MCAG

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

Type MCAG 14, 34: High Stability Circulating Current Relay

Features The MCAG 14 relay, used with a Description


stabilising resistor, is designed for
• High stability with through faults The relay is basically a standard
applications where sensitive settings with
• Tuned to rated frequency attracted armature unit of simple and
stability on heavy through faults are
• Operates in 25ms at 5 times setting robust construction. The operating coil of
required, and is recommended for
this unit is connected in series with a
balanced and restricted earth fault, bus-
Application small choke and capacitor, forming a
zone and certain forms of differential
series resonant circuit. These components
protection for generators, auto-
When circulating current protection are energised from an auto-transformer
transformers, reactors and motors. A
schemes are subjected to heavy through which is tapped to provide seven current
typical circuit diagram is shown in
faults, the sudden, and often settings.
Figure 2.
asymmetrical growth in the system
current can cause the protective current The relay circuit, tuned to the supply
The total impedance of the relay and
transformers to approach or even reach frequency, rejects the harmonics
series stabilising resistor is usually low
saturation level. Because of the produced by current transformer
enough to prevent the current
variations in the magnetising saturation. A slight time delay on
transformers developing voltages over
characteristics of the transformers a high operation helps to provide stability on
2kV during maximum internal faults, but
unbalance current may result. heavy external faults and is obtained by
in some applications a non-linear
allowing the auto-transformer to saturate
resistor is required to limit this voltage.
To ensure stability under these above the relay setting. This limits the
conditions, it is modern practice to use a Types MCAG 14 and MCAG 34 relays current supplied, and the attracted
voltage operated, high impedance relay, are single and triple pole, respectively. armature unit operates only on the
set to operate at a voltage slightly higher slower part of its time-current curve.
than that developed by the current
transformers under maximum external
fault conditions.

Figure 1

Type MCAG 34 relay


withdrawn from case
MCAG 14/ 34

366
A
B
C

Stabilising
Alarm Trip
Resistors
25 26 27
1 3 2 4 23 24 28
CT Shorting
Contacts
A IA IB IC

B
Note:
All three elements
are identical.
Only one is shown

Figure 2 Internal and external circuit diagram for unbiased differential protection of generators, reactors
and synchronous motors using type MCAG 34 relay

Figure 3 Type MCAG14 relays applied to restricted earth fault protection of power transformer

100
Operating Time in Milliseconds

50
MCAG 14/ 34

0
1 2 3 4 5 6 7 8 9 10
Multiples of Pick Up

Figure 4 Time/current characteristic

367
Technical Data Operation indicator Metrosil
A hand reset operation indicator is fitted A Metrosil is required to limit the CT
Burdens as standard output voltage under an internal fault if
Vp>3kV. The voltage spike (Vp) due to
1 VA at setting
CT saturation is calculated from:
Current transformer knee-point
voltage Vp = 2 √2VkA (Vf–VkA)
Standard current settings
The knee-point voltage is defined as the Vf = Ifint (Rs+Rp+Rsr+VA)
5% – 20%, 10% – 40% or 20% – 80% of
point on the magnetisation curve at
0.5A, 1A or 5A (CT secondary), Ir2
which a 10% increase in excitation
adjustable by plug setting bridge in
voltage produces a 50% increase in Where:
seven equal steps
excitation current. The required stability Ifint = maximum secondary internal
voltage setting (Vs’) minimum knee-point fault current
Rated frequency voltage (Vk) and maximum excitation
current (Ie) are calculated as follows: VkA = actual CT knee - point voltage
50Hz or 60Hz
Vs’ ≥ If (Rs+Rp) Standard single disc metrosils suitable
for Ifint ≤ 50A (RMS)
Operating time VsA = VA + Ir Rsr
25ms at 5 times current. See Figure 4. Ir
Stabilising resistance
Vk ≥ 2VsA
Externally mounted, continuously
Thermal withstand
Ie = Is-Ir variable resistors of 470Ω, 220Ω and
• Relay
n 47Ω for 0.5A, 1A and 5A CT
5 times tap setting continuous secondaries respectively are supplied as
20 times tap setting for 3s where standard. Non-standard resistance
• Contacts If = maximum secondary through fault values and non-linear voltage limiting
Two pairs of make self-resetting current devices are available.
contacts are provided on single
Is = effective fault setting expressed in The appropriate value of series
element relays and two on three
secondary amps resistance (Rsr) required to ensure
element relays. In three element relays
the contacts are connected in parallel, Ir = relay setting current stability is calculated as follows:
as shown in Figure 2, or brought out
Rs = CT secondary winding resistance Rsr = Vs’ – VA/Ir
to separate case terminals if required
Rp = maximum loop lead resistance Ir
Contact ratings between CTs and relay where
• Make and Carry Continuously n = 3 for restricted earth fault Vs’ = minimum required stability
ac 1250VA with maxima of protection on delta windings voltage
5A or 300V
(3CTs)
dc 1250W with maxima of VA = relay burden
5A or 300V n = 4 for restricted earth fault
protection on star windings (4CTs) Ir = relay setting current
• Make and Carry for 3s
n = 2 for machine differential In certain applications there is no need
ac 7500VA with maxima of
30A or 300V protection to utilise stabilising resistors in series
with the MCAG14/34 (indicated by
dc 7500W with maxima of n = number of CT groups forming the negative stabilising resistor value) the
30A or 300V
protected zone for bus-zone impedance of the relay elements alone
• Break differential protection will offer sufficient stabilising.
ac 1250VA with maxima of
VsA = Actual voltage setting
5A or 300V
MCAG 14/ 34

dc 100W (resistive)
50W (inductive) with
maxima of 5A or 300V

368
High voltage withstand • EMC compliance Product safety
• Dielectric withstand 89/336/EEC
IEC 60255-5:1977 Compliance to the European
Commission Directive on EMC is 73/23/EEC
2kV rms for 1 minute between all
terminals and case earth. claimed via the Technical Construction Compliance with the European
File route. Commission Low Voltage Directive.
2kV rms for 1 minute between
terminals of independent circuits, with EN 50081-2:1994 EN 61010-1: 1993/A2:1995
terminals on each independent circuit EN 50082-2:1995 EN 60950: 1992/A11:1997
connected together. Generic Standards were used to Compliance is demonstrated by reference
1kV rms for 1 minute across open establish conformity. to generic safety standards.
contacts of output relays.
• High voltage impulse
IEC 60255-5:1977
Three positive and three negative
impulses of 5kV peak, 1.2/50µs, 0.5J
between all terminals of the same
circuit (except output contacts)
between independent circuits, and
between all terminals connected
together and case earth.

Electrical environment
• High frequency disturbance
IEC 60255-22-1 Class III
2.5kV peak between independent
circuits and case.
1.0kV peak across terminals of the
same circuit.
No additional tolerances are required
for the operating time of the unit’s
thresholds.

Figure 5 External stabilising resistor assembly.

Figure 6 Outlines and mounting arrangement for the standard single disc Metrosil units.

Insulating Spacer

M6 ISO Terminals
MCAG 14/ 34

101 M12 ISO Stud


152

107

178 2mm - 7mm Fixing Holes


190±7
All dimensions in mm 240
25.4

369
Atmospheric environment
26
• Temperature 4 holes 4.4ø 23.5
71
IEC 60255-6
Storage and transit -25°C to +70°C
Operating -25°C to +55°C
168 159
IEC 60068-2-1 Cold
IEC 60068-2-2 Dry Heat
• Humidity Push button 73
IEC 60068-2-3 projection 10 max
Panel cut-out:
56 days at 93% RH and 40°C Flush mounting fixing details
• Enclosure protection
32 212 25 min.
IEC 60529
IP50 (dust protected)

Mechanical environment 177 157 max.


• Vibration
IEC 60255-21-1 Reset
0.5g between 10Hz and 150Hz
77 Flush mounting
• Mechanical durability
All dimensions in mm
Loaded contact
10,000 operations minimum
Figure 7 Case outline size 3
Unloaded contact
100,000 operations minimum

Cases
Single pole relays are housed in size 3
cases and triple pole relays in size 6
cases. See Figures 7 and 8 respectively.

103.6
Information Required with
149
4 holes ø 4.4 24
Order
• Relay type (MCAG 14 or MCAG 34)
• Current transformer secondary rating 168 159

• Frequency
• Current setting range
Push button 151
• Stabilising resistor value, projection 10 max
if non-standard Panel cut-out:
Flush mounting fixing details

32 212 25 min.
Additional Information
• Metrosil, if required:
• 1A relay:
Voltage setting (VsA) 177 157 max.
• 5A relay:
MCAG 14/ 34

Voltage setting (VsA) Reset


Secondary internal fault current (Ifint)
155 Flush mounting 11
All dimensions in mm

Figure 8 Case outline size 6

370

You might also like