Digix-1 Programmable Logic Controller: Features

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

DIGIX-1 Programmable Logic Controller

Features :
! Compact PLC with built in HMI
! 2 line 8 character LCD
! Real Time Clock
! Windows based user friendly software for ladder programming &
HMI configuration
! RS485 based communication with MODBUS protocol

Size : 70 x 90 x 66.4mm

Technical Specifications
Display Environmental Specifications
Display 2 line X 8 characters LCD (Green backlight) Operating Temperature 0 to 55 ºC
No. of keys 5 keys (4 - User configurable) Storage Temperature -20 to 70 ºC
Humidity (Non Condensing) 10% to 95% RH
Input Specifications
Digital Input
Mechanical Specifications
Digital inputs 8
Mounting DIN Rail Mount
Input Type PNP Weight Approx 240 gms.
Input Voltage Range 5 - 30V DC
Response Time Typical 2 mSec (Based on ladder scan time)
& 100 µSec for Fast Input Functional Features
Isolation No Timer Operational Modes On Delay, Off Delay, Pulse,
Debounce Time 0 to 255 mSec (Default 10 mSec) Special [Up/Down] Timer
Timer Accuracy 0.1% or 2 mSec (Whichever is greater) Timer Resolution 1 mSec (Accurate only for 1 mSec Timer block)
Fast Input Counter Up Counter, Down Counter,
No. of Channels 1 Up/Down Counter, Special [Up/Down] Counter
Frequency 5 kHz. Other Blocks Analog input, FTC, PID, Ramp Soak
Memory Retention 10 years
Output Specifications RTC No
Clock Data Retention NA
Digital Output - Relay
Digital Outputs 5 (NO type with 2 COM points) Clock Drift NA

Contact rating 5A @ 240V AC (Resistive)


5A @ 28V DC (Resistive)
Supply Specification
Isolation NO
Supply Voltage 90 to 270V AC 50/60 Hz., 18 to 30V DC
Response Time 10 mSec Power Consumption 6W Max
Mechanical Life 2000000 cycles Sensor Supply (SS) 10V, 50mA in AC model only
Communication VAR IN_OUT & VAR OUTPUT types Variables Maximum Retention 25 variables only each of 32 bit @ 110V
Communication Port RS485 [Slave] Dimensions (All dimensions are in mm)
RS485 [Master]
Communication Protocol MODBUS RTU 44
70
Connector RJ25

Functional Specifications
90

Programming Method Windows based software for ladder


45

programming and HMI configuration.


Memory Data memory : 16 kB
Code memory : 112 kB
EEPROM Memory : 1 kB
Max. no. of Objects 2000 (As per memory) 62

Minimum Scan Time 200 µSec


Typical Scan Time 2 mSec (Based on ladder scan time)

www.selec.com 1
DIGIX-1 Programmable Logic Controller

Terminal Connections Ordering Information


Order Code Description
DIGIX-1-1-1-230V 8 Inputs, 8 Outputs, RS485 Master, RTC, 230V AC Supply

DIGIX-1-230V 8 Inputs, 8 Outputs, 230V AC Supply

DIGIX-1-0-0-24VDC 8 Inputs, 8 Outputs, 24V DC Supply

Accessories (to be ordered separately)

Downloading Cable AC-USB-RS485-03

ACH-004 (RJ25 Cable)


Networking AC-IOEXP-03 (Expansion Adaptor)

AC-USB-RS485-02 (USB to RS485 Cable)

Digix-1-230V

Digix-1-0-0-24VDC

+24VDC

www.selec.com 2