Monitoring Modules For MPC-6000 & 7000 Control Panels: Features

The document summarizes intelligent interface modules for monitoring and controlling devices connected to MPC control panels. The 8702, 8703, and 8704 modules integrate microprocessors to interface and supervise dry contacts. The 8702 monitors a single contact while the 8703 monitors two contacts from one address. The 8704 also includes a relay in addition to contact monitoring. All modules use an LED to indicate status and are programmed using a portable programmer to set the electronic address non-volatile memory.

Uploaded by

Jakaria Shawon
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
116 views2 pages

Monitoring Modules For MPC-6000 & 7000 Control Panels: Features

The document summarizes intelligent interface modules for monitoring and controlling devices connected to MPC control panels. The 8702, 8703, and 8704 modules integrate microprocessors to interface and supervise dry contacts. The 8702 monitors a single contact while the 8703 monitors two contacts from one address. The 8704 also includes a relay in addition to contact monitoring. All modules use an LED to indicate status and are programmed using a portable programmer to set the electronic address non-volatile memory.

Uploaded by

Jakaria Shawon
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Monitoring Modules for MPC-6000 & 7000 Control Panels

Features
Intelligent Interface Modules for 8702, 8703 and 8704
• Interfaces and Supervises Normally Open Contacts

• Integral SPDT Relay (up to 4 amps) on 8704 Model

• Dual Input on 8703 Model using a single address

• Polarity InsensitiveTechnology

• Multi-color L.E.D. indicates status (green, amber, red)

• Easy front access to programming port and wiring terminals

• Mounts 4 inch square 2 ¼ deep box, or double gang box

• Dynamic Supervision

• Comes with 5x5 inch faceplate

• Two wire operation

• 8720 Device Program/Test Unit programs and Verifies


Device’s Address and Tests Devices functionality

• Electronic Address Programming is Easy and Dependable

• Listed, CFSM, NYMEA Approved

Introduction
The 8702, 8703 and 8704 Intelligent interface 8704 relay and contact device input are controlled
modules are designed to provide the means of at the same address. For the control panel system,
interfacing direct shorting devices to the MPC-6000 the relay and input contact can be controlled as a
& 7000 Control Panels. separate function. The relay is typically used where
control or shunting of external equipment is
The X1 Series Intelligent interface modules pro-
required.
vide the market’s most advanced method of ad-
dress programming and supervision, combined The 8703 is a dual input module and is designed to
with sophisticated control panel communication. supervise and monitor two sets of dry contacts.The
Each X1 Series interface module incorporates a Dual Input Module only requires one address but
microcomputer chip. The X1 Series microcomputer responds independently to each input. The 8703 is
chip technology and its sophisticated bi-directional ideal for monitoring a water flow switch and its
communication capabilities with the control panel, respective valve tamper switch.
achieve the state of an “Intelligence Device.”
The module has a multi-color Light Emitting Diode
Description that flashes green when operating normally, amber
if unit is in trouble condition, and red to indicate a
The X1 Series intelligent interface modules are
change of state. The 8704 red L.E.D. indicates a
available in three models. The 8702 and 8704 are
change of state in the relay.
designed to monitor a normally open dry contact.
The interface module reports the contact’s status to The device’s microcomputer chip has the capacity
the control panel. The 8702 model can only monitor of storing, in memory, identification information as
and report the status of the contact, while the 8704 well as important operating status information.
incorporates an addressable Form C relay. The

9609
FARADAY innovative technology allows all X1
Series intelligent interface modules to be pro-
grammed by using the 8720 Device Programming/
Test Unit. The 8720 is a compact, portable, menu
driven accessory that makes programming and
testing an interface device faster, easier and more
dependable than previous methods. The 8720
eliminates the need for mechanical addressing
mechanisms, such as program jumpers, DIP
switches or rotary dials, because the 8720 electroni-
cally sets the address into the interface’s micro-
computer chip nonvolatile memory. Vibration,
corrosion and other conditions that deteriorate
mechanical addressing mechanisms are no longer
a cause for concern.
The X1 Series modules are fitted with screw
terminals for connection to an addressable circuit.
The X1 Series modules are fully compatible
on the same circuit with intelligent detectors,
addressable manual stations or other addressable
intelligent modules.
All X1 Series intelligent interface modules are
UL listed.
Electrical Ratings
Environmental operating conditions for all 8700 Current Draw (Active or Standby):
Series modules are 32ºF (ºC) to 120ºF (49ºC) with a 1mA
relative humidity of not greater than 93% non-
condensating. 8704 Relay Ratings
Resistive:
4A, 125 VAC
Mounting Data 4A, 30 VDC
Addressable Interface Model 8702, 8703, 8704 Inductive:
mounts directly into a 4 inch square 2 ¼ deep 3.5A, 120 VAC (0.6P.F.)
box or a double gang box (user supplied). 3.0A, 30 VDC (0.6P.F.)
A 5 inch square off-white faceplate is included 2.0A, 120 VAC (0.4P.F.)
with each module. 2.0A, 120 VAC (0.35P.F.)
2.0A, 30 VDC (0.35P.F.)

Ordering Information

WARNING - The information contained in this document is intended only as a summary and
is subject to change without notice.The devices described in this document have specific
instruction sheets which cover various technical, limitation and liability information. Copies
Siemens Building Technologies, Inc. of these instruction sheets and the General Product Warning and Limitations Document,
8 Fernwood Road • Florham Park, NJ 07932 which also contains important information, are provided with the product and are available
from the Manufacturer. Information contained in these documents should be consulted
Tel: (973) 593-2600 • Fax: (973) 593-6670 before specifying or using the product. For further information or assistance concerning
Web: www.faradayfirealarms.com particular problems contact the Manufacturer.

5/06 2.5M SBT/IG May 2006 - Supersedes sheet dated 12/04

You might also like