Infinity 8 Conventional Fire Alarm Panel: (IN1, IN2, IN4, IN6, IN8)

The Infinity 8 control panel is a conventional fire alarm panel housed in an attractive ABS enclosure. It has a removable front cover for easy cable access and features like password access, one-man testing, zone and sounder disablement, space for batteries, and sounder delay options. The panel meets the requirements of EN54 standards and is available in models that support 1 to 8 zones and 2 to 4 sounder circuits.

Uploaded by

Mostafa Ali
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
403 views1 page

Infinity 8 Conventional Fire Alarm Panel: (IN1, IN2, IN4, IN6, IN8)

The Infinity 8 control panel is a conventional fire alarm panel housed in an attractive ABS enclosure. It has a removable front cover for easy cable access and features like password access, one-man testing, zone and sounder disablement, space for batteries, and sounder delay options. The panel meets the requirements of EN54 standards and is available in models that support 1 to 8 zones and 2 to 4 sounder circuits.

Uploaded by

Mostafa Ali
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Infinity 8 Conventional Fire Alarm Panel

(IN1, IN2, IN4, IN6, IN8)

The Infinity 8 control panel is housed in the


most attractive, modern designed, flame
retardent ABS enclosure, utilising a switch
mode power supply. It has a fully removable
front cover which improves ease of access for
cable installations.

Features
Access via password – removes problem of lost
keys
One man test facility
93 Disablement facility for zones & sounders
371mm 55 38
Space for up to 3Ah batteries
Sounder delay option
4 sounder circuitson ZT-IN4,6 & 8
Sounder circuits 3 and/or 4 can be configured as
302mm

Aux 24V supplies


Meets all requirements of latest EN54 part 2 and
part4

MODEL ZT-IN1 ZT-IN2 ZT-IN4 ZT-IN6 ZT-IN8


Part No 37-650 37-651 37-652 37-653 37-654
Mains Voltage 230V AC +10% / -15% @ 50/60 Hz
System Voltage 24V DC (Nominal)
Zone Voltage 21V DC (Nominal)
Sounder Alarm Output 2 x 150mA @ 24V DC 4 x 150mA @ 24V DC
Fault Relay 1 x Volt Free Relay, SELV @ 1A Max
Fault Relay 1 x Volt Free Relay, SELV @ 1A Max
Zone Capacity 32 devices per zone
Remote sounder operation Via N/O contact connected to Class Change
Sounder Activation Delay 0 to 9 minutes in 1 minute increments
Zone End of line 1N4002 Diode (Cathode Stripe to Zone +ve)
Sounder End of Line 10K resistor
Charger Voltage 27.6V
Battery cut off Battery voltage less than 20V
Battery Internal Resistance limit 0.9 ohm
Enclosure size 375 x 316 x 90 (mm)
Weight 3 kg (Excluding Batteries)
Maximum battery space 2 x 3.0 AH, 12 Vdc sealed lead acid

1 Conventional Fire Alarm Systems