0% found this document useful (0 votes)
93 views53 pages

Profihub B5plus B5plusrd Manual en v301

Download as pdf or txt
Download as pdf or txt
Download as pdf or txt
You are on page 1/ 53

ProfiHub B5+R and B5+RD

User manual
Safety Guidelines
This manual contains notices which you should observe to ensure your own personal safety, as well as to
protect the product and connected equipment. These notices are highlighted in the manual by a warning sign
and are marked as follows according to the level of danger:

 Draws your attention to important information on handling the product, a particular part of the
documentation or the correct functioning of the product.

Warning
This device and its components may only be used for the applications described in this manual and only in
connection with devices or components that comply with PROFIBUS and an RS 485 interface.
This product can only function correctly and safely if it is transported, stored, set up, installed, operated and
maintained as recommended.

Qualified Technicians
Only qualified technicians should be allowed to install and work with this equipment. Qualified technicians are
defined as persons who are authorized to commission, to ground, to tag circuits and systems in accordance
with established safety practices and standards. It is recommended that the technicians carry a Certified
PROFIBUS Installer or Certified PROFIBUS Engineer certificate.

Disclaimer of Liability
We have checked the contents of this manual as much as possible. Since deviations cannot be precluded
entirely, we cannot guarantee full agreement. However, the content in this manual is reviewed regularly and
any necessary corrections included in subsequent editions. Suggestions for improvement are welcomed.

Copyright © 2017 PROCENTEC


All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted,
in any form or by any means, electronic, mechanical, photocopying, recording or otherwise, without the prior
written permission of the publisher.

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 2/53


Important information
Purpose of the Manual
This manual explains how to put the ProfiHub B5+R into operation.

Recycling and Disposal


The parts of the ProfiHub can be recycled. For further information about environment-friendly recycling and
the procedure for disposing your old equipment, please contact:

PROCENTEC
Klopperman 16
2292 JD WATERINGEN
The Netherlands

Tel.: +31-(0)174-671800
Fax: +31-(0)174-671801
Email: [email protected]

Document Updates
You can obtain constantly updated information on PROCENTEC products on the Internet at
www.procentec.com

You can also contact PROCENTEC Customer Support:


• by phone at +31-(0)174-671800
• by fax at +31-(0)174-671801
• by email at [email protected]

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 3/53


Important notices

WARNING
When the product is in use at an ambient temperature of 63 degrees Celsius or 145 degrees Fahrenheit, the
housing of the ProfiHub B5+ will be hot. Do not touch the housing!

At normal operating temperatures of 25 degrees Celsius, the temperature of the housing will not exceed 35
degrees Celsius.

WARNING
When the product is in use at an ambient temperature of 63 degrees Celsius or 145 degrees Fahrenheit, the
housing of the ProfiHub B5+ will be hot. Do not touch wires which are in contact with the housing!

WARNING
When the product is in use at an ambient temperature of 63 degrees Celsius or 145 degrees Fahrenheit, the
housing of the ProfiHub B5+ will be hot. Use wires suitable for these temperatures!

HOT HOUSING warning located on the side of the housing. Make sure this warning is visible after wall
installation. UL certification demands the warning to be visible during operation.

To comply with UL certification regulations (UL60950-1) the power supply must be a Limited Power Source
(LPS) or NEC Class 2 or CEC Class 2 that cannot exceed 100VA.

According to UL60950-1, if a copper PROFIBUS cable is used outside, it is required to install surge protection
that is suitable for PROFIBUS.

To comply with UL certification regulations the ProfiHub B5+ is to be used on altitudes under 2000 m.

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 4/53


Contents
Important information ............................................................................................................................................ 3
Important notices ................................................................................................................................................... 4
Contents .................................................................................................................................................................. 5
1. Product Description ............................................................................................................................................ 7
1.1 Product Features.......................................................................................................................................... 8
1.2 Application areas ......................................................................................................................................... 9
1.3 Additional Benefits ...................................................................................................................................... 9
1.4 Channel Structure ...................................................................................................................................... 10
1.5 Grounding System...................................................................................................................................... 11
1.6 Cable lengths for PROFIBUS DP ................................................................................................................. 11
1.7 Cable types for PROFIBUS DP .................................................................................................................... 12
1.8 Status LEDs ................................................................................................................................................. 13
1.8.1 The red error LED................................................................................................................................. 13
1.9 Comparison table ....................................................................................................................................... 14
2 Installation Instructions ProfiHub B5+R ....................................................................................................... 15
2.1 Location ..................................................................................................................................................... 15
2.2 Position ...................................................................................................................................................... 15
2.3 Mounting ................................................................................................................................................... 15
2.4 Power Supply ............................................................................................................................................. 16
2.5 Grounding of the power ............................................................................................................................ 17
2.6 Relay contact ............................................................................................................................................. 18
2.7 Backbone ................................................................................................................................................... 18
2.8 Spur Segments ........................................................................................................................................... 19
2.9 Termination ............................................................................................................................................... 20
2.10 Baudrate switch ......................................................................................................................................... 21
2.11 Robust Repeating Mode ............................................................................................................................ 21
2.11 Channel Redundancy ................................................................................................................................. 22
3 Diagnostics Device........................................................................................................................................ 23
3.1 Setting up the Diagnostics Device .............................................................................................................. 24
3.1.1 Enabling the Diagnostics Device .......................................................................................................... 24
3.1.2 Changing the default PROFIBUS address ............................................................................................. 24
3.1.3 GSD file ................................................................................................................................................ 25
3.2 Configuring the Diagnostic Device ............................................................................................................. 25
3.2.1 Info data (mandatory module) ............................................................................................................ 25
3.2.2 Alarm Confirmation ............................................................................................................................. 25
3.2.3 Redundant Status ................................................................................................................................ 25
3.2.4 Baudrate Status ................................................................................................................................... 26

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 5/53


3.2.5 Relay Status ......................................................................................................................................... 26
3.2.6 Power Status ........................................................................................................................................ 26
3.2.7 Termination Status .............................................................................................................................. 27
3.2.8 Channel Status ..................................................................................................................................... 27
3.2.9 Livelist Status ....................................................................................................................................... 27
3.2.10 Statistics (Short Format, Long Format ) ........................................................................................ 28
3.3 Parameterizing the Diagnostic Device ....................................................................................................... 30
3.3.1 Diagnostics........................................................................................................................................... 30
3.3.2 Statistics............................................................................................................................................... 31
3.3.3 Extended Diagnostics on Events change ............................................................................................. 31
3.3.4 Extended Diagnostics on Statistics change .......................................................................................... 32
3.3.5 Alarm Relay on Events change ............................................................................................................ 33
3.3.6 Alarm relay on Statistics change .......................................................................................................... 33
3.3.7 Changing the Diagnostics duration/timeout ....................................................................................... 34
3.3.8 Changing the Device Lost timeout ....................................................................................................... 34
3.3.9 Changing the data format .................................................................................................................... 35
3.4 ProfiTrace plugin for the Diagnostic Device ............................................................................................... 35
3.4.1 Installing the Plugin ............................................................................................................................. 35
3.4.2 Using the Plugin ................................................................................................................................... 37
4 Technical Data ProfiHub B5+R / B5+RD ....................................................................................................... 38
5 Order codes .................................................................................................................................................. 40
6 Glossary ........................................................................................................................................................ 41
8 Revision History ............................................................................................................................................ 44
9 Notes ............................................................................................................................................................ 50
About PROCENTEC ................................................................................................................................................ 52

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 6/53


1. Product Description
ProfiHub B5+R is an advanced, flexible and robust network component for PROFIBUS DP installations, to create
backbone structures and long multi-device star/tree segments.

PROFIBUS DP is a high speed communication bus that must comply with strict rules concerning spur lines,
because of possible reflections that could lead to communication disturbances. If spur lines or star segments
are required, costly investments in repeaters have to be done.

The innovative ProfiHub B5+R is the perfect component for such applications. It is an economic solution to
realise reliable spur lines in high speed DP networks. They have the functionality of 5 galvanic isolated
transparent repeaters. This allows network structures with extended spur lines that individually can handle a
maximum of 31 devices and a length equal to the main bus. The ProfiHub B5+R refreshes a received message
on one Channel and transfers it to all the other Channels (chicken foot topology).

Because the ProfiHub B5+R creates isolated segments, the devices can now be removed and added during
operation. Also most electrical bus problems and EMC disturbances in a spur do not spread to the other
segments. The intelligent logic and isolation circuits of the ProfiHubs do not change the bit width. This means
the ProfiHubs do not have limitations in serial placement. The logic also detects the transmission speed
automatically.

To assist the installation work, termination is integrated and can be switched on/off. The grounding concept is
also selectable: direct or capacitive grounding. The ProfiHubs are powered by a 10 to 24 DC Voltage. For
troubleshooting, maintenance and commissioning the ProfiHubs are equipped with LEDs on the outside, which
indicate the status of each Channel (Data and Error).

If bus redundancy is enabled, 2 segments will form a redundant pair which is completely compatible with the
ABB RLM01. An alarm contact is linked to events based on the status of the power supply and the bus
redundancy status.

Fig. 1 - ProfiHub B5+R

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 7/53


1.1 Product Features
• 5 Galvanic isolated outgoing channels (repeater segments)

• Advanced Diagnostic capabilities (B5+RD version only)

• Transparent for all PROFIBUS DP protocols

• DP - RS 485 specifications for each channel

• Cable redundancy for channel 4+5

• 9.6 Kbps to 12 Mbps.

• 31 devices per channel

• 1200 m spur line length (depends on transmission speed)

• Redundant power supply

• No limit in serial placement or cascading of ProfiHubs

• Alarm contact, with manual reset button

• No address required (except for the B5+RD option)

• Integrated termination facilities (switches)

• Configurable grounding system (direct or capacitive)

• IP 20 classification

• Increased temperature range

• DNV / offshore Certification

• UL approvals

Alarm contact Intelligent Internal Backbone

Main
C1 C2 C3 C4 C5
Bus

Power supply 1

Power supply 2

Main bus In Channel 1 to 5


Main bus Out

Fig. 2 - ProfiHub connections

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 8/53


DP backbone

Wiring problems do
Each spur not spread to the
line can be other spur lines
200m at 1,5
Mbps

Fig. 3 - Long spur lines to instruments and the possibility to remove/insert them during operation. Short circuit protection on each spur
line is automatically provided.

1.2 Application areas


• Dynamic spur lines to actuators, flow meters and pH analyzers
• Removable drives and motors
• Pull/Plug motor control centers (drawers)
• Roof mounted devices in tank farms
• Barrier for non galvanic isolated equipment
• Networks with requirement for High Availability/uptime
• Large star/tree structured networks

1.3 Additional Benefits


• Hot slave insertion and removal during operation
• Short circuit protection on each Channel
• Option to create a redundant path to other Hubs or ComBricks
• Compact and robust construction
• Status and error display (per Channel)
• Suitable for all DP cables
• Conveniently arranged networks
• Easy extendable installations
• On-board DB9 female connector on each channel for maintenance activities
• Cost Savings

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 9/53


Fig. 4 - Because of the isolation and intelligence the ProfiHub provides, it can be used as a barrier for electrically sensitive
segments. This keeps the backbone and other Channels clean.

1.4 Channel Structure


Each Channel is electrically isolated and internally connected to the transparent intelligent backbone. The
termination is switchable and powered by the ProfiHub. The shielding of the PROFIBUS cable can be directly
grounded or indirectly grounded (see the next paragraph).

RX-OK
Powered
ERROR Termination Term.
Switch

Intelligent Isolation RS 485 A


Backbone Circuit Circuit B

DGND I Indirect grounding


C C

Isolated Area
To direct grounding of
other Channels
Fig. 5 - Channel structure

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 10/53


1.5 Grounding System
The ProfiHub B5+R can be grounded by 3 methods:
1. Direct grounding on the Ground Rail
2. Indirect grounding (through a capacitor)
3. Combination of direct and indirect.

The power supply must be grounded directly on the Ground Rail. The shielding of the PROFIBUS cables can be
directly or indirectly grounded. If you do not want to ground all or some cables to the common ground, i.e.
compensating current, the cable shielding must be connected to pin ‘I’ which stands for Indirect grounding. A
capacitor with a parallel high value resistor will separate the 2 potentials ( Fig. 5), ensuring protection of the
signal against non-DC disturbances.

If by accident on 1 channel the Direct Grounding is connected with the Indirect Grounding, the connection to
the Direct Grounding bypasses the capacitor in the Indirect Ground connection. The current on the shield will
flow to Direct Ground.

1.6 Cable lengths for PROFIBUS DP


The cables on the Channels and the Main-Channel must comply with the PROFIBUS DP cable specifications for
RS 485 (Fig. 6).

Baudrate (kbit/s) 9.6 19.2 45.45 93.75 187.5 500 1500 3000 6000 12000

Segment length 1200 1200 1200 1200 1000 400 200 100 100 100
(m)
Segment length 3940 3940 3940 3940 3280 1310 656 328 328 328
(feet)

Example: 1000 m cable per channel at 187,5 kbps

Maximum 31 devices

Other channels
With the same Device Device Device Device Device Device
Cable length
Fig. 6 - Cable lengths for PROFIBUS DP

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 11/53


1.7 Cable types for PROFIBUS DP
The cable type must comply with the PROFIBUS DP cable specifications for RS 485 (Fig. 7).

Parameter Value

Wires 2 (twisted)

Impedance 135 .. 165 Ohm at 3 to 20 MHz

Capacity < 30 pF/m

Loop resistance < 110 Ohm/km

Wire diameter > 0.64 mm

Wire area > 0.32 mm2

Fig. 7 - PROFIBUS DP cable specifications

The ProfiHub B5+R can handle cables based on multiple protection sheaths with an overall cable diameter
between 6 to 12 mm (Fig. 8).

Robust cable Flexible cable

Hybrid cable Food cable Shipboard cable

Trailing cable Festoon cable FRNC cable

Fig. 8 - Cables with different protection sheaths.

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 12/53


1.8 Status LEDs
The Status LEDs on the ProfiHub are very useful for diagnostics.

OFF Blinking ON

POWER 1 / 2  Power is not switched  Power supply not ☺ Power supply OK.
on or an internal failure stable, redundant power
supply interrupted or an
internal failure

READY  Power is not switched  Trying to detect the ☺ The transmission


on or an internal failure transmission speed, but speed has been detected.
has not locked it yet

Main RX-OK  No communication ☺ 1 or more devices ☺ 1 or more devices


detected on the Main- communicating on the communicating on the
Channel Main-Channel Main-Channel

Main ERROR ☺ No problem has been  Problem in the cabling  Problem in the cabling
detected has been detected (Main has been detected (Main
Channel) Channel)

Channel RX-OK  There is no ☺ 1 or more devices ☺ 1 or more devices


communication detected communicating (on this communicating (on this
(on this Channel) Channel) Channel)

Channel ERROR ☺ No problem has been  Problem in the cabling  Problem in the cabling
detected has been detected (on this has been detected (on this
Channel) Channel)

INT. TERM Termination for this Internal failure Termination for this
channel is OFF channel is ON

1.8.1 The red error LED


The red error LEDs will blink shortly if a corrupt message enters the ProfiHub. More specifically, this can be a
Parity error (the parity checksum of the byte is incorrect) or a Framing error (the FCS byte is different than the
real message). It is necessary to investigate further with an oscilloscope to find out what the problem is. This
can easily be done with ProfiTrace.

Another reason for the red error LED for channel 4 or 5 is a problem in the redundant cabling (if the ProfiHub is
set to redundant). If the redundant line is fixed, press the ‘Alarm Reset’ button.

It can also be that the baudrate is not locked (no PROFIBUS master on the bus) or the baudrate was set
manually and incorrectly with the rotary switch.

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 13/53


1.9 Comparison table

ProfiHub A5 ProfiHub B5 ProfiHub B5+R / B5+RD

Area IP 65 IP 20 IP 20

Redundant power supply No No Yes

Temperature range -20 to +60˚ Celcius -20 to +60˚ Celcius -25 to +70˚ Celcius

Housing Plastic Metal Metal

Mounting Corner screws DIN-rail DIN-rail

Weight 800 g 650 g 650 g

Dimensions 213 x 210 x 95 mm 167 x 111 x 32 mm 167 x 111 x 32 mm

PROFIBUS connectors Screw terminals (inside) Screw terminals and DB9 Screw terminals and DB9
Glands (outside) connectors connectors

Alternative connectors Glands can be replaced by No No


M12 connectors

Termination LEDs No Yes Yes

Ground rail Optional Yes Yes

Redundant channel No No Yes

Diagnostics Device None None Yes, in B5+RD

Offshore approvals None None Yes

UL approvals None None Yes

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 14/53


2 Installation Instructions ProfiHub B5+R

2.1 Location
The ProfiHub B5+R can be installed everywhere in a non-hazardous area that complies with IP 20 (DIN 40 050)
and the specified temperature range of -25 to +70o Celsius.

2.2 Position
The ProfiHub B5+R can be installed in every position, but it is recommended to install it with the cables
pointing down. In this position it is also easier to read the status LEDs.

2.3 Mounting
The ProfiHub B5+R can be mounted on 35 mm DIN-rail with a minimum width of 167 mm. Mounting brackets
are available for mounting the B5+R directly on a wall. The ProfiHub B5+R has only been UL and DNV approved
with 35 mm DIN-rail mounting!

The supplied rubber studs need to be placed on the back of the housing of the ProfiHub B5+R for extra fixation.
This is to prevent the product to potentially slide off the DIN-rail. See Fig. 9 for an example.
When used in DNV environments these rubber studs need to be installed!

Fig. 9 – Rubber studs on backside of housing

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 15/53


2.4 Power Supply
To comply with UL certification regulations the power supply must be a Limited Power Source (LPS) or
NEC Class 2 or CEC Class 2 that cannot exceed 100VA.

The two 2-pin screw type power connectors are located on the left of the ProfiHub B5+R (Fig. 10).
1 = + (left)
2 = - (right)

Power LEDs

Alarm contact

Power
Connectors

Grounding points

Both
Fig. 10power
- Powerconnectors are
connectors and linked 1-on-1 to the internal power supply of the
LEDs

B5+R. If one power supply fails, the other takes over without delay time. When redundancy is not required, it is
sufficient to use one power connector. Please note that when using only one power supply, a voltage of max.
0.25 V will exist on the other unconnected power connector, as shown in Fig. 11.

If only one power supply is used, the alarm contact is closed. If two power sources are connected, the contact
is open. As soon as one of the power supplies fails, the contact will close and the Power Indicator LED will blink.

Fig. 11 – Maximum voltage on unconnected Power Connector

For UL certified installations the power supply must comply with the following specifications:
• Limited Power Source (LPS) or NEC Class 2 or CEC Class 2
• Voltage: 12 - 24 VDC
• Current: min 275 mA
• Wire diameter: < 2.5 mm2

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 16/53


Procedure
To connect the 24V supply to the 2-pin screw-type terminal, proceed as follows:
• Strip the insulation from the cable or the conductors for the 24V power supply.
• Add cable crimp terminals/wire ferrules to the conductors.
• Secure the crimp terminals in the screw-type terminal.

To connect the power supply, you need a 3 mm screwdriver.

Testing
If the power is switched on it can be diagnosed by the following indicators:
• LEDs should be blinking in a circular animation for a short time.
• The POWER LED of the respective power connector (1, 2 or both) is ON.
• The READY LED is ON or Blinking, depending on baud rate lock.

2.5 Grounding of the power


It is recommended to use a power supply with a ground lead (3-wire). Connect the ground lead of the
 power lead to the Ground Rail of the ProfiHub B5+R. Connect the Ground Rail to the common ground
with a separate ground lead. See Fig. 12 for an example.

Fig. 12 - Connection to Ground Rail

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 17/53


2.6 Relay contact
The ProfiHub B5+R features a potential-free relay contact. This alarm contact can be used to monitor the
power supplies. Example applications are: Connect a LED tower, alarm buzzer, SMS server or use it as a digital
signal for the PLC. On the B5+RD version the relay can also be used for alarming in case of retires, illegals, or
other events. For more information refer to Chapter 0.

If only one power supply is used, the alarm contact is closed after 60 seconds after start-up. If two power
sources are connected, the contact is open. When one of the power supplies fails for 3 seconds or more, the
contact will close and the Power Indicator LED will blink. If you are using only one power source and wish to
use the Relay contact, simply connect Power 1 to Power 2.

In the case of an interrupted power supply you can reset the contact by pressing the ‘Reset’ button. The
contact will open and the LEDs will stop blinking.

The Alarm contact is also switched when the ProfiHub is in Redundant mode and one of the redundant paths
fails.

The maximum power to be connected to the alarm contact is 24 VDC. The maximum current consumption is
500 mA.

It is advised to use a Limited Power Source (LPS) of NEC Class 2 or CEC Class 2 for powering the alarm contact.

2.7 Backbone
Connect the DP backbone cable to the bottom-left connector of the Main-Channel (Fig. 13). If the ProfiHub is
not the last device on the bus segment, connect the Bus-Out cable to the right connector of the Main-Channel
(Fig. 13). The second method is to place a PROFIBUS standardized plug with an in/out cable on the DB9
connector.

Communication Status
LEDs

DB9 Bus-In/Out
Connector

Bus-In Bus-Out
Connector Connector

Fig. 13 - PROFIBUS DP backbone connection

Pin layout of the screw terminals


Pin “A”: Green wire
Pin “B”: Red wire
Pin “I”: Indirect cable shielding
Note: Connecting the Indirect cable shielding is not required when the ground clips are used.

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 18/53


Testing
• If the Main-Channel recognizes valid PROFIBUS messages from one or more connected devices, the RX-OK
LED of the Main Channel should be blinking.

2.8 Spur Segments


Connect the spur segments to the connectors of Channel 1 to 5 (Fig. 14). The second method is to place a
PROFIBUS standardized plug on the DB9 connector of the specific Channel.

Channel
Channel
Connectors
Connectors

Communication Status LEDs

Channel
Channel
Connectors
Connectors

Fig. 14 - PROFIBUS DP spur connectors

Pin layout of the screw terminals:


Pin “A”: Green wire
Pin “B”: Red wire
Pin “I”: Indirect cable shielding
Note: Connecting the Indirect cable shielding is not required when the ground clips are used.

Testing
• If a Channel recognizes valid PROFIBUS messages from one or more connected devices, the RX-OK LED of the
Channel should be blinking.

According to UL60950-1, if a copper PROFIBUS cable is used outside, it is required to install surge protection
that is suitable for PROFIBUS.

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 19/53


2.9 Termination
The termination of the Main-Channel has been set to OFF by default. If the ProfiHub is the last device on the
segment, the termination must be set to ON (Fig. 15).

The termination of the Channels have been set to ON by default, because it is assumed that the new segment is
started at the ProfiHub (Fig. 15).

Termination LEDs

Termination of the
Channel
Channels (Default set
Termination of the Main Connectors
to ON)
Channel (Default set to
OFF)

Fig. 15 - Termination Switches

The termination LED of the corresponding Channel is activated when the termination switch is set to ON.

When the DB9 connector is used and the cable starts at the ProfiHub, it is recommended to use the
 termination on the DB9 plug and NOT the ProfiHub. This way, the connector can be removed while
maintaining termination on the bus.

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 20/53


2.10 Baudrate switch
The ProfiHub B5+R recognizes the transmission speed by default. If it is required that the ProfiHub B5+R is
locked to a certain transmission speed, the baudrate switch should be set to the required value (Fig. 16).

Baudrate switch

Fig. 16 - Baudrate speed switch

To set the rotary switch, use a 3 mm screwdriver.

Switch values:
0 = Normal repeating, Auto baudrate detect (default)
1 = fixed 9.6 kbps, diagnostics device ON (B5+RD only)
2 = fixed 19.2 kbps, diagnostics device ON (B5+RD only)
3 = fixed 45.45 kbps, diagnostics device ON (B5+RD only)
4 = fixed 93.75 kbps, diagnostics device ON (B5+RD only)
5 = fixed 187.5 kbps, diagnostics device ON (B5+RD only)
6 = fixed 500 kbps, diagnostics device ON (B5+RD only)
7 = fixed 1500 kbps, diagnostics device ON (B5+RD only)
8 = fixed 3000 kbps, diagnostics device ON (B5+RD only)
9 = fixed 6000 kbps, diagnostics device ON (B5+RD only)
A = fixed 12000 kbps, diagnostics device ON (B5+RD only)
B = Robust repeating, Auto baudrate detect, diagnostics device ON (B5+RD only)
C = Robust repeating, Auto baudrate detect, redundancy on channel 4 and 5, diagnostics device ON (B5+RD
only)
D = Normal repeating, Auto baudrate detect, diagnostics device ON (B5+RD only)
E .. F = Reserved for future use

Please note that the position of the rotary switch is only sampled during start-up. Changing the position of the
switch will not have effect during operation.

The auto baudrate detect feature will search for the correct baud rate within 10 seconds of receiving the first
telegram. This baud rate lock will be lost after 50 seconds of incorrect or no message reception.

2.11 Robust Repeating Mode


The B5+ has two repeating modes: normal (default) and Robust Repeating (rotary switch setting B or C). In
normal mode the bits are transferred directly on the other channel with a minimal delay (see delay times in the
Technical Data chapter). In Robust mode, the first byte is checked to verify if the following bits are a real
PROFIBUS message. If the byte is corrupt, the message will not be transferred to the other channel. This helps
network stability in EMC sensitive environments.

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 21/53


ATTENTION:
Using the ProfiHub B5+R in Robust Repeating mode causes a delay in processing the telegrams. It is required to
increase the default MinTSDR in the PLC busparameters slightly. Recommended is to increase the MinTSDR
with a value according to the Delay Time table, column ‘Robust Mode’, described in the Technical Data chapter.
Generally a MinTSDR of 25 is sufficient.

2.11 Channel Redundancy


To use the Redundancy option of the B5+R, set the rotary switch to the ‘C’ position.
This enables the last two channels (4 and 5) to be one redundant path to another B5+R, to a redundant
ComBricks, or to any other supporting product. See Fig. 17 for an example.

Both Hubs are in


redundancy mode

Fig. 17 - Redundant path between two ProfiHubs

The telegrams are transferred onto both redundant channels. The logic inside the ProfiHub determines which
telegram is used to be transferred onto the other channels. A message received by a redundant channel is
repeated on all other channels, except the other redundant channel. A message received by a normal channel
is repeated on all other channels.

When one redundant cable breaks, the other cable ensures safe delivery of the telegram. In this event the
built-in alarm contact will close. The red ‘ERROR’ LED will blink with an interval of 100ms. When the redundant
path is fixed, press the ‘ALARM RESET’ pushbutton to reset the alarm.

ATTENTION:
Using the ProfiHub B5+R in Redundancy mode causes a delay in processing the telegrams. It is required to
increase the default MinTSDR in the PLC busparameters slightly. Recommended is to increase the MinTSDR
with a value according to the Delay Time table, column ‘Robust Mode’, described in the Technical Data chapter.
Generally a MinTSDR of 25 is sufficient.

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 22/53


3 Diagnostics Device
The B5+R is available with a built-in Diagnostics Device option. The order code for this ProfiHub B5 with
diagnostics device is 17020RD.

The Diagnostics Device is a very versatile statistics/diagnostics logger. It can be used to keep track of the overall
PROFIBUS network health and inform the PLC or DCS of any network failure such as repeats or illegals, missing
ProfiHub termination, live list changes, or power supply problems. Audible or visible feedback is also possible
by automatically switching the integrated alarm relay.

This information can also be read easily with ProfiTrace because the Diagnostic Device sends this data over
PROFIBUS. This enables maintenance engineers to immediately identify the affected segment in case of cable
problems or instrument failure. Having a Diagnostics Device in your network dramatically decreases downtime
because problems can be solved much quicker; it tells you where to look. SCADA applications can make this
even easier.

▪ Live List
PLC/DCS 1 PLC/DCS 2 ▪ Lost, Syncs,
▪ Retries,
▪ Channel No.,
▪ Redundancy,
DP Device DP Device ▪ Power supply,
▪ Termination
▪ Etc…….

DP Device DP Device DP Device

Cable
problem

Fig. 18 – Cable problems or node loss can be identified by the ProfiHub channel, and send this information over PROFIBUS to the PLC.
ProfiTrace can also read this.

The following statistics and events are continuously monitored:

Events: Statistics:
Alarm Relay opened/closed Losts
Cable Redundancy change Syncs
Baudrate change Repeats (total)
Power input changed Repeats (max. changed in 1 cycle)
Termination of Channel changed Illegals
Communication on Channel stopped/started Internal Diagnostics
Livelist changed (station removed or added) External Diagnostics
Diagnostics while in Data Exchange

All of these events and statistics can be transferred in four different ways, so that the PLC/DCS or user can be
warned that something is happening in the PROFIBUS network: a PROFIBUS input message, a diagnostic
message, an external diagnostics message, or it can trigger the built-in alarm relay.

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 23/53


PROFIBUS input Diagnostic message External diagnostic alarm Alarm Relay action
message

Events: Statistics: Events: Statistics: Events: Statistics: Events: Statistics:


Livelist change Repeats Livelist change Repeats Livelist change Repeats Livelist change Repeats
Power change Illegals Power change Illegals Power change Illegals Power change Illegals
Redund. change Syncs Redund. change Syncs Redund. change Syncs Redund. change Syncs
….. ….. ….. ….. ….. ….. ….. …..

Fig. 19 - Ways of notifying the user in case of problems

3.1 Setting up the Diagnostics Device

3.1.1 Enabling the Diagnostics Device


To enable the Diagnostics Device in the ProfiHub, set the rotary switch on the top left side to any position from
1 to D (for a complete list of rotary switch settings, refer to the Technical Data chapter). Next, power-cycle the
device by removing power and applying the power again. The rotary switch position is only read during start-up
of the ProfiHub.

3.1.2 Changing the default PROFIBUS address


By default the address of the Diagnostic Device is set to 126. To change the address, use a configuration tool
which supports the ‘Set Slave Address’ command. Most configuration tools support this feature.

Fig. 20 - ProfiCaptain changes the address from 126 to 20

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 24/53


3.1.3 GSD file
Locate and download the appropriate GSD file for the Diagnostics Device on www.procentec.com/downloads .
The correct GSD file for the ProfiHub B5+RD is: PROC6970.gsd. The zip file also contains the corresponding
.bmp (Bitmap) files. Import the GSD file into your configuration tool and insert the device in the PLC hardware
configuration.

3.2 Configuring the Diagnostic Device


The Diagnostic Device has many configuration options. It can be configured modularly. This paragraph
describes all the available options per module in list order.

3.2.1 Info data (mandatory module)


There is only one mandatory module, which is the first module in the list (“INFO DATA MANDATORY ON 1 st
SLOT”). It has 4 input bytes with the following meaning:

Byte 1: Input Identifier byte (always 0xDE)


Byte 2: Device type byte (0xB5 is ProfiHub B5+R, 0xB2 is ProfiHub B2+)
Byte 3: Version byte: 0x01
Byte 4: Data format byte (0x00 is Little Endian, 0x01 is Big Endian)

3.2.2 Alarm Confirmation


Input Identifier byte: 0x01

The Alarm Confirmation module has one Output, which can be used to reset the alarm. If the Alarm Relay has
been triggered by any event (see paragraph 0), it can be reset by the PLC by sending 0x01 or higher to the
output of this module.

3.2.3 Redundant Status


Input Identifier byte: 0x10

The next input byte is to indicate the status of the redundant path. It is divided in nibble 0..3 and 4..7.

Nibble 1 (0..3) Meaning


1 dec Redundancy not used
2 dec Redundancy error left channel
3 dec Redundancy error right channel
4 dec Redundancy error both channels
5 dec Redundancy OK
Nibble 2 (4..7)
1 dec Pending Alarm: Redundancy error left channel
2 dec Pending Alarm: Redundancy error right channel
3 dec Pending Alarm: Redundancy error both channels

Examples: 0x12 means Redundancy error on Left Channel, Pending alarm on Left Channel
0x05 means Redundancy OK

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 25/53


3.2.4 Baudrate Status
Input Identifier byte: 0x11

The next input byte is to indicate the baudrate lock status.


Dec Meaning
1 No baudrate detected
2 9.6 Kbit
3 19.2 Kbit
4 45.45 Kbit
5 93.75 Kbit
6 187.5 Kbit
7 500 Kbit
8 1.5 Mbit
9 3 Mbit
10 6 Mbit
11 12 Mbit

3.2.5 Relay Status


Input Identifier byte: 0x12

The next input byte is to indicate the alarm relay status.


Hex Meaning
00 Relay is off
01 Relay is on

3.2.6 Power Status


Input Identifier byte: 0x13

The next input byte is to indicate the status of the power inputs.
Nibble 1 (bit 0..3) Meaning
0 Power 1 is active
1 Power 2 is active

Nibble 2 (bit 4..7)


4 Pending Alarm: Power 1 not active
5 Pending Alarm: Power 2 not active

Examples: 0x03: Power 1 and 2 are active


0x21: Power 1 is active, pending alarm: Power 2 not active
0x32: Power 2 is active, pending alarm: Power 1 and 2 not active
(Relay should be reset in this case)

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 26/53


3.2.7 Termination Status
Input Identifier byte: 0x14

The next input byte is to indicate the status of the termination switches on the ProfiHub channels.

Bit Meaning
0 Main Channel termination ON
1 Channel 1 termination ON
2 Channel 2 termination ON
3 Channel 3 termination ON
4 Channel 4 termination ON
5 Channel 5 termination ON

Examples: 0x3F = All terminations are ON


0x01 = Only Main Channel termination is ON
0x10 = Only Channel 4 termination is ON

3.2.8 Channel Status


Input Identifier byte: 0x15

The next input byte is to indicate the communication status of the individual channels.

Bit Meaning
0 Communication on Main Channel
1 Communication on Channel 1
2 Communication on Channel 2
3 Communication on Channel 3
4 Communication on Channel 4
5 Communication on Channel 5

Examples: 0x08 = Communication on Channel 3


0x0A = Communication on Channels 1 and 3
0x2C = Communication on Channels 2, 3 and 5

3.2.9 Livelist Status


Input Identifier byte: 0x20

The next input byte is to indicate which Channel is selected to display the Livelist status.

Hex Meaning
80 Livelist of Main Channel
81 Livelist of Channel 1
82 Livelist of Channel 2
83 Livelist of Channel 3
84 Livelist of Channel 4
85 Livelist of Channel 5
86 Livelist of this ProfiHub
FF Livelist of all channels (entire network)

The next 32 input bytes are used for the actual Livelist data. Each address uses two bits. So the first two bits of
the first byte are for address 0, the next two bits of the first byte are for address 1 and so on. The bits are used
to indicate if the station is a slave device, master device or both.

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 27/53


Device: Bit 1: Bit 0:
None 0 0
Slave Device 0 1
Controller 1 0
Both 1 1

Example: If there is a master device on address 2, and a slave device on address 3, then the first byte
will be 0x60, because it will look like this:

Bit 7 6 5 4 3 2 1 0
Value 0 1 1 0 0 0 0 0
Address 3 Address 2 Address 1 Address 0

This module also has 2 Output bytes. The first Output byte is used to select the Livelist of a specific Channel.
This selection can be read-back in the Input byte described above.

Hex Meaning
80 Livelist of Main Channel
81 Livelist of Channel 1
82 Livelist of Channel 2
83 Livelist of Channel 3
84 Livelist of Channel 4
85 Livelist of Channel 5
86 Livelist of this ProfiHub
FF Livelist of all channels (entire network)

The next Output byte can be used to reset the Livelist. Write 0x01 to this Output byte to reset the Livelist.

3.2.10 Statistics (Short Format, Long Format )


Input Identifier byte: 0x30 (short format) or 0x31 (Long Format)

The next byte is used to display the current selection of statistics that it sends.

Hex Meaning
00..7E Statistics for device 0..126
7F Statistics for undefined devices
80 Statistics of Main Channel
81 Statistics of Channel 1
82 Statistics of Channel 2
83 Statistics of Channel 3
84 Statistics of Channel 4
85 Statistics of Channel 5
86 Statistics of this ProfiHub
FF Statistics of all channels (entire network)

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 28/53


The next 16 bytes (Short Format) or 32 bytes (Long Format) are used to transfer the statistics of the selected
address, selected Channel or all Channels of the ProfiHub. Each statistic uses 2 bytes (Short Format, so a
maximum of 65535 decimal per statistic) or 4 bytes (Long Format) and is sent in the following order:

1. Lost count
2. Sync count
3. Repeats total count
4. Repeats max per cycle count
5. Illegals count
6. Int. diagnostics count
7. Ext. diagnostics count
8. Diagnostics while in Data Exchange count

This module also has 2 output bytes. The first byte is used to configure the ProfiHub Statistics; you can choose
which stations or Channels will display statistics. Configure it by sending the following output value:

Hex Meaning
00..7E Statistics for device 0..126
7F Statistics for undefined devices
80 Statistics of Main Channel
81 Statistics of Channel 1
82 Statistics of Channel 2
83 Statistics of Channel 3
84 Statistics of Channel 4
85 Statistics of Channel 5
86 Statistics of this ProfiHub
FF Statistics of all channels (entire network)

The next output byte can be used for clearing the statistics. Please note that the selected statistics of ALL node
addresses and/or ProfiHub channels are cleared, not only for the displayed address or channel.

Bit Meaning
0 Clear LOST statistics
1 Clear SYNC statistics
2 Clear REPEATS TOTAL statistics
3 Clear REPEATS MAX statistics
4 Clear ILLEGALS statistics
5 Clear INT. DIAG statistics
6 Clear EXT. DIAG statistics
7 Clear DIAG WHILE IN DX statistics

Example: To clear all LOST and ILLEGALS statistics, send 0x11


To clear all statistics, send 0xFF

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 29/53


3.3 Parameterizing the Diagnostic Device
The Diagnostic Device has many user-definable parameters that can be changed, to alter the behaviour and
options of the ProfiHub Diagnostics Device.

3.3.1 Diagnostics
The Diagnostics Device sends a diagnostic message on PROFIBUS whenever certain conditions are changed.
These changes can be any of the following:

• Livelist change (a station added or removed)


• Bitrate error
• Alarm relay active
• Power status changed (one of the two power sources added or removed)
• Redundancy status change (one of the redundant cables added or removed)
• Termination status change (a termination switch on the ProfiHub has been changed)
• Channel status change (communication stopped or started on a channel)
• Statistics change (any statistic has changed)

In your configuration tool you can toggle the diagnostics for each item.

Fig. 21 - Screenshot of ProfiCaptain - User Parameter window

The 8th byte of a diagnostic message from the Diagnostic Device indicates which options have been enabled or
disabled.

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 30/53


3.3.2 Statistics
You can choose which Statistics can trigger a diagnostic message, because not all statistics are interesting in all
networks. For example, Syncs have been disabled by default because this is not a statistic that is suitable for
PROFIBUS health monitoring.

Fig. 22 – You can choose which statistics trigger a diagnostic message

The following Statistics can trigger a diagnostic message of the Diagnostic Device:

• Lost changed • Illegals changed


• Sync changed • Internal Diagnostics changed
• Repeats (total) changed • External Diagnostics changed
• Repeats (max) changed • Diagnostics in Data Exchange changed

3.3.3 Extended Diagnostics on Events change


For more critical applications you can choose to enable the ‘Extended Diagnostics’ option for each of the
previously mentioned events. In the case of such an event, the Diagnostics Device will send out a diagnostics
message with the ‘Extended Diagnostic’ bit on. In a Busmonitor tool such as ProfiTrace the extended
diagnostics bit will appear as a red blinking square.

All Events described in paragraph 0 can trigger the Extended Diagnostic bit of the Diagnostic Device. By default,
the Extended Diagnostic option is disabled. Each item can be enabled individually.

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 31/53


3.3.4 Extended Diagnostics on Statistics change
The Extended Diagnostic option can also be enabled for each individual available statistic. This works the same
way as the Events described in paragraph 0.

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 32/53


3.3.5 Alarm Relay on Events change
The Alarm Relay on the ProfiHub can be switched on each Event described in paragraph 0. When such an Event
occurs, the Relay will be switched immediately without delay. The only Event that can delay the switching of
the Alarm Relay is the Lost event. See paragraph 0 for an explanation.

3.3.6 Alarm relay on Statistics change


The Alarm Relay on the ProfiHub can be switched (closed) on each change in Statistics, described in paragraph
0. When such an (enabled) Statistic change occurs, the Relay will be switched immediately without delay. The
only Statistic that can delay the closing of the Alarm Relay is the Lost event. See paragraph 0 for an explanation.

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 33/53


3.3.7 Changing the Diagnostics duration/timeout
You can change the duration of the Extended Diagnostics warning in steps of 100 milliseconds. The default
value is 10, so 1 second. The maximum value is 255.

3.3.8 Changing the Device Lost timeout


The Diagnostics Device waits for a certain time before it considers a slave to be lost. This works in a similar way
as the ProfiTrace Live List, where the background turns yellow when a slave stops communicating. This timeout
can be changed in steps of 1 second. Default value is 5, and maximum value is 255.

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 34/53


3.3.9 Changing the data format
The data format can be changed if needed. Default is Motorola, high-low-byte format.
You can change it to Intel, low-high-byte format.

3.4 ProfiTrace plugin for the Diagnostic Device


On the download section of www.procentec.com you can download a useful plugin for the Diagnostic Device.
It interprets all messages to and from the Diagnostic Device and displays the data in the Info Panel of
ProfiTrace.

3.4.1 Installing the Plugin


Once you have downloaded the file and extracted it to your hard drive, start ProfiTrace and choose ‘Settings –
Plugins’ to bring up the Plugin window.

Click ‘Install Plugin’ and locate it on your harddrive.


Next, click ‘Enabled’ so that ProfiTrace starts the plugin on startup.

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 35/53


ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 36/53
3.4.2 Using the Plugin
When the Plugin is correctly started and you have a ProfiHub with Diagnostics Device running, click ‘Start
Message Recording’ in ProfiTrace, and view the screen with messages (see Fig. 23). If you click on a data
exchange message to or from a Diagnostics Device, you will see all the interpreted data bytes in the Info Panel.
This is very useful for Troubleshooting activities.

A good example is the Statistics. These statistics are available per individual channel or station address (see
paragraph 3.3.2), so it is easy to see the source of the problem.

Fig. 23 - Info Panel with ProfiHub Diagnostics information

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 37/53


4 Technical Data ProfiHub B5+R / B5+RD

Technical Data ProfiHub B5+R and B5+RD

Dimensions and weight


Dimensions L x W x H (mm) with screws 167 x 111 x 32 mm
Weight Approximately 650 g

Ambient conditions
Operating temperature -25 to +70o Celsius
-13 to +158o Fahrenheit
Isolation class IP 20 (DIN 40 050)

Protocol specifications
Supported Protocols DP-V0, DP- V1, DP-V2, FDL, MPI, FMS, PROFIsafe, PROFIdrive
and any other FDL based protocol.

Transmission speed 9.6 kbps to 12 Mbps (including 45.45 kbps)


Transmission speed detection Auto detect (default) or selectable with rotary switch

Transmission speed switch For position 1..D on B5+RD: Diagnostics Device ON


0 = Normal repeating (Auto detect, diag off) (default)
1 = 9.6 kbps
2 = 19.2 kbps
3 = 45.45 kbps
4 = 93.75 kbps
5 = 187.5 kbps
6 = 500 kbps
7 = 1500 kbps
8 = 3000 kbps
9 = 6000 kbps
A = 12000 kbps
B = Robust repeating (auto baudrate detect)
C = Robust repeating, auto baudrate detect, redundancy on
channel 4 and 5
D = Normal repeating (auto baudrate detect)
E .. F = Same as 0

Transmission speed detection time < 10 s (if it is set to auto detect)

Data delay time At baudrate: Normal mode: Robust mode:


9.6 - 93.75 kbp ≤1.7 Tbit ≤13.25 Tbit
187.5 - 500 kbps ≤1.8 Tbit ≤13.30 Tbit
1.5 Mbps ≤1.9 Tbit ≤13.40 Tbit
3 Mbps ≤2.2 Tbit ≤13.60 Tbit
6 Mbps ≤3.0 Tbit ≤14.00 Tbit
12 Mbps ≤4.0 Tbit ≤15.00 Tbit

Delay time jitter Max. ¼ bit time

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 38/53


Technical Data ProfiHub B5+R and B5+RD

PROFIBUS Diagnostics Device specifications (only for B5+RD)


Supported protocol DP-V0
Ident Number 6970
GSD filename PROC6970.gsd
Bus address 0-126 (software address only, set by software)

Transmission speed 9.6 kbps .. 12 Mbps (including 45.45 kbps)


Transmission speed detection Auto Detect

Maximum transferrable data 85 bytes input and 5 bytes output

PROFIBUS cable specifications


Cable lengths 1200 m at 9.6 kbps to 93.75 kbps
1000 m at 187.5 kbps
400 m at 500 kbps
200 m at 1.5 Mbps
100 m at 3 Mbps to 12 Mbps

Cable thickness 10 mm (when the ground rail is used)


Wire diameter < 2.5 mm2
Wire type Stranded or Solid core

Number of devices Maximum 31 per Channel (including ProfiHubs, OLMs,


Laptops/PCs, etc)

Termination Integrated and switchable.


Powered according to IEC 61158 (390/220/390 Ohms)
- All Channels (default on)
- Main-Channel (default off)

Cascading depth No limits


Redundancy Yes
Power supply specifications
Power supply voltage 9 to 31 VDC
Redundant power supply Yes

Current consumption 130 mA at 24 V power supply (all Channels fully loaded)


Power dissipation Max. 4.1 W

Reverse polarity protection Yes


Cable thickness 10 mm (when the ground rail is used)
Wire diameter < 2.5 mm2
Alarm contact
Voltage Max. 24 VDC
Current 0.5 A

Others
MTBF 398723 hours according to IEC-62380 (RDF2000/UTE C 80-180)

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 39/53


5 Order codes

Component Order code Remarks

17020R ProfiHub B5+R


With Alarm contact
With redundant power input
With cable redundancy
ProfiHub B5+R

17020RD ProfiHub B5+R with Diagnostics Device


With Alarm contact
With redundant power input
With cable redundancy
ProfiHub B5+RD

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 40/53


6 Glossary

Address Unique number of a device connected to the network. With PROFIBUS this can
be 0 to 126. 127 is a broadcast address.

Analyzer Software tool to observe the protocol traffic. Combi-Analyzers can also inspect
the signal quality.
Other term: Bus Monitor.
Example: ProfiTrace.

Backbone The primary bus cable. Most of the time only the control systems, ProfiHubs and
fiber optic couplers are connected to this cable. The field devices are connected
behind the ProfiHubs and fiber optic couplers.

Bit Time (Tbit) The bit time Tbit is the time, which elapses during the transmission of one bit. It
depends on the baudrate and is calculated as follows Tbit = 1 (bit) / baudrate
(bps).
Examples:
12 Mbps --> Tbit = 83 ns
1.5 Mbps --> Tbit = 667 ns

Busparameters Settings that define the timing behaviour on the bus. They are defined in the
master. Examples: Tslot, MaxTSDR.

C Capacitance.

DGND Digital Ground.

DIN German Institute for Standardization (www.din.de).

DP-V0 DP-V0 is the basic stage of the PROFIBUS DP communication protocol. DP-V0
devices (master and slaves) perform the following basic functionalities:
- Cyclic exchange of I/O data between controlling and slave devices
- Device, Identifier (module) and Channel related Diagnosis
- Parameterization of DP-slaves
- Configuration of DP-slaves

DP-V1 DP-V1 is the first stage of extension of PROFIBUS DP after DP-V0. DP-V1 devices
shall comply with the following features:
- Device related diagnosis is replaced by status and alarms.
- The first three octets of the user parameterization data are now standardized
- Optionally these devices may support:
- Acyclic communication (MS1, MS2)
- If alarms are used, MS1 shall be supported

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 41/53


DP-V2 DP-V2 is the second stage of extension of PROFIBUS DP after DP-V1. DP-V2
devices shall comply with the following features:
- Data Exchange Broadcast (DxB) for slave to slave communication
(publisher/subscriber principle).
- Isochronous Mode (time tick synchronized operating slaves, e.g. drives)
- Up- and/or download of Load Region Data (domains)
- Clock Control (synchronization within slaves) and Time Stamping
- Redundancy.

Electromagnetic See EMC.


Compatibility

EMC The extent to which an electric or electronic device will tolerate electrical
interference from other equipment (immunity), and will interfere with other
equipment. Within the European Community as well as in other countries it is
regulated by law that electric and electronic components and equipment comply
with basic standards such as IEC 61000-6-2 or IEC 61326 or corresponding
individual product standards.

Hub A Hub refreshes a signal and passes the information on to all nodes which are
connected to the Hub. Data frames which were received on one port are
transferred to all the other ports (chicken foot topology).

MPI Multiple Protocol Interface. Protocol defined by Siemens which uses the layer 1
and 2 of PROFIBUS (FDL).

PCB Printed Circuit Board.

PROFIBUS DP Acronym for "PROFIBUS for Decentralized Peripherals". Specification of an open


fieldbus system with the following characteristics:
- Polling master-slave-system (cyclic communications, MS0)
- Flying masters with robin round token passing coordination (MM)
- Connection based (MS1) and connectionless (MS2, MS3) acyclic communication
between masters and slaves
Options (e.g.):
- Data exchange broadcast (DXB), i.e. slave to slaves communication
- Isochronous mode of slaves
- Clock synchronization
- Redundancy
PROFIBUS DP is standardized within IEC 61158 and IEC 61784, communication
profile families 3/1 and 3/2
The term "PROFIBUS DP" also is a synonym for the RS485 based deployments
within factory automation.

Repeater Active physical layer device that receives and retransmits all signals over a
different port to increase the distance and number of devices for which signals
can be correctly transferred for a given medium.

Spur line A cable attached to a bus segment with a T-connection . Spurs are not
recommended with PROFIBUS DP. They are prohibited with 12 Mbps and
PROFIsafe operations. German term is "Stichleitung".

Stub line See Spur line.

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 42/53


Tbit See Bit Time.

Termination A (powered) resistor network at both ends of a segment to prevent reflections


(with PROFIBUS DP the termination must be powered).

Topology In a communications network, the pattern of interconnection between network


nodes; e.g. bus, ring, star configuration.

PI PROFIBUS International.
The International PROFIBUS Organization based in Karlsruhe.

PNO PROFIBUS Nutzer Organization.


The German PROFIBUS Organization based in Karlsruhe.

Drop cable See Spur line.

Reflection Part of the original signal that is transmitted back along the cable. It corrupts the
original signal.

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 43/53


8 Revision History
Version 1.0
- First release (B5+)

Version 1.5
- Added the UL and DNV certificates
- Updated the Distributors chapter

Version 2.0
- Added chapter ‘Diagnostics Device’
- Textual changes in all chapters to adapt to B5+RD

Version 2.1.0
- Textual changes

Version 3.0
- Updated the manual to the new corporate style

Version 3.1.0
- Added PI certificate for diagnostics slave

Version 3.1.1
- Added note for Robust Repeating
- Minor changes

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 44/53


9 Sales offices and Distributors
HEADQUARTERS
PROCENTEC T: +31-(0)174-671800
Klopperman 16 F: +31-(0)174-671801
2292 JD WATERINGEN E: [email protected]
Netherlands I: www.procentec.com

ARGENTINA
eFALCOM T: +54 237 46 31 151
Alcorta 2411 F: +54 237 46 31 150
B1744 - Moreno E: [email protected]
Buenos Aires I: www.efalcom.com.ar
Argentina

AUSTRALIA
IS Systems Pty Limited T: +61 2 4964 8548
14 Laverick Ave., F: +61 2 4964 8877
Tomago E: [email protected]
NSW, Australia, 2322 I: www.issystems.com.au

Pentair Flow Control Pacific T: +61 2 4448 0466


1 Percival Road F: +61 2 4423 3232
Smithfield E: [email protected]
NSW, Australia, 2164 I: www.profibuscentre.com.au

BELGIUM and LUXEMBOURG


Bintz Technics N.V. T: +32 2 720 49 16
Brixtonlaan 23 F: +32 2 720 37 50
B-1930 Zaventem E: [email protected]
Belgium I: www.bintz.be

BRAZIL
Westcon Instrument. Indl Ltda T: +55 11 5561-7488
Rual Alvaro Rodrigues, 257 F: +55 11 5093-2592
São Paulo – SP E: [email protected]
Brazil - CEP 04582-000 I: www.wii.com.br

CANADA
Streamline Process Management Inc. T: +1 403 225 1986
#3, 4351 – 104 Ave SE F: +1 587 585 2828
Calgary, Alberta T2C 5C6 E: [email protected]
Canada I: www.streamlinepm.com

CHILE
RP Ingenieria Limitada T: +56-(0)41-2469350
Tucapel 92 oficina 52 F: +56-(0)41-2522592
Concepción E: [email protected]
Chile I: www.rpingenieria.cl

CHINA
PROCENTEC Beijing T: +86(10)84766911 or 84787311
Room E-1115 WangJingYuan YouLeHui F: +86(10)84766722
ChaoYang E: [email protected]
Beijing I: www.procentec.net
China

CZECH REPUBLIC
FOXON s.r.o. T: +420 484 845 555
Polní 367 F: +420 484 845 556
460 01 Liberec 12 E: [email protected]
Czech Republic I: www.foxon.cz

DENMARK
ProSaiCon T: +45 70 20 52 01
Jernbanegade 23B F: +45 70 20 52 02
DK 4000 Roskilde E: [email protected]
Denmark I: www.prosaicon.dk

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 45/53


EGYPT
Mas Trading T: +2 02 2524 2842
37, 105 Street F: +2 02 2524 2843
Al-Etihad Square E: [email protected]
Egypt I: www.masautomation.com

ESTONIA
Saksa Automaatika OU T: +372 605 2526
Peterburi Tee 49 F: +372 605 2524
Tailinn E: [email protected]
EE-11415 Estonia I: www.saksa-automaatika.ee

FINLAND
Hantekno Oy T: +358 40 8222 014
Kalliotie 2 E: [email protected]
04360 Tuusula I: www.hantekno.fi
Finland

FRANCE
AGILiCOM T: +33 247 76 10 20
Bâtiment B F: +33 247 37 95 54
1, rue de la Briaudière E: [email protected]
Z.A. La Châtaigneraie I: www.agilicom.fr
37510 BALLAN-MIRE
France

GERMANY
PROCENTEC GmbH T: +49-(0)721 831 663-0
Benzstrasse 15 F: +49-(0)721 831 663-29
D-76185 Karlsruhe E: [email protected]
Germany I: www.procentec.de

INDIA
UL Engineering Services & Software Pvt Ltd T: +91-202 696 0050
Nirman Classic, F: +91-202 696 2079
Katraj-Kondhwa Road, E: [email protected]
Katraj, Pune-411046 I: www.ulepl.com
India

IRELAND
PROFIBUS Ireland T: +353-61-202107 or +35361240240
Automation Research Centre F: +353-61-202582
University of Limerick E: [email protected]
National Technology Park, Plassey I: www.profibus.ie
Limerick
Ireland

ISRAEL
Instrumetrics Industrial Control T: +972-9-8357090
8 Hamlacha St. F: +972-9-8350619
New Industrial Zone E: [email protected]
Netanya, 42170 I: www.inst-ic.co.il
Israel

ITALY
PROCENTEC Italy T: +39 030 200 8610
Via Branze n. 43/45 F: +39 030 238 0059
25123 Brescia E: www.procentec.it
Italy W: www.procentec.it

JAPAN
TJ Group T: +81-3-6450-3739
C/O Japanese PROFIBUS Organisation F: +81-3-6450-3739
West World Building 4F E: [email protected]
3-1-6 Higashi-Gotanda,
Shinagawa-ku,
Tokyo, 141-0022
Japan

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 46/53


KOREA
Hi-PRO Tech. Co., Ltd. T: +82 82-31-216-2640
#2802, U-Tower, 1029 F: +82 82-31-216-2644
Youngduk-dong, Giheung-gu E: [email protected]
Yongin-Si, Kyunggi-do, I: www.profibus.co.kr
446-908 Korea

LEBANON
Industrial Technologies S.A.L. (ITEC) T: +961 1 491161
Point Center, Boulevard Fouad Chehab F: +961 1 491162
Sin El Fil E: [email protected]
Beirut I: www.iteclb.com
Lebanon

MEXICO
Grid Connect Inc. T: +1 530-219-2565 (Spanish)
E: [email protected]
I: www.gridconnect.com

NETHERLANDS
PROCENTEC B.V. T: +31 (0)174 671800
Klopperman 16 F: +31 (0)174 671 801
2292 JD Wateringen E: [email protected]
Netherlands I: www.procentec.com

NORWAY
AD Elektronikk AS T: +47 64 97 60 60
Boks 641 F: +47 64 97 60 70
N-1401 SKI E: [email protected]
Norway I: www.ade.no

PERU
ControlWare T: +51 1637 3735
Jr. Los Silicios 5409 F: +51 1528 0454
Los Olivos - L39 E: [email protected]
Peru I: www.controlware.com.pe

POLAND
INTEX Sp. z o.o. T: +48 32 230 75 16
ul. Portowa 4 F: +48 32 230 75 17
44-102 Gliwice E: [email protected]
Poland I: www.intex.com.pl

ROMANIA
S.C. SVT Electronics S.R.L. T: +40 365 809 305
Brǎila 7 F: +40 365 809 305
540331 Tg-Mure E: [email protected]
Romania I: www.svt.ro

SAUDI ARABIA
ASM Process Automation T: +966 2 691 2741
Al-Zahra Dist. – Attas st. F: +966 2 682 8943
cross section with helmy Kutby St. E: [email protected]
Villa no.25 I: www.asmestablishment.com
Jeddah-21553
Saudi Arabia

SINGAPORE / SOUTH EAST ASIA


Allegro Electronics T: +65 62878063
236 Serangoon Avenue 3 07-98 E: [email protected]
Singapore 550236 I: www.allegro.com.sg

Gissmatic Automatisierung Pte Ltd T: +65 900 912 76


318 Tanglin Road 01-34 E: [email protected]
Singapore 247979 I: www.gissmatic.com

SLOVAKIA
ControlSystem s.r.o. T: +421 486115900
Stúrova 4 F: +421 486111891
977 01 BREZNO E: [email protected]
Slovakia E: [email protected]

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 47/53


SOUTH AFRICA
IDX ONLINE CC T: +27(11) 548 9960
1 Weaver Street F: +27(11) 465-8890
Fourways E: [email protected]
Johannesburg I: www.idxonline.com
South Africa - 2191

SPAIN
LOGITEK, S.A T: +34 93 588 6767
Ctra. de Sant Cugat, 63 Esc. B Planta 1ª E: [email protected]
Rubí (BARCELONA), 08191 I: www.logitek.es
Spain

SWEDEN
P&L Nordic AB T: +46 451 74 44 00
Box 252 F: +46 451 89 833
S-281 23 Hässleholm E: [email protected]
Sweden I: www.pol.se/profibus

SWITZERLAND
Berner Fachhochschule T: +41 (0) 34 426 68 32
PROFIBUS Kompetenzzentrum F: +41 (0) 34 426 68 13
Jlcoweg 1 E: [email protected]
CH-3400 Burgdorf I: www.profitrace.ch
Switzerland

TAIWAN
Full Data Technology T: +886-2-87519941/9097
6F., No.200, Gangqian Rd. F: +886-2-87519533
Neihu District, Taipei City E: [email protected]
114, Taiwan I: www.fulldata.com.tw

TURKEY
Emikon Otomasyon T: +90 216 420 8347
DES Sanayi sitesi 103 sokak F: +90 216 420 8348
B-7 blok No:16 Yukari Dudullu / Umraniye E: [email protected]
Istanbul 34776 I: www.emikonotomasyon.com
Turkey

UNITED ARAB EMIRATES


Synergy Controls T: +971 4 3262692
907, IT Plaza Silicon Oasis : F: +971 4 3262693
DubaiI E: [email protected]
United Arab Emirates

UNITED KINGDOM and N. Ireland


Verwer Training & Consultancy T: +44 (0)1625 871199
5 Barclay Road E: [email protected]
Poynton, Stockport I: www.verwertraining.com
Cheshire SK12 1YY
United Kingdom

Hi-Port Software T: +44 (0)8452 90 20 30


The Hub 2 Martin Close F: +44 (0)2392 552880
Lee-on-Solent E: [email protected]
Hampshire PO13 8LG I: www.hiport.co.uk
United Kingdom

iTech T: +44 (0)1292 311 613


Unit 1 F: +44 (0)1292 311 578
Dukes Road E: [email protected]
Troon I: www.itech-troon.co.uk
Ayrshire KA10 6QR
United Kingdom

Parkelect Ltd. T: +44 2890 777743


84 Dargan Road F: +44 2890 777794
Belfast E: [email protected]
BT3 9JU I: www.parkelect.co.uk
N. Ireland

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 48/53


UNITED STATES
Grid Connect Inc. T: +1 630 245-1445
1630 W. Diehl Road F: +1 630 245-1717
Naperville, Illinois 60563 E: [email protected]
USA I: www.gridconnect.com/procentec.html

VIETNAM
Bavitech Corporation T: +84-8-3547 0976
42 Truong Son Street F: +84-8-3547 0977
Ward 2, Tan Binh District E: [email protected]
Ho Chi Minh City I: www.bavitech.com
Vietnam

For the up to date list of the Sales Offices and Distributors see www.procentec.com/company/distributors/. If
your country or region is not listed, please contact us. We are still searching for distributors who can cover
complete areas or countries.

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 49/53


9 Notes
____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 50/53


____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

____________________________________________________________________________________________________________________

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 51/53


About PROCENTEC
PROCENTEC is a specialist in PROFIBUS and PROFINET technology and develops products to optimize the
production processes of end users. Our innovative solutions ensure that our customers successfully operate
in the world of industrial automation and enjoy maximum results from their process.

PROCENTEC globally supplies all the components required to install a measurable and steerable network. We
develop and produce all products in the Netherlands and they are exported through our worldwide distribution
network. At PROCENTEC, we have a professional team of qualified support engineers who provide technical
support on-site and online. Our professionals have more than 20 years of experience with PROFIBUS and
PROFINET technology. They provide the necessary support to end users during implementation procedures,
certification processes, audits and malfunctions. PROCENTEC also is the international accredited Competence
and Training center for PROFIBUS and PROFINET. We provide training courses that help employees using those
techniques optimally for their business objectives.

Products Training courses Services


• ProfiTrace • PROFIBUS training courses • Competence center
• ComBricks • PROFINET training courses • Support & Consultancy
• ProfiHub • Product training courses • Network certification & Audits
• PROFINET tools • Testlab & Democenter
• Cables and connectors

ProfiHub B5+R / B5+RD Manual | April 2017 | © PROCENTEC 52/53


PROCENTEC BV
Klopperman 16
2292 JD Wateringen
The Netherlands

T: +31 (0)174 671 800


F: +31 (0)174 671 801
E: [email protected]
W: www.procentec.com

You might also like