Lightning Performance of Insulated Wires On Overhead Power Distribution Lines
Lightning Performance of Insulated Wires On Overhead Power Distribution Lines
ICLP 2010
LIGHTNING PERFORMANCE OF INSULATED WIRES ON
OVERHEAD POWER DISTRIBUTION LINES
Shigeru Yokoyama1, Tomoyuki Sato1,Sekioka Shozo2,and Yosuke Hashimoto3
1
Central Research Institute of Electric Power Industry (CRIEPI), Tokyo, Japan
2
Shonan Institute of Technology , Kanagawa-ken, Japan
3
Kyushu Electric Power Com.,Inc., Fukuoka-ken, Japan
email:[email protected]
1055-1
30th International Conference on Lightning Protection - ICLP 2010
(Cagliari, Italy - September 13th -17th, 2010)
(5-mm thick covering) is 6% to 7% higher than that Figures 3(a) (bare wire) and 3(b) (insulated wire) show
between the rod electrode and the bare wire in the time- an example of the application of a lightning impulse
to-crest value(Tƒ) range of 2 to 250 µs. voltage to the core conductor of a bare wire and an
(3) Discharge progressing manner from a rod electrode to insulated wire. When applied to the bare wire, the higher
a bare wire and an insulated wire strung equidistantly the lightning impulse voltage, the shorter the flashover
A bare wire and an insulated wire (2-mm thick time and the sharper the drop to zero voltage from the
covering) were strung equidistantly from the rod discharge point. On the other hand, for a insulated wire
electrode and we tested which wire is prone to a there is a drop in the voltage in an earlier stage, as shown
flashover. The gap length was fixed at 3 m for a negative in Figure 4, but thereafter, the voltage is increases
voltage and 7 m for a positive voltage. When a 50 % slightly, resulting in either no insulation breakdown or
sparkover voltage with a negative polarity was applied, insulation breakdown . In the case of the insulation
all sparkovers occurred to bare conductors. Figure 2(a) breakdown the voltage ultimately drops sharply.
shows the progressing manner of a discharge measured The first gentle voltage drop (A) indicates a flashover
using the ALPS (Automatic Lightning discharge on an insulator only. Since the capacitance of the
Progressing feature observation System[4])for impulse insulator section is fairly low compared to that of the
voltages of negative polarity. We can see that when the covering of an insulated wire, the insulator bears the
downward leader from the rod electrode progresses majority of an applied voltage, and the insulator section
through about 1/5 of the gap, and upward leader starts to is the first to sparkover. As the insulation strength of a
progress from the bare wire, while no leader occurs at all insulator wire covering is higher than that of the insulator
from the insulated wire. This phenomenon indicated section, at this moment no complete insulation
that the occurrence of an upward leader from an insulated breakdown occurs.
wire was delayed and the downward leader joined with Total insulation strength of the combination of an
the upward leader from a bare conductor at an earlier insulator and an insulation covering can not be
time. Note that when an overvoltage larger than V50 was determined clearly because the electric field of a
applied, pinholes were made in an insulated conductor, circumstance of a insulated conductor supported by a
even in cases where there was no flashover on the insulator is complicated and the mechanism of a surface
insulated wire, as shown in Figure 2(b). discharge after insulator sparkover is not fully clarified.
Experiments show different results on the increase rate of
3. Combined Insulation Breakdown Characteristics insulation strength of the combination to that of insulator
of Insulated Wire and Insulator [5] alone(or insulated wire alone) depending upon the kind
When an insulator (small capacitance) is combined of insulators and the thickness of insulated wire
with an insulated wire (large capacitance), the insulators’ coverings.
share of the applied voltage increases, resulting in
flashover occurring first on the insulator section. Whether
Rod electrode
flashover continues on the insulated wire after that varies
by conditions.
Rod electrode
1055-2
30th International Conference on Lightning Protection - ICLP 2010
(Cagliari, Italy - September 13th -17th, 2010)
Total insulation strength of combination of an insulator Table.1 Example of breakdown voltages of insulated wire
and an insulation covering is not the sum of the insulation on Clamp-top type insulator
strength of the insulator and that of the insulation
covering of an insulated wire , but 60-80% of the sum of Breakdown voltage(kV)
them typically[6]. One typical example of the breakdown Insulator Breakdown
type, Condition 50% flashover
voltages is shown in Table 1. Range
Average
voltage of
voltage of V0
Polarity value(V0) insulated V + V
insulator(V1) 1 2
wire(V2)
4. Line-Break Mechanism and Time-Current
LP-20 dry 249~264 255 162 179 0.75
Characteristics of Insulated Wire Breakdown Positive wet 235~247 239 159 175 0.72
Since the 6.6 kV power distribution lines in Japan are
operated as an insulated system, a ground fault LP-20 dry 227~244 231 177 210 0.60
current ,that flows in the case of a singe-phase ground Negative wet 224~244 232 174 180 0.65
fault, is several amperes at the most, and insulation LP-30 dry 297~324 308 212 179 0.79
frequently recovers in a short time, so that ground faults Positive wet 276~319 289 208 175 0.76
do not lead to a line break. dry 284~313 296 228 210 0.68
LP-30
When a two or three-phase ground fault occurs, a short Negative wet 272~284 277 235 180 0.67
circuit between phases occurs, and a short current of
several thousand amperes may flow. This short current
causes an insulated wire break. On insulated wire, the
location of inflow and outflow of a short current is fixed 5.Conclusions
on an insulation’s pinhole(Fig.5) caused by first Insulated wires have different characteristics from bare
insulation breakdown, and the arc heat concentrates on conductors in the viewpoint of lightning performances.
the pinhole, resulting in a line break in a short time. The authors have clarified the following characteristics of
Figure 6 shows the relationship between the arc current insulated wires by experiments in a laboratory and field
value and breaking time of ACSR 120 mm2 bare wire and surveys.
OC-ACSR 120 mm2 insulated wire[6]. The breaking time (1) Lightning discharge characteristics to an insulated
of insulated wires is extremely short (about 1/5 to 1/10 of wire and an overhead ground wire
the time for a bare wire). This indicates the high (2) Combined insulation breakdown characteristics of an
probability that the wire breaks before a substation relay insulated wire and an insulator
operates to interrupt the fault current. (3) Line-break mechanism due to Meltdown time-Arc
current characteristics of insulated wires
Pinhole
(a) Bare wire (b) Insulated wire
Fig. 3. Sparkovers in an insulator and an insulater wire
1055-3
30th International Conference on Lightning Protection - ICLP 2010
(Cagliari, Italy - September 13th -17th, 2010)
1
0.7
0.5
ACSR120mm2
0.3
Meltdown time(sec)
gap250mm
Naked wire
0.1 ACSR120mm2
0.07 gap50mm
Naked wire
0.05
0.03 OC-ACSR120mm2
Maximum value
Minimum value
0.01
0.7 1 3 5 7 10
References
[1] Y.Hongo, T.Saito, Y.Nikaido, T.Endo, H.Honda,
S.Yokoyama, “Observation of Lightning Performance on
Distribution Line at Shirakawa District in Fukushima
Prefecture by Still Cameras”, Proc.of IEEJ Annual
Conference, No.7-018, 2003 (in Japanese)
[2] Y.Hashimoto, S.Yokoyama, T.Yokota, and A.Asakawa,
“Studies on Characteristics of Lightning Stroke Distance
to Power Distribution Lines: Discharge Characteristics of
Open Wire and Insulated Wire,” Transactions of the
Institute of Electrical Engineers of Japan Vol.115-B,
No.12, pp 1508-1514, 1995(in Japanese)
[3] S.Yokoyama, “Lightning Protection of Overhead Power
Distribution Lines”, OHMsha, 2005 (in Japanese)
[4] S.Yokoyama, A.Asakawa, Y.Hashimoto, Y.Morooka,
“Lightning Stroke Attachment Characteristics of a
Covered Conductor and a Bare Conductor on Power
Distribution Lines”, ISH ’99, No.2.317,1999
[5] S.Yokoyama , K.Miyake , T.Suzuki and S.Kanao ,
“Winter Lightning on Japan Sea Coast -Development of
Measuring System on Progressing Feature of Lightning
Discharge - ” , IEEE Trans. , Vol.PWRD-5 , No.3 ,
pp.1418-1425,1990-7
[6] Sectional Committee for Distribution Lines, Lightning
Protection Design Study Committee, “Lightning
Protection Design Guide-Book for Distribution Lines”,
CRIEPI Report No.175030,pp.48-52, 1976(in Japanese)
1055-4