Belko Podporkin Analysis of Current Distribution Among Long-Flashover Arresters
Belko Podporkin Analysis of Current Distribution Among Long-Flashover Arresters
Belko Podporkin Analysis of Current Distribution Among Long-Flashover Arresters
(3)
(1)
I – current through the LFA-M, A.
tf – lightning impulse front time, µs
t50% – lightning impulse time to half-value, µs F. MOV arrester
Im – peak lightning current, A MOV arrester is defined by nonlinear resistance with VTC
n=5 – parameter defining current form steepness. [10]. For the study, a MOV arrester with classification voltage
D. Source of induced voltage surges of 21 kV at the in-phase current component of 1 mA was
chosen.
In case of lightning strike far from the line, the well-known
formula UIOV=28∙I0∙heff /y [1] is not applied for determination of III. CALCULATION RESULTS
induced overvoltages (IOV), since it is resulted in implausibly
Let's review a special case of a DLS with the lightning
high values of overvoltage, up to 5 MV at a distance of 1 m to
current of 40 kA, front time of 6 µs and time to half-value of
the strike point. Had such IOV values existed, that would have
75 µs. The lightnings with parameters not exceeding the above-
caused flashover of the whole insulation of the pole in 110 kV
said ones are registered in 70% of cases [11, 12]. The study has
line upon lightning strike into the cable even at minimum
an assumption that the lightning strikes into the outer conductor
lightning currents, but this does not occur in real situation. The
(phase А).
model used an assumption that the IOV value should be
TABLE I.
PARAMETERS OF SURGES THROUGH THE ARRESTERS IN CASE OF MID-SPAN
DLS
Im (kA)
RF (Ω) Phase tf / t50% (µs)
Pole 1 Pole 2 Pole 3 Pole 4 Pole 5 Pole 6
16.4 6.3
A — a
— — —
5/43 20/80
-0.6
10 B — — — — —
2/10
-4 4
C — — — —
25/100 25/100
16 4.7
A — — — —
5/33 10/120
-2.4 2.4
20 B — — — —
10/50 10/50
-3.6 1.2 2.4
C — — —
10/50 4/13 10/110
15.8 3.8 3.2 1.4
A — —
5/40 6/50 15/60 30/140
-2.8 2.8
30 B — — — —
12/60 12/60
-4.2 2.1 1.7 2.8
C — —
10/60 4/12 6/15 18/70 Figure 5. Surge currents through LFA-M upon mid-span DLS for RF=20 Ω
a. The arrester did not operate on the pole of this phase.
It should be noted that dangerous cases are those when two
or three arresters on one pole flash over; it can lead to two- or
A. Lightning strike far from substation three-phase short circuits with high fault currents. Other cases
Since the calculation is being made for the lightning strike result in current faults through the poles' footing resistances or
into the middle of the line, then current distributions among the in phase-to-ground faults.
arresters relative to the point of strike are symmetrical. Additionally, a peculiarity of arresters discharge "next
Therefore, the results from one side of the line only can be nearest" is observed, when a flashed over arrester on one phase
reviewed. The poles numbering starts from the point of transfers the potential to this pole, thus reducing voltage
lightning strike. between the pole and the other phases and preventing flashover
of the other arresters.
Table 1. shows the results of calculations of current
distribution in case of a mid-span DLS, i.e.: current peak, front Oscillograms of currents through operated arresters for the
time and time to impulse half-value, non-flashed over arresters mid-span DLS and RF=20 Ω are shown in Fig. 5.
are marked with “—”. Table 2. shows the results of calculations in case of
Traditionally, in lightning protection it is customary to lightning strike into the conductor close to the pole.
calculate an impulse duration as time until the moment of In case of strike in close vicinity to the pole, the situation is
reaching the current equal to half of maximum value of this identical, save that the peak current value ~30 kA is almost
impulse. It is reported that the current surge through the twice higher than in the previous case. This means that the
arresters mounted on phase A of the poles closest to the point closer to the pole the lightning strikes, the larger fraction of
of strike will be shortened in 1.5÷2 times from the impulse current runs out through the nearest arrester. Current
shape of 6/75 µs. Moreover, current peak value here is 16 kA. electromagnetic surge runs to the neighboring pole twice
In arresters of phases В and C of this pole, there occur back- longer; therefore, less current flows down through it than in the
flashovers with currents of 2÷4 kA (negative values in Table case of a mid-span strike. This impulse is 1.5÷2 times
1.) with no significant impulse reduction. Surges in other shortened relative to the reference one. Currents in distant
discharged arresters either have similar duration, or "elongate" arresters also elongate and in general align in values with the
up to 120 µs with front time of 15÷20 µs, but at the same time ones from the case of the mid-span DLS. Oscillograms of
having lower current values of 2÷3 kA. In real situation, full currents through operated arresters for the DLS close to the
impulse duration corresponds to the time of the lightning pole and RF=10 Ω are shown in Fig. 6.
current passage, but due to flowing of current through the poles
and running of its principal part out through the nearest Upon lightning strike with currents higher than 40 kA, the
arrester, the surge "top" in distant arresters is cut off, the picture of currents distribution among arresters is generally the
current drops slower there, thus technically "elongating" the same. Due to operation of large amount of arresters far from
reference lightning current shape. However, within the the strike, currents therein will not exceed 3÷4 kA. For
framework of usual terminology, where an impulse duration is arresters of pole 1, Im at lightning currents in the range of
determined as time of reaching a current value equal to 50% of 30÷100 kA can be evaluated in proportion by means of
the peak one, its "elongation" is observed here. changing values in Table 1 and Table 2 relative to 40 kA
lightning current.
TABLE II.
PARAMETERS OF SURGES THROUGH THE ARRESTERS IN CASE OF DLS CLOSE
TO THE POLE.
Im (kA)
RF (Ω) Phase tf / t50% (µs)
Pole 1 Pole 2 Pole 3 Pole 4 Pole 5 Pole 6
31.2 6.4
A — a
— — —
5/40 15/130
-6 2.9
10 B — — — —
18/75 15/70
-8.5 2.6 3.2
C — — —
10/55 5/12 25/90
29.7 4.6 4.2
A — — —
5/33 6/150 25/85
-7.5 1.2 2.5 2
20 B — —
8/42 5/20 12/35 30/100
-9.5 2 2.8
C — — —
10/50 5/20 12/80
29 4 3.4
A — — —
5/40 4/170 14/75
-8 1.4 3.2 2.3
30 B — —
12/70 4/12 12/25 25/100
-10.3 2.2 2.3 2.6
C — —
8/60 4/12 5/60 20/85
a. The arrester did not operate on the pole of this phase. Figure 6. Currents through LFA-M upon 40 kA DLS close to the pole for
RF=10 Ω
All impacts received due to 40 kA lightning strike with Therefore, influence of the substation proximity on the
impulse shape of 6/75 µs can be divided into 3 types: current distribution is felt on one side from the point of
lightning strike only. On the opposite side of the line the
a) Shortened impulse: with current peak value of 16 kA correlation with results of the off-substation strike is observed.
(mid-span strike), 30 kA (strike close to the pole) and current This very case determines more dangerous impact;
shape of 5/35 µs. consequently, it must be determinative.
b) Elongated impulse: with peak value of 2÷4 kA
current shape of 15/110 µs. It shall be noted that the current surge distribution in case of
no arresters will have a qualitatively similar picture. Instead of
c) Back-flashover impulse: with peak value of 3÷4 kA arresters discharge, there will occur flashovers of insulators,
(mid-span strike), 7÷9 kA (strike close to the pole) and current which the surge currents of design values and forms are
shape of 10/65 µs. flowing through.
B. Lightning strike near substation IV. CONCLUSION
Design model for this case is distinguished by the presence
(1) The paper presents the results of mathematic simulation
on one side near the substation of surge arresters grounded via
of 10 kV OHL upon direct lightning strike into the phase
0.5 Ω low resistance of the substation. A part of lightning
conductor. There have been obtained surge currents'
current is now flowing out through surge arresters, thus
distributions among arresters mounted on the poles depending
reducing the impact to the arresters from the substation side.
on the point of lightning strike and the footing resistance.
The study includes calculations of lightning strike at different
distances from the substation. As an example, Table 3 contains (2) Thee principal types of impulse actions that can be
the results for the case of DLS into the mid-span between poles recommended for running adequate tests and evaluating
2 and 3. The poles numbering starts from the substation. arresters' operational efficiency have been revealed.
In case of a near-substation DLS, current distributions are Shortened impulse with maximum current (it can be
asymmetric relative to the point of strike. Table 3 shows that named “main”). It has current peak value of ~40% of
the impulse on the side of substation in the arrester nearest to maximum lightning current upon mid-span DLS and
the strike is being shortened more than on the side of the line, ~75% in case of lightning strike close to the pole. Time
since a part of the current runs to the substation. The current to half-value is 1.5÷2 times less than that of lightning
impulses' shape on the side of the line is generally preserved, as current impulse.
in the case of the off-substation strike. The same can be said
about maximum currents. Poles 4÷7 suffer flashovers by one Elongated impulse with current peak value of 3÷4 kA
insulator per pole with phase rotation. and time to half-value 1.5 times longer than the
reference one.
TABLE III.
PARAMETERS OF SURGES THROUGH THE ARRESTERS IN CASE OF MID-SPAN DLS BETWEEN POLES 2 AND 3 NEAR SUBSTATION.
Im (kA)
RF (Ω) Phase tf / t50% (µs)
MOV Pole 1 Pole 2 Pole 3 Pole 4 Pole 5 Pole 6 Pole 7
3.2 4 16.1 16.1 6.5
A — a
— —
50/120 10/170 6/29 6/48 12/75
1.4 -1.5
10 B — — — — — —
20/60 18/70
2.6 2.2 -4 -3.6 4.1
C — — —
20/70 6/20 18/55 25/100 20/100
5.5 5 14.2 15.3 6 2.5
A — —
40/130 8/30 5/33 5/50 8/34 25/130
2.5 -5.2 2.6
20 B — — — — —
25/70 20/75 18/85
4.5 -5.2 -3 3.6
C — — — —
25/70 16/62 16/7 13/55
6.4 3 15 15.2 5.4 3
A — —
35/140 8/40 5/40 5/35 80/200 16/60
4.2 -3.4 -3.4 2.6
30 B — — — —
20/80 18/55 20/50 12/45
5.1 1.7 -4.6 -4.4 -4.7 1.8 2.6
C —
20/80 8/12 18/60 15/40 60/170 80/200 17/70
a. The arrester did not operate on the pole of this phase.
Back-flashover impulse with reference duration and [4] Podporkin, G.V., "Lightning Protection of Overhead Power Lines" (in
Russian), G.V. Podporkin, SPb: PH "Rodnaya Ladoga", 2015, 176 p.
current peak of 3÷10 kA at the lightning current of 40
kA. [5] Kostenko M.V., et al., "Physics of Lightning Discharge and Lightning
Protection of Overhead Distribution Lines"(in Russian), L.: Leningrad
(3) The current peak value of “main” impulse depends on Polytechnical Institute, 1982.
distance between the lightning strike point and the pole. It has [6] J.R. Marti, "Accurate modelling of frequency-dependent transmission
maximum value when lightning strikes to conductor just near lines in electromagnetic transient simulations", IEEE Transactions on
Power Apparatus and Systems, vol. PAS-101, No. 1, pp. 147-157,
the pole and decreases with the distance increase. January 1982.
(4) In case of a near-substation DLS, the picture is different [7] RD 153-34.3-35.125-99 Guide to Protection of 6-1150 kV Electrical
Circuits against Lightning and Internal Overvoltages (in Russian).
on the side of substation only, due to influence of the
substation's low grounding resistance. On the opposite side of [8] F. Heidler, J.V. Cvetic, B.V. Stanic, "Calculation of Lighting Current
Parameters", IEEE Transactions on Power Delivery, vol. 14, No. 2, pp.
the lightning strike, the distribution correlates with results of 399-404, April 1999.
the off-substation strike. [9] C. Mazzetti et al., "Volt-time characteristics reproduction of MV line
insulation under impulses similar to lightning induced overvoltages",
REFERENCES 28th ICLP, pp. 1448-1452, 2006.
[1] IEEE Guide for Improving the Lightning Performance of Electric Power [10] M.V. Dmitriev, G.A. Evdokunin, V.A. Gamilko, "EMTP Simulation of
Overhead Distribution Lines, IEEE Std. 1410-2010. the secondary arc extinction at overhead transmission lines under single
[2] M. Washino, A. Fukuyama, K. Kito, K. Kato, "Development of Current phase automatic reclosing", IEEE St.Petersburg PowerTech
Limiting Arcing Horn for Prevention of Lightning Faults on Distribution Proceedings, Report №15, June 27-30, 2005.
Lines", IEEE Transactions on Power Delivery, vol. 3, No. 1, pp. 138- [11] IEC 62305-1:2010 Protection against lightning. Part 1: General
152, January 1988. protection.
[3] G.V. Podporkin, V.E. Pilshikov, A.D. Sivaev, "Lightning Protection of [12] P. Chowdhuri et al., Parameters of Lightning Strokes: A Review, IEEE
Medium Voltage Overhead Lines by Modular Long-Flashover Transactions on Power Delivery, vol. 20, No. 1, pp. 346-358, January
Arresters", IEEE Transactions on Power Delivery, vol. 18, No. 3, pp. 2005.
781-787, July 2003.