Kinetrol Actuators and Add-On Control Units: Abbreviations

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

Kinetrol Actuators and Add-On Control Units

Ordering Codes
ACTUATOR ACTUATOR or SWITCH OPTIONS
MODEL ACTUATOR/SOLENOID SPRING RETURNS (see pages 31 to 34)
SIZE/THREAD VALVE ASSEMBLY

Actuator
0

023 - Male Drive 0 No Spring Return Optional Suffixes Optional Supplementary


ISO/DIN Flange 0 No Actuator
to In Place Of “-”: Codes Including
203 Actuator
F ISO Female 1 With Actuator 2 Spring Return cw
AP AP Positioner
Drive Spring High Temperature Seals
see page 42 for full
2 Actuator & 3 Port 3 Spring Return ccw Restricted Travel
Actuator codes
014 S Serrated Female Single Solenoid Silicone Free
to Metric Drive Spring 4 Positioner 4-20 mA Keyway Shafts
EL EL Positioner
604 Thread 3 Actuator & 5 Port ccw - No Actuator
1 see page 40 for full
Single Solenoid contact Kinetrol for details
5 Positioner 3-15 psi codes
Actuator ccw - No Actuator
017 NB Other Solenoids M Clear Cone
to ANSI by description 6 Positioner 3-15 psi Position Monitor
607 Thread cw - No Actuator
4 Actuator & Positioner R Clear Cone Position
4-20 mA ccw 7 Positioner 4-20 mA Monitor -
03A ISO/DIN Flange cw - No Actuator Chemical Resistant
to with NAMUR 5 Actuator & Positioner
15A 3-15 psi ccw 8 Alternative Spring S Solenoid Valve
Adaptor
Return Flange Silencers/Flow
6 Actuator & Positioner Drillings cw Regulators
03B Actuator with 3-15 psi cw
to 9 Alternative Spring U VLS/ULS Limit
NAMUR Adaptor
15B 7 Actuator & Positioner Return Flange Switch Box
Metric Thread
4-20 mA cw Drillings ccw see page 32 for full
codes
03C Actuator with 9 Special Product
to NAMUR Adaptor Specifications W Low Temperature
15C P - contact Kinetrol Seals
ANSI Thread
X Explosion Proof
1 Limit Switch Box
Abbreviations: see page 34 for full
Give electrical details codes
cw: clockwise (voltage & hertz)
ccw: counter Z Less coupling
(or anti)
clockwise

EXAMPLES

A: 054-100 Double acting actuator (Metric threads) no optional supplementary items

B. 054-120M A + spring return (fail-safe cw) + Clear Cone monitor

C. 057-100 Double acting actuator (ANSI threads)

D. 144-130-4900 144 actuator (Metric threads) + spring return fail-safe ccw (2 x 124 springs)

E. 053F100 Double acting actuator with ISO adaptor

180° Actuator ordering codes - see page 51


Damper Drive ordering codes - see page 54
Female Drive Spring Unit ordering codes - see page 29
Geared Manual Override ordering codes - see page 55
ISO Adaptor ordering codes - see page 26
Low Pressure Air Application ordering codes - see page 28
Manual Fail-Safe Unit ordering codes - see page 47
Fire Fail-Safe Unit ordering codes - see page 49
P3 On/Off Positioner ordering codes - see page 44
Explosion Proof P3 On/Off Positioner ordering codes - see page 45
Spring to Centre ordering codes - see page 50
DeviceNet ordering codes - see page 37

30
Offers a wide range of signalling options in a fully enclosed,
corrosion resistant metal case. Available for direct mounting
onto Kinetrol rotary actuators or discrete mounting via
an industry standard VDI/VDE interface onto any make of
VLS/ULS Limit

rotary actuator. Easy to wire and set up with industrial


Switch Box

standard robustness. Internally fitted options include AS


Interface digital communication and a 4-20mA, 2-wire
modulating angle retransmit circuit.

The range of switch and terminal arrangements includes 2 or


4 switches, extra connections allowing single point
termination of wiring for limit switches and solenoid valves.
ATEX approved Ex d (Category 2) explosion proof and
Ex ia intrinsically safe packages (Category 1). Integral
sealed Clear Cone Monitor and red/green Led indicator
options also give high visibility external visual indication of
position.

Specification Units sealed to IP67/NEMA 6 (ATEX units IP66/NEMA 4X, IP67 option available)

Casing Robust corrosion resistant epoxy painted diecast box


Precision diecast aluminium
alloy, switch option 003 Easy and accurate setting of switch position
Ex d diecast zinc alloy
Available for direct mounting to Kinetrol models 03 to 15 (for minimum height)
Finish Discrete Kinetrol 05 square drive insert for use with Kinetrol actuator models 16 to 60
Epoxy stove enamel
Quick access - No special tools required
Seals
Nitrile rubber ‘O’ ring seals Discrete VDI/VDE (NAMUR) interface option for use with industry standard actuators

Two or four cable entries as standard to allow back wiring of solenoid valves
Cable entry options
2 or 4 entries
Multiple switch options available for general and hazardous areas
M20 x 1.5 Conduit thread
or AS Interface bus circuit option inside box reads up to 4 switch inputs, drives up to
1/ NPS Conduit thread
2 2 solenoids powered by bus only (see pages 35 & 36)
4 Way plug DIN 43650A
DeviceNet option inside box with various network speeds allows 2 on / off inputs and
(fits either conduit thread)
drives up to 2 solenoids (see page 37)
4 Way M12 Connector
(M20 Conduit thread only) Optional Clear Cone monitor available

Dimensions Integral LED indicator lamps and angle retransmit circuit options are available
See page 61
Compact SPST version of type 004 available for model 02 actuator

LOAD RATINGS FOR


STANDARD MICROSWITCHES (type 004)
Voltage Resistive Load Weight
125 V AC 15A VLS – 0.68kg
250 V AC 15A ULS Switch Options
up to 12 V DC 15A 001 and 009 – 1.05kg
up to 24 V DC 10A
003 – 1.4kg
up to 48 V DC 3A
up to 250 V DC 0.25A

MULTIPLICATION FACTORS Temperature Range


FOR NON-RESISTIVE LOADS Standard -20°C to +80°C
Steady state tungsten lamp load - x 0.1 High Temp Seals up to 100°C
Steady state inductive load - x 0.2
Also see switch temperatures on page 32
31 Peak inductive load - x 1.0
Ordering Codes
Switch Type 001 Switch Type 009
2 intrinsically safe 2 wire inductive proximity sensors 2 x 3 wire gold plated contacts intrinsically safe

VLS/ULS Limit
for hazardous areas (ATEX CAT 1), microswitches for SPDT (ATEX CAT 1).

Switch Box
normally closed. Ambient temperature range -20°C to +80°C
Ambient temperature range -20°C to +80°C
Switch Type 00E
Switch Type 002 2 x 2 wire proximity sensors 20-140 volts AC /
2 pneumatic switches with 4mm (5.32”) push in 10-140 volts DC.
fittings (ATEX CAT 2), normally closed. Ambient temperature range -25°C to +80°C
Ambient temperature range -15°C to +60°C
Switch Type 00M
Switch Type 003 4 x 3 wire inductive proximity sensors
Certificated unit to EEx ed II T6 for hazardous areas 10-30 volts DC, normally open.
to Zone 1 (ATEX CAT 2) 2 x 3 wire switches for Ambient temperature range -25°C to +70°C
SPDT.
Ambient temperature range -20°C to +70°C Switch Type 00N
2 x 3 wire inductive proximity sensors
Switch Type 004 10-30 volts DC, normally open.
2 x 3 wire microswitches for SPDT. Ambient temperature range -25°C to +80°C
Ambient temperature range -40°C to +80°C
Electronics Option B - E
Switch Type 005 AS interface options are available with both
2 x 2 wire proximity sensors 20-250 volts AC, the two and four entry Kinetrol Universal Limit
normally open. Switch Box. Options B to E allow for
Ambient temperature range -25°C to +70°C different extended addressing options. For
more information on the Kinetrol AS
Switch Type 006 interface card see page 35 & 36.
2 x 2 wire proximity sensors 5-60 volts DC, normally
open, with Led switch status indicators. Electronics Option P
Ambient temperature range -20°C to +80°C Two or four way Universal Limit Switch Box
fitted with potentiometer (20K ohms
Switch Type 007 conductive plastic type).
4 x 3 wire microswitches for DPDT.
Ambient temperature range -40°C to +80°C Electronics Option R
Two or four entry Universal Limit Switch Box
Switch Type 008 fitted with angle retransmit, loop powered two
2 x 2 wire inductive slotted proximity sensors, wire circuit passes 4-20mA current,
normally closed. proportional to 0-90° position of actuator.
Ambient temperature range -20°C to +80°C
Electronics Option U (standard)
For ATEX ratings please refer to TD139 Two or four entry Universal Limit Switch Box
without AS interface card, angle retransmit
SWITCH TYPE or potentiometer.
1=2x V3 i-SAFE PROXIMITY SENSORS ATEX
2=2x PNEUMATIC SWITCHES ATEX ELECTRONICS OPTION 0=DIRECT MOUNT UNIT
3=2x SWITCHES EExe II T6 CERTIFIED ATEX B=WITH ASi BUS † (See KF-496) 1=DISCRETE UNIT WITH KINETROL SQUARE
4=2x V3 SPDT SWITCHES † C=ASi EXTENDED ADDRESSING, 2=DISCRETE UNIT WITH NAMUR INTERFACE
5=2x 20-250Vac PROX. SENSORS † OUTPUTS DISABLED † 3=DISCRETE UNIT WITH KINETROL SQ.+HI TEMP SEALS †
6=2x 5-60Vdc PROX.SENSORS † D=ASi EXTENDED ADDRESSING, 4=DISCRETE UNIT WITH NAMUR INTERFACE+HI TEMP SEALS †
7=4x V3 DPDT SWITCHES † OUTPUTS ENABLED † 5=DIRECT MOUNT BOX+HI TEMP SEALS †
8=2x SLOTTED PROX SENSORS † E=ASi EXTENDED ADDRESSING,
9=2x V3 SPDT i-SAFE (GOLD PLATED) ATEX OUTPUTS ENABLED, SEPARATE
A=4x CODE 1 SENSORS 7.530Vdc † POWER SUPPLY † 0= 2X3 CONNECTION TERMINAL BLOCKS
B=4x CODE 5 SENSORS † U=WITHOUT ELECTRONICS 4= 3X3 CONNECTION TERMINAL BLOCKS
C=4x CODE 6 SENSORS † R=WITH ANGLE RETRANSMIT † 5= 4X3 CONNECTION TERMINAL BLOCKS †
D=4x CODE 9 SWITCHES † P=WITH POTENTIOMETER † 6= MULTI-TERMINAL PCB (5x3 + 1x2) †
E=2x V3 20-140Vac / 10-140Vdc INDUCTIVE SENSORS †
F=4x CODE E SENSORS †
M=4x 10-30Vdc PNP 3 WIRE PROX. SENSORS † M=CLEAR CONE MONITOR - STANDARD †
N=2x 10-30Vdc PNP 3 WIRE PROX. SENSORS † B R=CLEAR CONE MONITOR - EXTRA CHEMICAL RESISTANCE †
C A=CLEAR CONE MONITOR - ATEX (SWITCH OPTION 1 & 9 ONLY)

0=NO ACTUATOR D
0=NO LED FITTED
1=ACTUATOR E 1=2 LED'S RED + GREEN 240 / 110 V ac †
ACTUATOR U 2=2 LED'S RED + GREEN 12 / 24 V dc †
MODEL 3=2 LED'S RED + GREEN WITH ASi BUS †
R
03 - 60
RH P 0=PNEUMATIC SWITCH CONNECTION
For more information
1=2 ENTRIES - 2 TRANSIT PLUGS
4=M20 (ISO)
7=1/2" NPS
2=2 ENTRIES - 1 TRANSIT, 1 BLANKED (R.H.) see KF-487
3=2 ENTRIES - DIN PLUGS †
APPROVAL TYPE 4=2 ENTRIES - DIN PLUG, 1 BLANKED (R.H.) †
SPRING 5=4 ENTRIES - 4 TRANSIT PLUGS †
V= STANDARD
LH OPTIONS 6=4 ENTRIES - 3 TRANSIT, 1 BLANKED (R.H.)
0=ATEX
0=NO SPRING 7=4 ENTRIES - 4 DIN PLUGS †
(001, 003 & 009)
2=CW SPRING 8=4 ENTRIES - 3 DIN PLUGS, 1 BLANKED (L.H.) †
3=CCW SPRING 9=4 ENTRIES - 2 DIN PLUGS, 1 BLANKED (L.H.), 1 TRANSIT †
0= NO ANGLE RETRANSMIT
† NOT AVAILABLE ON ATEX VERSIONS 1= ANGLE RETRANSMIT CW † PLUG OPTIONS FOR AS INTERFACE †
2= ANGLE RETRANSMIT CCW † A=M12 PLUG FOR AS INTERFACE & TRANSIT (RH)
B=M12 PLUG, M12 SOCKET WITH ASI CABLE CLAMP & TRANSIT (RH)
C=M12 PLUG FOR AS INTERFACE & BLANK (RH)
EXAMPLES: D=M12 PLUG, M12 SOCKET WITH ASI CABLE CLAMP & BLANK (RH)
054-001U001000 = 05 ULS BOX WITH 2 X V3 ISAFE PROXIMITY SENSORS, 2 TRANSIT PLUGS, 2 X 3 WAY TERMINALS, ATEX APPROVED Unless otherwise specified M12 plug will always be connected on the left side port
074-004UV01000 = 07 VLS BOX WITH 2 X V3 SPDT SWITCHES, 2 TRANSIT PLUGS, 2 X 3 WAY TERMINALS
074-004RV12000 = 07 VLS BOX WITH 2 X V3 SPDT SWITCHES, ANGLE RETRANSMIT CLOCKWISE,1 X TRANSIT & 1 BLANKING PLUG, 2 X 3 WAY TERMINALS
094-124BV02000 = 09 SPRING RETURN CLOCKWISE ACTUATOR & VLS BOX WITH 2 X V3 SPDT SWITCHES,STANDARD ASi, 2 TRANSIT PLUGS, 2 X 3 WAY TERMINALS
094-109U001000 = 09 DOUBLE ACTING ACTUATOR, ULS BOX WITH 2 X V3 ISAFE MECH. SWITCHES GOLD PLATED, 2 TRANSIT PLUGS, 2 X 3 WAY TERMINALS, ATEX APPROVED

Further switch options are available upon request -contact Kinetrol for details
32
Explosion Proof Limit

The Explosion Proof Limit Switch Box offers a


Switch Box

wide range of signalling options in a compact


corrosion resistant aluminium alloy housing.
Available for close - mounting onto Kinetrol
actuators or discrete mounting via a Kinetrol 05
square or industry standard VDI/VDE
interface onto any make of rotary actuator. Easy
to wire and set up with true industrial robustness.

Internally fitted options include AS interface


digital communication and a 4-20mA, 2-wire,
modulating angle retransmit circuit. The range of
switches and terminal arrangements includes 2 or
4 switches and extra connections - allowing single
point termination of wiring for limit switches and
solenoid valves. This product is available to mount
on Kinetrol models 03 - 60.

Wide range of worldwide explosion proof approvals including IECEX, ATEX & FM
(for USA & Canada) - all in one device

All units protected to IP66 / NEMA 4X / TYPE 4X

Attractive, functional and part-spherical profile. Robust corrosion resistant,


anodised & epoxy painted diecast aluminium alloy housing

Close - mount to Kinetrol actuator models 03 - 15 for low profile

Discrete Kinetrol 05 square drive insert for use with Kinetrol actuator models 16 - 60

Discrete NAMUR drive for use with VDI/VDE 3845 drive actuators

2 or 4 cable entries available to allow back wiring of solenoid valves

Up to 4 switches available for SPDT, DPDT or multiple circuit operation

Easy and accurate setting of switching position

Optional antistatic Clear Cone Monitor available

Integral angle retransmit circuit options are available

Integral AS interface bus circuit option reads up to 4 switch inputs and drives up to
2 bus powered solenoids

-40° C to +80° C ambient operating temperatures (dependent on switch options)

Positioner options available

33
Explosion Proof Limit
Switching Operation Conditions Specification
Switch Voltage Temperature

Switch Box
Current NORTH AMERICAN APPROVAL
Code AC DC Range
Type of US: Class I, Division 1, Gas groups
1/A — 8 6mA -20°C to +80°C protection, B,C,D. Class II, Division 1, Dust groups
Explosion E,F,G. T5 NEMA 4X.
4/7 250 48 2.4A AC/1.8A DC -40°C to +80°C
Proof For Gas group A use order code “P”.
5/B 250 300 100mA -25°C to +70°C CANADA: Class I, Division 1, Gas
groups B,C,D. Class II, Division 1,
6/C — 60 100mA -20°C to +80°C Dust groups E,F,G. T5 TYPE 4X.
9/D — 30 100mA -40°C to +80°C
EUROPE/GLOBAL - ATEX / IECEx APPROVAL
E/F 140 140 200mA -25°C to +80°C Protection Group II C/A21, Category 2, Gas &
M/N — 30 100mA -25°C to +70°C concept, Dust, T5, IP66
Flame Proof ‘d’
Labels
Casing precision diecast LM24 alloy, anodised
IECEx & ATEX - Approval type E & epoxy stove enamel.

Coupling zinc plated steel.

Seals fluoropolymer dynamic seals and


NBR static seals.

Weight 1.5 kg

Cable Entry M20 x 1.5 or 1/2” 14 NPT conduit


FMC/U, IECEx & ATEX - Approval type F & P Options entry threads.

Dimensions see page 61

Ordering Codes
B = 2 ENTRY 0 = CLOSE-MOUNT (03-14 MODEL-SPECIFIC)
D = 4 ENTRY 1 = DISCRETE KINETROL 05 SQUARE DRIVE (16-30 MODEL-SPECIFIC)
APPROVAL TYPE 2 = DISCRETE NAMUR
E = IEC / ATEX IIC, IIB, IIA 3 = NO MOUNTING PARTS (NON MODEL-SPECIFIC)
F = FM / FMC GRPS B,C,D
P = FM GRP A NOTE: ACTUATORS 16 - 60 REQUIRE DISCRETE MOUNTING
MOUNTING PARTS AVAILABLE:
SP1601 - 05 SQUARE DRIVE
SWITCH OPTIONS SP1602 - 07/05 SQUARE REDUCER
(SUPPLIED WITH 2 STRIKERS AS STANDARD) SP1603 - NAMUR DRIVE
1 = 2 x V3 7.5-30Vdc, NC, 2 WIRE INDUCTIVE SENSORS SP1604 - 07/03 SQUARE REDUCER
4 = 2 x V3 SPDT, 0-250Vac, MECHANICAL MICROSWITCHES SP/ASP1607 - CLOSE MOUNTING KIT
5 = 2 x V3 20-250Vac / 10-300Vdc NO, 2 WIRE, INDUCTIVE SENSORS SP/ASP1608 - 12/14/15 ACCESSORY MOUNTING ADAPTOR (UNDRILLED)
6 = 2 x V3 5-60Vdc, NO, 2 WIRE, INDUCTIVE SENSORS SP/ASP389 - MODEL 16 MOUNT KIT
7 = 4 x CODE 4 MICROSWITCHES SP/ASP329 - MODEL 18 MOUNT KIT
9 = 2 x V3 SPDT, GOLD PLATED CONTACTS SP/ASP400 - MODEL 20 - 60 MOUNT KIT
MECHANICAL MICROSWITCHES
A = 4 x CODE 1 SENSORS
B = 4 x CODE 5 SENSORS TERMINALS NEEDED FOR OPTIONS
C = 4 x CODE 6 SENSORS NO BACKWIRING
D = 4 x CODE 9 MICROSWITCHES ASI + 2 OR 4 SWITCHES = 2x3 (0)
E = 2 x V3 20-140Vac / 10-140Vdc, NO, 2 WIRE, INDUCTIVE SENSORS A/R + 2 SWITCHES = 2x3 (0)
F = 4 x CODE E SENSORS A/R + 4 SWITCHES = PCB (6)
M = 4 x 10-30Vdc, PNP, 3 WIRE, PROXIMITY SENSORS 0 = 2 x 3 TERMINALS
POT + 2 OR 4 SWITCHES = PCB (6)
N = 2 x 10-30Vdc, PNP, 3 WIRE, PROXIMITY SENSORS 4 = 3 x 3 TERMINALS
5 = 4 x 3 TERMINALS 2 SWITCHES = 2x3 (0)
0 = NO SR 6 = MULTI-TERMINAL PCB (2x6 + 1x3 + 1x2) 4 SWITCHES = 4x3 (5)
2 = SR CW WITH BACKWIRING
3 = SR CCW
0 = WITHOUT ACT A/R + 2 SWITCHES = PCB (6) For more information
1 = WITH ACT A/R + 4 SWITCHES = PCB (6)
0 = STANDARD INDICATOR POT + 2 SWITCHES = PCB (6)
see KF-619
— = MALE
F = FEMALE A = ANTI-STATIC MONITOR POT + 4 SWITCHES = PCB (6) SEE NOTE
S = SERRATED 2 SWITCHES = 3x3 (4)
– X 0 4 SWITCHES = PCB (6)

NOTE - POT + 4 SWITCHES WITH BACKWIRING


WILL NOT HAVE ENOUGH TERMINAL
CONNECTORS TO WIRE ALL NORMALLY
OPEN / NORMALLY CLOSED SWITCH
CONNECTIONS WITH 3 POT CONNECTIONS.
ACTUATOR
MODEL
03 - 60
0 = NO OPTIONS
B = ASi BUS
3 = DIN FLANGE STANDARD (FEMALE DRIVE)
NOT AVAILABLE WITH C = ASi EXTENDED ADDESSING OUTPUTS DISABLED
4 = ISO (M20) THREAD
APPROVAL TYPES D = ASi EXTENDED ADDRESSING OUTPUTS ENABLED
A = DIN FLANGE STANDARD WITH NAMUR ADAPTOR
F&P E = ASi EXTENDED ADDRESSING OUTPUTS ENABLED, SEPARATE POWER SUPPLY
B = ISO (M20) THREAD STANDARD WITH NAMUR ADAPTOR
F = ANGLE RETRANSMIT CLOCKWISE
C = ANSI (1/2" NPT) THREAD STANDARD WITH NAMUR ADAPTOR
G = ANGLE RETRANSMIT ANTI-CLOCKWISE
7 = ANSI THREAD (1/2" NPT) P = POTENTIOMETER
34
Bus Communications
The Kinetrol AS Interface Card
AS Interface

The Kinetrol AS Interface card is fitted inside the


Kinetrol VLS Limit Switch box, thus combining
the industrial quality robustness of the box with
the advantages of digital serial communication.

The AS interface bus cable can be routed in


through the conduit entries and connected to the
internal terminal blocks. Alternatively, an M12
connector plug facing outwards from the conduit
entry can be supplied to allow quick connection
from M12 sockets or with clip on adaptations for
ribbon type yellow AS interface cables.

AS Interface Card Features

AS interface 2.1 compatibility


AS Interface Bus
Up to 31 units with solenoid valve on-off
The Actuator Sensor Interface card allows easy control, powered and controlled via a single,
digital serial communication for your sensors two core cable
and actuators, allowing your actuators to be
controlled and monitored when they are in the Up to 62 units (using extended addressing)
field, via a single 2 wire cable.
All metal robust industrial-quality limit switch
AS interface devices are used to make up control box, direct mounted on a Kinetrol actuator
systems based on a two-wire communication
cable known as a bus. These can be controlled 2 on/off outputs per unit
or monitored by means of a digital signal sent via
the bus to and from a "master" device (which 4 on/off inputs per unit
can be a computer or a PLC).
Reads mechanical switches or inductive
The slave devices will always function in sensors
response to commands sent by the master
device, either to actuate or to return a message Retrofittable to standard Kinetrol VLS
reporting the value of a sensed variable, or both. Limit Switch Box
The AS Interface specification allows 31 or fewer
slave devices to be powered by a DC voltage Can also be supplied in an explosion proof
fed into the same two wire cable used as the housing and with European, North American
communication bus, with allowed power and Worldwide approvals
consumption adequate to drive the slave plus a
standard pneumatic solenoid valve. LED external indicator option

An AS Interface bus can be used as the final Up to 31 24V 2.5W solenoid valves can be
field link in a more complex hierarchy of devices connected to bus with no separate power
making up a large plant-wide control system. supply
Actuators and sensors must often be installed in
unprotected environments where conditions can M12 connector plug option available for
be demanding; the AS Interface bus can be instant bus connection
used as the link between these field devices and
the "indoor" equipment making up the upper part Cable clamping connector block for yellow
of the control system. ribbon-type AS interface cable available with
M12 socket to fit onto plug option
The AS Interface bus is designed for on/off
control and monitoring. It is a good choice when Output short circuit protection built in
a simple, economical, reliable and robust
solution is required for controlling and monitoring Operating temperature range
a series of actuators and sensors in a process -20°C to +80°C
control or machine application. (-40°C option available - contact Kinetrol)
35