The document summarizes the design of a septic tank and soil absorption system for a hostel housing 125 persons. The septic tank is designed to be 8.5m x 3.4m x 1.1m to treat the peak flow of 300 liters per minute. 25 soak pits are designed, each being 31m long and 1m wide, with a 2m spacing between pits. The total land area required is 2325m2 and the total percolation area is 775m2.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
2K views5 pages

Design of Septic Tank

The document summarizes the design of a septic tank and soil absorption system for a hostel housing 125 persons. The septic tank is designed to be 8.5m x 3.4m x 1.1m to treat the peak flow of 300 liters per minute. 25 soak pits are designed, each being 31m long and 1m wide, with a 2m spacing between pits. The total land area required is 2325m2 and the total percolation area is 775m2.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

Design of Septic tank

Dr Girija.T.R,
Department of Civil Engineering,
School of Technology,
Assam DonBosco University
• Design a Septic tank for a hostel housing 125 persons. Also design the soil absorption system
for the disposal of septic tank effluent assuming the percolation rate as 20 minutes /cm.Peak
discharge for 125 persons is equal to 300 lpm.Assume sludge withdrawal once in a year.
Solution:
From the design specification:
Surface area required = 0.92 𝑚2 for every 10 lpm peak flow rate.
Capacity for Sludge digestion = 0.032 𝑚3 /capita
Storage of sludge and scum = 7.3 𝑚3 /100 persons for a cleaning interval of 1 year
Design of Septic tank:Peak discharge = 300 lpm
0.92
Surface area of tank @0.92 𝑚2 for every 10 lpm = × 300 = 27.6 𝑚2
10
Assume Depth of sedimentation =0.3 m ; Provide free board of 0.3 m; Total Volume of the tank :
1. for sedimentation = 27.6x0.3 =8.28 𝑚3
2.for digestion = 0.032x125 =4 𝑚3
7.3
3.For sludge storage = x125 =9.125 𝑚3
100
4.Free board
(including provision for seed sludge) =27.6x0.3 =8.28 𝑚3
Total(1+2+3) =29.685 𝑚3 contd
𝑇𝑜𝑡𝑎𝑙 𝑉𝑜𝑙𝑢𝑚𝑒 29.685
Total Depth of tank = = = 1.076 𝑚
𝐴𝑟𝑒𝑎 27.6
Provide a Depth of 1.1 m .
Keep L/B ratio 2.5
Area =LxB = 2.5xBxB =27.6 ; from which B=3.32
Keep B = 3.4 m ; L = 2.5x3.4 =8.5 m
Hence tank dimensions are 8.5 mx3.4 mx1.1 m
Design of Absorption system
The total subsurface soil area required for the soak pits or dispersion
trenches is given by:
Q = 130 /√𝑡; where Q is the maximum rate of effluent application in
lpd/𝑚2 of the leaching surface.
t = standard percolation rate for the soil , in minutes /cm
here t = 20 min/cm
Q = 130 20 = 581 lpd/𝑚2
Total sewage flow per day = 300 l/min = 300 x60x24 =432000 litres/day
Total sewage flow per day 432000
Total trench area required = = = 743.54 𝑚2
𝑚𝑎𝑥𝑖𝑚𝑢𝑚 𝑟𝑎𝑡𝑒 𝑜𝑓 𝑒𝑓𝑓𝑙𝑢𝑒𝑛𝑡 𝑎𝑝𝑝𝑙𝑖𝑐𝑎𝑡𝑖𝑜𝑛 581

Assume the width of trench as 1m length as 30 m spacing between the trenches as 2m .


No of trenches required = 743.54/(30x1)=24.78.
Provide 25 trenches with 31 m length and 1m width . With spacing as 2m ,
Total land area required = 25 x31 x3 =2325 𝑚2
Percolation area =25x31x1 =775 𝑚2
Details of septic tank and the soil absorption system are shown
in the next slides