General Specifications: GS 33K01A10-50E
General Specifications: GS 33K01A10-50E
General Specifications: GS 33K01A10-50E
All Rights Reserved. Copyright © 2011, Yokogawa Electric Corporation GS 33K01A10-50E June 1, 2012-00
<<Contents>> <<Index>> 3
Optional Software ● Layer 2 Switch (L2SW)
Optional software packages are available that perform L2SW relays communications among devices
special functional blocks on FCS, other than the basic connected to the Vnet/IP network. The Vnet/IP domain
software. refers to the Vnet/IP system area connected by
LFS3132 Valve Pattern Monitor Package L2SW. In the Vnet/IP domain, use L2SW with 1 Gbps
LFS8620 Off-site Block Package communication speed.
For details, refer to GS for each software package.
● Layer 3 Switch (L3SW)
Generic Subsystem Gateway (GSGW) L3SW relays communications among Vnet/IP domains.
GSGW is a station for operation and monitoring For communication among Vnet/IP domains, use L3SW
subsystems. By using a PC as a platform, GSGW with 1 Gbps communication speed.
package establishes communications with subsystems
● SNTP Server
via OLE for Process Control (OPC) interface defined
SNTP server performs time synchronization via
by the OPC Foundation. Subsystem data is assigned
networks. Connect Vnet/IP station to SNTP server
to the GSGW’s function blocks which can be controlled
for synchronizing its time to the Universal Time,
and monitored via HIS as same as other control
Coordinated (UTC).
stations.
LFS1250 Generic Subsystem Gateway Package ● V net Router
For more details, refer to GS for Generic Subsystem V net router connects and transmits control
Gateway Package (GS 33K20F10-50E). communications between the Vnet/IP and V net
domains. The control data can be sent and received
● Unified Gateway Station (UGS) in both ways between the Vnet/IP and V net domains.
UGS is a station exclusively used for Vnet/IP to Control and monitoring of the control stations in the
integrate CENTUM VP and subsystem controllers such other domain, and vice versa, is enabled.
as STARDOM controllers (FCN/FCJ) and other third-
AVR10D Duplexed V net Router (duplexed
party programmable logic controllers (PLCs).
communication modules and duplexed
The UGS standard function allows CENTUM VP to power supply modules)
communicate with subsystem controllers via various For more details, refer to GS for Duplexed V net Router
communication protocols such as Modbus, EtherNet/IP (GS 33K50D10-50E).
or OPC DA. And CENTUM VP is able to control and
monitor those subsystems via UGS in the same way as
its own FCS. RELEVANT SYSTEMS
With two units of UGS, the UGS can be configured in ● Plant Resource Manager (PRM®)
dual-redundant. PRM is a software package for online asset
LBC1500 Unified Gateway Station Standard management of field devices and equipments. By
Function monitoring and managing the device status and the
LBC1501 Dual-redundant Package (for UGS) maintenance information, it enables to reduce plant’s
LBC1550 OPC Communication Package (for UGS) Total Cost of Ownership (TCO).
LBC1553 Modbus Communication Package PRM communicates with devices with digital
(for UGS) communication functions such as FOUNDATION fieldbus,
LBC1591 EtherNet/IP Communication Package HART, and field wireless (complies with ISA 100.11a)
(for UGS) devices, as well as conventional analog devices with no
For more details, refer to GS for each software digital communication function.
package. For more details of the PRM specifications, refer to GS
● System Integration OPC Station (SIOS) for Plant Resource Manager (GS 33Y05Q10-32E).
SIOS is a station to integrate CENTUM VP and the ● ProSafe-RS Safety Instrumented System
third-party process control systems (PCSs). SIOS ProSafe-RS has certified by Technische Überwachungs
enables CENTUM VP exchanges data with and Verein (TÜV) as a safety system to satisfy safety
receives alarms and events from the third-party PCSs integrity level (SIL) 3 of IEC 61508.
via OPC interface.
A safety control station (SCS) of ProSafe-RS monitors
LBC2100 System Integration OPC Client Package plant safety always, and it performs safety functions
For more details, refer to GS for System Integration when needed. Safety engineering PC (SENG)
OPC client Package (GS 33K20D10-50E). performs engineering and maintenance of SCS.
● Advanced Process Control Station (APCS) ProSafe-RS can be integrated with CENTUM VP, which
APCS performs advanced control and computation for enables SCS operation and monitoring from HIS.
improving plant operation efficiencies. For more details, refer to GS for ProSafe-RS Safety
LFS1200 APCS Control Functions Instrumented System (GS 32Q01B10-31E).
For more details, refer to GS for APCS Control
Functions (GS 33K15U10-50E).
● Peripheral Devices
Printers and other peripherals devices which each OS
support are available to use with CENTUM VP. For
details of other peripherals, contact Yokogawa for
information.
All Rights Reserved. Copyright © 2011, Yokogawa Electric Corporation GS 33K01A10-50E Apr. 1, 2013-00
<<Contents>> <<Index>> 4
SYSTEM SPECIFICATIONS
HIS Operation/Monitoring Tags:
Maximum 100000 per system (when LHS4000 is in use, up to 1000000 per system).
The Vnet/IP devices refer to a PC with Vnet/IP Interface Card (VI702), an FCS for Vnet/IP, and/or a V net router.
Followings are Vnet/IP devices for CENTUM VP.
HIS: Human Interface Station
ENG: Engineering Station
FCS: Field Control Station
APCS: Advanced Process Control Station
GSGW: Generic Subsystem Gateway
UGS: Unified Gateway Station
SIOS: System Integration OPC Station
Exaopc: OPC Interface Package
AVR10D: V net Router
Vnet/IP
FCS
SCS
V net router
ESB Bus Node
SIOS GSGW APCS
UGS
Modbus
Other
ESB Bus Node Third-party V net
Third-party system domains
PCS
subsystem STARDOM
Boundary Router
Remote
L3SW: Layer 3 Switch Network
All Rights Reserved. Copyright © 2011, Yokogawa Electric Corporation GS 33K01A10-50E Aug. 19, 2011-00
<<Contents>> <<Index>> 5
System Expansion
By adopting layer 3 switch (L3SW), Vnet/IP domains can be connected to form a hierarchical system configuration.
With a V net router, V net domains can be connected with other V net and/or VL net systems. The existing HF bus
and/or RL bus systems cannot connect directly with Vnet/IP domains; however, it can be connected using a bus
converter (BCV) on the V net via V net router. When the system is configured hierarchically using L3SW and V net
routers, it is possible to expand the system scale exceeding the maximum system configuration per domain. It means
that CENTUM VP system can be extendedly connected with other control systems in hierarchical layers beyond its
maximum system scale.
No. of domains: Maximum 16 domains (Vnet/IP domains + V net domains)
No. of domain layers connected with Vnet/IP systems via V net routers:3 layers (2 layers for bus converter, 3 layers
for V net)
No. of operation/monitoring tags: Maximum 100000 (when LHS4000 is in use, up to 1000000 per system)
Connecting devices: L3SW, V net router, and Bus converter
When counting the number of V net layers, Vnet/IP domains and V net routers in the access paths are not counted as
a layer. The figure below shows an example of layers in hierarchical configuration.
Vnet/IP domain
L2SW×2 L3SW×2 L2SW×2
FCS FCS FCS FCS SCS
Vnet/IP domain
V net V net
router router
V net domain V net domain
BCV
FCS SCS
V net domain FCS SCS
Bus converter x 0 layer, Bus converter x 1 layer, Bus converter x 2 layers, and
and V net x 1 layer and V net x 2 layers V net x 3 layers (max.)
beyond V net router beyond V net router beyond V net router
F02E.ai
All Rights Reserved. Copyright © 2011, Yokogawa Electric Corporation GS 33K01A10-50E Aug. 19, 2011-00
<<Contents>> <<Index>> 6
MULTIPLE PROJECT CONNECTION
CENTUM VP manages FCS and HIS engineering data, generated by the system builder functions, by the unit of
project. The multiple project connection is a function to integrate operation and monitoring of the multiple projects.
CENTUM VP HIS integratively monitors CENTUM VP, CENTUM CS 3000, CENTUM CS 1000, and CENTUM CS
projects without changing the identical names (e.g. tag name, project name, and plant hierarchy name) and common
resources (e.g. engineering unit, and operation mark).
There are two ways of multiple project connection.
Hierarchical Connection
CENTUM VP project on the upper-layer operates and monitors lower-level projects. In this case, CENTUM VP on the
upper-level project requires installing a multiple project connection package. From the lower-level projects, operation
and monitoring of the CENTUM VP on the upper-level is not available. Following types of multiple connections are
available.
CENTUM VP→CENTUM VP CENTUM VP→CENTUM CS 3000 CENTUM VP→CENTUM CS 1000 CENTUM VP→CENTUM CS
F05E.ai
Bi-directional Connection
Operation and monitoring of the connected projects are enabled bi-directionally. The bi-directional connection is
applicable only for CENTUM VP projects and/or CENTUM VP and CENTUM CS 3000 projects. Multiple project
connection packages are required for both upper- and lower-levels of the systems.
CENTUM VP CENTUM VP
upper/lower level project upper/lower level project
For more details, refer to GS for LHS5450, LHS4450 Multiple Project Connection Package (GS 33K05K20-50E).
All Rights Reserved. Copyright © 2011, Yokogawa Electric Corporation GS 33K01A10-50E Aug. 19, 2011-00
<<Contents>> <<Index>> 7
NETWORK SPECIFICATIONS
CENTUM VP uses Vnet/IP and Ethernet for communications among configured devices.
Vnet/IP
Vnet/IP is a gigabit Ethernet-based control network for process automation. It provides real-time communication
with high reliability which is indispensable for stable plant operations. Vnet/IP is a dual-redundant control network,
consisting of Bus 1 and Bus 2. Bus 1 is normally used for control communication to transmit control data; however,
when the Bus 1 fails, it automatically switches its communication path and Bus 2 continues the control communication
without stopping.
Vnet/IP domain
HIS ENG
APCS GSGW A wide area connection
Exaopc via dedicated network is
available.
Max.7 levels
1000BASE-T for Layer 2
Max. 100 m Switch
Bus 1 Layer 3
V net router Switch
Layer 2 Switch
V net Vnet/IP Vnet/IP
domain Bus 2 domain domain
Layer 2 Switch
Layer 3
Switch
BCV
HF-bus FFCS-L
domain
F03E.ai
Communication Specification
Control Communication
Communication method: Read/write communication, message communication, link transmission
Link transmission period: 100 ms
Transmission specifications
Network topology: Star topology
Transmission redundancy: Dual-redundant (for control network communication only)
Transmission cable: Unshielded twist-pair (UTP) with enhanced category 5 or superior
Cable Maximum
Connection Speed
Standard Distance
100BASE-TX
100 Mbps (*1)
(IEEE802.3u)
Between component and a layer 2 switch 100 m
1000BASE-T
1 Gbps
(IEEE802.3ab)
1000BASE-T
1 Gbps 100 m
(IEEE802.3ab)
Between layer 2 switches
1000BASE-LX
1 Gbps 5 km (*2)
(IEEE802.3z)
1000BASE-T
1 Gbps 100 m
(IEEE802.3ab)
Between a layer 2 switch and a layer 3 switch
1000BASE-LX
1 Gbps 5 km (*2)
(IEEE802.3z)
All Rights Reserved. Copyright © 2011, Yokogawa Electric Corporation GS 33K01A10-50E Apr. 1, 2013-00
<<Contents>> <<Index>> 8
Ethernet
Ethernet is a network used for file transfer and information communication among HIS, ENG, and other general-
purpose Ethernet instruments. Ethernet communication is usually performed via an Ethernet card mounted a PC or a
server. In this section the term, Ethernet communication, refers to the communication based on the various Ethernet-
based standard protocols.
Communication Protocol
Based on IEEE802.3
Conditions for Ethernet Communication using Vnet/IP Bus 2
Ethernet communication usually uses a network independent from Vnet/IP. However, when all the following conditions
are met, it is enabled to perform Ethernet communication by using Vnet/IP Bus 2. In case any one of the conditions is
not met, it is recommended to use an independent network from Vnet/IP for Ethernet communication.
• A system is composed of only Vnet/IP network and has no connection with V net or VL net via V net router.
• A system includes none of the followings – Exaopc (*1), HIS-TSE, UGS (*2), SIOS, GSGW, or APCS.
• No integration with ProSafe-RS.
• When using PRM, PRM server and field communications server run on the same PC, and PRM client runs on a PC
with Vnet/IP Interface Card, such as HIS or PC on which field communications server runs.
• 16 or less PCs with Vnet/IP interface card for HIS and ENG. (*3)
• Instruments connected with L2SW for Bus 2 are Vnet/IP interface card’s Bus 2 port mounted on the PC, a network
printer (*4), and a file server (*4) only.
When the Ethernet communication is performed by the Vnet/IP Bus 2, it is called an open communication. Vnet/IP
realizes dual-redundancy of the control communication. Bus 2 always performs the open communication while Bus
1 is for control communication. When the Bus 1 control communication fails, Bus 2 performs both the control and the
open communications.
*1: NTPF100 Exaopc OPC Interface Package (refer to GS 36J02A10-01E). This condition is not applied for LHS2411 Exaopc
OPC Interface Package (for HIS).
*2: For the dual-redundant configuration of UGS (refer to GS 33K20C10-50E), it is strongly recommended to perform Ethernet
communication by the network connected to a UGS’s Ethernet card, and do not use Vnet/IP Bus 2 communication.
*3: When the number of PC with Vnet/IP interface card exceeds 16, it is suggested to perform Ethernet communication by
the network connected to a PC’s Ethernet card, and do not use Vnet/IP Bus 2 communication. When the number of PC
exceeds 50, this method is strongly recommended.
*4: When the Vnet/IP Bus 2 performs Ethernet communication, it is possible to connect a network printer or a fileserver to the
Vnet/IP Bus 2. However, the sum of the communication band by these equipments should not exceed 300 Mbps.
For more information about using Vnet/IP bus 2 to perform Ethernet communication, refer to Vnet/IP Network
Construction Guide(TI 30A10A05-01E).
All Rights Reserved. Copyright © 2011, Yokogawa Electric Corporation GS 33K01A10-50E Mar. 5, 2012-00
<<Contents>> <<Index>> 9
I/O COMMUNICATIONS BUS
ESB Bus/Optical ESB Bus for AFV30/AFV40
An ESB bus and an optical ESB bus are used as an input/output communication bus connecting an FCS’s intelligent
part with an ESB bus node unit and optical ESB bus node unit.
Communication Specifications
Applicable units: ESB Bus Node Unit (ANB10), Optical ESB Bus Node Unit (ANB11), and Unit for Optical ESB
Bus Repeater Module (ANT10U).
No. of communication units: Numbers of ESB bus node units and optical ESB bus node units that can be connected
to ESB bus varies depending on the control functions. Number of unit for optical ESB bus repeater
module is not included in the number of the communication devices.
No. of ESB and
Field Control Unit Control Function
Optical ESB Bus Node Units (*1)
Control Function for Field Control Station (LFS1700) Max. 3/FCU
Control Function for Field Control Station (LFS1700) plus
AFV30 (*2) Max. 9/FCU
Node Expansion Package (LFS1750-V11)
AFV40 (*2)(*3)
Control Function for Field Control Station (LFS1700) plus
Max. 13/FCU
Node Expansion Package (LFS1750-V21)
*1: Model codes for ESB Bus Node Unit ANB10 and Optical ESB Bus Node Unit is ANB11.
*2: For connecting ESB bus node units and optical ESB bus node units to the FCUs (AFV30/AFV40), install ESB Bus
Coupler Modules (EC401 or EC402) in slots No. 7 and 8. Maximum 9 units of node units can be connected to EC401. As
for EC402, maximum 9 units of node units can be connected to upper and lower sides each; however, the total number of
the connected node units must not exceed the maximum numbers indicated in the above table.
*3: As for AFV40, the maximum 11 units of ESB bus node units, optical ESB bus node units, and units for optical ESB bus
repeater module can be installed in a single cabinet.
Transmission Specifications
Network topology: Bus topology
Transmission: Dual-redundant or single. When the processor module has a dual-redundant configuration,
the dual-redundant transmission is mandatory.
Transmission speed: 128 Mbps
Transmission cable: Dedicated cable (YCB301), or optical fiber cable (*1)
Transmission distance: Max. 10 m (*2), and 50 km (with Optical ESB Bus Repeater Module) (*3)
All Rights Reserved. Copyright © 2011, Yokogawa Electric Corporation GS 33K01A10-50E Nov. 18, 2011-00
<<Contents>> <<Index>> 10
ESB bus can be extended using an optical ESB bus repeater module. Chain, star, or combinations of others are
available for communication topologies.
ESB Bus
FCU ESB Bus Node ESB Bus Node
YCB301 YCB301
Optical ESB
ESB Bus Node ESB Bus Node
Bus Node YCB301 YCB301
*1: Model codes for ESB Bus Node Unit is ANB10 and ER Bus Node Unit is ANR10.
*2: For connecting ESB bus node units in an AFV10, install ESB Bus Couple Modules (EC401) in slots No. 7 and 8.
Transmission Specifications
Network topology: Bus topology
Transmission: Dual-redundant or single. When the processor module has a dual-redundant configuration,
the dual-redundant transmission is mandatory.
Transmission speed: 128 Mbps
Transmission cable: Dedicated cable (YCB301)
Transmission distance: Max. 10 m
All Rights Reserved. Copyright © 2011, Yokogawa Electric Corporation GS 33K01A10-50E Nov. 18, 2011-00
<<Contents>> <<Index>> 11
ER Bus for AFV10
An ER bus is used as an input/output communication bus connecting an ER bus node unit with ESB bus node unit or
FCU for AFV10.
Communication Specifications
Applicable units: ER Bus Node Unit (ANR10)
Number of ER buses: Max. 4 per FCU
No. of communication units: Numbers of ER bus node units that can be connected to ER bus varies depending
on the control functions.
No. of ER Bus Node No. of ESB and ER Bus Node
Field Control Unit Control Function
Units (*1) Units (*1)
Control Function for Field Control Station (LFS1500) Max. 3/FCU Max. 3/FCU
AFV10 Control Function for Field Control Station (LFS1500)
Max. 14/FCU (*2) Max. 14/FCU
plus Node Expansion Package (LFS1550)
Transmission Specifications
Network topology: Bus topology
Transmission: Dual-redundant or single. When the processor module has a dual-redundant configuration,
the dual-redundant transmission is mandatory.
Transmission speed: 10 Mbps
Transmission cable: Coaxial cable (YCB141, YCB311).
Use “YCB147/YCB149” Bus Adapter unit to connect YCB311 with YCB141 cable for
extension. Use a Grounding Unit (YCB117) per segment (*1) when YCB311 is used.
Transmission distance:
For YCB141: Max. 185 m
When YCB141 and YCB311 are connected: Length of YCB141 + (185/500) x Length of YCB311 ≤ 185 m
No. of bus adapter units: Max. 4 per segment (*1)
*1: When ER bus is used with repeaters, each part of the ER bus segmented by a repeater is called a segment.
All Rights Reserved. Copyright © 2011, Yokogawa Electric Corporation GS 33K01A10-50E Nov. 18, 2011-00
<<Contents>> <<Index>> 12
EB401
AFV10D (Node1)
ER bus
EB501
ANR10D (Node2)
AFV10D EB401
(Node1)
Repeater Repeater
EB501 EB501
ANR10D (Node3) ANR10D (Node2)
Optical Fiber Optical Fiber Optical Fiber Optical Fiber Optical Fiber Optical Fiber
Cable Cable Cable Cable Cable Cable
F04E.ai
All Rights Reserved. Copyright © 2011, Yokogawa Electric Corporation GS 33K01A10-50E Aug. 19, 2011-00
<<Contents>> <<Index>> 13
REMARKS FOR SYSTEM CONFIGURATIONS
Use of server due to the number of PC in a system
When a CENTUM VP system consists of five or more PCs, for use as HIS and others, consider if a server (OS:
Windows Server) is required or not for storing CENTUM VP project data. A server is required when a CENTUM
VP system with nine or more PCs and LHS5425 Expanded Test Functions are applied. In case LHS5170 Access
Administrator Package (for FDA:21 CFR Part11 compliant) is applied where there are nine or more PCs connected,
provide a server for historical data storage.
Judging Criteria
Equation 5 No. of stations connected = No. of recipe management package + No. of ENG
No. of Recipe Management Package: No. of PC with LHS5166 Recipe Management Package (VP Batch).
ENG: No. of PC with LHS5100/LHM5100 Standard Builder Function.
All Rights Reserved. Copyright © 2011, Yokogawa Electric Corporation GS 33K01A10-50E Aug. 19, 2011-00
<<Contents>> <<Index>> 14
Maximum number of FCS per an entire system
A control drawing describes FCS’s application program. It consists of several function blocks and inputs/outputs, and
it describes a part of plant equipment control. When LFS1750 Node Expansion Package (for AFV30/AFV40) is
used together with LFS1700 Control Function for Field Control Station (for AFV30/AFV40, Vnet/IP and FIO), the
number of connectable nodes and application capacities can be expanded. When creating a new FCS definition using
LFS1750, the number of control drawings can be specified by the builder function. The number of control drawings
can be selectable as shown below.
No. of control drawings: Selectable from 200 (default), 300, 400, or 500
Note: When LFS1750 is not used, the number of control drawings is fixed at 200.
The maximum number of FCS to be configured in the entire system depends on how many control drawings per FCS
are specified. The table below shows a guideline of the maximum number of FCS that can be configured in a system
when all the FCS selects the same number of control drawings per FCS. When different number of control drawings
are assigned per FCS, the maximum number of FCS per system changes. Please contact Yokogawa for details.
No. of control drawings per FCS Maximum No. of FCS per system
200 114 (*1)
300 83
400 65
500 54
*1: This is the sum of all types of FCS for Vnet/IP and V net. Out of 114 FCS, up to 86 of AFV30/AFV40 or 64 of AFV10
can be configured. Please contact Yokogawa for details.
All Rights Reserved. Copyright © 2011, Yokogawa Electric Corporation GS 33K01A10-50E Nov. 18, 2011-00
<<Contents>> <<Index>> 15
COMPLIANCE TO FDA: 21 CFR PART 11
Part 11 of Title 21 of the Code of Federal Regulations; Electronic Records; Electronic Signatures (21 CFR Part 11) is a
regulation issued by the U. S. Food and Drug Administration (FDA) providing a criteria of electronic records, electronic
signatures, and handwritten signatures executed to electronic records as equivalent to paper records and handwritten
signatures executed on paper. The main categories of the FDA: 21 CFR Part 11 requirements to the process control
system can be interpreted as “limiting system access to authorized individuals” and “audit trail” functions.
Here is an example of CENTUM VP system configuration complied with 21 CFR Part 11. LHS5166 Recipe
Management Package of VP Batch is adopted for recipe management.
Recipe Management
Engineering Function
Function
Recipe Data Project
(Basic Recipe) Database
Ethernet
Save / Restore
Control Network
Auxiliary Storage Device
Historical
Log Data
PC for Audit Trail
Change File
HIS Database
All Rights Reserved. Copyright © 2011, Yokogawa Electric Corporation GS 33K01A10-50E Aug. 19, 2011-00
<<Contents>> <<Index>> 16
CENTUM VP ENTRY CLASS INSTALLATION ENVIRONMENT
SYSTEM CONFIGURATION Hardware standard installation environment is
CENTUM VP Entry Class is a system designed for a described as below, except for that of PC, Enclosed
small-scale project. CENTUM VP Entry Class controls Display Style Console, Node Units and I/O Modules for
and monitors up to 8000 tags. FIO. For more details, refer to the specifications or GS
for PC, HIS for enclosed display style console, open
desktop style console, Node Units and I/O Modules for
System Configuration and Software FIO node unit.
CENTUM VP Entry Class offers the following software Ambient temperature:
packages. 5 – 40 °C (Desk for CENTUM (YAX101),
General-purpose Desk(YAX801))
Model Code 0 – 50 °C (FCS, BCV, Bus Repeater,
for
CENTUM VP
Description Remarks Node Unit)
Entry Class Ambient humidity:
20-80 % RH
Standard Operation and No. of Tags:
LHM1101
Monitoring Function Maximum 8000 10-90 % RH (FCS, BCV, Bus Repeater,
Node Unit with no dew condensation)
Server for Remote
LHM1150 Operation and Monitoring —
Temperature change rate: ± 10°C/hour
Function Power supply:
100-120V AC ± 10%, Frequency; 50/60
Control Drawing Status
LHM4410
Display Package
— Hz ± 3 Hz
220-240V AC ± 10%, Frequency; 50/60
Logic Chart Status Display
LHM4420
Package
— Hz ± 3 Hz
24 V DC ± 10%
Process Management No. of Active
Withstanding Voltage:
Package Recipe:
Type A: 4 or less 100-120 and 220-240 V AC: 1500 V AC
LHM6660 Type B: 10 or for 1 minute
less 24 V DC: 500 V AC for 1 minute
Type C: 999 or Insulation resistance:
less 20 MΩ/500 V DC
FCS Data Setting/ 10 MΩ/500 V DC (for YAX101 and
LHM6710 Acquisition Package — YAX801)
(PICOT) Grounding: Independent ground of up to 100 Ω
resistance
Software for Engineering Noise:
Electrical Field: Up to 3 V/m (26 MHz to 1.0 GHz)
Model Code Up to 3 V/m (1.4 to 2.0 GHz)
for
Description Remarks
Up to 1 V/m (2.0 to 2.7 GHz)
CENTUM VP Magnetic Field: Up to 30 A/m (AC), Up to 400 A/m
Entry Class (DC)
LHM5100 Standard Builder Function — Static: Up to 4 kV (direct discharge), Up to 8 kV
LHM5150 Test Function — (aerial discharge)
Self-documentation Continuous Vibration:
LHM5490 — Displacement amplitude: Up to 0.25 mm (1 to 14
Package
Hz)
The same packages for CENTUM VP system can be Acceleration: Up to 2 m/s2 (14 to 100 Hz)
used other than the above packages. There is no
limitation in FCS.
LHS4000 Million tag handling package (for one million
tag) is not applicable to CENTUM VP Entry Class HIS.
As for multiple project connection function for CENTUM
VP Entry Class, refer to GS for Multiple Project
Connection (GS 33K05K20-50E).
All Rights Reserved. Copyright © 2011, Yokogawa Electric Corporation GS 33K01A10-50E Jan. 1, 2012-00
<<Contents>> <<Index>> 17
REGULATORY COMPLIANCE
CENTUM VP hardware conforms to the standards listed below. See respective GS to find out what standards each
hardware complies.
Safety Standards (*1) (*2) Note: According to th e New Approach Directive, the
[CSA] manufacturer and the representative office in EU
are indicated below:
CAN/CSA-C22.2 No.61010-1 Manufacturer: Yokogawa Electric Corporation (2-
[CE Marking] Low Voltage Directive 9-32 Nakacho, Musashino-shi, Tokyo 180-8750,
EN 61010-1 (*3) Japan).
Representative office in EU Community:
EMC Conformity Standards (*2) Yokogawa Europe B.V. (Euroweg 2, 3825 HD
[CE Marking] EMC Directive Amersfoort, The Netherlands).
EN 55011 Class A Group 1 (*4)
EN 61000-6-2 (*5) *1: For ensuring all the hardware devices to satisfy
EN 61000-3-2 (*6) the safety standards, the dedicated breakers in
the power supply distribution board must conform
EN 61000-3-3 (*7)
to the following specifications.
[C-Tick Marking] [CSA] CAN/CSA-C22.2 No.5 or UL 489
EN 55011 Class A Group 1 (*4) [CE Marking] EN 60947-1 and EN 60947-3
[KC Marking] *2: To conform to the safety standards and the
EMC conformity standards, install the 19-inch
Korea Electromagnetic Conformity Standard rack mountable type devices in a keyed metallic
Standards for Hazardous Location Equipment cabinet.
For selecting the right products for explosion protection, *3: Analog input side of this equipment has
please refer to TI 33Q01J30-01E without fail. Measurement category I. For details, see
“CENTUM VP Installation Guidance” (TI
[CSA Non-Incendive] (*8) 33M01J10-40E).
Class I, Division 2, Groups A,B,C and D Temperature *4: A Class A hardware device is designed for use in
code T4 the industrial environment. Please use this device
CAN/CSA-C22.2 No. 0-M91 in the industrial environment only.
CAN/CSA-C22.2 No. 0.4-04 *5: A lightening arrestor or the like is required to
meet this surge immunity standard. The length
CAN/CSA-C22.2 No. 157-92
of the cable to feed the external power supply
C22.2 No. 213-M1987 for AGS813 AO channels should not exceed 30
TN-078 meters.
(for 100-120 V AC and 24 V DC power supply) *6: An external device such as a power unit with
[FM Non-Incendive] (*9) harmonic current neutralizer and an active
Class I, Division 2, Groups A, B, C and D harmonics conditioner must be connected to meet
this harmonic current emission standard.
Temperature code T4
*7: The specified limits of voltage drop across wiring
Class 3600: 1998 must be satisfied to meet this standard.
Class 3611: 2004 *8: To meet the standard for hazardous location
Class 3810: 2005 equipment, 19-inch rack-mounted devices must
(for 100-120 V AC, 220-240 V AC and 24 V DC be installed in a keyed metallic cabinet approved
power supply) by CSA or non-incendive regulator in your area.
[Type n] (*10) *9: To meet the standard for hazardous location
equipment, 19-inch rack-mounted devices must
II 3 G Ex nA IIC T4 Gc (*11) be installed in a keyed metallic cabinet approved
II 3 G Ex nA nC IIC T4 Gc (*12) by FM or non-incendive regulator in your area.
EN 60079-0:2009 *10: To be compatible with Type n, for example the
EN 60079-0:2012 requirements of cabinet must be met. For details,
EN 60079-15:2010 refer to the Explosion Protection (TI 33Q01J30-
(for 24V DC power supply) 01E).
II 3G EEx nA II T4 *11: Applied for products complied with Type n, except
EN 50021: 1999 for AFV10S, AFV10D, AFV30S, AFV30D and
ADR541.
(I/O Module with built-in barrier, for 24 V DC power
*12: Applied for the below products.
supply) AFV10S, AFV10D, AFV30S, AFV30D and
[Type i (Intrinsic Safety)] ADR541
II (1) G D [EEx ia] II C
EN 50014: 1997 +A1 +A2
EN 50020: 1994
[FM Intrinsic Safety]
Associated intrinsically safe apparatus for connection to
Class I, II and III, Division 1, Groups A, B, C, D, E, F
and G or
Class I, Zone 0, Group II C
Class 3600: 1998
Class 3610: 2010
ANSI/ISA-60079-0: 2009
ANSI/ISA-60079-11: 2009
All Rights Reserved. Copyright © 2011, Yokogawa Electric Corporation GS 33K01A10-50E Apr. 1, 2013-00
<<Contents>> <<Index>> 18
TRADEMARKS
• CENTUM, Vnet/IP, ProSafe and Exaopc are
registered trademarks of Yokogawa Electric
Corporation.
• Windows is a registered trademark of Microsoft
Corporation in the United States and /or other
countries.
• Ethernet is a registered trademark of XEROX
Corporation.
• Modbus is a registered trademark of Schneider
Electric and/or such related companies.
• EtherNet/IP is a trademark of Open DeviceNet
Vendor Association (ODVA).
• “FONDATION” of “FONDATION fieldbus” is a registered
trademark of Fieldbus Foundation.
• HART is a registered trademark of the HART
Communication Foundation.
• Other product and company names appearing in this
document are trademarks or registered trademarks of
their respective holders.
All Rights Reserved. Copyright © 2011, Yokogawa Electric Corporation GS 33K01A10-50E Jan. 1, 2012-00
Subject to change without notice.