Model: LTPF: Current

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

MODEL: LTPF

Power Transducer Series LT-UNIT [3] CT INPUT (balanced load)


Current
1: 1 A AC
POWER FACTOR TRANSDUCER
2: 2 A AC
Functions & Features
5: 5 A AC
• Providing a DC output signal in proportion to power factor
• DC output containing little ripple is ideal for computer
input [4] OUTPUT SIGNAL POLARITY
• Isolation up to 2000 V AC P: Negative in lag, positive in lead
• High-density mounting M: Negative in lead, positive in lag
• Conforms to IEC 60688

[5] OUTPUT
Typical Applications
Current
• Centralized monitoring and control of power management
A: 4 – 20 mA DC (Load resistance 500 Ω max.)
system in a manufacturing facility or building
FW: -10 – +10 mA DC (Load resistance 1000 Ω max.)
• Measuring power factor for a motor
GW: -1 – +1 mA DC (Load resistance 10 kΩ max.)
JW: -5 – +5 mA DC (Load resistance 2000 Ω max.)
72
(2.83) Z: Specify current (See OUTPUT SPECIFICATIONS)
Voltage
6: 1 – 5 V DC (Load resistance 5000 Ω min.)
111 1W: -10 – +10 mV DC (Load resistance 10 kΩ min.)
(4.37)
2W: -100 – +100 mV DC (Load resistance 100 kΩ min.)
3W: -1 – +1 V DC (Load resistance 1000 Ω min.)
4W: -10 – +10 V DC (Load resistance 10 kΩ min.)
5W: -5 – +5 V DC (Load resistance 5000 Ω min.)
143 (5.63) 0: Specify voltage (See OUTPUT SPECIFICATIONS)
mm (inch)

[6] AUXILIARY POWER SUPPLY


AC Power
MODEL: LTPF–[1][2][3][4][5]–[6][7]
K3: 100 – 120V AC
(Operational voltage range 85 - 132 V, 47 - 66 Hz)
ORDERING INFORMATION L3: 200 – 240V AC
• Code number: LTPF–[1][2][3][4][5]–[6][7] (Operational voltage range 170 - 264 V, 47 - 66 Hz)
Specify a code from below for each of [1] through [7]. DC Power
(e.g. LTPF-115PA-R/T/Q) R: 24 V DC
• Special output range (For codes Z & 0) (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
• Specify the specification for option code /Q V: 48 V DC
(e.g. /C01) (Operational voltage range 48 V ± 10 % , ripple 10 % p-p max.)
P: 110 V DC
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)
[1] CONFIGURATION
(CE not available)
1: 3-phase / 3-wire
4: 3-phase / 4-wire
[7] OPTIONS (multiple selections)
Terminal Cover
[2] VT INPUT (balanced load)
blank: Without
For 3-phase / 4-wire, phase voltages (e.g. 110 V / √3 ) are used.
/T: With
1: 100, 110, 115, 120 V AC
Other Options
2: 190, 200, 210, 220, 230, 240 V AC
blank: none
4: 380, 400, 415, 430, 440, 480 V AC
/Q: Option other than the above (specify the specification)

LTPF SPECIFICATIONS ES-3359 Rev.12 Page 1/4

http://www.m-system.co.jp/
MODEL: LTPF
■ OPERATION DIAGRAM (example)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.) • Negative in lag, positive in lead
/C01: Silicone coating OUT OUT
20mA +10V
/C02: Polyurethane coating
/C03: Rubber coating 12
0

4
GENERAL SPECIFICATIONS -10V
Connection: M4 screw terminals (torque 1.2 N·m) 0.5 1 0.5 0.5 1 0.5
(Lag) (Lead) (Lag) (Lead)
Screw terminal: Chrome-plated steel
Housing material: Flame-resistant resin (black) • Negative in lead, positive in lag
OUT OUT
Isolation: Voltage input to current input to output to 20mA +10V
auxiliary power
Computation: Phase angle detection 12
0
Overrange output: Approx. -10 to +120 % at 1 – 5 V
4
Zero adjustment: -5 to +5 % (front) -10V
Span adjustment: 95 to 105 % (front) 0.5
(Lag)
1 0.5
(Lead)
0.5
(Lag)
1 0.5
(Lead)

INPUT SPECIFICATIONS Remark: When there is no input voltage or 5% or less of


rated input current , the output may become unstable (hunting).
Note: A device which employs different measuring methods
may show different outputs from that of M-System’s with
distorted input waveforms. INSTALLATION
Frequency: 50 or 60 Hz Power Consumption
■ VOLTAGE INPUT •AC: Approx. 2 VA
Operational range: 85 – 120 % of rating •DC: Approx. 2 W (18 mA at 110 V)
Overload capacity: 150 % of rating for 10 sec., 120 % Operating temperature: -10 to +55°C (14 to 131°F)
continuous Operating humidity: 30 to 85 %RH (non-condensing)
Input burden: 0.5 VA Mounting: Surface or DIN rail
■ CURRENT INPUT Weight: 450 g (0.99 lb)
Operational range: 10 – 120 % of rating
Overload capacity: 4000 % of rating for 1 sec., 2000 % for 4
sec., 120 % continuous PERFORMANCE in percentage of span
Input burden: 0.1 VA (input 1 A) Accuracy: ±2 % with input 1 – 0.866, balanced load
0.2 VA (input 2 A) ±4 % with input 0.866 – 0.5, balanced load (at 23°C ±10°C
0.5 VA (input 5 A) or 73.4°F ±18°F, 45 – 65 Hz)
■ Input range: Magnetic field (ext. origin) effect: ±2 % (400 A/m)
Lag 0.5 – 1 – lead 0.5 Response time: ≤ 2 sec. (0 – 100 % ±1 %)
Lead 0.5 – 1 – lag 0.5 Ripple: 0.5 %p-p max.
Line voltage effect: ±1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
OUTPUT SPECIFICATIONS Dielectric strength: 2000 V AC @ 1 minute
■ DC Current: -10 – +20 mA DC (voltage input to current input to output to auxiliary power
Span: Min. 1 mA, max. 20 mA to ground)
Offset: Max. 1.5 times span Impulse withstand voltage: 1.2 / 50 μsec., ±5 kV
Load resistance: Output drive 10 V max. (input to output or ground)
■ DC Voltage: -10 – +12 V DC
Minimum span: 5 mV
Offset: Max. 1.5 times span STANDARDS & APPROVALS
Load resistance: Output drive 1 mA max. at ≥ 0.5 V EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive

LTPF SPECIFICATIONS ES-3359 Rev.12 Page 2/4

http://www.m-system.co.jp/
MODEL: LTPF
EN 61010-1
Measurement Category II (input)
Installation Category II (auxiliary power)
Pollution Degree 2
Input to output or auxiliary power: Reinforced insulation
(550 V)
Output to auxiliary power: Reinforced insulation (300 V)
RoHS Directive
EN 50581

CONNECTION DIAGRAM
■ 3-PHASE/3-WIRE ■ 3-PHASE/4-WIRE
SOURCE SOURCE
1 2 3 N 1 2 3
FUSE VT FUSE VT
V v P2 U u P2
8 11 + 8 11 +
OUTPUT OUTPUT
U u P3 V v P0
9 12 – 10 12 –
V v
P3
15 U(+) 9 15 U(+)
* U u *
AUXILIARY AUXILIARY
K POWER K POWER
k
16 V(–) k
16 V(–)
1S 1S
1 1
CT CT
1L 1L
2 2
l l
L L

LOAD LOAD

*The transducer can be powered from the input voltage


when the voltage is sufficiently stable and meets within
the range of auxiliary power supply of the unit specified
in the data sheet/instruction manual.

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)


10 (.39) 16–M4 SCREW
2–M4 MTG HOLE

TERMINAL COVER (option /T)

DIN RAIL
1 2 3 4 5 6
35mm wide
111 (4.37)
98 (3.86)
80 (3.15)

7 8 9 10

11 12 13 14 15 16

54 (2.13) 8 (.31)
3
72 (2.83) (.12) 143 (5.63) [4 (.16)]

• When mounting, no extra space is needed between units.

LTPF SPECIFICATIONS ES-3359 Rev.12 Page 3/4

http://www.m-system.co.jp/
MODEL: LTPF

Specifications are subject to change without notice.

LTPF SPECIFICATIONS ES-3359 Rev.12 Page 4/4

http://www.m-system.co.jp/

You might also like