Factor - Transversal

The document describes the computation of stiffness, girder factors, and moment factors for the structural analysis of a building using the factor method. Key steps include calculating the stiffness of columns and beams based on their cross-sectional properties, computing girder factors and column factors at each joint, and determining girder moment factors and column moment factors by summing the products of stiffness and factors. The constant N is also computed using the sums of lateral forces and column moments for each story.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
50 views11 pages

Factor - Transversal

The document describes the computation of stiffness, girder factors, and moment factors for the structural analysis of a building using the factor method. Key steps include calculating the stiffness of columns and beams based on their cross-sectional properties, computing girder factors and column factors at each joint, and determining girder moment factors and column moment factors by summing the products of stiffness and factors. The constant N is also computed using the sums of lateral forces and column moments for each story.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 11

FACTOR METHOD

WIND LOAD – TRANSVERSAL SECTION

COMPUTATION OF STIFFNESS
I
K=
L
Where:

bh3
I=
12
L = Length of beams and column

SIZES OF COLUMNS AND BEAMS

COLUMNS, in mm BEAMS, in mm HEIGHT, in meters

FIRST FLOOR 500 500 450 500 4

SECOND FLOOR 450 450 400 450 4

STIFFNESS COMPUTATIONS, in mm3

FOR COLUMNS, x 10 4 mm3

GROUND TO SECOND FLOOR 130.2

SECOND FLOOR TO ROOF TOP 85.4

FOR BEAMS, x 10 4 mm3

WIDTH, in meters 2ND FLOOR LEVEL ROOF LEVEL

B1 6.2 75.6 49.0

B2 4.2 111.6 72.3

B3 4.2 111.6 72.3

B4 4.2 111.6 72.3

B5 4.2 111.6 72.3

B6 5 93.8 60.8

Campuses: Hilltop | MH del Pilar | Pallocan East | Pallocan West | Lipa


Telephone Numbers: +63 43 723 1446 | 980 0041
Website: www.ub.edu.ph
COMPUTATION OF GIDER FACTOR, G FOR EACH JOINT

∑k COLUMN
G=
∑ k @ JOINT

ROOF LEVEL SECOND FLOOR LEVEL

C-D 0.635 B-E 0.740

D-C 0.413 E-B 0.535

D-I 0.413 E-H 0.535

I-D 0.371 H-E 0.491

I-J 0.371 H-K 0.491

J-I 0.371 K-H 0.491

J-O 0.371 K-N 0.491

O-J 0.371 N-K 0.491

O-P 0.371 N-Q 0.491

P-O 0.391 Q-N 0.512

P-U 0.391 Q-T 0.512

U-P 0.584 T-Q 0.697

COMPUTATION OF COLUMN FACTOR, C

C = 1 – GIRDER FACTOR

ROOF LEVEL SECOND FLOOR LEVEL

C-D 0.365 B-E 0.260

D-C 0.587 E-B 0.465

D-I 0.587 E-H 0.465

I-D 0.629 H-E 0.509

I-J 0.629 H-K 0.509

Campuses: Hilltop | MH del Pilar | Pallocan East | Pallocan West | Lipa


Telephone Numbers: +63 43 723 1446 | 980 0041
Website: www.ub.edu.ph
J-I 0.629 K-H 0.509

J-O 0.629 K-N 0.509

O-J 0.629 N-K 0.509

O-P 0.629 N-Q 0.509

P-O 0.609 Q-N 0.488

P-U 0.609 Q-T 0.488

U-P 0.416 T-Q 0.303

COMPUTATION OF GIRDER MOMENT FACTOR

GMF = SUM OBTAINED x k

ROOF LEVEL SECOND FLOOR LEVEL

GMFCD 0.842 x 49 = 41.258 GMF BE 1.008 x 75.6 = 76.205

GMF DC 0.731 x 49 = 35.819 GMF EB 0.905 x 75.6 = 68.418

GMF DI 0.599 x 72.3 = 43.308 GMF EH 0.781 x 111.6 = 87.160

GMF ID 0.578 x 72.3 = 41.789 GMF HE 0.759 x 111.6 = 84.704

GMF IJ 0.557 x 72.3 = 40.271 GMF HK 0.737 x 111.6 = 82.249

GMF JI 0.557 x 72.3 = 40.271 GMF KH 0.737 x 111.6 = 82.249

GMF JO 0.557 x 72.3 = 40.271 GMF KN 0.737 x 111.6 = 82.249

GMFOJ 0.557 x 72.3 = 40.271 GMF NK 0.737 x 111.6 = 82.249

GMFOP 0.567 x 72.3 = 40.994 GMF NQ 0.747 x 111.6 = 83.365

GMF PO 0.577 x 72.3 = 41.717 GMFQN 0.758 x 111.6 = 84.593

GMF PU 0.683 x 60.8 = 41.526 GMFQT 0.861 x 93.8 = 80.762

GMFUP 0.780 x 60.8 = 47.424 GMFTQ 0.953 x 93.8 = 89.391

Campuses: Hilltop | MH del Pilar | Pallocan East | Pallocan West | Lipa


Telephone Numbers: +63 43 723 1446 | 980 0041
Website: www.ub.edu.ph
COMPUTATION OF COLUMN MOMENT FACTOR

CMF = SUM OBTAINED x k

2ND FLOOR TO ROOF LEVEL (k = 85.4) GROUND TO 2ND FLOOR (k = 130.2)

CMF CB 0.495 x 85.4 = 42.273 CMF BA 0.260 x 130.2 = 33.852

CMF BC 0.443 x 85.4 = 37.832 CMF AB 0.130 x 130.2 = 16.926

CMF DE 0.820 x 85.4 = 70.028 CMF EF 0.465 x 130.2 = 60.543

CMF ED 0.759 x 85.4 = 64.819 CMF FE 0.233 x 130.2 = 30.337

CMF IH 0.884 x 85.4 = 75.494 CMF HG 0.509 x 130.2 = 66.272

CMF HI 0.824 x 85.4 = 70.370 CMF GH 0.255 x 130.2 = 33.201

CMF JK 0.884 x 85.4 = 75.494 CMF KL 0.509 x 130.2 = 66.272

CMF KJ 0.824 x 85.4 = 70.370 CMF LK 0.255 x 130.2 = 33.201

CMF ON 0.884 x 85.4 = 75.494 CMF NM 0.509 x 130.2 = 66.272

CMF NO 0.824 x85.4 = 70.370 CMF MN 0.255 x 130.2 =33.201

CMF PQ 0.853 x 85.4 = 72.846 CMF QR 0.488 x 130.2 = 63.538

CMF QP 0.793 x 85.4 = 67.722 CMF RQ 0.244 x 130.2 = 31.769

CMF UT 0.568 x 85.4 = 48.507 CMF TS 0.303 x 130.2 = 39.451

CMF TU 0.511 x 85.4 = 43.639 CMF ST 0.152 x 130.2 = 19.790

∑Q 885.258 ∑Q 594.625

Campuses: Hilltop | MH del Pilar | Pallocan East | Pallocan West | Lipa


Telephone Numbers: +63 43 723 1446 | 980 0041
Website: www.ub.edu.ph
COMPUTATION OF CONSTANT, N X
FORMULA:

∑ H (h)
N X=
∑QCOLUMN

WHERE:
N X – Moment constant @ x-storey
∑ H - Sum of lateral forces for x-storey
∑ Q - Sum of column moments factor for the storey
h – Height of every storey

2ND STOREY
∑ H = 6.50 + 3.50 = 10
∑ Q = 885.258
h=4

10(4 )
N X=
885.258
N X =0.045185

1ST STOREY
∑ H = 6.50 + 3.50 + 11.50 + 6.00 = 27.50
∑ Q = 594.625
h=4

27.5(4 )
N X=
594.625
N X =0.18499

Campuses: Hilltop | MH del Pilar | Pallocan East | Pallocan West | Lipa


Telephone Numbers: +63 43 723 1446 | 980 0041
Website: www.ub.edu.ph
COMPUTATION OF COLUMN MOMENT FACTOR

CM =N X (CMF)

2ND STOREY 1ST STOREY

CM CB 42.273 x 0.045185= 1.910 CM BA 33.852 x 0.18499 = 6.262

CM BC 37.832 x 0.045185= 1.709 CM AB 16.926 x 0.18499 = 3.131

CM DE 70.028 x 0.045185 = 3.164 CM EF 60.543 x 0.18499 = 11.200

CM ED 64.819 x 0.045185= 2.929 CM FE 30.337 x 0.18499 = 5.612

CM IH 75.494 x 0.045185= 3.411 CM HG 66.272 x 0.18499 = 12.260

CM HI 70.370 x 0.045185= 3.180 CM GH 33.201 x 0.18499 = 6.142

CM JK 75.494 x 0.045185= 3.411 CM KL 66.272 x 0.18499 = 12.260

CM KJ 70.370 x 0.045185= 3.180 CM LK 33.201 x 0.18499 = 6.142

CM ON 75.494 x 0.045185= 3.411 CM NM 66.272 x 0.18499 = 12.260

CM NO 70.370 x 0.045185= 3.180 CM MN 33.201 x 0.18499 = 6.142

CM PQ 72.846 x 0.045185= 3.292 CM QR 63.538 x 0.18499 = 11.754

CM QP 67.722 x 0.045185= 3.060 CM RQ 31.769 x 0.18499 = 5.877

CM UT 48.507 x 0.045185= 2.192 CM TS 39.451 x 0.18499 = 7.298

CM TU 43.639 x 0.045185= 1.972 CM ST 19.790 x 0.18499 = 3.661

Campuses: Hilltop | MH del Pilar | Pallocan East | Pallocan West | Lipa


Telephone Numbers: +63 43 723 1446 | 980 0041
Website: www.ub.edu.ph
COMPUTATION OF JOINT FACTOR, J FOR GIRDER

∑ M Columnmoment @ joint
J=
∑ Q GMF @ joint

ROOF LEVEL 2ND FLOOR LEVEL

1.910 0.0463 1.709+ 6.262 0.1046


@ Joint C= @ Joint B=
41.258 76.205

3.164 0.0400 2.929+11.2 0.0908


@ Joint D= @ Joint E=
35.819+43.308 68.418+87.160

3.411 0.0416 3.180+12.260 0.0925


@ Joint I = @ Joint H=
41.789+40.271 84.704+82.249

3.411 0.0424 3.180+12.260 0.0939


@ Joint J = @ Joint K=
40.271+40.271 82.249+82.249

3.411 0.0420 3.180+12.260 0.0932


@ Joint O= @ Joint N =
40.271+40.994 82.249+83.365

3.292 0.0395 3.060+11.754 0.0896


@ Joint P= @ Joint Q=
41.717+ 41.526 84.593+80.762

2.192 0.0462 1.972+7.298 0.1037


@ Joint U= @ Joint T =
47.424 89.391

Campuses: Hilltop | MH del Pilar | Pallocan East | Pallocan West | Lipa


Telephone Numbers: +63 43 723 1446 | 980 0041
Website: www.ub.edu.ph
COMPUTATION OF GIRDER MOMENTS

ROOF LEVEL SECOND FLOOR LEVEL

GM CD 41.258 x 0.0463 = 1.910 GM BE 76.205 x 0.1046 = 7.971

GM DC 35.819 x 0.0400 = 1.433 GM EB 68.418 x 0.0908 = 6.212

GM DI 43.308 x 0.0400 = 1.732 GM EH 87.160 x 0.0908 = 7.914

GM ID 41.789 x 0.0416 = 1.739 GM HE 84.704 x 0.0925 = 7.835

GM IJ 40.271 x 0.0416 = 1.675 GM HK 82.249 x 0.0925 = 7.608

GM JI 40.271 x 0.0424= 1.707 GM KH 82.249 x 0.0939 = 7.723

GM JO 40.271 x 0.0424 = 1.707 GM KN 82.249 x 0.0939 = 7.723

GM OJ 40.271 x 0.0420 = 1.691 GM NK 82.249 x 0.0932 = 7.666

GM OP 40.994 x 0.0420 = 1.722 GM NQ 83.365 x 0.0932 = 7.770

GM PO 41.717 x 0.0395 = 1.648 GM QN 84.593 x 0.0896 = 7.580

GM PU 41.526 x 0.0395 = 1.640 GM QT 80.762 x 0.0896 = 7.236

GM UP 47.424 x 0.0462 = 2.191 GM TQ 89.391 x 0.1037 = 9.270

Campuses: Hilltop | MH del Pilar | Pallocan East | Pallocan West | Lipa


Telephone Numbers: +63 43 723 1446 | 980 0041
Website: www.ub.edu.ph
WIND LOAD – LONGITUDINAL SECTION
(FACTOR METHOD)
SUMMARY TABLE

JOINTS MEMBERS MOMENT (kN·m)

GIRDER COLUMN

A A-B 3.131

B-A 6.262

B B-E 7.971

B-C 1.709

C C-B 1.910

C-D 1.910

D D-C 1.433

D-E 3.164

D-I 1.732

E-B 6.212

E E-D 2.929

E-F 11.200

E-H 7.914

F F-E 5.612

G G-H 6.142

H-G 12.260

H H-E 7.835

H-I 3.180

H-K 7.608

I I-D 1.739

Campuses: Hilltop | MH del Pilar | Pallocan East | Pallocan West | Lipa


Telephone Numbers: +63 43 723 1446 | 980 0041
Website: www.ub.edu.ph
I-H 3.411

I-J 1.675

J-I 1.707

J J-K 3.411

J-O 1.707

K-J 3.180

K K-H 7.723

K-L 12.260

K-N 7.723

L L-K 6.142

M M-N 6.142

N-K 7.666

N N-M 12.260

N-O 3.180

N-Q 7.770

O-J 1.691

O O-N 3.411

O-P 1.722

P P-O 1.648

P-Q 3.292

P-U 1.640

Q Q-N 7.580

Q-P 3.060

Q-R 11.754

Q-T 7.236

R R-Q 5.877

S S-T 3.661

T-Q 9.270

T T-S 7.298

Campuses: Hilltop | MH del Pilar | Pallocan East | Pallocan West | Lipa


Telephone Numbers: +63 43 723 1446 | 980 0041
Website: www.ub.edu.ph
T-U 1.972

U U-P 2.191

U-T 2.192

Campuses: Hilltop | MH del Pilar | Pallocan East | Pallocan West | Lipa


Telephone Numbers: +63 43 723 1446 | 980 0041
Website: www.ub.edu.ph