Bus Protection Application Challenges 1 PDF
Bus Protection Application Challenges 1 PDF
Paper will be illustrated with real life examples of the Figure 1. Double Bus Single Breaker
application challenges and how these challenges can be
addressed. With a low impedance bus differential protection in the
digital relays, able to adapt to a re-configurable buses and
Index Terms — Bus bar protection, CT Trouble, Bay able to provide additional means to achieve security and
identification, Intelligent electronic device (IED), Centralized dependability in bus differential protection applications it is
bus bar, CT secondary Open, blind spot, breaker failure, possible.
Bypass isolator, elimination of transfer bus, end fault, bus
unification, directional principle, zones of protection, breaker II. APPLICATION CHALLENGES
re-trip, under voltage security
A. INCREASE SECURITY WITH SUPERVISING ELEMENTS
I. INTRODUCTION
The low impedance bus protection IEDs on the market
Power systems used to have simple busbars with dedicated today have multiple additional security features to secure the
current transformers (CTs) and unidirectional current flow Bus Protection (87B) from unwanted operations during
during load and fault conditions. These buses traditionally external faults or switching conditions; such as CT saturation
were protected by the high-impedance principle – a fast and detection, directional (phase) comparison and bus zone
reliable scheme with decades of dependable and secure field breaker/isolator monitoring. However, these security means
experience. are still may not be enough for high-end transmission bus
protection applications.
No matter how reliable or how high the mean time between
failures (MTBF) of IEDs is, they are electronic devices which
can fail, and the MTBF can never be high enough on high-end
bus protection applications due to the severe impact of any
incorrect operations.
B. OPEN CT DETECTION
Bus bar protection purely depends on CTs and failure of its
circuit or IED itself would challenge the security of the
protection. Such challenges are addressed by modern
numerical IEDs, where several protection elements for
additional security are embedded.
BUS 1
Another advantage of using dual isolator auxiliary contacts
+
BUS PROTECTION RELAY
status is ability to monitor disagreement between 89a and 89b
ISO1
7B 7A 7A On
7B Off
ISO 1 CLOSED INCLUDE CURRENT C1
INTO ZONE1(BUS1)
contacts for alarm purposes and also to define an action in
ISO 2 OPEN
DO NOT INCLUDE C1
INTO ZONE 2 (BUS2)
case of such disagreement.
DO NOT EXECUTE THE
+ ISO 3 OPEN LOGIC FOR BREAKER
ISO2 BYPASSED IN THE
9B 9A 9A Off
9B On
RELAY
D. DETECTION OF EXTERNAL FAULTS
BUS 2 Some bus protection configurations are facing with the
+
challenge that some outgoing feeders would have lower CT
ISO3
5B 5A 5A Off ratios compared to power supply feeders, hence would be
5B On
CB 1
TRIP CB1, IF FAULT ON BUS 1
exposed to severe and fast CT saturation conditions [5] during
DO NOT TRIP CB1, IF FAULT ON BUS 2
external faults on these outgoing feeders, as highlighted
CT1
INCLUDE CURRENT C1 INTO ZONE1(BUS1)
DO NOT INCLUDE C1 INTO ZONE 2 (BUS2)
below:
C1 ~ ~
Figure 6. Isolator status and relay currents
Power supply
Switching of the isolators follows a certain procedure to feeders
3000/5
assure the power supply of the primary circuit is not disrupted. F1
To reflect the new position of the circuit, the relay monitors a
pair of auxiliary contacts associated with each isolator. One
normally open 89a and one normally closed 89b auxiliary
contact are connected to the relay, such that when 89a 600/5
I2 I1
contact is detected open and 89b contact is detected closed,
the isolator status is detected open. When the status of these F2
contacts is reverted, the isolator is detected closed.
Load or small generation feeders
Depending on the status of the main isolator, the relay
either includes (isolator closed) the circuit current from the bus Figure 8. Fast CT Saturation on outgoing feeder
zone, or excludes (isolator open) it from that zone. To avoid
differential protection tripping, the inclusion and exclusion of In this example, the problem is that the fault current I2 on
the circuit current in and out the zone must follow very the outgoing feeder, which occurs when a power supply
accurately the moment of closing and opening of the main feeders would feed fault F2, is much larger than fault current
isolator. I1 for a fault at F1 on the bus through the same outgoing
feeder.
Figure 7 shows how the time of open and close state for
each auxiliary contact from the pair of contacts need to be The outgoing feeders CTs are typically sized for line load
adjusted and assure the current of the circuit will be included and not for the system fault conditions, hence significant CT
in the differential protection zone exactly at the moment of saturation may occur on the outgoing feeder.
closing of the isolator, and will be excluded exactly at the
moment of isolator opening state. In simple terms, the relay The low impedance bus differential element would expect
must detect isolator closed from the pair of contacts before the the differential-vs-restraining currents trajectory to move from
moment of actual isolator closing, and must not show open t0 to t1 and then to t2 as below:
before the actual isolator knifes departed open.
ISOLATING MARGIN
Figure 7. Auxiliary contacts and Isolator status Figure 9. CT Saturation Detection on External Faults
In some cases the CT saturation might be in less than
2.5ms at 50Hz as shown below:
IV. REFERENCES
[1] K.N. Dinesh Babu, P.K.Gargava, M.V.Gopalan,
Veera Vijayan and M. Ada Jinu P Josephmiak, "A Novel Bus
Protection for Complicated Bus Arrangements without using
isolator status wiring", International Conference on Advances
in Power System Control, Operation and Management
Figure 12. Eliminating over-trip when CB opened (APSCOM), November 2015.
[2] K.N. Dinesh Babu, Veera Vijayan, M.V.Gopalan,
This spot is thus a blind spot not covered by the differential, Bala Vinayagam,Appanna, Raghu and Jorge Cardenas,
since tripping the differential zone with the bus feeder CB "Adaptation of Bus Bar Protection of GE for Complicated Bus
already open, will not clear the fault. Arrangements in Sharavathy Generation Station, Karnataka
Power Corporation Limited ", PAC World Glasgow Scotland
Conference, June/July 2015.
[3] K.N. Dinesh Babu, A.B. Sudarshan and Jorge
Cardenas, "CT Open Bay Detection logic in Centralised low
Impedance bus bar protection IED ", Conference/Jourbal
TNEB BB, November 2015.
[4] B90 Low Impedance Bus Differential System Manual,
GE Publication GEK-119611A.
[5] Bogdan Kasztenny , Jeff Mazereeuw, Kent Jones:
Figure 13. End Fault Protection “CT Saturation in Industrial Applications – Analysis and
Application Guidelines”. GE Multilin GET 8501
The protection function needed to clear this type of fault is
so-called End Fault Protection [4]. [6] Lubomir Sevov, Bogdan Kasztenny, Ed Taylor:
Commissioning and Testing Complex Busbar Protection
End fault protection consists of an instantaneous Schemes – Experience at Pacific Gas&Electric”, WPRC,
overcurrent, enabled only if the CB is open, has a pickup delay October 2006
of at least 1.3 cycles to allow for adequate current ramp down
after the CB opened, and must be blocked by the manual V. AUTHORS INFORMATION
close command.
JC (Jacobus) Theron is Snr Product Manager for Grid
Typically end fault protection would send a transfer trip to Automation division of GE Digital Energy. He received the
the remote end of the bus feeder or power system component degree of Electrical and Electronic Engineer from the
it is covering. University of Johannesburg, South Africa in 1991. Mr. Theron
has 24 years of engineering experience; 6 years with Eskom
Most modern low impedance bus protection IEDs do include (South Africa) as Protection / Control and Metering Engineer,
end fault protection and typically one per bus zone feeder. 11 years with GE Multilin (Canada) as Product / Technical
support / Protective Relaying Consultant/Protection and
Systems Engineer leading the Project and Consulting
III. CONCLUSIONS
Engineering team and as Product Manager, 2 years with
As power systems have evolved, their associated busbar Alstom T&D (USA) as Senior Systems Engineer and 5 years
schemes have become much larger and more complex. with Hydro One as Operations Assessment Engineer / P&C
Reconfigurable buses are essential, and low impedance bus Technical Services Manager. He specializes in transmission,
protection schemes have had to evolve to ensure all bus distribution, bus and rotating machines protection applications
support, system designs and transient system testing. He is a
member of IEEE.
Lubomir Sevov (M’90) received his M.Sc. degree from
Technical University of Sofia, Bulgaria in 1990. After
graduation, he worked as a protection and control engineer for
National Electric Company (NEC) Bulgaria. Mr. Sevov joined
GE Multilin in 1998, where he currently works as a senior
application engineer in the research and development team. In
the last eight years, Mr. Sevov has been mainly involved in the
design and application of industrial protective relays and
controls. He authored and presented more than 60 papers at
various protective relay conferences. His areas of interests
include feeder, bus and transformer protection, control,
monitoring, and diagnostic.
Lubomir is a registered professional engineer in the province
of Ontario, Canada. He is a senior member of IEEE, and chair
of the PSRC K1 working group developing a Guide for the
Application of Protective Relaying for Phase-Shifting
Transformers.