X Ray Room

Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 2

ROOM LAYOUT FOR AN X-RAY INSTALLATION

Location of X-Ray Installation:


Rooms housing diagnostic X-ray units and related equipment shall be located as far away as feasible from
areas of high occupancy and general traffic, such as maternity and paediatric wards and other departments
of the hospital that are not directly related to radiation and its use. In case the installation is located in a
residential complex, it shall be ensured that (i) wall(s) of the X-ray rooms on which primary X-ray beam
falls is (are) not less than 35 cm thick brick or equivalent, (ii) walls(s) of the X-ray room on which scattered
X-ray fall is (are) not less than 23 cm thick brick or equivalent, and (iii) there is a shielding equivalent to at
least 23 cm thick brick or 1.7 mm lead in front of the door(s) and windows of the X-ray room to protect the
adjacent areas, either used by general public or not under possession of the owner of the X-ray room.

Layout
The layout of rooms in an X-ray installation shall be such that the number of doors for entry to the X-ray
rooms shall be kept to the minimum. The unit shall be so located that it shall not be possible to direct the
primary X-ray beam towards dark room, door, windows, and control panel, or areas of high occupancy.

Room Size
The room housing an X-ray unit shall be not less than 18 m2 for general purpose radiography and
conventional fluoroscopy equipment. The size of room housing the gantry of the CT unit shall not be less
than 25 m2. Also, not more than one unit of any type shall be installed in the same room, and no single
dimension of these X-ray rooms shall be less than 4 m.

Shielding
Appropriate structural shielding shall be provided for walls, doors, ceiling and floor of the room housing
the X-ray unit so that doses received by workers and the members of public are kept to the minimum and
shall not exceed the respective annual effective doses as prescribed by the competent authority. Appropriate
shielding shall also be provided for the dark room to ensure that the undeveloped X-ray films are not
exposed to more than 10 µ Gy per week.

Openings and Ventilation


Unshielded openings in an X-ray room for ventilation or natural light shall be located above a height of 2 m
from the finished floor level outside the X-ray room.

Illumination Control
Rooms housing fluoroscopy equipment shall be so designed that adequate darkness can be achieved
conveniently, when desired, in the room.

Control Panel
The control panel of diagnostic X-ray equipment operating at 125 kVp or above shall be installed in a
separate room located outside but contiguous to the X-ray room and provided with appropriate shielding,
direct viewing and oral communication facilities between the operator and the patient. In case of X-ray
equipment operating up to 125 kVp, the control panel can be located in the X-ray room. The distance
between control panel and X-ray unit/chest stand shall be not less than 3 m for general purpose fixed X-ray
equipment.

Waiting Areas
Patient waiting areas shall be provided outside the X-ray room.

Warning Light and Placard


A suitable warning signal such as red light shall be provided at a conspicuous place outside the X-ray room
and kept “ON” when the unit is in use to warn persons not connected with the particular examination from
entering the room. An appropriate warning placard as indicated in

Dark Room
The dark room shall be located adjacent to the X-ray room such that no primary or secondary X-rays reach
inside the dark room.

You might also like