Emerson PLC Ec20: HMI Setting

The document provides guidelines for connecting an Emerson PLC EC20 series PLC to Emerson HMI devices using an RS232 connection. It lists the recommended communication parameters for the HMI, the Modbus RTU protocol used by the PLC, and addresses for reading and writing data types in the PLC. Wiring diagrams are provided for connecting several HMI models to the PLC's RS232 terminal using a 9-pin to 9-pin cable.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
324 views3 pages

Emerson PLC Ec20: HMI Setting

The document provides guidelines for connecting an Emerson PLC EC20 series PLC to Emerson HMI devices using an RS232 connection. It lists the recommended communication parameters for the HMI, the Modbus RTU protocol used by the PLC, and addresses for reading and writing data types in the PLC. Wiring diagrams are provided for connecting several HMI models to the PLC's RS232 terminal using a 9-pin to 9-pin cable.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

PLC Connection Guide

EMERSON PLC EC20


Supported Series: EMERSON PLC EC20 Series. (Modbus RTU Protocol)

HMI Setting:
Parameters Recommended Options Notes
PLC type EMERSON PLC EC20
PLC I/F RS232
Baud rate 9600 9600, 19200, 115200
Data bits 8 7 or 8
Parity Even Even, Odd, None
Stop bits 1 1 or 2
PLC sta. no. 0 0-255

PLC Setting:
Communication mode Modbus RTU protocol

Device Address:
Bit/Word Device type Format Range Memo
B Y OOO 0 ~ 377 0000-02550
B X OOO 0 ~ 377 1200-01455 0000-0255
B M DDDD 0 ~ 1999 2000-3999
B SM DDD 0~ 255 4400-4655
B S DDD 0 ~ 991 6000-6991
B T DDD 0 ~ 255 8000-8255
B C DDD 0 ~ 255 9200-9455
W D DDDD 0 ~ 7999 0000-7999
DW D_Double DDDD 0 ~ 7998
W SD DDD 0 ~ 255 8000-8255
W Z DD 0 ~ 15 8500-8515
W TV DDD 0 ~ 255 9000-9255
W CV DDD 0 ~ 199 9500-9699
DW C_Double DDD 200 ~ 255 9700-9811
PLC Connection Guide

Wiring Diagram:
Emerson EC 20 COM1: RS-232 Terminal (Diagram 1 ~ Diagram 3)
Diagram 1
cMT Series cMT3071 / cMT3072 / cMT3090 / cMT3103 / cMT3151

eMT Series eMT3070 / eMT3105 / eMT3120 / eMT3150

MT-iE MT8073iE / MT8102iE

MT-XE MT8092XE

MT-iP MT6103iP / MT8102iP

HMI PLC
COM1 COM3
RS232
RS232 RS232 Terminal
9P Female 9P Female
Rx 2 8 TX
Tx 3 7 RX
GND 5 5 GND
PLC Connection Guide

Diagram 2
cMT Series cMT-SVR / cMT-G01 / cMT-G02 / cMT-HDM / cMT-FHD

mTV mTV

MT-iE MT8070iE / MT6070iE / MT8100iE / MT8121iE / MT8150iE /


MT8071iE / MT6071iE / MT8072iE / MT6072iE / MT8073iE /
MT8101iE / MT8102iE / MT8103iE
MT-XE MT8121XE / MT8150XE / MT8090XE

HMI PLC
COM1
RS232
RS232 Terminal
9P Female
Rx 2 TX
Tx 3 RX
GND 5 GND

Diagram 3
MT-iE MT8050iE / MT8053iE

MT-iP MT6051iP / MT8051iP / MT6071iP / MT8071iP

HMI PLC
COM1
RS232
RS232 Terminal
9P Female
Rx 9 TX
Tx 6 RX
GND 5 GND