Construction Notes: CASE-1
Construction Notes: CASE-1
COMPACTED
A. GENERAL WIDTH (W) BACKFILL
1. CONSTRUCTION NOTES AND TYPICAL DETAILS APPLY TO ALL DRAWINGS UNLESS OTHERWISE SHOWN OR NOTED.MODIFY TYPICAL
DETAILS AS DIRECTED TO MEET SPECIAL CONDITIONS. NAT'L GRADE LINE
2. SHOP DRAWINGS WITH ERECTION AND PLACING DIAGRAMS OF ALL STRUCTURAL STEEL, MISCELLANEOUS IRON, PRE-CAST CONCRETE ETC. CL SEE
SHALL BE SUBMITTED FOR ENGINEER'S APPROVAL BEFORE FABRICATION. COLUMN
REBAR
VARIES
4. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE ADEQUATE SHORING AND BRACING OF THE STRUCTURE FOR ALL LOADS THAT 75 mm 75 mm
MAYBE IMPOSED DURING CONSTRUCTION.
ASW
LENGTH (L)
B. CONCRETE & REINFORCEMENT
THICKNESS
CL
t
1. ALL MATERIALS AND WORKMANSHIP SHALL CONFORM WITH THE LATEST BUILDING CODE OF AMERICAN CONCRETE INSTITUTE (ACI-318). ASW 75 mm
2. ALL CONCRETE SHALL DEVELOP A MINIMUM COMPRESSIVE STRENGTH AT THE END OF TWENTY EIGHT (28) DAYS WITH CORRESPONDING
MINIMUM SIZE AGGREGATE AND SLUMPS AS FOLLOWS :
VARIES
SLAB ON GRADE. . . . . . . . . . . . . . . . . . . . . 1 1/2 IN. (40 MM.)
BEAM STIRRUPS AND COLUMN TIES. . . . . . . . . . . . . 1 1/2 IN. (40 MM.) 75 mm
WHERE CONCRETE IS EXPOSED TO EARTH ASW
LENGTH (L)
BUT POURED AGAINST FORMS. . . . . . . . . . . . . . . .2 IN. (50 MM.)
THICKNESS
CL
WHERE CONCRETE IS DEPOSITED
t
DIRECTLY AGAINST EARTH. . . . . . . . . . . . . . . . . 3 IN. (75 MM.) ASW 75 mm
6. SPLICES SHALL BE SECURELY WIRED TOGETHER AND SHALL LAP OR EXTEND IN ACCORDANCE WITH (TABLE OF LAP SPLICE AND ANCHORAGE HOOK AT END
LENGTH) UNLESS OTHERWISE SHOWN ON DRAWINGS, SPLICES SHALL BE STAGGERED WHENEVER POSSIBLE.
7. ALL ANCHOR BOLTS, DOWELS, AND OTHER INSERTS, SHALL BE PROPERLY POSITIONED AND SECURED IN PLACE PRIOR TO PLACING OF
CONCRETE. ASL L X W PROVIDE 150 mm THK
COMP. GRAVEL BEDDING
8. ALL CONCRETE SHALL BE KEPT MOIST FOR A MINIMUM OF SEVEN (7) CONSECUTIVE DAYS IMMEDIATELY AFTER POURING BY THE USE OF WET ASL
BURLAP, FOG SPRAYING, CURING COMPOUNDS OR OTHER APPROVED METHOD.
C. MASONRY
1. ALL CONCRETE HOLLOW BLOCK (CHB) SHALL USE NON-LOAD BEARING CHB UNLESS OTHERWISE SPECIFIED.
D. STRUCTURAL STEEL
1. ALL STRUCTURAL STEEL SHALL CONFORM TO ASTM A-36 fy=36,000 PSI (248 MPa).
E. FOUNDATION
1. THE ALLOWABLE FOUNDATION PRESSURE USED WAS BASED ON ASSUMED VALUE OF 300 KN/SQM. BASED ON CHAPTER 7
TABLE 7-B OF THE NSCP.
2. PROVIDE ADEQUATE SHORING & PROTECTION FOR EXCAVATION OF EARTH.
3. NO FOOTING MUST REST ON FILL.
PROJECT PROPOSED THREE STOREY HOSPITAL SHEET CONTENT/S: STRUCTURAL DESIGNED BY: REVISION DATE ISSUED : 06/23/18 SHEET NO.:
CYRIL A. ALEA
DESCRIPTION DATE
OWNER MR. & MRS. CLEMENTE & DIVINA ALEA - CONSTRUCTION NOTES CAD BY : C. A. A. STRUCTURAL / CIVIL ENGINEER :
CYRIL A. ALEA
- FOOTING DETAILS
S-1
PRC Reg. No. : 2013-00298-LQ-0 Date :
BLDG. PERMIT No.__________ DATE : ________ISSUED AT : ________
- SCHEDULE OF FOOTINGS CHECKED BY : PTR : Date :
TIN : Date :
LOCATION BRGY. SAN LORENZO, LOPEZ QUEZON OWNER'S APPROVAL ENGR. RODEL O. FLORIDO PLACE : PROV. OF QUEZON