Monitoring Relay
for Tap Changers
Elektromotoren und Gerätebau Barleben GmbH
Table of Contents
Page
Company history 3
1. Preface 4
2. Design features 5
3. Function 6
4. Tests 7
5. Type list 8
7. Technical data 10
8. Versions/special designs 11
2
Company history
Since its foundation the company has passed through an eventful history with regard to
ownership, affiliation and change of name associated with such development.
3
Elektromotoren und Gerätebau Barleben GmbH
1. Preface
The monitoring relay for tap changers, also known as the protection relay for tap changers or oil flow
relay, is a monitoring device for insulating liquid-filled tap changers with conservators. It protects the
tap changer and the transformer from damage. The monitoring relay responds to excessive oil flow in
the direction of the conservator and generates a signal disconnecting the tap changer and the trans-
former immediately from voltage supply.
Elektromotoren und Gerätebau GmbH (EMB GmbH) provides more than 45 years experience in pro-
ducing monitoring relays and other protection devices for liquid-cooled and liquid-insulated applian-
ces. It ranks among the most distinguished manufacturers of this type of equipment.
EMB monitoring relays feature easy operation, high reliability and a very long life.
Our staff of highly qualified engineers and experienced skilled workers ensures top quality and high-
precision products. The casings are machined on modern CNC controlled machine tools. All products
are subjected to final inspection when all functions are checked using special test equipment.
Profound experience and expertise in this special field are a sound basis for high product quality.
Extensive references from reputed tap changer and transformer manufacturers as well as other users
are proof of the high qualitative level of the products.
EMB GmbH is certified to DIN EN ISO 9001/2008, DIN GOST R, IEC and AEO F.
Figure 1. - Certificates
4
2. Design features
5
Elektromotoren und Gerätebau Barleben GmbH
Switchgear
- Switching system
- Frame
- Mechanical testing unit.
- Damper
- Permanent magnet(s)
- Magnet contact(s).
The damper is retained in its normal and response positions by a magnet. Via a link the permanent
magnet is firmly connected with the damper and initiates the contact-making process of the magnet
contact tube.
3. Function
The monitoring relay is installed in the pipe between the tap changer and the conservator as close
as possible to the tap changer head.
During normal operation of the tap changer gases are generated which are collected in the gas
dome of the monitoring relay. If the gas volume exceeds the volume of the dome, the gas flows in
the direction of the conservator.
Fault: An incident causes an oil flow in the direction of the conservator.
Response: The liquid flow reaches the damper. If the flow rate exceeds the operating value of the
damper, the latter moves in flow direction.
This movement actuates a switch contact, and the tap changer and the transformer are
disconnected.
Gas
Oil
6
4. Tests
Each monitoring relay is provided with a works number that is specified on the test certificate and the
name plate. The tests carried out on the monitoring relay are recorded in the test certificate:
- Dielectric strenght test
- Leakage test
- Functional test
- Flow test.
Monitoring relays are delivered in cardboard boxes.
For each relay delivered the following documents in the language
agreed are provided:
- Operating instruction
- Test certificate.
Date of manufacture
Type
(week/year)
Type code/
damper setting
Figure 4.1. - Functional and leakage test Figure 4.2. - Flow test
7
Elektromotoren und Gerätebau Barleben GmbH
5. Type list
Weight
Pipe
Type Flange dimensions Device dimensions without
Type of connection diameter
Internal description (mm, in) (mm) packing
DN (mm)
(kg)
d1 d2 d3 d4 d5 f l h1 h2
12 Flange
(ÜRF 25/10) 4-hole 25 115 85 68 14 16 200 195 62 4.0
15 Flange
(ÜRF 25) 4-hole 25 115 85 - M12 15 160 185 62 3.6
16 Flange l1=200
(ÜRF 25/10-26) 4-hole 28* 115 85 - 14 16
l2=204**
195 62 4.0
170
75
h1
h2
R80
d5
f d1
l d4
d3
Figure 5.1. - Dimensional drawing, type 12 d2
170
75
h1
h2
R 80
d5
f d1
l d3
Figure 5.2. - Dimensional drawing, type 15 d2
170
75
h1
h2
R8
d5
f d1
l1
d3
l2
d2 * Suitable for pipe diameter DN 25 and 26 mm
Figure 5.3. - Dimensional drawing, typ 16 ** l2 = with sealing
l1 = without sealing
8
6. Switching system design options
Magnet contact tubes are used as switching elements. These are normally-open (NO), normally-
closed (NC) and change-over (CO) contacts. The magnet contact tube design can be derived from
the last two digits of the type code. For coding, see Ordering data/type code under Section 11. on
page 14.
13 11 1 13 23 11 21 13 11
14 12 2 4 14 24 12 22 14 12
22 24 12 14 24 12 14 22 12 14 14 24 34 14 24 12
14 13 24 23 14 13 24 23
34 33 12 11
The inner side of the cap accommodates a plate with the graphic symbol and the connection
diagram. The schemes show the switching systems in their neutral position. The neutral po-
sition is the operating condition when the device to be protected operates without any fault.
9
Elektromotoren und Gerätebau Barleben GmbH
7. Technische Daten
The technical data in the table apply to all monitoring relays of standard design manufactured by EMB.
Other versions and special designs are listed under section 8. on page 11. These additional
versions are provided with a separate code in the ordering data/type code.
10
8. Versions/special designs
Cable gland *
Explanation Code
M20x1.5: 1 cable gland and 1 dummy plug 1
M25x1.5: 1 cable gland and 1 dummy plug 2
M20x1.5: 2 cable glands 3
M20x1.5: 2 cable gland and 1 dummy plug (enclosed) 3B
M25x1.5: 2 cable glands 4
M25x1.5: 2 cable gland and 1 dummy plug (enclosed) 4B
1/2“ NPT: 1 cable gland and 1 dummy plug 6
1/2“ NPT: 2 cable glands 7
Cable gland: on customer’s request 9
Casing colour *
RAL 7001 (silver-grey) 41
RAL 7012 (basalt-grey) 42
RAL 7022 (umber-grey) 43
RAL 7033 (cement-grey) 44
RAL 7038 (agate-grey) 45
RAL 7035 (light-grey) 46
RAL 7016 (anthracite-grey) 47
RAL 9002 (grey-white) 48
RAL 7032 (siliceous-grey) 49
Insulation liquid
Insulating liquid, silicone oil 20
Insulating liquid on ester basis 21
Casing
Metal name plate 15
With bleeder valve 97
With gasket (ÜRF 25/10-26 only) 98
Customer’s request
Special request (as agreed with customer) 29
* Mandatory ordering data, for other mandatory data see section 11. on page 14
11
Elektromotoren und Gerätebau Barleben GmbH
9. Explanations on code 97
Monitoring relays for tap changers with bleeder valve (1) can be vented through the bleeder valve,
if required.
12
10. Use of monitoring relays in combination with Buchholz relays
EMB monitoring relays were developed to reliably protect tap changers and transformers from da-
mage. In the event of excessively high oil flows in the direction of the conservator a signal is sent that
immediately disconnects the tap changer and the transformer from voltage supply.
However, monitoring relays do not provide protection from gas accumulation as is required increa-
singly today for the protection of vacuum tap changers. In order to ensure both reliable protection
from excessive oil flows and warning in the case of gas accumulation, EMB monitoring relays of type
16 (ÜRF 25/10-26) can be combined with an EMB Buchholz relay of type 06 (BF 25/10). In this case,
the Buchholz relay also provides protection from loss of insulating liquid.
For that purpose, BF 25/10 is installed in series directly downstream of ÜRF 25/10-26. In the event
of an excessive oil flow, the monitoring relay will disconnect the tap changer from voltage supply. In
order not to affect this reaction, the damper of the Buchholz relay is usually set to a response value
of 3.0 or 4.0 m/s. The Buchholz relay will respond by generating an alarm signal in the event of gas
accumulations, and by disconnection in the event of loss of insulating liquid.
Technical data
Parameter Monitoring relay Buchholz relay
Type 16 (ÜRF 25/10-26) Type 06 (BF 25/10)
Voltage AC 5 V - max. 250 V AC 5 V - max. 250 V
DC 5 V - max. 250 V DC 5 V - max. 250 V
Current AC 0.01 A - max. 6 A AC 0.01 A - max. 6 A
DC 0.01 A - max. 6 A DC 0.01 A - max. 6 A
Switching capacity AC max. 1500 VA AC max. 1500 VA
DC max. 1250 W DC max. 1250 W
Dielectric strength:
- between electric circuit and earth AC 2500 V AC 2500 V
- between open contacts AC 2000 V (NO, NC) AC 2000 V (NO, NC)
AC 1000 V (CO) AC 1000 V (CO)
Gas accumulation - 250 ml ± 15 %
Insulation liquid flow 0.90 to max 1.5 m/s ± 15 % 3.00 to max. 4.00 m/s ± 15 %
13
Elektromotoren und Gerätebau Barleben GmbH
XX X. XX. XX. XX XX
Type (see section 5.)
Ordering example:
A customer needs a monitoring relay of type ÜRF 25/10 with cable gland and a dummy plug M20x1.5.
The damper should respond at a flow rate of 2.00 m/s. The switching system should be equipped
with 2 switching elements (magnet contact tubes). One contact should be normally-closed, the other
one normally-open. The device should be delivered in colour RAL 7033.
(Note: The unit is suitable for use of standard mineral oils and standard degree of protection IP 56)
Based on the above data the relay ordered has the following
14
12. Other products of EMB GmbH
Elektromotoren und Gerätebau Barleben GmbH also offers protective and control units for liquid-
insulated transformers and choke coils.
15
Elektromotoren und Gerätebau Barleben GmbH
- ZG 3.1.
The Buchholz gas flows through two different chemical solutions and the
colour reactions indicate the nature of the fault.
- ZG 3.2.
The Buchholz gas flows through two different test tubes, and the colour
reactions allow conclusions about the availability of carbon monoxide and
hydrogen.
16
Reflux lock ZG 4.1.
The device prevents insulating liquid from flowing into the gas testing de-
vice. The device is installed between the Buchholz relay or gas sampling
device and the gas testing device.
The test pumps check the function of the upper switching system (alarm)
of the Buchholz relay by pumping in air. The test can be performed direct-
ly on the Buchholz relay. For that purpose, the test pump is connected to
the test valve of the Buchholz relay. When the test is performed via the
gas sampling device, the test pump is connected to the gas outlet tap of
the gas sampling device.
The oil sampling device is connected to the Buchholz relay via a pipe and
is used to take oil samples from the Buchholz relay (suitable for use with
Buchholz relays with an oil drain plug). The pipe is supplied to customer’s
specifications.
17
Elektromotoren und Gerätebau Barleben GmbH
The Buchholz gas sampler provides a safe method of taking and trans-
porting gas samples from the Buchholz relay or the gas sampling device.
Its capacity is 100 ml.
18
12.4. Breathing buffer box
The breathing buffer box (G3B) installed in the breathing line of the trans-
former upstream of the desiccant solves this problem. It ensures hermetic
sealing of the transformer.
19
Elektromotoren und
Gerätebau Barleben GmbH
Hamburg
EMB GmbH
Otto-von-Guericke-Allee 12
D-39179 Barleben | Germany Hannover
Barleben Berlin
Magdeburg
Email: [email protected]
Frankfurt
Website: www.emb-online.de
www.buchholzrelay.com
München
Due to technical improvement of our products the information contained in this catalogue is subject to change without notice. We further
would like to apologize for any printing errors which have not been found despite intensive proof-reading. We assume no liability for
such errors. Thank you for your understanding.