855 313 105 ICT180S 12I Manual PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 28

The Power of Reliability

0*;+*+0:;90)<;0657(5,3
ICT180S-12I INTELLIGENT MODEL
(SERIES 2)

INSTRUCTION MANUAL

0556=
( ; 0=
,
 *09*
< 0;
 ;,*/
5 63
 6.
@ 3;+

      
TABLE OF CONTENTS

Warnings Page 2

Product Description Page 3

Installation Page 4

LCD/Select Button Operation Page 7

Web-Based Configuration Utility Page 9

Status Page 10

Device Setup Page 11

Output Setup Page 12

Network Setup Page 13

E-mail Setup Page 15

Alarm Setup Page 16

User Setup Page 18

Maintenance Page 19

Mobile Web App Page 20

Text Message Alarm Notifications Page 20

Password Reset Page 21

Router Configuration Page 21

Troubleshooting Page 24

Product Specifications Page 25

Limited Warranty Page 26

1
WARNING
Risk of serious personal injury or damage to equipment and property! Always observe the
following:

Use an appropriately rated over-current protection device in line with the main battery connection
to the Distribution Panel input to protect the high current input wiring

Use an appropriately rated disconnect switch or circuit breaker in line with the Distribution Panel
input to enable installation and service with the battery or power source disconnected

Always disconnect main power source before installing or removing fuses, or connecting or
disconnecting wiring

Use wire and connectors rated for the maximum load current and size of fuse or circuit breaker

Carefully observe wiring polarity when making input and output connections

Securely tighten all connections and insert fuses fully

No internal user serviceable parts. Refer all product service to an authorized ICT Ltd. service
facility

CAUTION
Risk of personal injury or damage to equipment! Always observe the following:

Fuses may be HOT to touch. Disconnect power and allow to cool before removing or replacing

Wiring terminals may be HOT to touch. Disconnect power and allow to cool before disconnecting
load wires

Install in a protected environment, keep sources of moisture away from unit

2
PRODUCT DESCRIPTION
The ICT180S-12I Intelligent Distribution Panel is designed for either 12 or 24VDC applications. It
provides 12 output positions that are individually protected by blade type fuses. Nine of the outputs
use ATO/ATC blade fuses that are rated up to 25A each. Three of the outputs use JCASE fuses and are
rated up to 40A each. These fuses are located on the front of the panel for easy monitoring and
replacement. Each positive output terminal point is connected through a fuse to a positive internal bus.
All negative output terminal points are connected to a negative internal bus.

There are five alarm inputs on the back of the panel for connecting external Dry Contact sensors for
site monitoring and reporting of alarms such as door, water, and smoke detectors.

System voltage, system current, output currents, fuse status, and alarm input status can be monitored
onsite through the LCD graphics display. Fuse status is also displayed by an LED indicator located over
each fuse. Form “C” alarm contacts (C/NO/NC) are provided on the back of the panel which can be
connected to an external alarm circuit for monitoring alarms generated by the panel.

Remote monitoring is available through the integrated security protected Ethernet communications
port on the back of the panel. The panel has a built-in web server with an embedded web-based GUI
that can be accessed using any standard commercial web browser such as Internet Explorer. The web
server not only displays panel information, it can also be set up to send an alarm to user-defined
email accounts in the event a fault occurs. The web server can also be used for data logging of up to
30 days of time stamped event information. All these features are packaged in a 1RU enclosure to
save valuable rack space and fit standard 19” equipment racks. The rack mounting position is
adjustable.

FRONT PANEL

Figure 1.

1. FUSE STATUS LEDs: Turns on when a fuse is blown or missing.


2. ATO/ATC FUSES: Location of the ATO/ATC fuses rated up to 25A.
3. LCD: Displays system voltage, system current, output current and fuse
status for each of the 12 output positions.
4. OUTPUT SELECT BUTTON: For switching between LCD screens, and resetting
network, web server and password settings to original factory default values.
5. JCASE FUSES: Location of the JCASE fuses rated up to 40A.

3
BACK PANEL

Figure 2.

1. NEGATIVE INPUT STUD: For DC power source connection up to 180A peak and 150A
continuous.
2. OUTPUT TERMINAL BLOCK 10 – 12: For DC load connections up to 40A each pair.
3. ALARM FORM “C” CONTACTS: For external alarm circuit to monitor alarms generated by the panel.
4. ALARM SENSOR INPUTS: Inputs for external Dry Contact sensors.
5. LAN PORT: For remote monitoring via TCP/IP network.
6. CHASSIS GROUND STUD: For Earth ground connection.
7. OUTPUT TERMINAL BLOCK 1 – 9: For DC load connections up to 25A each pair.
8. POSITIVE INPUT STUD: For DC power source connection up to 180A peak and 150A
continuous.

INSTALLATION

1. Inspect panel and accessories to make sure everything is complete and in good condition.

2. For rack set up, install panel on the rack using appropriate size screws and star washers on all four
mounting holes. If equipment rack is not electrically connected to Earth ground, connect a ground
cable from the ground stud on the back of the panel to a known Earth ground point. Otherwise, the
four mounting screws and washers may be sufficient for earth ground connection.

OR

For non-rack set up, connect a ground cable from the ground stud on the back of the panel to a
known Earth ground point.

3. Remove the plastic shield(s) covering the output terminal block(s) located on the back of the panel.
Connect the positive of the load to the positive terminal point (labeled “+”) and the negative of the load
to the negative terminal point (labeled “-”).

4
4. Install fuse on the front of the panel for each output terminal block. The fuse number on the front
of the panel matches the output terminal block number on the back of the panel. Consult your local
electrical codes for wire ampacity and fuse sizing. Typically, fuses and wiring are derated to 80% of
their rating (e.g. 12 Amps maximum for a 15 Amp fuse). For terminal blocks with no load connected,
insert any size fuse to prevent the LED on the front of the panel from turning on and the alarm from
activating if the form “C” alarm is used.

5. Remove the plastic caps covering the input insulated studs. Connect the positive of the power
source to the red insulated stud (labeled “+”) and the negative of the power source to the black
insulated stud (labeled “-”).

6. Re-install plastic shield(s) to the output terminal block(s) and plastic caps to the input studs.

7. For remote monitoring and power control, connect your network interface to the Ethernet port on
the back of the panel. The recommended cable for Ethernet connection is Cat5e UTP network cable.

8. The Alarm Form “C” Contacts on the back of the panel can be connected to an external alarm circuit
to monitor alarms generated by the panel. Depending on the alarm circuit (refer to table 2), connect it
between normally open (NO) and common (C), between normally close (NC) and common (C), or both.
The built-in web server controls this alarm. The alarm connector can be unplugged from the panel for
easy installation.

9. For monitoring external Dry Contact sensors, connect each sensor between an Alarm Input (1 - 5)
and common (C) on the alarm input connector. The alarm input connector can be unplugged from the
panel for easy installation. Refer to table 3 for the alarm input connector pin-out.

10. Power up the distribution panel, and check for proper operation of the connected load(s), fuse
status LEDs, LCD, form “C” alarm (if using) and Ethernet communications (if connected).

LED FUSE STATUS


ON Blown or missing
OFF Good

Table 1: Fuse Status LED

5
NC/C PINS NO/C PINS CONDITION
Fuse Alarm
• Activate Alarm Form C Contact is checked
• One or more blown or missing fuse

System Under - Voltage Alarm


• Activate Alarm Form C Contact is checked
• System Voltage is below the set value

System Over - Voltage Alarm


• Activate Alarm Form C Contact is checked
• System voltage is above the set value

System Over - Current Alarm


• Activate Alarm Form C Contact is checked
Open Closed • System current is above the set value

Alarm Input #1 - #5
• Activate Alarm Form C Contact is checked
• Digital Alarm is triggered

Output Over - Current Alarm #1 - #12


• Activate Alarm Form C Contact is checked
• Output Current is above the set value

Output Under - Current Alarm #1 - #12


• Activate Alarm Form C Contact is checked
• Output Current is below the set value

No power to unit
Activate Alarm Form C Contact is checked and no fault occurred
Closed Open
All Activate Alarm Form C Contact is not checked

Table 2: Form “C” Alarm

PIN DESCRIPTION
1 Common
2 Alarm Input # 1
3 Common
4 Alarm Input # 2
5 Common Table 3: Alarm Input Connector Pin-out
6 Alarm Input # 3
7 Common
8 Alarm Input # 4
9 Common
10 Alarm Input # 5

6
LCD/SELECT BUTTON OPERATION

At power up, the LCD of the panel will display the main screen. To switch between the various
LCD screens, press the Output Select button on the front of the panel (see Figure 3 for screen
order).

Figure 3: LCD Screens

Holding the Output Select button for 2 seconds at any screens will return you to the main
screen.

Holding the Output Select button for 20 seconds at any screens will reset the password (see
Password Reset section).

The backlight of the LCD turns off if the Output Select button is not pressed for 15 minutes.
Press the Output Select button to turn the backlight back on.

7
MAIN SCREEN
Line 1: Displays the name of the panel, which is customizable through the web-based configuration
utility.
Line 2: blank
Line 3: Displays the system voltage. Voltage display will blink if the system voltage exceeds the
Under-Voltage or Over-Voltage Thresholds set on the Alarm Setup page.
Line 4: Displays the system current. Current display will blink if the system current exceeds the
Over-Current Threshold set on the Alarm Setup page.

NETWORK SCREEN

Line 1: Displays the network status.


Line 2: Displays the connection type.
Line 3: Displays the IP address assigned to the panel.
Line 4: Displays the MAC address of the panel.

OUTPUT SCREEN (1 – 12)


Line 1: Displays the name of the load, which is customizable through the web-based configuration
utility.
Line 2: Displays the fuse status. OK for good fuse and OPEN for blown or missing fuse.
Line 3: Displays the output voltage. Voltage display will blink if the voltage exceeds the Under-Voltage
or Over-Voltage Thresholds set on the Alarm Setup page.
Line 4: Displays the output current for that individual output. Current display will blink if the output
current exceeds the Output Over-Current or Under-Current Thresholds set on the Output Setup page.

ALARM INPUT SCREEN (1 – 5)

Line 1: Displays the alarm input number.


Line 2: Displays the name of the alarm input if it has been entered through the web-based
configuration utility. Otherwise, this line is blank.
Line 3: blank
Line 4: Display the alarm input status. ALARM if the alarm input is triggered, READY if the alarm input
is not triggered.

Note: The alarm input screens are only displayed if the alarm input has enabled (see Alarm Setup
section in the instruction manual).

8
WEB-BASED CONFIGURATION UTILITY

Follow these steps to access the panel from a browser. The recommended web browsers to use with
this panel are Microsoft Internet Explorer, Mozilla Firefox or Google Chrome.

1. Start your web browser.


2. Enter the IP address of the panel in the location/address field of the browser.

Figure 4.

If the panel is connected to a network with a DHCP server, the panel will be assigned an IP address
automatically. To find the current IP address of the panel, see the LCD Operation section in the
instruction manual. If the panel is not connected to a network with DHCP, it will use a default IP address
of 192.168.0.180.

3. Enter your user name and password. The default Administrator user name is admin, and there is no
password by default.

Figure 5.

9
4. Once connected, the panel Status page will appear in your browser window.

Figure 6.

STATUS
This page provides information on system voltage, system current, fuse status, current level by output
contact (1 through 12), and alarm status.

If any alarm inputs are enabled, the status of the alarm inputs will be shown on this page.

10
DEVICE SETUP
This page allows you to configure the device settings of the panel. To save any changes to the device
settings, click on Save Settings at the bottom of this page.

DEVICE INFO

Site Name: Allows you to assign a custom name to the panel.

Model: Displays the model number of the panel.

Hardware: Displays the hardware version of the panel.

DATE AND TIME SETTINGS

Current System Time: Displays the current date and time of the panel’s onboard clock. This clock is
used to timestamp the log entries in the data log. The clock can either be set manually, or it can be
synchronized with a remote NTP Time Server over Ethernet.

Synchronizing the clock with a NTP Server is recommended to ensure that the date and time will still be
correct after a power failure.

Synchronize with NTP Server: Checking this box will enable date and time synchronization with a NTP
Server. A valid server address must also be entered in the NTP Server field.

NTP Server: The name or IP address of the NTP Server used for date and time synchronization
(such as pool.ntp.org ).

Time Zone: Select a time zone to convert the time received from the NTP Server to your local time.

Set Time Manually: Checking this box will allow you to manually set the panel’s date and time. The
date must be entered in MM/DD/YY format, and the time must be entered in HH:MM:SS format.

DATA LOGGING

Data Logging: Allows you to enable data logging. With data logging enabled, the panel will record the
system voltage, system current, output currents, fuse status, and alarm input status at a sample rate of
1 sample per minute. To view the log while data logging is enabled, click on the Download Log button
next to the data logging dialog box. This will download the log in Comma Separated Values (CSV)
format, which can be opened by most spreadsheet software applications such as Microsoft Excel. The
log will hold up to 30 days of data, with oldest log entries at the top of the log file.

11
OUTPUT SETUP
This page allows you to configure the output settings of the panel. In the Select an Output to edit box,
click on the output number of the output you wish to configure. To save any changes to the output
settings, click on Save Settings at the bottom of this page.

To copy the configuration settings from one output to all of the other outputs, click on Copy Settings to
All, and then click on Save Settings to save the new settings.

OUTPUT SETTINGS

Label: Allows you to assign a custom name to each individual output. The output names are displayed
on the Status page, as well as on the LCD screen.

Ignore Fuse Status: If this box is checked, the panel will not monitor the status of the fuse for the
selected output. This will prevent nuisance alarms if an unused output does not have a fuse in place.

OUTPUT OVER-CURRENT ALARM

Over-Current Threshold: If the current on the selected output rises above the value in this field, the
output over-current alarm will trigger. The output current must remain above the over-current
threshold for at least 5 seconds before the alarm will be triggered.
To disable this alarm, set the value in this field to 0 Amps.

Activate Alarm Form C Contact: If this box is checked, the Alarm Form “C” Contacts on the panel will
indicate a fault condition when the over-current alarm is triggered for the selected output.

Send E-mail: If this box is checked, an e-mail alarm notification will be sent when the over-current
alarm is triggered for the selected output. The e-mail settings on the E-mail Setup page must be
configured correctly before e-mail notifications can be sent.

OUTPUT UNDER-CURRENT ALARM

Under-Current Threshold: If the current on the selected output drops below the value in this field, the
output under-current alarm will trigger. The output current must remain below the under-current
threshold for at least 5 seconds before the alarm will be triggered.
To disable this alarm, set the value in this field to 0 Amps.

Activate Alarm Form C Contact: If this box is checked, the Alarm Form “C” Contacts on the panel will
indicate a fault condition when the under-current alarm is triggered for the selected output.

Send E-mail: If this box is checked, an e-mail alarm notification will be sent when the under-current
alarm is triggered for the selected output. The e-mail settings on the E-mail Setup page must be
configured correctly before e-mail notifications can be sent.

12
NETWORK SETUP
WARNING: Changing the network settings will reboot the panel..

This page allows you to configure the network settings of the panel. To save any changes to the network
settings, click on Save Settings at the bottom of this page and panel will reboot.

NETWORK

MAC Address: Displays the MAC address assigned to the panel. It can also be found on line 4 of the
network status screen of the LCD (see LCD/Select Button Operation).

Enable DHCP: Turn on this setting if your network is using a DHCP server to automatically assign IP
addresses (DHCP is enabled by default). To manually assign a Static IP address to the panel, uncheck
the Enable DHCP box and then set the following settings.

IP Address: Specify a unique IP address for the panel.

Subnet Mask: Specify the mask for the subnet the panel is located on.

Gateway: Specify the IP address of the default router (gateway) used for connecting attached devices to
different networks.

Primary DNS: Specify the IP address of the Primary DNS Server for your network.

Secondary DNS: Specify the IP address of the Secondary DNS Server for your network.

WEB SERVER

WARNING: Changing these ports may affect your ability to access the panel.

The web server port numbers can be changed to any port within the range 1 – 65565.

HTTP Port: Allows you to change the HTTP port number. This port is used for HTTP traffic between the
panel and web browser. The default HTTP port is 80. If you change the HTTP port to a number besides
80, you will have to append the new port number to the URL used to access the panel (e.g.
http://192.168.0.180:8000 for IP address 192.168.0.180, port 8000).

HTTPS Port: Allows you to change the HTTPS port number used by the panel. HTTPS (HTTP secure) is a
protocol which encrypts data transfered between web browsers and servers. The default HTTPS port is
443.

To access the panel through a secure HTTPS connection, type https:// in front of the URL used to access
the panel (e.g. https://192.168.0.180:8888 for IP address 192.168.0.180, HTTPS port 8888).

UDP Port: Allows you to change the UDP port number used by the panel. This port is used when applying
firmware upgrades to the panel. The default UDP port is 9393.

13
SNMP

Configure these settings if you would like to use SNMP monitoring. SNMP (Simple Network Management
Protocol) is the industry standard protocol for network management software. When SNMP is enabled on
the panel, it allows standard SNMP management software to connect to the SNMP agent running on the
panel and read real-time system information such as voltage and current. A SNMP trap can also be sent
to your SNMP management software when an alarm or error occurs.

The information available from the SNMP agent is described in a MIB (Management Information Base)
file, which can be downloaded from the Help page. The MIB file must be imported into your SNMP
management software.

Enable SNMP: If this box is checked, the panel SNMP agent will be enabled.

Read Community: Enter the community string/password here for read-only SNMP access. The default
read community string is “public”.

Trap Community: Enter the community string/password that is sent with all traps. Some trap receivers
are able to filter on trap community.

Trap IP Addresses: Enter the IP addresses for up to two devices that will receive SNMP traps from the
panel.

SNMP Contact Information: Allows you to assign system contact information (such as a name and
phone number) for the panel, which can be read via SNMP querys. This information is optional and can
be left blank if you prefer.

14
E-MAIL SETUP
Configure these settings if you would like to receive e-mail alarm notifications from the panel. The
information for the following settings is available from your Network Administrator or Internet Service
Provider (ISP).

E-MAIL

SMTP Server: The name or IP address of your SMTP server used for sending outgoing e-mail.

SMTP Server requires SSL: Check this box if your SMTP Server requires an encrypted SSL connection.

SMTP Port: The port used by your SMTP server. The standard port used by most SMTP servers is 25.

Sender E-mail Address: Enter the e-mail address you wish to appear as the sender of the e-mail
notifications.

Recipient E-mail Addresses: Enter the e-mail addresses you wish to receive the e-mail notifications.
If multiple e-mail addresses are entered, use commas to separate the addresses. This field can also be
used to send a text message notification to a cell phone. See the Text Message Alarm Notifications
section for more information.

SMTP User Name: If your SMTP server requires a user name and password, enter the user name here.
Leave this field blank if your SMTP server does not require authentication.

SMTP Password: If your SMTP server requires a user name and password, enter the password here.
Leave this field blank if your SMTP server does not require authentication.

Minimum E-mail Interval: This setting allows you to specify how many minutes have to elapse
between e-mail notifications. This setting is used to prevent your network from being flooded with
alarm e-mails if your alarm thresholds are not set correctly. The default setting is 1 minute. This setting
can be changed to anything between 0 and 60 minutes.

GENERAL E-MAIL NOTIFICATIONS

The Distribution Panel restarts: Check this box to receive an e-mail notification when the panel
restarts after a power failure or a soft reset.

15
ALARM SETUP
This page allows you to select which alarms you wish to monitor, and also allows you to enter custom
thresholds for each status condition. To save any changes to the alarm settings, click on Save Settings
at the bottom of this page.

FUSE ALARM

Activate Alarm Form C Contact: If this box is checked, the alarm form “C” contacts on the panel will
indicate a fault condition when an output fuse is blown.

Send E-mail: If this box is checked, an e-mail alarm notification will be sent when an output fuse is
blown. The e-mail settings on the E-mail Setup page must be configured correctly before e-mail
notifications can be sent.

SYSTEM UNDER-VOLTAGE ALARM

Under-Voltage Threshold: If the system voltage drops below the value in this field, the system under-
voltage alarm will trigger.

Under-Voltage Recovery: If the system voltage rises above the value in this field, the system under-
voltage alarm will clear. The value in this field must be at least 0.50V higher then the Under-Voltage
Threshold.

Activate Alarm Form C Contact: If this box is checked, the Alarm Form “C” Contacts on the panel will
indicate a fault condition when the system under-voltage alarm is triggered.

Send E-mail: If this box is checked, an e-mail alarm notification will be sent when the system under-
voltage alarm is triggered. The e-mail settings on the E-mail Setup page must be configured correctly
before e-mail notifications can be sent.

SYSTEM OVER-VOLTAGE ALARM

Over-Voltage Threshold: If the system voltage rises above the value in this field, the system over-
voltage alarm will trigger.

Activate Alarm Form C Contact: If this box is checked, the alarm form “C” contacts on the panel will
indicate a fault condition when the system over-voltage alarm is triggered.

Send E-mail: If this box is checked, an e-mail alarm notification will be sent when the system over-
voltage alarm is triggered. The e-mail settings on the E-mail Setup page must be configured correctly
before e-mail notifications can be sent.

16
SYSTEM OVER-CURRENT ALARM

Over-Current Threshold: If the total system current rises above the value in this field, the system
over-current alarm will trigger.

The system current must remain above the over-current threshold for at least 5 seconds before the
alarm will be triggered.

Activate Alarm Form C Contact: If this box is checked, the alarm form “C” contacts on the panel will
indicate a fault condition when the system over-current alarm is triggered.

Send E-mail: If this box is checked, an e-mail alarm notification will be sent when the system over-
current alarm is triggered. The e-mail settings on the E-mail Setup page must be configured correctly
before e-mail notifications can be sent.

ALARM INPUT #1 - #5

Alarm Name: Allows you to assign a custom name to each individual alarm input.

Contact Type: Allows you to configure each individual alarm input as a “Normally Open” contact, a
“Normally Closed” contact, or as “Not Used”.

If the alarm input is configured as “Not Used”, it will be disabled and will not appear on the Status page
or on the LCD screen.

Activate Alarm Form C Contact: If this box is checked, the alarm form “C” contacts on the panel will
indicate a fault condition when this alarm input triggers.

Send E-mail: If this box is checked, an e-mail alarm notification will be sent when this alarm input
triggers. The e-mail settings on the E-mail Setup page must be configured correctly before e-mail
notifications can be sent.

17
USER SETUP
This page allows you to configure passwords for accessing the panel. To save any password changes,
click on Save Settings at the bottom of this page.

The Administrator account has no password assigned to it by default. For improved security, it is
recommended that you assign a password to the account.

WARNING: Please record your password. If the Administrator password is lost, the panel must be reset
to return the password to the default setting. See the Password Reset section for more information.

Select a User to Edit: There are two user accounts with access to the panel:

Administrator (user name: admin) – This account has full access to the panel.

Standard User (user name: user) – This account has view-only access to the panel. This
account cannot be used to change settings.

New Password: Allows you to change the password for the selected user.

Confirm New Password: When changing a password, you must re-enter the new password here.

Administrator Password: Enter the current Administrator password here to confirm changes.

18
MAINTENANCE
This page allows you to reset the panel, restore the panel to factory default settings, and send test
e-mail to verify that functionality.

RESET COMMUNICATIONS

Pressing the Reset button will reset the Ethernet communications port on the panel without interrupting
DC power to the output terminals. Current settings are maintained during the reset.

RESTORE FACTORY DEFAULT SETTINGS

Pressing the Restore button will restore ALL settings to the original factory default values, including the
passwords. If you only want to restore the network settings and passwords, see the Password Reset
section.

SEND TEST E-MAIL

Pressing the Send Test E-mail button will send test e-mail to the specified recipient using the e-mail
settings on the Network Setup page.

PING DIAGNOSTICS TOOL

This tool can be used to verify connectivity to any network device. To use the tool, Enter the hostname or
IP address of the target device, then click Ping.

19
MOBILE WEB APP
A mobile version of the Status page is available which is optimized for smartphone web browsers.

To access the Mobile Web App, type the address of the panel in the location/address field of the
browser on your smartphone, followed by /m
(e.g. https://192.168.0.180/m ). You will be prompted for your user name and password.

For increased security when accessing the panel over the Internet, it is highly recommended that you
connect to the Mobile Web App using a HTTPS connection, or use a Virtual Private Network (VPN)
connection.

Figure 7: Mobile Web App

The Mobile Web App provides information on system voltage, system current, alarm input status, fuse
status, and current level by output contact (1 through 12).

TEXT MESSAGE ALARM NOTIFICATIONS


The panel can send text message alarm notifications to a cell phone by sending the alarm e-mail to an address at
the mobile phone provider. On the E-mail Setup page, enter the address for your phone in the Recipient E-mail
Addresses field. For example, to send a text message to an AT&T phone, enter [email protected], replacing
cellnumber with your cell phone number.

Here are some address formats for other mobile phone providers:

AT&T [email protected]
Verizon [email protected]
T-Mobile [email protected]
Virgin Mobile [email protected]
Nextel [email protected]
Bell Mobility [email protected]
Rogers [email protected]
Telus [email protected]

20
PASSWORD RESET
Resetting the password resets the Administrator password, network and web server settings to the
original factory default values. The Standard User password is not affected. To reset, do the following:

1. Press and hold the Output Select button on the front of the panel (approximately 20 seconds) until
Resetting is shown on the LCD.

2. Release the button.

3. After reset is complete, press and release the Output Select button once to view the network status
screen on the LCD. The new IP address of the panel will be displayed.

ROUTER CONFIGURATION
This section explains how to set up the panel behind a router and enable remote access to the panel
over the Internet.

A router allows multiple PCs to share a single Internet connection. To enable access to the panel over
the Internet, you will need to configure your router to forward incoming remote data to the local IP
address of your panel.
The following steps use a Linksys WRT54G router as an example.

1. Log in to your router and go to the port forwarding screen. In the Linksys WRT54G, this is located in
the Applications and Gaming tab. The location of port forwarding may be different on other routers
(consult your router manual for instructions).

2. To configure HTTP forwarding, following these steps:

a. Enter a unique name in the Application field.


b. Enter the HTTP port number that the panel is using in the Start and End fields. If you are
using the default panel port settings, the port number is 80.
c. Select Both under Protocol (TCP and UDP).
d. Enter the local IP address of the panel (e.g. 192.168.0.180) in the IP Address field. See
step 2 of Web-based Configuration Utility section to find the actual local IP address of
your panel.
e. Check Enable, and then click on Save Settings.

NOTE: Many ISPs block access to port 80. If your ISP does block port 80, you will need to change
the HTTP port the panel uses from 80 to something else, such as 8000. Valid port numbers
are in the range of 1 - 65535. See the Network Setup section for instructions on how to
change the panel network ports. You will also need to change the HTTP port number from
80 to something else if your local network already contains another device using port 80
such as another panel or a web server.

21
Figure 8.

3. To configure HTTPS forwarding, repeat steps 2a – 2e with the HTTPS port number that the panel
is using. If you are using the default panel port settings, the HTTPS port number is 443.

4. To set up your router to allow remote panel firmware upgrades, repeat steps 2a – 2e with the
UDP port number that the panel is using. If you are using the default panel port settings, the UDP
port number is 9393. Firmware upgrades can still be applied locally if this step is skipped.

5. Before you can access the panel over the Internet, you will need to know the WAN IP address of
the router, which is assigned by your ISP. With the Linksys WRT54G router, this information is
available in the Status tab, listed as IP Address (see Figure 9).

NOTE: If you are using a Dynamic IP address, your WAN IP Address may change from time to time
without warning, depending on your ISP. You may want to obtain a Static IP address from
your ISP, which will be more convenient to use to access the panel from a remote location.
A Static IP address is a fixed IP address that will not change. Alternatively, if a Static IP
address is not available, you can use a Dynamic DNS service such as Dyn (see
www.dyn.com).

22
Figure 9.

6. To access the panel over the Internet, type the WAN IP Address of the router in the
location/address field of your browser, followed by a colon and the HTTP port number that the panel
is using (e.g. http://209.123.10.33:8000 for IP Address 209.123.10.33, Port 8000).

Figure 10.

23
TROUBLESHOOTING
I am unable to access the web-based configuration utility:

Check that you are using the correct IP address to access the panel by pressing the Output Select
button on the front of the panel to view the Network Status screen on the LCD. The IP address for
the panel may have changed if DHCP is enabled.

If the Network Status screen on the LCD shows Network Not Connected, check the network cable
connections to the panel and the network.

Ensure that you are using the correct type of network cable. An industry standard "crossover" cable
should be used for connecting directly to a computer, and a “straight-through” cable should be used
for connecting to a network.

Ensure the network card settings on your computer are appropriate for accessing the IP address of the
panel. To access a panel wtih the default IP address of 192.168.0.180, typical network settings for
your computer are:
o IP Address: 192.168.0.100
o Subnet Mask: 255.255.255.0
o Gateway: 192.168.0.1

If the HTTP port of the panel has been changed, you must append the port number to the URL used to
access the panel. See the Password Reset section for instructions on how to reset the port number
to the default setting.

If your network switch allows you to manually configure port speed and duplex settings, turn on
“Auto-negotiation” on the switch port that the panel is connected to.

I forgot my password:

See the Password Reset section for instructions on how to reset the password.

I am not receiving e-mails from the panel:

On the Network Setup page, ensure that the SMTP Server field is entered correctly. The SMTP Port
should be set to 25 for most servers.

If your SMTP server requires SSL encrytion, ensure that the SMTP Server requires SSL checkbox is
checked. Otherwise, this box must be left unchecked.

If your SMTP server requires authentication, ensure that the SMTP User Name and SMTP Password
fields are entered correctly. If no authentication is required, leave these fields blank.

Verify your e-mail settings by going to the Maintenance page and clicking on the Send Test E-mail
button to send a test e-mail. The Send Test E-mail page will display an error message if the panel
unable to send the e-mail.

On the setup pages, ensure that the Send E-mail checkboxes are checked for alarm conditions you
wish to receive notifications for.
24
PRODUCT SPECIFICATIONS
Operating Voltage: 10 to 32VDC
Panel Capacity: 150A (Continuous)
180A (Peak)
Fuse Capacity: 25A Maximum ATO/ATC Blade x 9
40A Maximum JCASE x 3
Note 1: Ensure that the load total connected to the fused outputs does not exceed the panel capacity rating.

Note 2: Most fuses should be continuously operated at no more than 80% of their nominal current rating.
Consult the fuse manufacturers specifications.

Power Consumption: 2.5 watts


Voltage Drop (without fuse): 60mV (Typical)

Alarm Form “C” Contact: Form “C” Dry Contacts


1A/60VDC Max

Alarm Sensor Inputs: External dry contact alarm inputs, configurable for NO or NC logic.
Applied voltage 3.3V, 0.4mA for contact closure detection.

Ethernet: RJ45, 10Base-T/100Base-T


SNMP: SMNPv1/v2c

Input Connector: Heavy Duty Insulated M10 Stud


75in-lbs Max

Output Connector: Barrier Terminal Block


M4 Screws
8 – 20AWG Wire Range
12in-lbs Max
Alarm Connectors: Euro Terminal Block
M2 Screws
16 – 28AWG Wire Range
1in-lbs Max
Operating Temperature: -4°F to 140°F
-20°C to +60°C
Dimensions: 19.0” x 9.29” x 1.75”
483mm x 236mm x 45mm

Weight: 8.0lbs (3.6kg)

Warranty: 3 years

25
LIMITED WARRANTY
ICT Ltd. warrants to the original consumer purchaser that this product shall be in good working order,
free from defects in materials and workmanship, for a period of three (3) years from the date of
purchase. Should failure occur during the above stated time period, then ICT will, at its option, repair or
replace this product at no additional charge except as set forth below. All parts, whether for repair or
replacement, will be furnished on an exchange basis. All exchange pieces become the property of ICT.
This limited warranty shall not apply if the ICT product has been damaged by unreasonable use,
accident, negligence, disaster, service, or modification by anyone other than the ICT factory.

Limited warranty service is obtained by delivering the product during the above stated three (3) years
warranty period to an authorized ICT dealer or ICT factory and providing proof of purchase date. If this
product is delivered by mail, you will insure the product or assume risk of loss or damage in transit, and
prepay shipping charges to the factory.

Every reasonable effort has been made to ensure that ICT product manuals and promotional materials
accurately describe ICT product specifications and capabilities at the time of publication. However,
because of ongoing improvements and updating of ICT products, ICT cannot guarantee the accuracy of
printed materials after the date of publication and disclaims liability for changes, errors or omissions.

If this ICT product is not in good working order, as outlined in the above warranty, your sole remedy shall
be repair or replacement as provided above. In no event will ICT be liable for any damages resulting
from the use of or the inability to use the ICT product, even if an ICT employee or an authorized ICT
dealer has been advised of the possibility of such damages, or for any claim by any other party.

ICT reserves the right to make changes without further notice to any products or documentation for
improvement of reliability, function, or design.

ICT Ltd. does not recommend use of its products in life support applications wherein a failure or
malfunction of the product may directly or indirectly threaten life or cause injury. The user of ICT
products, which are to be used in life support applications as described above, assumes all risks of such
use and indemnifies ICT against all damages.

INNOVATIVE CIRCUIT TECHNOLOGY LTD.


26921 GLOUCESTER WAY LANGLEY, BRITISH COLUMBIA, CANADA V4W 3Y3
T 604.856.6303 F 604.856.6365 www.ict-power.com