Controlled Switching of Circuit Breaker and Its Site Measurement
Controlled Switching of Circuit Breaker and Its Site Measurement
Country own 1987 1988 1989 1990 1991 1992 I993 Sub-total
I Austria 15 1 13 10 39
Belgium 2 4 6 I
-777-
Even though there were studies on this phase-controlled means CB’s mechanical performance must be very
switching technique in China long time ago, but there stable: closing or opening time for every 2 operations
was no application in the electric network until 1997. In should be equal or less than 0.5 ms, even coils are under
1998. the first unit of phase-controlled switching device different operation voltages.
was used in 500 KV transmission line instead of closing For CB used to break the sinall inductive current, in
resistors. In 2000, 2 units of phase-controlled switching order to get optimum break performance ( i.e. the
devices were in service for breaking reactors. By the minimum switching over-voltage), this CB should be
end of 2001, there will be 5 units for breaking reactors, specially staggered: phase A opened first, phase B and
and 2 units for capacitor banks in service, all of them C staggered 90 degree and opened simultaneously. For
being used together with SF6 breakers for 35 KV 50 Hz system, phase B and C delay 5 ins. Figure 2
distribution network. These phase-controlled switching shows opening diagram of ABB LTB 72.5DI/BUS
CBs used in distribution system are all from ABB breaker. We can see phase B and C delayed 5 ms than
company. Fig. 1 shows the phase-controlled switching phase A.
-778-
determined by the processor based on entered data and A breaker always has a certain scatter of the operation
i n Adaptive Mode the results of earlier closing. time and dielectric strength. Statistically, the best phase
When E l 13 is used in Adaptive Mode, it notes the position for closing is little bit later than theoretical one.
phase position for switching carried out and adjusts its Because an early phase position gives a bigger prestrike
waiting time TVTOT for the next switching, taking into than a late phase position. E l 13 takes this into account
account any deviation from the desired phase position. with the factor TDz .
Such deviation can, for example, be caused by variation Since closing usually takes place by pre-arcing. the time
in the operation time. Adaptive mode is most required at from issued command until the circuit closes is
closing, at which current onset in current transformer normally longer than the operation time measured fi-om
'4' is usually used to detect that switching has been when command is issued until galvanic closing occurs.
carried out. E l 13 takes this into account with factor TD;. (see Fig.
3)
Closing the Shunt Capacitor Bank
Breaking of Shunt Reactors
Because the time zero of processor is the reference
voltage zero point, but the reference voltage is not Ideal breaking for shunt reactor is non-reignition
al"'ays the "Itage Of the CB phase to be first closed. breaking. That means to make the arcing as long as
Usually, the best phase position for switching has a possible, and break circuitat current zero,
distinct to the phase position Of the CB was connected into circuit like shown in figure 4,
"Itage in the Same phase' The phase difference To set the parameter of phase control switching unit.
between the latter and the reference "Itage used because reference voltage is from phase A. and first
depends On from which phase, Or between which phase opening phase is phase A too, so we input the parameter
the reference voltage is taken. The time difference
between the reference voltage and the best like following: T D I = S . O ~ S ,T D ~ =3.7IllS TD;
=O.Oms .
switching moment is called time delay TDI. In Fig.3,
closing capacitor bank, for phase R, TDI=O , (reference
voltage is taken from phase R ); for phase S , T ~ i = 6 . 7
ins; for phase T, T ~ 1 = 3 . 3ms. ( for 50 Hz network).
-779-
Voltage and current of phase A and C were recorded by
oscilloscope on site test. Each phase-controlled
switching CB was tested 3 times. One typical
oscillogram is shown in Figure 5. From the oscillogram.
we can found that the phase A and C almost ideally
. . break the current on Current zero point( See arrow
!
..- point). Each test is of almost the same results. .The
.- .
maximum over-voltage is about 1.09 P.u..
CONCLUSIONS
REFERENCES
Uref : ( Phase A to earth) Reference voltage: 1: line
current : ug : Recovery voltage : Ubd : Dielectric strength of 1 . ClGRE Report, ELEKTRA No. I63
llic arc-quenching chamber : T a m i n : Shortest Arcing Time which
2 . ' SWITCHSYNC E 113 for synchronous switching
hcs not cause reignition at recovery voltage corresponding to I
of circuit breaker', ABB Product information. 5409
722-96E rev. 1
11 ti : 2 T ~ : 2Total window for contact separation .
Fig.4 The breaking principle to break a star
connection shunt reactor[*]
-780-