Cause and Effect Drawing

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

05/26/2017 Page: 1

Drawings & Document ECOMS File: custdocs.nsf


Cover Sheet As of 02/04/05
5710 Mellon Road
Export, PA 15632-8948
Attn: Debbie Harbaugh / Document Control

FS-Elliott Factory Order: C611520MOD1 User Location: KUWAIT


Purchaser:BADER AL-MULLA AND General Order:
BROS. CO. WLL
Customer Purchase 4300007456 Customer Item No:
Order:
User: KUWAIT NATIONAL Serial No: 54368
PETROLEUM COMPANY

Title Document No FS-Elliott Drawing/Document No


(if required)
CAUSE AND EFFECT LIST C611520MOD1-413

Total No of Sheets Rev Code Sent Size Customer


(If reqd) Tag No
2 0 R
Includes Cover Sheet?
Yes

This Drawing/Document Supersedes: Rev Date Superseded

Date Sent Return By Date


05/26/2017 06/09/2017
Distribution Note: Project Engineer
Return Documents To: Name: MALLORY STEWART
Debbie Harbaugh Email: [email protected]
Document Control Administrator
FS-Elliott Company, LLC
5710 Mellon Road
Export, PA 15632-8948

E-Mail: [email protected]
Phone: 724-387-4982
Fax: 724-387-3270

AP = FOR CUSTOMER APPROVAL - RETURN APPROVED DOCUMENT IF REQUIRED:


R = FOR RECORD - DO NOT RETURN, ONLY FOR CORRECTION RETURN THE ATTACHED
C = CERTIFIED, FINAL - DO NOT RETURN DRAWING/DOCUMENT WITHIN (2) WEEKS
AFTER THE ISSUE DATE. IF COMMENTS
PR = PRELIMINARY - RETURN APPROVED DOCUMENT
ARE APPLICABLE, COMMENTS WILL BE
AB = AS BUILT - DO NOT RETURN CONSIDERED AND THE DOCUMENT
I = FOR INFORMATION - DO NOT RETURN REISSUED.
Q = ELECTRONICALLY FAILURE TO RETURN
CD = CD ROM DRAWING/DOCUMENT OR PROVIDE
D = DISKETTE FURTHER COMMENTS BEYOND REVISION
1 OR AS STATED IN THE CONTRACT, MAY
RESULT IN DELAY IN MANUFACTRURING
AND MAY INCUR ADDITIONAL COSTS.
SYMBOL DRAWING
PID
CAUSE AND EFFECT CHART ABBREVIATIONS USED IN THE MATRIX :

O = Open
C = Close

COMP
R = Run (Start) Equipment

MTR

MTR

OHR

CAR
UVT
AOP

AOP

CTR
TFA
IGV
SD = Shutdown
P = Permissive
Y = Yes

EFFECT
EQUIPMENT
A = Alarm
LOGIC IDENTIFICATION T = Trip

TAG
V = Voting

GENERAL NOTES:

TRANSMITTER FAIL ACTION


(1) Permissive to start the equipment  . 

SERVICE DESCRIPTION

AUX OIL PUMP START


‐Oil pressure must above low alarm

MAIN MOTOR START

ALARM INDICATION
AUX OIL PUMP STOP
UNLOADING VALVE

INLET GUIDE VANE


MAIN MOTOR STOP

TRIP INDICATION
‐Oil temperature  must be above low alarm

COMPRESSOR

AUTO START
OIL HEATER
SERVICE
(2)     Seal Air required to put Aux Oil Pump into 
Circulate Mode only, Aux Oil can be started   
MOTOR DRIVEN without seal air during the compressor 
starting sequence. 

(3)     Pressure to be above AOP shut off setpoint 
before AOP will be shut off during startup or 
will  start up be aborted. 

Transmitter Failure

Transmitter Failure
(4)     Alarms/Trips on a 4 second delay on startup 

SEE NOTE 2, 3 &7

ALARM-HIGH
ALARM-LOW
and instantaneous  afterwards 

TRIP-HIGH
SEE NOTE 6

TRIP-LOW
RANGE
NOTE
CAUSE

High
Low
(5)     Alarms/Trips  on a 25 second delay on startup 
and instantaneous  afterwards 

(6)     When oil  temperature reaches   the low  setpoint
the heater be activated to heat the oil.  If oil  is
Service Monitored below the low level setpoint the oil heater will 
FSE Ref. Symbol PID NUMBER Sheet # Description Tag #

10

11

12

13

14

15

16

17

18

19
Enabled be locked out.

9
Description By:
LVT-X WC - 254127 2 Low Speed Compressor Vibration X Transmitter (See Note 4) Compressor Yes PLC VE/VT-150 4 T R O SD C T Y Y 0 to 101.6 um --- 22.86 um --- 30.48 um -20.32 um 121.92 um (7)     AOP is shutdown  after the 15 minute cool 
down period is completed. 
HVT-X WC - 254127 2 High Speed Compressor Vibration X Transmitter (See Note 4) Compressor Yes PLC VE/VT-151 4 T R O SD C T Y Y 0 to 101.6 um --- 22.86 um --- 30.48 um -20.32 um 121.92 um
(8)     Any active alarm or trip will cause an 
IAT WC - 254127 3 Final Interstage Temperature Air Yes PLC TE/TT-150 T R O SD C T Y Y -28.9 to 104.4 °C --- 70.6 °C --- 73.3 °C -55.6 °C 131.1 °C Alarm/Trip Annunciation  .
ACT WC - 254127 3 After Cooler Disch. Air Temperature Air Yes PLC TE/TT-151 A Y -28.9 to 82.3 °C --- 48.9 °C --- --- -51.1 °C 104.5 °C
(9)       If condensate  level does not drop below the alarm    
AFDP WC - 254127 3 Air Filter Differential Pressure Air Yes PLC PDT-150 A Y 0 to 63.5 cmH2O --- 25.4 cmH2O --- --- -12.7 cmH2O 76.2 cmH2O state for 10 minutes the compressor will trip on  
DPT WC - 254127 3 Final Discharge Air Pressure Air Yes PLC PT-151 T R O SD C T Y 0 to 14.06 K/cm2 --- --- --- --- -2.81 K/cm2 16.87 K/cm2 condensate  level trip.

SPT WC - 254127 3 System Pressure Air Yes PLC PT-152 10 T R O SD C Y T Y 0 to 14.06 K/cm2 --- --- --- --- -2.81 K/cm2 16.87 K/cm2 (10)     When in Auto START or Auto START/STOP mode 
the air compressor will  start and/or stop when the   
SAPT WC - 254127 3 Seal Air Pressure Transmitter Air Yes PLC TBD A Y 0 to 1.05 K/cm2 0.17 K/cm2 --- --- --- -0.21 K/cm2 1.26 K/cm2
system  pressure signal rises above or falls below 
OPT WC - 254127 4 Inlet Oil Pressure Oil Yes PLC PT-158 T R O P(1&3) SD C T Y Y 0 to 7.03 K/cm2 1.48 K/cm2 --- 1.05 K/cm2 7.03 K/cm2 -1.41 K/cm2 8.44 K/cm2 the system pressure setpoint.

OFDP WC - 254127 4 Oil Filter Differential Pressure Oil Yes PLC PT-157 A Y 0 to 7.03 K/cm2D --- 1.27 K/cm2D --- --- -1.41 K/cm2D 8.44 K/cm2D

IOT WC - 254127 4 Inlet Oil Temperature Oil Yes PLC TE/TT-153 T R O P(1) SD C T Y Y -28.9 to 104.4 °C 21.1 °C 57.2 °C --- 60 °C -55.6 °C 131.1 °C

MAT WC - 254127 3 Motor Amps Transmitter Driver Yes PLC IT-150 T R O SD C T Y Y 0 to 200 Amps --- 61.38 Amps 11.16 Amps --- -40 Amps 240 Amps

CPT --- --- Control Panel Temperature Panel Yes PLC --- A Y -17.8 to 57.2 °C --- 29.4 °C --- --- -32.8 °C 72.2 °C

M --- --- Motor Status Signal From MCC Driver Yes PLC --- T R O SD C Y --- to --- --- --- --- --- --- ---

E-STOP --- --- Emergency Stop Pushbutton Driver Yes PLC --- T R O SD C Y --- to --- --- --- --- --- --- ---

PPS --- --- Panel Purge Switch Driver Yes PLC --- P Y Y --- to --- --- --- --- --- --- ---

PSFLT1 --- --- Power Supply Fault # 1 Panel Yes PLC --- Y --- to --- --- --- --- --- --- ---

PSFLT2 --- --- Power Supply Fault #2 Panel Yes PLC --- Y --- to --- --- --- --- --- --- ---

OHRSW --- --- Oil Heater On/Off Switch Oil Yes PLC --- R --- to --- --- --- --- --- --- ---

LOLS --- --- Low Oil Level Switch Oil Yes PLC --- Y Y --- to --- --- --- --- --- --- ---

KUWAIT NATIONAL PETROLEUM COMPANY CAUSE AND EFFECT CHART Doc. No. Order Number Pg. Rev.

S.O.: C611520MOD1 C611520MOD1 1 0