Liebert iCOM: User Manual - Intelligent Communications & Monitoring
Liebert iCOM: User Manual - Intelligent Communications & Monitoring
Liebert iCOM™
User Manual - Intelligent Communications & Monitoring
TABLE OF CONTENTS
1.0 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
i
4.0 TEAMWORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
4.1 Teamwork Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
4.1.1 Application of Teamwork Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
4.1.2 No Teamwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
4.1.3 Teamwork Mode 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
4.1.4 Teamwork Mode 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
4.1.5 Standby – Rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
ii
FIGURES
Figure 1 Liebert iCOM components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Figure 2 Liebert iCOM display components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Figure 3 Status menu, large display, graphical view. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Figure 4 Liebert iCOM default screen symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Figure 5 Menu tree—Small display, stand-alone or networked . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Figure 6 Menu tree—Large display, stand-alone. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Figure 7 Menu tree—Large display, networked. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Figure 8 User menu icons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 9 Service menu icons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Figure 10 Start-stop priority switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 11 Temperature proportional band . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 12 One single-step compressor without unloaders. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Figure 13 Two single-step compressors without unloaders or one compressor with an unloader (two-step) 17
Figure 14 Two compressors with unloaders (four-step) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 15 Digital scroll capacity modulation, 10-100% variable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Figure 16 Single and dual digital scroll compressor activation points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Figure 17 Three-point actuator control (example: cooling) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Figure 18 Second cooling source and compressorized cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Figure 19 Three-stage heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 20 Two single-step compressors with SCR reheat set to Tight mode . . . . . . . . . . . . . . . . . . . . . . . . . 24
Figure 21 Two single-step compressors with SCR reheat set to Standard mode . . . . . . . . . . . . . . . . . . . . . . 25
Figure 22 Humidity proportional band. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Figure 23 Teamwork Mode 1 with two cooling units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Figure 24 Connecting two cooling units, each with a small display using a crossover Ethernet cable . . . . 43
Figure 25 Wiring a small display for stand-alone operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Figure 26 Wiring a small display for U2U network operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Figure 27 Wiring a large display for stand-alone operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Figure 28 Wiring a large display for U2U network operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Figure 29 Liebert iCOM input-output control board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Figure 30 Liebert vNSA with optional remote large display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Figure 31 Liebert iCOM display dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
iii
TABLES
Table 1 Keyboard icons and functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Table 2 User menu icons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Table 3 Service menu icons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Table 4 Reheat configuration types. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Table 5 Parameters for infrared humidifier control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Table 6 Dehumidification With Comp settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Table 7 Customer inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Table 8 Possible event settings—some events not available in all units . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Table 9 Event notifications—large or small display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Table 10 Sample Liebert iCOM network configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Table 11 Ports available for connecting Liebert iCOM control devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Table 12 Setpoints parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Table 13 Spare part list parameters—large display only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Table 14 Event log parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Table 15 Graphics parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Table 16 View network parameters—large display only* . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Table 17 Set alarms parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Table 18 Sensor data parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Table 19 Active alarms parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Table 20 Display setup parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Table 21 Total run hours parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Table 22 Timer parameters—Sleep Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Table 23 Service contacts parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Table 24 Setpoints parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Table 25 Unit diary parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Table 26 Maintenance / wellness settings parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Table 27 Standby settings / lead-lag parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Table 28 Diagnostics / service mode parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Table 29 Set alarms parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Table 30 Set alarms parameters (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Table 31 Sensor calibration / setup parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Table 32 System / network setup parameters—large display only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Table 33 Network setup parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Table 34 Options setup parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Table 35 Service contacts parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
iv
Introduction
1.0 INTRODUCTION
The Liebert iCOM™ control offers the highest capabilities in unit control, communication and moni-
toring of Liebert mission-critical cooling units.
Liebert iCOM may be used to combine multiple cooling units into a team that operates as a single
entity, enhancing the already-high performance and efficiency of Liebert’s units.
Liebert iCOM is available as a factory-installed assembly or may be retrofitted on existing products
with SM, AM or AG controls. Large graphic display wall-mount versions of the control are available
for remote operation and monitoring of cooling units.
1.1 Features
Large and Small Displays
The Liebert iCOM control is available with either a large or small liquid crystal display.
• The Liebert iCOM with small display has a 128 x 64 dot matrix screen that simultaneously
shows two menu icons, along with descriptive text. This display is capable of controlling only the
unit it is directly connected to.
• The Liebert iCOM with large display has a 320 x 240 dot matrix screen that shows up to 16
menu icons at a time, as well as descriptive text. This display can be used to control a single cool-
ing unit or any cooling unit on a network, regardless of how it is connected—either integrated into
a cooling unit or simply connected to the network and mounted remotely.
Liebert iCOM’s menu-driven display is used for all programming functions on each connected cooling
unit. The Status menu shows the status of the conditioned space, such as room temperature and
humidity, temperature and humidity setpoints, alarm status and settings, event histories and the
current time.
Figure 1 Liebert iCOM components
1
Liebert iCOM Display Components and Functions
ESC
?
On/Off Key Help Key Left Arrow Key Enter Key Right Arrow Key
ESC
Escape Key Down Arrow Key
NOTE
The Help key may be pressed at any time for a brief explanation of what is being viewed.
2
Liebert iCOM Display Components and Functions
Increase Key
Moves upward in a menu or increases the value of a selected parameter.
(Up Arrow)
Decrease Key
Moves downward in a menu or reduces the value of a selected parameter.
(Down Arrow)
3
Liebert iCOM Display Components and Functions
4
Liebert iCOM Display Components and Functions
NOTE
Settings are readable without a password, but changing settings requires a password.
5
Liebert iCOM Display Components and Functions
NOTE
Entering the Service menu password permits access to both the User and Service menus.
To enter a password:
1. Navigate to the menu that contains the parameter to be changed.
2. Select Password in the submenu by pressing the Enter key
3. Press the Enter key to move your cursor to the right side of the screen to select the question
marks.
4. Use the arrow keys to enter the numeral for the password’s first digit (the up arrow key moves
from 1 to the next digit).
5. Use the right arrow key to move to the next question mark and repeat Step 4 to enter all digits in
the password.
6. After entering the password, press enter.
If the password is correct, the Actual Level shown to the right of Password will change
from 0 to 1 or 2. The menu will remain locked if the password was incorrect.
NOTE
Returning to the Status menu will require re-entering a password to make changes.
Status Menu
Unit 1 View
6
Liebert iCOM Display Components and Functions
Status Menu
Unit 1 View
7
Liebert iCOM Display Components and Functions
8
Liebert iCOM Display Components and Functions
°C / °F
View and change temperature and humidity
% RH Setpoints
setpoints
Small & Large
SET
EVENT
Event Log Contains last 400 events Small & Large
LOG
SET
Set Alarms Allows enable, disable and settings for alarms Small & Large
ALARMS
12
Change settings for display: language, time,
9 3 Display Setup
simple or graphic view
Small & Large
SET 6
9
Liebert iCOM Display Components and Functions
12
Allows setback settings for non-peak
9 3 Sleep Mode Small & Large
operation
6
10
Liebert iCOM Display Components and Functions
°C / °F
% RH Setpoints To view and change temperature and humidity setpoints Small & large
SET
Standby Settings/
Allows lead/lag setup when multiple units are connected Small & large
Lead-Lag
SERVICE
SET
Set Alarms Allows enable, disable and settings for alarms Small & large
ALARMS
Sensor
Allows calibration of sensors Small & large
+/- Calibration/Setup
NETWORK
System/Network
Allows setup and U2U communication for multiple units Large
Setup
11
Operation
3.0 OPERATION
The Liebert iCOM display for your Liebert cooling unit features an easy-to-use, menu-driven liquid
crystal display (LCD). All unit settings and parameters can be viewed and adjusted through three
menus: User, Service and Advanced. All active alarms are displayed on the LCD and annunciated.
The control is shipped from the factory with default selections for all necessary settings. Adjustments
can be made if the defaults do not meet your requirements.
References to menu items in this manual are followed by the main menu and the submenu where they
can be found.
For example:
• Temperature Setpoint (User Menu, Setpoints) - The Temperature Setpoint parameter is
located in the User menu under the Setpoints submenu.
• High Return Humidity (Service Menu, Set Alarms) - The High Return Humidity alarm is
located in the Service menu under the Set Alarms submenu.
NOTE
Customer switches: remote On/Off (if used) and display On/Off switches are in series. A
cooling unit will start only if both switches are On; if one of these switches is Off, the unit will
stop. Safety devices within the unit are also in series and will shut the unit down if required.
NOTE
If Remote On/Off is not used, a jumper is inserted to bypass the switch.
12
Operation
Autorestart
When there is a loss of power to the cooling unit and power comes back, the unit will return to its pre-
vious operating status—on if it was on before the power off, off if it was off.
When power returns, the autorestart time—time-selectable: Single Unit Auto Restart (Service Menu,
Options Setup)—controls the start of the unit. The autorestart time runs in a loop, starting the next
unit each time when elapsed, starting with Unit # 1.
NOTE
Loss of power alarm will be activated only on units that had the fan on before power was lost.
NOTE
When the Main Fan Overload alarm is active, the Loss of Airflow alarm is masked out.
13
Operation
NOTE
Low-pressure condition could be read through contacts or through pressure transducers with
threshold setting.
Pump Down
The Pump Down operation is performed to protect the compressor oil from being diluted with liquid
refrigerant to ensure that the compressor is properly lubricated for the next startup. The Pump Down
operation operates in the following manner:
Whenever a compressor is turned Off and the low-pressure switch is closed (pressure OK), the com-
pressor will be operated with the LLSV (liquid line solenoid valve) closed (de-energized) until the low-
pressure switch opens (low-pressure condition, without giving alarm). When there is a call to turn off
a compressor the LLSV is closed. If the low suction pressure switch (LPS) does not open within a spec-
ified time, the LLSV is turned On then back Off (to try to unstick the LLSV). The control will then
wait a set period of time for the LPS to open. This will happen three times. If, after three times, the
low suction pressure switch does not open, the compressor and LLSV are locked off and an alarm
“Pump Down not completed” will appear.
There is a re-pump down if the LPS opens again after the compressor has been already stopped—a
maximum of six re-pump-down cycles per hour are allowed. At the seventh request of re-pump down
the alarm “Comp 1 Pumpdown Fail” or “Comp 2 Pumpdown Fail” will appear and the compressor will
be locked out.
Pump down is always performed loaded (for compressors with unloaders: unloaders off, digital scroll:
control solenoid valve disabled).
For digital scroll only: when pump down has finished successfully (LPS opened), pump down will be
continued for another half-second with the control solenoid valve energized.
High Pressure Alarm
When the compressor is initially activated, the system will be monitored for a high pressure situation.
When a high pressure situation is detected during the first 10 minutes of operation, the unit will
attempt to correct the problem several times without notification. If the unit is unsuccessful in cor-
recting the problem, an alarm will occur and the affected compressor will be locked off. If high head
pressure alarm trips three times in a rolling 12 hour period, the affected compressor will be locked off.
After the compressor has been running for 10 minutes, if a high head pressure situation is detected,
an alarm will occur and the affected compressor will be immediately locked off without the unit trying
to correct the problem.
Once the compressor is locked off, it will not come back on until main power is reset, or until the
HP Alarm Counters (Service Menu, Diagnostics) are reset to 0. Setting the counter to 0 will auto-reset
the alarm without the need of pressing the reset button on the display. Even if the pressure in the
system drops below the alarm point, the compressor will remain off until the system is reset.
NOTE
If the unit is equipped with manual reset high head pressure switches, or if the auto reset high
head pressure switches don’t reset, the compressor will not be turned back on, but there will be
a 30-second delay from when the high head pressure situation occurs and when the alarm is
annunciated.
14
Operation
NOTE
The Auto setting attempts to maintain equal run times between compressors.
15
Operation
Without Deadband
Heating Cooling
- Temp + Temp
½ Proportional Band ½ Proportional Band
- 100 % 0% + 100%
Heating Setpoint Cooling
With Deadband
Dead-
Heating band Cooling
- Temp + Temp
½ Proportional Band ½ Proportional Band
- 100% 0% 0% + 100%
Heating Setpoint Cooling
When the return air temperature deviates from the setpoint it begins to penetrate one of the propor-
tional band halves, cooling or heating. If the return air temperature increases, the control calls for 0%
(none) to 100% (full) cooling capacity based on how far the temperature penetrates the cooling portion
of the proportional band. If the return air temperature decreases, the control calls for 0% (none) to -
100% (full) heating capacity based on how far the temperature penetrates the heating portion of the
proportional band.
When the return air temperature reaches the end of the proportional band, either 100% or -100%, full
cooling or full heating capacity is provided. No operation is performed when a 0% call is calculated.
The control varies the call for cooling and heating in 1% increments as the return air temperature
moves through the proportional band halves.
The deadband range is used to widen the setpoint. When the return air temperature falls within the
deadband, the control operates the same as if the temperature equaled the setpoint exactly. This set-
ting helps maximize component life by preventing excessive component cycling. The Temperature
Proportional Band and Temperature Deadband parameters are in the Service menu under the Set-
points submenu. The Temperature Setpoint parameter is in both the User menu and Service Menu
under Setpoints.
There is a parameter AutoSet Enable (Service Menu, Setpoints), which automatically sets the propor-
tional bands for temperature and humidity, and both the integration time factors according to the
type of unit (Chilled Water, single or double compressor), with influence of the selected Teamwork
Mode. See 4.1 - Teamwork Modes for more on using this feature.
16
Operation
70 71 72 73 74 75
0% + 100 %
½ Proportional Band
Cooling Cooling
Increasing Temperature
Figure 13 Two single-step compressors without unloaders or one compressor with an unloader (two-step)
70 71 72 73 74 75
Increasing Temperature
17
Operation
70 71 72 73 74 75
0% Cool 1 Cool 3 + 100 %
Cooling Off Off Cooling
Cool 2 Cool 4
Off Off
½ Proportional Band
Increasing Temperature
18
Operation
0% Loaded
0 5 10 15 20 25 30
On single and dual digital scroll compressor systems, the first compressor is started at 25% calculated
output from the temperature proportional band and stopped at 10%. On dual digital scroll compressor
systems, the second compressor is started at 35% and stopped at 20%, see Figure 16. When a com-
pressor is started, the solenoid is energized longer than it is de-energized to match the call for cooling.
When the call for cooling increases to 100%, the solenoid is de-energized for the entire 15 second cycle.
Comp 1 & 2 On
Temp Setpoint : 70°F Fully Loaded
Proportional Band : 8°F Comp 2 On Partially
Deadband : 2°F Loaded
Comp 1 On Partially
Loaded
½ Dead-
band
70 71 72 73 74 75
0% + 100 %
Comp 1
Cooling Cooling
Off
Comp 2
Off
½ Proportional Band
Increasing Temperature
19
Operation
Requested 3P Position
Cooling
0% - 3P Closed + Temp
½ Proportional Band
0% + 100%
Setpoint Cooling
20
Operation
The Value setting is the factory default setting on free-cooling and dual cooling units. If the tempera-
ture difference between the second source cooling fluid parameter, Free-cooling Fluid Temperature
(User Menu, Sensor Data) and room air is equal to or greater than the adjustable DT Between Room
Air / FC Fluid (Service Menu, Setpoints) value, then the second source cooling fluid will be used to
provide at least partial cooling (delta T between room and glycol = true).
Sensors used for this delta T are: room/local sensor or the return air sensor; and the glycol sensor.
If this delta T is true, the following actions will be performed:
1. The Free-Cooling Status indication will show “On” instead of “Off”.
2. The compressor band will be shifted to the right by 100%, and within the first 100% the free-
cooling valve band will take place (see Figure 18).
+ 100 %
Cooling
½ Dead-
band
2nd
Comp
Source
70 71 72 73 74 75 76 77 78 79
Minimum Chilled Water Temperature—This feature permits the user to select the minimum
chilled water temperature that allows simultaneous operation of the second cooling source (chilled
water control) and compressor control. This feature is enabled in the Service menu under Setpoints,
parameter Minimum CW Temp.
Below this minimum chilled water setpoint, parameter Minimum CW Temp Value, (Service Menu,
Setpoints), the control will operate ONLY the second cooling source control, i.e., the compressor is
locked out. Above the minimum chilled water setpoint, assuming the fluid temperature is below the
return room air temperature (delta T between room and glycol = true), the control will operate the
second cooling source control and compressor control simultaneously if needed.
If the Minimum CW Temp is disabled, the second cooling source temperature is ignored, the control
will always operate the second cooling source and compressors simultaneously when the load requires
it.
21
Operation
GLYCOOL™ Cooling—Free-Cooling
When GLYCOOL cooling is available, the temperature control will calculate a total cooling require-
ment of 200% rather than 100%. Assuming that full GLYCOOL capacity is available, the GLYCOOL
valve opens proportionally as the requirement for cooling rises from 0 to 100%. If more than 100%
cooling is required, then the compressors are activated at 150% and 200% respectively (133%, 163%,
180% and 200% for a four-step system). If full GLYCOOL capacity is not available, then the GLY-
COOL valve will be opened proportionally over a cooling requirement band equal to the available
GLYCOOL capacity. The compressors would be activated when the GLYCOOL capacity is exceeded.
For example, if the GLYCOOL capacity is 60%, then the GLYCOOL valve would be full open at 60%
cooling requirement and the compressors would activate at 110% and 160% cooling requirement. In
order to reduce compressor cycling and prevent hunting, GLYCOOL capacity first becomes available
when the entering glycol temperature is at least 8°F (-13°C) (22% capacity) below the return air tem-
perature, or 3°F (-16°C) below the return air temperature for two hours. GLYCOOL capacity is 100%
when the glycol temperature is 25°F (-4°C) below the return air temperature. The system will con-
tinue to operate in Econ-O-Cool mode as necessary as long as the entering glycol temperature
remains at least 3°F (-16°C) (0% capacity) below the return air temperature. If GLYCOOL is not
available, the temperature control will operate the compressors in the same manner as a two-step or
four-step system without GLYCOOL.
Dual Cooling Source
If dual cooling is available, the sensible cooling system operates in the same manner as a GLYCOOL
system, except that it is assumed that 100% chilled water capacity is available any time the chilled
water temperature is 3°F (-16°C) below the return air temperature.
NOTE
1. Hot gas / hot water are not influenced by the setting of electric reheat during
dehumidification.
2. Hot gas output will be set only if the selected compressor is in operation.
22
Operation
65 66 67 68 69 70
-100 % 0%
Heating Heat 3 Heat 2 Heat 1 Heating
Off Off Off
½ Proportional Band
Decreasing Temperature
23
Operation
NOTE
Some cooling units are not suited for a strict NO LOAD application. These cooling units
require a minimal load in the space. Consult factory for verification.
Figure 20 Two single-step compressors with SCR reheat set to Tight mode
Temp Setpoint: 70°F
Cool 2
Proportional Band: 8°F
On
Deadband: 0°F
SCR On
Cool 1 On
62 63 64 65 66 67 68 69 70 71 72 73 74
24
Operation
Standard Mode
In Standard mode, the SCR reheat operates only when the Temperature Proportional Band calls for
heating. SCR reheat output is adjusted proportionally as the Temperature Proportional Band varies
the requirement for heating from 0% to -100%. Compressors operate only when there is a call for cool-
ing as described in 3.2.2 - Compressor Control.
Figure 21 illustrates how SCR reheat operates when SCR Control Type is set to Standard mode.
Figure 21 Two single-step compressors with SCR reheat set to Standard mode
Temp Setpoint : 70°F
Proportional Band : 8°F Cool 2
Deadband : 0°F Cool 1 On
On
SCR
On
66 67 68 69 70 71 72 73 74
-100% 0% 100 %
Heating Cool 1 Off Cool 2 Cooling
SCR Off Off
25
Operation
Without Deadband
Humidification Dehumidification
- Hum + Hum
- 100% ½ Proportional Band 0% ½ Proportional Band
Setpoint + 100%
humidification
Dehumidification
With Deadband
Dead-
Humidification band
- Hum Dehumidification + Hum
- 100% ½ Proportional Band 0% 0% ½ Proportional Band + 100%
Humidification Setpoint Dehumidification
When the return air humidity deviates from the setpoint, it begins to penetrate one of the propor-
tional band halves, either dehumidification or humidification. If the return air humidity increases,
the control calls for 0% (none) to 100% (full) dehumidifying capacity, based on how far the humidity
penetrates the dehumidification portion of the proportional band. If the return air humidity
decreases, the control calls for 0% (none) to -100% (full) humidifying capacity based on how far the
humidity penetrates the humidification portion of the proportional band.
When the return air humidity reaches the end of the proportional band, either 100% or -100%, full
dehumidification or full humidification capacity is provided. No operation is performed when a 0%
call is calculated. The control varies the call for dehumidifying and humidifying in 1% increments as
the return air humidity moves through the proportional band halves.
The deadband range is used to widen the setpoint. When the return air humidity falls within the
deadband, the control operates the same as if the humidity equaled the setpoint exactly. This setting
helps maximize component life by preventing excessive component cycling. The Humidity Propor-
tional Band and Humidity Deadband parameters are in the Service menu under the Setpoints sub-
menu. The Humidity Setpoint parameter is in both the User menu and Service menu under
Setpoints.
26
Operation
3.5.1 Humidification
Infrared Humidifier
There are two types of infrared humidifiers: small pan (IFS) and large pan (IFL). The operating mode
of each is similar, however, some of the variables or timings differ.
Infrared humidifiers are started at 100% humidification request, and stopped at 0%. Infrared humid-
ifiers cannot be driven in proportional mode.
Table 5 Parameters for infrared humidifier control
Parameter IFS Default IFL Default
Humidity in Last xx Hours 15 hours 15 hours
Prefill Time 30 seconds 60 seconds
Fill Time 4 minutes 7 minutes
Humidifier On Time 8 or 10 minutes 10 minutes
Flush Rate 150% 150%
An autoflush system automatically controls a water makeup valve to maintain proper levels in the
infrared humidifier water pan during humidifier operation. If humidification is needed and 15 hours
have elapsed since the last time the humidifier was on, then the humidifier is not turned on until the
valve completes an initial fill of the humidifier pan. This pre-fill is about 30 seconds for a small pan
and 60 seconds for a large pan. The valve continues to fill and flush the pan for about 4-1/2 minutes
for a small pan or 7-1/2 minutes for a large pan. Pan size is selected based on unit specifications and
is preset at the factory.
During humidifier operation, with the flush rate set at the default of 150%, the valve is opened peri-
odically to add water to the pan (about 45 seconds every 7 minutes of humidifier operation for a small
pan, or 80 seconds every 10 minutes of operation for a large pan). This adds enough water to the pan
to cause about a third of the total water used to be flushed out of the overflow standpipe located in the
humidifier pan. This action helps to remove solids from the pan. The flush rate is adjustable from
110% to 500% in 10% intervals. Default is 150%. If the water quality is poor, it may be desirable to
increase the water flushing action above the normal 150% rate. Also, if the supply water pressure is
low, the flush rate adjustment can be increased so that sufficient water level is maintained during
humidification. The flush rate parameter, Infrared Flush Rate (Service Menu, Options Setup), is
adjustable from 110%-500%.
External Humidifier Control—Optional
A factory-supplied option may be provided to allow a start-stop command to be sent to the control of a
remote-mounted humidifier.
27
Operation
3.5.2 Dehumidification
The Dehumidification Enable parameter (Service Menu, Options Setup) allows for enabling/disabling
the dehumidification function.
A call for dehumidification is calculated in the same way as a cooling request. The components
(valves, compressors) will follow this dehumidification request as soon as it is higher than the request
for cooling.
NOTE
If a cooling unit is equipped with SCR reheat and the SCR Control Type parameter is set to
Tight mode, then Low Limit 2 will be ignored, see 3.4 - Temperature Control—Reheat.
Low Limit 1 & 2 will be available only on cooling units with two compressors when Dehumidification
With Comp is set to BOTH (see WARNING on page 29).
28
Operation
! WARNING
If the electrical service to the unit is not properly sized, it could trip the building circuit
breakers (or fuses) or, in extreme cases, damage the building wiring. This Warning applies
only when the Dehumidification With Comp is set to BOTH and the Electric Reheat
Operation is set to Staged. Consult factory before making any changes to the default settings.
29
Operation
NOTE
The actual return air temperature sensor reading is always displayed on the Status menu. The
value displayed for the return air humidity sensor reading depends on the Humidity Sensor
Control Type (see 3.6.2 - Humidity Sensor Reading Control Types).
NOTE
The historical humidity sensor graphs will display the real (unadjusted) sensor readings, no
matter which Humidity Control Sensor Type is selected. The graphical sensor data is in the
User menu under Graphics.
30
Operation
NOTE
The Supply Limit is calculated on each unit, independent of the other sensor readings on the
network.
NOTE
There is an auto-reset of the event messages if the temperature/humidity constantly stays 1.8°F
(1°C)/ 2% RH below or above the threshold for a time of one minute.
31
Operation
NOTE
To enabled/disabled, delay activation and set event type (alarm, warn, message) see Event
Types on page 33.
32
Operation
NOTE
Not all critical event properties can be adjusted.
Event Types
• Message: If this event occurs, it will only be entered into the event log.
• Warning: If this event occurs, a warning will be generated and entered into the event log. The
general alarm relay will be activated only if parameter Warning Activates Alarm Relay located in
the Service menu under Alarm Setup is set to Yes (Yes is the default setting from the factory)
• Alarm: If this event occurs, an alarm will be generated and entered into the event log. An alarm
does not necessarily switch off the whole cooling unit; it depends on which alarm occurs. If a
standby unit is set, any alarm will stop the faulty unit and ask the standby unit to start. Standby
activation is achieved on alarms ONLY; messages or warnings will not start the standby unit. For
more on standby units, see 4.0 - Teamwork.
Time Delay
Delays the event reaction once it is triggered. The time delay applies to safety functions and is
entered in seconds.
Enable or Disable
Disabled events do not show up in the event log, on the display or on monitoring devices. Also, the
common alarm relay will not be activated if a disabled alarm occurs. Safety functions, such as lockout
compressor in case of high pressure are still performed.
NOTE
Once a disabled event (set to Warn or to Alarm) becomes active, it will lock itself. Disabled
events may be reset only through the menu item Reset Disabled Alarms.
NOTE
The value of the external delay includes the internal delay:
external delay = setting – internal delay.
The minimum setting of the external delay is the value of the internal delay. This is valid only
for values marked with *.
33
Operation
34
Operation
35
Operation
36
Operation
37
Teamwork
4.0 TEAMWORK
Unit-2-Unit (U2U) Communications via a private network will allow the following functions to be
placed into operation when the requirement exists. The user must install the correct hardware
(see 5.0 - Installing a Liebert iCOM Unit-to-Unit Network) and properly program the units for
the selected functionality.
The Liebert iCOM network can perform the following functions:
The Teamwork Mode functions allow for multiple stages of cooling/heating and humidifica-
tion/dehumidification. Teamwork Mode can be used to prevent environmental units from “fighting,”
where one environmental unit might be cooling while another unit is heating.
The Standby (Lead/Lag) function allows one or more units to be set as “Running” and “Standby” for
activation in case of an alarm. This function also allows the units to be programmed in a rotation to
help ensure “Standby” unit operation.
The Cascade Operation function allows additional units to be staged-on based on the temperature
or humidity requirement.
4.1.2 No Teamwork
All cooling units work independently, responding to their own sensors.
Standby function and unit rotation are possible, but cascading is not (see Standby and Cascade on
page 40). Autoset will not adjust the proportional band in Teamwork mode No.
38
Teamwork
NOTE
1. Proportional actuators (chilled water valve, free-cooling actuator) are driven in parallel in
all units.
2. Changeover to second cooling source, low limit during dehumidification and low supply
limit control air local functions, managed from each unit independently.
Figure 23 shows how two cooling units work together in Teamwork Mode 1. Since Unit 1 and Unit 2
are available to operate, the master unit, Unit 1, averages the temperature and humidity sensor read-
ings from each unit.
The master unit determines that a 60% call for cooling is required for the system. Since there are two
available cooling units, each unit makes up half of the system proportional band; Unit 1 handles 0-
50% system call for cooling and Unit 2 handles 51-100%. For every 1% system call for cooling, each
unit provides 2% of its total cooling capacity.
The 60% system call for cooling exceeds the 50% Unit 1 can provide, so Unit 1 operates at full capac-
ity. The remaining 10% system call for cooling (60% - 50% = 10%) is handled by Unit 2. Unit 2
responds by operating at 20% cooling capacity (50% ÷ 10% = 20%).
System
Proportional Heating Cooling
Band +
- Temp ½ Proportional Band ½ Proportional Band Temp
- 100 % 0% + 100 %
Setpoint
39
Teamwork
NOTE
In Teamwork Mode 2, all units must have the same setpoints. The units’ proportional band,
deadband and related settings may differ.
NOTE
Before entering standby mode, units will operate the fan only for 3 minutes to cool the electrical
heaters, remove steam from the unit, etc.
NOTE
Cascaded units are not included in the calculation of the average temperature / humidity.
40
Installing a Liebert iCOM Unit-to-Unit Network
NOTE
The maximum number of cooling units that may be interconnected is 32.
41
Installing a Liebert iCOM Unit-to-Unit Network
Network communication can be configured during system startup by a Liebert-trained technician. For
technical issues contact:
Liebert Technical Service
1050 Dearborn Drive
Columbus, Ohio 43235
Telephone: 1-800-LIEBSRV (1-800-543-2778)
E-Mail: [email protected]
42
Installing a Liebert iCOM Unit-to-Unit Network
Figure 24 Connecting two cooling units, each with a small display using a crossover Ethernet cable
Three or more units with small displays: To network three or more cooling units, each equipped
with a small display, connect a straight-through CAT5 Ethernet cable from the P64 connector on each
cooling unit’s Liebert iCOM input/output board to a common network switch (see Figure 26).
Large Displays
A network switch is required to enable Ethernet communication on one or more cooling units with
large displays. Each cooling unit with a large display requires two straight-through Ethernet cables
from a network switch. One cable connects to port P64 on the Liebert iCOM input/output board and
the other straight-through cable connects to the female-female coupler provided with the unit. Con-
nect the red crossover cable, which is provided with the cooling unit, between the coupler and the P64
port on the back of the large display (see Figure 28).
NOTE
Only cooling units with large displays are supplied with a female-female coupler inside the
unit from the factory.
43
Installing a Liebert iCOM Unit-to-Unit Network
P61 P63 E5
P64
P67
P18 P65
P40
P32
P66
P8
P11
P12
P7 P13
iCOM
P33
P35
P43
P54 TB1 E1 E2 E3 E4
P22 P38 P39 P53 P52 P51 P4
182964
Page 1
Unit Electronics Compartment Rev. 0
P61 P63 E5
P64
P67
P18 P65
P40
P32
P66
P8
1 Straight-Through
P11
P12
Ethernet Cable
P7 P13
P35
P43
P54 TB1 E1 E2 E3 E4
P22 P38 P39 P53 P52 P51 P4
Networking Switch
182964
Page 1
Rev. 0
To Other Units
(64 nodes total;
maximum of 32 input/output boards)
44
Installing a Liebert iCOM Unit-to-Unit Network
8-Wire Crossover
Ethernet Cable (Red)
6-Wire Cable
P61 P63 E5
P64
P67
P18 P65
P32
P40
P66
P8
P12
P11 P7 P13
iCOM
P33
P35
P43
P54 TB1 E1E2 E3E4
P22 P38 P39 P53 P52 P51 P4
182964
Page 2
Unit Electronics Compartment Rev. 0
2 Straight-through
P61 P63 E5
Ethernet Cables-
P64 Connect One to P64
P67
P66
Crossover Coupler
P8
P11
P12
As Shown
P7 P13
iCOM
P33
P35
P43
P54 TB1 E1 E2 E3 E4
P22 P38 P39 P53 P52 P51 P4
Networking Switch
182964
Page 2
Rev. 0 To Other Units
(64 nodes total;
maximum of 32 input/output boards)
45
Installing a Liebert iCOM Unit-to-Unit Network
P67
P66
Liebert vNSA
The Liebert vNSA is designed to connect multiple Liebert iCOM control devices. The Liebert vNSA
contains either one or two powered industrial rail switches. An optional remote large display can be
attached to the front door as well. All models have a power supply that requires connection to a single
phase 120V or 240VAC power source. The enclosure features a key lock for security.
The Liebert vNSA supports autonegotiation, autopolarity and autocrossing, allowing for the use of
standard network cables for connection to each port, rather than special crossover cables. The switch
detects and makes adjustments for the network's speed and transmission mode, polarity and trans-
mit-and-receive pins. See the Liebert vNSA user manual, SL-18840, for more details.
The number of ports available for connecting Liebert iCOM control devices varies by model as shown
in Table 11. Models with a remote large display attached to the front door utilize one of the available
Ethernet ports in the Liebert vNSA. Models with two switches utilize two ports to connect the
switches.
Table 11 Ports available for connecting Liebert iCOM control devices
Liebert
vNSA With Number of Ports Number of Ports Number of Ports
Remote Used to Connect Used to Available to
Large Total Number Remote Large Interconnect Connect Liebert iCOM
Model Display of Ports Display Switches Control Devices
Liebert vNSA8-Liebert 8 1 - 7
iCOM
Yes
Liebert vNSA16- 16 1 2 13
Liebert iCOM
Liebert vNSA8 8 - - 8
No
Liebert vNSA16 16 - 2 14
46
Installing a Liebert iCOM Unit-to-Unit Network
3.298"
(84mm)
12"
(305mm)
14.25"
(362mm)
DPN001136
Rev. 0
47
Mounting a Large Display on a Wall
Mounting Instructions
1. See Figure 31 for dimensions and mounting arrangements. Mark the wall where screws or bolts
will be inserted to support the large display.
Either of two mounting methods may be used:
a. Secure the back of the large display to the wall by inserting screws or bolts through the
elliptical slots (recommended mounting method), or
b. Insert screws in the wall and use the keyhole-shaped holes on the back of the housing
2. Route the factory-supplied power supply cable and field-supplied CAT5 Ethernet cable through
the wall to the mounting location for connection to the rear of the Liebert iCOM wall-mount
display (see Figure 31).
3. Remove the back of the display by prying it away from the front half of the housing using the coin
slots along the seam.
4. Insert the power and Ethernet cables through slots in the rear of the display (slots are marked).
Leave adequate slack for connections and mounting.
To relieve strain on the connections to the display circuit board:
a. Use the strain-relief slots above the connections on the upper part of the recessed area to hold
the cables.
b. Use a twist tie to secure the cables to the small bridge on the back of the display.
5. Position the display and use either of the following methods to attach the display to the wall:
a. Elliptical Slot Mounting: Insert the #10 pan head screws or bolts through the elliptical
slots and screw into the wall or wall anchors. Tighten firmly.
OR
b. Keyhole Slot Mounting: Insert the #10 pan head screws or bolts into the wall, leaving space
between the screw head and wall to permit hanging the display.
6. Connect the power and Ethernet cables to the display circuit board (the board is marked).
7. Attach the front of the display to the mounted rear panel of the assembly—unit snaps together.
48
Mounting a Large Display on a Wall
AC Adapter/Plug
120V/60Hz-12VDC
10ft. (3048mm) routed
through wall to back 12VDC Pwr SW/U2U
P64
of display housing
(provided by Liebert)
3.14"
1.4" (80mm)
(36mm)
8.83"
(224mm)
4.52"
(115mm) 4.13"
(105mm)
1.4" 5.2"
2.11"
(36mm) (132mm)
FRONT VIEW (54mm)
BACK VIEW
SIDE VIEW
DPN000800a
Rev. 0
49
User Menu Parameters
50
User Menu Parameters
51
User Menu Parameters
Active Alarms
Permits viewing all current, active alarms.
Table 19 Active alarms parameters
!
Function
ACTIVE
Read/ Range Default
ALARMS Large Display Small Display Write Imperial (metric) Setting
Page 1 of 1
Active Alarms ACTIVE ALARMS R - -
52
User Menu Parameters
53
User Menu Parameters
9
12
3
Table 22 Timer parameters—Sleep Mode
6
Function
Read/ Range Default
Large Display Small Display Write Imperial (metric) Setting
Page 1 of 1
Password PASSWORD W - -
Sleep On: - - - -
Mon MON W No, Yes No
Tue TUE W No, Yes No
Wed WED W No, Yes No
Thu THU W No, Yes No
Fri FRI W No, Yes No
Sat SAT W No, Yes No
Sun SUN W No, Yes No
Sleep Every Day (1) - - - -
START1 / START1 / 00:00
From / To W Time (hh:mm)
STOP1 / STOP1 00:00
Sleep Every Day (2) - - - -
START2 / START2 / 00:00
From / To W Time (hh:mm)
STOP2 / STOP2 00:00
54
Service Menu Parameters
Page 2 of 5
Password PASSWORD W - -
Humidity Setpoint HUM SET W 20-80% 50%
Relative, Compensated,
Humidity Control Type HUM CTRL W Predictive
Predictive
Humidity Proportional Band HUM PB W 1-20% 10%
Humidity Integration Time HUM INT W 0-15 min 0
Humidity Deadband HUM DB W 0-50% 0
Dehum/Heat Low Limit 1 LO LIM 1 W (-)9.9°F - (-)2.0°F -
Dehum/Heat Low Limit 2 LO LIM 2 W (-)9.9°F - (-)2.0°F -7.0°F
Page 3 of 5
Password PASSWORD W - -
Supply Limit SUP LIM W Enabled, Disabled Disabled
Supply Limit Temp Value SUP TEMP W 41-77°F (5-25°C) 41°F
FC: Value;
DT between Room / FC Type FC TYPE W No, Contact, Value
DX,CW: No
DT between Room Air/ FC Fluid FC DT W 0-36°F (-18 - 2 °C) 8°F, 5°C
FC: Yes
Minimum CW Temp MIN CW W No, Yes
DX,CW: No
Minimum CW Temp Value MIN CW W 32-68°F (0-20°C) 45°F
55
Service Menu Parameters
°C / °F
Table 24 Setpoints parameters
% RH Function
Read/ Range Default
SET Large Display Small Display Write Imperial (metric) Setting
Page 4 of 5
Password PASSWORD W - -
VSD Fanspeed FANSPEED W Auto, Manual, Economy Auto
DX =100%
VSD Setpoint STD VSD SET W 60 to 100%
CW = 60%
DX =100%
VSD Setpoint MIN VSD MIN W 60 to 100%
CW = 60%
DX =100%
VSD Setpoint Dehum VSD DEH W 60 to 100%
CW = 60%
DX =100%
VSD Setpoint No Power VSD NOP W 60 to 100%
CW = 60%
Page 5 of 5
Password PASSWORD W - -
SCR Control Type SCR TYPE W Tight, Standard Tight
Start Compressor 1 At CO1 ON W -150 to +100% 0%
Stop Compressor 1 At CO1 OFF W -200 to +50% -200%
Compressor 1 Stop Delay CO1 TD W 0-30 min 20 min
Start Compressor 2 At CO2 ON W -150 to +100% 100%
Stop Compressor 2 At CO2 OFF W -200 to +50% 0%
Compressor 2 Stop Delay CO2 TD W 0-30 min 0 min
Cycle Time CYCLET R 1.0 – 200.0 sec -
SCR Factor SCRFACT W 1.0 to 10.0 1.0
Actual SCR Request ACT SCR R 0-100% -
56
Service Menu Parameters
See 3.8.1 - Calculation of Next Maintenance and Diagnostics for details on these menus.
Table 27 Maintenance / wellness settings parameters
WELLNESS Function
Read/ Range Default
Large Display Small Display Write Imperial (metric) Setting
Basic Settings (Page 1 of 8)
Password PASSWORD W - -
Maintenance Frequency Per Year FREQ/YR W 0-12 per year 1
Max Bonus BONUS W 0-12 0
Max Penalty PENALTY W 0-12 0
Last Maintenance LAST PM W Date -
Service Engineer SERVICE W Name -
Confirm PM CONFIRM W No, Yes -
Calculated Next Maintenance NEXT PM W Date -
57
Service Menu Parameters
58
Service Menu Parameters
59
Service Menu Parameters
Page 2 of 7
Password PASSWORD W - -
Manual Mode MANUAL W No, Yes -
Motor(s) MOTOR(S) W Off, On -
Compressor 1 COMP1 W Off, On -
Compressor 1 C1 MODE W Run, Evacuate, Charge -
Compressor 1 Capacity C1 CAP W Off, On -
Compressor 1 Cycle Ramp C1 CYCLE W 0-100% -
Compressor 1 LLSV LLSV 1 W Off, On -
Compressor 2 COMP2 W Off, On -
Compressor 2 C2 MODE W Run, Evacuate, Charge -
Compressor 2 Capacity C2 CAP W Off, On -
Compressor 2 Cycle Ramp C2 CYCLE W 0-100% -
Compressor 2 LLSV LLSV 2 W Off, On -
Page 3 of 7
Password PASSWORD W - -
Electric Heat 1 (or HG/HW) EL HEAT1 W Off, On -
Electric Heat 2 (or E.Heat 1) EL HEAT2 W Off, On -
Electric Heat 3 (or E.Heat 2) EL HEAT3 W Off, On -
BV Control BV CTRL W Manual, Auto -
LWD Value LWD Val R 0-100 -
Humidfier Fill HUM FILL W Off, On -
Humidifier HUM W Off, On -
Humidfier Drain H DRAIN W Off, On -
Humidifier Current HUM.C. R 0,00 - 99,99A -
Status LSI LSI R Off, On -
60
Service Menu Parameters
Page 6 of 7
Status HP1 HP1 R OK, Act -
Status LP1 LP1 R OK, Act -
Status C1 OL C1 OL R OK, Act -
Status HP2 HP2 R OK, Act -
Status LP2 LP2 R OK, Act -
Status C2 OL C2 OL R OK, Act -
61
Service Menu Parameters
62
Service Menu Parameters
63
Service Menu Parameters
64
Service Menu Parameters
65
Service Menu Parameters
Page 2 of 3
Password PASSWORD W - -
Temperature Sensor A TEMP A W ±18°F (±9.9°C) -
Calibrated Temperature Sensor A CAL A R 32-122°F (0-50,0°C) -
Humidity Sensor A HUM A W ±9.9% -
Calibrated Humidity Sensor A CAL A R 20-80% -
Temperature Sensor B TEMP B W ±18°F (±9.9°C) -
Calibrated Temperature Sensor B CAL B R 32-122°F (0-50,0°C) -
Humidity Sensor B HUM B W ±9.9% -
Calibrated Humidity Sensor B CAL B R 20-80% -
Page 3 of 3
Password PASSWORD W - -
Freecool Sensor PTC or NTC FC SNSR W PTC, NTC NTC
Freecool Sensor FC SNSR W ±18°F (±9.9°C) -
Calibrated Freecool Sensor CAL FC R 4-113°F (-15-45°C) -
Supply Sensor PTC or NTC SUP SNSR W PTC, NTC NTC
Supply Sensor SUP TEMP W ±18°F (±9.9°C) -
Calibrated Supply Sensor CAL SUP R 32-122°F (0-50,0°C) -
Temperature Sensor C TEMP C W ±18°F (±9.9°C) -
Calibrated Temperature Sensor C CAL C R 32-122°F (0-50,0°C) -
Humidity Sensor C HUM C W ±9.9% -
Calibrated Humidity Sensor C CAL C R 20-80% -
66
Service Menu Parameters
NETWORK
Table 32 System / network setup parameters—large display only
Function
Read/ Range Default
Large Display Small Display Write Imperial (metric) Setting
Page 1 of 2
Password PASSWORD W - -
Number of Connected —
W 1-32 -
Units
Teamwork Mode — W No,1,2 No
-
67
Service Menu Parameters
NETWORK
Table 33 Network setup parameters
Function
Read/ Range Default
Large Display Small Display Write Imperial (metric) Setting
Page 1 of 2
Password PASSWORD W - -
Monitoring Address MON ADD W 3
68
Service Menu Parameters
69
Service Menu Parameters
70
Service Menu Parameters
Notes
71
Service Menu Parameters
72
Ensuring The High Availability
0f Mission-Critical Data And Applications.
Emerson Network Power, the global leader in enabling business-critical Technical Support / Service
continuity, ensures network resiliency and adaptability through Web Site
a family of technologies—including Liebert power and cooling www.liebert.com
technologies—that protect and support business-critical systems. Monitoring
800-222-5877
Liebert solutions employ an adaptive architecture that responds
[email protected]
to changes in criticality, density and capacity. Enterprises benefit Outside the US: 614-841-6755
from greater IT system availability, operational flexibility and Single-Phase UPS
reduced capital equipment and operating costs. 800-222-5877
[email protected]
Outside the US: 614-841-6755
Three-Phase UPS
800-543-2378
[email protected]
Environmental Systems
800-543-2778
Outside the United States
614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
While every precaution has been taken to ensure the accuracy
and completeness of this literature, Liebert Corporation assumes no
Fax: +39 049 5841 257
responsibility and disclaims all liability for damages resulting from use of Asia
this information or for any errors or omissions. 7/F, Dah Sing Financial Centre
© 2007 Liebert Corporation 108 Gloucester Road, Wanchai
All rights reserved throughout the world. Specifications subject to change
without notice. Hong Kong
® Liebert and the Liebert logo are registered trademarks of Liebert 852 2572220
Corporation. All names referred to are trademarks Fax: 852 28029250
or registered trademarks of their respective owners.
SL-18835_REV01_09-07
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.
©2007 Emerson Electric Co.