Distributed to √ Areas:
All Areas Oceania Europe
China India NA
ASEAN and Others √ ME √ LA √
Taiwan Africa √ Brazil
NOTE ( )
Summary
Description
1. Applicable Models
Nominal Heat
Product Production Start of
Capacity Model Name Exchanger Model Code Power Source
Name Site Delivery
Capacity of AHU
2HP JDXF-2.0A1 2HP ZKHF3400000700
8HP
10HP JDXF-10.0A1 ZKHF3400001000
10HP
12HP
14HP
1PH/220-240V/50Hz, September
DX-Kit 20HP JDXF-20.0A1 16HP ZKHF3400001100 HAPQ
1PH/220V/60Hz 15th, 2019
18HP
20HP
22HP
24HP
30HP JDXF-30.0A1 26HP ZKHF3400001800
28HP
30HP
SG201924A
© 2019 Hitachi-Johnson Controls Air Conditioning, Inc.
New Products Information
Distributed to √ Areas:
All Areas Oceania Europe
China India NA
ASEAN and Others √ ME √ LA √
Taiwan Africa √ Brazil
NOTE ( )
2. Feature
(1) Enable combination of VRF system and large capacity AHU.
(2) Enable to correspond to custom requirement along with customer's specific project with combination
of VRF and AHU.
(3) Connection with 2nd Generation VRF outdoor unit is available.
(4) CE certified to EN60335-1, 60335-2-40, 62233, 55014-1, 61000-3-2, 61000-3-3 and 55014-2.
(5) Provide outlet air temperature control, inlet air (room air) temperature control and duty control.
Please refer to page 8 for the detail.
(6) Compatible with AHU including return air type, return air/fresh air mixing type and heat recovery
type.
(7) Compatible with central controller.
(8) The control box protection IP54 shall be installed to indoor unit or outdoor unit.
Flexible installation for expansion valve box.
(9) Suitable for complex facility, hotel, hospital, school and etc.
NOTE:
Duty control must be understood as a demand control, which signal is provided by an external Direct
Digital Controller (DDC).
The system capacity is fixed by an external input, which can be either a free voltage signal (0~10V or
0~5V) or a current signal (4~20mA).
Refrigeration Piping
VRF IDU
DX-KIT
Above: Expansion Valve Box
Below: Control Box
AHU
H-LINK
Central Station
SG201924A
© 2019 Hitachi-Johnson Controls Air Conditioning, Inc.
New Products Information
Distributed to √ Areas:
All Areas Oceania Europe
China India NA
ASEAN and Others √ ME √ LA √
Taiwan Africa √ Brazil
NOTE ( )
3. System Configuration
SG201924A
© 2019 Hitachi-Johnson Controls Air Conditioning, Inc.
New Products Information
Distributed to √ Areas:
All Areas Oceania Europe
China India NA
ASEAN and Others √ ME √ LA √
Taiwan Africa √ Brazil
NOTE ( )
SG201924A
© 2019 Hitachi-Johnson Controls Air Conditioning, Inc.
New Products Information
Distributed to √ Areas:
All Areas Oceania Europe
China India NA
ASEAN and Others √ ME √ LA √
Taiwan Africa √ Brazil
NOTE ( )
Appearance
< for JDXF-30.0A1 >
Dimensional
4 fixing screws
Drawing for the control
box cover
fixing bracket
Accessory
Accessory Qty Purpose
For Temperature of Sensing of
Outlet Air (red, 10m)
Thermistor 4 Inlet Air (blue, 10m)
Liquid Pipe (black, 10m)
Gas Pipe (yellow, 10m)
* Wired Controller is not included in the package. Please contact your distributor or dealer.
SG201924A
© 2019 Hitachi-Johnson Controls Air Conditioning, Inc.
New Products Information
Distributed to √ Areas:
All Areas Oceania Europe
China India NA
ASEAN and Others √ ME √ LA √
Taiwan Africa √ Brazil
NOTE ( )
NOTE:
When select AHU, the Heat Exchanger capacity and volume shall be within the range in the table above.
SG201924A
© 2019 Hitachi-Johnson Controls Air Conditioning, Inc.
New Products Information
Distributed to √ Areas:
All Areas Oceania Europe
China India NA
ASEAN and Others √ ME √ LA √
Taiwan Africa √ Brazil
NOTE ( )
7. General Specifications
・If the number of indoor unit connected in the system is the same or less than recommended: 1,000m
Maximum Total Pipe Length
・If the number of indoor unit connected in the system is more than recommended: 300m
Height Difference between When outdoor unit over indoor unit: 50m
Outdoor Unit and Indoor Unit When outdoor unit under Indoor unit: 40m
Temperature Control ** Inlet Air Temperature Control, Outlet Air Temperature Control, Duty Control
SG201924A
© 2019 Hitachi-Johnson Controls Air Conditioning, Inc.
New Products Information
Distributed to √ Areas:
All Areas Oceania Europe
China India NA
ASEAN and Others √ ME √ LA √
Taiwan Africa √ Brazil
NOTE ( )
8. Connection Ratio
ODU DX
Same as Left Same as Left
AHU
1 Outdoor Unit: 1 AHU ● 50% < Connection Ratio against ODU ≤ 100%
(Separate Type Heat Exchanger) ● All the AHU HEXs shall be the same capacity.
DX
● Max. number of DX-Kit connectable: 5
ODU DX
● Max. capacity of AHU: 96HP
HEX
Same as Left Same as Left
AHU
HEX
1 Outdoor Unit: Multiple AHU ● 50% < Connection Ratio against ODU ≤ 100%
● Different capacity AHUs can be connectable.
ODU ● Min. capacity of AHU:
DX DX Max. Capacity of Min. indoor unit capacity or
Single AHU in system Min. AHU capacity in a system
N/A N/A
32 to 60 HP 4.0 HP
62 to 90 HP 6.0 HP
AHU AHU
1 Outdoor Unit: AHU/IDUs < If max connection ratio against ODU is 50 to 100% >
● AHU Capacity : No Limitation
ODU ● Allowable AHU capacity in the system
DX (if multiple AHUs are connected in a system ): No Limitation
● Min. Indoor Unit Capacity
IDU
(If multiple Indoor Units are connected in a system):
SG201924A
© 2019 Hitachi-Johnson Controls Air Conditioning, Inc.
New Products Information
Distributed to √ Areas:
All Areas Oceania Europe
China India NA
ASEAN and Others √ ME √ LA √
Taiwan Africa √ Brazil
NOTE ( )
9. Temperature Control
(1) Inlet Air (Room Air) Temperature Control
● Capacity Control: For controlling inlet air (room air) temperature, capacity is adapted so that
detection temperature of inlet air (room air) reaches the set temperature by wired controller.
● Thermo-OFF Control: When thermistor detect inlet air (room air) temperature reaches the set
temperature by wired controller, the operation becomes Thermo-OFF.
A
Outlet Air Thermistor
Thermistor
A
A
Wired
Controller
ROOM
A
Outlet Air Thermistor
Thermistor
A
A
Wired
Controller
ROOM Fresh
SG201924A
© 2019 Hitachi-Johnson Controls Air Conditioning, Inc.
New Products Information
Distributed to √ Areas:
All Areas Oceania Europe
China India NA
ASEAN and Others √ ME √ LA √
Taiwan Africa √ Brazil
NOTE ( )
Installed just
before the DX coil.
A A
Thermistor Thermistor
A A Wired
Controller
ROOM
NOTE:
Wired controller JCWA10NEGQ does not support this control.
Please use another controller when using this function.
SG201924A
© 2019 Hitachi-Johnson Controls Air Conditioning, Inc.
New Products Information
Distributed to √ Areas:
All Areas Oceania Europe
China India NA
ASEAN and Others √ ME √ LA √
Taiwan Africa √ Brazil
NOTE ( )
(0-5V) < 0.4V ≥ 0.7V 0.7V 1.0V 1.2V 1.5V 1.8V 2.0V 2.3V
Duty Input (0-10V) < 0.8V ≥ 1.4V 1.4V 2.0V 2.4V 3.0V 3.6V 4.0V 4.6V
(4-20mA) < 5.28mA ≥ 6.24mA 6.24mA 7.20mA 7.84mA 8.80mA 9.76mA 10.40mA 11.36mA
Capacity (% of Normal) Thermo-Off Thermo-On 40% 45% 50% 55% 60% 65% 70%
(0-5V) 2.6V 2.8V 3.1V 3.3V 3.6V 3.9V 4.1V 4.4V 4.7V
Duty Input (0-10V) 5.2V 5.6V 6.2V 6.6V 7.2V 7.8V 8.2V 8.8V 9.4V
(4-20mA) 12.32mA 12.96mA 13.92mA 14.56mA 15.52mA 16.48mA 17.12mA 18.08mA 19.04mA
Capacity (% of Normal) 75% 80% 85% 90% 95% 100% 105% 110% 120%
Capacity
120%
100%
80%
Thermo Off
Thermo On
60%
40%
Wired Controller
A
Thermistor
NOTE:
Wired controller JCWA10NEGQ does not support this control.
Please use another controller when using this function.
SG201924A
© 2019 Hitachi-Johnson Controls Air Conditioning, Inc.
New Products Information
Distributed to √ Areas:
All Areas Oceania Europe
China India NA
ASEAN and Others √ ME √ LA √
Taiwan Africa √ Brazil
NOTE ( )
10. Installation
● Refer to the Installation Manual of DX-Kit for the detail of DX-Kit installation, Thermister installation,
other installation and Piping connection.
● Be sure to attach interlock for AHU protection.
SG201924A
© 2019 Hitachi-Johnson Controls Air Conditioning, Inc.