D5 - 480 Liter
DG SPEC D275D5 - 480 Liter
DG SPEC D275D5 - 480 Liter
Model: D275D5
Powered by DOOSAN
Generator Specification
Performance Data
Service PRP (1) ESP (2)
Model D275D5
Power (kVA) 250 275
Engine brand Doosan
Power (kW) 200 220
Engine model P126TI
Rated speed ( r.p.m) 1500
Speed control type Electronic
Standard voltage (V) 400/230V
Phase 3
Rated at power factor(cos phi) 0.8
Control system Digital
Star ter motor voltage 24V
AU VE
RI
BURE
ISO 9001
TA S
BUREAU VERITAS
Certification
182 8
Frequency 50HZ
Engine speed (RPM) 1500
AGG Power gensets are compliant with ISO 9001 and CE standard, which include the
following directives: 100% standby power 66.2
·2006/42/EC Machinery safety. Fuel 58.1
100% prime power
·2006/95/EC Low voltage Consumption
·EN 60204-1: 2006+A1: 2009, EN ISO 12100: 2010, EN ISO 13849-1: 2008, EN 75% prime power 43.6
12601 : 2010 (g/kwh)
50% prime power 30
(1) PRP (Prime Power):
According to ISO8528-1, prime power is the maximum power available during a variable
Standard reference Conditions
power sequence, which may be run for an unlimited number of hours per year, between
Note: Standard reference condition 25℃ (77℉) air inlet temp, 100m(328ft) A.S.L 30%
stated maintenance intervals. The permissible average power output during at 24 hours
relative humidity. Fuel consumption dat with diesel fuel with specific gravity of 0.85 and
period shall not exceed 80% of the prime power. 10% overload available for governing
conforming to BS 2869: 1998, Class A2
purposes only.
www.aggpower.co.uk
Your Professional Power Assistant
Injection timing 16°±1˚ BTDC Max. static pressure after radiator 0.125 kPa
Bore 123mm
Oil capacity
-Max. 23L
Cooling method Fresh water forced circulation Lub oil pressure Idle speed: Min 100 kPa
www.aggpower.co.uk
Your Professional Power Assistant
Alternator Specification
Emergency voltage curve
+1%
Poles 4 408 +1%
380
380
-1%
Winding Connections (standard) Star-serie 352
Terminals 12 296
IP rating IP23
54 +1%
50
-1%
+1%
50
-1%
46
38
30
0 1 2 3 4 5 6 7 8 9 10 11 12
δf%%: -10.64 Benchmark phase: A Min. frequency: 44.68Hz Recovery time: 1..95s
Three phase Reliable Single phase
δf%%: 7.74 Benchmark phase: A Max. frequency: 53.87Hz Recovery time: 0..54s
Options
· Water Jacket · Winding Temp measuring · Tools with the machine · Low fuel level alarm
Pre-heater Instrument · Extended range fuel tank · Automatic fuel
· Fuel heater · Alternator Pre-heater · Bunded fuel tank feeding system
· PMG · Fuel T-valves
· Anti-damp and anti-corrosion
treatment
· Anti-condensation heater
· Winding and bearing RTD
· Rental type · Oil Pre-heater · Front heat protection · Remote control panel
Canopy · Oil temp sensor · ATS
· Trailer · Synchronizing controller
· Adjustable ear th leakage
relay
www.aggpower.co.uk
Your Professional Power Assistant
Control Panel
Configuration Benefits
Operation conditions
Features
· Operation temp: -20 ˚C to + 70 ˚C
· Storage temp: -30 ˚C to + 80 ˚C
· Operating humidity: 95% w/o condensation
· Vibration: 5-25Hz, ±1.6 mm
5-1 00 Hz, a= 4g
· Shocks: a= 500m/s²
Options
[email protected] | www.aggpower.co.uk