NXC AC contactor

Overview
Applicable scop

The new NXC AC contactors feature a novel appearance and a compact structure. They are
mainly used for frequent starts and control of AC motors as well as remote circuit making /breaking.
They can also be combined with appropriate thermal overload relays to form electromagnetic
starters.
Compliant standards: IEC/EN 60947-1, IEC/EN 60947-4-1, IEC/EN 60947-5-1.

Parameters

● Rated operation current Ie: 6A~630A


● Rated operation voltage Ue: 220V~690V
● Rated insulation voltage: 690V (NXC-06M~100), 1000V (NXC-120~630)
● Number of poles: 3P and 4P (only for NXC-06M~12M)
● Coil control method: AC (NXC-06(M)~225), DC (NXC-06M~12M),
AC/DC (NXC-265~630)
● Installation method: NXC-06M~100 rail and screw installation,
NXC-120~630 screw installation

Operation and installation conditions

Type Operation and installation conditions

Installation class Ⅲ

Pollution degree 3

Compliant standards IEC/EN 60947-1, IEC/EN 60947-4-1, IEC/EN 60947-5-1

Certification mark CE

Enclosure protection degree NXC-06M~38: IP20; NXC-40~100: IP10; NXC-120~630: IP00

Operation temperature limits: -35℃~+70℃.


Normal operation temperature range: -5℃~+40℃.
Ambient temperature The 24-hour average temperature should not exceed +35℃.
For use beyond the normal operation temperature range,
see "Instructions for use in abnormal conditions" in the annex.

Altitude Not exceeding 2000 m above sea level

The relative humidity should not exceed 50% at the upper temperature limit
of +70℃.
Atmospheric conditions A higher relative humidity is allowed at a lower temperature, e.g. 90% at +20℃.
Special precautions should be taken against occasional condensation due to
humidity variations.

The angle between the installation surface and the vertical surface should
Installation conditions
not exceed ±5°.

The product should be installed in places without significant shaking,


Shock and vibration
shock, and vibration.

01 >> Empower the World


NXC AC contactor

Description

NXC AC contactor

NXC 12 /N 230V 50Hz

Model Rated current Special function Coil voltage Frequency

06, 09, 12, 16, /N: Reversible contactor 24V, 36V, 48V, 110V, 127V, 50Hz,
18, 22, 25, 32, 220V, 230V,240V, 380V, 60Hz,
38, 40, 50, 65, 415V, 440V, 480V, 660V 50/60Hz
75, 85, 100, (AC: 06A~225A;
120, 160, 185, AC/DC: 265A~630A)
225, 265, 330,
400, 500, 630

Note: 06A-100A products contain one NO auxiliary contact and one NC auxiliary contact. 120A-630A products contain two NO auxiliary contacts
and two NC auxiliary contacts.

NXC miniature 3P AC contactor

NXC 06M 10 /Z /N 230V 50Hz

Auxiliary
Model Rated current Coil form Special function Coil voltage Frequency
contact

06M 10: NO /Z: DC /N: AC: 24V, 36V, 50Hz,


09M 01: NC control coil Reversible 48V, 110V, 127V, 60Hz,
12M contactor 220V, 230V, 240V 50/60Hz
380V, 415V, 440V,
480V, 660V

DC: 24V, 48V,


110V, 220V

NXC miniature 4P AC contactor

NXC 06M /22 /Z /N 230V 50Hz

4P main contact
Model Rated current Coil form Special function Coil voltage Frequency
combination

06M /22: /Z: DC /N: AC: 24V, 36V, 50Hz,


09M 2 NO and 2 NC control coil Reversible 48V, 110V, 127V, 60Hz,
12M main contacts contactor 220V, 230V,240V, 50/60Hz
/04: 380V, 415V, 440V,
4 NC 480V, 660V
main contacts
/40: DC: 24V, 48V,
4 NO 110V, 220V
main contacts

Model example: NXC-12 240V 50Hz represents an AC contactor under AC-3 utilization category that provides a rated current of 12A at a main circuit
voltage of 380V/400V/415V. Each contactor body contains one NO auxiliary contact and one NC auxiliary contact. The coil control voltage and
frequency are 240V AC and 50Hz respectively.

Empower the World >> 02


NXC AC contactor

NXC AC contactor selection table

Motor power kW Maximum operation current A Number of contacts contained in the contactor body
Contactor model
220V/230V/240V 380V/400V 660V/690V (AC-3 380V/400V) NO NC

1.5 2.2 3 6 1 0 NXC-06M10

1.5 2.2 3 6 0 1 NXC-06M01

1.5 2.2 3 6 1 1 NXC-06

2.2 4 4 9 1 0 NXC-09M10

2.2 4 4 9 0 1 NXC-09M01

2.2 4 5.5 9 1 1 NXC-09

3 5.5 4 12 1 0 NXC-12M10

3 5.5 4 12 0 1 NXC-12M01

3 5.5 7.5 12 1 1 NXC-12

3 7.5 7.5 16 1 1 NXC-16

4 7.5 10 18 1 1 NXC-18

5.5 11 11 22 1 1 NXC-22

5.5 11 15 25 1 1 NXC-25

7.5 15 18.5 32 1 1 NXC-32

9 18.5 18.5 38 1 1 NXC-38

11 18.5 30 40 1 1 NXC-40

15 22 37 50 1 1 NXC-50

18.5 30 37 65 1 1 NXC-65

22 37 37 75 1 1 NXC-75

22 37 45 85 1 1 NXC-85

25 45 45 100 1 1 NXC-100

37 55 80 120 2 2 NXC-120

45 75 100 160 2 2 NXC-160

55 90 100 185 2 2 NXC-185

63 110 110 225 2 2 NXC-225

75 132 160 265 2 2 NXC-265

90 160 200 330 2 2 NXC-330

132 200 300 400 2 2 NXC-400

160 250 335 500 2 2 NXC-500

200 335 350 630 2 2 NXC-630

Coil voltage specification table

NXC-06M~12M

AC (V) 50Hz 24 36 48 110 127 220 230 240 380 415

AC (V) 60Hz 24 36 48 110 127 220 380 415

DC (V) 24 - 48 110 - 220 - -

NXC-06~100

AC (V) 50Hz 24 36 48 110 127 220 230 240 380 415

AC (V) 60Hz 24 36 48 110 127 220 380 415

NXC-120~225

AC (V) 50Hz - - - - 110 127 220 230 240 380

AC (V) 60Hz - - - - 110 127 220 380

NXC-265~630

AC/DC (V) - - - - 110~127 220~240 380~415 -

03 >> Empower the World


NXC AC contactor

Accessories

Accessory diagrams

SR2 surge suppression module

Mechanical interlock module

NXC AC contactor

AX-3C NXC
side-attached AC contactor
auxiliary contactor F5 delay head

AX-3X top-mounted auxiliary contact

AX-3X top-mounted auxiliary contact

Current-limiting contact module

AXC dust cover

SR8 surge suppression module

AX-3M top-mounted auxiliary contact

07 >> Empower the World


NXC AC contactor

Accessory description

Top-mounted auxiliary contact group Side-attached auxiliary contact group

AX - 3X 11 AX - 3M 11 AX - 3C / 11 B

Auxiliary NO and NC Auxiliary NO and NC Side-attached NO and NC A: Standard model,


contact auxiliary contact contact group auxiliary contact auxiliary contact contact pair left omitted, applicable to
group model pair combination model pair combination group model combination 6A~225A AC contactor

B: Expanded model,
Applicable to 11, 20, 02 Applicable to 11, 20, 02 used for 265A~630A
6A-630A 22, 13, 31 NXC-06M ~12M 22, 13, 31 AC contactor
AC contactor 04, 40 AC contactor 04, 40 11
product product

Dust cover Air delay head

AXC 1 F5 T 4

Dust cover 1: Used for NXC-06~22, NXC-120~630 Air delay Delay type Delay range
2: Used for NXC-25~38 head model
3: Used for NXC-40~65
4: Used for NXC-75~100
T: Power-on 0: 0.1~3s
delay 2: 0.1~30s
D: Power-off 4: 10~180s
delay

Empower the World >> 08

You might also like