1. General
1.1 Monitor data signed with a "T1" are only for T1-controls and must be 0 for M1-controls.
Reverse function for monitor data signed with a "M1".
1.2 The values in the brackets are recommended from the manufacturer and should not be changed
without consultation. In case different values are necessary for different machine types, refer to
the attached table. If there is an asterisk instead of a number in the bracket, the value must be
adapted to the machine.
1.3 The numbers in the circular brackets show a range of numbers which are allowed for these
parameters.
1.4 For the parameters which are selected by bits: -To use this function, the bit must be high. The
value of the bits are
BIT VALUE
0 1
1 2
2 4
3 8
4 16
5 32
6 64
7 128
If you will activate more than one bit, add the value of the activated bits together and write the sum in the
parameter.
2. User Monitor (MON)
Parameters: D, L, R
(For all 3 priorities, the hardware modification on axis controller is necessary and
parameter G7 bit 0 must be activated)
L0...MSD bits
bit 0...Diameter dimensions for input data (T1) <1>
bit 1...Inch dimensional for input data G70 <*>
bit 2...Displaying of the incoming data through serial interface on screen, also, there is no
checking of an already existing program, that means, you can write over an already
existing program in the memory <0>
bit 3...Deactivating of the software limit switch in manual mode <0>
bit 4...Tool measuring with reference workpiece (manual mode T1)
bit 5...Not used <0>
bit 6...Memory locked <0>
bit 7...Control locked <0>
L1...MSD bits
bit 0...Collet mode after power on initial <*>
bit 1...Automatic feedhold while moving parts catcher <0>
bit 2...M51 mode for bi-directional tool turret after power on initial <*>
bit 3...Modified tool turret control: <0>
a. indexing to the next position by reset
b. Indexing without JOG enable button in manual mode
c. Ml tool turret: indexing procedure:
feed override = 100%, switch function inactivate <0>
bit 4...Parts counter active <0>
bit 5...Parts preset counter active <0>
bit 6...Ignore end of bar signal <0>
bit 7...Door automatic: M53 mode after power-on initial <0>
1 start bit
7 data bits
1 stop tit
even parity
L5...MSD bits
bit 0...Alarm 57 will not appear in G41/42 mode <0>
bit 1...Not used <0>
bit 2...Not used <0>
bit 3...Not used <0>
bit 4...At the beginning and at the end, there will be 50 ASCII signs ".0" transmitted (for punched
tape)
bit 7...Not used <0>
L7...MSD bits
bit 0...Barfeeder active <*>
bit 1...FMS mode active
bit 2...Not used <0>
bit 3...Not used <0>
bit 4...Not used <0>
bit 5...Not used <0>
bit 6...Not used <0>
bit 7...Not used <0>
Parameters F, G, M, O, S, T, X, Z
F0...Numerical input limit for parameter F, also maximum threading pitch <32767>
F1...Feed limit per minute Execute and Automatic mode mm/min (see table)
F2...Feed limit per minute in manual mode mm/min (see table)
F4...Manual slow feed (max. feedrate, prior to reference) mm/min <300>
F5...Dryrun feedrate mm/min (see table)
F6...Rapid traverse X-axis mm/min (see table)
F7...Rapid traverse Y-axis mm/min (see table)
F8...Rapid traverse Z-axis mm/min (see table)
F9...Feedrate for referencing the machine
4. Connection Assignments
O0...Coolant ON/OFF
O1...Lubricant ON/OFF
O2...Close chuck/Open collet
O3...Open chuck/Close collet
O4...Alarm status output (x22a/1a)
I0...Door limit switch
I1...Pressure switch lubrication
I2...Coolant control input from motor driver board
I3...T1: End position monitoring clamping device or pressure switch front-end chuck
M1: 0V...fast transmission gear stage 24v..slow transmission gear stage
I4...System pressure chuck (or pressure switch chuck close/collet open) (x22a/3a)
4.2 Machine interface/terminal strip X16a on axis bus board (terminal designations 1-21 from top to
bottom in brackets)
4.3 Machine interface: plugs X16b and X16c in board handle (numbers of the Panduit plug pins in
brackets)
Note: On plug X16b the inputs MI28-31 (pins 16-13) as well as the outputs M014-17 (pins 4-1)
will be used later for the planned serial EMCO bus which will then assume the I/O
functions connected there are present.
TABLE FOR SPECIFIC MACHINE TYPE PARAMETER
The value for parameters M1, M2, M3 are standard values and must be adjusted individually to each
machine.