Hand Book Protecciones

Download as pdf or txt
Download as pdf or txt
You are on page 1of 356

BOOK No 6 Global Organization

Innovative
Revision 0 Solutions

Product &
Substation System
Business Business

PROTECTION

APPLICATION HANDBOOK

BA THS / BU Transmission Systems and Substations

LEC Support Programme

Suggestions for improvement of this book


as well as questions shall be addressed to:

BU TS / Global LEC Support Programme

C/o ABB Switchgear AB

SE-721 58 Västerås

Sweden

Telephone +46 21 32 80 00

Telefax +46 21 32 80 13

Telex 40490 abbsub s

Copyright © BU Tansmission Systems and Substations

2 BA THS / BU Transmission Systems and Substations LEC Support Programme


Protection Application

Handbook

Welcome to the Protection Application Handbook in the series of booklets


within the LEC support programme of BA THS BU Transmission Systems
and Substations. We hope you will find it useful in your work. Please note
that this is an advance copy that was used by ABB Substations in Sweden.
The handbook will be modified to better suit into the engineering documen­
tation planned to be issued in cooperation with the Global process owner
Engineering.

The booklet covers most aspects of protection application based upon


extensive experience of our protection specialists like:
- Selection of protection relays for different types of objects.
- Dimensioning of current and voltage transformers matching protection
relays requirements.
- Design of protection panels including DC and AC supervision, terminal
numbering etc.
- Setting of protection relays to achieve selectivity.
- Principles for sub-division of the protection system for higher voltages.

The booklet gives a basic introduction to application of protection relays


and the intent is not to fully cover all aspects. However the basic philosophy
and an introduction to the application problems, when designing the protec­
tion system for different types of objects, is covered.

The intention is to have the application as hardware independent as possi­


ble and not involve the different relay types in the handbook as the protec­
tion relays will change but the application problems are still the same.

The different sections are as free standing sections as possible to simplify


the reading of individual sections. Some sections are written specially for
this handbook some are from old informations, lectures etc. to bigger or
smaller extent.

BA THS / BU Transmission Systems and Substations LEC Support Programme 3


Content

Section
Page No
Network General
5
Fault calculation
23
Network earthing
51
Protection General
83
Protection Line
97
Protection Transformer
163
Protection Reactors
175
Protection Capacitors
185
Protection Bus and Breaker
189
Earth Fault protection
203
Current transformers
235
Voltage transformers
249
Requirement on current transformers 263

Control System structure 275

Protection settings 301

Sub divided systems 341

4 BA THS / BU Transmission Systems and Substations LEC Support Programme


Network General
1. TRANSMISSION LINE THEORY

1.1 GENERAL

For a long power line, symmetrical built and symmetrical loaded


in the three phases, voltage and current variation along the line
can be expressed as shown in fig. 2, with corresponding formu­
las. In these formulas the propagation of speed is included as a
variable.

The propagation of speed can be calculated according to:

γ= ( R + jX ) ( G + jB )= ZY

where “R”, “X”, “G” and “B” are the resistance, reactance, con­
ductance and susceptance per phase.

Surge impedance is defined as:

R + jX Z
Zv = ----------------- = ----
G + jB Y

For lines without losses the above formulas become:

ϒ= jω LC = j XB = jβ

X L
Zv = ---- = ---­
B C

The values of “X” and “B” can approximately be calculated from


the geometrical data of the power line according to the following
formulas:

–4  2H 
L = 2 × 10 ln  -------------- H/km
 R ekv

TRANSMISSION LINE THEORY

BA THS / BU Transmission Systems and Substations LEC Support Programme 5


 
 –6 
 10 
C=  --------------------------------  F/km
  2H  
 18 ln  -------------- 
  R ekv 

where:

“H” is the phase conductors height over earth

“Rekv” is the phase conductor equivalent radius. To determine the

equivalent radius see fig. 1.

The surge impedance is accordingly obtained as:

 2H 
Z v = 60 ln  --------------
 R ekv
For single conductors, “Zv” is approximately 360-400 ohm per
phase. For duplex conductors, “Zv” is approximately
300-320 ohm per phase.

Figure 1. Different conductor configurations.

The equivalent radius Rekv will be:

R ekv = n R × d n – 1
mean

where “n” is the number of conductors per phase.

TRANSMISSION LINE THEORY

6 BA THS / BU Transmission Systems and Substations LEC Support Programme


Network General
If the voltage “U2” and the current “I2” at the receiving side is giv­
en, the voltage at a distance “s” km from the supplying side (see
fig. 2) is given as:

Figure 2. Voltage distribution along a line.

U = U 2 cos βs + Z v I 2 sin βs

U
I = j ------2- sin βs + I 2 cos βs
Zv

1.2 POWER LINE AT NO LOAD, I2 = 0

Voltage and current along the line are following a cos- respective­
ly a sinus curve. The voltage as well as the current have the same
phase angle along the whole line. The phase angle between the
voltage and current is 90°.

1
U 2 ≈ U 1 × -------------------------------------
- at 50Hz
cos (0.06 × l)°

1
U 2 ≈ U 1 × ----------------------------------------- at 60Hz
cos (0.072 × l)°
where “l” is the line length in km.

It must also be considered that “U1” increases when the line is

connected to a network.

Qc
∆U 1 ≈ ---------------
-
S sh.c.

TRANSMISSION LINE THEORY

BA THS / BU Transmission Systems and Substations LEC Support Programme 7


where:

“Qc” is the capacitive power generated by the line and

“Ssh.c.” is the short-circuit power of the network.

The capacitive power generated by the power line can be calcu­


lated as:

U2
Q c = -------
Xc
Where “U” is the rated line voltage and “Xc” is the capacitive re­
actance of the power line.

1.3 POWER LINE SHORT-CIRCUITED, U2 = 0

For this case the voltage follows a sinus curve and the current fol­
lows a cosines curve i. e. opposite to when the power line is at no
load.

1.4 POWER LINE AT LOAD

At “surge impedance” load “U2 = Zv I2” the reactive power pro­


duced in the shunt capacitance of the line is same as the reactive
power consumed by the reactance along the line. The following
balance is obtained:

2 L
ωC × U 2 = ωL × I ⇒ U
---- = ---- = Z
v
I C

If the active losses of the line is neglected the following conditions


are obtained for different load conditions:
- If the transferred active power is less than the “surge impedance” load
and no reactive power is taken out at the receiving end, the voltage will
be higher at the receiving end than the voltage at the sending end. If
voltage is kept equal at both ends, the voltage will be higher at the mid­
dle of the line.
- If the transferred active power is higher than the ”surge impedance” load
and no reactive power is taken out at the receiving end, the voltage will
be lower at the receiving end than the voltage at the sending end. If the
voltage is kept equal at both ends, the voltage will be lower at the middle
of the line.

TRANSMISSION LINE THEORY

8 BA THS / BU Transmission Systems and Substations LEC Support Programme


Network General

In reality these conditions are modified a little due to the resis­


tance of the line. This will give a small voltage drop in the same
direction as the active power flow.

The “surge impedance load” is normally only considered for very


long transmission lines at very high voltages. For these cases the
actual power should not deviate too much from the “surge imped­
ance” load considering losses on the line, voltage fluctuation and
the availability of reactive power in the network.
In most cases, technical and economical aspects rules what
power that is to be transmitted over the line.

As a general guidance for “surge impedance load” you can as­


sume approximately 120 MW for a 220 kV line with a single con­
ductor and 500 MW for a 400 kV line with duplex conductors.

2. VOLTAGE DROP AND LOSSES IN POWER


SYSTEMS.
SHORT LINES (<50 KM)

E1 Z=R+jX
E 2

P 1
P 2

Q 1
I Q 2

E 1

a
Ia E2
Ir I

Figure 3. Load transfer on a short line.

VOLTAGE DROP AND LOSSES IN POWER SYSTEMS.

BA THS / BU Transmission Systems and Substations LEC Support Programme 9


2.1 VOLTAGE, REACTIVE AND ACTIVE POWER
KNOWN AT THE RECEIVING END

The impedance for short lines can be expressed as “Z=R+jX”,


see fig. 3. The voltage drop can be split into two components, one
in the same direction as “E2”, named “a” and one perpendicular
to “E2”, named “b”.

1 (R × P + X × Q )
a = ------
- 2 2
E2

1 (X × P + R × Q )
b = ------
- 2 2
E2

2 2
E1 = ( E2 + a ) + b

This means that if the voltage, the active and reactive power are

known at the receiving end, the voltage at the sending end can

be easily calculated.

For short lines, “b” will be small compared with the voltage and it

is possible to make the approximation “E1 =E2+ a”.

If “b” is less than 10% of “E2+ a”, the error when calculating “E1”
is less than 0.5%.

The active and reactive losses Pf and Qf on the line can be ex­

pressed as:

2 2
2 P2 + Q2
P f = 3R × I = R × ---------------------­
2
E2

P1 = P2 + Pf

2 2
2 P2 + Q2
Q f = 3X × I = X × ---------------------­
2
E2

VOLTAGE DROP AND LOSSES IN POWER SYSTEMS.

10 BA THS / BU Transmission Systems and Substations LEC Support Programme


Network General
Q1 = Q2 + Qf

2.2 VOLTAGE, REACTIVE AND ACTIVE POWER


KNOWN AT THE SENDING END

If the voltage, the active power and the reactive power are known
at the sending end the following equations are valid:
1 (R × P + X × Q )
a = ------
- 1 1
E1

1 (X × P + R × Q )
b= ------
- 1 1
E1

2 2
E2 = ( E1 – a ) + b

For short lines “b” will be small compared with “E1 - a” and the ap­
proximation “E 2 ≈  E 1 – a ” can be done in the same way as
when the voltage, the active and reactive power are known at the
receiving end.

The losses on the line can be expressed as:

2 2
2 P1 + Q1
P f = 3R × I = R × ---------------------­
2
E1

2 2
2 P1 + Q1
Q f = 3X × I = X × ---------------------­
2
E1

P2 = P1 – Pf

Q2 = Q1 – Qf

VOLTAGE DROP AND LOSSES IN POWER SYSTEMS.

BA THS / BU Transmission Systems and Substations LEC Support Programme 11


2.3 VOLTAGE KNOWN AT SENDING END, REACTIVE
AND ACTIVE POWER KNOWN AT THE RECEIVING
END

The cases when the voltage at the sending end and the reactive
and active power at the receiving end are known is quite com­
mon. The calculation will in cases like these be a little more com­
plicated and trial calculation is the best way. The voltage at the
receiving end is assumed “E’2” and from this value a voltage
“E’1”, at the sending end is calculated. The calculated value “E’1”
is subtracted from the given value “E1” and the difference is add­
ed to the previous guessed “E’2” value to get a new value.

E″ 2 = E′ 2 + E 1 –
E′ 1

The nominal sending end voltage can normally be assumed as


the first guessed value of “E’2”.

2.4 REDUCTION OF THE VOLTAGE DROP

For a power line at a certain load there are some possibilities to


reduce the voltage drop:
- Keeping the service voltage as high as possible.
- Decreasing the reactive power flowing through the line by producing re­
active power with shunt capacitors at the load location.
- Reducing the inductive reactance of power lines with series capacitors.

3. REPRESENTATION OF LONG POWER


LINES(>50 KM)

Long power lines are usually represented with a p-link,


see fig. 4.
Rπ X π

Bπ B π

REPRESENTATION OF LONG POWER LINES(>50 KM)

12 BA THS / BU Transmission Systems and Substations LEC Support Programme


Network General
Figure 4. The equivalent π representation of a line.

where:

Rπ = R  1 – 1
--- XB
 3

X π = X  1 – --1- XB
 6 

B π = --1- B  1 + -----
1-XB
2  12 

This scheme can be used up to 200 km length without long line


correction, which is the second term in the equation above. The
calculation error is then about 1.5% in resistance, 0.75% in reac­
tance and 0.4% in susceptance.

If the corrections are used the scheme above can be used up to


800 km line length. The calculation error is then about 1.0% in re­
sistance and 0.5% in reactance.

The values of “X” and “B”, can be calculated from the geometrical
data, see formulas for L and C in the beginning of the chapter.

REPRESENTATION OF LONG POWER LINES(>50 KM)

BA THS / BU Transmission Systems and Substations LEC Support Programme 13


4. SYNCHRONOUS STABILITY

4.1 ONE GENERATOR FEEDING A “STRONG” NET-


WORK

Assume that one generator is feeding a strong network through


a line, see fig. 5.

E 1
E1 E2
M0 X E2 ψ

Figure 5. Generator feeding a “strong” network.

E1 E2
- sin ψ
P = ------------
X

2
d ψ
ωJ ---------
2
- = P 0 – P max × sin ψ
dt

2
d ψ
2 = M 0 – M max × sin ψ
J ---------
-
dt
Where “ω“is the angular frequency, “2πf” and “J” are the angular
momentum.

The differential equation becomes possible to solve if the trans­


ferred power, during the fault is zero.
2
d ψ P dψ P0 P0 t2
2 = ------- ⇒ ------- = ------- × t + A ⇒ ψ ( t ) = ------- × 2 + A × t + B
---------
- 0 ----
dt ωJ dt ωJ ωJ
For steady state condition the derivative of the angle is zero i. e.

there is balance between the produced and transmitted power.

This gives “A”=0.

The angle for “t=0” gives “B=ψ 0”.

SYNCHRONOUS STABILITY

14 BA THS / BU Transmission Systems and Substations LEC Support Programme


Network General
The inertia constant “H” of a generator is defined as:
1
--- ω 2 × J 2 × Sn × H
2
H = ------------------- ⇒ ωJ = --------------------------
Sn ω

Inserting these values gives the following equation:


2
ω × P0 t
ψ ( t ) = -------------------------
- × ---- + ψ 0
2 × Sn × H 2

If the transferred power during the fault is not zero the equal area
criteria has to be used for checking the stability.

4.2 EQUAL AREA CRITERIA FOR STABILITY

A power station feeds power to a strong network through two par­


allel lines, see fig. 6.
E2
Xl

E1
Xs
G

mXl (1-m)X l

Figure 6. Line fault on one circuit of a double Overhead line.

When a three phase fault occur on one of the lines, the line will
be disconnected by the line protection.

The question is whether the synchronous stability is maintained


or not.

SYNCHRONOUS STABILITY

BA THS / BU Transmission Systems and Substations LEC Support Programme 15


Before the fault, the maximum transferred power is:

E1 × E2
P max = ---------------------
Xl
X s + -----
2

During the primary fault the reactance between the generator


and the strong network will be:
Xs Xl 1
X s + X l + ------------- = X s  1 + ----- + X l
mX l  m

this is obtained by an “Y-D-transformation” of the system


(see fig. 7).
Xl
Xs
Short-circuit since it is
a strong network

mXl (1-m)Xl This reactance can be igno­


red since it is short-circuited
by the strong source

Zero potential bus


Figure 7. Thevenins Fi
theorem applied on the faulty network.

Maximum transferred power during the fault is:


E1 × E2
P′ max = -
----------------------------------------
1
X s 1 + ---- -
m + X l

The power transfer during the fault is therefore limited. Maximum


power can be transmitted when “m”=1, i. e. a fault close to the
strong network. For faults close to the generator “m”=0 and no
power can therefore be transmitted during the fault.

When the faulty line has been disconnected the maximum trans­
ferred power will be:
E1 × E2
P″ max = --------------------
-
Xs + Xl

SYNCHRONOUS STABILITY

16 BA THS / BU Transmission Systems and Substations LEC Support Programme


Network General
The maximum transferred power after that the fault has been
cleared will be:

0.5P max < P″ max < P max

In fig. 8 the active power that can be transferred during the differ­
ent conditions is shown.
P

Pmax

P"max

Po

P’max

ψ
ψ ψ ψ π
0 1 2
Figure 8. The equal area method shows the stability limit.

The following equation is valid when the two areas in the figure
above are equal:
ψ1 ψ2
∫ ψ 0 P0 – P′max dψ= ∫ψ 1 P″max – P0 dψ
The angle is increasing from “y0” to “y1” during the fault. For the
worst condition when “m”=0 the accelerated power is constantly
equal to “P0” during the fault.

If the area below “P0” (see the dashed area in fig. 8) is smaller
than the maximum area between “P0” and the curve with “P”max”
as maximum the system will remain stable.

In fig. 8 the area above “P0” equal to the area below “P0” is

dashed which shows that the system will remain stable for the

case shown in fig. 8.

SYNCHRONOUS STABILITY

BA THS / BU Transmission Systems and Substations LEC Support Programme 17


5. ACTIONS TO IMPROVE THE STABILITY

This matter could be looked into from two different aspects, either
to increase the stability at a given transferred power or to in­
crease the transferred power maintaining the stability.

MORE THAN ONE PHASE CONDUCTOR PER PHASE

decreases the reactance of the line and thus the angle between
the line ends at a given transferred power, or it can increase the
power transferred with maintained stability. If the reactance is
100% with one conductor per phase it will become approximately
80% with 2 conductors, 70% with three conductors and 65% with
four conductors.

Multiple phase conductors reduces the electric field strength at


the surface of the conductors. This makes it possible to have a
higher voltage without getting corona.

SERIES CAPACITORS ON OVERHEAD LINESreduces the reactance


between the stations. The compensation factor “c” is the ratio be­
tween the capacitive reactance of the capacitor and the inductive
reactance of the overhead line. The power transfer can be dou­
bled if a compensation factor of 30% is used.

SHORT FAULT CLEARING TIME makes the increase of the angle


between the two systems at an occurring primary fault smaller.
The angle increase is proportional to the time in square.

SINGLE POLE AUTORECLOSING allows the two healthy phases to


transfer power even during the dead interval. For lines longer
than approximately 350 km it is then necessary to include four leg
reactors to extinguish the secondary arc due to the capacitive
coupling between the phases.

INCREASED INERTIA CONSTANT IN THE GENERATORS makes the


maximum allowed fault clearance time to increase proportional to
the square root of the inertia constant increase. The allowed pow­
er transfer can also be increased with maintained fault clearance
times.

ACTIONS TO IMPROVE THE STABILITY

18 BA THS / BU Transmission Systems and Substations LEC Support Programme


Network General
6. SHUNT REACTORS

Shunt reactors are used in high voltage systems to compensate


for the capacitive generation from long overhead lines or extend­
ed cable networks.

The reasons for using shunt reactors are two. One reason is to
limit the overvoltages, the other reason is to limit the transfer of
reactive power in the network. If the reactive power transfer is
minimized, i.e. a better reactive power balance in the different
part of the networks a higher active power can be transferred in
the network.

Reactors for limiting overvoltages are mostly needed in weak


power systems, i.e. when the network short circuit power is rela­
tively low. The voltage increase in a system due to the capacitive
generation is:
Q c × 100
∆U ( % ) = ------------------------
S sh.c.

where

“Qc” is the capacitive input of reactive power to the network and

“Ssh.c” is the short circuit power of the network.

With increasing short circuit power of the network the voltage in­
crease will be lower and the need of compensation to limit the ov­
ervoltages will be less accentuated.

Reactors included to get a reactive power balance in the different


part of the network are most needed in heavy loaded networks
where new lines can’t be built out of environmental reasons. The
reactors then are mostly thyristor controlled in order to adopt
quickly to the required reactive power.

Four leg reactors can also be used for extinction of the secondary
arc at single-phase reclosing in long transmission lines, see fig.
9. Since there always is a capacitive coupling between the phas-

SHUNT REACTORS

BA THS / BU Transmission Systems and Substations LEC Support Programme 19


es this will keep the arc burning (secondary arc). By adding one
single-phase reactor in the neutral the secondary arc can be ex­
tinguished and the single-phase auto-reclosing successful.

7. REACTORS FOR EXTINCTION OF SECOND-


ARY ARC AT AUTO-RECLOSING

It is a known fact that most of the faults in overhead lines are of


single phase type. It is therefore possible to open and reclose
only the faulty phase and leave the other two phases in service.
The advantage with this is that the stability of the network is im­
proved since the two remaining phases can transmit power dur­
ing the auto-reclosing cycle. This is of special interest for tie lines
connecting two networks, or part of networks.

Due to the capacitive coupling between the phases the arc at the
faulty point can be maintained and the auto-reclosing conse­
quently would be unsuccessful. With a dead interval of 0.5 sec­
onds, line lengths up to approximately 180 km can be reclosed
successfully in a 400 kV system. This with the assumption of fully
transposed lines. Should the line be without transposition the line
length with possible successful single-phase auto-reclosing
would be about 90 km. If the dead interval is increased to 1.0 sec­
ond the allowed lengths will be approximately doubled.

For successful auto-reclosing of lines longer than above it’s nec­


essary to equip the line with Y-connected phase reactors at both
ends, combined with “neutral” reactors connected between the
Y-point and earth. This solution was first proposed in 1962 by pro­
fessor Knudsen the reactor are therefore also called Knudsen re­
actor but it can also be called teaser reactor.

The teaser reactors inductance is normally about 26% of the in­


ductance in the phases. The maximum voltage over the teaser re­
actor then becomes approximately 20% of nominal voltage
phase/earth. The current through the teaser reactor during a sin­
gle-phase auto-reclosing attempt is about the same as the rated
current of the phase reactors. The duration of the dead interval is
usually 0.5-1 second. In normal service currents through a teaser

REACTORS FOR EXTINCTION OF SECONDARY ARC AT

20 BA THS / BU Transmission Systems and Substations LEC Support Programme


Network General
reactor is only a few amperes due to possible small unsymmetry
in the phase voltages and differences between the phase reac­
tors.

Because of the low powers and voltages in the teaser reactor the
reactor can be made very small compared with the phase reac­
tors. The extra cost to include the teaser reactor compared to the
“normal” shunt reactor cost is therefore not so large.

L L L L L L

0.26x 0.26x
L L

Figure 9. Single pole fault clearance on a power line with teaser reactors to
extinguish the arc.

REACTORS FOR EXTINCTION OF SECONDARY ARC AT

BA THS / BU Transmission Systems and Substations LEC Support Programme 21


REACTORS FOR EXTINCTION OF SECONDARY ARC AT

22 BA THS / BU Transmission Systems and Substations LEC Support Programme


Fault Calculation
1. INTRODUCTION

Fault calculation is the analysis of the electrical behavior in the


power system under fault conditions. The currents and voltages
at different parts of the network for different types of faults, differ­
ent positions of the faults and different configurations of the net­
work are calculated.

The fault calculations are one of the most important tools when
considering the following:
- Choice of suitable transmission system configuration.
- Load- and short circuit ratings for the high voltage equipment.
- Breaking capacity of CB:s.
- Application and design of control- and protection equipment.
- Service conditions of the system.
- Investigation of unsatisfactory performances of the equipment.

This description will be concentrated on fault calculations used at


application and design of protection equipment.

The major requirements on protection relays are speed, sensitiv­


ity and selectivity. Fault calculations are used when checking if
these requirements are fulfilled.

Sensitivity means that the relay will detect a fault also under
such conditions that only a small fault current is achieved This is
e. g. the case for high resistive earth faults. For this purpose fault
calculations for minimum generating conditions are performed to
make sure that the selected relay will detect the fault also during
minimum service conditions.

Selectivity means that only the faulty part of the network is dis­
connected when a fault occurs. This can be achieved through ab­
solute selectivity protection relays (unit protection) or time
selective relays. In a network, there is always time selective pro­
tection relays as back up protection. To be able to make selective
settings of these relays it’s necessary to have a good knowledge

INTRODUCTION

BA THS / BU Transmission Systems and Substations LEC Support Programme 23


of the fault current.

Speed means that a limited operating time of the relay is re­


quired. For many relays the operating time is depending on the
magnitude of the fault current. Thus it is important, when planning
the network to have a good knowledge of the fault current. Here­
by it’s possible to predict the operating time of the relay and thus
make sure that maximum allowed fault clearance time is fulfilled
under all circumstances.

2. FACTORS AFFECTING THE FAULT


CALCULATION.

Concerning fault calculations the first thing to do is to decide what


case or cases that shall be studied. The fault current and fault
voltage at different parts of the network will be affected by the fol­
lowing:
- Type of fault.
- Position of the fault.
- Configuration of the network.
- Neutral earthing.

The different types of faults that can occur in a network, can be


classified in three major groups:
- Short circuited faults.
- Open circuited faults.
- Simultaneous faults.

The short circuited faults consists of the following types of fault:


- Three phase faults (with or without earth connection).
- Two phase faults (with or without earth connection).
- Single phase to earth faults.

The open circuit faults consists of the following types of fault:


- Single phase open circuit.
- Two phase open circuit.

FACTORS AFFECTING THE FAULT CALCULATION.

24 BA THS / BU Transmission Systems and Substations LEC Support Programme


Fault Calculation
- Three phase open circuit.

Simultaneous faults are a combination of the two groups de­


scribed above, for example, if one conductor, at an overhead line,
is broken and one end of the line falls down. Then there is both
one single phase to earth fault and one single phase open circuit­
ed fault in the system.

Deciding what fault and how many locations of the fault, that shall
be studied, depends on the purpose of the study. If the sensitivity
of a differential relay is to be studied, the fault shall be located in­
side the protective zone. By this, knowledge of the differential
current at a fault is achieved. If, on the other hand, selectivity be­
tween the inverse time delayed over current relays is to be stud­
ied, other fault locations must be selected.

The configuration of the network is of greatest importance when


making fault calculations. There will be a big difference, compar­
ing the results, if the calculations are performed at minimum or
maximum generating conditions. The result will be affected by
how many parallel lines that are in service and if the busbars are
connected via bus coupler or not etc.

The large number of conditions that affect the fault calculation


makes it practical to have a standard fault condition to refer to,
normally the three phase short circuit faults. This short circuit lev­
el may be expressed in amperes, or in three phase MVA corre­
sponding to the rated system voltage and the value of the three
phase fault current.

3. BASIC PRINCIPLES

3.1 TIME ASPECT

It is a well known fact that the effects of a fault, changes with the
time that has passed since the fault occurred. The physical rea­
son for this transient process is that electromagnetic energy is
stored in the inductances of the circuits. This energy can not be

BASIC PRINCIPLES

BA THS / BU Transmission Systems and Substations LEC Support Programme 25


altered in a indefinite short time. Therefore some time will pass
while the new electrical field is created. These time intervals are
known as the sub-transient and transient conditions. The duration
of the transient interval is counted in ms. In this case, the fault cal­
culations are intended to be used for application and design of re­
lay equipment. The fastest protection relays have operating times
of about 10 ms. When time selectivity is to be investigated the
time can vary from 0.3 second up to a few seconds. Therefore
fault calculations are made for conditions when the first transient
condition “sub transient conditions” have come to an end i.e. the
transient reactances of the generators are used.

3.2 TYPE OF FAULT

The task of the protection relays is to protect the high voltage


equipment.This is done by a trip signal, given to the circuit break­
ers, when a fault occurs. The most dangerous phenomena is nor­
mally the high current that occurs at a short circuit. When making
fault calculations for the purposes here discussed, short circuit
type faults are normally considered. Open circuit faults will not
cause high Overcurrent or high overvoltages and are therefore
normally not dangerous to the network. Open circuit faults will
cause heating in rotating machines, due to the “negative se­
quence current” that will flow in the system. The machines are
therefore equipped with negative sequence current protection.
The setting of this relay normally needs no fault calculation and
can be done correctly without knowledge of the problems men­
tioned above.

A network is usually protected against phase and earth faults by


protection relays. The magnitude of the fault current is dependent
on what type of fault that occurs. At earth faults the size of the
fault current is depending on the earthing resistance or reactance
(if applicable) and on the resistance in fault. The fault resistance
for a phase fault is much smaller than that for an earth fault. This
shows why fault calculations for earth faults with a specified re­
sistance in the fault normally is recommended.

Three phase faults normally gives the highest short circuit cur-

BASIC PRINCIPLES

26 BA THS / BU Transmission Systems and Substations LEC Support Programme


Fault Calculation
rents. Therefore short circuit calculations for three phase faults
also normally are used.

Two phase faults normally gives lower fault currents than three
phase faults, why normally the need for fault calculations for two
phase faults is limited. However, a two phase fault calculation can
be necessary to check the minimum fault current level to verify
the sensitivity for the back-up protection.

3.3 DEFINITION

Faults can be divided into two groups, symmetrical (balanced)


and unsymmetrical (unbalanced) faults. The symmetrical faults
are only concerning three phase faults, all other faults are seen
as unsymmetrical.

4. BALANCED FAULT CALCULATION

When a balanced fault i.e. a three phase fault occurs, the relation
between the phases is maintained. This means that the fault cur­
rents and the fault voltages are equal in the three phases. The
only difference is the phase angle which will be maintained even
during the fault. It is therefore sufficient to use a single phase rep­
resentation of the network and calculate the fault currents and
voltages at one phase. The result will be applicable at all three
phases, with the angle (120°) maintained between the phases.

The short circuit calculations are easiest done by using Theve­


nin´s theorem which states:
Any network containing driving voltages, as viewed from any two
terminals, can be replaced by a single driving voltage acting in se­
ries with a single impedance. The value of this driving voltage is
equal to the open circuit voltage between the two terminals before
the fault occurs, and the series impedance is the impedance of the
network as viewed from the two terminals with all the driving volt­
ages short circuited.

The two terminals mentioned in the theorem are located at the


fault. This way of calculating will only give the change in voltage

BALANCED FAULT CALCULATION

BA THS / BU Transmission Systems and Substations LEC Support Programme 27


and current caused by the short circuit. To get the correct result
the currents and voltages that existed in the system before the
fault must be superimposed geometrically to the calculated
changes.

The two following simplifications are normally made:


- The same voltage is used in the whole network (voltage drops from load
currents are neglected).
- All currents are considered to be zero before the fault occurs, which
means that no load currents are considered.

4.1 STEP BY STEP INSTRUCTIONS - SHORT CIR-


CUIT CALCULATIONS

When making three phase short circuit calculations these four


steps should be followed:
1) Short circuit all E.M.F. s (Electro Motoric Forces) in the network and
represent the synchronous machines with their transient reactances.
2) Decide one base voltage and transform all impedances into that volt­
age level.
3) Reduce the network to one equivalent impedance.
4) If “U” is the selected base voltage and “Z” is the resulting impedance
of the network the total short circuit current “Isc” in the fault itself, at a
three phase short circuit, is:

U
I sc = -----------
Z 3

Clause 1 can be commented as follows:


It depends on what part of the network that is of interest, how the
sources are represented. If the voltages and currents of interest
are located not too far from the generator, the synchronous ma­
chines should be represented as mentioned. If however the area of
interest is far from the generating plants it´s normally more conve­
nient to use the short circuit power closer to the fault point as
source.

The four steps are further developed:

BALANCED FAULT CALCULATION

28 BA THS / BU Transmission Systems and Substations LEC Support Programme


Fault Calculation
Representation of the network components

Overhead lines are represented by their resistance and reac­

tance.

The positive sequence values are used for phase faults. For earth

faults, the zero sequence values are used. Negative sequence

components for overhead lines are always equal to the positive

sequence components.

The values mentioned, must be given by the constructor of the

overhead lines. The values depends on the size of the line itself,

as well as on the physical configuration of the lines (both within a

phase and between the phases).

For zero sequence impedance, the earth conditions are also of

greatest importance. When two or more lines are placed at the

same towers, there will be a mutual impedance between the

lines. The mutual impedance is only important at earth faults,

though it, for phase faults, is that small it can be neglected. Con­

sideration to the mutual impedance must only be taken when

earth faults are calculated.

Thumb roles concerning overhead lines:

- For line reactance of a HV overhead line the reactance is about


0.3-0.4 ohm/km at 50 Hz.
- The resistance is normally small (0.02-0.05 ohm/km) and of minor
importance to the short circuit calculations.
- The zero sequence reactance is approximately 3-4 times the positive se­
quence reactance and the mutual reactance is approximately 55-60%
of the zero sequence reactance.

One way to describe these values is to give them in%, pu. Then
the basic power also will be given.

Example: A 400 kV line “x” = 1.76% and “Sbase”= 100 MVA gives:
2
X = ----------- × ------------ = 28.16Ω
1.76 400
100 100

Cables are represented by the same values as the overhead


lines, i.e. resistance and reactance. Also here the cable manufac-

BALANCED FAULT CALCULATION

BA THS / BU Transmission Systems and Substations LEC Support Programme 29


turer must give the data as the values changes with the type of
cable. Typically a cable impedance angle is around 45 ° and the
zero sequence values are of the same magnitude as the positive
sequence values.

Transformers are represented by their short circuit impedance.


As the transformer is almost entirely inductive, the resistance
normally is neglected.

The impedance of the transformer is:

zk 2

- × ------
X = ---------
100 S N
where “zk” is the short circuit impedance. For a three winding
transformer there are short circuit impedances between all of the
three windings.

Figure 1. The Star delta impedance transformation is necessary to calculate


fault currents when three winding transformers are involved.

In this case the star/triangle transformation is useful.


z 12 × z 13
z1 = z + z + z -
------------------------------------
12 13 23

z 12 × z 23
z 2 = ------------------------------------
z 12 + z 13 + z 23
-

z 13 × z 23
z 3 = ------------------------------------
z 12 + z 13 + z 23
-

BALANCED FAULT CALCULATION

30 BA THS / BU Transmission Systems and Substations LEC Support Programme


Fault Calculation
z1 z2 + z2 z3 + z3 z1
z 12 = -----------------------------------------------
z3
-

z1 z2 + z2 z3 + z3 z1
z 23 = -----------------------------------------------
z1
-

z1 z2 + z2 z3 + z3 z1
z 13 = -----------------------------------------------
z2
-

Typical values for “zk” are 4-7% for small transformers (<5MVA)
and 8-15% for larger transformers (these figures must be given
by the transformer manufacturer in every single case as the val­
ues can differ within a wide range).

When it comes to the zero sequence impedance of the transform­


er, It’s depending on the type of connection. These figures must
be given by the manufacturer in every single case. The following
figures can be a guideline:
Dyn: Z0 = 0.8-1.0 times Zk
Yzn: Z0 = 0.1 times Zk
Yyn+d: Z0 = 2.5 times Zk
Yyn: Z0” = 5-10 times Zk for a three leg transformer without equalizing
winding.

Yyn: Z0” = 1000 times Zk for a five leg transformer or single phase trans­

formers.
Zk is the short circuit impedance for three phase faults.

Synchronous machines are represented by the transient reac­


tance as described earlier when the time aspect was discussed.

Asynchronous machines only contributes to the fault current,


the motor operates as a generator, for about 100 ms after the
fault occurrence. They are therefore neglected in short circuit cal­
culations for protection relay applications.

BALANCED FAULT CALCULATION

BA THS / BU Transmission Systems and Substations LEC Support Programme 31


Impedance transformation
To be able to make the calculations with Thevenin´s theorem,
all impedances must be transformed to the same voltage level
with the following formula:
2
V 
Z 1 =  -----1- × Z 2

 V 2

where index 1, is the primary side and index 2, is the second­


ary side of the transformer.

Network reduction
When all network parameters has been transformed into the
same voltage level they can be calculated in the same way as
series and parallel resistance. The total network impedance is
then reduced to one impedance.

Short circuit calculation


Now the phase voltage is connected to the impedances calcu­
lated above. The short circuit current is calculated with Ohm´s
law.

4.2 SHORT CIRCUIT CALCULATIONS WITH


SHORT CIRCUIT POWER

As an alternative to the impedance calculations described the


short circuit power of the different objects can be used. It´s
then to be observed that:
- The result of short circuit powers in parallel is the series of the indi­
vidual short circuit powers.
- The result of short circuit powers in series is the parallel connection
of the individual short circuit powers.

The following examples shows the two methods used and nor­
mally a combination of both is used.

BALANCED FAULT CALCULATION

32 BA THS / BU Transmission Systems and Substations LEC Support Programme


Fault Calculation

BALANCED FAULT CALCULATION

BA THS / BU Transmission Systems and Substations LEC Support Programme 33


Example 1. Calculate the fault current IK4 at a three phase
fault.
.

10
2
132  2
X g1 = 0.15 --------- ----------  = 130.7 Ω
20  10 
2
132
X tr1 = 0.05 ------------ = 43.6 Ω
20

X g1 + X tr1 = 174.3 Ω = X k1

10 132 
2 2
X g2 = 0.19 --------- ----------  = 331.1Ω
10  10 

2
132
X tr2 = 0.06 ------------ = 104.5 Ω

10

X g2 + X tr2 = 435.6Ω = X k2

The total short circuit impedance of the 132 kV busbar is:

X k3 = X g1 + X tr1 //X g2 + X tr2 = X k1 //X k2

which gives:

X k3 = 124.5Ω

BALANCED FAULT CALCULATION

34 BA THS / BU Transmission Systems and Substations LEC Support Programme


Fault Calculation
We get the equivalent circuit:

The following result is achieved:

76.2
I k4 = --------------- = 0.46 kA
124.5

Calculation with short circuit power:


20 - × ----------
---------- 20 ­
0.15 0.05-
S k1 = -----------------------------
20 20 = 100MVA
----------- + ----------­
0.15 0.05

10 - × ----------
---------- 10 ­
0.06 0.19-
S k2 = -----------------------------
10 - ---------- 10 ­ = 40MVA
---------- +
0.06 0.19

“Sk1+Sk2= Sk3” which gives: “Sk3”= 140 MVA.

The equivalent short circuit power of the line is:


2
132
S L = ------------ = 435.6 MVA
40

BALANCED FAULT CALCULATION

BA THS / BU Transmission Systems and Substations LEC Support Programme 35


Now we get the total short circuit power up to the fault:
(100 + 40) × 435.6
S k4 = -------------------------------------------------
100 + 40 + 435.6 = 105.9 MVA
-

This finally gives the fault current:

105.9
I k4 = ----------------------- = 0.46 kA
3 × 132

5. UNBALANCED FAULT CALCULATION

Unbalanced faults means single phase faults or two phase


faults with or without earth connection.

For a two phase fault without earth connection the fault current
will be:

3
I 2ph = ------- × I 3ph
2

In reality there always is a resistance at the fault. The resis­


tance at two phase faults consist mainly of the arc resistance.
In some cases the resistance at the fault can be much higher
than usual. For example when a wooden branch is stuck be­
tween the phases. To get a correct calculation of two phase
faults symmetrical components are normally used.

For earth faults the earthing principle is the most important for
the fault current. In an effectively earthed system, the fault cur­
rent is of the same size as the three phase fault current. To
make correct calculations of this current symmetrical compo­
nents are used.

5.1 SYMMETRICAL COMPONENTS

The method of symmetrical components provides a practical


technology for making fault calculations of unsymmetrical

UNBALANCED FAULT CALCULATION

36 BA THS / BU Transmission Systems and Substations LEC Support Programme


Fault Calculation
faults, both single- and two phase faults. The method was invent­
ed by Charles L Fortescue in 1913 and was developed further by
others until its final form was presented in 1943.

The method is a mathematical tool which is used to describe and


calculate the phenomena in a three phase system at unsymmet­
rical load or when an unsymmetrical fault occurs. For the three
phase system three distinct sets of components are introduced
for voltages and currents: positive, negative and zero sequence
components.

POSITIVE SEQUENCE SETThe positive sequence components


consist of the balanced three phase currents and lines to neutral
voltages supplied by the system generators. They are always
equal in magnitude though the phases are displaced 120°. The
positive system is rotating counterclockwise at the system fre­
quency. To document the angle displacement it’s convenient to in­
troduce an unit phasor with an angle displacement of 120°, called
“a”. We get the following relations:

a = 1/120° = -0.5+j0.866
a2 = 1/240° = -0.5-j0.866
a3 = 1/360° = 1.0+j0

CONVENTION IN THIS PAPERThe phase components are


designated “a”, “b”, and “c”. Positive sequence components are
designated “1”, negative “2” and zero sequence components “0”.
For example “Ia1” means the positive sequence component of the
phase current in phase “a”.

Now the positive sequence set of symmetrical components can


be designated:
Ia1 = 1

Ib1 = 2aIa1 = 2aI1 = 1I

/240°

Ic1 = aI
a1 = aI1 = 1I

/120°

V a1 = 1

V b1 = 2aV a1 = 2aV 1 = 1V

/240°

UNBALANCED FAULT CALCULATION

BA THS / BU Transmission Systems and Substations LEC Support Programme 37


V c1 = aV
a1 = aV
1 = 1
V

/120°

NEGATIVE SEQUENCE SET This is also a balanced set of


quantities with 120° phase displacement. The difference from the
positive sequence components is that the system is rotating
clockwise at power frequency.

The negative sequence set can be designated:


Ia2 = 2

Ib2 = aI
a2 = aI
2 = 2I

/120°

Ic2 = 2aIa2 =a2I2 = 2I

/240°

V a2 = 2

V b2 = aV a2 = aV2 = 2V

/120°

V c2 = 2aV a2 = 2aV 2 = 2V

/240°

ZERO SEQUENCE SET The zero sequence components are al­


ways equal in magnitude and phase in all phases.

We get the following equations:


Ia0 = b0
I = c0
I =I

V a0 = b0
V = c0V
=V0

Description of the system


All conditions in the network can be described using the above
defined symmetrical components. Three groups of equations are
used:

BASIC EQUATIONS These equations are valid during all conditions


in the network and is a description of how the system of symmet­
rical components is built.

V a = 0V

+V 1+V 2
(1)

+a2V 1+aV2

V b = 0V
(2)

Vc = +aV1+a2V 2

0 (3)

Ia = 0I

+I1+I2
(4)

+a2I1+aI2

Ib = 0I
(5)

Ic = +aI1+a2I2

0I
(6)

UNBALANCED FAULT CALCULATION

38 BA THS / BU Transmission Systems and Substations LEC Support Programme


Fault Calculation
GENERAL EQUATIONS These equations are valid during all
conditions in the network and give the conditions for the electro­
motoric forces in the network. The electromotoric forces only ex­
ists when the positive sequence components in a network are
balanced before the fault occurs. The electromotoric forces only
exist in the positive sequence system.

According to the superposition theorem the following statement


is valid:
A network can be replaced by a simple circuit, where the electro­
motoric force voltage equals the open circuit voltage of the net­
work and the internal impedance equals the impedance of the
network measured from the external side, if the voltage sources in
the network are short circuited. The currents are defined positive
out from the network.

This gives the following equations:

E 1 = 1V

+I1Z 1 (7)

0 = 2V

+I2Z 2 (8)

0 = 0V

+I0Z 0 (9)

Where “Z1” is the positive sequence impedance of the network,


“Z2” is the negative sequence impedance and “Z0” is the zero se­
quence impedance of the network. The actual values of these
network impedances are depending on the network and are used
and reduced in the same way as when calculating symmetrical
faults.

SPECIAL EQUATIONS These equations varies from fault to fault.


They will be explained more in detail when the fault types are dis­
cussed later on, but can shortly be explained:

Ia = 0 (10)

Ib+Ic = 0 (11)

V b-Vc = I

bZ bc (12)

UNBALANCED FAULT CALCULATION

BA THS / BU Transmission Systems and Substations LEC Support Programme 39


Impedance between two phases

E1 Z1

E2=0 Z2 b

E0=0
Z0 c

Ib Ic

Zbc

When the impedance “Zbc” is inserted, an unsymmetrical current


is drawn from the network. The following equations are achieved
according to the general, special and basic equations showed
above.

According to equation (4):


I0+I1+I2 = aI

= 0

Ib = -Ic inserted in equation (5) and then taking (5) + (6) give:
2)I+(a2 + a)I

2I0+(a+a 1 2 = 0

which means that:


I0 = 0, since there is no earth-connection in the fault (13)

I1+I2 = 0
(14)

Equation (12) together with (2), (3) and (14) give:


(a2-a)(V1-V2) = Zbc(a2-a)I1
V 1-V2 = bc
Z I1 (15)

Equation (7) and (8) together gives:


E 1 = V1-V2+I1Z 1-I

2Z 2
(16)

Insert (14) and (15) into (16):


E1
I 1 = ----------------------------------- = – I 2 (17)
Z 1 + Z 2 + Z bc

UNBALANCED FAULT CALCULATION

40 BA THS / BU Transmission Systems and Substations LEC Support Programme


Fault Calculation
Equations (13) to (17) gives for a two phase fault the following
block diagram:
I1 = 2-I
I0 I1
I2

Z2

Insert 13, 17 into 7, 8 and 9 and you will get:


 Z1 
V 1 = E 1 1 – -----------------------------------  (18)
 Z 1 + Z 2 + Z bc 

Z2
V 2 = E 1 ----------------------------------
- (19)
Z 1 + Z 2 + Z bc

and:
V0 = 0 (20)

The unknown phase currents and voltages can be calculated by


inserting 11,13 and 14 into 17 into the basic equations:

2 E1
I b = –I c = a – a ----------------------------------
- (21)
Z 1 + Z 2 + Z bc

Before the fault occurred there were only positive sequence volt­
age.
E a = 1

E b = 2a

E 1

E c = aE

UNBALANCED FAULT CALCULATION

BA THS / BU Transmission Systems and Substations LEC Support Programme 41


“Ea“, “Eb” and “Ec” are the voltages, when the system is in a
balanced condition.

This gives:

Eb – Ec
I b = –I c = ----------------------------------- (22)
Z 1 + Z 2 + Z bc
and:

 Z1 – Z2 
V a = E a 1 – ----------------------------------
- (23)
 Z 1 + Z 2 + Z bc 

and:

Eb Z1 – Ec Z2
V b = E b – ----------------------------------
- (24)
Z 1 + Z 2 + Z bc

Ec Z1 – Eb Z2 (25)
V c = E c – ----------------------------------
-
Z 1 + Z 2 + Z bc
In reality, we have “Z1 = Z2 = Z”. The following network is
achieved:

The following equations are achieved:


Eb – Ec (26)
I b = –I c = -----------------------
2Z + Z bc
V a = a

E (27)

UNBALANCED FAULT CALCULATION

42 BA THS / BU Transmission Systems and Substations LEC Support Programme


Fault Calculation
V b = bE - ZI
b
(28)

V c = cE - ZI
c
(29)

For a two phase fault without fault resistance “Zbc” is set to 0.

Impedance between phase and earth


E1 Z1 VC
E2 = 0 Z2 VB

E3 = 0 Z0 VA
0

Za
Ia

The general and the basic equations will still be the same as in
“Impedance between two phases” but the following special equa­
tions are achieved:

The special equations:


Ib = 0 (30)

Ic = 0 (31)

V a = aI

Za (32)

UNBALANCED FAULT CALCULATION

BA THS / BU Transmission Systems and Substations LEC Support Programme 43


Transformation of the equations 30, 31, 5, 6, as in ”Impedance
between two phases” gives the following result:
I0 = I1 = I2 (33)

E 1

I 1 = I 2 = I 0 = ------------------------------------------------- (34)

3Z a + Z 0 + Z 1 + Z 2

E1 Z1
V 1 = E 1 – ------------------------------------------------
- (35)
3Z a + Z 0 + Z 1 + Z 2

E1 Z2
V 2 = ------------------------------------------------- (36)
3Z a + Z 0 + Z 1 + Z 2

E1 Z0
V 0 = ------------------------------------------------- (37)
3Z a + Z 0 + Z 1 + Z 2

This gives the following figure:

3E a
Ia = ------------------------------------
- (38)
2Z + Z 0 + 3Z a

Ib = Ic = 0 (39)

UNBALANCED FAULT CALCULATION

44 BA THS / BU Transmission Systems and Substations LEC Support Programme


Fault Calculation

 2Z + Z 0 
V a = E a 1– ------------------------------------
- (40)
 2Z + Z 0 + 3Z a 

Z0 – Z (41)
V b = E b – E a ------------------------------------
-
2Z + Z 0 + 3Z a

Z0 – Z (42)
V c = E c – E a ------------------------------------
-
2Z + Z 0 + 3Z a

This simple network is achieved:


EC Z
VC
EB Z
VB
EA Z
VA

Za
1/3(Z0-Z) 0

Example 1

Generator: Xg = 24.2 Ω/ph, (X1 = X2)


Transformers: Xk1 = 12.1 Ω/ph, Xk2 = 10 Ω/ph
(Zero and positive sequence impedances equal).
Network: Xn = 8.3 Ω/ph
Line: X1 = 40 Ω/ph, X0 = 120 Ω/ph

UNBALANCED FAULT CALCULATION

BA THS / BU Transmission Systems and Substations LEC Support Programme 45


Calculate the fault current for:
a) Two phase fault with zero fault resistance.
b) Single phase solid earth fault.

a) Two phase short circuit

This scheme is valid when “Z1=Z2=Z”.

In this case “Zbc” is set to 0.


The value of “Z” is calculated:
(X g + X k1 )(X L + X k2 + X n )
Z = --------------------------------------------------------------------
X g + X k1 + X L + X k2 + X n

Then “Z” = 22.4 Ω/ph and “Ib” = 1.23 kA/ph

b) Single phase solid earth fault

This scheme is also valid when “Z1=Z2=Z” and “Z” = 22.4 Ω/ph

UNBALANCED FAULT CALCULATION

46 BA THS / BU Transmission Systems and Substations LEC Support Programme


Fault Calculation

3E a
I a = -------------------------------------
2Z + Z 0 + 3Z a

X k1 (X 0L + X k2 )
X 0tot = -
----------------------------------------
X k1 + X 0L + X k2

This gives “X0tot” = 11.1 Ω/ph and

55 × 3
I a = ------------------------------------------------- = 1.71 kA
3 ( 11.1+2 × 22.4)

It should be noted that the current at single phase fault is higher


than the fault current at three phase fault.

Example 2:

Transformer: 20MVA, 16/77 kV, xk =8%, Yd11

Generator: 20MVA, 16 kV, x(transient) =25%, X2 = X1


Line: X1 = 84 Ω/ph, X0 = 300 Ω/ph

The line is considered unloaded before the fault and all resis­
tance and capacitance is neglected. The voltage at the fault po­
sition is 75 kV before the fault.

Calculate the fault current through the earth connection of the


transformer, the phase currents on both sides of the transformer
and the voltages (to earth) in the HV terminals of the transformer.

UNBALANCED FAULT CALCULATION

BA THS / BU Transmission Systems and Substations LEC Support Programme 47


Calculation of the 77 kV impedances.

Generator:
2  2
16 77
X 1 = X 2 = 0.25 × --------- × ------  = 74Ω/ph
20 16 
Transformer:

77 2 = 23.7Ω/ph
X 1 = X 2 = 0.08 × -----
-
20

Line:
Ω/ph, 0X= 300
X 1 = 2X = 84 Ω/ph

The following block diagram is achieved:

Ω/ph
X 1 = 2X = 181.7

Ω/ph
X 0 = 323.7

75
I 1 = I 2 = I 0 = -----------------------------------------------------------= 0.063 kA/ph
3 ( 2x181, 7 + 323, 7 )
The current through the earth connection of the transformer.
Ig = 3xI0 = 0.189 kA

The component voltages at the HV side:


U 1 = 1E

+dU 1 = 43.3-(j97.7)(-j0.063) = 37.15 kV

U 2 = dU

2 = -j97.7(-j0.063) = -6.15 kV

U 0 = dU

0 = -j23.7(-j0.063) = -1.49 kV

Phase voltages:
UNBALANCED FAULT CALCULATION

48 BA THS / BU Transmission Systems and Substations LEC Support Programme


U a = U0+U 1+U 2 = 29.5/0° kV

U b = U0+a2U 1+aU2 = 41.3/-114.4° kV

U c = U0+aU1+a2U 2 = 41.3/114.4° kV

Phase currents:
Ia = I

0+I1+I2 = 3x0.063 = 0.19 kA

+a2I1+aI2 = 0.063(1+a

Ib = 0I 2
+a) = 0 kA

+aI1+a2I2 = 0.063(1+a

Ic = 0I 2
+a) = 0 kA

Phase currents on the LV side:


Connection:

Figure 2. The positive sequence current is turned +30°, while the negative
sequence current is turned -30°.

At the 16 kV side there is no zero sequence current as the trans­


former is Yd connected “I0”=0.

The phase currents at the 16 kV side:

I a = 77
j30° –j30°
------ (0 + 0.063e + 0.063e )=
16
77
= ------ 3 × 0,063= 0.52 kA
16

I b = 77
j30° 2 – j30°
------ (0 + 0.063e a + 0.063e a)=
16

77 j30° –j120° –j30° j120°


= ------(0.063e e + 0.063e e ) = 0kA
16

UNBALANCED FAULT CALCULATION

49 BA THS / BU Transmission Systems and Substations LEC Support Programme


j30° – j30° 2
I c = 77
------ (0 + 0.063e a + 0.063e a )=

16

= 77
j30° j120° –j30° –j120°
------ (0.063e e + 0.063e e )
16

77 3 × 0,063= 0.52 kA

= -----
-
16

UNBALANCED FAULT CALCULATION

50 BA THS / BU Transmission Systems and Substations LEC Support Programme


System Earthing
1. WHAT IS SYSTEM EARTHING

The term “earthing” consists of several functions which only have


“utilizing the earth” in common. Before describing the system
earthing, it can be of interest to know a bit about the different
types of earthing.

Protective earthing is applicable mainly in electronic equipment


to prevent damage or errors at the components. Example of pro­
tective earthing is when a screened cable is earthed, or when an
incoming signal conductor is connected to earth through a ca­
pacitor or a filter.

Protective earthing can be described as a way of protecting man


from dangerous voltages. Example of protective earthing is,
when the casing of e.g. a washing machine is connected to earth
(green/yellow conductor) or when a row of switchgear cubicles
are connected to an earth conductor, which connects the cover
of the cubicle to earth.

Lightning protection can also be a part of system earthing.

System earthing concern the kind of deliberate measures that


connects a normally live system to earth. It is normally the zero
point of the system that is connected to earth but other solutions
can occur.

Of course, all types of systems can be earthed, and the terminol­


ogy “system earthing”, can thus be used. Systems like electronic
systems and battery systems, measuring transformer circuits
etc., are often earthed. In the following text we will only consider
system earthing of alternating current systems for power distribu­
tion and transmission, with a voltage over 150 V.

If a point in a system is earthed the whole system will be earthed


as far as the galvanic connection goes. A system earthing on the
contrary does not affect the parts of the network that are connect-

WHAT IS SYSTEM EARTHING

BA THS / BU Transmission Systems and Substations LEC Support Programme 51


ed magnetically to the earthed part of the network, for example
through transformers. See figure 1.

Figure 1. The earthing of a system is effective for all galvanic connected


parts.

2. WHY USE SYSTEM EARTHING

The main reason for connecting the network to an earth potential,


is of course that both human beings and equipment will be pro­
tected. These are only two reasons for system earthing but many
other requirements on operation reliability have to be fulfilled as
well.

Some of the reasons to use system earthing are described in the


following text.

2.1 FIX THE NETWORK TO EARTH POTENTIAL

All alternating current networks are in one way or another cou­


pled to earth through leakage capacitances. The capacitances
can be so small that the network at some occasions can reach a
dangerously high potential.

WHY USE SYSTEM EARTHING

52 BA THS / BU Transmission Systems and Substations LEC Support Programme


System Earthing

If a connection between the conductors in two networks with dif­


ferent voltage occurs, the network with the lowest voltage would
get a dangerously increased voltage to earth. This can be pre­
vented by a suitable earthing of the network with the lowest volt­
age.

Even if there is no direct connection a dangerous voltage can oc­


cur due to the capacitive coupling between the two networks.

2.2 REDUCE THE FAULT CURRENT AT EARTH


FAULT.

In an unearthed network a capacitive current will appear when an


earth fault occurs. This derives basically from the leakage capac­
itance in cables and overhead lines but also generators, motors
and transformers contributes. Depending on the voltage level and
the distribution of the network this current can reach values from
a few, up to hundreds of Amperes in big cable networks. The ca­
bles will give the highest capacitive current.

A formula for the capacitive current IC of cables is normally stated


as IC = UH/10x3 A/km, where UH is the line voltage.

If the capacitance of the network is compensated with a reactor


connected to the neutral point, the current through the fault point
can be drastically reduced, See figure 2. This is advantages since
the damage caused by the fault current through the fault location
is limited.

WHY USE SYSTEM EARTHING

BA THS / BU Transmission Systems and Substations LEC Support Programme 53


L1

L2

L3

IL Ic Ic
Ij

L1U

Ictot
L2Ic

L1Ic UN
L3U L2U

IL

Figure 2. Reduction of earth fault current with a neutral-point impedance.


Resulting earth fault current Ij is very small if IL= ICTot

2.3 REDUCE OVERVOLTAGES

The overvoltages that can be reduced through system earthing

are those who depend on transient earth faults, increased neu­

tral-point voltage and transients due to switching or lightning.

Transient earth faults

At occurring earth faults, especially in systems with small earth

fault current, the conditions are such that the arc will be extin­

guished at the zero passage of the current. Afterwards it will be

re-ignited when the voltage increases over the fault point again.

This phenomenon is in USA, called “arcing grounds”.

If the current and the voltage at the fault point not are zero simul­

taneously the transient fault can throughout repeated extinctions

and reignitions create a high overvoltage in the whole network.

The overvoltage will be particularly high if the system is com-

WHY USE SYSTEM EARTHING

54 BA THS / BU Transmission Systems and Substations LEC Support Programme


System Earthing
pletely unearthed and the earth fault current is only dependent of
the leakage capacitance of the system, this is shown in Figure 3.

Xco/R
Xco/XL

Xc0 is the total network reactance to earth 1/ωC.


R0 is the neutral resistor resistance at resistance earthing
XL is the neutral reactor reactance ωC
Figure 3. The influence of earthing, in the maximum overvoltage, due to tran­
sient earth faults.The transient overvoltage in the figure, is written in percent
of the phase voltage top value. The upper curve shows the overvoltage for
a neutral reactor earthing.

“XC” is the leakage capacitive reactance to earth which is depen­


dent of the total capacitance (1/wC) of the network and “R” is the
resistance of the neutral resistor.

The figure above shows that an earthing should be performed in


such a way that the earthing resistance is less or equal to the ca­
pacitive reactance to earth. If the system is earthed through a re­
actor its reactance should be almost equal to, or a lot less, than
the total capacitive reactance to earth.

The figure shows the overvoltages that can occur during unfavor­
able circumstances but normally overvoltages are less. As can
be seen the overvoltages in unearthed systems can be of the
size, or higher than, the test voltage for new generators and mo­
tors. The risk of damaging these apparatuses will therefore be
very high. Surge arresters won’t give a reliable protection, since
they will be destroyed at repeated overvoltages. A system which
WHY USE SYSTEM EARTHING

BA THS / BU Transmission Systems and Substations LEC Support Programme 55


contains generators or motors should therefore always be
earthed in some way.

Increased neutral-point voltage


In case of an earth fault in one phase in an unearthed network a
phase-ground voltage will appear in the neutral-point and the oth­
er two phases will thus have their phase-phase voltage to earth.
By using an effective earthing (see section 3.2) the voltage can
be reduced to 80% of the phase-phase voltage. It’s then possible
to choose apparatuses with lower insulating level which means
considerable cost reducing at high voltage networks. A trans­
former with a direct earthed neutral-point can furthermore be
equipped with graded insulation. This means that the insulation
level is lower close to the neutral-point than at the line terminals
which give considerable savings for big power transformers.

Coupling and lightning overvoltages


Operating of switching apparatuses can create overvoltages
which usually are higher than three times the nominal voltage but
of short duration. The overvoltages are created through transient
oscillation in the capacitance and the inductance of the circuit.

Neutral point earthing will probably not reduce the overvoltages


created by switching waves or lightning. They can though distrib­
ute the voltage between the phases and reduce the possibility of
a high voltage stress on the insulation between one phase and
earth.

2.4 SIMPLIFY LOCATION OF EARTH FAULTS

In an unearthed network it’s often difficult to detect and clear an


earth fault. Through a suitable earthing it’s possible to create an
earth fault current that can be measured and also form a base for
the locating of the earth faults.

WHY USE SYSTEM EARTHING

56 BA THS / BU Transmission Systems and Substations LEC Support Programme


System Earthing
2.5 AVOID FERRO-RESONANCE

Voltage transformers connected to an unearthed network can un­


der particular circumstances create abnormal neutral-point volt­
ages. The voltage transformer can then be regarded as an
non-linear inductance, which goes into self-oscillation with the
capacitance of the network. This phenomenon is called “fer­
ro-resonance”.

The abnormal neutral point voltage can damage the voltage


transformers and create unwanted earth fault indications. If the
network is earthed the phenomenon will not appear. In an un­
earthed network the oscillation can be prevented by connecting
a resistor either to the “delta” winding in a three phase voltage
transformer or to a zero-point voltage transformer. Note that such
a resistor gives the same result as a resistor with a very high re­
sistance connected directly between the zero-point and earth
(See figure 4).

Figure 4. Three equal methods to prevent ferro resonance.

WHY USE SYSTEM EARTHING

BA THS / BU Transmission Systems and Substations LEC Support Programme 57


3. DIFFERENT TYPES OF SYSTEM EARTHING

In Swedish Standards (following IEC) the following earthing alter­


natives are given:
a) Systems with an isolated neutral-point
b) Coil earthed systems.
c) Earthed system:

-Effectively earthed system

-Not effectively earthed system.

In american literature, “Electrical power distribution for Industrial


Plants” (ANSI/IEEE 141 1986), the following alternatives are
mentioned:
a) Solidly earthed (without deliberate earthing impedance)
b) Reactance earthed
c) Resistance earthed by low- or high resistance.
d) Unearthed

With these alternatives as a base it’s possible to distinguish the


types of earthing that are explained in the following sections:

3.1 DIRECT EARTHING

Direct earthing means that the neutral-point of the network is


earthed in at least one point without deliberately inserting any im­
pedance. Observe that this not quantifies how effective the earth­
ing is since the neutral point impedance still can be high. This can
happen if i.e. the neutral-point in a transformer, that is small com­
pared to the short circuit effective output of the network, is
earthed. It can also happen if the earth resistance is high.

Direct earthing describes how the earthing is done not the result
achieved. However, normally it’s understood that the direct
earthed system should be effectively earthed.

DIFFERENT TYPES OF SYSTEM EARTHING

58 BA THS / BU Transmission Systems and Substations LEC Support Programme


System Earthing
3.2 EFFECTIVE EARTHING

An effectively earthed network follows the requirements given in


ANSI and SS (Cenelec). A system, or a part of a system, is con­
sidered effectively earthed, when the following statements are
valid in all points of the system:

ANSI & SS (Cenelec) gives “X0≤3X1” and “R0≤X1”, where “X0” is


the zero sequence reactance, “R0” is zero sequence resistance
and “X1” is the positive sequence reactance.

The requirements leads to a maximum voltage of 80% of nominal


line voltage between a phase and earth, called the earthing fac­
tor. Therefore lower insulation requirements can be accepted and
surge arresters with lower extinction voltages can be used.

3.3 REACTANCE EARTHING

The concept reactance earthing occurs basically in american lit­


erature and relates to earthings where “X0≤10X1”. The factor “10”
is required to drastically reduce the overvoltages due to transient
earth faults. Reactance earthing is used mainly when a direct
earthing of a generator’s neutral point is not desired.

3.4 LOW RESISTANCE EARTHING

Resistance earthing is an earthing where “R0≤2X0” but “R0”, still


is so small that a big earth fault current is obtained. The resis­
tance earthing is normally done in such a way that, when a fully
developed earth fault occurs, an earth fault current between 200
and 2000 A is achieved. The advantage with this way of earthing
is that normal relays can be used for detection of earth faults.

Resistance earthing is one out of two methods recommended by


the english standard CP 1013:1965. The proposed current value

DIFFERENT TYPES OF SYSTEM EARTHING

BA THS / BU Transmission Systems and Substations LEC Support Programme 59


is 300 A. The other method is earthing through a voltage trans­
former i. e. a unearthed networks.

DIFFERENT TYPES OF SYSTEM EARTHING

60 BA THS / BU Transmission Systems and Substations LEC Support Programme


System Earthing
3.5 HIGH RESISTIVE EARTHING

High resistive earthing concerns the cases where the factor


“3R0≤Xco”, where “Xco” is the total capacitance of the network
per phase against earth, is obtained by using the biggest possi­
ble resistance R0 to earth.

If the capacitive current in a network at a fully developed earth


fault is less than 30 A it’s possible, up to voltages of 25 kV, to pro­
vide the system with a neutral-point resistance for currents of at
least the same size as the capacitive current of the network.

At transient earth faults the voltage in the network stays within


reasonable limits (see figure 3) and the current to earth increas­
es with only 50% compared to the unearthed system. The neu­
tral-point resistance can, if desired, relatively easy be installed to
withstand the phase voltage. Therefore it’s not necessary to have
a tripping earth fault relay at locations where it would create ma­
jor disadvantages for the operation. This can e. g. be the case for
industrial plants where tripping can cause a big disturbance for
the service.

When high resistive earthing is mentioned, basically in American


literature, an earthing through an one-phase transformer loaded
with a resistor secondary is intended. This is electrically equiva­
lent to a resistor directly connected between the neutral-point
and earth. See figure 5.

G G

Figure 5. Two equivalent methods for high resistance earthing.

DIFFERENT TYPES OF SYSTEM EARTHING

BA THS / BU Transmission Systems and Substations LEC Support Programme 61


3.6 RESONANCE EARTHING (EARTHING WITH PE-
TERSÉN-COIL)

For resonance earthing an inductance calibrated to the capaci­


tance of the network at rated frequency is chosen. This leads to
a small resulting operating frequency earth fault current and it is
only caused by the current due to insulation leakage and corona
effect. An arc in the fault point can therefore easily be extin­
guished since current and voltage are in phase and the current is
small. Observe that a strike through a solid material like paper,
PVC, cambric or rubber isn’t self-healing why they don’t benefit
from the resonance earthing.

The resonance coil should be calibrated to the network for all


connection alternatives. Therefore the setting must be changed
every time parts of the network are connected or disconnected.
There however exists equipment, e. g. in Sweden, Germany and
Austria, that will do this automatically.

At a resonance earthing it is often difficult to obtain selective


earth fault relays. Therefore the resonance coil is connected in
parallel with a suitable resistor giving a current of 5 to 50 A at full
zero-point voltage, i. e. a solid fault. The resistor should be
equipped with a breaker for connecting and disconnecting at
earth faults. The breaker should be used for the In-Out automatic
and for the thermal release of the resistor, if the fault is not auto­
matically cleared by the protection relays, as these normally are
not designed to allow continues connecting.

The theories about resonance earthing are very old and were de­
veloped at the time when only overhead transmission lines exist­
ed. In cable networks, high harmonic currents are generated
through the fault point. Even if the network is exactly calibrated
it’s possible that currents up to several hundred amperes ap­
pears. This of course leads to difficulties for an earth fault to self
extinguish.

DIFFERENT TYPES OF SYSTEM EARTHING

62 BA THS / BU Transmission Systems and Substations LEC Support Programme


System Earthing
Resonance earthing can also be a way to fulfil the requirements
concerning the standards for maximum voltage in earthed parts.

Through resonance earthing a smaller earth leakage current is


obtained and consequently a higher earthing grid resistance can
be accepted.

In an unearthed or voltage transformer earthed system the risks


for overvoltages at transient faults are not considered.
Generally it is recommendable to avoid unearthed systems. In
the British standards this is explicitly stated.

DIFFERENT TYPES OF SYSTEM EARTHING

BA THS / BU Transmission Systems and Substations LEC Support Programme 63


4. TO OBTAIN A NEUTRAL-POINT

In a three phase network the neutral-point often is available in a


“Y” connected transformer or in a generator neutral. This should
then be utilized at system earthing.

If the transformer is connected “Y0/D” or “Y-0/Y-0” with delta


equalizing winding, the “Y-winding” can be utilized even for direct
earthing. An “Y/Y” connected transformer without such an equal­
izing winding shall not be directly earthed but can under some cir­
cumstances be utilized for high resistance or resonance earthing.

4.1 Y0/Y-CONNECTED TRANSFORMER

If one side of a “Y/Y” connected transformer is earthed, theoreti­

cally there wouldn’t flow any current through the earth connection

since it is impossible to create a magnetic balance in the wind­

ings for this kind of currents. However, the flow is closed through

leakage fields from yoke to yoke through insulation material and

plates. This can create a local heating that will damage the trans­

former.

If the transformer has a magnetic return conductor as e. g. a five

leg transformer or three one phase units the earth current leads

to a flow in the return conductor.

The zero sequence impedance for an “Y0/Y” transformer is al­

ways high but varies, depending on the design, from 3 to 40 times

the short circuit current impedance.

If you are aware of the high zero sequence impedance and if the

transformer construction accepts the heating problems a “Y0/Y”

connected direct earthed transformer limiting the earth fault cur­

rent to about the transformers rated current can be utilized in the

power system.

4.2 Z/0-CONNECTED EARTHING TRANSFORMER

In the “Z/0” connected transformer, see figure 7, a magnetic bal­


ance for zero sequence current leading to a low zero sequence

TO OBTAIN A NEUTRAL-POINT

64 BA THS / BU Transmission Systems and Substations LEC Support Programme


System Earthing
impedance is created. The neutral point of the transformer can ei­
ther be connected directly to earth or through another neutral
point apparatus such as a resistor or reactor. In the first case the
thermal consequences must be cleared in advance as the
“Z/0”.transformer often has limited thermal capability. The earth­
ing “Z/0” transformer is thus often specified for 10 or 30 sec ther­
mal rating.

Figure 6. Z/0-connected earthing transformer.

TO OBTAIN A NEUTRAL-POINT

BA THS / BU Transmission Systems and Substations LEC Support Programme 65


5. DISTRIBUTION OF EARTH FAULT CURRENT

In calculating earth fault currents it’s advantageous, but not nec­


essary, to use symmetrical components to check the flow of the
earth fault currents.

A very simple way of checking, where only peripherally the theory


of symmetrical components is used, could be utilized. According
to this theory a current “3I0” (three times the zero sequence cur­
rent), flows through the neutral-point. This can be used in letting
the fault be represented by three “current arrows” and then exam­
ine how these can be distributed in the system maintaining the
magnetic balance. Possible positive and negative sequence cur­
rents are then not considered. Some examples of these calcula­
tions are shown in the text that follows but first an explanation of
the “zero sequence impedance”.

5.1 ZERO SEQUENCE IMPEDANCE

In the previous discussion the name “zero sequence impedance”


has been used at several occasions. The easiest way to under­
stand this term is to indicate how to measure it in practice.

The measurement of zero sequence impedance is done by short


circuiting the three phases with preserved earthing of the net­
work. Each phase has then a zero sequence impedance which is
three times the impedance measured between the three phases
and earth.

5.2 CURRENT DISTRIBUTION AT AN EARTH FAULT


WITH A Z/O EARTHING TRANSFORMER.

Whether the network has been earthed in the neutral-point, or


with a Z/O connected transformer on the generator’s line termi­
nals, the result of the earthing will be the same. This is illustrated
in figures 8 and 9.

DISTRIBUTION OF EARTH FAULT CURRENT

66 BA THS / BU Transmission Systems and Substations LEC Support Programme


System Earthing

Figure7. Figure 8.

Figure 7. The earth fault current distribution, with a resistance in the gener­

ator neutral-point.

Figure 8. The earth fault current distribution, with a neutral-point resistance,

connected to a Z/O-connected earthing transformer.

The figures above shows that the earthings are equal from the

networks point of view.

In the first case a zero sequence current goes through the gen­

erator.

In the second case the current does not contain any zero se­

quence component since the sum of the currents in the three

phases is zero.

The generator current contains only one positive and one nega­

tive sequence component.

5.3 CURRENT DISTRIBUTION AT AN EARTH FAULT


IN A TRANSMISSION NETWORK.

To show that the earth fault current not necessarily need to come
from the same direction as the power an earth fault, in a directly

DISTRIBUTION OF EARTH FAULT CURRENT

BA THS / BU Transmission Systems and Substations LEC Support Programme 67


earthed transmission network, where the receiving transformer is
earthed but unloaded is chosen, see figure 10.
G1 T1 T2

Figure 9. Current distribution in a transmission network.

It is possible to see in the figure, that neither the generator nor the
transformer “T1” has a zero sequence current since the sum of
the currents in all phases is zero. It is however easy to realize that
a negative sequence current exist. An earth current protection
measuring negative sequence current at “T2:s” HV line terminal,
would thus operate despite the fact that “T2” is unloaded.

DISTRIBUTION OF EARTH FAULT CURRENT

68 BA THS / BU Transmission Systems and Substations LEC Support Programme


System Earthing
6. TO CHOOSE SYSTEM’S EARTHING POINT

Normally in directly earthed and effectively earthed systems ev­


ery available neutral point is earthed. Deviations from this occurs
when the transformers neutral points are left unearthed. This is
done to limit the maximum earth fault current which can arise to
reasonable values. In these cases the neutral-point is equipped
with surge arresters. This is only acceptable if the network at all
operation modes still can be considered as effectively earthed
(X0≤3X1).

For the other earthing methods it is somewhat more complicated.


For example the wish to keep the earth fault current more or less
constant, at the same time as the network always must be
earthed independently of the operation mode, gives contradic­
tions and difficult choices.

6.1 INDIVIDUAL EARTHING IN EVERY NEUTRAL


POINT OF THE POWER SOURCES

G G

Figure 10. Earthing individual neutral-point with impedances.

When there only are a few generators or transformers in a sta­


tion, individual neutral-point impedances are often used. Hereby
the neutral-point connection is fixed without intervening connec-

TO CHOOSE SYSTEM’S EARTHING POINT

BA THS / BU Transmission Systems and Substations LEC Support Programme 69


tion devices. When just two power sources are used individual
neutral-point impedances are preferred to a common earthing
impedance. When several power sources are used the earth fault
current is increased every time a power source is connected and
can reach unwanted values. At resistance earthing every resistor
must be dimensioned for a current high enough to satisfy the op­
eration of the relay equipment, when this is working alone. Con­
sequently the total earth fault current at several aggregates,
becomes several times the value required for a satisfying relay
function. A disconnector is thus often provided to enable discon­
nection of resistors when system is in parallel service condition.

The method with individual earthing is normally utilized at resis­


tance and reactance earthing, but it can also be utilized at high
resistive earthing. For resonance earthing the method is very un­
suitable.

Together with generators or motors, multiple earthing can be un­


suitable due to the danger of circulating third harmonic currents.

6.2 COMMON EARTHING THROUGH A NEUTRAL


BUSBAR.

When there are more than two generators, or transformers, in a


station it can be preferable to use just one neutral-point appara­
tus. The neutral-point of every power source is then connected
through a coupling device, breaker or disconnector, to a common
neutral busbar which is earthed through a resistor or a reactor.
This arrangement keeps the earth fault current at optimal size,
since it never has to be higher than what is needed to avoid ov­
ervoltages or to give a safe relay protection operation. There is al­
ways the same earth fault current independent of the service
condition.

Two different connections with neutral-point busbars are shown


in figures 12 and 13.

TO CHOOSE SYSTEM’S EARTHING POINT

70 BA THS / BU Transmission Systems and Substations LEC Support Programme


System Earthing

Figure 11. Resistance earthing, of the generator neutral-point, with a neutral


busbar and individual neutral-point breakers.
Figure 12. Resonance earthing, of transformer neutral-point, with a neutral
busbar and individual disconnectors.

Due to the third harmonic problem only one of the breakers in fig­
ure 12 resp. 13 should be closed at a time.

When one of the generators is taken out of service it’s important


that the corresponding neutral point breaker (or disconnector) is
opened. This since the neutral busbar will be current carrying at
an earth fault and achieve the phase voltage to earth.

6.3 COMMON EARTHING THROUGH A EARTHING


TRANSFORMER ON THE BUSBAR.

An effective and often cheap way to make sure that the system
always is correctly earthed is to connect any earthing transform­
er, according to section 4, to the busbar. See figure 13 which
shows the same network as in figure 10 but with an alternative
method of earthing.

TO CHOOSE SYSTEM’S EARTHING POINT

BA THS / BU Transmission Systems and Substations LEC Support Programme 71


Z-0

G G

Figure 13. Earthing, with a Z/O-connected transformer on the busbar.

TO CHOOSE SYSTEM’S EARTHING POINT

72 BA THS / BU Transmission Systems and Substations LEC Support Programme


System Earthing
7. PRACTICE OF EARTHING

The practice of earthing differs very much from country to coun­


try. It is however possible to distinguish countries as Germany,
Netherlands and Sweden etc., where the main direction has
been to protect the telephone networks and people. It is also pos­
sible to distinguish countries as USA, Canada and England,
where the power network protection has been considered first.
The first mentioned countries has focused on limiting the earth
faults currents to low values, while the latter countries has ac­
cepted the higher earth faults currents to prevent overvoltages in
the power system and simplify fault clearance.

A summation of the practices in different countries would unfor­


tunately be very extensive, especially as the networks differs
even within the countries. However, a simplified summary follows
below.

7.1 VOLTAGES OVER 100 KV

At high voltages there is an economic advantage in earthing the


network directly (effectively). By doing so transformers and insu­
lators etc. can be built with a lower test voltage at neutral and a
graded insulation, which gives considerable cost savings.

In most countries it’s normal with a direct earthing at voltages


over 100 kV. In e. g. Germany, Netherlands and Norway, however
there are 130kV networks with resonance earthing.

7.2 VOLTAGES BETWEEN 25 AND 100 KV

USA Most parts of the country are directly earthed but resistance
and reactance earthing occur.

ENGLAND Most parts of the country are resistance earthed in the


neutral-point of the power source. The resistance gives an earth

PRACTICE OF EARTHING

BA THS / BU Transmission Systems and Substations LEC Support Programme 73


fault current of the same size as the rated current in the trans­
former. Some 33 kV networks can however be resonance
earthed.

GERMANY, SWITZERLAND, AUSTRIA, NETHERLANDS, BELGIUM,

Uses reso­
SPAIN, IRELAND, NORWAY, DENMARK, SWEDEN, JAPAN.

nance earthing.

FRANCE, SOUTH AFRICA.


Most parts of the countries are resistance earthed (reactance
earthing occur). France is investigating the possibilities of a
change over into resonance earthing (with transient measuring
earth fault protection).

AUSTRALIA Uses direct earthing and resonance earthing. Some


33 kV networks can however be resistance earthed.

NEW ZEALAND Uses direct earthing

INDIA, MALAYSIAResonance earthing is the most common earth­


ing but also resistance earthing occurs. And in India also direct
earthing can occur.

7.3 VOLTAGES BETWEEN 1 AND 25 KV FOR DISTRI-


BUTION WITH OR WITHOUT DIRECT CONNECTED
GENERATORS

In most countries varying types of earthing can occur but the res­
onance earthing is the most common. However unearthed net­
work as well as high resistance earthings can occur.

Resistance earthing is most common in USA and England.

Direct earthing is most common in Australia and Canada but can


also occur in USA and Finland.

The earthing in Sweden, is mainly decided by §73 in Kommer­


skollegi standards, which says it’s practically impossible to use di­
rect, or reactance earthing concerning these voltage levels. This
is due to high requirements on detection of fault resistances at

PRACTICE OF EARTHING

74 BA THS / BU Transmission Systems and Substations LEC Support Programme


System Earthing
earth faults. Fault resistance values of 3000 resp. 5000 Ω are
mentioned depending of type of feeder.

7.4 GENERATOR NETWORK

Generator networks, are the type of limited networks that consist


of one or several generators connected to a primary transformer,
but without direct connection to the distribution lines.

These limited networks are almost always high resistance


earthed. However at new constructions unearthed networks rare­
ly occurs.

7.5 VOLTAGES UNDER 1 KV

These networks are normally direct earthed. In industries with


pure motor networks, unearthed or high resistance earthed net­
works are mainly used.

A special type of earthing, is used by the Swedish state power


board in their “unearthed” motor network. The high resistance
network has been replaced with a voltage dependent resistor. At
earth faults a small current is created through the resistor and the
network can be considered as unearthed. At flash-over from the
network, at the primary side of the transformer (normally a high
resistance earthed 10 kV network) the resistance in the resistor
will be so low that the overvoltage in the low voltage network will
be limited to 2 kV. See figure 15.

< 2 kV

PRACTICE OF EARTHING

BA THS / BU Transmission Systems and Substations LEC Support Programme 75


Figure 14. Earthing with a voltage dependent resistor, to limit the overvolt­
age, at a break-down of a high voltage network.

PRACTICE OF EARTHING

76 BA THS / BU Transmission Systems and Substations LEC Support Programme


System Earthing
7.6 CHOICE OF EARTHING METHOD

It’s rarely possible to change an already established earthing


practice. At new deliveries or extensions it’s therefore necessary
to adapt to the already existing practice. Depending on the qual­
ities considered important, the earthing that will give the most ad­
vantages and the lowest total cost solution, regarding the
methods described in the following section is chosen.

7.7 COMPARISON OF DIFFERENT EARTHING PRIN-


CIPLES

A comparison between different system earthing principles, can,


based on the different parts according to table 1, be done. In the
table resistance earthing is divided into low resistance and high
resistance earthing depending on the effects regarding the dam­
ages from the current.
Tabell 1:

Type of
Solidly/ Low High
earthing/ Reactance Resonance Unearthed
Effectively resistance Resistance
Feature

Damage of --- -- - ++ +++ ++


equipment
Damage of -- -- - ++ +++ ++
property
Person inju­
--- --- --- + + -
ries
Arcing faults +++ +++ +++ ++ ++ ---
Overvoltage +++ ++ ++ + + ---
Ferro reso­ +++ +++ +++ +++ +++ ---
nance
Req on --- -- - + ++ ++
earthing grid
Apparatus +++ - - - - ---
insulation

PRACTICE OF EARTHING

BA THS / BU Transmission Systems and Substations LEC Support Programme 77


Tabell 1:

Type of
Solidly/ Low High
earthing/ Reactance Resonance Unearthed
Effectively resistance Resistance
Feature

Selective ++ +++ +++ + - -


protection

DAMAGES ON EQUIPMENT Damages on the electrical equipment

are normally pure quadrilateral dependent on the current and the

fault time. Since “I2t” measures the energy, a lower current is a

big advantage in limiting the damages. This is of major impor­

tance when rotating machines are included in the network.

DAMAGES ON PROPERTY Damages on property are depending on

the current but normally in steps since damages on equipment

(for example the telephone network) occur, when its durability is

surpassed. The risk for fire due to an earth fault, follows the “I2t”

relation. Note that for higher voltages there are such big distanc­

es to earth and between phases that a good protection exist in

the physical construction. On distribution level the risk for damag­

es on property is however of greater importance.

INJURIES ON PERSONSAs mentioned earlier, some countries have

chosen to keep the current low to protect people and property.

Other countries have considered it as more important to optimize

the system and ensure simple and fast fault clearance.

The risk for injuries on persons can be divided into occuring step

and touch voltages at primary faults of the power system.

Figure 16 shows the risk for injuries of people in an electrical ac­

cident and how contact and step voltages arises. The injuries

consists partly of the risk for heart stop due to heart oscillation

which occurs at 30 mA and the burn injuries in the skin layers at

which the contact was made. The type of burn injuries are of

course completely dependent on the current level.

PRACTICE OF EARTHING

78 BA THS / BU Transmission Systems and Substations LEC Support Programme


System Earthing

Step voltage

Touch
voltage

Figure 15. How the step and touch voltages, arises in a direct earthed net­
work.

TRANSIENT EARTH FAULTS These consist of increased voltage at


healthy phases during a reignition of the earth fault current after
a zero crossing. A connection of the network to earth limits the
overvoltages according to the previous discussion (See figure 3).

FERRO RESONANCE (See section 2.5). A system earthing limits


the risk of ferro resonance in the voltage transformers. The un­
earthed system, or systems who risks to be unearthed under cer­
tain operation circumstances, have a big disadvantage regarding
the risk of ferro resonance.

REQUIREMENTS ON THE EARTHING GRID A limit set to the earth


fault current reduces the requirements on the earthing grid since
these are constructed to limit arisen step, and touch voltages,
which in their turn are totally dependent of the fault current.

PRACTICE OF EARTHING

BA THS / BU Transmission Systems and Substations LEC Support Programme 79


SELECTIVE EARTH FAULT PROTECTION With the relay technique of
today selective earth fault protection relays can be used in most
networks (independent of system earthing). Directional protec­
tion relays, with sensitivities of a few Ampere primary operates on
the transient and detects the earth fault even with high fault resis­
tance. Modern Protection relays which measures fundamental or
high frequency can sucessfully be used at earth fault protection.

Historically the using of selective earth faults was an important


reason to choose a high earth fault current. In directly earthed
transmission network that generates earth fault current from
many points, the using of selective earth fault protection will be
more complicated and require direction, inverse time character­
istics and calculations on current distribution in all possible fault
situations, to select settings which will give selectivity.

APPARATUSES INSULATION TO EARTH In an effectively (direct)


earthed network a graded insulation can be utilized. This gives
cost savings of 10-15% for voltages of type 130 kV. Regarding
the apparatus prices at higher voltage levels a fully insulated ze­
ro-point and the requirements on the insulation becomes impor­
tant. At voltages above 130-170 kV, nothing else but direct
earthing is used.

8. DESIGN OF EARTH FAULT PROTECTION


RELAYS

An earth fault protection relay should be constructed to interact


well with the system earthing method chosen for the network.
The system earthing shouldn’t be negatively affected by the re­
quirements on the earth fault protection relays. In some cases,
the system earthing can be chosen to make relays work more
safely.

A few of these cases will be penetrated below and Earth fault pro­
tection is further discussed in a separate section.

8.1 PARALLEL RESISTORS FOR THE RESONANCE

DESIGN OF EARTH FAULT PROTECTION RELAYS

80 BA THS / BU Transmission Systems and Substations LEC Support Programme


System Earthing
EARTHING

The existence of the parallel resistor is only for making the use of
selective earth fault protection relays possible. Since the resistor
is disconnected during the time the resonance will work to distin­
guish the fault arc, the disadvantage with resistors is eliminated.

Today, this solution is used together with a quick auto-reclose in­


stead of a previously used disconnection automatics and self-ex­
tinguisher. Tests have shown that self extinction of the short
current wasn’t possible since it was difficult to obtain a satisfacto­
ry calibration of the reactor to the capacitance in the network.

The resistor gives a possibility to instantaneous detection of the


fault. This is done by a quick disconnection of the line and it can
be connected again within 0,4 seconds with the fault point deion­
ized. This solution has begun to dominate.

8.2 INCREASED CURRENT THROUGH THE RESIS-


TOR AT HIGH RESISTANCE EARTHING.

In many cases the formula “3R0≤XC0” for high resistance earthing


gives a resistance which at full zero-point voltage only gives a few
Amperes. To be able to install selective earth current protection
the current must at least exceed 5 A. This normally gives no se­
rious disadvantages as the current still is low and can therefor be
accepted.

The highly sensitive earth current protection that is used in e. g.


Sweden and Germany seems to be rather unknown in countries
where low resistance earthing is of majority e.g. USA and En­
gland. This has resulted in that high currents in the resistance
earthed networks have been chosen to make Normal inverse
time relays (IMDTL) functional.

DESIGN OF EARTH FAULT PROTECTION RELAYS

BA THS / BU Transmission Systems and Substations LEC Support Programme 81


DESIGN OF EARTH FAULT PROTECTION RELAYS

82 BA THS / BU Transmission Systems and Substations LEC Support Programme


Protection General
1. THE TASK OF THE PROTECTION SYSTEM

The protection system shall, together with the circuit breakers,


disconnect faulty parts of the power system to:
- Protect the primary equipment against unnecessary damages.
- Save people in the vicinity of the electrical plant from injuries.
- Enable continued service in the undamaged parts of the network.

At an occurring fault in a power network the faulty part, and all


other sections where the fault current is distributed to the fault,
are exposed to abnormal forces and thermal stresses. Rotating
machines can be thermally damaged at unsymmetrical faults due
to occurring negative sequence currents.

The protection of the primary equipment must involve not only the
faulty parts but also the other equipment in the network.

At electrical faults damages in the electrical environment can be


caused by heat radiation, induction, rise of the ground potential
etc. The protection of people and plants must satisfy the mini­
mum requirements decided by the authorities.

In a power plant a strong electrical coupling of the different parts


is often desired to minimize losses and voltage drops. A “strong”
coupling like this may lead to major effects on the whole, or at
least big parts, of the plant by a single failure. If not disconnected
the fault will adventure the whole plant directly or by a domino-ef­
fect. A number of electrical faults are inevitable in a power plant.
These faults can, only in exceptional cases, be allowed to adven­
ture the operation of the whole plant, eventually also with other
damages on apparatuses as a consequence. A satisfying fault
clearance is therefor a necessary condition for an operative pow­
er plant.

THE TASK OF THE PROTECTION SYSTEM

BA THS / BU Transmission Systems and Substations LEC Support Programme 83


2. OPERATING CONDITIONS OF POWER SYS-
TEM

From the protection relays point of view the most important oper­
ation conditions can be classified and connected according to
Figure 1.

Abnormal,
but secure,
condition

Fault
Normal
condition
service
condition

Abnormal
service
condition

not controlled sequence

initiated by protection

manual or automatic operation

Figure 1. The power system´s operation conditions.

Under normal operation condition the power plant fulfil its duties
and all consumers will receive both nominal voltage and frequen­
cy.

Under abnormal operation condition all consumers will be fed


with voltage and/or frequency which can be abnormal. Equip­
ment parts of the plant can also be stressed out of limit values.
These operation condition will after a short time lead to a fault
condition if not corrected.

OPERATING CONDITIONS OF POWER SYSTEM

84 BA THS / BU Transmission Systems and Substations LEC Support Programme


Protection General

The correcting measures can be initiation of regulation interfer­

ence, disconnection of some parts of the load, connection of

back-up capacity or, as a last possibility, disconnection of the crit­

ical apparatus. Mostly these precautions are initiated by protec­

tion relays which supervises the conditions in the electrical

equipment. All these measures are preventive in the sense that

they will be executed before a fault is created and before damag­

es in the apparatuses occurs. However the apparatus is not total­

ly uninfluenced. A cooling time may be required before the

reconnection but reparation or exchange is not necessary. Ef­

fects like increased aging can still occur.

Under fault conditions the power plant is usually not able to fulfil

it’s functions as supplier of energy of acceptable quality to the

consumers. At some faults the power plant can fulfil its functions

but due to abnormal values the equipment will be stressed in

such a way that sequential faults will occur and the power system

will collapse. Even at faults where the consumers are not con­

cerned the system will be stressed to a collapse if precaution not

will be taken.

Faults can be of varying types (see fig 2).

Shunt faults L1

L2

Series faults
L1

L2
I
L3
I
Figure 2. Different fault types in a power system.

OPERATING CONDITIONS OF POWER SYSTEM

BA THS / BU Transmission Systems and Substations LEC Support Programme 85


SHUNT FAULTS A fault current has developed due to insulation
breakdown in one or several phases. These faults are called
shunt faults and can be single phase to earth, two phase with or
without earth connection, or three phase.

SERIES FAULTS A primary current loop has been broken into one
or two phases. Such faults are called series faults.

The power system can not be allowed to be in service with a


shunt, or a series fault under an unlimited time. The only practical
operation is to disconnect the faulty part of the plant, so the sys­
tem is put back at a abnormal, but safe, condition.

Theoretically at a series fault, a parallel link can be connected.


This is not practically possible because such a link doesn’t exist.
A high impedance earthed cable network can be allowed to stay
in service, during a limited time and under certain conditions, at
a permanent earth fault. In these networks manual clearance of
permanent earth faults is allowed. This will be initiated at an ap­
propriate time for the operation.

In the “safe” condition, that will occur after faulty or abnormal ser­
vice conditions, the consumer can get voltage of poor quality, or
no voltage at all. In meshed networks the power system still can
carry out its primary tasks even if the preparedness for interfer­
ences will be reduced. In case of a second fault the system can
often no longer fulfil its duties.

The system must consequently as soon as possible return from


the “safe” condition, to a normal service condition. To be able to
reconnect the system parts, manually or automatically, knowl­
edge about the cause of the fault is required to not increase the
damages on the apparatuses or stress the system further. The
protection relays must consequently, not only disconnect the
faulty parts, but also diagnose the fault by indicating of which type
it is.

The power system can be stressed by abnormal service condi­


tions. Such abnormal conditions can be thermal overload, abnor-

OPERATING CONDITIONS OF POWER SYSTEM

86 BA THS / BU Transmission Systems and Substations LEC Support Programme


Protection General
mal frequency or abnormal voltage. The power transfer is, under
such conditions, maintained but the abnormal condition will, if
maintained, develop to a primary fault.

Protection against abnormal service is therefor required in order


to prevent unnecessary damage to the primary equipment.

3. REQUIREMENT ON PROTECTION SYSTEM

A basic requirement on the protection equipment is that it will


clear the fault with sufficient speed to limit the consequential
damages in the plant. Further the fault clearance must be quick
enough to avoid a total, or partial, power network collapse.

At a primary fault speed is not of main importance, as the fault po­


sition has already been damaged and will require repairing. How­
ever, the consequential damages of other parts must be avoided.
These damages are often of thermal nature as gas development,
heat radiation and heating of conductor material.

A type of stress which can’t be limited by the protection relays is


the mutual forces between conductors leading fault currents. This
stress will be fully developed at the first current peak. Since pro­
tection relays and the belonging breakers can’t give a fault clear­
ance time less than 2 cycles, the first current peak always will
develop. These dynamic mechanical stresses can only be limited
by fuses or special short circuit limiters which limits the progress
of the current.

One requirement is insurance of a sufficient sensitivity to detect


all possible shunt- and series faults. This also includes possible
high resistive faults occurring at earth faults. An other require­
ment is that the high resistive faults should be detected after a
limited time from when the fault is developed.

The protection relays today have a basically satisfying detection


capability with the exception of overhead lines, where the detec­
tion of highly resistive earth faults isn’t always considered com-

REQUIREMENT ON PROTECTION SYSTEM

BA THS / BU Transmission Systems and Substations LEC Support Programme 87


pletely satisfying without special measures.

The function of the protection relays to initiate the disconnection,


is of outmost importance for the function of the whole power sys­
tem. Therefore the protection relays must have a very high reli­
ability.

A incorrect initiated trip of the circuit breaker will affect the power
system negatively. Therefor a very high security against unnec­
essary clearances from the protection relays is required. The un­
necessary clearances can be spontaneous or unselectable. The
latter are functions due to a wrongly initiated operation for a fault
outside the detection zone of the protection relay, executed by the
protection relay. Consequently there are high requirements on
the selectivity and reliability of the protection relays.

The operation capability of the protection system is summarized


in “reliability”, which includes both the security in fault clearance
and the security against undesired clearances. The security in
fault clearance is called dependability and the security against
undesired clearances is called security.

The reliability of the system depends on a lot of factors and gen­


erally the reliability of the total system is not better than the weak­
est component.

Example of factors which influences the reliability:

THE PROTECTION SYSTEM The engineer responsible must do a


multitude of choices when a plant is projected. The protection
system is chosen after voltage level, the weight of the plant, the
possibility to have back-up functions, distribution of current faults
and system earthing etc. The choices are also affected by the
customs, the authorities and the economical situation. The sys­
tem is chosen to fulfil the requirements on the plant and to give
the lowest possible “Life Cycle Cost”.

THE PRINCIPLES OF MEASURING Different principles of measuring


are used to protect the electrical plants. Every principle has its
advantages and disadvantages and a choice of principle must be
done based on access to measuring transformers, communica-

REQUIREMENT ON PROTECTION SYSTEM

88 BA THS / BU Transmission Systems and Substations LEC Support Programme


Protection General
tion channels and demands on fault coverage at high resistive
earth faults etc.

ENVIRONMENT Of course, the environment has affect on the reli­


ability location in switchgear rooms, tropical and cold climate,
heavy polluted environment etc., gives a lower reliability).

THE SETTING OF THE PROTECTION RELAYSA properly chosen


measuring principle can evidently be totally ruined by an incor­
rect setting. A protection relay which, under back-up load condi­
tions, operates unnecessary due to a too low setting can
disconnect parts of the net

THE MAINTENANCE Independently of the quality of the protection


system, a periodic maintenance must be executed. This includes
test of relays and trip schemes. Bad design or construction solu­
tions gives a difficult maintenance and thus a lower reliability.

FLEXIBILITY UNDER DIFFERENT SERVICE CONDITIONS AND EXTEN-


SION OF THE NETWORK Since all network changes during its life
time it’s important that the protection equipment is chosen after a
measuring principle, and has settings, to allow development of
network and the varying service conditions.

4. CHOICE OF PROTECTION EQUIPMENT

The protection equipment is chosen to secure fault clearance in


the power network. The base upon which the choices are made
is the generally accepted “Single Failure Criteria” that says that
a clearance must be executed even in case of a single fault in the
clearance chain.

The fault clearance chain contains several components accord­


ing to Figure 3 and failure of each component can prevent a trip
function. It is therefore important that no part of the clearance
chain will be executed with a lower reliability. A failure can never
be totally excluded.

CHOICE OF PROTECTION EQUIPMENT

BA THS / BU Transmission Systems and Substations LEC Support Programme 89


Requirement in safe clearance imply, that there must be a
back-up clearance function.

Figure 3. The different parts of the fault clearance chain.

This function can be executed either as a remote back-up or as a


local back-up. The intention is that, even at a back-up tripping, an
as small part of the plant as possible will be disconnected.

The single failure criteria can be fulfilled with a protection system


including back-up protection. The back-up protection must be
able to detect all primary faults, detected by the primary protec­
tion primarily intended to clear the fault. There are two different
ways of arranging back-up protection:

Remote back-up is the most common way of arranging back-up


in a distribution network. This means that the back-up protection
is available at a separate breaker. Remote back-up is normally
achieved through a time grading where the back-up protection is
given a longer operation time than the primary protection.

Local back-up is used when remote back-up is difficult to


achieve or when time grading for selectivity is not acceptable due
to thermal limits or network stability reasons. Local back-up
means that at the breaker location a second protection relay that

CHOICE OF PROTECTION EQUIPMENT

90 BA THS / BU Transmission Systems and Substations LEC Support Programme


Protection General
detects the same faults as the primary relay shall be provided.
The two systems are operating in parallel on the same breaker.

Selectivity is necessary for the back-up functions. There are two


types of selectivity.
- Time selectivity, means that the protection relays, at the circuit breakers,
have a graded time scale proportioned to each other.
- Absolute selectivity, which means that the relay can determine in what
part, of the plant, the fault is located.

Remote back-up with time selectivity is most common at medi­


um, and low voltage networks, where there is pure distribution
and where two different relays, which opens two different break­
ers, relatively easy can detect all types of fault.

Figure 4 shows the primary and secondary zones in a distribution


network. The protection zones are decided by the location of the
current transformers.

Primary protection measuring zone


Back-up protection measuring zone

Figure 4. Primary and back-up protection zones

The back-up protection function, is arranged by time grading


where the back-up protection relay has a longer fault clearance
time than the primary protection relay (see fig 5).

In these cases it is necessary to consider even the battery sys­


tem design, so that the protection equipment which gives a
back-up for other protection equipment is not fed from the same

CHOICE OF PROTECTION EQUIPMENT

BA THS / BU Transmission Systems and Substations LEC Support Programme 91


DC supply. This is sometimes forgotten and can increase the
consequences of a fault drastically.

t1 t1 t1
G

t1

Figure 5. Back-up protection with time grading.

Take for example a fault at a distribution line. If this fault is cleared


by the primary protection the damages will be limited. If the
back-up function at the transformer clears the fault the damages
has increased due to the increased clearance time. The increase
will not be dramatically because the clearance time is within the
thermal capacity of the transformer and the switchgear.

The next big step in the consequence stage occurs if the protec­
tion of the transformer fails. This can for example happen if both
the line protection and the transformer protection are fed from the
same DC supply which, for example, has disappeared due to a
broken fuse

The relays further up in the system are not expected to recognize


the fault (and normally they don’t) so the fault will remain and
thermally overload both the transformer and the switchgear. The
clearance is obtained only when the transformer collapses and
the fault is cleared by the relays further up in the system. The con­
sequences have then increased drastically.

In cases where a remote back-up can’t be arranged for example


when there are difficulties in detecting the fault at an object from

CHOICE OF PROTECTION EQUIPMENT

92 BA THS / BU Transmission Systems and Substations LEC Support Programme


Protection General
an adjoining object, a local back-up must be arranged. This can
be the case at long distribution lines where a fault in the remote
part never can be detected by the relay at the feeding transform­
er, due to the small increase of current which appear at the trans­
former. A parallel overcurrent relay can be inserted and trip on
another trip coil.

In the meshed transmission network where fault currents are fed


from all directions normally a local back-up must be used. The lo­
cal back-up can be delayed, with a local relay at the object which
detects fault within the same, or a wider zone than the primary re­
lay but takes a longer time to trip.

The most common at high voltages, is to use double identical re­

lays called redundant relays. The redundant protection system

gives an improved reliability.

A normal practice at using redundant protection systems is to:

- Separate measuring cores used in measuring transformers (of econom­


ical reasons it is very rare to use double measuring transformers).
- The circuit breaker is not doubled, due to economical reasons, but pro­
vided with double independent trip coils.
- The DC distribution will be separated as far as possible. At higher volt­
age levels, double battery systems will normally be provided.
- The protection systems are placed physically separated and often also
separate cable ways are used.

CHOICE OF PROTECTION EQUIPMENT

BA THS / BU Transmission Systems and Substations LEC Support Programme 93


In Figure 6 the fault clearance chain with redundant protection
system is shown.

Figure 6. The fault clearance chain at redundant protection systems.

Due to the cost of the breaker this will not be doubled but it will
be provided with double trip coils. However, a small risk for break­
er failure still exist according to statistics. To ensure fault clear­
ance in case of breaker failure, and secure a short fault clearance
time, a breaker failure function is included (see fig 7).
The breaker failure function will trip surrounding breakers if one
breaker would fail.

Figure 7. The principle of a breaker failure protection.

CHOICE OF PROTECTION EQUIPMENT

94 BA THS / BU Transmission Systems and Substations LEC Support Programme


Protection General

Due to the big impact for the operation of the network that a
breaker failure trip causes, very high requirements are set on a
breaker failure relay security against unwanted functions.

A breaker failure is designed with high internal security. The cur­


rent through the breaker will be controlled after a trip attempt and
if it don’t disappear in a reasonable time (less than 60 ms), a
breaker failure exists and the surrounding breakers will be
tripped. Often a “2 out of 2" connection of the current and time is
sometimes used to obtain highest possible security against un­
necessary operations. For new numerical products the same risk
of failures of a current detection relay or a time-lag relay do not
exist and the “2 out of 2” is not any more required.

A duplication of the breaker fault function gives a higher reliability


but at the same time a lower security which is a disadvantage.
Due to the minimal risk of a breaker failure, and the negligible risk
that the breaker failure relay fails at the same time, only one
breaker failure relay is used.

The most important in the choice of protection equipment is that


desired trip security is obtained. After that the cost for the differ­
ent alternatives must be considered where the guiding principle
is the Life Cycle Cost.

The cost for operation and maintenance must be considered. Re­


dundant protection systems cost more to install as well as under
its life time. However big savings can be made in the primary sys­
tem by securing the short fault clearance time. The primary ap­
paratuses can then, for example, be dimensioned for 0.5 seconds
thermal capability instead of 1.0 second. Furthermore a later re­
building can be avoided when the network is to be extended to a
more meshed configuration with higher fault levels.

CHOICE OF PROTECTION EQUIPMENT

BA THS / BU Transmission Systems and Substations LEC Support Programme 95


5. DISTURBANCE REGISTRATION AND FAULT
SIGNALLING

The fact that the operation personnel will be informed of all fault
signals is as important as all other parts in the fault clearance
chain. If the design is well designed with alarms for problems in
the DC system, but that alarm wont reach the responsible per­
sonnel, the alarm is of no use. This means that the design of the
DC supply distribution for the alarm system is very important.
Alarms must not be attached to the same group as the distribu­
tion and the alarm voltage must always be supervised.

To be able to follow a protection systems behavior when the net­


work changes and to make sure that a fault really will be cleared,
a disturbance recorder and an event recorder can be used.
These two devices registers all important signals in case of a dis­
turbance. The analysis of the print-out is an excellent comple­
ment to the maintenance. These analysis is made from print-outs
from both the line in question and the surrounding lines, which
gives a possibility to discover inoperative relays as well as incor­
rect settings and badly chosen measuring principle.

These global analysis has a great value in changing the network


world.

DISTURBANCE REGISTRATION AND FAULT SIGNALLING

96 BA THS / BU Transmission Systems and Substations LEC Support Programme


Line protection
1. INTRODUCTION

The transmission lines are the most widely spread part of the

power system and the overhead lines are the, from environmen­

tal influences, least protected part of the system. The number of

line faults will thus be very high compared with the total number

of faults in the whole power system. Therefore the line protection

are one of the most important protection systems in the whole

power system.

Another aspect is that the power lines are the part of the system

that is most likely to cause injuries to people and also to cause

damages to equipment and structures not part of the power sys­

tem. Therefor the line fault clearing is subject to authority regula­

tions.

In the voltage range above 170 kV, practically all systems are sol­

idly earthed. In the range 50-170 kV some systems are earthed

over Petersén reactors. These systems are seldom equipped

with earth fault protection relays. Earth faults are then cleared

manually or with special transient measuring protection relays.

The clearing of multi-phase faults will basically not be different in

these systems than in solidly earthed systems. Systems with Pe­

tersén reactors will therefor not be discussed separately.

Overhead lines in the voltage range of 170 kV will have a length

from a few up to approximately 400 km. Cable lines are limited to

a maximum length of about 20 km.

Some lines are mixed and consist of both cable and overhead

lines. Cable and overhead lines have different phase angles and

“Z0/Z1” ratio. These differences complicates the impedance dia­

gram for the mixed lines where the cable impedance can’t be ig­

nored in relation to the overhead line impedance. Mostly the

cable is short and the mixed line can be handled, from protection

point of view, as an overhead line.

INTRODUCTION

BA THS / BU Transmission Systems and Substations LEC Support Programme 97


1.1 FAULT STATISTICS

The probability of line faults, caused by lightnings, are 0,2-3 faults


per 100 km and year. To this have to be added faults caused by
pollution, salt spray, swinging conductors, lifting devices touching
the conductors. In most cases lightning faults are much dominat­
ing.

About 80% of the line faults are single phase to earth, 10% are
two phase to earth faults, 5% are isolated two phase faults and
5% are three phase faults. At lower voltages the multi phase fault
will be more common due to the lower basic insulation level. The
number of faults also increases due to the lower distances.

Simultaneous
faults Earth
Arc RN faults
R S

Two phase
faults
S T
Three phase
Interline faults
faults T R

Figure 1. Faults occurring on a transmission line tower are of different types.

1.2 FAULT TYPES

Transient faults are common on transmission lines. They will


disappear after a short “dead interval” and self distinguish. Light­
ning is the most common reason for transient faults. The by light­
ning induced overvoltages will cause flash-over in an insulator
chain.

INTRODUCTION

98 BA THS / BU Transmission Systems and Substations LEC Support Programme


Line protection
The fault must be cleared to clear the arc. After a short interval,
to allow deionisation, the voltage can be restored without causing
a new fault.

Transient faults can also, further to lightnings, be caused by fac­


tors such as swinging lines, falling trees and birds.

Approximately 80-85% of faults at HV lines are transient. The fig­


ures appearing at lower voltages are less.

Persistent faults can be caused by a broken conductor, a falling


tree, a mechanically damaged insulator etc. These faults must be
localized and the damage repaired before the normal service can
be reestablished. The system is during the reparation in an ab­
normal but safe condition.

1.3 SPECIAL FAULT TYPES

In double circuit lines (two lines at the same tower) simultaneous­


and inter-line faults can occur.

Simultaneous fault are most likely to be two single phase to


earth faults that will occur on different phases on the two lines on
the same transmission line tower. Both faults will though then be
in the same tower. The common footing resistance will compli­
cate the detection of this type of fault.

The Inter-line fault is a connection between two phases of the


parallel lines on the same transmission line tower with the arc.
The probability for simultaneous fault and interline fault is low.

The fault resistance at a multi-phase fault consists only of arc re­


sistance and can practically be ignored. At cross country faults,
an earth resistance is added to the arc resistance and the fault
resistance will then be significant. The probability for this type of
fault is very small in a solidly earthed system and is mostly ig­
nored. In systems earthed over Petersén reactors where fault is
not immediately disconnected this type of fault can’t be ignored.

INTRODUCTION

BA THS / BU Transmission Systems and Substations LEC Support Programme 99


The fault resistance can’t be ignored in case of an earth fault.
When the fault occurs at a tower the footing resistance is added
to the arc resistance. The footing resistance depends on the line
design and is almost always less than ten ohms but the resis­
tance can be tens of ohms in extreme cases. When earth faults
between the towers, called mid-span faults, occurs the footing re­
sistance is beyond control and can in extreme cases be up to
tens of kiloohms. Mid-span faults can be caused by growing
trees, bush fire or objects touching the phase conductors.

One very serious type of mid-span faults are caused by mobile


cranes. The mid-span faults have to be payed special attention
due to the risk of injuries to people if they not are cleared proper­
ly.

2. REQUIREMENTS ON LINE PROTECTION

The choice of protection relays for a specific application, depends


on the network configuration, type of line (single or parallel, long
or short, series compensated or not), load current level, and ex­
pected tower foot resistances etc. A choice must be done individ­
ually for each application and the future expansion of the network
must be kept in mind.

The most important features of the line protection relays are:

Speed
Speed i. e. short operating time for severe faults.

As mentioned above a very short clearance time is required for

severe faults, sometimes down to a few milliseconds. One exam­

ple is a three-phase fault in a 400 kV system having 20 kA in

short-circuit current and 13000 MVA in short circuit power. The

thermal and mechanical stresses at such a fault are very high.

Speed is thus important to:

- limit the damages on the high voltage apparatus as well as limit the ther­
mal and mechanical stresses.

REQUIREMENTS ON LINE PROTECTION

100 BA THS / BU Transmission Systems and Substations LEC Support Programme


Line protection
- limit the ionization at the fault which will increase the chances of a suc­
cessful Auto reclosing and thus shorten the dead interval.
- increase the power transmission capability of the network without de­
creasing the safety margin for the network stability.

REQUIREMENT ON SPEED The maximum fault clearance time is


important i. e. including the back-up protection function and the
possibility of a breaker failure. The network must be stable under
maximal conditions. Times from 250 ms up to several seconds
can occur depending on line type, location in the network, sourc­
es etc.

Sensitivity
Sensitivity means the capability to detect all types of fault.

It is important to detect all faults even if the fault current is smaller


than the load current. Equipment damages due to induction in
low voltage equipment, or person injuries due to rise in earth po­
tential, can occur also for low magnitude faults. High resistive
earth faults are quite likely to occur at long transmission lines and
the relay system must be able to detect such faults before the
faults developes further or people will get seriously injured. Sen­
sitivity is therefore the second important aspect in the perfor­
mance of line protection relays.

REQUIREMENT ON SENSITIVITY The requirement on the line pro­


tection systems sensitivity at earth faults is often discussed and
varies between utilities. The mid-span fault often requires higher
sensitivity than what can be achieved by the primary protection
relay used. A maximum sensitivity of approximately “RF<50 Ω”
can be achieved by the primary protection.

An acceptable sensitivity can only be achieved utilizing zero se­


quence components in overcurrent, directional overcurrent or di­
rectional comparison schemes. These relays can only detect
earth faults.

Selectivity
Selectivity i. e. the capability to determine the fault location and
only disconnect the faulty object.
REQUIREMENTS ON LINE PROTECTION

BA THS / BU Transmission Systems and Substations LEC Support Programme 101


The consequences of a fault must be limited and the power sup­
ply to the consumers secured. The protection system must there­
for be capable of distinguish between an external and an internal
faults also for low magnitude faults on a heavy loaded object, or
for parallel objects where close to similar parameters exist for
both healthy and faulty object.

Requirement on selectivity
In order to fulfil these requirements the protection relays has to
be able to distinguish between the normal operating condition of
the protected object and an electrical fault i.e. give a reliable fault
detection unaffected by normal operating conditions such as
load, inrush currents etc. In some cases it is also required that
the protection relay must be able to detect also other abnormal
operating conditions such as overexcitation, overload, broken
conductor etc. These aren’t electrical faults but may still damage
the protected object or other apparatus in the network. Since
power apparatus in many applications have to operate near their
rated limits it is important that this part of the protection system
exactly can distinguish between permissible and none permissi­
ble operating conditions.

Electrical faults are normally required to be cleared instanta­


neously. Other abnormal operating conditions, can be accepted
to result in time delayed action.

Dependability and security are contradictory to each other but


have to be evaluated together due to the linking of the two quali­
ties. In redundant protection schemes the whole scheme has to
be evaluated not only the individual relays.

To achieve maximum dependability combined with maximum se­


curity the communication demands shall be at minimum. Wide
band transmission is not only expensive it will also be more ex­
posed to interference. The latter is apparent when power line car­
rier is used. The communication demand is therefore linked with
dependability and security.

REQUIREMENTS ON LINE PROTECTION

102 BA THS / BU Transmission Systems and Substations LEC Support Programme


Line protection
Operate time, sensitivity and dependability are contradictory to
security, therefore none of the first qualities have to be exagger­
ated.

3. MEASURING PRINCIPLES

The basic type of measuring principles can be used for line pro­
tection relays. One, or combinations, of the measuring principles
below can be used to create the total line protection scheme.

Overcurrent protection relays are undirectional, or directional,


current measuring relays with a back-up feature due to the cur­
rent measuring principle.

Pilot wire, optical line differential and phase comparison


measuring principles gives exclusive unit protection without
any back-up feature. New types of Optical line differential relays
with Distance back-up functions do now exist on the market
which solves the back-up function problem.

Distance and directional impedance measuring principles


basically gives time/distance selective protection with a back-up
function. By using communication an unit protection function can
be achieved together with the time/distance function with
back-up.

Travelling vawe protection is a unit protection where the two


line ends are communicating through a fast channel in a permis­
sive or blocking scheme.

3.1 OVERCURRENT RELAYS

Overcurrent relays are normally used in networks with system


voltage below 70 kV where fault infeed is from one direction only
and where relatively long operating time is acceptable. At higher
voltage levels in the transmission lines the directional, or undirec­
tional, overcurrent relays are used as back-up protection to the
instantaneous primary protection relays. The overcurrent protec-

MEASURING PRINCIPLES

BA THS / BU Transmission Systems and Substations LEC Support Programme 103


tion will then operate as a back-up to the primary protection and
for special types of faults e. g. high resistance earth faults which
cannot be detected by the primary protection.

3.2 PILOT WIRE, OPTICAL LINE DIFFERENTIAL AND


PHASE COMPARISON RELAYS

Introduction
Pilot wire and phase comparison relays are unit protection relays,

which only detects faults in the zone between the relays. No

back-up function is included, so a separate back-up relay is nor­

mally required.

Optical line differential relays are also unit protection normally

without back-up function. However there exists now such relays

with a built-in back-up Distance protection function.

Communication between line ends is required and can be ac­

complished with any of the following:

- Pilot wires

- Power line carrier


- Radio link
- Optical fibre

Pilot wires can be placed in soil or at towers. The resistance will


limit the possibility to use pilot wires. The use is mostly restricted
to distances less than 10km.

Power line carrier (PLC) equipment is based on a capacitive


connection of signals, with a frequency of 50-500 kHz, in the
power line. A frequency keying is normally used to transmit a trip,
block or phase angle signals to the remote end.
PLC equipment can also be used in very long lines and for re­
mote control.

MEASURING PRINCIPLES

104 BA THS / BU Transmission Systems and Substations LEC Support Programme


Line protection

Figure 2. Communication through a high frequency signal, interposed at the


high voltage line (PLC).

Radio links are reliable, but expensive, communication links and


are therefor rarely used.

Optical fibres have two big advantages, the insensitivity to noise


and its possibility to transmit huge amount of information. An in­
crease in the use of optical links have been noticed during the
last number of years. Cost has decreased and new Optical line
differential relays utilizing the transmitting capability has been de­
veloped giving improved protection capability. See separate sec­
tion below.

Principle design of pilot wire differential relay


Pilot wire differential schemes gives an absolute selectivity and a
short operating time. It can use wires of metal or, with recent de­
veloped relays, optical fibres. The use of optical fibres in trans­
mission tower top lines will increase during the forthcoming
years, and several new products using optical fibres will be avail­
able. Probably also combined products where a single phase dif­
ferential relay is combined with back-up functions, the lack of
which up to now have been a draw-back for the pilot wire differ­
ential relays.

A short description of the pilot wire differential relay princi­


ple:

The measuring principle is based on a comparison of amplitude


and phase angle at the two line ends according to the differential

MEASURING PRINCIPLES

BA THS / BU Transmission Systems and Substations LEC Support Programme 105


current principle (Kirchhoffs first law). A relay is of practical rea­
sons, provided at each line end to detect the faults and to trip the
circuit breakers.

A summation transformer is often used to transform three phase


systems into single phase form enabling the use of one pair of pi­
lot wires only. With the voltage balance principle, the current un­
balance is changed into a voltage balance. The principle of a
voltage balance differential relay is shown in fig 3.

A relay with a matching current ratio is connected to the current


transformer at the line ends (1 A can be used at one end and 5 A
at the other but the same primary current is required). The pilot
wires resistance “Rp” and the settable resistor “Rp/2” are con­
nected to the secondary of the summation transformer. A relay is
connected between the pilot wire terminal and the mid-point of
the summation transformers secondary winding. These points
will with the used dimensioning of the pilot resistance and the
built in resistor have the same potential at normal service condi­
tions (see fig 3a).

MEASURING PRINCIPLES

106 BA THS / BU Transmission Systems and Substations LEC Support Programme


Line protection

A B

E E
Rp/2 Rp Rp/2
EA EB
EA EB

E 2EA

2EB
E

a) Normal operating conditions

2EAmax
E

2EBmax
E

b) External fault ideal transformers

E E

2EAmax 2EBmax

c) Internal fault, double end infeed

Figure 3. A voltage balance current differential relay

At high through fault currents the voltage across the relay will be
zero although the voltages “2EA” respectively “2EB” will increase
to the maximum value “EAmax” respectively “2EBmax”, dependent
of the two regulating diodes. The relay operating voltage is select­
ed to prevent maloperation due to small differences e. g. caused
by saturation of current transformers cores (see fig 3b).

If a fault, fed from both directions, occurs within the protected


area the summation transformers outputs will be in phase oppo­
sition. No currents can therefor circulate in the pilot wires. The
secondary voltages will be limited by the regulating diodes to
“2EAmax” resp. “2EBmax”. Operating voltages will occur across

MEASURING PRINCIPLES

BA THS / BU Transmission Systems and Substations LEC Support Programme 107


the relays and the differential relays at both end will trip (see fig
3c).

Also at an internal fault fed from only one line end, voltages will
occur across the relays and both relays will operate (see fig 3d).

Principle design of Optical line differential functions


The optical line differential functions have been introduced on the

market during the last number of years together with the start of

provision of optical fibres between the two stations, giving a

broad band connection enable direct differential measurement

on a phase per phase basis.

The differential current principle is shown in figure 4. One relay is

provided at each line end. The communication can be through

separate dedicated fibre, through a MUX’ed 54/64 kbit/s channel

complying to CCIT and EIA standards or even through separate

pilot wires in special cases.

3Id 3Id
Communication
channel
Interface to MUX
dedicated fibre etc.

Figure 4. The principle for an optical line differential relay with one protection
relay at each line end communicating through a communication channel.

The differential measurement is stabilized with the current scalar

form as per below figure 5. The degree of stabilization for through

faults and the minimum operating current is settable. Modern re­

lays also normally have a CT supervision detector to lower the re­

quirement on current transformer cores.

An advantage with these modern optical relays based on numer­

ical principles is the possibility to set the CT ratio adaption. Dif­

ferent CT ratios can then be used at the two line ends.

MEASURING PRINCIPLES

108 BA THS / BU Transmission Systems and Substations LEC Support Programme


Line protection
An intertrip channel for direct intertrip from e. g. Breaker failure

protection is normally also available in the relays.

In some types of relays the differential functions can be comple­

mented with an back-up protection in form of a Distance protec­

tion or a simple short circuit and earth fault protection. This

function can then operate in parallel with the differential function

or only as a back up when the communication channel is missing.

Idiff
Stabilization at
CT saturation

IDiffLVL2

Stabilization at
normal faults

IMinOp
Ibias
IMinSat ILVL1/2Cross

Figure 5. The stabilization characteristic.

Principle design of phase comparison relay


Phase comparison relays is used in some countries. However the
relays haven’t been able to take big market shares mostly be­
cause of the fact that they provide only unit protection not includ­
ing any back-up functions, but also due to the high requirement
on a fast communication between ends which mostly means a
separate PLC equipment for this protection relay only.
The “phase comparison principle” indicates that the phase angle
of the current at the two line ends are compared each cycle as
shown in figure 6.

MEASURING PRINCIPLES

BA THS / BU Transmission Systems and Substations LEC Support Programme 109


ILoad
I1 I2
Ø> Ø>

e2

e1-e2

α
e1

I2

Operating Ø
I1

area Ø

I2

Figure 6. Measuring principle of a phase comparison relay. The angle differ­


ence, between the currents at the two line ends, is compared.

The measured time for the zero crossing is transmitted to the oth­

er end with a short, and well defined, channel time.

At normal load, or through faults, the phase angle at the two ends

is rather alike. A small difference will though occur due to the ca­

pacitive generation of the line. An amplitude requirement is often

added to the phase angle requirement.

To limit the transmission of signals to fault conditions a start cri­

teria is normally added. Overcurrent, Overcurrent/Undervoltage,

MEASURING PRINCIPLES

110 BA THS / BU Transmission Systems and Substations LEC Support Programme


Line protection
Impedance or combinations of all above can be used as start el­
ements.

3.3 DISTANCE AND DIRECTIONAL IMPEDANCE


PROTECTION

Principle design
Distance protection relays are the most common relays on trans­
mission lines. The reason for this is the simple measuring princi­
ple, the built-in back-up and the low requirement on
communication with remote end.

The Distance protection relay is a directional underimpedance


relay. Normally two to four measuring zones are available.

Basically the Distance protection relays measures the quotient


“U/I”, considering also the phase angle between the voltage “U”
and the current “I”. The measured “U/I” is then compared with the
set value. The relay will trip when the measured value is less than
the value set. The vector “ZL” in figure 7 shows the location of a
metallic fault on a power line in the impedance plane. Power lines
normally have impedances of 0,3-0,4 Ω/km at 50 Hz and the an­
gle normally is 80-85°.

X [Ω]

ZL

Rf
ZL=R+jX
Rf

Rf
Z< Z<
Load

R [R [Ω]

Figure 7. The principle of a Distance protection relay.

However, metallic faults are relatively rare. Most faults are


caused by a flashover between phase and earth or between
phases.

MEASURING PRINCIPLES

BA THS / BU Transmission Systems and Substations LEC Support Programme 111


A small arc resistance “Rf ” exists in the fault. The arc resistance
Rarc can according to Warrington be calculated as:
Rarc = 28700 * a / I1.4
where:

a is the length of the arc in m i. e. the length of the insulator for

earth fault and the phase distance at phase faults.

I is the fault current through the fault resistance in A.

During earth faults, the tower foot resistance also will occur in the

fault loop. The Distance protection relays must therefor cover an

area of the line impedance, plus the fault resistance as indicated

in the figure. Tower foot resistances should normally be kept be­

low 10 Ω. Top lines connecting towers together will give parallel

path and lower the tower foot resistance.

In some areas as high values as 50 Ω can exist and special pre­

cautions to protect against earth faults can then be necessary.

The vector “Zb” shows the location of the load impedance. Nor­
mally the load impedance is close to “cos Ø=1”. The Distance
protection relays must be able to distinguish between fault and
load conditions even if the impedances are of the same size.

The detection of the forward direction is an important function for


a Distance protection. The directional sensitivity must be abso­
lute and serve down to zero voltage.

The back-up function is simply achieved, by an extension of the


impedance reach with time steps (see figure 8).

For normal lines with a distance longer than approximately 15 km


the first step of impedance, is underreaching the line end with ab­
solute selectivity covering about 80% of the line. The 80% reach
is selected due to errors in distance measurement due to Current
and Voltage transformer errors, relay accuracy and influence
from the system as described further below.
A fault at “F1” will be tripped instantaneously from both protection
“A” and “B”. Normal operating time in modern Distance protec­
tion relays is 15-30ms. Operating time will be dependent on
source to impedance ratio, setting, fault resistance, fault position,
CVT filter and the point of wave at which the fault occurs.

MEASURING PRINCIPLES

112 BA THS / BU Transmission Systems and Substations LEC Support Programme


Line protection

A fault at “F2” is tripped instantaneously by relay “B” and by relay


“A”, after the time “t2”.

A fault at “F3” is normally tripped instantaneously by relay “C” and


“D”. If the relay at “C” or the breaker fails, relay “A” will trip.

t3
t2
t1
l
A C

ZA F1 F2 ZB ZC F3 ZD

t3
t2
t1
l
B A

Figure 8. The principle of line protection, with Distance protection relays at


both line ends.

Distance protection relay -Design


The design of a Distance protection is much dependent of the
technic used. Today there are products of electromechanical and
static, as well as numerical, design. However the numerical
schemes have clearly started to take over.

The two main types of Distance protection relays are “switched


scheme” and “full scheme”. The switched scheme relays consists
of a start relay selecting the correct measuring loop to the single
measuring relay. The start relays are in their simplest form cur-

MEASURING PRINCIPLES

BA THS / BU Transmission Systems and Substations LEC Support Programme 113


rent relays at all three phases and in the neutral. In more expen­
sive solutions, the start relays are underimpedance relays.

A full scheme relay has a measuring element for each measuring


loop and for each zone. All measuring elements then does the
measuring in parallel which this leads to shorter operating times.

The cost advantages with a switched scheme compared to a full


scheme have been minimized with the introduction of numerical
relays where all calculations are made by a processor.
The design of a numerical distance protection is shown in Figure
9. Input transformers provides the disturbance barrier and trans­
forms the analogue signals into a suitable voltage, for the elec­
tronic circuits. Passive analogue filters prevents anti-aliazing. The
analogue values for all voltages and currents are in an A/D con­
verter transformed into digital values and are after a digital filter­
ing sent in series to the measuring unit.

Figure 9. The design of a Numerical distance protection relay.

In the measuring unit a Fourier analyze and an impedance calcu­


lation are performed. A Directional check also is made. The direc­
tional check includes a positive sequence memory polarizing to
secure correct function even with a completely collapsed voltage
at a close-up fault.

MEASURING PRINCIPLES

114 BA THS / BU Transmission Systems and Substations LEC Support Programme


Line protection
Impedance and direction criteria are checked in a logic and to­
gether with the time elements the full scheme protection relay is
built up.

Impedance measurement
The measure impedance at a certain fault position must not be
dependent of the fault type. The correct voltages and currents
must therefor be measured for each fault loop and the evaluation
of loop impedance and the phase impedance to the fault must be
done. The Distance protection relays settings are always based
on the phase impedance to the fault. The measuring loops for dif­
ferent fault types are shown in figure 10.

Earth faults
Zs IR RL XL
URN

RN XN

Two-phase faults

Zs RL XL
IR
URS
IS

Three-phase faults

Zs IR RL XL
URN
IS
USN
IT
UTN

Figure 10. The impedance measuring loops for different fault types.

MEASURING PRINCIPLES

BA THS / BU Transmission Systems and Substations LEC Support Programme 115


For two and three phase faults the phase voltage and the differ­
ence between line currents are used. With this principle the mea­
sured impedance is equal to the positive sequence impedance at
the fault location.

The earth fault measurement is more complicated. Using of


phase currents and phase voltages gives an impedance as a
function of the positive and the zero sequence impedance:

U = I1 Z1 + I0 Z0 + I2 Z2

Z1 = Z2

U = Z 1 (I 0 + I 1 + I 2 ) + I 0 Z 0 – I 0 Z 1

I = I0 + I1 + I2

 Z0 

U = IZ1 + I0Z1  -----


- – 1

 Z1 

IN  Z0 

U = IZ1 + ---- Z1  -----


- – 1

3  Z1 

The current used is the phase current plus the neutral current
times a factor KN.
The zero sequence compensation factor is “KN” = “(Z0-Z1)/3Z1”.

The factor “KN” is a transmission line constant and “Z0/Z1” is pre­


sumed to be identical throughout the whole line length.

The total loop impedance for the earth fault loop can be de­
scribed “(1+KN)Z1”.

Measuring principle
Modern static Distance protection relays can be made with Am­
plitude- or Phase angle comparators. Both principles gives iden­
tical result.

An Amplitude comparison “|IxZK|>|U|” gives in a R-X diagram a


circular characteristic which is the simplest principle for a Dis-

MEASURING PRINCIPLES

116 BA THS / BU Transmission Systems and Substations LEC Support Programme


Line protection
tance protection. “ZK” is the model impedance of the relay i.e. the
set impedance. “I” and “U” are the measured voltages and cur­

rents. The relay will give operation when the measured imped­

ance “|Z|<|ZK|”.

The same characteristic is achieved by comparing the signals

“IxZK-U”, and “IxZK+U”, with operation for “-π/2 <Ø <-π/2 ”.

The comparators can be instantaneous, integrating or a combi­

nation of both.

The selected principle is decided by factors like circuit costs,

speed requirements, immunity to disturbances etc.

Integration will make the relay slower but more resistant against

disturbances. However, in modern numerical and static relays the

immunity is achieved by an improved filtering technic. Instanta­

neous comparators can therefor be used with improved operating

times as a result.

In numerical Distance protection relays the impedance is calcu­

lated for each measuring loop and is then compared with the set

impedance.

Varying algorithms are used by different manufacturers depen­

dent of the relay. In some new numerical relay of type RELZ

100/REL 521 from ABB Network Partner, the impedance measure­

ment is based on:

The resistive component is calculated:

UV × DIH – UH × DIV
R = ---------------------------------------------------------
DIH × IV – DIV × IH -

The reactive component is calculated:

UH × IV – UV × IH
X = ω × dt × ----------------------------------------------------
DIX × IV – DIV × IH

MEASURING PRINCIPLES

BA THS / BU Transmission Systems and Substations LEC Support Programme 117


The values above are based on the voltage “U”, the current “I”,
and the current change between the samples “DI”, sent through
the Fourier filter. The Fourier filter creates two ortogonal values,
each related to the loop impedance of each measuring loop.

X
UH = R × IH + ------------------- × DIH
ω0 × dt

X
UV = R × IV + ------------------- × DIV
ω0 × dt

Where “H” is the horizontal (active part), and “V” is the vertical
(imaginary part).

DIRECTIONAL MEASUREMENT At fault close to the relay location


the voltage can drop to a value, where directional measurement
cannot be performed. Modern Distance protection relays will in­
stead use a cross-polarization where the healthy voltage e. g. for
a “R” fault the voltage “UST = US-UT” with a 90° phase shift com­
pared to “URN”. Different degrees of cross-polarization between
the healthy and faulty phases exists in different products.

For three-phase faults the cross polarization does not enable


measurement as all phases are low. A voltage memory circuit is
then used to secure correct directional discrimination even at
close-up faults with zero voltage in all three phases.

In new relays the memory is based on the positive sequence volt­


age. The memory is held for about 100 ms after the voltage drop.
After 100 ms the most common principle is to seal-in the direction
measured until the current disappears.

INSTRUMENT TRANSFORMERS The measurement of impedance


and direction is done by signals from the current- and voltage
transformers. Conventional current transformers may saturate
due to the DC component in the short-circuit current. The best so­
lution is to do the measurement before the CT-saturation. This re­
quires a high speed performance of the relay.

MEASURING PRINCIPLES

118 BA THS / BU Transmission Systems and Substations LEC Support Programme


Line protection
For distance measurement another solution is to measure the
zero crossings. Even during a transient saturation of a CT core
one zero crossing per cycle will be correctly reproduced.

CVT-transient is a big problem for the directional measurement in


relays of Distance relay type. For these relays the CVT- transient
has to be filtered out. The CVT transient is defined in IEC 186 and
the transient voltage shall at a solid fault with zero voltage be
<10% after one cycle. It is obvious that quick operating relays will
be much disturbed by a CVT transient.

If the change in voltage is used instead of the voltage itself, the


problem can be completely avoided.

True secondary current


Secondary current of TPX CT core

Fault inception
point

10% t

1 cycle

Figure 11. Output signals from a DC saturated current transformer and from
a CVT at a close-up fault.

Communication principle
In most Distance protection scheme applications, at least at volt­
ages ≥130kV, communication channels between the two ends
are utilized to improve the protection system behavior.

The most common communication links are PLC equipment.

MEASURING PRINCIPLES

BA THS / BU Transmission Systems and Substations LEC Support Programme 119


Communication schemes
The Distance protection relays can communicate in “Permissive”
or “Blocking” schemes.

In Permissive schemes an acceleration signal “CS” is sent to the


remote end, when the fault is detected “forward”. Tripping is
achieved when the acceleration signal “CS” is received if the local
relay has detected a forward fault as well.

Two main types of permissive schemes exist, see figure 12:


1) Underreaching schemes, where the acceleration signal is sent from
a zone underreaching the remote end, usually zone 1, “Z1”.
2) Overreaching schemes, where the acceleration signals are sent from
one overreaching zone, usually zone 1 “Z1” or zone 2 “Z2“overreaching
the remote end A directional start can also be used.

The overreaching schemes are normally used for short lines (<15
km) to improve the resistive coverage.

Receiving the carrier signal will, dependent of the selected


scheme mean a time acceleration of Zone 1 (at Z1 overreach), or
Zone 2 or Zone 3.

MEASURING PRINCIPLES

120 BA THS / BU Transmission Systems and Substations LEC Support Programme


Line protection

Permissive system
A B

Z< Z<

Carrier send CS = Z< Forward, under or overreach

Trip = Z< Forward Z1, Z2 or Z3 & Carrier received

Blocking system

Z< Z<

Carrier send CS = Z< Reverse zone


_____________
Trip = Z< Forward Z1, Z2 or Z3 & Carrier received &T0
Figure 12. Communication with remote end, in Permissive schemes or
Blocking schemes. CS from Underreaching zone or Overreaching zone.

In Blocking schemes a blocking signal “CS”, is sent to the remote


end when the fault is detected to be reverse. Tripping is achieved
when the acceleration signal “CS” is not received within a time of
T0 and if the local relay has detected a forward fault as well. A
time margin T0 of 20-40ms to check if the signal is received is al­
ways needed in a blocking scheme.

The accelerated tripping after “T0” are from “Z2” or “Z3”.

If different types, or manufacturer, of Distance protection relays


are used at the two line ends blocking schemes should be used
only after checking that the relays will operate together. A relay

MEASURING PRINCIPLES

BA THS / BU Transmission Systems and Substations LEC Support Programme 121


where a blocking signal is sent for “start” but not “forward” should,
as a general principle, never be used together with a relay with a
true reverse directional element sending the blocking signal.

The using of Permissive schemes or Blocking schemes in the


system depends on the preference for Security or Dependability.
A Blocking scheme will be Dependable, i. e. it will operate for an
internal fault also with a failing communication link, but it has a
lower security as it can maloperate for an external fault due to a
failing communication link. The Permissive scheme has the op­
posite behavior. The advantage with the blocking scheme is that
communication signals are sent on healthy lines whereas on per­
missive scheme the communication signals are sent over a faulty
line.

Reasons for incorrect impedance measurement


To enable a correct impedance measurement the measured volt­
age must be a function of only the locally measured current “IA”
and the impedance at the fault. This is naturally not always the
case in double-end infeed and meshed transmission networks.

REMOTE FAULTS If a fault occurs on an outgoing line in the re­


mote substation where the own line will feed fault current “If1”,
see fig 13, the other lines in the remote station will also contribute
with the fault currents “If2” and “If3”. The measured impedance at
the local station will then be as in the figure and the measured im­
pedance at the fault will seem much higher than the “true” imped­
ance to the fault. The relays will thus get an apparent underreach.
This means that, in practice the possibility to get a “remote
back-up” in a transmission network is limited. A local back-up
must therefor normally be provided.

MEASURING PRINCIPLES

122 BA THS / BU Transmission Systems and Substations LEC Support Programme


Line protection

If1 ZL

If1
Um
Z< If2

If3 If1+If2+If3
Measured voltage
Um=If1*ZL+(If1+If2+If3)*ZF ZF

Measured impedance If
Zm=Um/Im

X [Ω]
[ ]

ZL

Load

R [Ω]
[ ]
Figure 13. The Distance protection underreach at a remote fault.

At high resistive line faults on a


HIGH RESISTIVE LINE FAULTS

transmission line with double-end infeed a similar situation will


occur. In normal service a load current “Ib” flows through the line.

The current level is expressed:


E A – E B

I b = ----------------------
Z L
-

MEASURING PRINCIPLES

BA THS / BU Transmission Systems and Substations LEC Support Programme 123


“UA” and “UB” must have a phase difference to allow the current
to flow. This, if the voltage amplitude is the same, which is a “nor­
mal case” in the transmission network. When a fault occurs, the
currents “IA” and “IB”, are lagging “EA” respectively “EB”, and
have therefor also a phase difference compared to each other.
The resistance “R” at the fault will be seen as a resistance plus a
reactance reduction (at export) and a reactance addition (at im­
port).

UB

Figure 14. Measuring error at a high resistive earth fault in a line with
double side infeed.

The measuring error will be:

IA
------- R sin Θ
–I B f

–IB
------- R sin Θ
IA f

At the two line ends (see fig), “Θ” is the phase angle difference
between “A” and “B” stations. The exporting end will thus over­
reach i. e. a fault at the line end can be seen as an internal fault,

MEASURING PRINCIPLES

124 BA THS / BU Transmission Systems and Substations LEC Support Programme


Line protection
and the import end will underreach i. e. a fault will seem further
off than it is in reality.

If the power direction always is the same a compensation can be


made when setting the relays. The earth fault loop setting must
especially be considered as the high resistive faults normally only
occur at earth faults only.

PARALLEL POWER LINES When parallel lines at the same tower


are used there will be a mutual impedance, normally only of in­
terest when an earth fault occurs. Normal values of the mutual
impedance at earth faults for transmission line towers are “Zm” =
“0,5-0,6xZ0”.

The mutual impedance will for earth faults mean over- respective­
ly underreach for the two line ends. The over- or underreach is
dependent on the fault position and the zero sequence sources
at the two line ends. The level of overreach resp underreach in
the measurement is in the range up to 16%.

Different situations will occur when:


- Parallel lines are in service.
- Parallel lines are out of service and earthed.
- Parallel lines are out of service (floating).

Compensation have to be done for the different cases when set­


ting the relay earth fault reach. The “KN” factor is adjusted to
achieve a suitable setting. Normally the worst case is selected
and the “KN” is set to prevent overreaching, and thus unneces­
sary operation. The overreach is caused by the parallel line out of
service and earthed at both ends and the factor KN should be set
as:
2 2
X 0 – X m0 – X 0 X 1
K N
= -----------------------------------------------
3X 0 X 1 ­

MEASURING PRINCIPLES

BA THS / BU Transmission Systems and Substations LEC Support Programme 125


When the parallel line is out of service but ungrounded the reach
will be reduced with a factor k1. This factor should be checked
and the overlapping of zone 1 from both end at underreaching
schemes should be verified.

( 1 + K N1) 3X 1
k 1 = ---------------------------------------
2X 1 + X 0 ­

The setting of KN factor for zones 2 and up should always be as


the normal setting with an extended factor of 1,25 to cover a

worst case which occurs when no fault current is fed in at the re­

mote terminal.

Note that the change of reach for parallel lines with compensated

KN is only valid for single phase faults. For multi phase faults the

reaches are not influenced.

Figure 15 shows the principle of the mutual impedance.

A B
ZL

Z0M
ZL
<

U0

A B
Z0M I0 Z0-Z0M

1/ 1
I0 Z0-Z0M

Figure 15. Influence of mutual impedance, at parallel lines, at the same


tower.

MEASURING PRINCIPLES

126 BA THS / BU Transmission Systems and Substations LEC Support Programme


Line protection
Special functions
Some special functions are of interest with Distance protection
relays and should be mentioned.

SWITCH ONTO FAULT (SOTF)At energizing a power line onto a for­


gotten earthing, portable or fixed, no measuring voltage will be
available and the directional measuring can thus for three phase
faults not operate correctly. A special SOTF function is thus pro­
vided in Distance protection relays. Different principles can be
utilized, from an one phase current/one low voltage measure­
ment to an undirectional impedance measuring as per figure 16.
The SOTF function is connected for some second/s only when
energizing. The criteria that there is a SOTF condition can either
be taken from the manual closing signal (called DC SOTF) acti­
vating an input in the relay, or can be detected internally by the
relay (AC SOTF) where a no voltage-no current condition for a
certain time is taken as confirmation that the line is dead.

X [[Ω]
If

U=0 V ZL
Z<

R [[Ω]]

Figure 16. Switch Onto Fault function ensures fast tripping when energizing
a line onto a forgotten earthing.

MEASURING PRINCIPLES

BA THS / BU Transmission Systems and Substations LEC Support Programme 127


POWER SWING BLOCKING (PSB) FUNCTION

Power swings can occur at double end in-feed networks. A Power


swing can be started by a sudden load change, due to e. g. man­
ual switching, or at a fault somewhere in the network.

Close to the centre of the power swing low voltages and thus low
impedances will occur. A Distance protection relay can thus op­
erate at a power swing and this is in most countries not accepted.
A Power Swing Blocking device is available for all schemes. The
most used principle used is to “measure the speed of the imped­
ance locus”. This is done by two impedance circles, or rectan­
gles, and a measuring of the time between passing the outer and
the inner line. Normally the time used is 35-40ms.
Exceeded time will make an alarm telling that a Power swing has
occurred. A blocking of the Distance protection zones will then be
made. Normal power swings in networks have a swing cycle of
0.5-10 seconds.

X [[Ω]

ZL
Rf

Power swing
Rf locus

Rf
Load

R [[Ω]

Figure 17. Power Swing Blocking function. Two rectangles can be provided
and the time between passing the outer and inner rectangle is measured.

STUB PROTECTION FUNCTION In one and a half and ring busbar


arrangements the voltage transformer will be located outside the

MEASURING PRINCIPLES

128 BA THS / BU Transmission Systems and Substations LEC Support Programme


Line protection
line disconnector but the bays can be in full service with the

breaker closed even if the line disconnector is opened e. g. due

to make maintenance on the power line.

A fault in the line bay section, will not be possible to detect by the

distance protection. It’s also a risk of incorrect directional mea­

surements due to induced voltages or back-feed of voltage from

the remote end. The Distance protection directional impedance

measuring is blocked and a so called Stub protection is intro­

duced. The Stub protection is a simple current relay activated

only when line disconnector is open.

Figure 18. Stub protection function protects the line exit when the line
disconnector is open.

MEASURING PRINCIPLES

BA THS / BU Transmission Systems and Substations LEC Support Programme 129


3.4 APPLICATION PROBLEMS

A number of interesting application problems occurs in a trans­


mission line. Among them should be mentioned: Current reversal
In the quite common “parallel line applications” current reversal
can occur. The principal problem is shown in figure 17 and an ex­
ample of the logic used to ensure correct operation is shown in
figure 18

110ms 80ms
RN
G G
Z< Z<

A B
Z< CS Z<
ZMrev ZMforw
Figure 19. Fault current reversal occurring, with parallel lines, at the same
tower.

ZM2

CR
& Trip

60
ZM3R &
40

Carrier
&
send
Figure 20. Fault current reversal logic for overreaching scheme in RELZ

100/REL 511/521./531 “ZM2” is measuring zone 2, “ZM3R” is Zone 3 re­

verse and “CR” is carrier receive.

When a fault occurs at a line, on a parallel connection, the fault

will always be cleared from one line end first. When the first
breaker opens, the fault current in the parallel line will have a
change of direction and if nothing is done in the logic for commu­
nication, maloperation can occur on the parallel healthy line. It
should be noted that the problem occurs for overreaching
schemes only.

MEASURING PRINCIPLES

130 BA THS / BU Transmission Systems and Substations LEC Support Programme


Line protection
SIMULTANEOUS FAULTS In the quite common “parallel line appli­
cations” simultaneous faults can occur. A fault can occur between
“L1” and “L2” but the phases are at different lines. A full scheme
relay is a must to give correct operation for simultaneous faults as
the measuring loops for earth faults must detect one forward- and
one reverse fault in different phases and a logic must be provided
in the relay to get the correct operation. Many Distance protection
relays (even of new types), will risk maloperation at these faults
and care must also be taken when the relay zones and the phase
selection are set.

Switched schemes can due to the starter function not operate


correctly for simultaneous faults. The starter will select both in­
volved phases to the measuring element on both involved lines
distance protection relay. The measurement will then naturally be
incorrect.

Figure 21 shows the principle for simultaneous faults. The new


Distance protection relays from ABB Network Partner provides a
logic to cover the problem.
A RN/SN RN Forw
Forw SN Rev B

RN

Z< Z<

SN
Z< Z<
RN/SN SN Forw
Forw RN Rev

Figure 21. Simultaneous faults, in parallel lines, at the same tower.

SERIES CAPACITORSThe use of forward impedance measurement


using the reactive characteristic of the transmission lines, implies
that Distance protection relays can’t be used in series compen­
sated lines without special care. Experts must be consulted for
such applications. This is also valid for surrounding lines in the
same station.

MEASURING PRINCIPLES

BA THS / BU Transmission Systems and Substations LEC Support Programme 131


3.5 TRAVELLING WAVE PROTECTION RELAYS

The travelling wave detector, was a revolution in relay technology,


when first developed at the end of the seventies.

A fault in the power network, moves with the speed of light and
causes changes in the transmission network.

By detection of the transient changes in the current “∆i”, and in


the voltage “∆u”, and by comparing the signs of the two, the di­
rection to the fault can be determined. The fault detection can be
done very quickly. In the total trip time the communication time for
the communication with the remote end also must be included as
the protection forms a directional comparison scheme.

The travelling wave protection schemes are only used in EHV


networks and are very suitable to be used in series compensated
lines where a distance protection scheme has a draw-back.

Due to the rather limited use for EHV lines the protection will not
be discussed further in this document.

4. AUTO RECLOSING

4.1 THE PRINCIPLE OF AN AUTO RECLOSING DE-


VICE

For restoration of the normal service after a line fault an Auto re­
closing attempt is mostly made for Overhead lines. From fault sta­
tistics it has become accepted that as high as 95% of the faults
are of transient nature i.e. an Auto reclosing can be successful.

The three phase quick Auto reclosing attempt is mostly carried


out after a synchro check where the voltages on both sides of the
circuit breaker are checked and it is verified that they are not out
of phase due to e. g. a heavy power swing.

AUTO RECLOSING

132 BA THS / BU Transmission Systems and Substations LEC Support Programme


Line protection
For single phase Auto reclosing an identification of the faulty
phase is necessary. This phase selection can not be achieved at
high resistive earth fault, when “RF>50-200 Ω”. Faults with higher
“RF” can be detected by zero sequence current protections but
can’t be single phase Auto-reclosed as the discrimination of the
faulty phase is difficult. Special schemes have however been de­
veloped for cases where there is a definite need to disconnect
only one phase due to a very weak network.

4.2 GENERAL CONDITIONS FOR AUTO RECLOSING

The Auto reclosing shall be coordinated with various equipment


as indicated in Figure 22.
AR - Auto-recloser

BFR - Breaker failure relay

COM - Communication

COND - CB condition

DLC SC - Dead line check and synchronism check

LP - Line protection

MAN - Manual CB control

PD - Pole discordance relay

COM

BFR

LP2

LP1
AR SC
PD
M
Man COND
Close

Figure 22. The Auto recloser and communicating equipment in a line bay.

Line protection relays.


There may be a single distance relay or duplicated protection. A
delayed back-up function is normally included. The Auto recloser

AUTO RECLOSING

BA THS / BU Transmission Systems and Substations LEC Support Programme 133


is started at relay tripping. At delayed tripping the recloser is nor­
mally blocked.

Communication.
Communication between the line relays is used to ensure quick
and simultaneous tripping at both ends. With relay cooperation in
the permissive mode there is a risk for delayed tripping at one
end if the communication is not working when a line fault occurs.
Dead time at quick Auto reclosing must be increased or recloser
start should be blocked at loss of communication.

Circuit breaker operating gear.


Energy is stored for close and trip operations. If there is insuffi­

cient energy stored for a close-trip sequence, recloser start shall

be prevented.

Circuit breaker failure relays. Circuit-breaker trouble detected by

breaker failure relay or pole discordance relay should block Auto

reclosing.

Dead-line check and synchronism check.


Depending on the power grid configuration it may be necessary
to use a synchro-check relay to prevent Auto reclosing at loss of
synchronism. Dead line check is then made at one line end and
synchronism check at the other. In power grids with several reli­
able parallel circuits high-speed Auto reclosing is, however, often
arranged to work without any synchro-check function.

Manual CB operation.
At manual CB closing the recloser is blocked. Should there be a
fault on the line it is then tripped but not reclosed. At manual CB
tripping the recloser is not started.

Status of recloser.
The recloser status shall influence the tripping. In the recloser for
single-pole or three-pole reclosing there is a programming for se­
lection of reclosing mode. If the program is set to the position for
three-phase reclosing or reclosing off, or the recloser is blocked
by external conditions, all trippings shall be made as three-pole
operations. Sometimes, when investment in communication be­
tween distance relays is not made, the relays are set with a zone
1 overreach and thus cover more than the whole line at the first

AUTO RECLOSING

134 BA THS / BU Transmission Systems and Substations LEC Support Programme


Line protection
tripping. At reclosing the zone 1 reach is shortened to ensure se­
lective clearance of persistent faults. When the recloser is
blocked or switched off, the zone 1 reach shall also be reduced
to give selective fault clearance already at the first tripping.

The principle for an Auto reclose cycle


The principle of an auto reclosing cycle is shown in figure 23.

Figure 23. The operating principle of an Auto reclosing device.

The Auto reclosing device is providing a reclosing attempt, after


a dead interval with sufficient length, to ensure that deionisation
of the fault area has taken place. The dead, and blocking time
must match the breaker capability. Normally the circuit breakers
fulfil the IEC duty cycle for circuit breakers O - 0.3 seconds CO ­
3 min CO

FAULT TIMES AND DEIONISATIONThe time to achieve deionisa­


tion after the fault is dependent of several factors such as time to
fault clearance, fault current, wind, air humidity, capacitive cou­
pling to live parts etc.

The dead interval must be selected to give sufficient time, to


deionisate the fault area. For instantaneously cleared faults
(<100ms), a dead time of 300-400ms can be sufficient.

AUTO RECLOSING

BA THS / BU Transmission Systems and Substations LEC Support Programme 135


If the fault clearance is delayed, say fault clearance times of 0.5-1
second, the dead interval must be longer e.g. 1 second.

When single phase Auto reclosing is used the dead time must
also be longer. Normally times of 0.8-1.2 seconds are used. The
reason for this is the capacitive coupling to live phases which will
maintain the arc. For long lines (>150km) it may even be neces­
sary to introduce a neutral reactor to the line (teaser reactor). The
teaser reactor shall have an inductance matching the line capac­
itive reactance to enable single phase auto reclose with reason­
able long dead time.

Auto reclosing schemes


There is a number of different practices, the most common ones
are:
- Three phase auto-reclosing at all type of faults.
- Three phase auto-reclosing only at single phase faults.
- Single phase auto-reclosing at single phase faults together with three
phase auto-reclosing at multi phase faults.
- Single phase auto-reclosing at single phase faults only.

Three types of dead interval are used:


- Quick Auto reclosing, with a dead interval less than 0.8 seconds. A quick
Auto reclosing requires communication between the line ends and an in­
stantaneous fault clearance at both ends.
- Quick auto-reclosing with a dead interval longer than 0.8-2 seconds can
be used when no communication exist and the fault clearance will or can
be made from the Distance protection second zone at one of the line
ends. The dead interval must then be increased.
- Delayed auto-reclosing, with a dead interval from 6 seconds up to sev­
eral minutes is mostly used in distribution networks but are also used at
transmission voltages in some countries.

4.3 BLOCKING

The Auto recloser must be blocked under the following condi­


tions:

AUTO RECLOSING

136 BA THS / BU Transmission Systems and Substations LEC Support Programme


Line protection
- Energizing of a line onto a fault. When a line is closed onto a fault the
Auto recloser is blocked to prevent unnecessary disturbances in the
power network. The chance of a persistent fault is high as the line has
not been carrying load and is therefor not a part of “normal conditions”.
- Auto-reclosing onto a persistent fault. An unsucessful auto reclosing
means that the fault probably is persistent. The auto-recloser is then
blocked to prevent new attempts. Solutions with several attempts how­
ever exists but the breaker duty cycle must then be carefully checked.
- “Breaker not ready” is used to block the auto-recloser. The breaker is
then not ready to perform any attempt and the breaker can not be auto­
matic reclosed.
- PLC (or communication channel) out of service must be connected to
block the Auto recloser if a quick auto reclose attempt is used. The fault
has not surely been cleared from the remote end and an auto reclose
might therefor not be successful.

5. AUTO RECLOSE FOR ONE-AND A HALF


BREAKER OR RING BUSBAR SCHEMES.

Auto reclosing of transmission line circuit-breakers is somewhat


more complicated in One- and a half breaker, 2–breaker and
Ring busbar stations than in simpler stations with a One line -
One breaker arrangement. At a line fault two CB’s shall be tripped
and reclosed at each end of the line and some coordination is re­
quired. In addition one circuit breaker (tie breaker) is shared by
two circuits in One- and a half breaker and Ring busbar stations.
A standardized Auto reclosing scheme designed by ABB com­
bines flexibility with some particular features:
- High-speed or delayed Auto reclosing.
- Single-pole an/or three-pole Auto reclosing with independent setting of
dead times.
- Synchronism check feature as an option. It can be combined with de­
layed or high-speed three pole Auto reclosing.
- Cooperation with single- or duplicate line relays.
- Adapted to communicating line relays or Distance relays with overreach
of zone 1 before Auto reclosing.

AUTO RECLOSE FOR ONE-AND A HALF BREAKER OR

BA THS / BU Transmission Systems and Substations LEC Support Programme 137


- Suitable for various station arrangements including One- and a half
breaker and ring busbar stations. The two line CB:s in a station can be
reclosed successively with a priority circuit.
- Only those CB:s which were closed before the line fault are reclosed.
- The dead line time is not influenced if one of the two line CB:s in a station
is out of service when the fault occurs.
- Correct behavior also for interline faults when parallel lines are used.

A
CB3

AR
CB2 AR

AR

AR
CB1

Figure 24. Auto reclosing of transmission line CB:s.

AUTO RECLOSE FOR ONE-AND A HALF BREAKER OR

138 BA THS / BU Transmission Systems and Substations LEC Support Programme


Line protection
INFLUENCE OF THE STATION ARRANGEMENT ON THE
AUTO RECLOSING

The type of switchgear arrangement will influence the introduc­


tion of Auto recloser and Synchro check devices. A number of
possible different arrangements are shown in below figure.

AUTO RECLOSE FOR ONE-AND A HALF BREAKER OR

BA THS / BU Transmission Systems and Substations LEC Support Programme 139


Figure 25. Examples of multi breaker switchgear arrangements

MULTI BREAKER ARRANGEMENT


Application of Auto reclosing in an One- and a half breaker, Two
-breaker or a ring busbar station requires some particular atten­
tion. After a line fault two CB’s at each end of the line shall be re­
closed and need to be coordinated. One CB can be taken out of

AUTO RECLOSE FOR ONE-AND A HALF BREAKER OR

140 BA THS / BU Transmission Systems and Substations LEC Support Programme


Line protection
service independently of the line and that CB shall in such a case

not be Auto-reclosed if a line fault occurs.

In a One- and a half-CB station each centre CB is shared by two

circuits, for instance a line and a transformer as in Fig. 25c, or two

lines as in Fig. 25d. In a ring busbar station all CB’s serve two cir­

cuits in the same way. Interconnecting circuits are necessary be­

tween the line oriented equipment, CB equipment and Auto

recloser. It is important to arrange these circuits in a manner that

the correct and reliable function is obtained and that the arrange­

ment can be simple understood, checked and maintained.

A standard scheme with options for different requirements is thus

preferable.

Following special problems should be considered.

Priority circuit.

When one line is controlled by two circuit breaker both must be

opened when a fault occurs and should consequently also be re­

closed. To limit the consequences if the fault is persistent the two

breakers are reclosed in sequence and a priority circuit is built-up

to manage the priority. The common way is to reclose the bus

breaker first in a one- and a half breaker scheme. In other ar­

rangements one CB must be given the higher priority.

The priority circuit is based on the start of the AR devices where

the start of the highest priority CB AR device puts the low priority

CB AR on a “wait” condition until the first CB has successfully re­

closed and the AR device has reset. The dead time for the sec­

ond CB is then started and the second CB reclosed. The

advantage is that the low priority CB need not to be stressed if

the fault is persistent.

Should the first breaker fail to reclose due to a persistent fault a

circuit is arranged to reset the second recloser also when the new

trip is achieved.

AUTO RECLOSE FOR ONE-AND A HALF BREAKER OR

BA THS / BU Transmission Systems and Substations LEC Support Programme 141


AR out of service.
Of course the circuit breaker shall not be single phase trip is the
Auto recloser is in “OFF” position, in the “3 phase” position or out
of service due to e. g. AR device Auxiliary voltage supply failure.
CB not ready should also be included in this circuit. It is then es­
sential that a prepare three phase trip circuit is designed and for
multi breaker schemes this must be done on the trip unit for each
circuit breaker as the choice can be made independently for each
breaker. It must be remembered to use a fail safe connection in­
dependent of the voltage supply of the AR device. The circuit is
shown in below figure. The circuit must include preparation of
three phase tripping in both of the redundant trip systems. Prin­
ciples for exchange of information between sub systems should
then be considered, see a separate section in this book.

Figure 26. The principle circuit for arrangement of prepare three phase trip
at a multi breaker arrangement.

AUTO RECLOSE FOR ONE-AND A HALF BREAKER OR

142 BA THS / BU Transmission Systems and Substations LEC Support Programme


Line protection
In Fig. 27 some examples are illustrated. In the following, Auto re­
closing of a line in an One- and a half-breaker bay for two lines
will be used as an example. It is a representative complicated
case.

A
CB3

CB2
D

E
Line fault
CB1

Figure 27. Some Auto reclosing sequences in multi breaker systems.

5.1 AN AUTO RECLOSING SCHEME

An Auto reclosing scheme in a multi breaker bay can include:


- One Auto recloser for each line CB.
- Coordination between auto-reclosers.
- Dead line/synchro-check circuits and relays for CB conditions and inter­
connection with CB pole discordance relay.
- Adaptation of the trip relay circuits.
- Interconnection and interfacing with line protection relays and commu­
nication equipment.
The equipment in a bay of a One- and a half-breaker station is
shown in Fig. 28 and in Appendix 3.

AUTO RECLOSE FOR ONE-AND A HALF BREAKER OR

BA THS / BU Transmission Systems and Substations LEC Support Programme 143


Man
COM
Cl.
COND AR CB1
LP2
DLC
PD
SC
Man

LP1 Cl. CB2


COND AR

LP2 DLC
PD
SC
Man

Cl.
LP1 COND AR CB3

PD DLC
SC
COM

Figure 28. Auto-reclosers (AR) and cooperating equipment in a One- and a


half-breaker bay

The line protection relays are normally Distance protection relays

which are designed to cooperate with the auto-reclosers.

Duplicate, redundant Distance relays are often used for impor­

tant transmission lines. The reclosers must thus cooperate with

two such protection systems.

The auxiliary supply circuits are essential for the reliability. The

Auto reclosing scheme can be combined with duplicate DC sys­

tems. The primary protection relays, the Auto-reclosers, the syn­

chro-check relays etc. are then supplied from one DC-system.

The secondary redundant protection relays and trip circuits are

connected to the second DC system.

Each CB has an independent Auto recloser so each line protec­

tion has cooperation with two Auto reclosers and the line can be

Auto-reclosed even if one CB or one recloser is out of service or

switched off when the fault occurs.

In order to gain maximum flexibility the auxiliary DC sub-distribu­

tion is normally made with individual fusing (by MCB or fuses) for

each CB section and each line. The auxiliary supply can thus be

switched off when maintenance is made on one CB or on the line

equipment.

Auxiliary and time-lag relays are used for various purposes, trip­

ping, interfacing, galvanic separation etc.

AUTO RECLOSE FOR ONE-AND A HALF BREAKER OR

144 BA THS / BU Transmission Systems and Substations LEC Support Programme


Line protection
5.2 AUTO RECLOSING SEQUENCES.

Some Auto reclosing sequences obtained by use of ABB stan­

dardized Auto reclosing scheme in a One- and a half-breaker bay

are described below. The arrangement is shown in Appendix 3.

Assumptions:

All CB’s and disconnectors are closed. The lines are in normal

service. All protection relays with power line carrier (PLC) com­

munication are in operation.

The reclosers are set for 1- and/or 3-pole tripping and Auto re­

closing. The dead times are 1.0 and 0.4 seconds respectively.

CB 1 shall reclose before CB 2. CB1 is selected to energize the

line and the Voltage check VC is released. CB 2 is selected to

Synchro check SC and no VC is allowed.

The line shall be reenergized from this station with CB 1 as first

priority.

A Three-pole Auto reclosing with VC resp. SC


Approximate time plan.

0.0 s A multi-phase fault occurs on line 1. The line relays operate

instantaneously and the trip relays in all three phases operate.

The conditions for auto-recloser start are fulfilled. The reclosers

for CB 1 and CB 2 are started for a three-pole reclosing.

The priority circuit from the CB 1 recloser keeps the CB 2 recloser

waiting.

CB 1 and CB 2 and remote end CB’s clear the fault. The line re­

lays and the trip relays resets.

0.2 s The VC/SC device detects a dead line condition.

0.4 s The CB 1 recloser timer for 3-pole dead time operates.

The VC/SC condition is fulfilled and CB 1 is given a reclosing

pulse. The CB 1 recloser is put in a blocking state for a certain

Reclaim time, e.g. 180 sec.The CB 2 recloser is released.

0.5 s CB 1 recloses and energizes the line.

0.7 s The dead line condition has disappeared but the VC/SC

relay operates for synchronous conditions.

0.8 s The CB 2 recloser operates and gives CB 2 a closing

command. The recloser is then blocked for the Reclaim time.

0.9 s CB 2 has closed.

AUTO RECLOSE FOR ONE-AND A HALF BREAKER OR

BA THS / BU Transmission Systems and Substations LEC Support Programme 145


180 s The reclosers reset when reclaim time expires. They are
then ready for a new operation.

Above a high-speed Auto reclosing is described but the reclosers


can of course also be set for delayed reclosing.

Single-pole reclosing
Approximate time plan.

0.0 s. A single-phase fault occurs on the line. Single-pole tripping

of CB 1 and CB 2. The CB 1 and CB 2 reclosers are started. The

CB 2 recloser is kept waiting by the priority circuit. The reclosers

block the pole discordance relays and in applicable cases Earth

fault current relays are blocked during the single-pole dead inter­

val.

1.0 s. The CB1 recloser operates. VC or SC is not necessary at

single-pole reclosing. CB 1gets a closing pulse. The CB 1 reclos­

er is blocked for the Reclaim time and the CB 2 recloser released.

1.1 s. CB 1 recloses the open pole.

2.0 s. The CB 2 recloser operates.

2.1 s. CB 2 recloses the open pole.

e.g. 180 seconds. The reclosers reset after the Reclaim time

Influence on the Auto reclosing by various conditions.

1) Delayed tripping. At tripping by delayed steps of Distance re­

lay, or at other back-up relay tripping the reclosers are blocked.

2) The recloser selector switch of one recloser, e.g. CB 1, is set

in OFF position. The CB 1 trip relays are then interconnected. At

a single-phase fault on Line 1, CB 1 will trip three-pole. CB 2 will

trip single-pole and reclose.

3) Communication trouble at Distance relay cooperation in a per­

missive scheme.

The relay trips instantaneously, but lacking communication (e.g.

by power line carrier, PLC) there is a risk that the remote end Dis­

tance relay trips with a zone 2 delay. Start recloser is blocked

since the line dead time may be too short for fault deionisation.

Alternatively an additional time is added to the 3 phase dead

time.

4) One CB was open before the line fault.

Assume that CB 1 is open. The CB 1 conditions for Auto reclosing

are not met. At a fault the CB 1 reclosing will not be started and

AUTO RECLOSE FOR ONE-AND A HALF BREAKER OR

146 BA THS / BU Transmission Systems and Substations LEC Support Programme


Line protection
it will not delay the CB 2 recloser. CB 2 will reclose without pro­
longing the dead line time.
5) CB operating gear not charged.

The CB conditions for reclosing are not fulfilled. See point 4

above!

6. SYNCHRO CHECK DEVICE

By use of a quick-acting synchronism check functions,


high-speed reclosing with synchronism check can be employed
and can be a valuable tool to improve operational reliability of a
power system. With synchronism check is meant the check of a
dead line condition with a Voltage check and the check of the par­
alleling condition with a check of phase angle and voltage differ­
ence with frequency difference within a set limit. Single-pole
reclosing does not require any synchronism check.
In the following only three-pole reclosing with Synchro check will
be discussed.

Three-pole reclosing can be performed when the two parts of the


grid are in synchronism. Synchronism can be secured by circuits
in parallel to the tripped line. The possibility that a parallel line
could, for instance, is affected by a fault or can temporarily be out
of service, must be considered when the need for Synchro check
is discussed.
In some cases, for instance with one single line between two
parts of the power system, three-pole auto-reclosing cannot be
used. It is very unlikely that the two parts maintain synchronism
after a three-pole tripping. In such cases one has to refrain from
three pole auto-reclosing or limit the use to single-pole tripping
and auto-reclosing at single-phase faults. After a three-pole trip­
ping the two parts must be synchronized together.

Figure 29 illustrates power grids with varying degree of meshing.


In the systems of fig. 29b, 29c and 29d three-pole reclosing can

SYNCHRO CHECK DEVICE

BA THS / BU Transmission Systems and Substations LEC Support Programme 147


be utilized. Synchronism check at reclosing is particularly inter­
esting in the cases fig. 29b and 29c.

Figure 29. Power grid with different degree of meshing between A and B

SYNCHRO CHECK DEVICE

148 BA THS / BU Transmission Systems and Substations LEC Support Programme


Line protection
6.1 SYNCHRO CHECK AT HIGH-SPEED AUTO RE-
CLOSING

Direct three-pole high-speed Auto reclosing is applied in power

grids similar to fig. 29d. It is simple and uncomplicated and gives

a short disturbance time.

The fault clearing is made as quick and as simultaneous as pos­

sible at the two ends. The Automatic reclosing is performed with­

out any intentional time difference between the ends. Has the

fault disappeared at reclosing, the line can immediately pick-up

load. The dead line time, and the time the circuit is open, are al­

most the same.

A certain power system swing is caused by the fault and the

switching of the line in and out. After automatic reconnection the

system swings back to pre-fault conditions. The amplitudes of the

swing depends upon the load transfer before the fault, the fault

type, the fault location, the fault clearance time, number and

length of parallel lines and other power system parameters.

Care shall be taken not to apply direct Auto-reclosing close to

power stations, especially close to thermal plants with turbo gen­

erators. A reclosing into a close-up persistent fault would for such

applications result in a considerable strain of the generators.

6.2 DELAYED AUTO RECLOSING WITH SYNCHRO


CHECK

The fault clearance is made simultaneously or with a small


non-intentional time difference between the line ends. Delayed
auto-reclosing is normally combined with synchronism check.
The C. B. reclosing at one end is then preceded by a live-bus and
dead-line check. Once the line is energized, the synchronism can
be checked at the other end of the line before completing the au­
to-reclosing sequence.
The completion of the reclosing is somewhat delayed by the syn­
chronism check. To the dead time is added the time required for
the synchronism check and the C. B. closing. This extra time is
less important at delayed reclosing. Typical times can be: Dead

SYNCHRO CHECK DEVICE

BA THS / BU Transmission Systems and Substations LEC Support Programme 149


time 10 seconds, synchro-check time 0.2 seconds, C.B. closing
0.1 seconds, giving 0.3 seconds to be added to the dead time.
As in the case of high-speed reclosing, a swing occurs after the
fault and the fault clearance. A sufficiently stable power system
swings to a new state and is relatively stable at the instant of de­
layed reclosing. The synchro-check device checks the voltage
levels at both side of the circuit breaker, the voltage level differ­
ence, phase angle shift and frequency difference before the Auto
reclosing attempt is made.
The difference in voltage and the phase shift, together with line
and source impedances, determine the shock at reconnection. At
short lines and strong power systems the voltage difference and
phase shift are generally small and the synchronism check de­
vice should be set in accordance with those conditions.
At long lines on the other hand, the phase shift due to high load
through long and weak parallel circuits, may be considerable. The
setting must then be at least equally high and it can well be re­
quired to be up to 60°. The shock at reclosing will still be moder­
ate due to the high line impedance.
A frequency difference between the two parts of the power sys­
tem may exist due to a system swing or lost synchronism.

Consider a case according to fig. 29b. The line from B to C is as­


sumed to be open at B. Only little power is transferred between A
and B, when a fault occurs on that line. The power system is then
split into two parts and can loose synchronism. The two parts
may however have just a small difference in frequency. A reclos­
ing of the interconnecting line could fail if the two non-synchro­
nous parts are strong and heavy and the line is incapable of
reestablishing synchronism. The synchronism check devices
should therefore have a high sensitivity to frequency difference in
this kind of application. A sufficiently high sensitivity for frequency
difference is not a disadvantage at delayed reclosing as the sys­
tem is given sufficient time to stabilize before reclosing.

To conclude: A synchronism check device for delayed auto-re­


closing shall have the following features:
- a check of voltage level and/or voltage level difference,
- a phase shift sensitivity settable within wide limits,
- a sensitive frequency difference check and

SYNCHRO CHECK DEVICE

150 BA THS / BU Transmission Systems and Substations LEC Support Programme


Line protection
- a moderate operation time, typically less than 0.2-0.5 seconds.

6.3 HIGH-SPEED AUTO RECLOSING WITH SYN-


CHRONISM CHECK

In power systems where the stability is strained under periods of

high load, one would like to reclose quickly in order to improve the

stability. If the parallel interconnection is unreliable, for instance

in a system like fig. 29b or 29c, it can be risky to perform a

high-speed reclosing without synchronism check. One can then

be forced to refrain from reclosing, rely on single pole auto-re­

closing at single-phase faults or take a chance with delayed au­

to-reclosing.

In the latter case the Auto reclosing may be blocked at high loads,

which is unfortunate, especially if a high-speed reclosing could

have saved the stability. In such cases it would be preferable to

adopt high-speed reclosing with dead line check and synchro­

nism check.

When a parallel line is in service Auto-reclosing can then be per­

formed. On the other hand, when the parallel circuit is out of ser­

vice, the reclosing will be blocked as the synchronism is most

likely lost during the dead time.

Auto-reclosing with dead line and synchronism check can in

many cases be applied also for lines near a power station.

By choosing to energize the line from the remote end the strain

at reclosing into a persistent fault will be moderate. Because the

remote end is retripped at a persistent fault, the end near the

power station will not be reclosed. Only after a successful line re­

energizing the synchronism check conditions will be met and the

line reclosing completed.

At a controlled high-speed Auto reclosing the dead line check is

made during the dead interval of 0.4-1.0 seconds and a time for

dead-line check of 0.2 seconds can be allowed. The synchronism

check is made after line reenergizing and the check should be

quick to avoid unnecessary delay of the reclosing. It must howev­

er wait about 0.1 seconds for a possible retripping of the remote

end. Assuming a dead interval of 0.4 seconds, a synchronism

check time of 0.2 seconds and time for circuit-breaker closing of

SYNCHRO CHECK DEVICE

BA THS / BU Transmission Systems and Substations LEC Support Programme 151


0.1 seconds the open-circuit time will be 0. 4 + 0. 2 + 0.1 seconds
= 0.7 seconds.

One must expect a considerable power system swing at


high-speed reclosing of long transmission lines in a system with
threatened stability. Therefore, the synchronism check device
must not be too sensitive, but allow fairly high values of phase
shift and frequency difference. Values of 70° and 200 mHz are re­
alistic. The synchronism check shall be supplemented by a timer
to interrupt the auto-reclosing if the check conditions are not met
within a short time, e.g. 1 seconds

SYNCHRO CHECK DEVICE

152 BA THS / BU Transmission Systems and Substations LEC Support Programme


Line protection
6.4 ARRANGEMENT OF SYNCHRO-CHECK UNITS
FOR AUTO RECLOSING

In Fig. 30 is indicated Auto reclosing with dead line check at one


end and synchronism-check at the other end. It would thus be
sufficient with a live-bus/dead-line check unit in the first and a
synchronism check device in the other end. Complete syn­
chro-check devices with live bus/dead-line check facility are how­
ever usually installed at both ends. In this way the direction of line
reenergizing can easily be changed by change of settings.

Figure 30. Dead line check (DLC) and synchronism check (SC) at auto-re­
closing. 25 = DLC/SCdevice

Normally there are several lines connected to a substation. It is


practical to install a synchro-check device for each line cir­
cuit-breaker. In case of a simultaneous tripping of two lines the
Auto reclosers can then operate independent of each other. Si­
multaneous faults could occur at lightning strokes in towers com­
monly used for two lines. Furthermore, by use of one
synchro-check device per line breaker there will not be any need
for complicated selection in the voltage and trip circuits.
In stations of breaker- and -a-half, double breaker or ring busbar
type, two circuit-breakers per line end are tripped at line faults
and shall be reclosed.

The line is energized by one circuit-breaker and if the fault has


disappeared, then the other breaker is also reclosed. The order
is determined by a priority circuit between the reclosers. In Fig.
31 is shown successive reclosing with dead line check of the first

SYNCHRO CHECK DEVICE

BA THS / BU Transmission Systems and Substations LEC Support Programme 153


CB closing (Al) and synchronism check of the second CB (A2).

Should however the first CB be out of service at the fault, no re­

closing is made with this CB.

In that case the second CB shall energize the line and the syn­

chro-check device shall be arranged to permit dead line charging.

In the other station sequential Auto reclosing of the CB’s is also

used but combined with synchronism check as indicated in

Fig. 31.

The four synchro-check devices are set in such manner, that A1

and A2 permit reclosing at dead line or at synchronism condi­

tions, but devices B1 and B2 require synchronism at reclosing.

Figure 31. Dead line check and synchronism check at auto-reclosing in a


One- and a half-breaker station and a Ring busbar station

6.5 SYNCHRO-CHECK RELAY/FUNCTION.

The synchro-check relay measures in a single phase mode the


voltage on both sides of the open circuit breaker and it checks:
- Voltage levels
- Difference in voltage level
- Phase angle difference
- Frequency difference

SYNCHRO CHECK DEVICE

154 BA THS / BU Transmission Systems and Substations LEC Support Programme


Line protection
When a voltage check function is used it can be set to allow en­

ergizing in one or the other, or both directions, or be blocked. To

suit different applications there are wide range of application se­

lections or/and settings, which differ with respect to speed and

frequency difference sensitivity.

The functions are made to suit the conditions at Quick and De­

layed Auto-reclosing as discussed above. It is then set for contin­

uous output signal as long as the conditions are fulfilled and it

releases the auto-recloser.

The main characteristics for a suitable Synchro check function

are as follows:

Synchro check unit (paralleling check):

Limit for normal voltage UH: 45-80% of Un

Max voltage difference, ∆U = 5-75% of Un.

Max phase angle difference, ∆Ø=5 -75°.

Max frequency difference, ∆f = 20-200 mHz

Operation time: t = 0.2-0.5 seconds

Voltage check unit (dead line check):

Limit for dead equipment, UL=30-80% of Un

Limit for live equipment, UH = 80% of Un


Operation time: t = 0.1-0.2 seconds.

6.6 7. EXAMPLE OF SYNCHRO CHECK FUNCTION


SETTINGS

Reference is made to Users Guide for the different functions/

relays.

Application: High-speed auto-reclosing.

On all four SC/VC functions in Fig. 29 above are set:

Nominal voltage U1, U2: Un =110/63.5 V

- Voltage difference ∆U: e.g. 15% of Un

- Phase angle difference ∆Ø: e.g. 45 °

The Synchro check function is set for continuous output signal

when conditions are fulfilled.

Unit A1 is set for line energizing: Dead Line - Live Bus DLLB

SYNCHRO CHECK DEVICE

BA THS / BU Transmission Systems and Substations LEC Support Programme 155


Continuous output

No delay.

Dead line voltage:

The unit A2 can be set at energizing “BOTH” i. e. allowing ener­

gizing of one or the other direction. The other settings are as for

A1.

The B1 and B2 units are set with Dead line energizing blocked.

The other settings are as for A1.

7. LINE PROTECTION SYSTEM

7.1 GENERAL DESIGN

A block diagram for a EHV/HV line protection system is shown in


Appendix 1.

A redundant protection scheme with two Distance protection re­


lays is provided. The high resistive earth faults are detected by a
Directional earth fault relay (DEF), including communication with
remote end in a permissive or blocking scheme. The DEF is pro­
vided in one of the systems only as the consequences for the
power network are smaller due to the lower magnitude of fault
current and as the fault is in one phase only. These high ohmic
faults will also develop to a low ohmic fault if not cleared within a
reasonable time and fault clearance is thus secured in both sub
systems.

An Auto-Reclosing device is provided to restore the normal oper­


ation as quick as possible. To verify that Auto-Reclosing can take
place at multi-phase faults a Synchro check function is provided.

To measure the distance to the fault, thus simplifying the localiza­


tion, a Fault locator is supplied as an option to the Distance pro­
tection. This will much improve the time to repair for a fault on a
long transmission line.

A Fault recorder is included to register the analogue signal at the


faults, enabling a post fault analyze to check the behavior of the
protection system and by that improve the total reliability.

LINE PROTECTION SYSTEM

156 BA THS / BU Transmission Systems and Substations LEC Support Programme


Line protection

A Breaker failure relay is provided to transfer the trip to the sur­


rounding breakers. This is only used for the case where the line
breaker fails to trip.

In Appendix 2 a MV/HV cable line protection based on a Differen­


tial relay and a back-up protection with directional short circuit
and Earth fault protection.

Appendix 1

The protection system Block diagram for a EHV/HV Line.

LINE PROTECTION SYSTEM

BA THS / BU Transmission Systems and Substations LEC Support Programme 157


LINE PROTECTION SYSTEM

158 BA THS / BU Transmission Systems and Substations LEC Support Programme


Line protection
Appendix 2

The protection system Block diagram for a HV/MV Cable.

LINE PROTECTION SYSTEM

BA THS / BU Transmission Systems and Substations LEC Support Programme 159


LINE PROTECTION SYSTEM

160 BA THS / BU Transmission Systems and Substations LEC Support Programme


Line protection
Appendix 3

The Auto Reclosers and Line protection for a One- and a Half
Breaker Bay section.

LINE PROTECTION SYSTEM

BA THS / BU Transmission Systems and Substations LEC Support Programme 161


LINE PROTECTION SYSTEM

162 BA THS / BU Transmission Systems and Substations LEC Support Programme


Transformer Protection

1. INTRODUCTION

A power transformer is an important and expensive part of a pow­


er network. High availability of the power transformer is therefore
very important in order to prevent disturbances in the power net­
works transfer of power.

A high quality power transformer, correctly designed and with


suitable protection relays and supervision is very reliable. Less
than one fault per 100 transformer and year can be expected.

When a fault occurs in a power transformer this will normally


cause severe damage. The power transformer has to be trans­
ported to a workshop for reparation, which takes considerable
time. Operation of a power network, when the power transformer
is out of service is always difficult. A power transformer fault
therefore often is a more severe disturbance for the network, than
an overhead line fault which usually can be repaired rather quick­
ly.

2. CONDITIONS LEADING TO FAULTS

Insulation breakdown
Insulation breakdown of the windings will cause short-circuits
and/or earth-faults. These faults causes severe damage on the
windings and the transformer core. In addition to that an over­
pressure may develop damaging the transformer tank.

Insulation breakdown, between windings or between winding and


core can be caused by:
- Ageing of insulation due to overtemperature during a long time.
- Contaminated oil.
- Corona discharges in the insulation.
- Transient overvoltages, due to lightning or switching, in the network.

INTRODUCTION

BA THS / BU Transmission Systems and Substations LEC Support Programme 163


- Current forces on the windings due to high currents at external faults or
the inrush currents when a transformer is energized.

3. RELAY PROTECTION

3.1 GENERAL

When a fault occur in a power transformer, the damage will be


proportional to the fault clearance time. The power transformer
therefore must be disconnected, as quick as possible. It is of out­
most importance that quick and reliable protection relays are
used to detect faults and initiate tripping.

Monitors at the power transformer can also be used for detecting


of abnormal conditions which may develop into a fault.

The power transformers size and voltage level influences the ex­
tent the choice of monitors and the protection relays used to limit
the damage at an possible fault. The cost for these is small com­
pared both to the total cost of the power transformer and the cost
due to a transformer fault.

There are often different opinions about the extent of transformer


protection. However, transformers with oil conservators usually
are equipped with the following protection and monitoring:

Transformers larger than 5MVA


- Pressure guard (Buchholz-relay).

- Overload protection (normally winding temperature supervision within


the transformer).
- Overcurrent protection.
- Earth fault protection.
- Differential protection.
- Pressure relay for tap changer compartment.
- Oil level monitor.

Transformers smaller than 5MVA

RELAY PROTECTION

164 BA THS / BU Transmission Systems and Substations LEC Support Programme


Transformer Protection
- Pressure guard (Buchholz-relay).

- Overload protection (normally winding temperature supervision within


the transformer).
- Overcurrent protection.
- Earth fault protection.
- Oil level monitor.

3.2 DIFFERENTIAL PROTECTION OF LOW IMPED-


ANCE TYPE

A differential protection compares the currents flowing into and


out from the transformer. Auxiliary current transformer “aux.ct:s”,
for adjusting the phase angle and ratio are necessary. Ratio cor­
rection is normally calculated for tap changer at middle position.

In new numerical protection relays aux.ct:s are not necessary.


Phase shift, voltage levels and CT-ratios are then programmed
into the protection and compensated for at differential current
measurement. Further zero sequence current filtering is also
made in software whereas in older static relays this was made by
including delta windings in the auxiliary current transformers.

A differential protection must operate quickly, when the differen­


tial current exceeds the settings of the relay and only operate for
a fault within its zone. The protection therefore must be stable
concerning:
- Inrush currents.
- Through fault currents.
- Overfluxing of the transformer.

This must be ensured, even with a tap-changer in the end posi­


tion.

Inrush current
Inrush current develop, when the transformer is connected to the
network. The magnitude and duration are dependent on:

RELAY PROTECTION

BA THS / BU Transmission Systems and Substations LEC Support Programme 165


- Transformer size and design.

- Source impedance.
- Remanence of the core.
- Point of the sinus wave at which the transformer is switched on.

Inrush currents can develop in all phases and in an earthed neu­


tral. Currents of magnitude 5-10 times the transformers rated cur­
rent can be obtained.

Inrush current can have the shape shown in fig. 1. Maximum in­
rush is achieved when the transformer is switched in at zero volt­
age and the magnetic flux, from the inrush current, have the
same direction as the remanence flux of the core. The two fluxes
are added and the core can saturate. When the transformer core
saturates the inrush current is only limited by the network source
impedance and transformer residual impedance.

Figure 1. Recorded inrush current for a 60MVA transformer 140/40/6,6kV,


connected YNyd

When the new flux at the swithing in have the opposite direction
of the remanence flux, no saturation of the core will be obtained
and the inrush current will be comparatively small. The size of the
inrush current therefore is dependent of where on the wave the
transformer is switched in.

RELAY PROTECTION

166 BA THS / BU Transmission Systems and Substations LEC Support Programme


Transformer Protection

The inrush current also have a large DC-component and is rich


of harmonics. The fundamental frequency and the second har­
monic are dominating. Damping of the inrush current is depen­
dent on the total resistance of the feeding network. Duration can
vary from less than 1 second, up to minutes in extreme cases,
when a transformer is switched in, in parallel with another, al­
ready energized, transformer.
In order to prevent unwanted functions at switching in the trans­
former the differential protection is supplied with a second har­
monic restraint measuring the content of second harmonic
compared with the fundamental frequency. The second harmonic
restraint will block unwanted tripping by increasing the stabiliza­
tion if the second harmonic content is large. A normal content is
>13-20% depending on the manufacture and type. For modern
numerical relays the stabilization level can be set for each appli­
cation.

Normal service
At normal service there will be a small differential (unbalanced)
current flow due to mismatch of ratio (aux.ct:s normally have a
limited number of taps and will not get exact adjustment), power
transformer magnetizing current and the position of the
tap-changer. The position of the tap changer is the factor that
gives the dominating differential current.

External faults
The “normal” differential current in service increases at an exter­

nal fault. A through fault of 10 times the rated current (with a tap

changer at end position) can cause a differential current of 1-2

times the power transformer rated current.

In order not to maloperate under these conditions the differential

protection is provided with a percentage, through fault, restraint

circuit. The percentage restraint ensures that the function only is

obtained if the differential current reaches a certain percentage

of the total through fault current (see fig. 2).

The current (I1+I2)/2 is the measured through fault current and

the differential current required for operation will increase with in-

RELAY PROTECTION

BA THS / BU Transmission Systems and Substations LEC Support Programme 167


creasing through fault current and a stabilization for the differen­
tial current achieved due to tap changer in offset position is then
achieved.

Figure 2. Through fault restraint gives an increased required differential cur­


rent when the through fault current is increasing.

Overexcitation
Overexcitation of a transformer means that the magnetic flux in
the core is increased above the normal design level. This will
cause an increase of the magnetizing current and the transform­
er can be damaged if this situation isn’t taken care of.

Overexcitation of transformers in transmission and distribution


networks is caused by overvoltages in the network.
For step-up transformers connected to generators during
start-up, overexcitation can occur since the flux is dependent of
the factor voltage/frequency. This means that the voltage must be
gradually increased, with increasing frequency, in order not to
overexcite the transformer.

The overexcitation is not an internal transformer fault, although


can lead to one. The differential protection must therefore be sta­
bilized under these conditions as tripping of transformers and
thus load will only mean that the overvoltage condition in the net­
work is becoming worse.

RELAY PROTECTION

168 BA THS / BU Transmission Systems and Substations LEC Support Programme


Transformer Protection
The current during overexcitation has a lot of fifth harmonic, see
fig. 3. This fact is utilized in modern transformer protection to sta­
bilize the transformer against unwanted functions during these
kind of conditions.

Figure 3. Magnetizing current at Overexcitation where“I1” is the fundamen­


tal frequency current, “I5” is the fifth harmonic current, “Im ” is the total mag­
netizing current and “In” is the nominal current.

If overexcitation of the transformer due to overvoltage or under­


frequency is likely to happen, a separate overexcitation protec­
tion should be supplied. This protection has inverse
characteristics according to the transformers capability to re­
strain overexcitation “V/Hz”. This protection must be connected to
a transformer winding with fixed number of turns. If the transform­
er is supplied with tap changer the protection must be connected
to a side without tap changer. The side with the tap changer can
withstand different voltages depending on the tap changer posi­
tion and is therefore not suitable for overexcitation protection.

3.3 DIFFERENTIAL PROTECTION FOR

RELAY PROTECTION

BA THS / BU Transmission Systems and Substations LEC Support Programme 169


AUTO-TRANSFORMERS

For auto-transformers a high impedance type of differential pro­


tection can be used. CT:s with the same ratio and no turn correc­
tion are then supplied at both high and low voltage side of the
transformer as well as in each phase of the neutral.

With this type of protection a higher sensitivity, 5-10% of rated


current, and a faster tripping (10-15ms) compared with the low
impedance type can be obtained.

Drawbacks with this type of protection can be:


- If the transformer is delivered separately, it can be difficult to ge
each phase, at the neutral side of the winding.

- Delta winding of the transformer has to be protected separately.

3.4 BACK-UP PROTECTION RELAYS

A transformer is always supplied with a number of back-up pro­


tection relays, e.g. back-up for short circuits or earth faults in the
low side system. These protection relays are definite or inverse
time delayed and connected to high- and low voltage side as well
as on the neutral side/sides for the earth fault functions.
They will provide system back-up rather than being back-up for
internal system faults, e. g. the short circuit protection on the HV
side of the transformer provides back-up to the short circuit pro­
tection on the outgoing feeders when these fails to clear the fault.
UN protection in the LV bay or a IN protection in the transformer
neutral will provide back-up protection for earth fault protection
relays on the outgoing feeders.

Monitoring on the transformer


The monitoring devices on the transformer are often the main
protection. They detect abnormal service conditions, which can
lead to a fault. They can also quickly detect internal faults e. g. the
Buchholz relay. Typical location of monitors is shown in fig. 4.

RELAY PROTECTION

170 BA THS / BU Transmission Systems and Substations LEC Support Programme


Transformer Protection

EXPANSION
ROOM

DRYER
ALARM TRIP

COMPENSATED
BUCHHOLZ THERMOMETER

TOP OIL DEVICE


ROOM
TOP OIL
THERMOMETER

Figure 4. Location of buchholz, top oil thermometer and winding tempera­


ture indication

Gas detector relay (Buchholz)


At a fault in an oil immersed transformer the arc will cause the oil
to decompose and gas will be released. The gas will pass
through the pipe between the main tank and the conservator and
can be detected by a gas detector relay.

The gas detector have an alarm unit collecting the gas, and one
unit for tripping responding to the high flow of gas at a serious in­
ternal fault.

The collected gas can be analyzed and give information about


what caused the gas.

It should be noted that the trip signal from the Buchholz some­
times can be very short at a serious internal fault due to that the
relay will be destroyed (blown away). Receiving of this signal in
the relay system therefore must have a seal-in feature to ensure
that a sufficient length of the tripping signal is given to the CB and
to indication relays.

RELAY PROTECTION

BA THS / BU Transmission Systems and Substations LEC Support Programme 171


Temperature monitoring
A too high temperature in a transformer can be caused by over­
loading or by problems in the cooling equipment. Overfluxing can
also cause a temperature raise.

Oil immersed transformers are supervised with thermometers.


These are included in the power transformer standard equip­
ment. There are two types to choose between, oil-, or winding
temperature measuring devices and both are normally supplied
on transformers bigger than a few MVA.

Both types are overloading sensors for the transformer. There is


normally one alarm and one trip level at each type of measuring
devices.

4. PROTECTION BLOCK DIAGRAM

The protection system for a typical HV/MV power transformer is


shown in figure 5. It should be noted the mix between protection
for internal transformer faults and the back-up protection provid­
ed for external faults mainly in the low voltage system.

PROTECTION BLOCK DIAGRAM

172 BA THS / BU Transmission Systems and Substations LEC Support Programme


Transformer Protection

Figure 5. A typical protection system for a HV/MV power transformer.

PROTECTION BLOCK DIAGRAM

BA THS / BU Transmission Systems and Substations LEC Support Programme 173


The protection system for a typical EHV/HV power transformer is
shown in figure 6. For such big system transformers a sub-divid­
ed protection system is normally required and provided. Further
back-up protection are often of impedance type to allow setting
matching the line protection on the outgoing lines.

Figure 6. A typical protection system for a EHV/HV system power


transformer.

PROTECTION BLOCK DIAGRAM

174 BA THS / BU Transmission Systems and Substations LEC Support Programme


Reactor Protection
1. NEED FOR SHUNT REACTORS

Shunt reactors are used in high voltage systems to compensate

for the capacitive generation of long overhead lines or extended

cable networks.

The reasons for using shunt reactors are mainly two. The first

reason is to limit the overvoltages and the second reason is to

limit the transfer of reactive power in the network.

If the reactive power transfer is minimized i. e. the reactive power

is balanced in the different part of the networks, a higher level of

active power can be transferred in the network.

Reactors to limit overvoltages are most needed in weak power

systems, i.e. when network short-circuit power is relatively low.

Voltage increase in a system due to the capacitive generation is:

Q C × 100

∆U ( % ) = -----------------------
S sh˙c
-

where “Qc” is the capacitive input of reactive power to the network


and “Ssh.c” is the short circuit power of the network.

With increasing short circuit power of the network the voltage in­
crease will be lower and the need of compensation to limit over­
voltages will be less accentuated.

Reactors to achieve reactive power balance in the different part


of the network are most needed in heavy loaded networks where
new lines cannot be built because of environmental reasons.
Reactors for this purpose mostly are thyristor controlled in order
to adapt fast to the reactive power required.

Especially in industrial areas with arc furnaces the reactive power


demand is fluctuating between each half cycle. In such applica­
tions there are usually combinations of thyristor controlled reac­
tors (TCR) and thyristor switched capacitor banks (TSC). These
together makes it possible to both absorb, and generate reactive
power according to the momentary demand.
NEED FOR SHUNT REACTORS

BA THS / BU Transmission Systems and Substations LEC Support Programme 175


Four leg reactors also can be used for extinction of the secondary
arc at single-phase reclosing in long transmission lines. Since
there always is a capacitive coupling between phases, this ca­
pacitance will give a current keeping the arc burning, a second­
ary arc. By adding one single-phase reactor in the neutral the
secondary arc can be extinguished and the single-phase auto-re­
closing successful.

2. CONNECTIONS IN THE SUBSTATION

The reactors can be connected to the busbar, a transformer ter­


tiary winding or directly to the line, with or without a circuit-break­
er (see figure 1).

Figure 1. Different locations of shunt reactors.

Tertiary connected reactors will have the lowest cost but extra
losses will be obtained in the transformer. The rated voltage of
the reactor must be taken into account as well as the large volt­
age drop at the power transformers.

A voltage drop in the tertiary, equal to the power transformer im­


pedance, will be obtained when the reactor is connected. Lets
assume that the transformer have an impedance voltage of 15%
and a rated voltage in the tertiary of 20 kV. Also assume that the

CONNECTIONS IN THE SUBSTATION

176 BA THS / BU Transmission Systems and Substations LEC Support Programme


Reactor Protection
auxiliary power to the station is taken from the tertiary through a
20/0.4 kV transformer.

When a reactor with rated power equal to the rated power of the
tertiary winding, is connected, the voltage in the tertiary will de­
crease to 0.85x20 = 17 kV. This will also mean that the auxiliary
power voltage will decrease with 15% and some kind of voltage
stabilization regulation is therefore necessary to keep the 0.4 kV
voltage level within required limits.

If the reactors are to be used for secondary arc extinction at sin­


gle-pole reclosing, they must be connected directly to the line.
This also have to be done if the reactors are supposed to keep
down the voltage at the open end of a long transmission line.

Busbar connected reactors can be used for voltage regulation


and reactive power balance.

Line Reactors can either be connected continuously together


with its line, or be connected to the network at low load condi­
tions.

3. SYNCHRONOUS SWITCHING OF SHUNT


REACTOR CIRCUIT-BREAKERS

Synchronized closing, and opening of shunt reactors CB:s, is


possible by using the Switchsync relay. This will give the closing
impulse at the correct instance to achieve pole closing at maxi-

SYNCHRONOUS SWITCHING OF SHUNT REACTOR CIR­

BA THS / BU Transmission Systems and Substations LEC Support Programme 177


mum phase voltages. Closing at voltage maximum gives the min­
imum possible disturbances in the network (see fig. 2).

Synch Man Close


close

Closing impulse
is sent.
+6.66 ms (50 Hz)
+3.33 ms (50 Hz)
CB closing time

L1 L2 L3

Figure 2. Synchronized closing of Shunt Reactor Circuit Breakers.

Shunt reactors CB:s should be closed at voltage maximum. CB:s


with Switchsync relay to control the closing instance don’t require
any pre-insertion resistors, which mean a less mechanical com­
plex CB, and of course, a less expensive CB.

Switchsync can also be equipped with an adaptive control which


automatically will adjust to changes in the CB:s operating time.

4.THYRISTOR (PHASE-ANGLE) CONTROLLED


REACTORS (TCR)

In order to get a continuous control of the reactive power and to


damp power swings in the network, thyristor controlled reactors

THYRISTOR (PHASE-ANGLE) CONTROLLED REACTORS

178 BA THS / BU Transmission Systems and Substations LEC Support Programme


Reactor Protection
can be installed. These can respond within only half a cycle delay
to the required amount of reactive power needed.

The current is controlled in such a way, that the firing pulses to


the thyristors are delayed so that they wont disturb the natural
zero crossings of the current. This regulating can be done contin­
uously and reactive power can therefor be steplessly adjusted to
the required value (see fig. 3).

Ir

Firing pulses

Figure 3. Voltage and current wave form and thyristor firing control.

This control is practically transient free but causes harmonics,


that have to be taken care of by harmonic filters. The harmonics
generated, are “n x f±1”, where “n” is an integer. The harmonics of
the lowest order are the largest and the level decrease with high­
er orders. Filters therefore normally only are needed for 5’th, and
7’th harmonics.

TCR reactors are always both connected to the network through


a power transformer, and delta connected (see fig. 4). The volt­
age level is chosen to get a current suitable for the rated currents
of the thyristors selected.

THYRISTOR (PHASE-ANGLE) CONTROLLED REACTORS

BA THS / BU Transmission Systems and Substations LEC Support Programme 179


5TH 7TH
Figure 4. Thyristor controlled reactors (TCR).

5. SINGLE, AND THREE-PHASE REACTORS

Three-phase reactors are manufactured for system voltages up


to 400 kV. At higher voltages the reactors usually are of sin­
gle-phase type and more or less necessary for the operation of
the system. Using single-phase units makes it easier with spares,
as only one single phase unit have to be kept in the substation.

Sizes can either be standardized by the customer or individually


optimized for each case.

6. RELAY PROTECTION FOR DIRECT


EARTHED SR:S

A differential relay, of high impedance type should be used as


main protection. CT:s should be specified at both the phase and
the neutral side of each phase and a three phase protection
should be used as a three phase protection gives a higher sensi­
tivity for internal faults.

SINGLE, AND THREE-PHASE REACTORS

180 BA THS / BU Transmission Systems and Substations LEC Support Programme


Reactor Protection

If the reactor has its own CB, the CT:s at the phase side could be
located together with the CB. If the reactor is connected without
CB a bushing CT:s should be used.

CT:s on the neutral side of the winding should be integrated in the


reactor (bushing CT:s). If it isn’t possible to get one CT at each
phase on the neutral side a common CT at the earth connection,
must be supplied. In this case a single-phase high impedance
protection should be supplied.

A three-phase overcurrent protection should be used as back-up


protection. Earth fault current is normally not supplied since the
residual current will be equal to the load current during internal,
as well as external faults. In addition to this the inrush current in
the neutral is both high and long lasting. This means that setting
of an included earth fault current protection would in principle be
the same as the overcurrent protection and any increase of the
sensitivity can not be obtained by earth fault current protection
and it is thus not required.

7. DESIGN OF HIGH IMPEDANCE DIFFEREN-


TIAL PROTECTION RADHA

7.1 RELAY SETTING

The general requirement on the function values of the high im­


pedance differential protection is that at maximum through fault
current for an external faults the relay wont maloperate even with
one CT fully saturated.

For a reactor the dimensioning criteria will be for the inrush cur­
rent, since a reactor only will give a through fault current equal to
rated current, at an external earth-fault.

DESIGN OF HIGH IMPEDANCE DIFFERENTIAL PROTEC­

BA THS / BU Transmission Systems and Substations LEC Support Programme 181


The maximum inrush current for a reactor is approximately two
times the rated current. If no specific requirement concerning at
what current the relay should be stable exists, five times the rated
current is used when operating voltage is selected.

This rather high value is set in order not to get problem at reactor
breaker openings. As the CB is chopping the current at opening,
a high frequency current (1-12 kHz) will oscillate between the re­
actor reactance and the circuits leakage capacitance. This oscil­
lating current could lead to maloperation of the Differential relay.
If there are maloperation problems at opening of the CB, the rem­
edy for this is to connect a capacitor in the relay circuit.

The function value of the relay should be chosen:

U function ≥ 5I n (R ct + 2R I )

where “In” is the reactors rated current at the secondary side of


the CT, “Rct” is CT secondary resistance at 75 °C and “Rl” is the
lead resistance, from the CT to the summation point. The princi­
pal connection for one phase is shown in fig. 5.

Figure 5. Connection principle for a high impedance differential protection.

In order to protect RADHA, from overvoltages at internal faults,


non-linear resistors are connected, in parallel with the relay, at
each phase (see fig. 5).

DESIGN OF HIGH IMPEDANCE DIFFERENTIAL PROTEC­

182 BA THS / BU Transmission Systems and Substations LEC Support Programme


Reactor Protection
7.2 CURRENT TRANSFORMER DESIGN

CT:s for High impedance type Differential protection must have a


saturation, or knee-point voltage, of at least twice the selected
operation value of the relay. CT:s must not be equipped with turn
correction since this could lead to maloperation of the protection.

If possible the CT:s on the phase and neutral side should be


made with similar magnetizing characteristic.

The ratio of the CT:s should be chosen corresponding to approx­


imately twice the rated current. This is done in order to not getting
too few secondary turns. Secondary rated currents should be se­
lected to 1 A, since the primary rated current usually is quite low,
and 5 A will give too few secondary turns.

DESIGN OF HIGH IMPEDANCE DIFFERENTIAL PROTEC­

BA THS / BU Transmission Systems and Substations LEC Support Programme 183


7.3 PRIMARY SENSITIVITY

Primary sensitivity of approximately 10-15% of the reactors rated


current normally can be obtained.

The primary sensitivity can be calculated as:

I p = n ( I r + I res + I m )

where

“Ip” is the protection primary operation current

“n” is the current transformer ratio

“Ir” is the current through the relay at function

“Ires” is the current through the voltage dependent resistor

“Im” is the sum of the magnetizing currents.

For this calculation the actual angles for the different currents

must be considered.

“Ir” angle is given in relay catalogues and for RADHA and RADHD

angle is +20-40 degrees depending on function value and fre­

quency.

“Ires” is purely resistive and have an angle of 0 degrees.

“Im” angle vary depending on applied voltage but -60 degrees is a

good approximation that can be used for this calculation.

DESIGN OF HIGH IMPEDANCE DIFFERENTIAL PROTEC­

184 BA THS / BU Transmission Systems and Substations LEC Support Programme


Capacitor Protection
1. GENERAL ABOUT CAPACITOR BANKS

Capacitor banks are normally used in medium voltage networks


to generate reactive power to industries etc. Capacitor banks are,
almost always, equipped with a series reactors to limit the inrush
current (see fig. 1).

INDUSTRIAL
LOAD

Figure 1. Capacitor banks with series reactors.

Harmonic filters, for thyristor controlled reactors, are also varia­

tions of capacitor banks having the reactor inductance together

with the capacitor capacitance tuned for series resonance at a

certain frequency. The tuning are purposely a little bit incorrect,

in order not to get a too low impedance for the harmonic, to which

it is tuned.

The capacitor banks usually are connected in double Y-connec­

tion with the neutral of the halves connected. The current be­

tween the two neutrals are supervised by an overcurrent

(unbalance) relay.

GENERAL ABOUT CAPACITOR BANKS

BA THS / BU Transmission Systems and Substations LEC Support Programme 185


2. CAPACITOR BANK PROTECTION

2.1 UNBALANCE RELAY

This overcurrent relay detects an asymmetry in the capacitor


bank caused by blown internal fuses, short-circuits across bush­
ings, or between capacitor units and the racks in which they are
mounted.

Each capacitor unit consist of a number of elements protected by


internal fuses. Faulty elements in a capacitor unit are disconnect­
ed by the internal fuses. This causes overvoltages across the
healthy capacitor units.

The capacitor units are designed to withstand 110% of the rated


voltage continuously. If this level is exceeded, or if the faulty units
capacitance have decreased below 5/6 of the nominal value, the
capacitor bank must be taken out of service.

In normal service when all capacitor units are healthy the unbal­
ance current is very small. With increasing number of blown inter­
nal fuses the unbalance current increases and the unbalance
relay will give an alarm. The alarm level is normally set to 50% of
the maximum permitted level. The capacitor bank then should be
taken out of service to replace the faulty units. If not the capacitor
bank will be tripped when the maximum allowed unbalance cur­
rent level is exceeded.

2.2 CAPACITOR BANK OVERLOAD RELAY

Capacitors of today have very small losses and are therefore not
subject to overload due to heating caused by overcurrent in the
circuit.

Overload of capacitors are today mainly caused by overvoltages.


It is the total peak voltage, the fundamental and the harmonic
voltages together, that can cause overload of the capacitors. The
capacitor can withstand 110% of rated voltage continuously. The

CAPACITOR BANK PROTECTION

186 BA THS / BU Transmission Systems and Substations LEC Support Programme


Capacitor Protection
capability curve then follows an inverse time characteristic where
withstand is approximately 1 second -180%, 10 cycles -210%.

Since the capacitors mostly are connected in series with a reac­


tor it is not possible to detect overload by measuring the busbar
voltage. This is because there is a voltage increase across the re­
actor and the harmonic currents causing overvoltages will not in­
fluence the busbar voltage.

ABB Transmit Oy have designed a relay that measures the cur­


rent in the capacitor bank and transforms this into a voltage that
corresponds to the voltage across the elements in the capacitor
bank.

This relay is called SPAJ 160C and includes unbalance protec­


tion, overload protection and undercurrent relay. The undercur­
rent function is used to prevent the charged capacitor bank to be
reconnected when a short loss of supply voltage occurs.

The connection of the relay is shown in fig. 2.

Figure 2. A SPAJ 160 connected to a capacitor bank.

CAPACITOR BANK PROTECTION

BA THS / BU Transmission Systems and Substations LEC Support Programme 187


2.3 SHORT-CIRCUIT PROTECTION

In addition to the relay functions described above the capacitor


banks needs to be protected against short circuits and earth
faults. This is done with an ordinary two- or three-phase short cir­
cuit protection combined with an earth overcurrent relay.

CAPACITOR BANK PROTECTION

188 BA THS / BU Transmission Systems and Substations LEC Support Programme


Bus&Breaker Protection
1. GENERAL ABOUT BUSBAR PROTECTION

A Busbar protection is a protection to protect Busbars at


short-circuits and earth-faults. In the “childhood” of electricity no
separate protection was used for the busbars. Nearby line protec­
tion were used as back-up for busbar protection.

With increasing short-circuit power in the network separate bus­


bar protections have to be installed to limit the damage at primary
faults. A delayed tripping for busbar faults can also lead to insta­
bility in nearby generators and total system collapse.

1.1 BUSBAR PROTECTION - REQUIREMENTS

Following requirements must be fulfilled. The Busbar protection:


- Must have as short tripping time as possible.

- Must be able to detect internal faults.


- Must be absolutely stable at external faults. External faults are much
more common than internal faults. The magnitude of external faults can
be equal to the stations maximum breaking capacity, while the function
currents can go down to approximately 2% of the same. The stability
factor therefor needs to be at least 50 times i. e. 20. CT-saturation at ex­
ternal faults must not lead to maloperation of the busbar protection.
- Must be able to detect and trip only the faulty part of the busbar system.
- Must be secure against maloperation due to auxiliary contact failure, hu­
man mistakes and faults in the secondary circuits etc.

1.2 TYPES OF BUSBAR PROTECTION

The busbar protections are mostly of differential type measuring


the sum of current to all objects connected to the busbar, Kirch­
hoffs law.

GENERAL ABOUT BUSBAR PROTECTION

BA THS / BU Transmission Systems and Substations LEC Support Programme 189


Differential type of busbar protections can be divided into three
different groups:
- low impedance.
- medium impedance.
- high impedance.

For metal enclosed distribution busbars, arc detectors also can


be used as busbar protection. For systems that are only radial fed
blockable overcurrent relays in the incoming bays can be used as
busbar protection.

2. PRINCIPLES OF DIFFERENTIAL BUSBAR


CONFIGURATIONS

The simplest form of busbar protection is a 1-zone protection for

single busbar configuration, see fig. 1. If the main CT:s have

equal ratio auxiliary CT:s are not necessary.

If the busbar protection is of the high impedance type the main

CT:s must have the same ratio and auxiliary CT:s may then not

be used. Separate CT-core/s must also be supplied for the bus­

bar protection.

Other protection relays must be connected to other CT-cores.

PRINCIPLES OF DIFFERENTIAL BUSBAR CONFIGURA­

190 BA THS / BU Transmission Systems and Substations LEC Support Programme


Bus&Breaker Protection
For single busbar arrangement no switching is done in the CT-cir­
cuits and a check zone is therefore not necessary.

Figure 1. A one zone differential relay for a single busbar.

At 1 1/2-breakers system arrangements a 2-zone protection must


be used se fig. 2.

PRINCIPLES OF DIFFERENTIAL BUSBAR CONFIGURA­

BA THS / BU Transmission Systems and Substations LEC Support Programme 191


If the main CT:s have equal ratio, which is normally the case, aux­
iliary CT:s are not necessary.

Figure 2. A two-zone busbar differential relay for 1 1/2-breaker switchgear

At double busbar switchgear a 2-zone protection shall be used,


see fig. 3. If the main CT:s have equal ratio auxiliary CT:s are not
necessary.

CT-circuits are switched depending on the position of the busbar


disconnectors. The current is either connected to busbar A or
busbar B:s differential protection. Switching is easiest performed
by using repeat relays (RXMVB 2), controlled via two auxiliary
contacts at each busbar disconnector, see fig. 5.

PRINCIPLES OF DIFFERENTIAL BUSBAR CONFIGURA­

192 BA THS / BU Transmission Systems and Substations LEC Support Programme


Bus&Breaker Protection

Figure 3. 2-zone busbar differential protection, for double busbar switchgear.

Many cases when switching in CT-circuit is done requires a check


zone for the busbar protection, see fig. 4. The check zone is
fixed and has no switching of CT:s in all outgoing circuits and is
not connected at busbar sections and busbar couplers. Check
zone, will detect faults anywhere in the substation but can not dis­
tinguish in what part of the substation the fault is located. When
the check zone detects a fault it gives a release signal to the bus­
bar protection relays in all individual, discriminating zones. The
busbar protection discriminating zones will then trip the part of
the substation that is faulty.

The releasing when the check zone detects a fault is normally


done by sending out positive DC-voltage to the discriminating
zones. Another way to do the releasing is to connect the negative
DC-voltage to all trip relays from the check zone and to connect
the positive DC-voltage from the discriminating zones.

PRINCIPLES OF DIFFERENTIAL BUSBAR CONFIGURA­

BA THS / BU Transmission Systems and Substations LEC Support Programme 193


Figure 4. 2-zone busbar differential protection, for double busbar switchgear
(including check zone), releasing the main zones for busbar A and B.

3. SWITCHING IN CURRENT CIRCUITS

For busbar systems, where the object can be connected to more


than one busbar, double busbar systems, the current must be
switched to the correct zone busbar protection. This switching
must be done in such a way that no differential current develops
in any of the busbar protections concerned. The switching is done
by using two auxiliary contacts on the busbar disconnectors.
These auxiliary contact are energizing throw-over relays (RXM-
VB 2) which perform the switching in the CT-circuits. The discon­
nectors auxiliary contacts must be provided as in fig. 5.

Following requirements must be fulfilled by the auxiliary contacts


“a” and “b” respectively:

SWITCHING IN CURRENT CIRCUITS

194 BA THS / BU Transmission Systems and Substations LEC Support Programme


Bus&Breaker Protection

- The auxiliary contact


a” must “

close minimum 100 ms before the main conta


can start to carry current.

- The auxiliary contact “b” must open before the auxiliary contact “a” clos­
es.
- The auxiliary contact “b” must not close before full insulation is secured
(normally at 80% of the full insulation distance).

Figure 5. Requirements and connection of busbar disconnector auxiliary


contacts, for switching of RXMVB 2 repeat relays.

4. PROTECTION OF MV BUSBARS IN DISTRI-


BUTION NETWORKS

For busbars in distribution networks Busbar protection can be


achieved mainly in two different ways, either by blockable over­
current protection at the incoming bays to the switchgear, or by
locating arc detectors inside the enclosure.

Blockable overcurrent protection is based upon the principle that


fault current is only fed by the incoming to the busbar. The incom­
ing circuit is equipped with an overcurrent relay that have a fast
step definite time-delay of approximately 100 ms (this step is

PROTECTION OF MV BUSBARS IN DISTRIBUTION NET­

BA THS / BU Transmission Systems and Substations LEC Support Programme 195


blocked if any of the overcurrent relays in the outgoing circuits

starts, se fig. 6.

For metal enclosed busbars, arc detectors can be used as busbar

protection. The arc at a primary fault is detected by a arc sensitive

device, which trips all incoming circuit breakers. In order not to

risk maloperation due to photographic flashes etc., it’s advisable

to also have an overcurrent interlock.

3I>
100 ms
BLOCK &

TRIP

START
START

START
START

3I> 3I> 3I> 3I>

Figure 6. Blockable Overcurrent protection.

5. APPLICATION OF BUSBAR PROTECTION

Figure 7 gives a survey of different type of busbar protectio

Figure 7. Application of different types of busbar protection relays

APPLICATION OF BUSBAR PROTECTION

196 BA THS / BU Transmission Systems and Substations LEC Support Programme


Bus&Breaker Protection
For busbars in distribution networks the protection can be
achieved mainly in two different ways. One way is by blockable
overcurrent protection at the incoming bays to the switchgear an­
other way is by locating arc detectors inside the enclosure.

High impedance protection needs separate CT-cores with equal


ratio at each feeder, bus-coupler and bus-section. This means
that other protection relays cannot be connected to the same
CT-core. This type of busbar protection is mainly for medium volt­
age levels.

RADSC is a new type of low impedance busbar protection that


can be used as an alternative to high impedance protection re­
lays. It has a maximum of 6 inputs and can therefore not be used
in larger substations. It can however use the same CT-cores as
other protection relays but requires auxiliary CT:s if the main
CT:s in the different bays have different ratio.

Summation type of busbar protection can be used for more eco­


nomical variants of protection. The Summation type Busbar pro­
tection relays has only one measuring unit which means that
there is no internal back-up for 2-phase and 3-phase faults. Pri­
mary operating current varies with a factor 4 depending on in
which phase the fault occurs. Phase indication cannot be ob­
tained.

RADSS and REB 103 are medium impedance type of busbar


protection relays, during internal faults, but low impedance pro­
tection during load and external faults. RADSS and REB 103 can
therefor be used together with other types of object protection on
the same cores. This kind of protection is intended for high (HV)
and extra high voltage (EHV) levels.

RADSS can be used without auxiliary CT:s if the main CT:s have
equal ratio. This gives a solution that is both economical and
saves space. The only restraint is that the maximum circulating
current through RADSS, power transferred through the zone,
must not exceed 4 A secondary. This could be a problem if the

APPLICATION OF BUSBAR PROTECTION

BA THS / BU Transmission Systems and Substations LEC Support Programme 197


main CT:s both have 5 A secondary but can be overcome by in­
creasing the primary ratio of the main CT:s.

When main CT:s have different ratio REB 103 gives a more eco­
nomic solution since REB 103 is designed with auxiliary CT:s of
small physical sizes. REB 103 cannot be used without auxiliary
CT:s.

INX 5 is a low impedance busbar protection for high (HV), and ex­
tra high voltage (EHV) levels.

REB 500 is a new decentralized, or centralized, numerical Bus­


bar protection relay with a process bus connecting the different
bays. The relay is mainly intended for the HV and EHV voltages.

6. BREAKER FAILURE RELAYS

In order to take care of possible breaker failure, Circuit Breaker


Failure relays normally are installed in high voltage, and extra
high voltage systems.

All protection tripping (not manual opening) will start a current re­
lay measuring the current through the CB. If the current has not
disappeared within the set time, all adjacent CB:s will be tripped
to clear the fault.

BREAKER FAILURE RELAYS

198 BA THS / BU Transmission Systems and Substations LEC Support Programme


Bus&Breaker Protection
The time “split up” at a normal tripping and a breaker failure trip­
ping is shown in fig. 8.
Fault
occurs

Normal clearing time

Normal
clearing
Protection Breaker inter­
time rupting time Margin

Back-up breaker
Breaker failure timer interrupting time
Breaker
failure
tripping
Failed
breaker

Breaker failure total clering time

Figure 8. Time scheme for breaker failure relays

In normal cases the total fault clearing time will be the protection
relay operating time plus the CB interrupting time. Every time a
relay gives a trip order it will at the same time start the Circuit
Breaker Failure (CBF) relay. The CBF-timer will be running as
long as the current is flowing through the CB. When the CB inter­
rupts the current the CBF-current relay will reset and the
CBF-timer will stop.

BREAKER FAILURE RELAYS

BA THS / BU Transmission Systems and Substations LEC Support Programme 199


The setting of the CBF-timer must be:
maximum interrupting time of the ordinary CB, plus the reset time
of the CBF-current relay, plus the impulse margin time of the
CBF-timer, plus a margin.

With “impulse margin time” is meant the difference between set


time and the time “to no return”. If the timer is set to 100 ms and
is fed during, lets say 98 ms, it will continue to operate since the
margin between the set time and the actual time is small. The
margin should be chosen to at least 50-60 ms to minimize the risk
of unnecessary tripping, specially considering the heavy impact
on the network a CBF tripping will cause.

7. POLE DISCORDANCE RELAYS

For circuit breakers with one operating device per pole, it is nec­
essary to supervise that all three phases have the same position.

This is normally done by using the auxiliary contacts on the circuit


breaker according to figure 9.

Figure 9. Connection of a Pole Discordance relay.

POLE DISCORDANCE RELAYS

200 BA THS / BU Transmission Systems and Substations LEC Support Programme


Bus&Breaker Protection
Pole discordance relay “PD” is necessary to prevent service with

only one or two phases of a circuit breaker closed. This will cause

an unsymmetry that can lead to damage of other apparatus in the

network. Unsymmetrical conditions can only be accepted during

a single pole Auto reclosing cycle.

When single pole Auto reclosing is used a blocking of the PD is

necessary during the single phase dead time, see figure 9.

The timing sequence at closing and opening of breakers and the

timing of the operation at a pole discrepancy tripping must be

checked carefully. It is e. g. often necessary to operate the flag

relay first and the tripping from this relay to achieve correct indi­

cation at a trip as the main contacts will rather fast take away the

actuating quantity when the remaining poles are opened.

Tripping from PD should be routed to other trip coil than the one

used by manual opening. This is due to the fact that at manual

opening there could be an incipient fault in the circuit. This incip­

ient fault could result in that only one or two phases operate and

the MCB for the circuit is tripped. PD would thus not be able to

operate if connected to the same coil as manual opening.

Operation of PD shall in addition to tripping the own circuit break­

er start Circuit Breaker failure relay, lock-out the own circuit

breaker and give an alarm.

A normal time delay for a PD relay should be approximately

150-200 ms when blocking during single pole Auto reclose is per­

formed. If not the necessary time is about 1,2 sec.

Note: Some customers do not rely only on the auxiliary contacts

and want to detect Pole discordance also by measuring the resid­

ual current through the breaker at breaker for some second at

opening and closing.

We have however good experience of the contact based principle

and recommend only this simple principle.

Residual current measurement at closing and opening is not a re­

liable function either as there is no load current when a line is

closed from one end only and on the other hand normal residual

POLE DISCORDANCE RELAYS

BA THS / BU Transmission Systems and Substations LEC Support Programme 201


currents can occur if the closing is onto a fault or e. g. energizes
a transformer at the far end of the system.

Conclusion is to use a simple contact based Pole Discordance


function which is simple and reliable. The residual current based
principle is more complicated and can give difficulties in setting
of sensitivity etc.

POLE DISCORDANCE RELAYS

202 BA THS / BU Transmission Systems and Substations LEC Support Programme


Earth Fault Protection
1. INTRODUCTION

The fault statistic shows that earth faults are the dominating fault
type and therefor the earth fault protection is of main importance
in a network.

The type of earth fault protection used is dependent of the sys­


tem earthing principle used. In the following the earth fault pro­
tection for solidly- (effectively), reactance-, high resistive- and
resonance earthed systems are covered.

2. EFFECTIVELY EARTHED SYSTEMS

In the effectively earthed systems all transformers are normally


connected to earth and will thus feed earth fault current to the
fault. The contribution from all earthing locations gives special re­
quirements for the protection system.

2.1 FAULT RESISTANCE AND FAULT


CURRENT LEVELS

In order to calculate fault currents in an effectively earthed sys­


tem we must use the representation with symmetrical compo­
nents.

The symmetrical component scheme for a 132 kV system with a


fault according to Figure 1 is shown in Figure 2.

INTRODUCTION

BA THS / BU Transmission Systems and Substations LEC Support Programme 203


.

Figure 1. An earth fault in a direct, effectively earthed system.

Positive sequence

Uh/√3

3Rf
Negative sequence

U0 Zero sequence U0

I01 I02

Figure 2. The symmetrical components are used to calculate the “I0” current
for the fault in figure 1, “3I0” is the total fault current.
The distribution of fault currents, from the different system earth­
ing points, can be derived from the distribution in the zero se­
quence network (see figure 2). By inserting varying fault
resistances one can get the fault current level.

EFFECTIVELY EARTHED SYSTEMS

204 BA THS / BU Transmission Systems and Substations LEC Support Programme


Earth Fault Protection
The fault resistance “Rf ”, consists of the arc resistance and the
tower foot resistance. The arc resistance is calculated by the for­
mula:
Rarc = 28700a / If1.4 (according to Warrington)

where “a”, is the arc length in meter, normally the insulator length,
and “If ” is the fault current in “A”.

A calculation will show that values will differs from below 1 Ω for
heavy faults, up to 50-400 Ω for high resistive earth faults.

The tower foot resistance depends on the earthing effectiveness


of the towers, whether top lines are used etc. For the tower foot
resistance values from below 10 Ω up to 50 Ω have been docu­
mented.

2.2 NEUTRAL POINT VOLTAGES

The occurring neutral point voltage, at different locations, can be


seen in figure 2. The designate “U0”, represents the neutral point
voltage (3U0 = UN). It’s to be noted that “U0” is generated by the
earth fault current “I0” through the zero sequence source. This im­
plies that the angle between “U0” and “I0” is always equal to the
zero sequence source angle, independent of the fault resistance
and the angle between the faulty phase voltage and the line cur­
rent in the faulty phase.

It must also be noted that “UN” will be very low when sensitive
earth fault relays are used in a strong network with low zero se­
quence source impedances.

As an example we can use the 132kV network according to figure


1 and 2. With an “IN” setting of 120A, the “I0” is 40A and with a
zero sequence source impedance of say 20 Ω, the zero se­
quence voltage component “U0” will be 40x10 = 400V and “3U0”
will then be 1200V. This will, with an open delta winding with 110V

EFFECTIVELY EARTHED SYSTEMS

BA THS / BU Transmission Systems and Substations LEC Support Programme 205


secondary, mean a percentage voltage of 1.6%, i.e. the polariz­
ing sensitivity of directional earth fault relays must be high.

In an open delta secondary circuit there is a voltage also during


normal service due to unbalances in the network. The voltage is
mainly of third harmonic and of size 0,2-0,5% with conventional
VT:s and 1-3% together with CVT:s.

This means that the sensitive directional earth fault protection


must be provided with a third harmonic filter when used together
with CVT:s. The filtering must be quite heavy to ensure correct di­
rectional measuring for 1% fundamental content also with third
harmonic contents of say 3%.

2.3 RESTRICTED EARTH FAULT PROTECTION


(REF).

For solidly earthed systems a restricted earth fault protection is


often provided as a complement to the normal transformer differ­
ential relay. The advantage with the restricted earth fault relays is
their high sensitivity. Sensitivities of 2-8% can be achieved. The
level is dependent of the current transformers magnetizing cur­
rents whereas the normal differential relay will have sensitivities
of 20-40%.

Restricted earth fault relays are also very quick due to the simple
measuring principle and the measurement of one winding only.
The differential relay requires percentage through fault and sec­
ond harmonic inrush stabilization which always will limit the min­
imum operating time.

EFFECTIVELY EARTHED SYSTEMS

206 BA THS / BU Transmission Systems and Substations LEC Support Programme


Earth Fault Protection
The connection of a restricted earth fault relay is shown in Figure
3. It is connected across each transformer winding in the figure.

Id

Id

To Diff
protection

Figure 3. A restricted earth fault relay for an YNdyn transformer.

It is quite common to connect the Restricted earth fault relay in


the same current circuit as the transformer differential relay. This
will due to the differences in measuring principle limit the differ­
ential relays possibility to detect earth faults. Such faults are de­
tected by the REF. The mixed connection is shown in the low
voltage winding of the transformer, see figure 3.

EFFECTIVELY EARTHED SYSTEMS

BA THS / BU Transmission Systems and Substations LEC Support Programme 207


The common principle for Restricted earth fault relays is the high
impedance principle, see figure 4.
IF

e1 e2

Rct RL RL Rct
Is
Xm1 UR Z=>0 Xm2
at sat.

Secondary current and voltage with


no voltage limiter.

Figure 4. The high impedance principle.

The relay provides a high impedance to the current. The current

will, for through loads and through faults, circulate in the current

transformer circuits, not go through the relay.

For a through fault one current transformer might saturate when

the other still will feed current. For such a case a voltage can be

achieved across the relay. The calculations are made with the

worst situations in mind and an operating voltage “UR” is calcu­

lated:

U R ≥ I Fmax (R ct + R I )

where

“IFmax” is the maximum through fault current at the secondary

side,

“Rct” is the current transformer secondary resistance and

“Rl” is the loop resistance of the circuit.

EFFECTIVELY EARTHED SYSTEMS

208 BA THS / BU Transmission Systems and Substations LEC Support Programme


Earth Fault Protection
The maximum operating voltage have to be calculated (both neu­
tral loop and phase loop must be checked) and the relay set high­
er than the highest achieved value.

For an internal fault the circulation is not possible and due to the
high impedance the current transformers will immediately satu­
rate and a rms voltage with the size of current transformer satu­
ration voltage will be achieved across the relay. Due to the fast
saturation very high top voltages can be achieved. To prevent the
risk of flashover in the circuit, a voltage limiter must be included.
The voltage limiter can be either of type surge arrester or voltage
dependent resistor.

The relay sensitivity is decided by the total current in the circuit


according to the formula:

I p ≥ n ( I R + I res + ΣI mag )

where “n” is the CT ratio, “IR” is the current through the relay, “Ires”
is the current through the voltage limiter and “∑Imag” is the sum of
the magnetizing currents from all CT’s in the circuit (normally 4).

It should be remembered that the vectorial sum of the currents


must be used. The current measurement have to be DC insensi­
tive to allow a use of AC components of the fault current in the
calculations.

2.4 LOGARITMIC INVERSE RELAY

Detection of earth fault and back-up tripping with maintained se­


lectivity in a solidly (effectively) earthed system is rather compli­
cated due to the infeed of fault current from different direction
concerning all faults. A special inverse characteristic with a log­
aritmic curve has been developed to be suitable for these appli­
cations. The principle for earth fault relays in a effectively earthed
system is shown in figure 5 and the logaritmic inverse character­
istic is shown in figure 6. The inverse characteristic is selected so

EFFECTIVELY EARTHED SYSTEMS

BA THS / BU Transmission Systems and Substations LEC Support Programme 209


that if the current of the largest infeed is less than 80% of the
faulty objects current selectivity is achieved.

I I

I I

Figure 5. Earth fault protection in a solidly earthed system.

Figure 6. The logaritmic inverse characteristic. A fault current of the biggest


infeed less than 0,8 times the current of the faulty object, gives a selective
tripping.

EFFECTIVELY EARTHED SYSTEMS

210 BA THS / BU Transmission Systems and Substations LEC Support Programme


Earth Fault Protection
To enable use together with Distance protection giving sin­
gle-phase tripping a definite minimum time is set (normally 0.3
sec.). This ensures that a single phase tripping for heavy single
phase faults can be done by distance protection relay first.

2.5 DIRECTIONAL COMPARISON SCHEMES.

To provide detection of high resistance earth faults in an effec­


tively earthed network it’s common to use a directional compari­
son scheme with directional earth fault relays at both ends of the
power line. The relays at the two ends are directed towards each
other and a communication between the relays, through a power
line carrier (PLC) or a radio link, is introduced.

Principle for communication schemes


Communication can be made according to two main principles:
- permissive scheme
- blocking scheme

In a permissive scheme the Directional earth fault relays will


send a signal (CS) to the remote end at detection of a forward
fault. At reception of a signal and detection of a forward fault at
the receiving end, an instantaneous trip is given. Normally the
same situation occurs at both ends. A permissive scheme princi­
ple is shown in Figure 7.
Forward dir
3I0

Block input 50 ms
&
t T0=0-150 ms Trip
BL3
& TR POR
Carrier rec
CR2 50 ms
t Carrier send
≥1 CSEF

Figure 7. A permissive overreaching scheme (POR) with directional earth


fault relays.

In a blocking scheme the directional earth fault relays are pro­


vided with a reverse locking element as a complement to the for­
ward element. The reversed element is set to be more sensitive

EFFECTIVELY EARTHED SYSTEMS

BA THS / BU Transmission Systems and Substations LEC Support Programme 211


than the forward element and will, when a reverse fault is detect­
ed, send a signal (CS), to the remote end. At the remote end the
forward element is provided with a short time delay “T0” normally
set to 50-150 ms, to check if a blocking signal is received. If not,
the relay will trip. The same situation will for internal faults occur
at both line ends. The principle of a blocking scheme is shown in
Figure 8.
Forward dir
T0=0-150 ms Trip
3I0
& TR BL

Carrier rec
CR2

Reverse dir
3I0 Carrier send
& CSEF
Block input 50 ms
t
BL3

Figure 8. A blocking scheme with directional earth fault relays.

In most cases the Directional earth fault relays in a communica­


tion scheme also includes a communication independent
back-up tripping with a time delay. Inverse or definite time delay
can be used. Normally the inverse characteristic and the logarit­
mic inverse characteristic gives the best possibility to achieve
time selectivity also at back-up tripping.

Single phase tripping.


When Distance protection relays with single phase tripping and
auto reclosing are used at the same line as a scheme with earth
fault relays it must be ensured that the Distance protection relays
are allowed to give their single-phase tripping first. Earth fault re­
lays must therefor be time delayed to allow this. This is also valid
when communication schemes are used. A blocking of the earth
fault scheme at distance protection operation is often used to en­
able use of short time delays in the communicating earth fault re­
lays.

During a single phase trip an unbalance in the complete network


occurs and an earth fault currents flows through the network.

EFFECTIVELY EARTHED SYSTEMS

212 BA THS / BU Transmission Systems and Substations LEC Support Programme


Earth Fault Protection
These currents reaches levels up to 20% of the load current and
an unnecessary tripping from earth fault relays can therefor be
achieved. The earth fault relays are normally blocked during the
single phase auto reclose cycle.

Current reversal
A special application problem occurs together with directional
earth fault schemes communicating in a POR scheme. The prob­
lem is fault current reversal which occurs when the CB at one end
of the faulty line trips before the breaker at the other end. The fault
current changes direction in the parallel line and a timing problem
to prevent maloperation at the end with a CS signal receipt at the
original fault occurring will occur (see figure 9). A special logic ac­
cording to Figure 10 is required to prevent a unneccesary func­
tion.

Trip 80 ms Trip 65 ms

Trip can be
given at Cur rev

Forw 25-80ms
Rev 80-100ms

Rev 25-80ms
Forw 80-100ms
Figure 9. The current reversal problem at parallel lines.
Carrier rec T0=0-150 ms Trip
CR2
TR POR
Forward dir &
3I0 50 ms
& t Carrier send
Block input 50 ms
BL3
t
70 ms & ≥1 CSEF
Reverse dir 20 ms & t
3I0 & t

EFFECTIVELY EARTHED SYSTEMS

BA THS / BU Transmission Systems and Substations LEC Support Programme 213


Figure 10. A logic in directional earth fault relays, to prevent unnecessary
operation during current reversal.

Weak-end infeed
In special applications, a situation where the fault current infeed
from one end isn’t ensured during certain service conditions.
A special weak end infeed logic can be used together with POR
schemes. It is based on occurring zero sequence voltage and the
receipt of a carrier signal CS from the remote (strong) end. The
logic for an earth fault weak-end infeed function includes a check
of occurring UN voltage at carrier receipt and the breaker is
tripped even if no operation of DEF relay is achieved due to a to
weak source. It is also necessary to “mirror” the Carrier signal
back so the signal is sent back on receipt if the UN voltage is low,
or if the circuit breaker is open.

2.6 INRUSH CURRENT STABILIZATION

In some countries a second harmonic stabilization is required for


sensitive earth fault relays. The background to this is that the in­
rush currents occurring at transformer energizing which, in some
networks has long durations. The long durations are often
achieved in weak networks. The second harmonic stabilization
can then block the earth fault relay, during the inrush and prevent
the risk of an unnecessary operation.

It should be noted that a POR communication scheme can not


operate for inrush currents as only one end will have conditions
fulfilled whereas the other end has a blocking condition.

For inverse time delayed scheme a time setting is selected to


achieve selectivity to instantaneous protection. This gives a long
delay compared to normal inrush times and the inverse charac­
teristic will then match the decay of the inrush current and keep
the relay away from unwanted functions.

The only time when a stabilization is necessary is when very sen­


sitive definite time delayed relays are used. In such cases the in­
rush can cross the corner with minimum current before the time
elapses and an unwanted function can occur.

EFFECTIVELY EARTHED SYSTEMS

214 BA THS / BU Transmission Systems and Substations LEC Support Programme


Earth Fault Protection

3. REACTANCE EARTHED SYSTEMS

The earth fault protection in a reactance earthed system is made


with a simple design as the generation of fault current comes
from the source side of the network only. The earthing is made at
the feeding transformer or at the busbar through a Z-0 earthing
transformer.

3.1 Z-0 EARTHING TRANSFORMER.

The earthing transformer is selected to give an earth fault current


with a well defined level. Normally the selected current is 750 to
1500A. The Z-0 (zig zag) transformer principle is shown in Figure
11.

I0
I0

3I0
I0

3I0 I

Figure 11. The principle of a Zig-zag transformer providing earth fault cur­
rent in a reactance earthed system.

REACTANCE EARTHED SYSTEMS

BA THS / BU Transmission Systems and Substations LEC Support Programme 215


The reactance is selected to give the fault current. It must be re­
member that the zero sequence reactance in Ω/phase is three
times the reactance calculated by the formula:
Un
3I0 i. e. I N = 1000A = -------------------­
3 × ZN

respectively
Un
------------------ = Z N
3 × IN

This means that, for a 20kV system with a 1000A earthing the Z-0
transformer shall be selected with a zero sequence reactance.

20
X0 = ------- 1000 = 11.6 ⇒ Select 35Ω ⁄ phase
3
A Z-0 transformer can often be provided with an auxiliary power
supply winding with a 400V secondary. This is possible up to 800
-1000kVA and the protection system have to be checked so that
the proper fault protection of the low voltage side of the auxiliary
transformer is achieved. One solution is to use delta connected
short circuit protection at the HV side (Z-0 winding).

Fuses and breakers placed at the HV side of a Z-0 transformer


should be avoided as the network earthing then can be discon­
nected and the risk of earth fault trips disappears. It will also in­
volve a risk of arcing faults and of ferro resonance in the voltage
transformers.

3.2 FAULT RESISTANCE AND FAULT CURRENT


LEVELS

In a reactance earthed system the current still is quite high. The

fault resistance will therefor decrease and a beginning fault will,

rather quickly, develop into a fault situation.

The fault current level will be quite independent of the fault posi­

tion. If a reactance earthing with 1000 A is used in a 20 kV sys­

tem, the apparent neutral reactance will be 12 Ω. This means that

a reactance to the fault, through a line of 12 Ω, will make the fault

REACTANCE EARTHED SYSTEMS

216 BA THS / BU Transmission Systems and Substations LEC Support Programme


Earth Fault Protection
current level half (12 Ω will be the reactance of a 30k m line in a
50 Hz system).

If a fault resistance is introduced the resistance will add vectorial


to the reactance and the current will change slowly with the fault
resistance.

3.3 NEUTRAL POINT VOLTAGES.

The neutral point voltage is calculated in the same way as the


source impedance (i.e. Zn (1/3Z0)xIf). This means that for a fully
developed earth fault full neutral displacement occurs and a fault
current of 20% e.g. 200 A in a 1000 A earthed system will be
20% of “Un”.

3.4 RESTRICTED EARTH FAULT PROTECTION.

A Restricted earth fault protection REF can not be justified in a


reactance earthed system in the same way as in a directly (effec­
tively) earthed system. This is because the fault current is much
lower and by that also the occurring damage which is dependent
of the “I2t” condition.

REACTANCE EARTHED SYSTEMS

BA THS / BU Transmission Systems and Substations LEC Support Programme 217


However in many countries REF protection relays are specified
also in reactance earthed systems the connection of a REF relay
is shown in Figure 12.

Id

Id

To Diff
protection

Figure 12. A Restricted earth fault relay in a reactance earthed system with
a Z-0 transformer.

The application is fully possible but it must be ensured that a high


sensitivity is achieved. Operation values of 5-10% of the maxi­
mum earth fault current generated is required.

When the operating voltage of the REF is calculated the check of


required operating value must be done by first checking the earth
fault loops for phase CT:s and neutral CT:s. However, as the
maximum through fault current is limited by the reactance a
check of the occurring loop at phase faults must be performed.
The unbalanced voltage is caused by one phase CT which is sat­
urated and the other is not. This can be caused by, for example,
the DC components at fault current which is not equal between
the phases. This check will often set the required operating volt­
age as the fault current at phase faults is much higher. It is advan­
tageous to summate the three CT:s as close to the current
transformers as possible. This can sometimes be difficult be­
cause of the transformer differential relay and its interposing CT’s
are located in the same circuit.

REACTANCE EARTHED SYSTEMS

218 BA THS / BU Transmission Systems and Substations LEC Support Programme


Earth Fault Protection
3.5 EARTH FAULT PROTECTION.

The earth fault protection in a reactance earthed system is nor­


mally provided with time delayed simple and undirectional earth
fault current measuring relays.

Time grading of the protection, furthest out in the system to the


protection in the neutral of the zig-zag transformer is used. The
time delay can be with normal inverse, or definite time delay. A
solution with inverse time delayed relay is shown in figure 13.

I0
I0

3I0
I0

3I0 I

Figure 13. An earth fault protection system for a reactance earthed network
where selectivity is achieved by inverse time delayed relays.

REACTANCE EARTHED SYSTEMS

BA THS / BU Transmission Systems and Substations LEC Support Programme 219


4. HIGH RESISTANCE EARTHED SYSTEMS

4.1 PRINCIPLE

The high resistance earthed networks are earthed at the source


side of the network only. Normally the earthing is restricted to one
point only and an arrangement is provided to allow varying con­
nection possibilities of the earthing point due to the service con­
ditions (see figure 14).

Open

A disconnector arr
allows separated
service. When BS is
closed only one
resistor is connected

Figure 14. A high resistance earthed network and a selection of service


conditions with disconnectors.

4.2 FAULT RESISTANCE AND FAULT CURRENT


LEVELS.

The earthing resistor is mostly set to give an earth fault current of


5-15A. The trend to decrease the current level gives lower re­
quirement of earthing grid and higher neutral point voltages at
high resistive earth faults.

HIGH RESISTANCE EARTHED SYSTEMS

220 BA THS / BU Transmission Systems and Substations LEC Support Programme


Earth Fault Protection

Due to the low current magnitude, high resistance earth faults will
not quickly develop to lower resistance so a high fault resistance
need to be detected. In Sweden a fault resistance of 5000 Ω must
be detected for some types of overhead lines. In order to detect
such high values it is often necessary to use a resonance earth­
ing in order to achieve reasonable high neutral point voltages.
(>5V at 5000 Ω).

Due to the high sensitivity required it’s required to use cable cur­
rent transformers surrounding the three phases to do the mea­
suring. The current transformer is then selected with a suitable
ratio independent of load current and no current will flow during
normal services. A sensitivity down to 1-2A primary is required at
high resistance earthed systems.

4.3 NEUTRAL POINT VOLTAGES.

In order to detect high values of fault resistance up to 5000 Ω“it’s


often necessary to use a resonance earthing to achieve accept­
able high neutral point voltages (>5V at 5000Ω). The neutral point
voltage is required to give the directional criteria for the direction­
al earth fault protection and is also used to provide a back-up
earth fault protection at the busbar or the transformer bay.

A small neutral point voltage exists, during normal service of the


network due to unsymmetrical capacitance of the phases to earth
and the resistive current leakage at apparatus such as surge ar­
resters. Normally the occurring levels of unbalance currents is
0,2 - 5%. Neutral point detection relays and directional relays
should therefor never be allowed to have sensitivities below
5-10% to compare with the requirements of very low levels in sol­
idly earthed systems.

The neutral point voltages are calculated with the fault resistance
“Rf ” in series with the neutral reactance “ZN”. The neutral imped­
ance consists of the earthing resistance “RN” and the capacitive

HIGH RESISTANCE EARTHED SYSTEMS

BA THS / BU Transmission Systems and Substations LEC Support Programme 221


reactance of the network “XC”. The factor “Rf/Rf+ ZN”, gives the
occurring, per unit, voltage.

The “ZN” impedance can be calculated “Un/( 3 xlf)”, where If is


the total fault current.

It must be remembered that “ZN”, as well as the vectorial sum


have to be calculated.

4.4 DIRECTIONAL EARTH FAULT PROTECTION

Due to the infeed of capacitive currents from healthy objects dur­


ing an earth fault it’s usually required to use directional earth fault
relays. Directional relays are used when the infeed of capacitive
current from an object during a fault in an other object is higher
than 60% of the required sensitivity.

The directional relays will measure the active component of the


fault current only, i. e. the current generated by the earthing resis­
tance. The principle for fault current and capacitive current gen­
eration is shown in Figure 15.

HIGH RESISTANCE EARTHED SYSTEMS

222 BA THS / BU Transmission Systems and Substations LEC Support Programme


Earth Fault Protection

Open

IR
UN UN

IR
UN> UN>
Ic2
Ic3 Ic2 Ic3
L1

L2 Ic2+IcL2
UL1 Ictot
L3
Ic3+IcL3

Ic2+IcL2
Ic3+IcL3
Ic2 Ic3
IR
IcL2 UL3 UL2

I
IcL3
UN
Note: CT does not
measure Ic2 and Ic3
Note: UN has always the
Ic2 angle of the faulty phase
Fault in L1 (+180 deg)

Ic3

Figure 15. The fault and capacitive current distribution in a high resistance
earthed network.

4.5 CALCULATION OF EFFICIENCY FACTOR.

The efficiency factor must be calculated when sensitive earth


fault relays are used (see later sections).

5. RESONANCE EARTHED SYSTEMS

5.1 PRINCIPLE

The resonance earthed networks are earthed at the source side


of the network only. Normally the earthing is restricted to one
point only, or two with parallel transformers, and an arrangement

RESONANCE EARTHED SYSTEMS

BA THS / BU Transmission Systems and Substations LEC Support Programme 223


is provided to allow connection with the earthing point. This var­
ies with the service conditions. The earthing consists of a tapped
reactor tuned to the network capacitance compensating the cur­
rent and gives a fault current close to zero Amperes at the fault.

In many cases high ohmic resistors is connected in parallel to


generate a resistive fault current for the protection system to
measure.

Alternatives without this type of resistor and with transient mea­


suring relays as described below are used.

Figure 16 shows the earthing principle and the flow of earth fault
current components.

5.2 FAULT RESISTANCE AND FAULT CURRENT


LEVELS

The earthing resistor is mostly set to give an earth fault current of


5-15A. The trend to decrease the current level gives lower re­
quirement of earthing grid and higher neutral point voltages at
high resistive earth faults.

Due to the low current magnitude, high resistance earth faults will

not quickly turn into low resistance. This means that a high fault

resistance need to be detected. In Sweden for overhead lines

with insulation a fault resistance of 5000 Ω, must be detected and

up to 20 kΩ alarmed.

For other overhead lines the value for detection is 3000 Ω.

In order to detect these high values it’s often necessary to use a


resonance earthing to achieve acceptable high neutral point volt­
ages (>5V at 5000Ω).

Due to the high sensitivity required it’s advantageous to use cable


current transformers surrounding the three phases to do the
measuring. The current transformer is then selected, with a suit­
able ratio independent of load current, and no current will flow
during normal services.

RESONANCE EARTHED SYSTEMS

224 BA THS / BU Transmission Systems and Substations LEC Support Programme


Earth Fault Protection
A sensitivity down to below 1A primary is required with reso­
nance earthed systems.

5.3 NEUTRAL POINT VOLTAGES

In order to detect high values of fault resistance, up to 5000 Ω, it’s


often necessary to use a resonance earthing to achieve accept­
able high neutral point voltages (>5V at 5000 Ω). The neutral
point voltage is required to give the directional criteria for the di­
rectional earth fault protection and is also used to provide a
back-up earth fault protection at the busbar or the transformer
bay.
A small neutral point voltage exists, during normal service of the
network, due to unsymmetrical capacitance of the phases to
earth and current leakage at apparatus as surge arresters. Nor­
mally the occurring levels, of unbalance currents, is 0,2 - 5%.
Neutral point detection relays and directional relays should there­
for never be allowed to have sensitivities below 5-10%. Compare
with the requirements of very high sensitivity in solidly earthed
systems.

The neutral point voltages are calculated with the fault resistance
“Rf ”, in series with the neutral reactance “ZN”. The neutral imped­
ance consists of the earthing resistance “RN”, the capacitive re­
actance of the network “XC” and the reactance of the earthing
reactor (normally tuned, “XL”).

The factor “Rf/(Rf+ ZN)” gives the occurring, per unit, voltage.
The “ZN” impedance can be calculated “Un/( 3 xlf)”, where If is
the total fault current.

It must be remembered that “ZN”, as well as the vectorial sum


have to be calculated. This means that the capacitive and reac­
tive components “XC” and “XL” are in opposition and normally will
end up close to zero. This means that the fault current is lower
and the total reactance also will be close to zero.

RESONANCE EARTHED SYSTEMS

BA THS / BU Transmission Systems and Substations LEC Support Programme 225


5.4 DIRECTIONAL EARTH FAULT PROTECTION

Due to the infeed of capacitive currents, from healthy objects,


during an earth fault, it’s usually required to use directional earth
fault relays. Directional relays are used when the infeed of capac­
itive current from an object, during a fault in an other object, is
higher than 60% of the required sensitivity.

The directional relays will measure the active component of the


fault current only, i.e. the current generated by the earthing resis­
tance (the principle for fault current and capacitive current gener­
ation is shown in Figure 16).

Open

IR IL
UN UN

IL
IR
UN> UN>
Ic2
Ic3 Ic2 Ic3

L1

L2 Ic2+IcL2
IL Ictot
L3 UL1
Ic3+IcL3
IR

Ic2+IcL2
Ic3+IcL3
Ic2 Ic3
IR
IcL2 UL3 UL2

IcL3
UN
Note: CT does not
measure Ic2 and Ic3
Note: UN has always the
Ic2 angle of the faulty phase
Fault in L1 (+180 deg)

Ic3

Figure 16. A Directional earth fault relay on a resonance earthed system.

RESONANCE EARTHED SYSTEMS

226 BA THS / BU Transmission Systems and Substations LEC Support Programme


Earth Fault Protection
5.5 NEUTRAL POINT CONTROL WITH SPECIAL
EQUIPMENT

A new principle for earthing has been discussed in Sweden and


some other countries during the last couple of years. This princi­
ple includes a neutral point control, where the unsymmetrical
voltage occurring in the neutral during normal service is mea­
sured, and compensated for in all phases by reactive elements.

The earthing is done with a neutral reactor in combination with a


movable core (other solutions exists) able to continuously regu­
late the reactance and compensate for the capacitive current in
the network.

The unsymmetry occurring due to e.g. unsymmetrical capaci­


tances at the different phases to earth as shown in figure 14 will
cause a neutral point voltage. This can be compensated for in dif­
ferent ways but phase-wise reactor/resistors as shown in figure
15, will with an intelligent measuring, enable a regulation and a
compensation for the unbalance. This means that the neutral
point voltage during normal service is zero.

Earth fault currents down to tenth of an ampere can then be


achieved and its possible to have the network in service during
an earth fault until it is convenient to take the line out of service
for reparation. Earth fault protection must here be arranged,
based on other principles than measuring of fundamental earth
fault currents. A transient measuring relay as described below is
one possible solution.
-∆IL
-IR0 ∆Ico
∆IL IL IcL2
L1 Ico
UL1
IcL3
L2 IR0

L3
∆C0 C0 C0 C0

R0 R0 R0
UN
L - ∆L UL3 UL2

UN

Note: UN has always the


angle of the faulty phase
(+180 deg)

RESONANCE EARTHED SYSTEMS

BA THS / BU Transmission Systems and Substations LEC Support Programme 227


Figure 17. Unsymmetrical capacitances giving neutral point voltages during
normal service.
L1

L2

L3

Course adj. Regulation &


UN
supervision

Harmonic
compensation

Figure 18. A compensation equipment for neutral point unsymmetry.

5.6 TRANSIENT MEASURING RELAYS

In the high resistive, resonance and unearthed systems, an earth


fault measuring based on the transient occurring at an earth fault
can be used. The transient is caused by the sudden change of
voltages and the sudden inrush of capacitive currents into the
healthy phases of the power lines.

This current can be measured with a residual sum measurement


or with cable current transformers.

The transients occur with a frequency of 100-5000 Hz and is


damped out very quickly. Normally within the first half cycle after
the fault, see figure 19. The measurement is therefore combined
with a measurement of neutral point voltage and the relay will
seal-in the direction of the transient as long as the neutral point
voltage is available.

Forward as well as reversed direction can be detected by the di­


rection of the transient.

Transient measuring relays can for resonance earthed system be


set to be sensitive to high resistive earth faults if no resistor is
used, as the occurring neutral point voltages will be rather high.

RESONANCE EARTHED SYSTEMS

228 BA THS / BU Transmission Systems and Substations LEC Support Programme


Earth Fault Protection
The transient in the current is independent of the neutral device
as this is caused by the transient change of voltages.

Figure 19. The neutral point voltages and the high frequency transient oc­
curring at an earth fault.

6. MEASURING EARTH FAULT CURRENT

6.1 INTRODUCTION

At earth faults in a three phase system the residual sum of the


three phase currents will not end up to zero as during normal ser­
vice. The earth fault current can be measured by a summation of
the three phase currents.

The summation can either be made by a summation of the three


phase current transformers, in a residual sum connection or by a

MEASURING EARTH FAULT CURRENT

BA THS / BU Transmission Systems and Substations LEC Support Programme 229


cable current transformer surrounding the three phase conduc­
tors. Figure 20 shows the alternatives).

Figure 20. Measurement of earth fault current can be made with a residual
sum measurement of a cable CT surrounding all three phases.

MEASURING EARTH FAULT CURRENT

230 BA THS / BU Transmission Systems and Substations LEC Support Programme


Earth Fault Protection
6.2 RESIDUAL SUM CONNECTED CURRENT TRANS-
FORMERS

When a residual sum connection is used a residual current can


be achieved caused by the small differences between the current
transformers in the three phases. Especially during a short cir­
cuit, the residual current can reach high values. This can make
high sensitivity earth fault relays operate e.g. in high resistive or
resonance earthed systems.

To prevent operation of earth fault relays a release of earth fault


relay by a neutral point voltage protection and/or a blocking of the
earth fault relay at operation of a overcurrent protection should be
performed

A much higher sensitivity can be achieved with cable current


transformers than with residual connected phase current trans­
formers, as the current ratio can be selected freely. In the residual
connected case the current transformers are given a ratio above
the maximum load currents.

For reactance- and solidly earthed systems this is not necessary


due to the low sensitivity of the earth fault protection.

6.3 CABLE CURRENT TRANSFORMER

Cable current transformers are available in varying types with dif­


ferent mounting principles, different ratios and for different cable
diameters. Epoxy quartz transformers must be thread onto the
cable end before the cable box is mounted. Transformers with
openable cores can be mounted after mounting of the cables is
done.

Different ratios are used. Today 150/5 and 100/1A is common


whereas 200/1A has been a common figure in past.

A much higher sensitivity can be achieved with cable current


transformers than with residual connected phase current trans-

MEASURING EARTH FAULT CURRENT

BA THS / BU Transmission Systems and Substations LEC Support Programme 231


formers as the current ratio can be selected freely. When residual
connected the current transformers are given a ratio higher than
the maximum load currents.

For reactance- and solidly earthed systems this is not necessary


due to the low sensitivity of the earth fault protection.

The earth fault protection relays setting range must be selected


together with the current transformer ratio to give the requested
primary sensitivity.

6.4 MOUNTING OF CABLE CURRENT TRANSFORM-


ER

In order to achieve a correct measurement the cable sealing end


must be insulated from earth and the cable screen earthing must
be done as in Figure 20. The current in the cable screen will then
be in opposite direction to the current in the earthing connection,
and will thus not be measured. Therefor the fault current going
out to the fault is the only current to be measured.

The cable must be centralized in the hole of the transformer in or­


der to prevent unbalance currents.

Cables are normally earthed at one end only if they are sin­
gle-phased. This is to prevent the load current causing an in­
duced current flowing in the screen/armory. If the cables are
three phase one- or two ends can be earthed.

7. CALCULATION OF EFFICIENCY FACTOR

7.1 EARTH FAULT RELAY SENSITIVITY

When the primary earth fault current “3I0” is transformed in the


residual sum connected current transformers or in the cable cur­
rent transformer a part of the current is used to magnetize the
current transformers to the terminal voltage “U” required to
achieve the operating current in the relay.

CALCULATION OF EFFICIENCY FACTOR

232 BA THS / BU Transmission Systems and Substations LEC Support Programme


Earth Fault Protection
The phase angle must be considered at calculation of the effi­
ciency factor “η”:

η = I set ⁄ 3I 0 × n

where “Iset” is the set value of the earth fault relay, “3I0” is the pri­
mary earth fault current and “n” is the turns ratio of the current
transformer

CALCULATION OF EFFICIENCY FACTOR

BA THS / BU Transmission Systems and Substations LEC Support Programme 233


CALCULATION OF EFFICIENCY FACTOR

234 BA THS / BU Transmission Systems and Substations LEC Support Programme


Current Transformers
1. INTRODUCTION

The main tasks of instrument transformers are:


- To transform currents, or voltages, from a high value to a value easy to
handle for relays and instruments.
- To insulate the metering circuit from the primary high voltage.
- To provide possibilities of a standardization, concerning instruments and
relays, of rated currents and voltages.

Instrument transformers are special types of transformers intend­


ed for measuring of voltages and currents.

For the instrument transformers, the common laws for transform­


ers are valid.

For a short circuited transformer:


I 1
N 2

---
-
= N
I 2
------

For a transformer at no load:

E1 N1
-----
E2 - = ------
N 2

First equation gives the current transformation in proportion to

the primary and secondary turns.

Second equation gives the voltage transformation in proportion

to the primary and secondary turns.

The current transformer is based on equation 1 and is ideally a

short-circuited transformer where the secondary terminal voltage

is zero and the magnetizing current is negligible.

The voltage transformer is based on equation 2 and is ideally a

transformer under no-load condition, where the load current is

zero and the voltage drop only is caused by the magnetizing cur­

rent and therefor is negligible.

INTRODUCTION

BA THS / BU Transmission Systems and Substations LEC Support Programme 235


In practice, the ideal conditions are not fulfilled as the instrument
transformers have a burden in form of relays, instruments and ca­
bles. This causes a measuring error in the current transformer
due to the magnetizing current, and in the voltage transformer
due to the load current voltage drop.

The vector diagram for a single phase instrument transformer is


shown in figure 1. The turn ratio is scaled 1:1 to simplify the rep­
resentation. The primary terminal voltage is “U1” multiplied with
the vectorial subtraction of the voltage drop “I1Z1” from “U1”, which
gives us the emf “E”. “E” is also the vectorial sum of the secondary
terminal voltage “U1” and the secondary voltage drop “I2Z2”. The
secondary terminal voltage “U2” is expressed as “I2Z”, where “Z” is
the impedance of the burden.
The emf “E” is caused by the flux Ø, lagging “E” with 90°. The flux
is created by the magnetizing current “Im”, in phase with Ø. “Im” is
the no load currents “I0’s” reactive component in phase with “E”.
The resistive component is the power loss component “If ”.

Figure 1. The principle of an instrument transformer.

INTRODUCTION

236 BA THS / BU Transmission Systems and Substations LEC Support Programme


Current Transformers
2. MEASURING ERROR

The current transformer is normally loaded by an impedance,


consisting of relays, instruments and, perhaps most important,
the cables.

The induced emf “E”, required to achieve the secondary current


“I2”, through the total burden “Z2+Z”, requires a magnetizing cur­
rent “I0”, which is taken from the primary side current. The factor
“I0”, is not part of the current transformation and used instead of
the rated ratio “Kn”.
I1
Nominal ratio K n = ---
I 2­

we will get the real current ratio “Kd“,


I1 – I0
Real ratio K d = -------------
I2 ­

where “I1”, is the primary rated current and “I2”, is the secondary
rated current.

The measuring error “ε” is defined:

Kn Is – Ip
ε = --------------------- × 100
Ip

where “Is”, is the secondary current and “Ip”, is the primary cur­
rent.

The error in the reproduction will appear, both in amplitude and


phase.

The error in amplitude is called current, or ratio, error. According


to the definition, the current error is positive, if the secondary cur­
rent is higher then the rated current ratio.

MEASURING ERROR

BA THS / BU Transmission Systems and Substations LEC Support Programme 237


The error in phase angle, is called phase error or phase displace­
ment. The phase error is positive, if the secondary current is lead­
ing the primary.

If the magnetizing current “I0” is in phase with the secondary cur­


rent “I2” (the maximum error), we will, according to equation 6, get
the error ε.
I1 – I0 I
-------------
I - – ---1-
Kd – Kn 2 I2 I0
ε = ------------------- × 100= ------------------------- × 100= ---- × 100
Kd I1 I1
I-
---
2

“I0” is consisting of two components, a power-loss component “If ”,


in phase with the secondary voltage and a magnetizing compo­
nent “Im”, lagging 90° and in phase with the emf “E”.

The magnetizing current causing the measuring error, depends


on several different factors (as shown in Figure 2).
B
N1 I1
[T]

N2
I2

Z
IN/cm

E2 =2π/√2 * N A ^
Bf

N1/N2=I2/I1

Figure 2. The factors influencing the current transformers output and mag­
netizing current.

For the induced emf “E”, the normal formula is valid, see fig 2. The
induced emf is given the capability to carry burdens the same
size as a transformer.

The burden is defined in IEC 185 as the power in VA can be con­


nected to a current transformer at secondary rated current and at
a given power factor (cos Ø=0,8 according to IEC 185). The sec­
ondary rated current is standardized to 1 and 5 A. The output volt-

MEASURING ERROR

238 BA THS / BU Transmission Systems and Substations LEC Support Programme


Current Transformers
age of a current transformer, shows the capability of the
transformer to carry burden.

As shown in figure 2, three factors will influence the emf “E”. It’s
the number of secondary turns “N”, the core area “A” and the in­
duction in Wb/m2 “B”. The induction is dependent of the core ma­
terial, which influences the size of the magnetizing current.
For a certain application the secondary turns and the core area
are thus selected to give the required emf output.

3. CURRENT TRANSFORMER OUTPUT

The output required of a current transformer core is dependent of


the application and the type of load connected.

METERING OR INSTRUMENTS Equipment like kW-, kVAr- and A in­


struments or kWh and kVArh meters measures under normal
load conditions. For metering cores a high accuracy for currents
up to the rated current (5-120%), is required. Accuracy classes
for metering cores are 0.1 (laboratory), 0.2, 0.5 and 1.

PROTECTION AND DISTURBANCE RECORDING In Protection relays


and Disturbance recorders the information about a primary dis­
turbance must be transferred to the secondary side. For these
cores a lower accuracy is required but also a high capability to
transform high fault currents and to allow protection relays to
measure and disconnect the fault. Protection classes are 5P and
10P according to IEC 185. Further cores for transient behavior
are defined in IEC 44-6.

In each current transformer a number of cores can be contained.


From three to six cores are normally available and the cores are
then one or two for measuring purposes, and two to four for pro­
tection purposes.

CURRENT TRANSFORMER OUTPUT

BA THS / BU Transmission Systems and Substations LEC Support Programme 239


3.1 METERING CORES

To protect instrument and meters from high fault currents the me­
tering cores must be saturated 10-40 times the rated current de­
pending of the type of burden. Normally the energy meters have
the lowest withstand capability. Typical values are 12-20 times the
rated current.The instrument security factor “Fs”, indicates the
overcurrent as a multiple of rated current at which the metering
core will saturate. This is given as a maximum value and is valid
only at rated burden. At lower burdens the saturation value in­
creases approximately to “n”.

S 2
R CT +  ----- 
 I n-
S n 2- × F S
n = --------------------------------
R CT + -----  
 I n-

where “Sn” is the rated burden in VA, “S” is the actual burden in VA,
“In” is the rated secondary current in A and “Rct” is the internal re­
sistance in Ω, at 75 °C.

According to IEC 185 the accuracy class shall be fulfilled from 25


to 100% of the rated burden.

To fulfil the accuracy class and to secure saturation for a lower


current than instrument/meter thermal capability the rated bur­
den of the core must be relatively well matched to the burden
connected.

Standards.

Table 1 below shows the requirement in IEC 185 for ratio and an­

gle error for different classes for a protection respectively a me­

tering core.

meas. error e (%) angle error (min)


class purpose
at In resp ALF at In
0.2 0,2 10 rev. metering
0.5 0,5 30 stat. metering
1 1 60 instrument
5P 1,0 at In, 5 at ALF*In 60 protection
10P 3 at In, 10 at ALF*In 180 protection

CURRENT TRANSFORMER OUTPUT

240 BA THS / BU Transmission Systems and Substations LEC Support Programme


Current Transformers
Table 1. The accuracy classes for a current transformer. For me­
tering classes there are additional requirements for 5 and 20%
of In.

3.2 PROTECTION CORES

The main characteristics of protection CT cores are:


- Lower accuracy than for measuring transformers.
- High saturation voltage.
- Little, or no turn correction at all.

The factors defined the cores are:


- The composite error with class 5P and 10 P. The error is then 5 respec­
tively 10%, at the specified ALF and at rated burden.
- The Accuracy Limit Factor “ALF” indicates the overcurrent as a multiple,
times the rated current, up to which the rated accuracy (5P or 10P) is
fulfilled (with the rated burden connected).
- The ALF is given as a minimum value and in the same way as for FS for
a metering Core, the overcurrent factor is changed when the burden is
different to the rated burden.

The formula for the overcurrent factor “n” achieved for a connect­
ed burden different than the rated burden is similar to the formula
for metering cores.
S 2
R CT + -----  
 I n-
S n 2- × ALF
n = --------------------------------
R CT + -----  
 I n-

where “Sn” is the rated burden in VA, “S” is the actual burden in VA,
“In” is the rated secondary current in A and “Rct” is the internal re­
sistance in Ω, at 75 °C.

Note that the burdens today are generally pure resistive and
much lower than the burdens, several years ago, when electro­
magnetic relays and instruments were used.

CURRENT TRANSFORMER OUTPUT

BA THS / BU Transmission Systems and Substations LEC Support Programme 241


3.3 TRANSIENT BEHAVIOR

The short-circuit current can be expressed as:


–t ⁄ T1
i K = I k [ cos ∅ × e – cos (wt + ∅)]

where “iK” is the instantaneous value of the fault current, “Ik” is the
instantaneous amplitude value of the fault current and “Ø” is the
phase angle, at the fault inception.

The variable “Ø1” is set to zero, i.e. a pure resistive burden which
is the normal situation and simplifies the calculation. The first part
of the formula is the DC component of the fault current and the
second part is the pure AC component.

The “et/T1”, implies that the DC component is a decaying exponen­


tial function, with the time constant “T1”. The maximum amplitude
depends on where on the voltage sine wave the fault occurred.

Concerning the protection relays, intended to operate during the


fault, it’s important to check the core output under transient con­
ditions.

The fault must occur between two extreme conditions:


1. Ø=90° i.e. a fault at voltage maximum.The fault current will be a pure
sinus vawe. To transform the fault current without saturation, the ALF
factor must be ALF≥ “Ik/In”.
2. Ø=0° i.e. a fault at voltage zero. The short circuit current will have full
a symmetry with a maximum DC component. Fortunately these cases
are quite rare as faults normally occur close to voltage maximum rather
than close to voltage zero.

The DC component will build up a DC flux in the core and an in­


terposed AC flux.The flux will increase and decrease according
to the time constants. The rise is dependent of the network time

CURRENT TRANSFORMER OUTPUT

242 BA THS / BU Transmission Systems and Substations LEC Support Programme


Current Transformers
constant “T1” (L/R) and the decay follows the current transformers
secondary time constant “T2”.

B
[T]

T1 40 ms
T2 2200 ms

T1 40 ms
T2 180 ms

t [sec]
Figure 3. AC and DC flux dependent of time, at faults with full DC component
and with different primary and secondary time constants.

i [A]

t [sec]

T1
Figure 4. The primary fault current with a DC component.

“T2” is the current transformer secondary time constant “L0/R0”,


where “L0” is the inductance of the secondary winding and “R0” is
the resistance of the secondary winding.

CURRENT TRANSFORMER OUTPUT

BA THS / BU Transmission Systems and Substations LEC Support Programme 243


The quotient between the maximum value of the DC component
and the maximum value of the AC component is called the tran­
sient factor “KT” and is defined:
2 2
∅(ac flux) × (ωT 1 cos ∅ – sin ∅ )
K T = ------------------------------------------------------------------------------------------
-
∅(ac
ˆ flux)

which for a resistive burden (cos Ø2 = 1,0). This gives “KT = wT1”,
which with a primary time constant of, e.g. “T1” = “L/R” = 100 ms
= 31.4, which in turn gives a DC flux “31.4” multiplied with the AC
flux.

To transform the short circuit current correctly, the protection core


must have an ALF factor “31.4” multiplied with the ALF factor for
case 1.

The situation becomes even worse if a quick auto-reclosing is


used. At fault current breaking the core will be left magnetized to
“Ømax ” as the breaking is made at current zero crossing i.e. volt­
age is close to maximum and the flux is thus also close to maxi­
mum. The remanence flux “Ør” in the core will decay according to
the formula:
t

– -------
∅ r t = ∅ max × e
T2

Ø max

Ør
t [sec]

T2

Figure 5. The decay of the flux and the remanence flux.

At a reclosing for a permanent fault after the time “t” (the same
flux direction is foreseen in the worst case), a part of the core is
CURRENT TRANSFORMER OUTPUT

244 BA THS / BU Transmission Systems and Substations LEC Support Programme


Current Transformers
already used for the remanence flux. To manage a correct trans­
formation of the current during an auto reclosing sequence the
core must be further increased with a remanence factor “Kr”.
This factor is according to IEC:
f max
K r = ------------------
f max – f-r

The current transformer cores must thus be increased with the


transient- and the remanence factor “KT” and “Kr”.This is required,
if saturation isn’t allowed during the transient fault having a full
DC offset and with an Auto reclose sequence.

Saturated
output

Figure 6. Secondary current at DC saturation. For some cycles the positive


part of the sine wave will be destroyed.

Ideal transformation of short circuits using DC component and


during Auto reclose will give very high over dimensioning require­
ments. All clearances of parameters will be multiplied and can
give unrealistic requirements on core size after multiplying with
“KT” and “Kr”.

CURRENT TRANSFORMER OUTPUT

BA THS / BU Transmission Systems and Substations LEC Support Programme 245


4. SELECTION OF CT CORES

Some general guidelines for selecting current transformer cores,


for metering and protection purposes, can be given.

SELECT THE RATED CURRENT The primary rated current is select­


ed to be 10-40% higher than the object rated current. This always
gives a high resolution of the metering equipment and instru­
ments.

For the protection cores it can be of interest to have the highest


possible ratio as this gives the least requirements of core data.
The modern relays have wide measuring ranges.

A primary- or secondary tap to get several ratios can be useful in


metering cores. Remember however that the output is reduced
when fewer turns are used.

The secondary current can be 1 or 5 A. Today 1A is the dominat­


ing as the protection and metering equipment have so low bur­
dens. The cable burden is “I2R” which indicates that a 1A circuit
has 25 times lower cable burden, measured in VA, than a 5 A cir­
cuit. This means that cores can be made in smaller dimensions
with a lower cost as a result.

SELECT BURDEN Do not use an over dimensioned burden more


than necessary. A too high rated burden compared to actual bur­
den can mean that the metering equipment is destroyed as the
Security factor “Fs” factor is valid at rated burden.

For relay cores an extra clearance concerning burden can give


unrealistic core sizes after multiplication with “KT” and “Kr”.

SELECT “Fs” AND ALF FACTORSSelect the correct Security factor


Fs and Accuracy Limit Factors ALF, dependent of the type of
equipment connected. Always refer to the product description
and check the overcurrent capability for instruments and meters
and the requirement on core output for relays.

SELECTION OF CT CORES

246 BA THS / BU Transmission Systems and Substations LEC Support Programme


Current Transformers
Remember also possible clearances of the burden which will in­
fluence the real Overcurrent factor.

Do not overdimension!

In practice all current transformer cores should be specially


adapted for their application in each station.

SELECT ACCURACY Do not specify higher requirements than nec­


essary. For metering cores especially with A-turns less than
about 400-500 a too high requirement can mean extra expenses
as a more expensive core material must be used.

SOME RULES OF THUMB


The secondary resistance “RCT is important for the CT output
and should be limited, specially for 1 A high ratio CT’s, to give an
efficient use of the current transformers i. e. the core voltage out­
put shall be used to support the connected burden and not the in­
ternal resistance. A good goal could be to always have internal
resistance lower than rated burden, preferable much lower.

When the secondary resistance following rule of thumb can be

used:

RCT ≤ 0,2 - 0,5 Ω per 100 turns.

Bigger values for big cores and small values for small cores.

Cores are considered to be big when the voltage output is of


range 1 - 2 V per 100 turns and medium size cores have outputs
0,5 - 1 V per 100 turns.

Generally the resistance values are lower for 5 A circuits as the


winding has bigger Area for 5 A than for 1 A. However the prob­
lem that the secondary resistance is high is occuring mainly on 1
A as the number of turns are five times higher for 1 A than for 5 A.
It is thus essential to keep core size and secondary resistance
down to get useful cores where the voltage output is mainly pro­
ducing current to the load and not giving internal voltage drop
and power loss.

SELECTION OF CT CORES

BA THS / BU Transmission Systems and Substations LEC Support Programme 247


SELECTION OF CT CORES

248 BA THS / BU Transmission Systems and Substations LEC Support Programme


Voltage Transformers
1. VOLTAGE TRANSFORMER (VT) AND CA-
PACITIVE VOLTAGE TRANSFORMER (CVT)

1.1 INTRODUCTION

Voltage transformers can be of two types, magnetic voltage

transformers (VT) and capacitive voltage transformers (CVT).

The magnetic voltage transformers are most economical for volt­

ages up to about 145 kV and the capacitive voltage transformers

there above. A CVT can also be combined with the PLC equip­

ment used for communication over the high voltage transmission

lines.

Voltage transformers are in most cases connected between

phase and earth.

Voltage transformers are together with current transformers

called instrument transformers. The standard covering voltage

transformers is IEC 186.

The main tasks of instrument transformers are:

- To transform currents or voltages from a usually high value to a

value easy to handle for relays and instruments.

- To insulate the metering circuit from the primary high voltage.

- To provide possibilities of a standardization of instruments and

relays to a few rated currents and voltages.

Instrument transformers are special types of transformers intend­

ed for measuring of voltages and currents.

For the instrument transformers the common laws for transform­

ers are valid.

For a short circuited transformer the following formula is valid:

I 1
N 2

---
-

I 2
= -----
N 1
-

For a transformer in no load the following formula is valid:

E 1
N 1

E 2
-

----- = ------

N 2

INTRODUCTION

BA THS / BU Transmission Systems and Substations LEC Support Programme 249


Equation (1) gives the current transformation in proportion to the
primary and secondary turns. Equation (2) gives the voltage
transformation in proportion to the primary and secondary turns.
The current transformer is based on equation (1) and ideally a
short-circuited transformer where the secondary terminal voltage
is zero and the magnetizing current is negligible.
The voltage transformer is based on equation (2) and is ideally a
transformer under no-load condition where the load current is
zero and the voltage drop is only caused by the magnetizing cur­
rent and is thus negligible.
In practice the ideal conditions are not fulfilled as the instrument
transformers are loaded with burden in form of relays, instru­
ments and cables. This causes a measuring error in the current
transformer due to the magnetizing current and in the voltage
transformer due to the load current voltage drop.
The vector diagram for a single phase instrument transformer is
shown in figure 1.

Figure 1. The principle of an Instrument transformer.

The turn ratio is 1:1 to simplify the representation. The primary


terminal voltage is U1. The vectorial subtraction of the voltage
drop I1Z1 from U1 gives us the emf E. E is also the vectorial sum
of the secondary terminal voltage U1 and the secondary voltage
drop I2Z2. The secondary terminal voltage U2 is expressed as I2Z
where Z is the impedance of the burden.

INTRODUCTION

250 BA THS / BU Transmission Systems and Substations LEC Support Programme


Voltage Transformers
The emf E is caused by the flux Ø lagging E with 90°. The flux is
created by the magnetizing current Im in phase with Ø. Im is the
no-load current I0 reactive component and in phase with E is the
resistive component the power loss component If.

1.2 MEASURING ERROR

The voltage transformer is normally loaded by an impedance

consisting of relays, instruments and, perhaps most important,

the cables.

The induced emf E required to achieve the secondary current I2

through the total burden Z2+Z, requires a magnetizing current I0


which is taken from the primary side voltage.

The I0 is not part of the voltage transformation and instead of the

rated ratio Kn:


U 1

-----
U 2
- = NominalratioK n

we will get the real voltage ratio Kd:

U 1 – ∆U

--------------------
U 2
- = RealratioK d

where
U1 is the primary rated voltage
U2 is the secondary rated voltage
The measuring error ε is defined (IEC 186) as:

U 1
U – ∆U
1
------ –�--------------------
U 2
U2 - ∆U

---------------------------------
- × = U 1
- × 100= ε( 5 )
-------
U 1

-----
U -

where

U1 is the primary voltage

U2 is the secondary voltage

MEASURING ERROR

BA THS / BU Transmission Systems and Substations LEC Support Programme 251


The error in the reproduction will appear both in amplitude and

phase.

The error in amplitude is called voltage or ratio error. According

to the definition, the voltage error is positive if the secondary volt­

age is higher then the rated voltage ratio would give.

The error in phase angle is called phase error or phase displace­

ment. The phase error is positive if the secondary voltage is lead­

ing the primary.

According to the figure

∆U = ∆E1 + ∆E2

∆E1 = I1Z1
∆E2 = I2Z2
If Z1+Z2=Zk and I1=I0+I2 we will get
∆U=I0Z1+I2Zk
The error of a voltage transformer is thus dependent of one part

independent of the load current, but dependent of the voltage U

and the flux density and magnetizing curve, and one part depen­

dent of the load current.

The magnetizing current which causes the measuring error de­

pends on several different factors as shown in Figure 2.

For the induced emf E the normal formula is valid, see fig. The

induced emf is also gives the size of a transformer capability to

carry burden.

The no load voltage drop I0*Z1


Following relations are valid:
I0 =f(B)
I0 Z1= f(B)*R1 + jf(B)*X1

To achieve a low voltage drop following steps should be taken:


- The primary winding is wound with a wire with big Area.

- A low induction is used

- The reactance is kept low

This implies that a big core area must be used in order to flux high

enough and a not to high number of primary turns as the reac­

tance has a square dependence of the turns number.

The load dependent voltage drop I2Zk.

Zk=R1+ jX1+R2+j X2

MEASURING ERROR

252 BA THS / BU Transmission Systems and Substations LEC Support Programme


Voltage Transformers

U1

N1

N2
I2

^f
E 2 =2 / 2 * N A B

N1/N2=I2/I1

B
[T]

I0/cm

Figure 2. The factors influencing the voltage transformer output and magne­
tizing current.

To keep a low voltage drop due to the load current the primary

and secondary impedances must be kept as low as possible

which in practice means that a winding with big area on the wires

is used and the coils are made as compact as possible to reduce

the leakage flux.

The measuring error variation with the voltage.

The no load error I0Z1 varies with the voltage following the mag­

netizing curve of the transformer, the primary impedance Z1 can


be considered as a constant.

The load dependent voltage drop is proportional to U2 as I2 =

U2/Z where Z is the connected burden and Z1 and Zk are con­


stants.

The relative voltage drop is thus constant.

MEASURING ERROR

BA THS / BU Transmission Systems and Substations LEC Support Programme 253


Turns correction is often used on voltage transformers to achieve

a high accuracy. The high number of turns gives a possibility to

regulate in small steps.

According to IEC 186 a voltage transformer is required to fulfil its

accuracy class for burdens between 25 and 100% of rated bur­

den. A turns correction is mostly selected to give a positive error

+εmax at a burden of 25% of rated burden and -εmax at a burden

of 100% of rated burden. This is shown in Figure 3.

+εmax

10 25 50 65 100 % of S n

−εmax

Figure 3. The measuring error as a factor of secondary burden at a constant


primary voltage.

1.3 VOLTAGE TRANSFORMERS WITH SEVERAL


SECONDARY WINDINGS.

The voltage transformers can be designed with more than one


secondary windings. This is done when secondary windings for
different purpose are needed. Each loaded secondary winding
will take load current from the primary winding and the total volt­
age drop is cased by the sum of the secondary burdens.
The most common design is to provide one Y-connected winding
and one extra secondary winding for open delta connection, used
for earth fault protection relays. This winding is not loaded during
normal service and will thus not influence the measuring accura­
cy. The open delta winding is normally provided with 110 V sec­
ondary for solidly earthed systems and for 110/3 V for unearthed,
reactance or resistance earthed systems. This will give an open
delta output of 110 V during a solid earth fault in both systems.

VOLTAGE TRANSFORMERS WITH SEVERAL SECOND­

254 BA THS / BU Transmission Systems and Substations LEC Support Programme


Voltage Transformers

Open delta winding


for earth fault
detection

Y-winding for metering


and protection purpose

Figure 4. A Voltage transformer with two secondary windings, one Y-con­


nected and one Open delta connected.

Figure 5. The principle for a open delta winding. Occurring voltages at an


earth fault in a direct earthed system.

VOLTAGE TRANSFORMERS WITH SEVERAL SECOND­

BA THS / BU Transmission Systems and Substations LEC Support Programme 255


Healthy condition Fault condition
L1
L1 L1
L2
L3

L3 L2 L3 L2

L1

L3

L2
Ursd =0

Ursd=3*U 2n

Figure 6. The principle for a open delta winding. Occurring voltages at an


earth fault in a unearthed or high resistive/resonance earthed system.

1.4 VOLTAGE FACTOR

Voltage transformers are normally connected phase to earth. In

the event of a disturbance in the network the voltage across the

VT's (CVT's) will be increased in the healthy phases. IEC speci­

fies the voltage factors:

1,9 for systems not being solidly earthed.

1,5 for solidly earthed systems.

The saturation is specified to be 30 sec for systems with tripping

earth fault protection and 8 hours if no Earth fault tripping protec­

tion is used.

The VT's must not be saturated at the voltage factor.

1.5 BURDEN AND ACCURACY CLASSES.

A number of standard values of rated burden are given in IEC

186. Following burdens are preferred values.

10, 25, 50, 100, 200, 500 VA

VOLTAGE FACTOR

256 BA THS / BU Transmission Systems and Substations LEC Support Programme


Voltage Transformers
The values are rated values per phase for a three-phase set. The

standard values on burden is given at cos Ø=0,8.

The accuracy class is fulfilled for 25-100% of rated burden.

Burden of today protection and metering equipment is very low

(in range 5-10 VA for an object) and considering that accuracy

class is fulfilled down to 25% only a low selected rated burden

should be used.

A rated burden around 1,5* the connected burden will give max­

imum accuracy at the connected burden. Refer to figure 3.

Accuracy classes are specified for protection purpose and for

metering purpose. Table 1 below shows the requirement in IEC

186 for ratio and angle error for different classes.

class meas. error e (%) angle error (min) purpose


0.2 0,2 10 rev. metering
0.5 0,5 20 stat. metering
1 1 40 instrument
3P 3 120 protection

Table 1. The accuracy classes for a voltage transformer.

It should be noted that a voltage transformer winding can be giv­


en a combined class i e 0.5/3P which means that metering accu­
racy is fulfilled for 80-120% of nominal voltage but the
requirement for 5% of nominal voltage and the transient re­
sponse requirement from protection cores is also fulfilled.

1.6 VOLTAGE TRANSFORMER OUTPUT

The output required from a current transformer core is dependent


of the application and the type of load connected.
- Metering or instruments.

Equipment like kW, kVAr, A instruments or kWh or kArh meters

measures under normal load conditions. For metering cores a

high accuracy for voltages in range (80-120 %) of nominal volt­

age is required. Accuracy classes for metering cores are (0.1 lab­

oratory), 0.2, 0.5 and 1.0.

VOLTAGE TRANSFORMER OUTPUT

BA THS / BU Transmission Systems and Substations LEC Support Programme 257


- Protection and disturbance recording.

Protection relays and Disturbance recorders where information

about a primary disturbance must be transferred to the second­

ary side. For such windings a lower accuracy is required but a

high capability to transform voltages from 5 - Vf*rated voltage to

allow protection relays measure and disconnect the fault. Protec­


tion class is 3P.
Further a good transient response is required for the protection
transformers and this is a problem for CVT´s where the energy
stored in the capacitive voltage divider and in the interposing volt­
age transformer (IVT) will result in a transient voltage oscillation
on the secondary side. The transient oscillation consists of a low
frequency component (2-15 Hz) and a high frequency oscillation
(900-4000 Hz). The time constant for the high frequency part is
short (<10 ms) whereas the low frequency part has long time
constants. The amplitude is decided by the fault inception angle.
Higher capacitances in the voltage divider gives lower amplitude
of the low frequency oscillation. The IEC 186 states that the sec­
ondary value, one cycle after a solid short circuit shall be lower
than 10%.

Fault inception
point

10%
t

1 cycle

Figure 7. The transient voltage at a solid short circuit on the terminals of a


Capacitive voltage transformer.

1.7 FERRO RESONANCE

Ferro resonance can occur in circuits containing a capacitor and


a reactor incorporating an iron core (a non-linear inductance).
Both the CVT and a magnetic VT can be involved in Ferro-reso­
nance pfenomenon.

FERRO RESONANCE

258 BA THS / BU Transmission Systems and Substations LEC Support Programme


Voltage Transformers
Ferro resonance in a magnetic VT

The ferro resonance for a magnetic VT is an oscillation between

the inductance of the VT and the capacitance of the network. Fer­

ro resonance can only occur at ungrounded networks, but note

the risk that some part becomes ungrounded under certain cir­

cumstances.

An oscillation is normally triggered by a sudden change in the

network voltage. Ferro resonance phenomenon can occur both

with sub-harmonic frequencies or with harmonic frequencies.

Generally it is difficult to state when a risk of ferro-resonance oc­

curs but as soon a a system with a voltage transformer is left un­

grounded under some circumstances, preventive actions should

be taken (also consider the risk of capacitive charged systems

with a VT).

The damping of ferro-resonance is normally done with a 27-60 Ω,

200 W resistor connected across the open delta winding. The re­

sistor value should give a current as high as possible but a cur­

rent below the thermal rating of the voltage transformer.

Ferro resonance in a capacitive VT

The CVT with its capacitor and IVT is by itself a ferro-resonance

circuit. The phenomena is started by a sudden voltage change. A

sub-harmonic oscillation can be started and must be damped to

prevent damage of the transformer.

The IEC standard specifies that CVT´s must be provided with fer­

ro-resonance damping devices. Normally this consists of a satu­

rating reactor and a resistor in each phase.

1.8 FUSING OF SECONDARY CIRCUITS

Secondary fuses should be provided at the first box where the


three phases are brought together. The circuit before the first box
from the terminal box is constructed to minimize the risk of faults
in the circuit. Any fuse in the terminal box is preferable not used
as the voltage transformer supervision is difficult to perform then
and the fuses in the three phase box is still provided to enable a
fusing of the circuits to different loads like protection and meter­
ing circuit.
FUSING OF SECONDARY CIRCUITS

BA THS / BU Transmission Systems and Substations LEC Support Programme 259


The fuses must be selected to give a fast and reliable fault clear­
ance also for a fault at the end of the cabling. Earth faults and
two-phase faults should be checked. Refer to figure 7.

1.9 VOLTAGE DROP IN SECONDARY CABLING.

The accuracy of a voltage transformer is specified on the second­


ary terminal. The voltage drop and angle error in the secondary
cabling must thus be checked in order to confirm the total accu­
racy of the circuit.

Figure 8. The voltage drop for a voltage transformer secondary circuit.

The voltage drop and angle error in the secondary cabling should
be lower than the error given by the class specification of the
transformer.

VOLTAGE DROP IN SECONDARY CABLING.

260 BA THS / BU Transmission Systems and Substations LEC Support Programme


Voltage Transformers

VOLTAGE DROP IN SECONDARY CABLING.

BA THS / BU Transmission Systems and Substations LEC Support Programme 261


VOLTAGE DROP IN SECONDARY CABLING.

262 BA THS / BU Transmission Systems and Substations LEC Support Programme


CT Requirements
1. INTRODUCTION

Many types of protection relays are used in a power system. Dif­


ferential protection relays, distance protection relays, overcurrent
protection relays of varying types etc. will all have different re­
quirements on the current transformer cores depending on the
design of the individual protection relay.

Instantaneous and delayed protection relays will also have differ­


ent requirements. A DC component of the fault current need often
to be considered for the instantaneous types of protection relays.

Modern solid-state protection relays, of static or numerical types,


provides a much lower burden on the current transformer cores
and often also have lower requirements on the core output as
they normally are designed to operate with saturated CT cores
which was not the case for the old types of electro-mechanical re­
lays

Hereafter follows a briefing of requirements that modern ABB sol­


id state protection relays will set on current transformer cores. For
special types we further refer to manuals for the respective relay
and to tests of behavior at saturated current transformers per­
formed with the different products.

To explain the general expressions used we will show a normal


current transformer circuit.

RP RCT RL

OTHER
RR PHASES
RL
RN

Figure 1. The current transformer principle circuit with magnetizing reac­


tance and secondary resistance.

INTRODUCTION

BA THS / BU Transmission Systems and Substations LEC Support Programme 263


For phase to phase faults the loop-resistance will include the ca­

ble resistance “RL” plus the resistance of Phase measuring relays

“RR + RCT”.

For phase to earth fault loops the resistance will include two

times the cable resistance “RL+Rl” plus the total resistance of

Phase and Neutral measuring relays “RR +RN + RCT”.

Core voltage output can either be the knee-point voltage, if

known, or the secondary voltage output “E2” calculated with help

of 5P or 10P data, ALF and the secondary resistance according

to:

E2 = ALF x In(RCT + Rn)

where

“E2” is the secondary limiting emf

“In” is the CT rated secondary current

“RCT” is the CT secondary resistance at 75°C and

“Rn” is the CT rated burden, calculated as resistance.

Normally, modern relays provides a pure resistive burden.

Of course values given in ANSI, or other standards, can be used

in similar ways to calculate the cores secondary output and the

achieved value can be used instead. The differences in the volt­

age output at selected definition of core is of size some 10-20%

and is not of importance for the calculation.

2. OVERCURRENT PROTECTION RELAYS

Overcurrent relays are used both as short-circuit and earth-fault


protection. They can be instantaneous or delayed, definite- or in­
verse time. Current transformer cores must give sufficient output
to ensure correct operation.

OVERCURRENT PROTECTION RELAYS

264 BA THS / BU Transmission Systems and Substations LEC Support Programme


CT Requirements
The required CT core output is given below:

INSTANTANEOUS PROTECTION Core shall not saturate for an AC


current, smaller than “2xIset”. The DC component doesn’t need to
be considered as ABB overcurrent relays are designed with short
impulse limit time to secure operation also when only a very short
current pulse is achieved due to heavy saturated current trans­
former cores. Due to high setting of instantaneous stages the re­
quirement often will be quite high.

INVERSE TIME DELAYED OVERCURRENT PROTECTION RELAYS


Core may not saturate for an AC current less than “20xIset”.
The 20 times factor is required to ensure that the inverse time
characteristic will be correct and no extra delay will be introduced
in some relay (due to saturation in a CT core). Such a delay
would mean a lack of selectivity. If required, the factor 20 can be
changed to “the Maximum fault current of interest for selectivity
divided by the Set current”.

DEFINITE-TIME DELAYED OVERCURRENT PROTECTION RELAYS


Core may not saturate for a current “I” less than “2xIset” to secure
operation.

The current output is calculated:


E2
I
= -------------
R Loop-

Both phase and earth-faults values should be checked when


earth fault currents are high. Normally however the short circuit
protection will give the highest requirement.

Overcurrent relays have moderate requirement on accuracy. 5P


or 10P class according can be used without problems. If a low ac­
curacy class is used this should be considered when selecting
the setting. Especially the margin should be increased for earth
faults when the summation of the three phases is done as the
measuring error is increased when several current transformer
cores are involved.

OVERCURRENT PROTECTION RELAYS

BA THS / BU Transmission Systems and Substations LEC Support Programme 265


3. IMPEDANCE AND DISTANCE PROTECTION
RELAYS

Distance protection relays


Distance protection is an instantaneous impedance measuring

protection for MV and HV power lines. The general requirement

on current transformer cores which can be used for ABB Dis­

tance protection relays, of modern static and numerical type, is

that the core may not saturate within 50 ms for a fault at the end

of zone 1. Differences of acceptable saturation time between dif­

ferent relay types exists but a use of 50 ms is generally suitable.

For detailed information about the requirement we refer to the

manual of each relay. Saturation is allowed for internal faults as

the relays are designed to operate with saturated CT core without

any delay in operation. Saturation due to the DC component must

be considered due to the instantaneous operation of the protec­

tion.

The empiric formula for a CT free from saturation is:

E2= Is1(X/R+l)(RCT+RL) where

“Is1” is the current through the own line for a fault at set reach of

zone 1 and “Is1” is calculated as:

U
I s1 = ------------------­
3 × Zs

where

Zs is the total impedance for a fault at zone 1 reach.

X/R is the ratio of X/R up to the zone 1 reach.

RCT+RL give the secondary resistance of the current transformer

core and the connected burden to the current transformer termi­

nal.

To calculate the required output voltage for a saturated free volt­

age the following formula can be used. The secondary time con­

stant is then considered to be high and the influence neglected:

0.05
  T -
----------- 
E 2 = I s1  T 1 × w  1 – e 1  + 1 (R ct + R 1 )
   

IMPEDANCE AND DISTANCE PROTECTION RELAYS

266 BA THS / BU Transmission Systems and Substations LEC Support Programme


CT Requirements

where

T1 is the primary time constant.

4. DIFFERENTIAL PROTECTION RELAYS

There are many types of Differential protection relays used for


many different applications. Here follows a summary of the most
commonly used differential relays from ABB.

High impedance protection relays.


CT cores used together with high impedance protection must all
have identical turn ratio. Turn correction is not allowed. Normally
separate cores must be provided for this kind of protection on all
involved current transformers. However sometimes high imped­
ance type of relays at Restricted earth fault protection application
can be used on the same core together with the Transformer dif­
ferential protection if interposing CT:s, or insulated input trans­
formers, are provided.

All cores must have a saturation voltage Usat:


Usat>2Ur to ensure operation at internal faults.

Relay operating voltage Ur is calculated as:


Ur> Ismax (Rct + RLoop) where
Ismax” is the max secondary through fault current and
RLoop” is the max loop resistance seen from connection point.

Two-way cable resistance must normally be used but for applica­


tions as pure phase fault protection single way cable resistance
can be used.

Transformer differential protection.


Transformer differential protection relays are percentage restraint
differential protection relays. The operation level is increased at
through faults to ensure stability even with the tap changer in an
end position and with differences between high and low voltage
CT cores. Generally the CT cores should not saturate for any

DIFFERENTIAL PROTECTION RELAYS

BA THS / BU Transmission Systems and Substations LEC Support Programme 267


through fault but the percentage stabilization and an internal sta­
bilization for current transformer saturation means that the re­
quirement can be limited.

Following formula should be used:


E2 ≥ KTFx Ismax (Rct + RLoop) where

KTF is the transient overdimensioning factor


Ismax is the max secondary through fault current and
RLoop is the max loop resistance seen from connection point.

KTF should be selected dependent of the type of Protection relay


supplied and the application.

KTF = 2 should be used for RADSB with interposing CT’s.

KTF = 3 should be used for RADSB without interposing CT’s or

RET 521 DIfferential protection function.

KTF = 4 should be used for SPAD 346 or RET 316.

For one- and a half, Ring busbar or two breaker arrangements

separate stabilizing inputs shall always be used for CT's where

through fault currents can occur.

The modern relays are designed to operate correctly for heavy in­

ternal faults also with saturated CT's so the through fault condi­

tion to ensure that stability is achieved for outer faults will be

dimensioning for the involved cores. It is advisable to use as sim­

ilar saturation level (in current) for the involved current transform­

ers.

Accuracy class 5P according to IEC185, or similar accuracy

class in other standards, should preferable be used.

Pilot wire differential relay RADHL


RADHL operates with a circulating current in the pilot wires. Cur­
rent transformer cores must be provided with the same ratio at
the two terminals but don’t need to be of the same type. The CT
accuracy requirements are based on the most severe external
fault under symmetrical current conditions. Under these condi­
tions and with the CT burden composed of the CT secondary and
lead resistances, plus an allowance of 5 VA for the largest single

DIFFERENTIAL PROTECTION RELAYS

268 BA THS / BU Transmission Systems and Substations LEC Support Programme


CT Requirements
phase burden of the RADHL summation CT, the CT shouldn’t ex­
ceed 10% accuracy

This gives an expression


E2 – Ez
I s = -------------------------------------
R I + R ct + R sct-

where “Is” is the maximum secondary AC fault current, “E2” is the

CT:s secondary voltage with 10P (or 5P) accuracy and “Ez” is the

voltage across the regulating diodes reflected to the primary side

of summation CT.

For 1A RADHL at ph-ef faults, “Ez” is 0.7 V and for 1A RADHL at

ph-ph faults “Uz” is 3.9 V

For 5A RADH, at ph-ph faults “Ez” is 0.15 V and for 5A RADHL at

ph-ef faults “Uz” is 0.78 V

“Rl” is the cable resistance (one way for ph-ph and two way for

ph-ef faults), “Rct” is the CT:s secondary winding resistance and

“Rsc” is the summation CT resistance, reflected to the primary

side of the summation current transformer, 0.2 Ω.

When so selected no saturation due to DC component in asym­

metrical fault currents will cause maloperation. Neither will CT:s

that saturates during an internal fault, due to AC or DC, prevent

operation. General prudence suggests a limitation of the maxi­

mum fault currents to 100 times nominal current or 250 A sec­

ondary which ever is the smallest.

When current transformers of similar characteristic are provided

at both ends of the line the through faults will always saturate the

current transformers equal at both ends and smaller cores can

then be used.

The formula:

E2 ≥ 20 x In (RCT + Rl + R2 + 5/In2)

DIFFERENTIAL PROTECTION RELAYS

BA THS / BU Transmission Systems and Substations LEC Support Programme 269


should then be fulfilled, where:

R2 is the load of other equipment connected to the same core.

Rl is cable resistance (one way for ph-ph and two way for ph-ef
faults. If earth fault current is low only one way is sufficient).

Busbar differential protection type RADSS or REB 103 and


pilot wire differential protection RADSL
RADSS/L and REB 103 are moderate impedance restraint pro­
tection relays which due to extreme speed and restraining char­
acteristic is independent of CT saturation for both internal and
external faults.

To secure operation at internal faults the CT secondary limiting


emf “E2” or the CT knee-point voltage is:

E 2 ≥ 2U rs = I d1 (R dt + 28) + n d V d3

where

“Id1” is the RADSS/L, REB103 operating current

“Rdt” is the total differential circuit resistance

“28 Ω” is the secondary winding resistance of the aux CT in the

differential circuit, referred to the primary side and

“ndVd3 = 20V” is the forward voltage drop at the full wave rectifier

in the aux CT at the differential circuit secondary side.

Loop resistance
The permissible loop resistance for secure through fault stability
seen from the relay is:

R Ix = R dt × S ⁄ ( 1 – S)

where

“S” is the setting of the slope

“Rdt” is the total differential circuit resistance and

R dt = n d2× R d3 + R md + (R a × R d11 )

where

“nd” is the turns ratio of the aux CT in the differential circuit and is

10,

DIFFERENTIAL PROTECTION RELAYS

270 BA THS / BU Transmission Systems and Substations LEC Support Programme


CT Requirements
“Rd3” is the resistance of the fixed resistor set to l l Ω,

“Rmd” is the short circuit impedance of the aux CT in the differen­

tial circuit set to 350 Ω,

“Ra” is the resistance of the alarm relay set to 20 Ω and

“Rd11” is the resistance of the variable resistor

The loop resistance seen from the relay is:

R Imax = (R 2 + R I ) × n mx

where

“R2” is the main transformer secondary resistance,

“Rl” is the cable loop resistance and

“Imx” is the aux transformer ratio.

5. FAULT LOCATORS

Fault locator type RANZA.


Requirement on current transformer cores used for ABB Fault lo­
cator RANZA is that the core is not allowed to saturate within 30
ms from the fault inception for a fault at a location where the max­
imum measuring accuracy is required.

The formula for saturation free CT in 30 ms is:

E 2 = K tf (R ct + R I )

The transient dimensioning factor “Ktf ”=Ømax /Øssc

The flux at 30 ms, Ø(0,03) is:

 wT T  0.03 0.03  
 1 2  -----------
∅(0.03) = ∅ ssc ------------------ e T1 - T2 - 
-----------
+ 1
 T1 – T2  –e  
   

where

“T1” is the primary net time constant in seconds,

FAULT LOCATORS

BA THS / BU Transmission Systems and Substations LEC Support Programme 271


“T2” is the secondary time constant in seconds,

“Øssc” is steady state flux corresponding to the sinusodial current

and

“ω” is the angle speed i.e. 2πf where “f” is the net frequency.

For conventional CT's with a high “T2” compared to “T1” this can

be simplified:

0.03
  T -
----------- 
E 2 = I s1  T 1 × w  1 – e 1  + 1 (R ct + R 1 )
   
where

“Is1” is the max fault current for which the accuracy is required,

“R1” is the loop resistance seen from core terminals,

CT ratio must be selected to ensure that phase component of the

fault current always is bigger than 10% of rated current).

Accuracy class 5P according to IEC185 should preferably be ful­

filled.

Fault locator in Distance relay type REL100 or REL 511, REL


521 or REL 531
The built-in fault locator option in the Line protection terminals as
above is designed with the same measuring algorithm as in fault
locator type RANZA. The time window for measurement is how­
ever shorter and therefor a time to saturation for a fault at location
where maximum accuracy is required of 20 ms can be used.
Similar formula as for RANZA, but with 20 ms instead of 30 ms,
should thus be utilized.

Normally it’s sufficient to use cores suitable for the Distance pro­
tection without special check. However, when lines are long and
requirement on cores from Distance protection low, a high accu­
racy can be required for faults much closer to the station. Then
the requirement set by the Fault locator will often be dimension­
ing although the time to saturation allowed is much shorter.

A certain saturation can also be accepted without loss of measur­


ing accuracy due to the analogue and digital filtering of current
FAULT LOCATORS

272 BA THS / BU Transmission Systems and Substations LEC Support Programme


CT Requirements
signals. There is also a possibility to recalculate the result given
by the fault locator in above products using a different measuring
loop if a heavy DC saturation is noticed in some of the involved
phases. This can give a big improvement as the DC component
will always differ between phases for multi-phase faults.

6. BREAKER FAILURE RELAY TYPE RAICA

The requirement on a core feeding a Breaker failure relay RAICA


is:

E 2 ≥ 15 × I set (R ct + R 1 )

or:

E 2 ≥ 0.2 × I n × n(R ct + R 1 )

whichever is the biggest.

where

”Rct” is CT secondary resistance,

“R1” is the total loop resistance seen from CT terminals,

“Iset” is the RAICA set current,

“In” is the CT secondary rated current an

“n” is maximum primary fault current/CT primary rated current.

This will secure the operation of the Breaker failure relays even

with CT saturation. RAICA is designed with a energy storing to

give a continuous energizing of the output, even with heavy sat­

urated current transformers, and with short reset pulses every cy­

cle caused by the extreme speed of the measuring relay RXIB.

BREAKER FAILURE RELAY TYPE RAICA

BA THS / BU Transmission Systems and Substations LEC Support Programme 273


BREAKER FAILURE RELAY TYPE RAICA

274 BA THS / BU Transmission Systems and Substations LEC Support Programme


Control System Structure
1. INTRODUCTION

The control system equipment in a Substation is a vital part that

supervises, protects and controls the transmission of electrical

power.

The increasing complexity in the substations of today, together

with the increasing transmitted power and the increasing fault

current levels, means increasing requirement set on the control

and protection equipment.

Dependent of the stations location in the networks and the power

consumption, the operation and maintenance organization of the

customer and government regulations etc., many choices must

be done in order to achieve lowest possible Life Cycle Cost

(LCC).

The highest possible service reliability is a general goal. Flexibil­

ity and maintainability are also important factors in order to attain

a total reliability.

The first choices are the selection of the primary apparatus. The
choice of AIS or GIS switchgear and decision of the switchgear
arrangement, to be used and transformer sizes etc. are important
in order to achieve a low LCC.
Thereafter choices of control and protection equipment must be
done e. g. conventional or computerized control equipment, sin­
gle or redundant protection systems, design and voltage of bat­
tery system, choice of battery type etc. All choices must be done
with the expected future development in mind. Later changes will
always mean a much higher cost than a selection made after fu­
ture needs.

It’s always difficult to foresee the future but a summary of expect­


ed changes of the power network in the area of the new station
should always be done e.g. by checking plans for building of new
living areas, starting of new industries etc., with the communities.

INTRODUCTION

BA THS / BU Transmission Systems and Substations LEC Support Programme 275


The cost distribution for a construction of a typical Substation is
shown in Figure 1. It should be noted, that the control and protec­
tion equipment is about 10-15% of the stations total cost. If trans­
mission lines also are included in the comparison the cost part of
control and protection will be even smaller.

Figure 1. The cost distribution at installation of a HV substation.

The importance of control and protection equipment is expanding

if the total life cycle cost is considered. The control equipment is

very important for the station operation and the protection equip­

ment is an important part of the maintenance and thus the main­

tenance cost.

In most organizations a number of standards has been selected

and must be followed. Government also has a number of require­

ment which must be followed by the station owner. A standard

can often mean a high initial cost but will give a positive impact

on the life cycle cost, as the maintenance personal will be more

efficient as they are well familiar with the equipment. The spare

part cost will also be lower.

In this document a survey of different parts of the control and pro­

tection equipment is done. Equipment included in the control sys­

tem are:

- Auxiliary power systems.


- Protection system.
- Metering equipment.
- Control and regulation.
- Signalling and event recording.
- Operation.

INTRODUCTION

276 BA THS / BU Transmission Systems and Substations LEC Support Programme


Control System Structure
2. INSTRUMENT TRANSFORMERS

2.1 CURRENT TRANSFORMERS

Location
The location of the current transformers will give the limitation of
the protection zones.

The most common approach is to locate the current transformer


at the outside of the object circuit breaker, so that a Busbar differ­
ential protection will cover the circuit breaker.

The location should generally be as close as possible to the cir­


cuit breaker as the breaker will open when a fault is detected. The
zones where an incorrect tripping is achieved is thereby mini­
mized.

For GIS switchgears a requirement to cover all GIS compartment


from the busbar protection is often raised. This will ensure an in­
stantaneous trip for all faults in the GIS and the risk of
“burn-through” is thereby minimized.

For lower voltages where busbar protection is not used, a loca­


tion of the current transformer to between the breaker and the
busbar could be advantageous but is usually impossible to do
due to the mechanical construction.

When Transfer busbars, C-arrangements, are used a location of


current transformers outside the C-disconnector is preferred.
The object protection will then still be in operation when the trans­
fer busbar and transfer breaker is used to by pass another break-

INSTRUMENT TRANSFORMERS

BA THS / BU Transmission Systems and Substations LEC Support Programme 277


er scheduled for maintenance and a rearrangement of the trip

circuit to the transfer breaker can simply be done (see Figure 2).

Figure 2. The location of current transformer at a AC-Busbar arrangement.

At one and a half breaker systems and double breaker systems,


the current transformers in the two sections are connected to­
gether in a summation. Similar core data on the involved cores
will match each other when the cores are summed.

A control of possible primary current loops through the current


transformer must be done, when circuit breaker is earthed on
both sides. Resistance of primary loop is seen as the current
transformer ratio in square times the primary loop resistance
from the secondary side. A fault or load current in the other (sum­
mated) current transformer will thus be split up between protec­
tion/meters and the primary loop according to the impedances in
the two circuits.

Especially for CT:s with low ratio, primary resistance seen from
secondary side could be quite low, leading to an important mea­
suring error for the metering and fail to trip for a primary fault. This
is due to the fact, that a part of the load/fault current will create a
primary circulating current instead of going through the
meter/protection. For high impedance protection schemes this

INSTRUMENT TRANSFORMERS

278 BA THS / BU Transmission Systems and Substations LEC Support Programme


Control System Structure
could be a problem even with not so low CT-ratio and must be
checked. (See Figure 3)

Figure 3. Summation of current transformers in a double busbar arrange­


ment.

Earthing
To prevent dangerous potential in the secondary circuit of a cur­
rent transformer all secondary circuits shall be earthed.

Only one earthing point may be used when several current trans­
formers are connected together in a summation or differential
connection. This is necessary as equalizing currents else can
flow through the circuit, during a primary earth fault.
Neutral connection and earthing can be made according to vary­
ing practises in different countries and with different utilities.

Earthing towards the protected object and neutral connection are


the most common principles followed by most companies and
manufacturers of protection and metering equipment.

Within ABB Substations we follow the principles:


- Neutral and earth towards protected object.
- Neutral and earth toward the metering direction.

INSTRUMENT TRANSFORMERS

BA THS / BU Transmission Systems and Substations LEC Support Programme 279


Reconnected CT’s.
Primary as well as secondary reconnection is used.

At primary reconnection there are two primary windings, usually


only one turn each, which are connected in series or in parallel.
Independent of the connection the same core data will be
achieved.

Secondary reconnected cores has taps on the secondary wind­


ing. The core data will then be, as best, linearly reduced.
Due to the reduction of core data a difference between maximum
and minimum tap, higher than 1:2 should be avoided as the sec­
ondary circuit burden is always the same.

Secondary taps not used shall be left open.

Cores not used shall be short-circuited at maximum taps.

An open current transformer secondary circuit will mean danger­


ous voltages and must therefor be avoided carefully.

Terminals
To enable a simple testing and reconnection of current circuits at
commissioning/fault finding a terminal grouping as in Figure 4)
can be used. A simple change of current direction is achieved by
changing the link. A simple test of each core can be done from
the terminals. The terminals are openable with links and should
be suitable for connection of normal test wires.

INSTRUMENT TRANSFORMERS

280 BA THS / BU Transmission Systems and Substations LEC Support Programme


Control System Structure

Figure 4. A terminal arrangement which allows simple reconnection of a cur­


rent transformer direction and a simple testing of each core.

2.2 VOLTAGE TRANSFORMERS

Location
The location of the voltage transformers will primary depend on

the switchgear arrangement, the protection, the metering and the

automatics connected.

Normally, voltage transformers connected to the busbars and at

the low voltage side of the transformers are satisfactory in a dis­

tribution substation.

Directional Protection on outgoing bays are then fed from the

busbar VT:s.

INSTRUMENT TRANSFORMERS

BA THS / BU Transmission Systems and Substations LEC Support Programme 281


On the transmission voltage level the protection equipment will
normally require voltage transformers at all objects, sometimes
with exception of the HV side of power transformers.

Further, a single phase set is located at the busbars for voltage,


frequency and synchronizing purpose. This avoids complex volt­
age selection schemes.

Earthing and fusing.


The secondary circuits are fused and earthed in the VT marshal­
ling box. This will ensure that dangerous voltages will not occur.
Connection of different VT/CVT circuits should therefor be avoid­
ed to prevent equalizing currents in the secondary circuits during
primary earth faults.

The fusing can be done with diazed fuses or Miniature circuit


breakers (MCB:s). The tripping condition must be checked i.e. it
must be checked that the fuses/MCB will trip within a reasonable
time (e.g. 5 sec). This normally means that higher rated currents
than 6 A cannot be used.

Supervision
A fault can always occur even if the plant is well designed and
well constructed. When a fault occurs it’s of importance that the
fault is immediately detected and an alarm given to enable the
maintenance personal to quickly repair the fault. A fault in a me­
tering circuit will mean incorrect metering, with loss of income as
a result. A fault in a protection circuit can mean one missing or
incorrect tripping which will lead to unnecessary disconnecting of
one or several objects.

The supervision of a voltage transformer secondary circuit can


be done according to Figure 5 if the circuit supplies metering
equipment. An occurring unsymmetry between the phases will
be detected and the relay can by that detect one or two phase
fuse failure.

INSTRUMENT TRANSFORMERS

282 BA THS / BU Transmission Systems and Substations LEC Support Programme


Control System Structure

Figure 5. Supervision of a voltage transformer circuit (for alarm purpose


only).

If a protection relay is supplied a supervision according to Figure


6 can be used. A differential voltage measuring is used where the
voltage of a main fuse, supplying the protection relay, and a pilot
fuse are compared. This principle will detect one, two or three
phase fuse failures.

Figure 6. Supervision of a Voltage transformer secondary circuit (for block­


ing of protection).

INSTRUMENT TRANSFORMERS

BA THS / BU Transmission Systems and Substations LEC Support Programme 283


Another solution used to detect fuse failures in some types of Dis­
tance protection is to compare the occurrence of zero, or nega­
tive, sequence voltage with the occurrence of zero, or negative,
sequence current. If only voltage occurs the problem is a blown
fuse. If both current and voltages occur there isn’t a fuse problem
but a primary earth fault. The drawback with this principle is that
it will only detect one and two phase fuse failures. However the
normal faults on a voltage transformer circuits are to earth and in
rare cases between two phases.

If MCB:s are used an auxiliary contact can be used to give alarm.


If Distance protection relays shall be blocked a special MCB with
low instantaneous level and a very fast auxiliary contact must be
used.

Cabling
Dedicated cables shall be used for the voltage transformer sec­
ondary circuits. The cable shall be screened and earthed at both
ends to keep the disturbance voltages to low levels.

The secondary cabling must be dimensioned to:


- Ensure that fuse/MCB will operate, in a reasonable time, for a fault at the
far end of the cables.
- Keep the voltage drop, due to the burden, one level lower than the inac­
curacies in the voltage transformer.

A special problem occurring in voltage transformer circuits if fus­


es are used is the risk of back-feeding a faulty phase from the
healthy phases. This phenomena occurs when phase to phase
connected load exists. The phase with the blown fuse can reach

INSTRUMENT TRANSFORMERS

284 BA THS / BU Transmission Systems and Substations LEC Support Programme


Control System Structure
rather high voltage level. The level is decided by the load in the
different phases as indicated in Figure 7.

Figure 7. Back-feed of voltages to a faulty phase, when phase to phase load


exists.

2.3 AUXILIARY POWER DISTRIBUTION

The auxiliary power system has a very central role in a substa­


tion. A fault in the battery system will mean that neither control
and protection equipment nor primary equipment can fulfil their
tasks. Often a complete station or a big part of a station is influ­
ence by a main problem in the auxiliary power system.

At higher system voltages, two battery systems are mostly pro­


vided to feed the local back-up protection, in redundant protec­
tion systems.

At lower voltages this is not necessary as a protection system


with remote back-up normally is used. This means that faults can
be detected from another location as well.

INSTRUMENT TRANSFORMERS

BA THS / BU Transmission Systems and Substations LEC Support Programme 285


The DC distribution ensures that protection relays which are pro­
viding back-up to each other (e.g. outgoing feeder and transform­
er protection) are fed from different main fuses in the battery
distribution. This will ensure that minimum possible part is tripped
at a primary fault even with a single failure in the fault clearing
chain, as in this case, in the battery system.

The supervision of a the auxiliary power supply is of utmost im­


portance. The secured feeding of alarm circuits for DC problems
must be ensured.

A well designed supervision of the DC supply to an object should


supervise the feeding fuse, an open circuit and a blown
fuse/MCB in the sub distribution.

An example of a DC supervision is shown in Figure 8. It’s often a


good idea to include the contacts of the DC/DC converters in the
different protection relays in the supervision, so that a common
alarm is given when DC problems anywhere in the distribution
occurs.

Figure 8. Supervision of the DC supply to a protection panel, detecting faulty


supply fuse, open circuit and DC/DC converter failures.

Supply of different equipment


Varying principles are used in the auxiliary power supply of the
equipment.

INSTRUMENT TRANSFORMERS

286 BA THS / BU Transmission Systems and Substations LEC Support Programme


Control System Structure
An important principle is to limit the distribution of the auxiliary

power supply to the protection system as much as possible, and

to use only one supply to the protection of an object and the

breaker trip coil.

The limitation of the circuit distribution is done by feeding discon­

nector, earthing switch operation circuits and enabling circuits

etc. from separate supplies.

The trip coil can in a system without redundant protection be sup­

plied from the same supply as the protection relays and the trip

coil. A closing is then not possible if the voltage supply to trip isn’t

available.

To simplify the fault finding at earth faults in the DC supply system

a structured terminal system as shown in Figure 9 can be useful.

Figure 9. A terminal arrangement, enabling a simple localization of earth


faults and a simple design of the DC distribution to different panels and box­
es.

INSTRUMENT TRANSFORMERS

BA THS / BU Transmission Systems and Substations LEC Support Programme 287


The system includes a supply of marshalling boxes, control pan­
els (and other panels) and internal distribution from different ter­
minals, so that each circuit simply can be opened and checked
for e. g. bad insulation. The terminal numbering system utilized is
described later on.

To enable location of an earth fault, in a operation circuit, at a dis­


connector/earthing switch, with two pole operation, a resistor
shall be connected across the contact at the negative side.

3. PROTECTION AND CONTROL EQUIPMENT

3.1 DESIGN OF PANELS

The panel design and construction shall be done following a


number of general guidelines:
- The layout are to follow the layout of the primary switchgear to avoid con­
fusion.
- The panels should be clearly and visible labelled, so that objects located
in the panel is simply identified.
- The possibilities of future extensions should be kept in mind both in pan­
el design and the location in the room etc.
- Maintenance should be simplified as much as possible and the design
should minimize the risk of mistakes such as testing the wrong object or
the need of making a lot of reconnections, to enable testing.
- Two object per panel, should be avoided but must be done out of cost
reason. The belongings of the object shall then clearly be labelled both
on front and inside the panel.

Terminals
The terminals are small but important components in a substa­
tion. They should have possibility to simple connect and discon­
nect measuring wires with a clearly visible indication.

A maximum of two cores are to be connected at each side of the


terminal and a mixture of single core and stranded wires should
be avoided.

At terminal numbering a clear structure should be used to im­


prove the total quality. The design engineer will by that know
PROTECTION AND CONTROL EQUIPMENT

288 BA THS / BU Transmission Systems and Substations LEC Support Programme


Control System Structure
which terminal group to use for different types of circuits.
Different circuits in the panel can simply be separated. The work­
shop testing and the site commissioning personnel will from the
numbering see what circuit type they are working with e.g. they
can simple differ a current circuit from a auxiliary supply circuit.

The terminal numbering system used by ABB Substations AB is


shown in Appendix 1.

The system used enables a clear separation of main and back-up


protection and gives an indication of interface and trip circuits
which is of importance for the service and maintenance.

The system is also made for connection of cables. Cable cores


are simple to erect as the connection of the different cores is in
the same group. Extra terminals for future use can also simply be
added with a prepared and correct number.

Trip circuit design


The trip circuits are together with the DC supply key parts of the
fault clearance chain.

Trip circuit supervision can be used to improve the dependability


of the circuit. The circuit from the relay panel to the circuit break­
er, including the auxiliary contact of the breaker is supervised by
a small current (1-20 mA), fed through the circuit. Through a spe­
cial circuit, with a resistor and an auxiliary contact at the breaker,
the circuit can be supervised also when the breaker is open.
A double supervision where a current measuring relay is con­
nected both in the breaker circuit and across the relay can be
used when lock-out trip relays are used.

PROTECTION AND CONTROL EQUIPMENT

BA THS / BU Transmission Systems and Substations LEC Support Programme 289


The arrangement of a trip circuit supervision is shown in Figure
10.

Figure 10. Arrangement of a trip circuit supervision.a) Single supervision,


b) Double supervision (with lock-out trip relays).

The trip coils of the circuit breaker normally have a power need
of 200-300W. A common requirement is that the contacts of the
trip relays are capable of breaking the current to the trip coils
even though there is an auxiliary contact in the breaker doing this.
This contact will however not operate at a breaker failure and
heavy duty contacts are therefor advantageous.

Busbar protection trip circuits.


Trip arrangements for busbar protection relays can be done in dif­
ferent ways. The bus-principle as shown in Figure 11 is preferred,
as it gives a simple and clear technical solution, where Breaker

PROTECTION AND CONTROL EQUIPMENT

290 BA THS / BU Transmission Systems and Substations LEC Support Programme


Control System Structure
failure trip simple can be arranged to trip the busbar, without need
of extra auxiliary contact on the disconnectors.

Figure 11. A trip busbar arrangement, for busbar protection tripping, gives a
simple solution and allows the CBF trip to be connected without extra auxil­
iary circuits on the disconnectors.

Lock out tripping.


Lock-out of circuit breaker closing should be initiated from protec­

tion relays covering faults of permanent type. Lock-out relays are

reset manually, when the fault has been repaired. The best solu­

tion is to open the close circuit only. A permanent signal in the trip

circuit only isn’t good as the breaker then can be unnecessary ini­

tiated even though instantaneously retripped. A continuous trip

will also mean problems for trip circuit supervision and special

care need to be taken for this.

It should also be remembered that a Breaker trip coil cannot ac­

cept more than a short trip pulse. Long pulses will destroy the trip

coils and this can happen e. g. when a Breaker has not stored en­

ergy in the operating device and the trip relay is initiated, mostly

then during testing.

Lock-out should thus preferable be performed with self reset trip

relays and latching relays opening the closing circuit only.

PROTECTION AND CONTROL EQUIPMENT

BA THS / BU Transmission Systems and Substations LEC Support Programme 291


Capacitive discharges.
Trip and important operation relays should be stable during the
capacitive discharges which can occur at an earth fault in the DC
system. The problem is shown in Figure 12. Special types of re­
lays with a stabilization against this discharge are available.

Figure 12. An earth fault in the battery system, will give capacitive discharg­
es, which can operate trip relays. Secured trip relays should be used when
the circuit is simply available e.g. in terminals.

PROTECTION AND CONTROL EQUIPMENT

292 BA THS / BU Transmission Systems and Substations LEC Support Programme


Control System Structure
4. SIGNALLING

4.1 FAULT SIGNALLING

At a fault in the primary network it’s of importance that the oper­


ating personal receives information about fault type, whether the
fault is persistent or transient, what phases are involved and the
fault location so that correct actions can be taken.

At a fault in a the protection and control equipment it’s of great im­


portance that the operating personal receives information about
the disturbances so that corrective actions can be taken.

These faults don’t normally mean disturbance for the system ser­
vice but need to be repaired within a short time.

An alarm for a fault in the battery system like a lost battery charg­
ing need to be fixed within 4-10 hours depending on the batteries
capacity so that the station is not left without protection and con­
trol possibilities. A fault in the primary system would then cause
unnecessary large consequence, with damaged equipment and
disconnection of far to big parts of the network as a result.

Several different equipment types are used to give information


about primary and control equipment faults. Among them you’ll
find:
- Annunciator system
- Event recorder
- Disturbance recorder
- SCADA

One important part in order to achieve a high reliability and in or­


der to follow up disturbances in the primary system and the be­
havior of the protection system is the post fault analysis (see
Protection - General).

SIGNALLING

BA THS / BU Transmission Systems and Substations LEC Support Programme 293


4.2 ANNUNCIATOR SYSTEM

The annunciator system will give the operating personal quick in­
formation about a fault. At activation of an alarm point an audible
alarm is initiated. This alarm is locally switched off when the sta­
tion is remotely controlled.

All faults are to be alarmed but grouping in suitable groups is


done to save cost and to simplify for the operator as too much in­
formation will only be confusing when a quick decision have to be
taken.

4.3 EVENT RECORDER

The event recorders gives digital, time tagged, information about

all disturbances in the control system, as well as in the primary

system.

The sequence of events such as starting of measuring zones and

phase selection etc., can be followed with a resolution of some

ms which simplifies the follow up on a disturbance. This follow up

is performed later by experts at protection and control systems.

Information at the event recorder is just to a low extent used by

the operators.

4.4 DISTURBANCE RECORDER

The disturbance recorder gives information about the analogue


signals during a primary fault. A few digital event are also con­
nected to get a time reference and a possibility to compare the
event recorder and disturbance recorders information.

The disturbance recorder starts when any protection relay starts


or trips. A pre-fault memory is included. The recording will there­
by include information from just before the fault (0.1-0.5 seconds)
to up to after the fault has been cleared.

Today print-outs is on regular paper but there is also a possibility


to send the information in series form to a computer, as software
support today is available to most types of recorders.

SIGNALLING

294 BA THS / BU Transmission Systems and Substations LEC Support Programme


Control System Structure
4.5 REMOTE SIGNALLING.

Most stations in the world, are today remotely controlled, or pre­

pared for remote control.

Locally available signals must be transmitted with high reliability

to the dispatch center and to the operators. This concerns signals

for faults in the primary system, as well as faults secondary in the

control system.

5. INTERLOCKING

The interlocking system will prevent human mistakes which can

lead to severe damages of equipment and/or injuries of persons.

With the development of today control system and the increasing

integration of circuits it is of greatest importance to always keep

the independence requirement between the operation circuits

and the interlocking circuits in mind. An equipment fault must not,

at the same time, cause an operation of a disconnector and an

enabling signal.

Independency does not necessary mean independent hardware

but the design of the circuit to achieve a highest possible reliabil­

ity is important.

6. DOCUMENTATION

A big amount of documentation is necessary for each station in


order to enable service, maintenance, fault finding, purchasing of
spare parts and extensions of the station. The documentation is
the output of a process starting at contract signing and ending
with the Final acceptance.

The cost of design and documentation is about 20-30% of the to­


tal cost of the control system.

INTERLOCKING

BA THS / BU Transmission Systems and Substations LEC Support Programme 295


Documents for different categories
The documents produced are for varying categories of personal.
Erection, commissioning, maintenance and engineering depart­
ments, have all different requirements and uses different docu­
mentation in their work.

Documents groups
The documentation can be separated in three different parts:
- Operation and Maintenance manuals, gives information about operation
and maintenance of the station. General documents like Single-line di­
agrams, Block diagrams and User’s manuals for products, are included
here.
- Electrical design contains Circuit diagram, apparatus list and intercon­
nection tables etc., and gives detailed information to commissioning and
maintenance personal.
- Erection manuals includes information for mechanical construction such
as mounting information for panels and apparatus, mechanical draw­
ings etc. The erection manuals are used by the erection personal.

It is of utmost importance that the documentation is kept updated


and that old versions are thrown away. An up-to-date set shall be
stored at the substation.

7. CONCLUSION

When a control system is designed it is important to see to the

goal with the substation and to check that the purpose with the

document produced is clear.

A reliable plant, with a high availability, shall be simple to operate

and maintain. Simple solutions are always preferred as mistakes

and misunderstandings during the different stages of the project

are prevented.

The documentation system has a key role as carrier of informa­

tion between different departments during the different stages of

the project. A well structured organization where responsibilities

are known by all people is necessary to achieve a high quality

and reliable plant with high availability.

CONCLUSION

296 BA THS / BU Transmission Systems and Substations LEC Support Programme


Control System Structure
8. TERMINAL NUMBERING SYSTEM

8.1 RELAY PANEL, MAIN 1 PROTECTION

Function Type Terminal group


Current circuit
Core 1 I1 X11: 11-14
Core 2 I2 (other CT:s 21-24
Core 3 I3 are called 31-34
Core 4 I4 X111 etc.) 41-44

Voltage circuit
Distr 1 U1 X12: 11-19
Distr 2 U2 (other VT’s 21-29
Distr 3 U3 are called 31-39
Distr 4 U4 X112 etc. 41-49
Open delta 51-59

Auxiliary voltage
protection relays
DC distr R2+/- X13: 1-16

PLC sign X17: 1­

Sub 1-Sub 2 Interface X18: 1­

Trip outputs X19: 1­


(incl CB fail, intertrip etc.)

TERMINAL NUMBERING SYSTEM

BA THS / BU Transmission Systems and Substations LEC Support Programme 297


8.2 RELAY PANEL, MAIN 2 PROTECTION

Function Type Terminal group


Current circuit
Core 1 I1 X21: 11-14
Core 2 I2 (other CT:s 21-24
Core 3 I3 are called 31-34
Core 4 I4 X121 etc.) 41-44

Voltage circuit
Distr 1 U1 X22: 11-19
Distr 2 U2 21-29
Distr 3 U3 31-39
Distr 4 U4 41-49
Open delta 51-59

Auxiliary voltage
protection relays
DC distr R2+/- X23: 1-16

PLC sign X27: 1­

Sub 1-Sub 2 Interface


X28: 1­

Trip outputs
X29: 1-
(incl CB fail, intertrip etc.)

TERMINAL NUMBERING SYSTEM

298 BA THS / BU Transmission Systems and Substations LEC Support Programme


Control System Structure

8.3 OTHER CIRCUITS

Control circuits
DC distr X31: 1-10
Other circuits 21­
Annunciator circuits
DC distr X41: 1-10
Other circuits 21­
SCADA circuits
DC distr X51: 1-10
Other circuits 21­

Event recorder circuits


DC distr X61: 1-10
Other circuits 21­
Fault Recorder circuits
DC distr X71: 1-10
Other circuits 21­
DC Supply Main 1 (feeding MCB/fuse)
DC distr X91: 1-4

DC Supply Main 2 (feeding MCB/fuse)


DC distr X92: 1-4

AC Supply for Heaters Lighting etc.


AC distr X93: 1-10
Other circuits 21-

TERMINAL NUMBERING SYSTEM

BA THS / BU Transmission Systems and Substations LEC Support Programme 299


TERMINAL NUMBERING SYSTEM

300 BA THS / BU Transmission Systems and Substations LEC Support Programme


Setting of Protection
1. INTRODUCTION

The main function of the protection system is to isolate the mini­

mum possible part of the power system at a fault or an abnormal

condition. This is achieved by selecting a protection system suit­

able for the plant and object protected, and to set the protection

relays to suitable values. Suitable protection relays with incorrect

setting can cause severe disturbances of power supply and/or

unnecessary damage of equipment.

Faults occurring in the power system should always be detected

by two different protection relays to allow for a single failure. (Fus­

es are “secure break points” and do thus not require back-up pro­

tection). The protection relays are normally designated Main and

Back-up protection.

According to IEC it is the MAIN PROTECTION that is normally

expected to take the initiative in cases of a fault in the protected

zone. The BACK-UP PROTECTION is provided to act as a sub­

stitute for the main protection in case of failure or inability of this

to perform its intended function.

The protection system shall, as mentioned before, be able to iso­

late minimum possible part of the system. We can then introduce

the term SELECTIVITY.

SELECTIVE PROTECTION is a protection which determines

that the fault is within its zone and isolates that zone only. Selec­

tive protection relays can be ABSOLUTE SELECTIVE or RELA-

TIVE SELECTIVE.

ABSOLUTE SELECTIVITY is when a protection responds only to

faults within its own zone.

Examples of ABSOLUTE SELECTIVE protection relays are:

Differential protection relays (Transformer-, Pilot wire-, Busbar

differential protection)

Buchholz and Transformer Temperature devices

Tank and frame leakage protection

Distance protection first- and accelerated- zone, where operating

area is decided by impedance setting protection relays for indi-

INTRODUCTION

BA THS / BU Transmission Systems and Substations LEC Support Programme 301


vidual objects such as Reactor protection, Motor protection,

Shunt capacitor protection

As these protection relays only operates for faults within a certain

zone they are not required to be shown in the selectivity plan. Still

it can be advantageous to show them in the selectivity plan to get

the relation to other protection relays.

RELATIVE SELECTIVITY is when the selectivity is obtained by

grading the settings (i.e. time or current) of the protection relays

of several zones, all of which may respond to a given fault. These

protection relays can be either time or current selective or a mix­

ture of both.

Examples of RELATIVE SELECTIVE protection relays are

- Distance protection back-up zones


- Overcurrent protection
- Earth-current protection
- Overload protection
-Voltage protection
For these protection relays selectivity plans are made as they op­
erate for faults in a big part of the power system and disconnect
the faulty part only by grading of current, voltage and time setting.
Most types of faults initiate several protection relays in above
groups. For example, short circuits with earth connection can ini­
tiate overcurrent protection, earth current protection, overload
protection, differential protection, negative sequence protection
and undervoltage protection dependent on fault location, type of
earthing and the protection system provided.
SELECTIVITY CHARACTERISTIC or SELECTIVITY PLAN.
Diagram or table showing the operating times and corresponding
actuating quantities or fault positions for the selective protection
relays of a network.
The purpose of the SELECTIVITY PLAN is to coordinate the re­
lay settings so that:
- faulty equipment is tripped as fast as possible
- the least possible disturbance is obtained for healthy equipment
- a back-up protection is obtained if a main protection or its break­
er fails to trip.

The selectivity plan is performed in similar way for short circuit


and earth-fault protection relays. In a solidly earthed system an
intercheck between earth-fault and short circuit protection's oper­
ating times must be made as short circuit protection relays often

INTRODUCTION

302 BA THS / BU Transmission Systems and Substations LEC Support Programme


Setting of Protection
will operate for earth-faults as well. It is then checked that a short

circuit protection, measuring phase component of fault current,

will not have shorter operating time than the earth-fault protection

at the same location, for an earth-fault.

of the protection relays of several zones, all of which may re­

spond to a given fault. These protection relays can be either time

or current selective or a mixture of both.

Examples of RELATIVE SELECTIVE protection relays are

- Distance protection back-up zones


- Overcurrent protection
- Earth-current protection
- Overload protection
-Voltage protection
For these protection relays selectivity plans are made as they op­
erate for faults in a big part of the power system and disconnect
the faulty part only by grading of current, voltage and time setting.
Most types of faults initiate several protection relays in above
groups. For example, short circuits with earth connection can ini­
tiate overcurrent protection, earth current protection, overload
protection, differential protection, negative sequence protection
and undervoltage protection dependent on fault location, type of
earthing and the protection system provided.

SELECTIVITY CHARACTERISTIC or SELECTIVITY PLAN.

Diagram or table showing the operating times and corresponding

actuating quantities or fault positions for the selective protection

relays of a network.

The purpose of the SELECTIVITY PLAN is to coordinate the re­

lay settings so that:

- faulty equipment is tripped as fast as possible

- the least possible disturbance is obtained for healthy equipment

- a back-up protection is obtained if a main protection or its break­

er fails to trip.

The selectivity plan is performed in a similar way for short circuit

and earth-fault protection relays. In a solidly earthed system an

intercheck between earth-fault and short circuit protection relays

operating times must be made as short circuit protection relays

often will operate for earth-faults as well. It is then checked that a

short circuit protection, measuring phase component of fault cur-

INTRODUCTION

BA THS / BU Transmission Systems and Substations LEC Support Programme 303


rent, will not have shorter operating time than the earth-fault pro­
tection at the same location, for an earth-fault.

2. PROTECTION RELAYS SETTING

Absolute selective protection relays


Distance protection
Distance protection relays are set according to the setting in­
struction for the specific protection. Below follows just a brief in­
formation of the general principle of setting Distance protection
relays.
Distance protection relays use the impedance characteristic of
the transmission line to decide the distance to the fault. Due to in­
accuracies in instrument transformers, relays, line data etc. the
protection is normally set to cover about 80% of the line on the
first instantaneous zone. Faults up to 80% from each line end is
thus instantaneously tripped by the close end relay. The central
60% of the line will be instantaneously tripped from both line
ends.

Figure 1. A Distance protection with impedance characteristic for a power


line.

On higher voltages where fast fault clearance is required from


stability point of view faults on the last 20% of the line are tripped
instantaneously by aid of communication with remote end.
The two sides can communicate through:

PROTECTION RELAYS SETTING

304 BA THS / BU Transmission Systems and Substations LEC Support Programme


Setting of Protection
- Radio link
- Power line carrier (PLC)
- Pilot wires
- Optical fibre

Figure 2. The principle for Distance protection relays communication.

PLC is up to now by far the most common communication link but

during the 90’th the optical communication has started to be­

come popular due to the possibility to send big amounts of infor­

mation between the stations.

The two distance protection relays mainly communicate in two

different modes:

- Tripping (permissive) mode


- Blocking mode

PROTECTION RELAYS SETTING

BA THS / BU Transmission Systems and Substations LEC Support Programme 305


In tripping mode instantaneous tripping is achieved by tripping

the circuit breaker as soon as acceleration signal is received from

remote end.

In blocking mode the accelerated step trips after a short time de­

lay Tko to have time to check that no blocking signal is received.

When protection relays operate in blocking mode reverse looking

elements are added at both ends to send blocking signal for re­

verse faults. Sometimes the blocking signal is sent for a criteria

-Fault (from undirectional element) but not forward. This can

mean that short unnecessary blocking pulses are sent for forward

faults due to differences in operating time for the undirectional

and the directional element. This can cause problems for relays

with true directional element reverse.

Line impedance.

Line positive sequence reactance is normally of size 0.32-0.4

ohms/km at 50 Hz for HV - MV lines. Line zero sequence reac­

tance is approximately 3 times the positive sequence value. Line

positive sequence impedance angle is normally 70-85° and zero

sequence value slightly lower.

The impedance to be covered by Distance protection is the line

impedance up to the fault plus an additional arc resistance which

is approximately achieved from the following formula:

Rarc = 28700* (a+2*vt) / I1.4 Ω (Warrington Volume 2)

The arc voltage has a square wave form and is of size 1–2.5

kV/m. This can also be used to estimate an arc resistance as:

Rarc = 1 - 2.5 • a/ I

where

a is arc length (m)

v is wind speed (m/s)

t is arcing time (s)

I is fault current (A)

Both formulas give approximate, similar, values.

Arc voltage as function of current according to tests at ABB. Dif­

ferent designations are tests at different occasions.

PROTECTION RELAYS SETTING

306 BA THS / BU Transmission Systems and Substations LEC Support Programme


Setting of Protection

Figure 3. Distribution of arc voltage and current at many tests in ASEA.

Typical values for “a” (arc length) are:

72,5 kV 4.0 m

145 kV 5.0 m

245 kV 7.2 m

400 kV 12 m

Tower foot resistance.

In addition to the arc resistance a tower foot resistance exists.

The tower foot resistance depends on the soil resistivity, the ef­

fectiveness of the tower earthing and possible available top lines

between the towers.

The primary impedance of the line is calculated to the secondary


side of instrument transformers by use of the formula: Zp = Up/Ip
Zs = Us/Is
Zs = Zp* (Us*Ip) /(Ip*Up)
where

Up/Us and Ip/Is is the voltage respectively the current transformer

ratio.

PROTECTION RELAYS SETTING

BA THS / BU Transmission Systems and Substations LEC Support Programme 307


Distance protection principle.
The required reactance and resistance reach is achieved by, in

principle, two different characteristics available. These character­

istics are “quadrilateral” and “mho” characteristics. It must be re­

membered that Rarc is a loop resistance whereas the distance

protection relays measures the phase value.

When load is transferred on a power line with generation at both

ends, an angle difference will occur between the two sources.

This will give a current through the fault resistance which is not in

phase with the current measured at the two line ends and will

thus partly be measured as an additional reactance by the dis­

tance protection.

The situation for a fault at far line end is indicated in below figure.

Figure 4. A fault at a remote station will due to infeed from other objects be
seen as much further off than it really is.

PROTECTION RELAYS SETTING

308 BA THS / BU Transmission Systems and Substations LEC Support Programme


Setting of Protection

Figure 5. The Distance protection export end will overreach when a fault re­
sistance is added in a double end infeed system. The import end will under­
reach.

The importing end will measure a higher reactance and thus un­
derreach and the exporting end will measure a lower reactance
and overreach. This must be compensated for, when a high resis­
tive cover is required, with a decreased zone 1 E/F setting at ex­
porting end.
For power lines in parallel on the same towers an additional prob­
lem occurs due to mutual coupling between the two lines. The
mutual reactance can for an earth-fault be approximately 0.5 •
X0L whereas for a phase fault the value is just a few percent of
XlL. The mutual coupling can for earth-faults cause an overreach
of normally 5-15% and need to be compensated for in setting of
distance protection relays' earth-fault reach.

The second, third and possibly fourth zones are set with imped­
ance and time to be selective to distance protection relays first,
second and third zones respectively in a remote station and to
the protection for other objects, e.g. transformers in remote sta­
tion.

PROTECTION RELAYS SETTING

BA THS / BU Transmission Systems and Substations LEC Support Programme 309


At setting the back-up zones consideration need to be given the
infeed of fault currents from other lines in the remote station and
the apparent increase of measured impedance. Distance protec­
tion in station A will measure a higher voltage, and thus a higher
impedance U/I than only current would have caused. This means
that a remote back-up function is mostly difficult to achieve in a
HV meshed system and local back-up is thus necessary.

Differential protection relays

Differential protection relays are used for busbars, transformers

and feeders to give instantaneous primary protection of the ob­

ject. Differential protection relays measure the difference in cur­

rent and are thus absolute selective protection as they will only

respond to faults within a certain zone.

Examples of differential protection relays are:

- Busbar differential protection


- Transformer differential protection
- Transformer restricted earth-fault protection
- Optical line differential protection
- Pilot wire differential protection

These relays are set according to setting instructions for respec­


tive relay. Below follows just a brief information of the principles
for the respective protection relay type.

Busbar differential protection RADSS and REB 103.


RADSS and REB 103 are medium impedance percentage re­
straint relays which are normally set to the required value at de­
livery.

PROTECTION RELAYS SETTING

310 BA THS / BU Transmission Systems and Substations LEC Support Programme


Setting of Protection

Figure 6. RADSS/REB 103 operating principle for one phase.

RADSS setting is made by adjusting the so called slope, adjusted


on resistors Rs, which give the stability line of the protection and
the resistor Rd11 which gives the total resistance of the differen­
tial circuit and thus the operation level of differential relay dR. Set­
ting of these resistors give the operation value of the protection
together with setting of the separate start relay SR, provided to
give two separate conditions for tripping. The start relay is set
higher than maximum through load thus providing stability for
open CT circuits under load conditions. REB 103 has fixed set­
tings of slope and Rd11 resistor due to the design ensuring that
the relay is always suitable for all switchgears and short circuit
levels.

PROTECTION RELAYS SETTING

BA THS / BU Transmission Systems and Substations LEC Support Programme 311


Transformer differential protection

Transformer differential protection relays are percentage restraint

differential relays, where operation level is in percent of mea­

sured current for external faults which gives a secure through

fault stability. This is a necessary requirement for transformer dif­

ferential protection relays as normal differential currents occurs

due to tap changers (TC).

For internal faults the sensitivity will be in percent of the trans­

former rated current.

The percentage setting of Transformer Differential relays shall be:

Max. TC error (from mid-end position) + Errors from CT and aux

CT + 15 (margin).

A high set unrestraint stage provides extremely fast tripping for

heavy internal faults. The unrestraint stage must be set above

maximum through fault current and above maximum inrush cur­

rent. If inrush currents are not known the following table can be

used as a general guide.

Connection Rated power Energizing from


High voltage side
- <10 MVA 20 x
Yy 10-100 MVA 13 x
Yy >100 MVA 8x
Yd - 13 x
Dy <100 MVA 13 x
Dy >100 MVA 8x

PROTECTION RELAYS SETTING

312 BA THS / BU Transmission Systems and Substations LEC Support Programme


Setting of Protection

Figure 7. The differential relay for a transformer needs to have phase angle
shift compensation and must have a percentage restraint to operate correct­
ly for through faults as the tap changer percentage error will be increased at
through faults. Stabilization is achieved with a summation (I1 + I2)/2

Restricted earth-fault protection

As earth-fault protection on solidly earthed transformers a Re­


stricted Earth Fault protection (REF) is often provided. ABB REF
type RADHD or SPAE 010 are high impedance protection, stabi­
lized against maloperation by setting the operation voltage just
above the maximum achieved voltage during external faults with
one CT core fully saturated, which is the worst case. The principle
is simple and will thus give fast operating relays. However the
type can only be used for differential relays where the same ratio
is available for all involved CT’s.
A voltage dependent resistor is connected across the relay to lim­
it overvoltages at internal faults as high voltages will be achieved
at internal faults as current transformers due to the high internal
resistance will immediately saturate with high CT output voltages
as a result.

PROTECTION RELAYS SETTING

BA THS / BU Transmission Systems and Substations LEC Support Programme 313


The required voltage setting UR is selected as:

Figure 8. The connection and principle for a Restricted Earth Fault protec­
tion (REF)

UR ~ IFmax (RCT + RL) where


IFmax is max through fault current at an external fault
RCT = Current transformer secondary resistance
RL = Maximum cable loop resistance seen from the summation
point

Calculated required voltage setting will give a primary sensitivity

Ip:

Ip = n • (Ir + Ires +∑Im) where

Ir = relay current is 20 mA +24° to +45° dependent


on the selected relay operating voltage

Ires= current through voltage dependent resistor MXA

Im= sum of magnetizing current to all CT's. Angle of magnetizing


current is -34° to -60° dependent on relay operation voltage, type

of CT and the core data.

n = current transformer ratio

Normally a restricted earthfault protection will get a sensitivity of

5-15% of transformer rated current with higher values (lower sen­

sitivity) when lower CT ratios are provided as the influence of

magnetizing current is increasing.

PROTECTION RELAYS SETTING

314 BA THS / BU Transmission Systems and Substations LEC Support Programme


Setting of Protection
Pilot wire differential protection.
ABB pilot wire differential protection type RADHL communicates
with remote end RADHL on a pair of pilot wires. The relay has a
fixed sensitivity for all types of faults, where the sensitivity differs
between fault types because of the summation transformer. An­
other relay based on the same principle is SOLKOR Rf from Rey­
rolle protection.
No setting is required for RADHL if no starting relays are provid­
ed. The starting relays shall (when provided), with sufficient mar­
gin, be set above maximum load current. If no starting relays are
provided the relay will operate for open or short circuited pilot
wires as the sensitivity will be below rated current in most phas­
es. Due to the summation type input transformer the sensitivity
will vary with fault type.

3. RELATIVE SELECTIVE PROTECTION RE-


LAYS

Overcurrent relays
Overcurrent relays are used as Back-up protection for short cir­
cuits and earth-faults for most types of objects. Overcurrent re­
lays are relative selective protection relays where selectivity is
achieved by a grading of current and/or time setting.
Overcurrent relays can be current selective, time selective or cur­
rent and time selective.

Current selectivity
Current selectivity means that two overcurrent relays are made
selective by grading of current setting, i.e. relay at A below is set
high enough not to detect faults at F3 or F4 which should be
tripped by the relay at B.

RELATIVE SELECTIVE PROTECTION RELAYS

BA THS / BU Transmission Systems and Substations LEC Support Programme 315


Figure 9. Current selective relays at A and B.

In practice this method can only be used when impedance R1 +


jX1 is of a relatively high value and thus limits fault current much
more than the variation in source impedance. This is normally
only the case where transformers are involved and a high-set
stage with a well defined limited reach can be used.
For example an instantaneous high-set stage on relay at B above
would detect faults in F3 but not in F4. A low-set delayed stage
would then detect faults at F4 and further on in the system. Relay
A can then be set on a higher value than relay B instantaneous
stage and need thus only be time selective against relay B instan­
taneous stage, as current selectivity is achieved between relay at
B and low set stage on relay at A.

Time selectivity
Time selectivity is used at many occasions to get selectivity be­
tween independent time delayed current protection relays and
fuses.

Figure 10. A Fuse and time selective overcurrent protection.

For the simple radial power system above, fuse tB will blow first.

A time delay t1 of 150-250 ms is then required on relay B to allow

this to reset after the fuse blowout.

Relay at A must then be set selective to relay at B by setting a

time t2 which allows relay at A to reset for a fault successfully

cleared by relay at B. Required margins are discussed below.

Disadvantage with time selective protection is that times start

adding and back-up trip times will be very long for a fault between

RELATIVE SELECTIVE PROTECTION RELAYS

316 BA THS / BU Transmission Systems and Substations LEC Support Programme


Setting of Protection
A and B where fault current is highest as the fault is closest to the
source.

Current and time selectivity


lnverse type protection relays with Normal, Very or Extremely in­
verse characteristic have operating time dependent of fault cur­
rent. Inverse type protection relays are simultaneously time and
current selective.

Figure 11. Inverse time delayed relays are at the same time current and time
selective.

Such relays can decrease back-up tripping times in a system


since operation time is decreasing with increasing fault levels.
In a radial system as below where current selectivity cannot be
achieved between different relays, inverse type characteristics
will give an advantage as shown by the selectivity chart below.
Comparison of independent (definite) time-lag relays and inverse
time-lag relays:

Definite time-lag. Inverse time-lag.


Easy to apply Selectivity plan elaborate
Simple selectivity plan Distribution of load and fault currents affects the
tripping time.

RELATIVE SELECTIVE PROTECTION RELAYS

BA THS / BU Transmission Systems and Substations LEC Support Programme 317


Tripping time independent of Large variations in short circuit power may give
the actual short circuit power. long tripping time.
Good correspondence between tripping time and
short time current rating of primary equipment.

Short circuit protection


When overcurrent relays are used as short circuit protection, fol­
lowing aspects must be considered at the setting.
Current settings shall:
- be high enough not to risk maloperation at maximum load cur­

rents.

- be low enough to give secure operation at minimum fault current

(tripping requirement)

Generally one shall not use lower current setting than required to

detect the occurring fault currents as this will only increase the

risk of unnecessary operations.

Margin to load
When selecting current setting, sufficient margin must be given
for maximum load currents. The margin allows the current relay
to reset when fault is tripped by an other protection and only load
current is flowing again or after e.g. a transformer inrush or a mo­
tor start. For modern static relays the reset ratio can be 90-98%
whereas for electromechanical relays the resetting ratio can be
70% or even less. This means that a setting of 1.3 times max load
can be sufficient for a static relay, whereas an electromechanical
relay requires a setting of 1.5 times max load. For H.V. side of
transformers setting should be 1.3 - 2 times load current for in­
verse type protection relays and 3-5 times load current for definite
time delayed protection relays to prevent maloperation for trans­
former inrush currents.

RELATIVE SELECTIVE PROTECTION RELAYS

318 BA THS / BU Transmission Systems and Substations LEC Support Programme


Setting of Protection
Margin to other protection relays

Figure 12. Setting of overcurrent relays must provide margin to maximum


load current.

Further to margin to load, a short circuit protection selective to a


short circuit protection in a remote station, may not detect faults
not detected by the protection in remote station. This means a
setting of I1, according to fig, to: I1set + I2set + I3set + I4set
where:
I2set > I3set >I4set

It should be noted in the above formula that the load currents


have a lower phase angle than fault currents, which can be used
to get a low set value when problem arises with sensitivity under
minimum conditions.
When directional protection relays are used, the directional ele­
ment, normally with operation angle of 60° lagging, should be set
lower than 0.25-0.5 times the current relay setting, to ensure a
secure and quick operation of the directional element at opera­
tion current of the protection. The directional relay should howev­
er preferably not be operated during normal load.
The 60° characteristic achieved on ABB directional relays, when
used as short circuit protection, gives operation for other angles
Ø when:
I > Is/cos (60- Ø).

RELATIVE SELECTIVE PROTECTION RELAYS

BA THS / BU Transmission Systems and Substations LEC Support Programme 319


Figure 13. Directional short circuit protection, e. g. type RXPE 42 have
60-65° angle on characteristic for maximum sensitivity.

Instantaneous stage
An instantaneous stages can be used as short circuit protection
for passive loads as motors, reactors capacitors etc. with no or
limited outfeed of fault current. It can be also be used for trans­
formers, where the impedance of the transformer gives a limita­
tion of the fault current to a, for through faults, well defined value,
little dependent of the source variations.

Figure 14. For a transformer an instantaneous stage can be used as the im­
pedance of the transformer will limit the fault current at a low voltage fault.

For the above transformer a low voltage fault will have a higher
fault power than:

RELATIVE SELECTIVE PROTECTION RELAYS

320 BA THS / BU Transmission Systems and Substations LEC Support Programme


Setting of Protection
An instantaneous protection can thus, with a margin, be set high­
er than this, which means that the relay will detect faults inside
the transformer, but will never reach through the transformer.
Further factors to be considered at setting of instantaneous stage
for this transformer are:
- Transient overreach of current relay, i.e. overreach due to DC
component in fault current. This overreach can on modern relays
be of size 2-15% whereas for older electromechanical relays it
can be 10-30%. Transient overreach is defined as (1 -K)/K where
K = quotient between the operation value for symmetrical AC
component with fully developed DC component and the opera­
tion value for symmetrical AC current without DC component.
- Differences in transformer short-circuit impedance due to tap
changer step. Impedance is normally given at mid-point and can
differ + 1-2% percentage units (or even more) at end taps. (Note
that given percentage impedance is valid for the voltage at re­
spective tap).
- Maximum inrush current must be lower than selected setting.
After considering these factors the instantaneous stage is nor­
mally set to cover maximum 80% of transformer and is thus a
complement to transformer differential and Buchholz protection
for internal faults.

Margin to minimum fault current (Tripping requirement)

Figure 15. The minimum fault current achieved for which the overcurrent re­
lay is required to be back-up must be detected.

When setting is calculated according to above it has to be


checked that the minimum fault current, normally for a two phase
fault, is sufficient to operate the relay. A margin factor to minimum
fault current of at least 1.5 is required.

RELATIVE SELECTIVE PROTECTION RELAYS

BA THS / BU Transmission Systems and Substations LEC Support Programme 321


Consideration must be given to the fact that two different inde­

pendent protection relays, operating on different circuit breakers,

shall be able to detect the fault. This means e.g. that a fault at the

far end of a distribution line or on the low voltage side of a trans­

former in the remote station must be detected under minimum

fault current conditions.

This is often difficult to achieve, and compromises on selectivity

under maximum conditions might be necessary to ensure suffi­

cient sensitivity under minimum condition.

The tripping requirement must always have priority, i.e. lack of se­

lectivity is preferred compared to failure to trip.

Margin to equipment capacity


At primary short circuits the plant is exposed to heavy mechani­
cal and thermal stresses. The mechanical stresses cannot be in­
fluenced by the protection relays but the thermal stresses are
dependent upon fault time (time to fault clearance). Following ex­
pression can be used
Ik2 • tk = I12 where
Ik = Acceptable short circuit current for time tk
I1 = short circuit capacity for time 1 sec.
Above formula can be used to calculate the thermal capacity for

fault times in range 0.5 - 5 sec.

When setting short circuit protection relays, back-up protection

tripping should be achieved before the thermal capacity of an ob­

ject is exceeded.

Earth-fault protection
The earth-fault protection measures the residual sum of the
three-phase currents and will thus not measure any current dur­
ing healthy condition. The setting of earth-fault protection relays
can thus be made independent of load currents. The current set­
tings will be dependent of the power system earthing.

Solidly earthed system


In a solidly earthed system contributions to fault current is
achieved from all system earthings, i.e. normally all transformer
neutrals. Earth fault currents are normally not transferred to other
voltage levels as earth-fault currents, except when autotrans­
formers are involved.

RELATIVE SELECTIVE PROTECTION RELAYS

322 BA THS / BU Transmission Systems and Substations LEC Support Programme


Setting of Protection
Directional earth-fault relays are often required to give a possibil­
ity of achieving selectivity, but it can also be possible by using
protection relays with inverse-time characteristic and same set­
ting on all objects. The faulty objects is then tripped first since
fault current always is bigger on faulty object than on the object
with the highest infeed.

Figure 16. The earth fault protection relays in a solidly earthed system.

Protection operation level is dependent on practises in each

country, - on requirement from telecom-systems - on requirement

from personnel safety (due to voltage on tower structures at

faults) etc. For voltages 100-400 kV the earth-fault currents re­

quired to be detected can be in range 100-400 A whereas on low­

er voltages the value can be as low as 50-100 A.

When power lines are not transposed the occurring unbalance

current in the system will cause problems for sensitive earth-fault

protection relays. Operating current should then be increased to

up to 70% of maximum load.

Low impedance earthed system


For low-ohmic earthed systems, where system earthing is a

zig-zag transformer with or without a low-ohmic resistor, or a

low-ohmic resistor directly in a transformer neutral, the fault cur­

rent is generated from one point only and selectivity can be

achieved by grading the time settings of the earth-fault protection

relays at different locations.

Required current setting is normally 10 - 30% of achieved maxi­

mum earth-fault currents and the same for all protection relays in

the system. A small increase of protection settings, moving to-

RELATIVE SELECTIVE PROTECTION RELAYS

BA THS / BU Transmission Systems and Substations LEC Support Programme 323


wards the source should be used to prevent random operation
due to differences in CT's and protection relays.
As a complement a stand-by earth-fault protection can be includ­
ed in the zig-zag transformer neutral. This protection is set on the
continuous thermal capacity current of the zig-zag transformer
and on a very long time (20-30 sec.)

High-ohmic earthed system


High-ohmic earthed systems are earthed in the same way as

low-ohmic earthed systems but with a high-ohmic resistor in the

neutral. The resistor is normally selected to give fault currents of

5 - 25 A.

Current relays with definite time delay are used and selectivity is

achieved by time-grading. Required current setting is normally 10

- 30% of maximum earth-fault current and close to equal for all


relays throughout the system. Directional earth-fault relays, mea­
suring the resistive component only, are often required due to in­
feed of capacitive earth-fault current from healthy objects.

Time settings
The required time interval, for time selective protection relays,
with definite time delay, is decided as follows:

Relay A Operating time measuring relay A


+ Time lag relay operating time A
+ Auxiliary relay operating time A
+ Breaker A total breaking time
= Total fault clearance time for A
Relay B Total fault clearance time for A
- Time lag relay operating time B
+ Reset time measuring relay B
+ Retardation (overshoot) time, time lag relay B
- Impulse time for auxiliary relay B
+ Margin between A and B
= Required setting protection B

When inverse time-lag relays are used the situation is slightly


changed. The required time setting will then be:

RELATIVE SELECTIVE PROTECTION RELAYS

324 BA THS / BU Transmission Systems and Substations LEC Support Programme


Setting of Protection

Relay A Operating time for time-lag overcurrent relay (at maxi­


mum fault current for which A and B relays must be
selective)
+ Auxiliary relay operating time A
+ Breaker A total breaking time
= Total fault clearance time for A
Relay B Total fault clearance time for A
- Retardation (overshoot) time for time-lag overcurrent
relay at B at maximum fault current for which relays
needs to be selective plus possible load from other
objects)
- Impulse time for auxiliary relay B
+ Margin between A and B
= Required setting protection B

For selectivity between inverse time-lag relays or fuses the selec­


tivity has to be checked for all fault currents.
Special consideration has to be given maximum fault current con­
ditions since tripping times then are shortest

Time margin between A and B should, for short circuit protection


relays, be 100 -150 ms to allow for errors and not risk any malop­
eration. For earth fault protection relays, where CT's are residu­
ally connected, the time margin should be increased to 150-200
ms due to the additional error caused by the summation of cur­
rent transformers in the three phases.

Overload protection
Thermal overload protection relays are often used as protection
of objects such as motors, small transformers, generators and re­
actors with relatively large time constants and risk of overheating
due to overload. Overload protection relays should be included in
the selectivity plan and are set to provide protection against ther­
mal damage of protected object.

Proposed settings: Overload protection relays are set on 1.02 x


Object rated current (complying to 1.04*Thermal content) and set
with a thermal time constant not exceeding the thermal time con­
stant of the protected object. If no temperature compensation is

RELATIVE SELECTIVE PROTECTION RELAYS

BA THS / BU Transmission Systems and Substations LEC Support Programme 325


provided, object time constant for highest surrounding tempera­

ture must be considered.

Note: If shunt capacitors are included in e.g. a motor circuit, the

contribution of these capacitors must be considered when calcu­

lating the nominal load current.

Voltage protection
Different types of voltage protection relays are used in a power

system.

Neutral point voltage protection is used as a back-up protection

for earth faults both on solidly, low-ohmic and high-ohmic earthed

systems. Open delta winding on voltage transformer is normally

selected to give 110 V secondary at a solid earth-fault. This is

achieved with a secondary VT voltage of 110 V for solidly earthed

system and 110/3 for high-ohmic and unearthed systems.

Normally a setting of 20V is used. When lower settings are used,

e.g. for generators (normally about 5 V) or SVS (Static Var Sys­

tem), a third harmonic filter is mostly necessary to prevent mal­

operation due to the in normal service occurring third harmonic

component.

Neutral point voltage protection cannot discriminate where on a

power system voltage the fault occurs and must thus be given a

time delay to allow earth-fault current protection relays to trip first.

Undervoltage protection relays can be used for different applica­

tions

As undervoltage protection relays for busbars with synchronous

and/or asynchronous motors. Synchronous motors can at under­

voltage quickly come out of synchronism and must thus quickly

be disconnected. Asynchronous motors will, after an undervolt­

age of longer duration, at voltage recovery require new starting

currents which, if many motors are connected to the same bus­

bar, can cause operation of current protection relays on higher

level in the selectivity plan. Thus asynchronous motors need to

be disconnected when long voltage drops occur.

Suitable settings

t = 0.15 s for synchronous motors

t = 0.4 s for asynchronous motors

RELATIVE SELECTIVE PROTECTION RELAYS

326 BA THS / BU Transmission Systems and Substations LEC Support Programme


Setting of Protection
As undervoltage protection on busbars with high priority loads,

where voltage protection will separate power systems and allow

high priority network to be undisturbed.

Suitable settings

U = 80% t = 0.4 s

Undervoltage protection relays need not be included in the selec­

tivity plan but must of course be coordinated. Firstly, with the sys­

tem voltage profile obtained in the voltage drop calculations, to

prevent tripping under conditions where the service can be main­

tained. Secondly, to obtain a load shedding or sectionalizing in an

orderly manner.

No-voltage (Zero voltage) automatic is used to open the circuit

breakers at loss of voltage and thus prepare for system restora­

tion after a disturbance. This automatic is set to operate after all

other protection relays.

Suitable setting:

U = 40% - 50%

and the protection must thus be given a time delay to allow

earth-fault current protection relays to trip first.

4. SELECTIVITY PLAN

Preparation
Necessary informations when starting to prepare the selectivity
plan are
- System diagram is needed to follow the distribution of fault and
load currents.
- Maximum short-circuit currents are needed to check the rating
of the relays. (It is very much needed to check the stability of ab­
solute selective protection relays, e.g. differential protection re­
lays.)
- Minimum short-circuit currents are needed to ensure that no
current relay is set too high to operate (tripping requirement) un­
der minimum fault condition.
- Maximum service currents are needed to check that no protec­
tion relays trip erroneously during permissible service conditions.

SELECTIVITY PLAN

BA THS / BU Transmission Systems and Substations LEC Support Programme 327


The maximum service currents and their order and duration for

different objects can be:

Transformers: Inrush current about 5-20 • In during the first peri­

od, decreasing 20% per period.

Motors: Starting current 1.5-8 • In lasting up to 25 seconds (dif­

fers a lot depending on type of load).

Busbars: Reacceleration current to all supplied objects of the cur­

rents (motors) after a net disturbance of short duration. Size and

duration can be obtained through voltage drop calculations.

- Relay characteristics are needed to decide upon the margins


between consecutive protection relays. The margins are influ­
enced by protective relay accuracy, setting accuracy, tempera­
ture range, auxiliary voltage variations, reset value and “point of
no return” for the relays.
- Breaker characteristics, especially the total breaking time, are
needed to calculate required margin between the consecutive
protection relays time setting.
Step by step instruction
1) Prepare yourself by assembling and calculating: single line di­
agram, system rated data, fault powers/currents plus relay block
diagram and relay characteristics on log-log paper (50 mm scale
factor). Inrush currents for transformers, start currents for motors
etc. are also assembled as indicated under 3.1 above.
If different voltage levels are involved, which is normally the case,
it's advantageous to use MVA (kVA) instead of currents in the se­
lectivity plan. After selecting MVA (kVA) setting for each relay the
setting is calculated to primary and secondary current for the ob­
ject.
Use 50 mm scale factor log-diagrams, semi-transparent, for your
selectivity plan. When only definite time protection relays are
used semi-transparent paper and relay characteristics are not
needed.
2) Start with settings of overcurrent protection relays and then
calculate settings of earth-fault protection relays. Selectivity must
be checked for faults on all objects.
3) Indicate time and MVA (kVA) scale on semi-transparent paper.
Same time scale as on relay characteristics should preferably be
used.
4) Start with the object lowest in the selectivity chain, where the
highest setting is foreseen. Calculate current and time setting, or
select time constant (on inverse type relays), for the relative se-

SELECTIVITY PLAN

328 BA THS / BU Transmission Systems and Substations LEC Support Programme


Setting of Protection
lective protection required to operate first for a fault on the object
where selectivity is checked. See section 2.2 for setting calcula­
tion.

Figure 17. Set the first relay to 50 A by putting 50 A matching 1 on the relay
characteristic sheets.

5) Put the semi-transparent log-log paper over the selected relay

curve and check that 1 sec. fits to 1 sec. and that selected MVA

setting fits to 1 (set current/power) on the semi-transparent and

the relay characteristic paper respectively. Draw the selected re­

lay characteristic on the semi-transparent paper.

Example of setting 50 MVA, k = 0.05 sec.

6) Calculate required current setting on next relay to operate ac­

cording to instructions under section 2.2 and find a suitable time

setting by trying with different k values and checking time and

current margin for all fault currents. Doing this it is advantageous

to add information about maximum and minimum fault cur­

rent/power at/through different objects on the semi-transparent

log-log paper.

Relay setting 150 MVA k = 0.1

SELECTIVITY PLAN

BA THS / BU Transmission Systems and Substations LEC Support Programme 329


Figure 18. Set next relay to 150 A by putting 150 A matching 1 on the relay
characteristic sheets. Draw the required curve giving sufficient time margin
for all currents achieved.

7) Repeat the procedure for all further protection relays required

to be selective.

8) Check that the back-up tripping times does not exceed thermal

capacity of the objects

9) Repeat the same procedure for earth-fault relays.

Check for faults at different locations, that short-circuit protection

relays will not give shorter tripping times and thus disturb the se­

lectivity for earth-faults. Doing this it must be remembered that an

earth-fault protection measures neutral current whereas

short-circuit protection measures phase currents.

Absolute selective protection relays in the selectivity plan


It can sometimes be advantageous to indicate instantaneous unit

protection relays in the selectivity plan to check that relative se­

lective protection relays are not interfering.

A differential protection is simple to indicate as it will operate for

certain current levels only and provide a fixed operating time of

20-40 ms.

SELECTIVITY PLAN

330 BA THS / BU Transmission Systems and Substations LEC Support Programme


Setting of Protection

Figure 19. A Differential relay can be indicated in the selectivity plan with
the operating time and a current range starting from maximum sensitivity.

An impedance protection is more difficult to indicate as the oper­


ation is dependent of the quotient Z = U/I which means depen­
dence of the power S = Un (ZS + ZL) where ZS is source
impedance and ZL is distance protection setting for each zone.
Un is rated line to line voltage. Representation of a distance pro­
tection in a log-log diagram will be as below.

SELECTIVITY PLAN

BA THS / BU Transmission Systems and Substations LEC Support Programme 331


Figure 20. A Distance protection with three stages can be indicated with the
time stages and impedance stages recalculated to MVA or current at nomi­
nal voltage and possible some other voltage level as a range for each stage.

Special problems at setting of protection relays

Figure 21. A generating station with many infeeds to a fault on an outgoing


feeder.

It should be noted that for a system with many infeeds such as


H.V. grid systems, the currents through relays of different loca­
tions can be quite different, which can give a situation like this.
In this case the same setting can be used on all relays with main­
tained selectivity since current through faulty object always is big­
gest. The same situation also appears for earth-current relays in

SELECTIVITY PLAN

332 BA THS / BU Transmission Systems and Substations LEC Support Programme


Setting of Protection
solidly grounded systems with many grounding points. Also for
one of many generator feeders a similar situation occurs.

Figure 22. Similar settings can give selectivity due to differences in fault cur­
rents at different locations.

SELECTIVITY PLAN

BA THS / BU Transmission Systems and Substations LEC Support Programme 333


5. SETTING EXAMPLES

Setting of short circuit protection relays in a distribution network.


For a power system the settings of short circuit protection relays
shall be calculated. The network is a distribution network as
shown in below figure.

Figure 23. The selectivity plan must cover setting of all the protection relays
in the network.

Start to­
1) assemble data
a) One-line diagram see fig.
b) Rated data see fig.

SETTING EXAMPLES

334 BA THS / BU Transmission Systems and Substations LEC Support Programme


Setting of Protection
c) protection equipment. All relays are of type RXIDK 2H with
normal inverse characteristic. Recovery (Overtravel) time is < 80
ms. Directional relay is type RXPE 42 with definite time delay
0.2-3 s.
d) Calculate fault power at all locations. Max and min values are
required. See fig.
e) All breakers have tripping time 60 ms
Fuse is of type SHB. 100 A = 1.9 MVA
2) Draw 100 A fuse characteristic on the log-log paper.
3) Calculate setting of short circuit protection A. Check required
setting with achieved selectivity. Note that A protection is only re­
quired to cover 11 kV faults as a fuse is a “secure break point”.
Fault clearance time of fuse is 10 ms. A setting 15 MVA k=0.05
gives selectivity. Time margin 140 ms at max fault current on 11
kV (t1).
4) Calculate required setting for relay B. Relay B must be selec­
tive to relay A allowing for load on other objects on 11 kV busbar.
IB set ≥ IAset + ILOAD

Set = 20 MVA, k=0.15.

5) Calculate required setting of relay C.

Same setting of inverse type element can be used as for relay B

as transformer any way always is disconnected and on an

achieved selectivity will delay backup tripping 300-400 ms for

fault within transformer and for faults higher up in system. As

transformer is D/Y a phase to phase fault on low voltage side will

have only 0.866 p.u. of current when H.V side has 1.0 p.u. in one

phase and 0.5 p.u. in the other two phases. This must be com­

pensated for by selecting a little higher setting. Set 25 MVA,

k=0.15.

6) Select setting of instantaneous element of relay C.

Maximum fault power fed through the transformer for a low volt­

age fault will be 87 MVA. Select a setting of 120% of max current

plus margin for transient overreach. RXIDK 2H transient over­

reach for instantaneous step is < 18%.

Set 1.2-1.18-87=125 MVA.

7) Select setting of relay D.

D must be given a current setting IsD>Isc+ILOAD

A setting ISD = 30 MVA gives a sufficient margin not to operate

SETTING EXAMPLES

BA THS / BU Transmission Systems and Substations LEC Support Programme 335


during normal load, and also fulfils above requirement since fault
and load currents are not in phase, and as load transmitting pos­
sibility is limited because the voltage has collapsed. A check with
different k values and setting 30 MVA shows that k = 0.2 is a suit­
able value.
8) Select setting of relay E.

In this case relay E is required to be selective to relay D although

disconnecting the same line. Only the breaker closest to the fault

may trip as stations are unmanned with quite a distance between.

E relay is set to ISE = 34 MVA which gives margin for differences

in current transformers and relays. Time curve k=0.3 gives selec­


tivity to relay D. Time margin 0.3 sec. with max fault current at sta­
tion B.
9) Setting of relay F delayed stage.

Relay F shall be set on IFset ≥ IEset + ILOAD (other object) and >

1.4-1.5 • In for the transformer. Note that at maximum service two


transformers are connected in parallel. Fault current will also be
split up between two transformers at maximum service but at
minimum service only one transformer is feeding.
Set IFset = 60 MVA k=0.4 which gives a suitable curve.
10) Select setting of relay F instantaneous stage.

Instantaneous stage is set as under item 6.

Set IFInst = 1.2 -1.18*345 MVA = 490 MVA.

11) Set directional short circuit protection relays G. Protection G

are intended to operate for fault current fed from parallel trans­

former for a fault in one transformer low voltage bay. Relays must

operate selective to relay F for all occurring fault current fed from

parallel transformer (Maximum 690/2 MVA)

Protection has an operating angle of 60° and can be set on rated

power of transformer or even below if required.

Set IGset = 40 MVA t = 0.4 sec. which gives time selectivity to pro­

tection on high voltage side (F) for all fault currents.


12) Setting is now completed and all settings can be calculated

in current for the appropriate voltage level and then to secondary

current for setting of the relay. Minor adjustments might be nec­

essary if settings are not steplessly. The required time margin be­

tween selective relays is checked according to item 2.2.4.

Required time difference will be (simplified).

This is fulfilled for all steps.

SETTING EXAMPLES

336 BA THS / BU Transmission Systems and Substations LEC Support Programme


Setting of Protection

Figure 24. The selectivity plan will have all relays in the network indicated
and the time margin must be checked for all selective relays. The sensitivity
for back-up protection to fulfil tripping criteria must also be checked.

SETTING EXAMPLES

BA THS / BU Transmission Systems and Substations LEC Support Programme 337


Setting of short circuit protection relays in a generation net­
work
To illustrate use of inverse type characteristics we shall set the
protection relays the net as shown on fig.

1) Assemble data.
a) One-line diagram see fig.
b) Rated data see fig.
c) protection equipment. All relays are type RXIDK 2H with “nor­
mal inverse characteristic”. Recovery (overtravel) time < 80 ms
d) Calculate fault power for busbar fault.

Figure 25. The selectivity plan shows that selectivity is achieved with similar
settings due to the differences in fault currents.

SETTING EXAMPLES

338 BA THS / BU Transmission Systems and Substations LEC Support Programme


Setting of Protection
Max and min value required. Min generation is 4 generators. e)
Breakers tripping time is 60 ms.
2) Draw selected settings of outgoing object on log-log paper.

Only highest setting need to be shown i.e. draw Al setting.

3) Max operating time for fault on outgoing feeder A1 is about

0.75 sec. i.e. min operating time on each generator must be high­

er than 750 ms + C.B. (60 ms) + RXIDK recovery (80 ms) + mar­

gin i.e. > 1.0 s.

Current setting on generator is set with margin to max load.

Select 52 MVA (1.3-In) k=0.2 which gives a suitable curve.

It is noted that although generator setting is lower than for outgo­

ing feeders selectivity is still achieved because of the big differ­

ence in fault current for each object compared to the total current.

Setting of Back-up earth fault protection relays in a transmission


network
RXIDG 2H inverse characteristic.
Back-up earth fault protection relays shall be set in system as
shown in figure.
1) Assemble data
a) One line diagram see fig.
b) protection equipment. All relays are ABB type RXIDG 2H with
specially designed inverse characteristic for back-up earth-fault
protection relays in a H.V. meshed system.
c) Calculate fault current contributions from the different objects
under different occurring service conditions.
d) Set RXIDG 2H operation level on required level for system lev­
el. Select 120 A primary. Time curve is fixed and will always give
selectivity if biggest infeed is less than 80% of fault current on
faulty feeder. Inverse time characteristic has a definite min level
which is selected to allow for single-pole tripping and autoreclos­
ing. Set this level to 1.2 sec.

SETTING EXAMPLES

BA THS / BU Transmission Systems and Substations LEC Support Programme 339


Figure 26. The logaritmic inverse characteristic will give selectivity if the big­
gest object fault current contribution is lower than 80% of the faulty object
fault current.

Final conclusion
The setting of time and current selective relays is a quite compli­
cated task. The preparation is very important in order to make a
good selectivity plan. It must be remembered that a incorrect set­
ting can cause big disturbances in the power network with high
costs (missing earnings) as a result. The work should thus be
performed carefully and the future should be predicted as far as
possible to ensure that selected settings are suitable also when
network is extended and changed.
Modern tools are today available to perform a selectivity plan, but
they must always be used with human control, where all results
are checked and confirmed by a experienced relay engineer, as
tools are never better than the programmer of the tool. The same
philosophy is adapted when using a tool as described above. The
tool is just taking away the need for semi-transparent paper and
the work of drawing the characteristic.

SETTING EXAMPLES

340 BA THS / BU Transmission Systems and Substations LEC Support Programme


Sub-divided Systems
1. SUB-DIVIDED PROTECTION SYSTEMS.
WHY?

The single failure criteria can be fulfilled with a protection system


including back-up protection. The back-up protection must be
able to detect all primary faults detected by the primary protec­
tion, primarily intended to clear the fault. There are two different
ways of arranging back-up protection:
Remote back-up is the common way of arranging back-up in a
distribution network. This means that the back-up protection is
available at another breaker. Remote back-up is normally
achieved by a time grading where the back-up protection is given
higher time setting than the primary protection.
Local back-up is used when remote back-up is difficult to achieve
or when time grading to achieve selectivity is not acceptable due
to thermal limits or network stability reasons. Local back-up
means that at the breaker location, a second protection relay de­
tecting the same faults as the primary relay, is included. The two
systems are operating in parallel on the same breaker.
The principle with local back-up is mainly used in the HV trans­
mission network where the fault current is fed from many different
directions.
When the local back-up is operating with same time and principle
as the primary protection, the protection system consists of re­
dundant protection.

2. SUB-DIVIDED PROTECTION SYSTEMS.


HOW?

As mentioned above the task of the protection system is to clear


the primary faults and the abnormal service conditions. The total
fault clearance chain consists of different parts as shown in below
figure.

SUB-DIVIDED PROTECTION SYSTEMS. WHY?

BA THS / BU Transmission Systems and Substations LEC Support Programme 341


Breaking Breaker Trip Cable
element mech coil

DC
supply
Cable

Meas Aux
relay relay

Cable

Figure 1. The different parts of the fault clearance chain

As noted the secured clearance of the fault includes correct be­


havior of many different elements, none of which is allowed to fail.
All sections can thus be said to have the same importance which
puts stringent requirement on the plant design.

When remote back-up is used the fault clearance is secured with


two different breakers including protection relays capable of de­
tecting same faults. The important care needed to be taken in
such cases is to ensure that the same DC supply, or at least bat­
tery feeder, is not used for two protection relays where one is be­
ing back-up to the other.

When local back-up, with or without redundant protection, is used


the fault clearance chain will normally be as shown in figure 3.

SUB-DIVIDED PROTECTION SYSTEMS. HOW?

342 BA THS / BU Transmission Systems and Substations LEC Support Programme


Sub-divided Systems

Figure 2. Fault clearance chain at redundant protection systems

A common practices used at redundant systems is:


- Different cores are used on the instrument transformers.
Duplication of apparatus is very unusual due to the high cost involved
and the very good operating statistic.
- The circuit breakers are not duplicated of cost reason. However dupli­
cated trip coils are used.
- The DC supply is separated as far as feasible.
For HV system the use of redundant batteries is common practices.
- Physical separation is performed as far as realistic.
Often cables are laid in different cable ducts.

As the circuit breakers are not duplicated, the failure of a breaker


to operate will mean that the fault is not cleared. In order to clear
the faults the surrounding breakers are then required to operate
instead. For applications where local back-up is required due to
failure of “remote” protection relays to detect the fault, a breaker
failure relay is thus essential. The breaker failure relay measures
the fault current still fed through the breaker after expected trip­
ping and will then trip all surrounding circuit breakers.
An example of the protection system including redundant protec­
tion, for a HV line, is shown in Enclosure 1 under Protection Line.

SUB-DIVIDED PROTECTION SYSTEMS. HOW?

BA THS / BU Transmission Systems and Substations LEC Support Programme 343


Instrument transformer circuits
The instrument transformers are normally not duplicated but only
provided with different cores for the two sub-systems. The redun­
dant protection systems are connected to different cores and any
mixture, where one current transformer core is feeding both
sub-systems, should be avoided. This also includes feeding an­
other type of protection e. g. the Busbar protection, when this is
included in the other sub-system, from the same core.
Any current loop feeding more than one panel should be avoided
due to the risk of open circuits at terminating point or in the ter­
minal itself (specially when this has a disconnectable link).
Both sub systems are normally connected to the same CT con­
nection box. Physical separation in different CT boxes is normally
not possible.

For voltage transformer circuits a common way is similarly to use


separate secondary windings for the two sub-systems. In some
cases two windings are not available and in such cases the cir­
cuits should be separated on different fuse groups in the mar­
shalling box. This is normally a fully acceptable solution due to
the high availability proven for voltage transformers.

Physical location in panels


- When sub-divided systems are used the physical location in panels of
the protection relays and of necessary auxiliary relays is of main impor­
tance.
- The common practices on the highest voltages is to use different panels
for sub 1 and sub 2 equipment. The reason for physical split-up is to pre­
vent problems due to e. g. cable fire or mechanical damage in a panel.

However in some cases where the sub-systems takes small

place it must be considered acceptable to put the equipment for

both sub-systems in the same panel.

The risk of cable fire or other mechanical damage which could in­

fluence two systems in the same panel must be considered neg­

ligible. Problems with mixture of circuits and mistake at erection,

commissioning or maintenance must be considered and steps

taken to ensure that this will not happen.

SUB-DIVIDED PROTECTION SYSTEMS. HOW?

344 BA THS / BU Transmission Systems and Substations LEC Support Programme


Sub-divided Systems
Two different objects in the same panel will give similar problems
and need careful split-up of the equipment both on panel front
and inside the panel to prevent service and maintenance person­
nel from doing mistakes.

Figure 3 Figure 4
Figure 3. The front layout of a relay panel for a HV line where the sub­
systems are with panel separation. The equipment included is as shown on
block diagram for a HV line, see Line protection section.

Figure 4. Arrangement of two sub-systems in a common panel.

From above follows that an important part at panel design is to


clearly indicate to which object the equipment belongs. When
sub-divided systems are used the sub-system belonging shall
also be clearly indicated. This includes clear separation of the
equipment and clear labelling of different sections, also on sepa­
ration parts between sub-systems or objects. The separation
must also be performed inside the panel by physically separating
the terminal groups for the different equipment in the panel.

SUB-DIVIDED PROTECTION SYSTEMS. HOW?

BA THS / BU Transmission Systems and Substations LEC Support Programme 345


A terminal numbering system allowing for visibility of sub-system

and circuit belonging is then an important part to simplify and en­

sure a correct design. ABB SUB/T has set up rules for terminal

numbering in sub-divided systems.

Please refer to Control System structure section for this number­

ing system.

All equipment used in the protection system and also other aux­

iliary relays connected to the same battery system, or fuse

groups, shall be grouped together and clearly labelled.

Remember to include the equipment for closing, interlocking etc.

which is located in the protection panel.

DC supply
The DC supply is one of the key parts at arranging back-up pro­
tection both when local and remote back-up are used. Many trip
failures causing large equipment damage have been caused by
DC failures.
The principle which must be followed is to ensure that the Main
and the Back-up protection are not fed from the same DC supply.
The level of independence can be different. On the highest volt­
age completely redundant systems are used which then includes
two separate batteries, two to three battery chargers etc.
For simpler applications it can normally be considered sufficient
to separate the battery main distribution in two sections and feed
the main and back-up protection from different sections or at
least different main fuses on the battery distribution.

A commonly used principle is to minimize the sub 2 DC distribu­


tion as much as possible. Preferable it should only be used in re­
lay panel and on breaker trip coil.

An example showing the design of a DC system with redundant


batteries is available in Appendix 1.

SUB-DIVIDED PROTECTION SYSTEMS. HOW?

346 BA THS / BU Transmission Systems and Substations LEC Support Programme


Sub-divided Systems
2.1 ARRANGEMENT OF TRIP CIRCUITS

Another main part of the protection system is the trip circuits.

A failure of the trip circuit will of course give a failure to trip the

breaker. As mentioned above the breaker itself is not duplicated

of cost reason and the only realistic means of improving depend­

ability is to use two trip coils on the breaker. This will cover prob­

lems with DC supply, the wiring or the coil but will not give any

advantage for mechanical problems.

Duplication of the trip coil is today possible on all EHV, HV and

MV circuit breakers and to a low cost.

Another mean of further improving dependability of the trip circuit

is to include trip circuit supervision relay/s. These can supervise

the circuit from the relay panel to the breaker and will detect open

circuit or loss of DC supply. The common principle used is to feed

a small current through the circuit. The current path will be broken

at open circuit or DC problems and an alarm is given.

It should be ensured that all wiring is included in the supervision.

Specially care must be taken when some trip contacts are provid­

ed in a different panel which can happen for transformer bays or

generator bays.

2.2 EXCHANGE OF INFORMATION BETWEEN THE


TWO SUB-SYSTEMS

The main principle used when sub-divided systems are utilized is


to avoid exchange between the two systems. As far as possible
the systems shall operate completely independent of each other.
This gives the highest total security as problems at design, main­
tenance etc. due to human or equipment failure are avoided.

In most cases however some signals are required to go to other


sub-system. The most common signals are:
- Start and block of auto-recloser.

SUB-DIVIDED PROTECTION SYSTEMS. HOW?

BA THS / BU Transmission Systems and Substations LEC Support Programme 347


Auto-recloser is normally not duplicated due to speed problems with two
units and due to the minor consequence a failure to auto-reclose will mean.
A number of signals will be required between the sub-systems to give au­
to-reclose also when only the protection in the other sub-system operates.
- Start of Breaker failure protection
Similar to Auto-recloser the Breaker failure function (BFR) is not duplicated
in redundant systems. The reason for this is however completely different.
The Breaker failure function has extremely high requirements on the securi­
ty against unnecessary trippings and duplication will mean an increased de­
pendability but the security will decrease. As the risk of breaker failure
statistically is very low the security aspect is most important and the BFR
function is only provided in one of the systems, normally in the primary pro­
tection system.

The exchange of information between the systems should be

handled with outermost care to prevent problems e. g. when

maintenance is done in one of the systems.

Interface relays should be put inside or on front on a preferable

separate labelled area in one of the panels only.

The terminals should also be clearly indicated inside the panel in

order to simplify the finding and opening of the correct terminals

when the sub-systems are to be separated.

Interface relays should be separately mounted and preferably in

sub 2 panel. This will limit the distribution of the sub 2 DC supply

as mentioned above.

SUB-DIVIDED PROTECTION SYSTEMS. HOW?

348 BA THS / BU Transmission Systems and Substations LEC Support Programme


Sub-divided Systems

Figure 5. Sub 1 -Sub 2 interface for a HV overhead line


An example of how an interface unit for sub 1-sub 2 interface can
be arranged for a HV line is shown in Figure 5. The example is
same as on Block diagram in Enclosure 1 to Protection Line sec­
tion and on the panel layouts Figure 3 and 4. The terminal num­
bering used is based on the standard terminal numbering
system, refer to section Control System Structure.

2.3 CABLING

A common requirement for sub-divided protection system is to

use different cable ways for the two systems.

Often this requirement is limited to e. g. use of different cable lad­

ders in the same cable duct. The sub 1 and Sub 2 signals must

under all circumstances be in different cables.

SUB-DIVIDED PROTECTION SYSTEMS. HOW?

BA THS / BU Transmission Systems and Substations LEC Support Programme 349


2.4 ALARMING AND TESTING

The protection system is designed according to “single failure cri­


teria”. This means that the “single failures” in the protection sys­
tem must be discovered within a reasonable time. An alarming of
secondary system faults is thus of same importance as the
alarming of primary faults. The alarms must be connected to give
remote alarms as well.

Some faults are not detected by the supervision equipment. To

detect these faults regular system testing and post fault distur­

bance analysis are of vital importance.

Testing and analyzing of protection system behavior gives a pos­

sibility to detect “hidden faults” such as failure in some parts of a

protection relay or problems with selected settings or with the

used measuring principle.

A correctly performed alarming and regular testing of the protec­

tion system will ensure that faults in the secondary circuits are

discovered and the fault clearance at an occurring primary fault

secured.

2.5 GENERAL ASPECTS ON SECURITY AND DE-


PENDABILITY

As mentioned the reason for redundant systems is to ensure the


local back-up i. e. secure fault clearance according to the “single
failure criteria”. This is fulfilled with the two independent systems
where one system can fail in any component of the fault clear­
ance chain but the fault clearance is still secured.

Adding extra equipment and/or cross tripping etc. to cover even


more than a “single failure” should be avoided as the security and
the dependability are in opposition and an increased dependabil­
ity will always lead to a decreased security.

More equipment, a more complicated and advanced protection


system, cross tripping, where protection relays in each systems
are connected to trip also in the other system, shall be strictly

SUB-DIVIDED PROTECTION SYSTEMS. HOW?

350 BA THS / BU Transmission Systems and Substations LEC Support Programme


Sub-divided Systems
avoided. The simple reason is that security is always lost and the
total reliability is dependent on both security and dependability.

Most unwanted trippings in sub-stations are proven to be depen­


dent of human mistakes. A basic principle at protection system
design should thus be to design the protection system simplest
possible but fulfilling the single failure criteria.

The design shall be such that human mistakes are avoided and
this includes mistakes during all stages of a project from basic
design where guide-lines are set, through detailed design stage,
erection, commissioning and maintenance.

It must be remembered that the life-time total cost of a plant is to


a big part including cost for service and maintenance and also
cost for availability. The cost of an unnecessary tripping can be
much higher than the initial cost increase to include some extra
equipment. Unnecessary equipment and complications should
thus be avoided.

SUB-DIVIDED PROTECTION SYSTEMS. HOW?

BA THS / BU Transmission Systems and Substations LEC Support Programme 351


2.6 CONCLUSION

Means to ensure a reliable redundant protection system are:


- Limit the mixing of equipment from different objects or from different
sub-systems in the same panel. When mixing, clearly label the equip­
ment on the front and also within the panel to indicate object or sub-sys­
tem belonging.
- A standardized terminal numbering system simplifies design and mini­
mizes mistakes at panel design and erection and commissioning.
- Avoid exchange of information between sub-systems as far as possible.
When signals between the sub-systems are required, indicate where
these circuits are located both on the front and inside the panel. A sep­
arate terminal group should be used.
- Keep design as simple as possible. Do not include extra equipment to
cover more “if's”. Extra equipment can increase dependability but will al­
ways mean a reduced security and thus a reduced reliability.

Appendix 1 A redundant battery system Block diagram

SUB-DIVIDED PROTECTION SYSTEMS. HOW?

352 BA THS / BU Transmission Systems and Substations LEC Support Programme


Sub-divided Systems

SUB-DIVIDED PROTECTION SYSTEMS. HOW?

BA THS / BU Transmission Systems and Substations LEC Support Programme 353


SUB-DIVIDED PROTECTION SYSTEMS. HOW?

354 BA THS / BU Transmission Systems and Substations LEC Support Programme


We hope you have found the content of interest and of use for your work.

The protection application is an area where primary system knowledge is of


vital importance and where the technology of the secondary equipment is
going through a very fast change with micro-processor technology giving
many advantages such as:

- Self Supervision minimizing your maintenance

- Internal intelligence allowing improved functions for service values check­


ing, event listing and disturbance recording which gives a much improved
reliability of the protection system if correctly used for post-fault analysis.

- Few spare parts and thus low spare part cost due to the hardware plat­
forms for each products where different software is provided to give the dif­
ferent functions.

- Improved protection functionality where the numerical technic with possi­


bilities to store pre-fault conditions etc. gives a possibility to improve the pro­
tection functions.
BOOK No 6

Revision 0

PROTECTION

APPLICATION HANDBOOK

ABB Transmission and Distribution Management Ltd BU TS / Global LEC Support

BA THS / BU Transmission Systems and Substations C/o ABB Switchgear AB

P. O. Box 8131 SE - 721 58 Västerås

CH - 8050 Zürich Sweden

Switzerland

ReklamCenter AB (99244) Printed in Sweden, ABB Support 1999-06

You might also like