Parts: Pivclass® Reader

The document provides installation instructions for various physical access readers, including parts lists and specifications for each reader model. It details the components included and recommendations for installation, and provides specifications for each reader such as input voltage, current draw, operating temperature range, cable lengths and UL reference numbers.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
98 views8 pages

Parts: Pivclass® Reader

The document provides installation instructions for various physical access readers, including parts lists and specifications for each reader model. It details the components included and recommendations for installation, and provides specifications for each reader such as input voltage, current draw, operating temperature range, cable lengths and UL reference numbers.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

INSTALLATION GUIDE

GOVERNMENT SOLUTIONS for Physical Access

R10-H, RP10-H, R40-H, RP40-H, RK40-H,


RPK40-H, RKCL40-P, RPKCL40-P, RKCLB40-P

pivCLASS® Reader
PLT-01134 A.7

Parts
1 - Reader and base plate assembly
1 - Installation guide
2 - Terminal connector - terminal readers only
RKCL40, RPKCL40 & RKCLB40 R10, RP10, R40, RK40, RP40 & RPK40
4 - M3.5 mm x 12 mm Phillips machine screw 2 - M3.5 mm x 12 mm Phillips machine screw
4 - #6-32 x .375” Phillips self-tapping machine screw 3 - #6-32 x .375” Phillips self-tapping machine screw
4 - #6 x 1.5” Phillips sheet metal screw 2 - #6 x 1.5” Phillips sheet metal screw
3 - #6-32 x .4375” Spanner security screw, anti-tamper (black) 1 - #6-32 x .375” Spanner security screw, anti-tamper
3 - #6-32 x .4375 Phillips security screw (black) 1 - Mounting gasket (optional, recommended for outdoor
1 - Mounting gasket installation)

Recommended
• C able, 6 conductor, 22 or 24 AWG [65 mm or 51 mm] Twisted Pair, Over-All Shield (Belden 3108A or equivalent) - RS-485-FDX +
power
• Cable, 4 conductor, 22 or 24 AWG [65 mm or 51 mm] Twisted Pair, Over-All Shield and UL approved (Belden 3107A, or equivalent) -
RS-485-HDX + power
• Cable, 6 to 9 conductor, 22 or 24 AWG [65 mm or 51 mm] Over-All Shield, (Alpha 1296C or equivalent) - Wiegand + power
• DC power supply
• Metal or plastic double-gang junction box - RPKCL40 / RPKCL40 / RKCLB40
• Metal or plastic single-gang junction box - R10 / RP10 / R40 / RP40 / RK40 / RPK40
• Reader spacer when using metal junction boxes - see pivCLASS How to Order Guide
• Security tool (for spanner security screw, anti-tamper) HID 04-0001-03

Specifications
pivCLASS Protocol
CURRENT
BASE PART INPUT VOLTAGE OPERATING UL REF
PRODUCT Standby Maximum CABLE LENGTH
NUMBER (VDC) PEAK3 TEMPERATURE NUMBER
AVG1 AVG2
R10-H 900NHR 60mA R10Ex1x2x3
100mA
RP10-H 900PHR 75mA RP10Ex1x2x3
200mA
R40-H 920NHR 65mA -30° to 150° F R40Ex1x2x3
110mA
RP40-H 920PHR 85mA (-35° to 65° C) RP40Ex1x2x3
RS-485 = 500 ft - 22 AWG
RK40-H 921NHR 85mA (152 m) RK40Ex1x2x3
12VDC 125mA 220mA 300 ft - 24 AWG
RPK40-H 921PHR 95mA (91 m) RPK40Ex1x2x3
RKCL40-P 923NPR -4° to 149° F RKCL40Ex1x2x3
150mA 185mA 250mA
RPKCL40-P 923PPR (-20° to 65° C) RPKCL40Ex1x2x3
14° to 122° F
RKCLB40-P 924NPR 165mA 215mA 275mA RKCLB40Ex1x2x3
(-10° to 50° C)
1
Standby AVG - RMS current draw without a card in the RF field. UL Reference Number Deciphering
2
Maximum AVG - RMS current draw during continuous PIV card reads. Not evaluated by UL. x1 Reader Colors: K = Black
3
Peak - highest instantaneous current draw during RF communication.
x2 Wiring: N = Pigtail, T = Terminal
x3 Communications: N = No Module, R = RS-485

hid g l o b al.com An ASSA ABLOY Group brand


INSTALLATION GUIDE pivCLASS R10-H, RP10-H, R40-H, RP40-H, RK40-H, RPK40-H, RKCL40-P,
RPKCL40-P, RKCLB40-P

Wiegand and OSDP Protocol


CURRENT1
BASE PART INPUT VOLTAGE OPERATING UL REF
PRODUCT Standby Maximum CABLE LENGTH5
NUMBER (VDC) PEAK4 TEMPERATURE NUMBER
AVG2 AVG3
R10-H 900N 60mA R10Ex1x2x3
100mA Communication Lines
RP10-H 900P 75mA Wiegand = 500 ft - 22 AWG RP10Ex1x2x3
200mA (152 m)
R40-H 920N 5-16VDC 65mA 300 ft - 24 AWG R40Ex1x2x3
-30° to 150° F (91 m)
110mA
(-35° to 65° C)
RP40-H 920P 12VDC for RS-485 85mA RP40Ex1x2x3
RS-485 = Max. bus length
4000 ft - 24 AWG
RK40-H 921N 85mA RK40Ex1x2x3
(1,219 m)
125mA 220mA
RPK40-H 921P 95mA RPK40Ex1x2x3
Max length between nodes:
RKCL40-P 923N 1,640 ft - 24 AWG (500m) RKCL40Ex1x2x3
-4° to 149° F
12VDC 150mA 185mA 250mA
(-20° to 65° C)
RPKCL40-P 923P RPKCL40Ex1x2x3

1
Communication protocols other than Wiegand UL Reference Number Deciphering
2
Standby AVG - RMS current draw without a card in the RF field.
or Clock & Data require an additional hardware x1 Reader Colors: K = Black
3
Maximum AVG - RMS current draw during continuous PIV card reads.
module which increases current by 30 mA.
Not evaluated by UL. x2 Wiring: N = Pigtail
4
Peak - highest instantaneous current draw during RF communication. T = Terminal
5
Wiegand Cable Lengths: 100 ft (30.5 m) 22 AWG @ 5 - 6.4VDC x3 Communications: N = No Module,
500 ft (152 m) 22 AWG @ 6.5 - 16VDC R = RS-485 (OSDP)

Installation
1 Mounting
Attach Backplate and Mounting Gasket to Junction Box.

Contactless Models Contact Models


Mounting holes for US single-
gang electrical boxes.
Install gasket for RK40 and
RPK40 models.

Mounting holes for US


double-gang electrical
Junction box not included. boxes.

Reverse Configuration Rotating the backplate


180° allows for placing the Contact reader on left
and the Keypad reader on right.
See Section B Reconfigure Reader Assembly for
instructions, before proceeding to Section 2.

This Installation Guide is for informational purposes only. HID makes no warranties, expressed or implied, in this summary. Company, product names and data used in sample output
are fictitious. Specifications are subject to change without notice.
© 2012 - 2017 HID Global Corporation/ASSA ABLOY AB. All rights reserved. HID, the HID logo, and pivCLASS are trademarks or registered trademarks of HID Global in the U.S. and/or
other countries. All other trademarks, service marks, and product or service names are trademarks or registered trademarks of their respective owners.

hid g l o b al.com An ASSA ABLOY Group brand


INSTALLATION GUIDE pivCLASS R10-H, RP10-H, R40-H, RP40-H, RK40-H, RPK40-H, RKCL40-P,
RPKCL40-P, RKCLB40-P

2 Wiring
Beeper GPIO1
GRN LED GP102
GND OC/TMPR
+VDC DATA1/CLK
DRAIN DATA2/DATA
RED GPIO3
HOLD GPIO4

ATTENTION
Observe precautions for handling
ELECTROSTATIC SENSITIVE DEVICES

GRN LED
Beeper
DRAIN
HOLD

+VDC
GND
RED
P1
Notes:

GPIO4
GPIO3
DATA2/DATA
DATA1/CLK
OC/TMPR
GP102
GPIO1
BEEP (YEL)
P2 1. Previous iCLASS readers had reversed RS-485 wiring
18 in
GRN LED (ORN)
GND (BLK)
+VDC (RED) (P2-7 & P2-6 - A & B). When upgrading to a pivCLASS
(0.46 m)
DRAIN (BARE)
RED LED (BRN)
HOLD (BLU)
reader, ensure proper connections as defined below.
GPIO1(RED/GRN)
GPIO2 (TAN)
OC/TMPR (VIO) 2. Wiring the reader incorrectly may permanently damage
DATA1 (WHT)
DATA2 (GRN) the reader.
GPIO3 (PINK)
GPIO4 (GRAY)
3. For cable lengths greater than 200 ft. (61 m) or EMF
interference, install 120Ω +/- 2Ω resistor across
RS-485 termination ends.
4. It is possible to reuse existing Wiegand wiring for
OSDP, however, using simple stranded cable (typical of
Wiegand access control readers) usually does not meet
Pigtail Reader Terminal Reader RS-485 twisted pair recommendations.
(Module position varies) (Terminal block and module
position varies)

Pigtail Terminal Description Pigtail Terminal Description


Yellow P1-1 Beeper Input Red / Green P2-7 *GPIO1/OSDP (RS485-FDX/HDX-A)
Orange P1-2 LED Input (GRN) Tan P2-6 *GPIO2/OSDP (RS485-FDX/HDX-B)
Black P1-3 Ground (RTN) Violet P2-5 **Open Collector Output / Tamper
Red P1-4 +VDC White P2-4 ***Wiegand Data 1 / Clock
Drain P1-5 Unused Green P2-3 ***Wiegand Data 0 / Data
Brown P1-6 LED Input (RED) Pink P2-2 *GPIO3 (RS485-FDX-Z)
Blue P1-7 Hold Input Gray P2-1 *GPIO4 (RS485-FDX-Y)

*RS-485 applicable for pivCLASS readers.


**Tamper Output - When activated, output synchronizes to ground (default).
***Dependent upon reader configuration. See the HTOG for Wiegand and Clock-in-Data configurations.

This Installation Guide is for informational purposes only. HID makes no warranties, expressed or implied, in this summary. Company, product names and data used in sample output
are fictitious. Specifications are subject to change without notice.
© 2012 - 2017 HID Global Corporation/ASSA ABLOY AB. All rights reserved. HID, the HID logo, and pivCLASS are trademarks or registered trademarks of HID Global in the U.S. and/or
other countries. All other trademarks, service marks, and product or service names are trademarks or registered trademarks of their respective owners.

hid g l o b al.com An ASSA ABLOY Group brand


INSTALLATION GUIDE pivCLASS R10-H, RP10-H, R40-H, RP40-H, RK40-H, RPK40-H, RKCL40-P,
RPKCL40-P, RKCLB40-P

3 Attach to Backplate
Contactless Models

Attach Reader Install Security Screw

Contact Models

Reversed Configuration: Slide Reader


Assembly to the left to lock.

Default: Slide Reader Assembly


towards the right to lock.

This Installation Guide is for informational purposes only. HID makes no warranties, expressed or implied, in this summary. Company, product names and data used in sample output
are fictitious. Specifications are subject to change without notice.
© 2012 - 2017 HID Global Corporation/ASSA ABLOY AB. All rights reserved. HID, the HID logo, and pivCLASS are trademarks or registered trademarks of HID Global in the U.S. and/or
other countries. All other trademarks, service marks, and product or service names are trademarks or registered trademarks of their respective owners.

hid g l o b al.com An ASSA ABLOY Group brand


INSTALLATION GUIDE pivCLASS R10-H, RP10-H, R40-H, RP40-H, RK40-H, RPK40-H, RKCL40-P,
RPKCL40-P, RKCLB40-P

4 Power & Testing


Contactless Models
Turn on power Test card

Contact Models

Note:
With a keypad reader operating as 26 bit emulation, upon power up you have 5 seconds to enter the Facility Code followed by #.
If unsuccessful, the reader LED displays solid Red. Power-cycle the reader and retry entering the Facility Code.
The Facility Code needs to be manually entered as 3 digits (for example, if the Facility Code is 10, enter 0-1-0-#).
SE readers only use Facility Codes between 1-255. There is no default Facility Code.
Once the Facility Code has been entered, the LED will display Violet and then to a final Red. Then power-cycle the reader.
When using a keypad, if there are 2 short beeps after entering your PIN, the reader does not have a Facility Code configured yet.
In this event, an Administrator will need to power-cycle the reader and enter the Facility Code before the reader will accept your PIN.

This Installation Guide is for informational purposes only. HID makes no warranties, expressed or implied, in this summary. Company, product names and data used in sample output
are fictitious. Specifications are subject to change without notice.
© 2012 - 2017 HID Global Corporation/ASSA ABLOY AB. All rights reserved. HID, the HID logo, and pivCLASS are trademarks or registered trademarks of HID Global in the U.S. and/or
other countries. All other trademarks, service marks, and product or service names are trademarks or registered trademarks of their respective owners.

hid g l o b al.com An ASSA ABLOY Group brand


INSTALLATION GUIDE pivCLASS R10-H, RP10-H, R40-H, RP40-H, RK40-H, RPK40-H, RKCL40-P,
RPKCL40-P, RKCLB40-P

A Biometric Reader
Proper Usage
Ensure a good quality Contact:
• Do not press too hard
• Do not move during image acquisition
• Leave your finger on the sensor at least 2 seconds
• Do not slide or roll your finger across the sensor

Cleaning
For optimum performance, it is recommended that the user clean the bio-reader periodically.
The use of a dry cloth is recommended to clean the acquisition surface.
Caution: Acidic liquids, alcohol or abrasive materials are prohibited.
In order not to scratch the surface, remove all dust and residue with gentle movements.

Acquisition Surface

This Installation Guide is for informational purposes only. HID makes no warranties, expressed or implied, in this summary. Company, product names and data used in sample output
are fictitious. Specifications are subject to change without notice.
© 2012 - 2017 HID Global Corporation/ASSA ABLOY AB. All rights reserved. HID, the HID logo, and pivCLASS are trademarks or registered trademarks of HID Global in the U.S. and/or
other countries. All other trademarks, service marks, and product or service names are trademarks or registered trademarks of their respective owners.

hid g l o b al.com An ASSA ABLOY Group brand


INSTALLATION GUIDE pivCLASS R10-H, RP10-H, R40-H, RP40-H, RK40-H, RPK40-H, RKCL40-P,
RPKCL40-P, RKCLB40-P

B Reconfigure Reader Assembly


The following steps reconfigure the reader assembly to position
the Contact reader component on the left side of the assembly.
1. Disassemble the reader.
• Remove the Keypad reader from the backplate
• Carefully unplug the ribbon cable from the module in the
back of the Keypad reader. Caution: Do not pull on the ribbon
cable as this may damage the connection to the connector.
• Remove the Contact reader from the backplate
Contact reader Keypad reader
• Gently pull the ribbon cable through the backplate

Ribbon cable

Backplate

Keypad reader
Contact reader

2. Reassemble with the Contact reader on the left side of the assembly.
• Rotate the backplate so that the large cutout for the power cable is on the left
• Gently route the ribbon cable back through the backplate slots, as shown below
• Plug the ribbon cable back into the module (back of Keypad reader) and ensure module is fully
seated into the reader
• Attach the Contact reader to the backplate (this must be installed first, as the Keypad Reader will fit
slightly over the Contact reader)
• Attach the Keypad reader to the backplate (power cable must be threaded through the large
square cutout on the backplate)
Ribbon cable
• Return to Section 2
Backplate

Contact reader
Keypad reader

This Installation Guide is for informational purposes only. HID makes no warranties, expressed or implied, in this summary. Company, product names and data used in sample output
are fictitious. Specifications are subject to change without notice.
© 2012 - 2017 HID Global Corporation/ASSA ABLOY AB. All rights reserved. HID, the HID logo, and pivCLASS are trademarks or registered trademarks of HID Global in the U.S. and/or
other countries. All other trademarks, service marks, and product or service names are trademarks or registered trademarks of their respective owners.

hid g l o b al.com An ASSA ABLOY Group brand


INSTALLATION GUIDE pivCLASS R10-H, RP10-H, R40-H, RP40-H, RK40-H, RPK40-H, RKCL40-P,
RPKCL40-P, RKCLB40-P

C Credential Presentation Best Practices


To ensure a successful read of a PIV card:
1. Hold card between the thumb and index finger.
2. Present the card so that the index finger creates a spacing between the card and the reader face.
Do not place the card flat on the reader.
3. Place the card parallel to the reader form factor. Do not angle to the right or left
4. Place the card parallel to the reader face. Do not angle the card up or down from the reader
face.

UL
Connect only to a Listed Access Control / Burglary power-limited power supply. These readers are intended to be used with listed (UL294) control
equipment.
All models are suitable for outdoor use.
Evaluated for use over Wiegand and RS-485 communications.
Evaluated for use with the M2000 pivCLASS Authentication Module as well as Standard Wiegand and OSDP panels.

FCC Certification
CAUTION: Any changes or modifications to this device not explicitly approved by manufacturer could void your authority to operate this
equipment.
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.

HID Global
Americas & Corporate Asia Pacific Europe, Middle East & Africa
611 Center Ridge Drive 19/F 625 King's Road Phoenix Road
Austin, TX 78758 North Point, Island East Haverhill, Suffolk CB9 7AE
USA Hong Kong England
Support: 866-607-7339 Support: 852-3160-9833 Support: 55 11 5514-7100
Fax: 949-732-2120 Fax: 852-3160-4809 Fax: 55 11 5514-7109

For additional offices around the world, see www.hidglobal.com corporate offices.
HID Global Customer Support: www.hidglobal.com/customer-service

Equipment
8T29 General Signaling
ACC Control Reader Equipment

h id g l o bal.com An ASSA ABLOY Group brand

You might also like