Emerson PLC Ec20: HMI Setting
Emerson PLC Ec20: HMI Setting
HMI Setting:
Parameters Recommended Options Notes
PLC type EMERSON PLC EC20
PLC I/F RS232
Baud rate 9600 9600, 19200, 115200
Data bits 8 7 or 8
Parity Even Even, Odd, None
Stop bits 1 1 or 2
PLC sta. no. 0 0-255
PLC Setting:
Communication mode Modbus RTU protocol
Device Address:
Bit/Word Device type Format Range Memo
B Y OOO 0 ~ 377 0000-02550
B X OOO 0 ~ 377 1200-01455 0000-0255
B M DDDD 0 ~ 1999 2000-3999
B SM DDD 0~ 255 4400-4655
B S DDD 0 ~ 991 6000-6991
B T DDD 0 ~ 255 8000-8255
B C DDD 0 ~ 255 9200-9455
W D DDDD 0 ~ 7999 0000-7999
DW D_Double DDDD 0 ~ 7998
W SD DDD 0 ~ 255 8000-8255
W Z DD 0 ~ 15 8500-8515
W TV DDD 0 ~ 255 9000-9255
W CV DDD 0 ~ 199 9500-9699
DW C_Double DDD 200 ~ 255 9700-9811
PLC Connection Guide
Wiring Diagram:
Emerson EC 20 COM1: RS-232 Terminal (Diagram 1 ~ Diagram 3)
Diagram 1
cMT Series cMT3071 / cMT3072 / cMT3090 / cMT3103 / cMT3151
MT-XE MT8092XE
HMI PLC
COM1 COM3
RS232
RS232 RS232 Terminal
9P Female 9P Female
Rx 2 8 TX
Tx 3 7 RX
GND 5 5 GND
PLC Connection Guide
Diagram 2
cMT Series cMT-SVR / cMT-G01 / cMT-G02 / cMT-HDM / cMT-FHD
mTV mTV
HMI PLC
COM1
RS232
RS232 Terminal
9P Female
Rx 2 TX
Tx 3 RX
GND 5 GND
Diagram 3
MT-iE MT8050iE / MT8053iE
HMI PLC
COM1
RS232
RS232 Terminal
9P Female
Rx 9 TX
Tx 6 RX
GND 5 GND