User Manual: Electronic Control
User Manual: Electronic Control
User Manual: Electronic Control
electronic control
User manual
IMPORTANT WARNINGS
ENGLISH
CAREL bases the development of its products on several years’ experience in the HVAC field,
on continuous investment in technological innovation of the product, on rigorous quality
procedures and processes with in-circuit and function tests on 100% of its production, on
the most innovative production technologies available on the market. CAREL and its branch
offices/affiliates do not guarantee, in any case, that all the aspects of the product and the
software included in the product will respond to the demands of the final application, even
if the product is built according to state-of-the-art techniques. The client (builder, develo-
per or installer of the final equipment) assumes every responsibility and risk relating to the
configuration of the product in order to reach the expected results in relation to the specific
final installation and/or equipment. CAREL in this case, through specific agreements, can
intervene as consultant for the positive result of the final start-up machine/application, but in
no case can it be held responsible for the positive working of the final equipment/apparatus.
The CAREL product is a state-of-the-art product, whose operation is specified in the
technical documentation supplied with the product or can be downloaded, even prior to
purchase, from the website www.carel.com.
Each CAREL product, in relation to its advanced technological level, needs a phase of
definition / configuration / programming / commissioning so that it can function at its best
for the specific application. The lack of such phase of study, as indicated in the manual, can
cause the final product to malfunction of which CAREL can not be held responsible.
Only qualified personnel can install or carry out technical assistance interventions on the
product.
The final client must use the product only in the manner described in the documentation
related to the product itself.
Without excluding proper compliance with further warnings present in the manual, it is
stressed that in any case it is necessary, for each Product of CAREL:
• To avoid getting the electrical circuits wet. Rain, humidity and all types of liquids or con-
densation contain corrosive mineral substances that can damage the electrical circuits. In
any case, the product should be used and stored in environments that respect the range
of temperature and humidity specified in the manual.
• Do not install the device in a particularly hot environment. Temperatures that are too
high can shorten the duration of the electronic devices, damaging them and distorting
or melting the parts in plastic. In any case, the product should be used and stored in envi-
ronments that respect the range of temperature and humidity specified in the manual.
• Do not try to open the device in any way different than that indicated in the manual.
• Do not drop, hit or shake the device, because the internal circuits and mechanisms could
suffer irreparable damage.
• Do not use corrosive chemical products, aggressive solvents or detergents to clean the
device.
• Do not use the product in application environments different than those specified in the
technical manual.
All the above reported suggestions are valid also for the control, serial unit, programming
key or nevertheless for any other accessory in the product portfolio of CAREL.
CAREL adopts a policy of continuous development. Therefore, CAREL reserves the right to
carry out modifications and improvements on any product described in the present docu-
ment without prior notice.
The technical data in the manual can undergo modifications without obligation to notice.
The liability of CAREL in relation to its own product is regulated by CAREL’s general contract
conditions edited on the website www.carel.com and/or by specific agreements with
clients; in particular, within the criteria consented by the applicable norm, in no way will CA-
REL, its employees or its branch offices/affiliates be responsible for possible lack of earnings
or sales, loss of data and information, cost of substitute goods or services, damage to things
or persons, work interruptions, or possible direct, indirect, incidental, patrimonial, of covera-
ge, punitive, special or consequential in any way caused damages, be they contractual, out-
of-contract, or due to negligence or other responsibility originating from the installation,
use or inability of use of the product, even if CAREL or its branch offices/affiliates have been
warned of the possibility of damage.
Disposal of the product
In reference to European Community directive 2002/96/EC issued on 27 January
2003 and the related national legislation, please note that:
1. we cannot be disposed of as municipal waste and such waste must be collec-
ted and disposed of separately;
2. the public or private waste collection systems defined by local legislation must be used.
In addition, the equipment can be returned to the distributor at the end of its working life
when buying new equipment.
3. the equipment may contain hazardous substances: the improper use or incorrect dispo-
sal of such may have negative effects on human health and on the environment;
4. the symbol (crossed-out wheeled bin) shown on the product or on the packaging and on
the instruction sheet indicates that the equipment has been introduced onto the market
after 13 August 2005 and that it must be disposed of separately;
5. in the event of illegal disposal of electrical and electronic waste, the penalties are speci-
fied by local waste disposal legislation.
ENGLISH
1. INTRODUCTION 7
1.1 General description ..............................................................................................................................7
1.2 User interface ........................................................................................................................................7
2. CONNECTIONS 9
2.1 General diagram ...................................................................................................................................9
2.2 Network layout .....................................................................................................................................9
3. APPLICATIONS 10
3.1 Air/air unit ..............................................................................................................................................10
3.2 AIR/AIR heat pump ..............................................................................................................................11
3.3 AIR/WATER chiller ................................................................................................................................13
3.4 AIR/WATER heat pump .......................................................................................................................14
3.5 WATER/WATER chiller .........................................................................................................................16
3.6 WATER/WATER heat pump with reversal on gas circuit..............................................................17
3.7 WATER/WATER heat pump with reversal on water circuit..........................................................19
3.8 Air-cooled condensing unit without reverse cycle .......................................................................20
3.9 Reverse-cycle air-cooled condensing unit ......................................................................................21
3.10 Water-cooled condensing unit without reverse cycle ................................................................22
3.11 Reverse-cycle water-cooled condensing unit ...............................................................................23
3.12 Roof Top units ...................................................................................................................................24
4. PARAMETERS 25
4.1 General parameters .............................................................................................................................25
4.2 Menu structure .....................................................................................................................................25
4.3 Parameter tables ..................................................................................................................................26
6. TABLE OF ALARMS 57
8. DIMENSIONS 66
9. CODES 68
ENGLISH
1.1 General description
The μC2SE is a new compact CAREL electronic controller, the same size as a normal thermostat, for
the complete management of chillers and heat pumps: it can control air-air, air-water, water-water
and condensing units.
1.1.3 Programming
CAREL offers the possibility to configure all the unit parameters not only from the keypad on the
front panel, but also using:
• a hardware key;
• a serial line.
E D C B A L K
Fig. 1.a
1.2.2 Symbols on the display
Display with 3 green digits (plus sign and decimal point), amber symbols and red alarm symbols.
Go up a sub-group inside the programming area, until exiting (saving changes to EEPROM) press once
In the event of alarms, mute the buzzer (if present) and deactivate the alarm relay press once
L Access the direct parameters press for 5 s
Select item inside the programming area and display value of direct parameters/confirm the changes to the parameters press once
I+L Program parameters afters entering password press for 5 s
J Select top item inside the programming area press once or press and hold
Increase value press once or press and hold
Switch from standby to chiller mode (P6=0) and vice versa press for 5 s
Provides immediate access to the condenser and evaporator pressure and temperature probes and DTE, DTC1-2 press once
K Select bottom item inside the programming area press once or press and hold
Decrease value press once or press and hold
Switch from standby to heat pump mode (P6=0) and vice versa press for 5 s
Provides immediate access to the condenser and evaporator pressure and temperature probes and DTE, DTC1-2 press once
J+K Manual alarm reset press for 5 s
Immediately reset the hour counter (inside the programming area) press for 5 s
L+J Force manual defrost on both circuits press for 5 s
Table 1.b
1.2.5. Keypad
The keypad is used to set the unit operating values (see Parameters/alarms - Keypad
combinations)
ENGLISH
2.1 General diagram
CONVONOFF*:
PWM/digital PSOPZKEY*:
converter programming key
CONV0/10A0*:
PWM/analogic PW/Modbus® RTU
converter CAREL Supervisory
MCH200485*
NTC: temperature
RS485 MCH2*T*:
MCHRTF**A0: probes
serial card terminal
fan speed regulator
SPKT: 0 to 5 V MCH2*TSV*: PW CAREL
pres. transducer adapter Supervisory
Fig. 2.a
EV driver
Fig. 2.b
EV driver EV driver
ESP.
Fig. 2.c
2
μC SE - +030220426 - rel. 2.5 - 27.11.2012 9
3. APPLICATIONS
ENGLISH
Key: 1
1 condernser fan overload 2
2 fan 4
3 condenser probe
4 supply probe
5 electrical heater 3
6 evaporator
7 supply fan overload
8 supply fan 5
9 compressor 1
10 high pressure
11 compressor overload
12 low pressure
13 ambient probe 6
14 compressor 2
9 8
10 11 12
13
14
Fig. 3.a.a
Key:
1 condernser fan overload 1 and 2
1 1 1 2
2 fan 4
3 condenser probe 2 2
4 supply probe
5 electrical heater 1 and 2
6 evaporator 1 e 2 3 3
7 supply fan overload
8 supply fan
9 compressor 1
10 high pressure 1 and 2 5 1 2 5
11 compressor overload 1 and 2
12 low pressure 1and 2
13 ambient probe 6 6
1 2
14 compressor 2
15 compressor 3
16 compressor 4
7 7
9 15
8
10 1 1 11 12 1 2 12 11 2 10 2
14 16
13
Fig. 3.a.b
ENGLISH
Key:
3 1 1 3 2
1 condernser fan overload
2 fan
3 condenser probe 1 and 2
2 4 supply probe
5 electrical heater 1 and 2
4 6 evaporator 1 and 2
7 supply fan
B2 8 ambient probe
9 compressor 1
5 5 10 high pressure 1 and 2
1 2 11 compressor overload 1 and 2
12 low pressure 1and 2
13 compressor 2
1 6 6 2 14 compressor 3
15 compressor 4
9 14
7
10 1 1 11 12 1 2 12 11 2 10 2
13 8 15
Fig. 3.a.c
Key:
1
1 condernser fan overload
2 4
2 fan
3 condenser probe
4 supply probe
B2
3 5 electrical heater
6 evaporator
7 supply fan overload
8 supply fan
9 compressor 1
5 10 high pressure
11 compressor overload
12 low pressure
13 ambient probe
14 compressor 2
6 15 reversing valve
15
7
13
10 11 12
14
Fig. 3.b.a
Key: 1 1 2
1
1 condenser fan overload 1 and 2
2 fan 2 2
3 condernser probe
4 supply probe 3 3
5 electrical heater 1 e 2
6 evaporator 1 and 2
7 supply fan overload
8 supply fan
9 compressor 1
10 high pressure 1 e 2
4
11 compressor overload 1 and 2 B2
12 low pressure 1and 2
13 ambient probe
14 compressor 2
15 reversing valve 1and 2
16 compressor 3 5 1 2 5
17 compressor 4
1 6 6 2
15 1 2 15
7 7
9 8 16
10 11 12 13 12 11 10
1 1 1 2 2 2
14 17
Fig. 3.b.b
9 8
16
13
10 1 1 11 12 1 2 12 11 2 10 2
14 17
Fig. 3.b.c
ENGLISH
3.3.1 Single circuit
1 Key:
2 1 condernser fan overload
2 fan
3 condenser probe
3 4 flow switch
4 5 outlet evaporator probe
6 fan
7 antifreeze heater
8 inlet evaporator probe
5 9 compressor 1
10 high pressure
11 compressor overload
12 low pressure
13 water pump
14 compressor 2
6 7
13
10 11 12
14
Fig. 3.c.a
Key:
1 1 2 1
1 condenser fan overload 1 and 2
1 2 4 2 2 2 fan 1 and 2
5 3 condenser probe 1 and 2
1 3 2 3 4 flow switch
5 outlet temperature probe
6 evaporator 1 and 2
7 1
7 outlet evaporator probe 1 and 2
8 antefreeze heater 1 and 2
9 compressor 1
2 7 10 high pressure 1 and 2
11 compressor overload 1 and 2
12 low pressure 1and 2
13 inlet evaporator probe
1 6 8 8 6 2 14 compressor 2
1 2
15 water pump
16 compressor 3
17 compressor 4
9 16
13
10 1 1 11 12 1 12 11 10
15
14 17
Fig. 3.c.b
Key: 1
1 3 2 3
1 condenser fan overload
2 fan
3 condenser probe 1 and 2 2
4 flow switch
5 outlet temperature probe
6 evaporator 1 and 2 4
7 outlet evaporator probe 1 and 2
8 antifreeze heater 1 and 2 5
9 compressor 1
10 high pressure 1 and 2
11 compressor overload 1 and 2
12 low pressure 1and 2
13 inlet evaporator probe
7 1 7
2
14 compressor 2
15 water pump
16 compressor 3
17 compressor 4 6
1 8 1 2 8 6 2
9 16
13
10 1 1 11 12 1 2 12 11 2 10 2
15
14 17
Fig. 3.c.c
Key: 1
1 condenser fan overload 2
2 fan
3 sonda condensatore
4 flow switch 3
5 outlet evaporator probe
6 evaporator
7 antifreeze heater 4
8 inlet evaporator probe
9 compressor 1
10 high pressure
11 compressor overload 5
12 low pressure
13 water pump
14 compressor 2
6
7
10 11 12 13
14
Fig. 3.d.a
ENGLISH
1 1 1 2
Key:
1 2 4 2 2 1 condenser fan overload 1 and 2
2 fan 1 and 2
3 condenseer probe 1 and 2
1 3 5 2 3 4 flow switch
5 outlet temperature probe
6 evaporator 1 and 2
7 outlet evaporator probe 1 and 2
7 1 8 antifreeze heater 1 and 2
9 compressor 1
7 10 high pressure 1 and 2
2
11 compressor overload 1 and 2
6 6 12 low pressure 1 and 2
1 2
13 inlet evaporator probe
16 8 1 2 8 16 2
14 compressor 2
1 15 water pump
16 reversing valve 1 and 2
17 compressor 3
18 compressor 4
13
9 17
10 1 1 11 12 1 2 12 11 2 10 2
15
14 18
Fig. 3.d.b
1 3 2 3 Key:
1
1 condenser fan overload
2 fan
2 3 condenser probe 1 and 2
4 flow switch
5 outlet temperature probe
4 6 evaporator 1 and 2
7 outlet evaporator probe 1 and 2
5 8 antifreeze heater 1 and 2
9 compressor 1
10 hih pressure 1 and 2
11 compressor overload 1 and 2
12 low pressure 1 and 2
7 1 13 inlet evaporator probe
2 7 14 compressor 2
15 water pump
1 6 6 16 reversing valve 1 and 2
2 17 compressor 3
8 8 16 18 compressor 4
16 1 1 2 2
13
9 17
15
10 1 1 11 12 1 2 12 11 2 10 2
18
14
Fig. 3.d.c
Key:
1 water condensing temperature probe 3
2 condensator
3 flow switch
4 outlet evaporator probe 1 4
5 evaporator
6 antifreeze heater
7 inlet evaporator probe
8 compressor 1
9 high pressure 2
10 compressor overload
11 low pressure 6
12 water pump 5
13 compressor 2
7
8
9 10 11 12
13
Fig. 3.e.a
Key:
1 water condensing temperature probe
1 and 2
2 condensator 1 and 2 3
3 flow switch
4 outlet evaporator probe 4
5 evaporator 1 1 1 2
6 antifreeze heater 1 and 2
7 compressor 1
8 high pressure 1 and 2
9 compressor overload 1 and 2
10 low pressure 1 and 2 2 1 2
2
11 inlet evaporator probe
12 water pump
13 compressor 2 6
14 compressor 3
15 compressor 4 5
7 14
11
8 1 1 9 10 1 2 10 9 2 8 2
12
13 15
12
Fig. 3.e.b
ENGLISH
Key:
3 1 water condensing temperature probe
1 and 2
4 2 condensator 1 and 2
3 flow switch
4 outlet temperature probe
1 1 1 2 5 outlet evaporator probe 1 and 2
5 1 6 antifreeze heater 1 and 2
5 7 evaporator
2
8 water pump
2 9 compressor 1
2 1
2 10 high pressure 1 and 2
11 compressor overload 1 and 2
7 6 1 2 6 7 12 low pressure 1 and 2
1 2 13 compressor 3
14 compressor 2
15 compressor 4
16 inlet evaporator pressure
9 13
16
10 1 1 11 12 1 2 12 11 2 10 2
8
14 15
Fig. 3.e.c
3
Key:
1 condenser probe
1 2 condenser
4
3 flow switch
4 outlet evaporator probe
5 antifreeze heater
2 6 reversing valve
5 7 inlet evaporator probe
8 compressor 1
9 high pressure
10 compressor overload
11 low pressure
12 water pump
6 13 compressor 2
7
8 12
9 10 11
13
Fig. 3.f.a
Key:
3
1 water condensing temperature probe
1 and 2
2 condensator 1 and 2 4
3 flow switch
4 outlet evaporator probe
1 1 5 1
5 outlet evaporator probe 1 and 2 1 2
6 evaporator 1 and 2 5
7 antifreeze heater 1 and 2 2
8 water pump 2 2
9 compressor 1 2 1
9 15
8
10 1 1 11 12 1 2 12 11 2 10 2
14 17
Fig. 3.f.b
Key:
3
1 condenser probe 1 and 2
2 condenser 1 and 2 4
3 flow switch 1 1
1 2
4 outlet evaporator probe
5 evaporator
6 antifreeze heater 1 and 2
7 compressor 1 2 1 2
2
8 high pressure 1 and 2
9 compressor overload 1 and 2
10 low pressure 1 and 2 6 1
5 6 2
11 inlet evaporator probe
12 water pump
13 compressor 2 1 2
7 15
8 1 1 9 10 1 2 10 9 2 8 2
12
13 16
12
Fig. 3.f.c
ENGLISH
1 2 Key:
1 external
2 internal
3 3 reversing valve
4 4 flow switch
5 outlet evaporator probe
5 6 antifreeze heater
7 evaporator
8 condenser
8 9 condenser probe
7 10 compressor 1
6 11 high pressure
12 compressor overload
13 low pressure
10 14 water pump
9 15 compressor 2
11 12 13
14
15
1 2
Fig. 3.g.a
1 2
3
Key:
4 5 1 external
2 internal
6 3 reversing valve 1 and 2
4 condenser probe
5 flow switch
6 outlet evaporator probe
9 7 condenser probe 1 and 2
7 1
9 7
1 2 2 8 condenser 1 and 2
9 outlet evaporator probe 1 and 2
8 8 10 antifreeze heater 1 and 2
1 2 11 evaporator 1 and 2
1 11 10 1 10 2 11 2 12 compressor 1
13 high pressure 1 and 2
14 compressor overload 1 and 2
15 low pressure 1 and 2
12 16 16 compressor 3
17 inlet evaporator probe
17 18 water pump
19 compressor 2
13 14 15 15 14 13 20 compressor 4
1 1 1 2 2 2
18
18
19 3 20
1 2
Fig. 3.g.b
1 2
Key: 3
1 external
2 internal
3 reversing valve 1 and 2 4
4 condenser probe 5
5 flow switch
6 outlet evaporator probe 6
7 condenser probe 1 and 2
8 condenser 1 and 2
9 outlet evaporator probe 1 and 2 7 7
10 antifreeze heater 1 and 2 1 2
11 evaporator 1 and 2
12 compressor 1 8 1
8
13 high pressure 1 and 2 2
14 compressor overload 1 and 2
15 low pressure 1 and 2 9 1 2 9
16 compressor 3 10
17 inlet evaporator probe
18 water pump
19 compressor 2 12 16
20 compressor 4
11
13 1 14 1 15 1
17 15 14 13
2 2 2
18 17 19
3
1 2
Fig. 3.g.c
1
Key:
1 condenser fan overload 2
2 fan
3 condenser probe
4 compressor 1 3
5 high pressure
6 compressor overload
7 low pressure
8 compressor 2
5 6 7
Fig. 3.h.a
ENGLISH
1 1 Key:
1 condenser fan overload
2 2 2 fan
3 condenser probe
3 3 4 compressor 1
5 high pressure 1 and 2
6 compressor overload 1 and 2
7 low pressure 1 and 2
8 compressor 2
9 compressor 3
10 compressor 4
4 9
5 1 1 6 7 1 5 2 2 6 7 2
8 10
Fig. 3.h.b
1
2
Key:
3 1 condenser fan overload
2 fan
3 condenser probe
4 compressor 1
5 high pressure
6 compressor overload
7 low pressure
8 compressor 2
9 reversing valve
5 6 7
Fig. 3.i.a
Key:
1 condenser fan overload
2 fan 1
3 condenser probe
4 compressor 1
5 high pressure 1 and 2
6 compressor overload 1 and 2 2
7 low pressure 1 and 2
8 compressor 2 3 3
9 compressor 3
10 compressor 4
11 reversing valve
11 11
4 9
5 1 1 6 7 1 5 2 2 6 7 2
8 10
Fig. 3.i.b
Key:
1 flow switch
1
2 water cond. temperature probe
3 condenser
4 compressor 1 2
5 high pressure
6 compressor overload
7 low pressure
8 compressor 2
3 11
5 1 6 7
Fig. 3.j.a
ENGLISH
1
Key:
B7 1 flow switch
2 water cond. temperature probe
2 2 3 condenser
4 compressor 1
5 high pressure
6 compressor overload
7 lw pressure
3 3 8 compressor 2
9 compressor 3
10 compressor 4
11 water pump
4 9
5 1 1 6 7 1 5 2 2 6 7 2
8 10
11
Fig. 3.j.b
Key:
1 condenser probe
1 2 2 condenser
3 antifreeze heater
4 compressor 1
5 high pressure
6 compressor overload
7 low pressure
3 8 compressor 2
9 reversing valve
5 6 7
Fig. 3.k.a
Key:
1 condenser probe
2 condenser 1 and 2
3 antifreeze heater 1 and 2 1 2 1 2
1 2
4 reversing valve
5 compressor 1
6 high pressure 1 and 2
7 compressor overload 1 and 2
8 low pressure 1 and 2 3 1 3 2
9 compressor 3
10 compressor 2
11 compressor 4
12 water pump 4 4
5 9
12 12
6 1 1 7 8 1
6 2 2 7 8 2
10 11
Fig. 3.k.b
3 1
1 3 2
4
Key:
1 condenser fan overload
2 fan
3 condernser probe 1 and 2
4 supply probe
5 electrical heater 1 e 2
6 evaporator 1 e 2 19
7 supply fan overload
8 supply fan
9 compressor 1
10 high pressure 1 and 2
11 compressor overload 1 and 2
12 low pressure 1 and 2 5 1 2 5
13 ambient probe
14 compressor 2 1 6 6 2
15 reversing valve 1and 2
16 compressor 3 15 1 2 15
17 compressor 4 7 7
18 freecooling/freeheating damper
19 enable humidifier
9 8
16
13
10 1 1 11 12 1 2 12 11 2 10 2
14 17
18
Fig. 3.k.l
ENGLISH
4.1 General parameters
The parameters are divided into 4 different types, according to their level of access by the user
(password) and their function.
For each level, only the access to the parameters of the same or lower level can be set.
This means that through “factory” password, acessing the menù “levels” (L-P), it is possible to set
the desired level for each parameter.
• Factory parameters: Accessible with the 66 “Factory” password, allow the configuration of all
the unit parameters.
• Super User parameters: Accessible with the 11 “Super User” password, allow the
configuration of the Super User, User and Direct parameters.
• User parameters: Accessible with password 22, allow the configuration of the parameters
that typically can be set by the user (User parameters) and the Direct parameters, consequently
relating to the options.
• Direct parameters: Accessible without password, this are used to read the probe
measurements and any data, by any user, without compromising the operation of the unit.
N.B.: The modifications to the parameters regarding the configuration of the unit (type, number level level name password
of compressors,...) must be performed with the controller in Standby. _d_ direct no password
_U_ user 22
_S_ super user 11
_F_ factory 66
4.2 Menu structure
main menù
F or 5”
parameters F-r*
parameters A*
software probe settings
antifreeze
t* parameters
probes
parameters r*
regulation
parameters c*
parameters P* compressor
alarm
parameters D*
parameters H*
defrost
unit setting parameters F*
Or
parameters F1
parameters Fn
Fig. 4.a
2
μC SE - +030220426 - rel. 2.5 - 27.11.2012 25
4.3 Parameter tables
The following tables show of the parameters divided by type/family (e. g. compressor, probes,
fans etc.).
ENGLISH
ENGLISH
A01 Alarm set point antifreeze/low ambient temperature (air/air) U A07 A04 °C/°F 0.1 30 - 11 (R/W) 11 Analog
A02 Differential for antifreeze/low ambient temperature alarm (air/air) U 3 1220 °C °F 0.1 50 - 12 (R/W) 12 Analog
A03 Bypass time for antifreeze alarm/low ambient temp. when turning on U 0 150 s 1 0 - 22 (R/W) 229 Integer
the unit in heating mode
A04 Set point for the activation of antifreeze heater/auxiliary heater U A01 r16 °C/°F 0.1 50 AA 13 (R/W) 13 Analog
A04 Antifreeze/support heater set point differential U 0 200 °C/°F 0.1 70 AR 77 (R/W) 77 Analog
A05 Diff. for antifreeze heater/auxiliary heater U 3 500 °C/°F 0.1 10 - 14 (R/W) 14 Analog
A06 Antifreeze heater/auxiliary heater probe F 0 1 Flag 1 0 - 6 (R/W) 6 Digital
0= Control probe see (see Table 5.a)
1= Antifreeze probe see (see Table 5.a)
A07 Antifreeze alarm set point limit F -400 1760 °C °F 0.1 -400 - 15 (R/W) 15 Analog
A08 Auxiliary heater set point in heating mode U A01 r16 °C °F 0.1 250 AA 16 (R/W) 16 Analog
A08 Antifreeze/support heater set point differential U 0 200 °C °F 0.1 70 AR 78 (R/W) 78 Analog
A09 Auxiliary heater differential in heating mode U 3 500 °C/°F 0.1 30 - 17 (R/W) 17 Analog
A10 Antifreeze automatic start up U 0 3 1 0 - 23 (R/W) 230 Integer
0= disabled function
1= Heaters and pump on at the same time on A4/A8
2= Heaters and pump on indipendently on A4/A8
3= Heaters ON on A4/A8
A11 Auxiliary heater 2 set point in heating U A01 r16 °C/°F 0.1 250 AA 67 (R/W) 67 Analog
A11 Support heater 2 differential in heating U 0 200 °C/°F 0.1 70 AR 79 (R/W) 79 Analog
A12 T diff. set point for dirty filters (air/air) U 0 1760 °C/°F 0.1 150 - 57 (R/W) 57 Analog
A13 Outlet limit set point in freecooling conditions U A07 r16 °C/°F 0.1 30 - 80 (R/W) 80 Analog
A14 Antifreeze alarm set point from EVD U A07 A04 °C/°F 0.1 30 - 82 (R/W) 82 Analog
Table 4.c
4.3.4 Probe reading parameters (b*)
display parameter and description default min. max. U.O.M. variat. default visibility supervis. Modbus variable
indicat. level variable type
b00 Config. of probe to be shown on the display U 0 11 N 1 0 - 24 (R/W) 231 integer
0= probe B1 1= probe B2
2= probe B3 3= probe B4
4= probe B5 5= probe B6
6= probe B7 7= probe B8
8= set point without compensation
9= dynamic set point with possible compensation
10= remote ON/OFF digital input status
11= μAD probe
b01 Value read by probe B1 D 0 0 °C /°F - 0 - 102 (R) 102 Analog
b02 Value read by probe B2 D 0 0 °C /°F - 0 - 103 (R) 103 Analog
b03 Value read by probe B3 D 0 0 °C /°F - 0 - 104 (R) 104 Analog
b04 Value read by probe B4 D 0 0 °C /°F/ - 0 - 105 (R) 105 Analog
Dbar
b05 Value read by probe B5 D 0 0 °C /°F - 0 X 106 (R) 106 Analog
b06 Value read by probe B6 D 0 0 °C /°F - 0 X 107 (R) 107 Analog
b07 Value read by probe B7 D 0 0 °C /°F - 0 X 108 (R) 108 Analog
b08 Value read by probe B8 D 0 0 °C /°F/ - 0 X 109 (R) 109 Analog
Dbar
b09 Driver 1 evaporator temperature D 0 0 °C /°F - 0 V 110 (R) 110 Analog
b10 Driver 1 evaporator pressure D 0 0 Dbar - 0 V 111 (R) 111 Analog
b11 Driver 1 superheating D 0 0 °C /°F - 0 V 112 (R) 112 Analog
b12 Driver 1 saturation temperature D 0 0 °C /°F - 0 V 113 (R) 113 Analog
b13 Driver 1 valve position D 0 1000 % - 0 V 114 (R) 114 Analog
b14 Driver 2 evaporator temperature D 0 0 °C /°F - 0 XV 115 (R) 115 Analog
b15 Driver 2 evaporator pressure D 0 0 Dbar - 0 XV 116 (R) 116 Analog
b16 Driver 2 superheating D 0 0 °C /°F - 0 XV 117 (R) 117 Analog
b17 Driver 2 saturation temperature D 0 0 °C /°F - 0 XV 118 (R) 118 Analog
b18 Driver 2 valve position D 0 1000 % - 0 XV 119 (R) 119 Analog
b19 Temp. probe at the outlet of the external coil c1 D 0 0 °C /°F - 0 V 120 (R) 120 Analog
b20 Temp. probe at the outlet of the external coil c12 D 0 0 °C /°F - 0 XV 121 (R) 121 Analog
b21 Terminal probe (for μAD terminal) D -400 800 °C /°F 0.1 0 - 128 (R/W) 128 Analog
Table 4.d
4.3.5 Compressor setting parameters (c*)
display parameter and description default min. max. U.O.M. variat. def. visib. supervis. Modbus variabile
indicat. level variable type
c01 Minimum on time U 0 999 s 1 60 - 25 (R/W) 232 Integer
c02 Minimum off time U 0 999 s 1 60 - 26 (R/W) 233 Integer
c03 Delay between 2 starts of the same compressor U 0 999 s 1 360 - 27 (R/W) 234 Integer
c04 Delay between starts of the 2 compressors U 0 999 s 1 10 - 28 (R/W) 235 Integer
c05 Delay between 2 shut-downs of the 2 compressors U 0 999 s 1 0 - 29 (R/W) 236 Integer
c06 Delay at start-up U 0 999 s 1 0 - 30 (R/W) 237 Integer
c07 Delay in switching on the compressor after switching on the U 0 999 s 1 20 - 31 (R/W) 238 Integer
pump/inlet fan (air/air)
c08 Delay in switching OFF the compressor after switching OFF the U 0 150 min 1 1 - 32 (R/W) 239 Integer
pump/inlet fan (air/air)
c09 Maximum compressor operating time in tandem U 0 60 min 1 0 - 33 (R/W) 240 Integer
c10 Compressor 1 timer D 0 8000 100 hours - 0 - 122 (R) 122 Analog
c11 Compressor 2 timer D 0 8000 100 hours - 0 - 123 (R) 123 Analog
c12 Compressor 3 timer D 0 8000 100 hours - 0 - 124 (R) 124 Analog
c13 Compressor 4 timer D 0 8000 100 hours - 0 - 125 (R) 125 Analog
c14 Operation timer threshold U 0 100 100 hours 1 0 - 34 (R/W) 241 Integer
c15 Hour counter evaporator pump/fan 1 D 0 8000 100 hours - 0 - 126 (R) 126 Analog
c16 Hour counter condenser backup pump/fan 2 D 0 8000 100 hours - 0 - 127 (R) 127 Analog
c17 Minimum time between 2 pump starts U 0 150 min 1 30 - 35 (R/W) 242 Integer
c18 Minimum pump ON time U 0 15 min 1 3 - 36 (R/W) 243 Integer
c19 Delay between valve and compressor U 0 100 s 1 3 - 125(R/W) 332 Integer
Table 4.e
ENGLISH
H01 Unit model F 0 11 Flag 1 2 - 54 (R/W) 261 Integer
0= air_air unit
1= air_air heat pump
2= air_water chiller
3= air_water heat pump
4= water_water chiller
5= water_water heat pump with reversal on gas circuit
6= water_water heat pump with reversal on water circuit
7= condensing unit
8= reverse-cycle condensing unit
9= water-cooled condensing unit
10= reverse-cycle water-cooled condensing unit
11= cooling only air-air unit with electric heaters
H02 Number of condensers U 0 1 Flag 1 0 F 12 (R/W) 12 Digital
0=1 circuit
1=2 circuits
H03 Number of evaporators F 0 1 Flag 1 0 - 13 (R/W) 13 Digital
0=1 evaporator
1=2 evaporators
H04 Number of compressors per circuit F 0 5 Flag 1 0 - 55 (R/W) 262 Integer
0=1 comp. ON 1 circuit (single circuit)
1=2 comp. in tandem ON 1 circuit (single circuit)
2=1 comp. per circuit, 2 circuits (two circuits)
3=2 comp. in Tandem, 2 circuits (two circuits)
4=1 compressor and 1 Capacity step in one circuit
5=1 compressor and 1 capacity Step per circuit
H05 Pump/outlet fan (Air/Air) mode (output N2) F 0 5 Flag 1 1 - 56 (R/W) 263 Integer
0= absent
1= always ON
2= ON upon request of the controller
3= ON upon request of the controller and for set time
4= follow hot keep or hot start in heating, always on in cooling
5= follow hot keep or hot start in heating, follow the comp. in
cooling
H06 Cooling/Heating digital input U 0 1 Flag 1 0 - 14 (R/W) 14 Digital
0= absent
1= present
H07 ON/OFF digital input U 0 1 Flag 1 0 - 15 (R/W) 15 Digital
0= absent
1= present
H08 μC2SE network configuration F 0 3 Flag 1 0 - 57 (R/W) 264 Integer
0= μC2SE only
1= μC2SE + valve
2= μC2SE + exp.
3= μC2SE + exp. + valve1 + valve2
4= μC2SE + exp. + valve1
H09 Keypad qualification U 0 1 Flag 1 1 - 16 (R/W) 16 Digital
0= disabled keypad
1= enabled keypad
H10 Serial address U 1 200 - - 1 - 58 (R/W) 265 Integer
0= future use as terminal
H11 Output modes (see pag. 46) F 0 12 Int 1 0 - 59 (R/W) 266 Integer
H12 Capacity-control and reversing valve logic F 0 3 Flag 1 1 - 60 (R/W) 267 Integer
0= Both normally closed
1= Both normally open
2= Inversion valve normally open and capacity-control valve normally
closed
3= Inversion valve normally closed and capacity-control valve
normally open
H13 Activate pump down F 0 1 - 1 0 V 17 (R/W) 17 Digital
H14 Minimum pump down pressure F 0 500 Dbar 0.1 20 M 37(R/W) 37 Analog
H15 Maximum pump down time F 0 180 s 1 30 M 61 (R/W) 268 Integer
H16 Activate autotuning F 0 1 Flag 1 0 - 22 (R/W) 22 Digital
H17 Minimum DTE value allowed F 0.0 1760 °C/°F 0.1 0 - 68 (R/W) 68 Analog
H18 Maximum DTE value allowed F 0.0 1760 °C/°F 0.1 800 - 69 (R/W) 69 Analog
H19 Maximum DTC value allowed F 0.0 1760 °C/°F 0.1 800 - 70 (R/W) 70 Analog
H21 Second pump function F 0 4 int 1 0 - 62 (R/W) 269 Integer
0= Disabled
1= Backup and weekly rotation
2= Backup and daily rotation
3= Condensing control on corresponding set point
4= Condensing control always on
H22 Disable load default values F 0 1 Flag 1 0 - 18 (R/W) 18 Digital
0= Function disabled
1= Function enabled
H23 Enable Modbus® F 0 1 Flag 1 0 - 11 (R/W) 11 Digital
Table 4.h
ENGLISH
r01 Cooling set point D r13 r14 °C/°F 0.1 12.0 - 41 (R/W) 41 Analog
r02 Cooling differential D 3 500 °C/°F 0.1 30 - 42 (R/W) 42 Analog
r03 Heating set point D r15 r16 °C/°F 0.1 400 - 43 (R/W) 43 Analog
r04 Heating differential D 3 500 °C/°F 0.1 30 - 44 (R/W) 44 Analog
r05 Compressor rotation F 0 3 Flag 1 0 - 78 (R/W) 285 Integer
0= disabled;
1= FIFO type
2= hour control
3= direct relation between (D.I. and compressors D.O.)
r06 Type of compressor control F 0 4 Flag 1 0 - 79 (R/W) 286 Integer
0= proportional on inlet
1= proportional on inlet + dead zone
2= proportional on outlet
3= proportional on outlet + dead zone
4= time on outlet with dead zone
r07 Dead zone differential F 1 500 °C/°F 0.1 20 - 45 (R/W) 45 Analog
r08 Maximum control output activation time F 0 999 s 1 120 - 80 (R/W) 287 Integer
r09 Minimum control output activation time F 0 999 s 1 100 - 81 (R/W) 288 Integer
r10 Maximum control output deactivation time F 0 999 s 1 120 - 82 (R/W) 289 Integer
r11 Minimum control output deactivation time F 0 999 s 1 100 - 83 (R/W) 290 Integer
r12 Compressor deactivation differential F 0 500 °C/°F 0.1 20 - 46 (R/W) 46 Analog
r13 Minimum set point in Cooling U -400 r14 °C/°F 0.1 -400 - 47 (R/W) 47 Analog
r14 Max. Cooling set point U r13 1760 °C/°F 0.1 800 - 48 (R/W) 48 Analog
r15 Min. Heating set point U -400 r16 °C/°F 0.1 -400 - 49 (R/W) 49 Analog
r16 Max. Heating set point U r15 1760 °C/°F 0.1 800 - 50 (R/W) 50 Analog
r17 Cooling compensation constant U -50 50 - 0.1 0 - 51 (R/W) 51 Analog
r18 Maximum distance from the set point U 3 200 °C/°F 0.1 3 - 52 (R/W) 52 Analog
r19 Start compensation temperature in cooling mode U -400 1760 °C/°F 0.1 300 - 53 (R/W) 53 Analog
r20 Start compensation temperature in heating mode U -400 1760 °C/°F 0.1 0 - 54 (R/W) 54 Analog
r21 Second cooling set point from external contact D r13 r14 °C/°F 0.1 120 - 55 (R/W) 55 Analog
r22 Second heating set point from external contact D r15 r16 °C/°F 0.1 400 - 56 (R/W) 56 Analog
r23 Select automatic changeover probe D 0 8 Flag 1 0 - 84 (R/W) 291 Integer
r24 Automatic changeover set point D r15 r16 °C/°F 0.1 400 - 61(R/W) 61 Analog
r25 Outside temp set point to stop compressors D -400 800 °C/°F 0.1 -400 - 65 (R/W) 65 Analog
r26 Cooling set point in dehumidification D r13 r14 °C/°F 0.1 120 - 66 (R/W) 66 Analog
r27 Enable accumulation vessel suppression F 0 3 Flag 1 0 - 88 (R/W) 295 Integer
0= Disabled
1= Enabled in cool
2= Enabled in Heat
3= Always enabled
r28 Min. compressor running time for low load/damper travel time F 0 999 s 1 60 - 89 (R/W) 296 Integer
r29 Chiller low load differential/freecooling differential F 10 500 °C/°F 0.1 30 - 58 (R/W) 58 Analog
r30 Heat pump low load differential/freeheating differential F 10 500 °C/°F 0.1 30 - 59 (R/W) 59 Analog
r31 Heating compensation constant U -50 50 - 0.1 0 - 60 (R/W) 60 Analog
r32 Hot Start set point D r15 r16 °C/°F 0.1 120 - 71(R/W) 71 Analog
r33 Hot Start differential F 3 500 °C/°F 0.1 30 - 72 (R/W) 72 Analog
r34 Enable Freecooling/Freeheating F 0 12 Flag 1 0 - 116 323 Integer
0= disabled (R/W)
1= freecooling / without compressors / cooling only
2= freecooling / with compressors / cooling only
3= freeheating / without compressors / heating only
4= freeheating / with compressors / heating only
5= freecooling and freeheating / without compressors / freecooling
cooling only and freeheating heating only
6= freecooling and freeheating / with compressors / freecooling cooling
only and freeheating heating only
7= freecooling / without compressors / always
8= freecooling / with compressors / always
9= freeheating / without compressors / always
10= freeheating / with compressors / always
11= freecooling and freeheating / without compressors / always
12= freecooling and freeheating / with compressors / always
r35 Compressor deactivation time with freecooling/freeheating active F 0 999 s 1 240 - 117 324 Integer
(R/W)
r36 Maximum damper operating time F 0 600 s 1 20 - 118 325 Integer
(R/W)
r37 Damper opening duty cycle differential F 03 500 °C/°F 0.1 30 - 73 (R/W) 73 Analog
r38 Damper closing duty cycle differential F 03 500 °C/°F 0.1 30 - 74 (R/W) 74 Analog
r39 Autotuning correction coefficient F 11 30 - 0.1 13 - 75 (R/W) 75 Analog
r40 Indicates when to operate minimum damper opening F 0 7 - 1 0 - 119 326 Integer
0= never (R/W)
1= only in freecooling
2= only in freeheating
3= in freecooling and in freeheating
4= only if the freecooling and freeheating conditions end
5= only if the freeheating conditions are not present
6= only if the freecooling conditions are not present
7= always
r41 Minimum damper opening F 0 100 % 1 0 - 120 327 Integer
(R/W)
r42 Freecooling operating threshold with compressors disabled. U A07 1760 °C/°F 0.1 50 - 81 (R/W) 81 Analog
r43 Heater set point F 0 3 - 1 0 - 121 328 Integer
0= A4, A8 and A11 absolute values (R/W)
1= A4 absolute value, A8 and A11 values relative to the set point
2= A4 value relative to the set point, A8 and A11 absolute values
3= A4, A8 and A11 values relative to the set point
r44 Inactivity time in Freecooling control F 0 240 - 1 5 - 123 330 Integer
(R/W)
Table 4.k
ENGLISH
bit3= enable dehumidification
bit4= enable humidification
bit5= terminal probe alarm
bit6= activate boiler output
bit7= 0= process mode active; 1= process mode
disabled
- Signals to the μAD D 0 255 - 0 136 (R) 343 Integer
bit0= cool/heat request from uAD in progress
bit1= cool/heat request accepted from μAD (1= cooling;
0= heating)
bit2= start fans
bit3= alarm active on μCH
bit4= RTC available on μCH2 SE
- DTE value saved in EEPROM D 0 0 - 0 98 (R) 98 Analog
- Internal set point compensated in the event of D 0 0 - 0 97 (R) 97 Analog
autotuning
- Ambient set point (from μAD) D -400 1760 0,1 0 95 (R/W) 95 Analog
- Set point variation from μAM (μedronic) D -100 100 0,1 0 96 (R/W) 96 Analog
- Differential for the ambient set point D -100 100 0,1 0 94 (R/W) 94 Analog
- Controls by the μAD from save D 0 32767 1 0 - 137 (R/W) 344 Integer
- “Active alarm signal: D 0 32767 1 0 - 128 (R/W) 335 Integer
bit0= probe alarm (E1,E2,E,E4,E5,E6,E7,E8)
bit1= high pressure alarm (HP1, HP2)
bit2= low pressure alarm (LP1, LP2)
bit3= flow switch alarm (FL)
bit4= expansion communication alarm (ESP)
bit5= EE2PROM alarm (EPB)
bit6= antifreeze alarm (A1, A2)
bit7= thermal overload alarm (TP, TP1, TP2)
bit8= hour counter alarm (H1, H2, H, H4)”
- Terminal humidity probe (per terminal μAD) D 0 1000 % 0,1 0 129 (R/W) 129 Analog
- Reset alarms D 0 1 1 0 78 (R/W) 78 Digital
- Digital input B D 0 1 - 0 79 (R) 79 Digital
- Set-point Forced D -400 1760 °C/°F 0,1 -400 130 (R/W) 130 Analog
- Differential room D -100 100 °C/°F 0,5 20 131 (R/W) 131 Analog
Table 4.m
If probe B2 is placed in the outlet air flow (air/air units), A01 becomes the outlet limit, and if the
ON
outlet probe reading (B2) < outlet limit (A1) then:
1. bypass waiting time A3;
2. stop the compressors; if already off go to pt. 4; OFF
A1 A1+A2 2
3. bypass waiting time A3;
4. close damper with 50% duty cycle if FC active and the ambient temperature means damper open Fig. 5.a.a
or dead zone. If FC is not active go to pt. 6;
5. bypass waiting time A3 after having closed r28 twice (from the end of the last period); Key:
6. If B2 < A1 the alarm “A1” is activated. The alarm reset depends on P5. 1. freecooling or comp 2. probe B2
2
34 μC SE - +030220426 - rel. 2.5 - 27.11.2012
- Antifreeze/low room temperature (air/air) alarm differential
A02: This represents the differential for the activation of the antifreeze alarm (low room
temperature in air/air units); the alarm condition cannot be reset until the temperature exceeds
ENGLISH
the set point + differential (A01+A02 or A14+A02).
- Antifreeze alarm bypass time low room temperature from unit start in heating mode
A03: This represents the delay in the activation of the antifreeze alarm when starting the system.
In the case of air/air units, this parameter represents the delay time for the low room temperature
(return-intake air) signal, only in heating mode. This means that the room being heated is too cold
(threshold set by the user).
- Antifreeze heater/auxiliary heater set point in cooling
A04: Determines the threshold below which the antifreeze heater is switched on. In the air/air
units (H01=0, 1) this parameter represents the temperature value below which the auxiliary heater
is activated. This temperature is compensated according to the following equation:
Set_heaters (cooling)= A04+(Compensated set point – Set point set)
In the air/air heat pumps (H01=1) the auxiliary heaters are not used in cooling mode.
N.B. The antifreeze set points are not compensated.
• antifreeze alarm A01 (remains active even at the end of the special operation if the unit was
previously ON, deactivated by manual reset or in standby).
A10=3: heaters ON based on the respective set point A04 and A08.
Do not use with H1= 6
- Antifreeze heater 2 set point in defrost/auxiliary in heating
A11: Heater 2 set point in heating, the control of the auxiliary heaters has been separated, each
having its own activation set point (see A08).
- Dirty filter signal set point (air/air units only)
A12: Set point for the dirty filter signal based on B1-B2, the deactivation differential is A05
• Valid in the following conditions:
• air-air units;
• B1 is configured;
• outlet limit active;
• freecooling not active;
• at least 1 compressor ON.
The warning is reset automatically in the following conditions:
• air-air units;
• B1 is configured;
• outlet limit active;
• freecooling not active.
- Outlet limit set point in freecooling conditions
A13: With freecooling active, and only when the compressors are off, this represents the outlet
limit. When the compressors are on, even if freecooling is active, the outlet limit alarm is bypassed
and the antifreeze alarm is used.
- Antifreeze alarm set point from EVD
A14: With the EVD connected in the tLAN, A14 represents the evaporation temperature (sent by
the EVD) below which the antifreeze alarm is activated; when the alarm is active, the compressors
in the circuit affected are switched off, while the pump remains on to reduce the possibility of
freezing. Manual reset (or automatic, depending on parameter P05), only occurs when the water
temperature returns within the operating limits (that it, exceeds A14+A02
• Probe readings: parameters (B*)
- Select probe to be shown on display.
b00: Sets the probe reading to be displayed.
0= probe B1
1= probe B2
2= probe B3
3= probe B4
4= probe B5
5= probe B6
6= probe B7
7= probe B8
8= set point without compensation
9= dynamic set point with possible compensation
10= remote ON/OFF digital input status
For the list of parameter-probe associations see Table 4.d ON
Note: probes that are not present cannot be selected. 1
OFF
• Compressor settings: parameters (c*) t
- Minimum ON time ON
c01: This establishes the time that the compressor must remain ON for when started, even if the 2
OFF
stop signal is sent. C2 t
Key: 3
1. signal; 3
2. compressor;
Fig. 5.a.d
3. min. OFF time-interval.
- Delay between 2 starts of the compressor
ON
c03: This sets the minimum time that must elapse between two successive starts of the same
1
compressor (determines the maximum number of starts per hour for the compressor). The OFF
t
compressor LED flashes in this phase. If by mistake the user enters a value lower than the sum of
ON
C01 + C02, this parameter will be ignored and only the times C01 and C02 will be considered.
2
Key: OFF
C2 t
1. signal;
3
2. compressor;
3. min. time-interval between two ON routins. Fig. 5.a.e
36 μC2SE - +030220426 - rel. 2.5 - 27.11.2012
ON
- Start delay between compressors
1 c04: This sets the delay between the starts of the two compressors, so as to reduce the peak
OFF power input and make the compressors start more smoothly. The compressor LED flashes in this
ENGLISH
ON phase.
2
• In the event of capacity control, the delay c04 between compressor and valve becomes c04/2;
OFF
ON
• In the event of defrost operation, the delay between compressor and compressor is 3 seconds,
3 and between compressor and valve is 2 seconds.
OFF
ON Key:
4
1. 1st signal;
OFF
C4 2. 2nd signal;
5 3. 1st compressore;
4. 2nd compressor;
Fig. 5.a.f 5. time delay between two compressors ON routines/time-delay of the capacity-controlled
routine.
ON
1
OFF
ON - Stop delay between compressors
2 c05: This sets the stop delay between the compressors.
OFF
ON
Key:
3
OFF 1. 2nd signal;
ON 2. 1st signal;
4 3. 2nd compressor;
OFF
C5 4. 1st compressore;
5. time delay between two compressors OFF routines/time-delay before the capacity-controlled
5
routine.
Fig. 5.a.g
Pressing and together, when the hour counter is displayed, resets the hour counter and,
consequently, cancels any maintenance requests in progress.
c10= operating hours comp. 1
c11= operating hours comp. 2
c12= operating hours comp. 3
c13= operating hours comp. 4
ENGLISH
d02=1: the defrost starts and ends according to the temperature or pressure thresholds, see d03
and d04;
d02=2: the pressure transducer and temperature probe are both located on the outside
exchanger; the defrost starts when the value read by the pressure transducer is below the
threshold d03 and ends when the value read by the temperature probe is above the threshold
d04; during the defrost, the pressure probe controls the fan speed, as in chiller mode, so as to limit
the pressure, even if the NTC probe, caked by ice, delays the end defrost. In any case, after the
maximum time allowed for the defrost, the unit will always exit the defrost procedure.
d02=3: enable sliding defrost.
In the event of low outside temperatures, the evaporator pressure or temperature may fall below
the threshold set to start the defrost (d03) even if there is effectively no ice on the coil. This can
be corrected by shifting the start of the defrost proportionally to the lowering of the outside
temperature. This procedure can be performed based on the temperature or the pressure alone,
and not combined. It is disabled if the outside compensation probe is not fitted or is broken. It
is performed based on the pressure only if both the pressure probe and temperature probe are
configured.
2 Key:
1. end defrost T/P ;
t
2. start defrostT/P;
7 6 5
3. start defrostT;
4. end defrost;
Fig. 5.a.k 5. min. time-interval to start a def. cycle (d6);
6. min defrost interval (d5);
7. timer reset.
d10= 3: start and end defrost from external contact enabled therefore:
• if the contact of the input is open, the end/start of the defrost is enabled;
• if the contact of the input is closed, the defrost follows the normal procedure.
ENGLISH
- Maximum temperature/pressure differential deviation for defrost
d19: This value is expressed in °C if the compensation is controlled by temperature, or in bar if
controlled by pressure. The value set is subtracted from d03.
0% 0%
F05 F08
2 2
F06 F09
Fig. 5.a.l
1 3 1 3
100 %
F05 F08
F04 F04
F03 F03
0% 0%
2 2
F07 F06 F09 F10
Fig. 5.a.m
F02=3: ON when the corresponding compressor is ON, with speed control. When the
compressors are stopped the corresponding fans are also stopped, irrespective of the condensing
temperature/pressure.
With F02=3 and an NTC condenser probe, when the compressor starts the fans are started at
maximum speed for the time F11, irrespective of the temperature measured.
In the event of a condenser probe fault, the fans will be switched OFF.
the maximum speed must be set. The set value does not correspond to the actual voltage in Volts
applied, but rather to an internal unit of calculation in the μC2SE. If using FCS controllers, set this
parameter to 100.
F04 = Represents the maximum threshold for the triac
ENGLISH
F13 = 1: the fans are ON as in cooling mode, based on the temperature or pressure.
F13 = 2: the fans are OFF until the end defrost temperature or pressure is reached, above which
they are started at maximum speed for the time set for parameter d16. Only at the end of this
time will the cycle return to heat pump mode with the normal management of the fans.
Note: If the unit is running the Fan Defrost function (parameter d17), the fan management
selected by F13 is disabled.
management of the heaters and the antifreeze function is performed only on B2. Vice-versa, with
2 evaporators (H03=1) antifreeze control will be performed using B2 and B6, while input B5 is
used to control the water outlet temperature.
- Number of compressors/circuits
H04: This establishes the number of compressors per circuit and the number of circuits. For
further details see Table 4.g.
- Enable keypad
H09: Used to disable the modification of the DIRECT and USER parameters from the keypad. The
value of the parameters can always be displayed. The enable/disable cooling, heating and reset
counter functions are also available.
Values:
0: keypad disabled
1: keypad enabled (default)
- Serial address
H10: Establishes the address of the instrument for the serial connection, via an optional board, to
a PC for supervision and/or telemaintenance.
ENGLISH
C1 compressor 1 compressor 1 compressor 1 compressor 1 compressor 1 compressor 1
C2 heater 1 heater 1 heater 1 reversing valve 1 reversing valve 1 heater 1
C3 Pump/evaporator (fan) (on Pump/evaporator (fan) (on Pump/evaporator (fan) (on Pump/evaporator (fan) (on evaporator pump Pump/evaporator (fan) (on
air/air units) air/air units) air/air units) air/air units) air/air units)
C4 reversing valve 1 Compressor 2 (or capacity Compressor 2 (or capacity Compressor 2 (or capacity Compressor 2 (or capacity condenser fan 1
control comp. 1) control comp. 1) control comp. 1) control comp. 1)
C5 alarm alarm reversing valve 1 alarm alarm alarm
C6 compressor 2 compressor 3 compressor 3 compressor 3 not used compressor 2
C7 heater 2 heater 2 heater 2 reversing valve 2 heater 1 heater 2
C8 Condenser pump/backup Condenser pump/backup Condenser pump/backup Condenser pump/backup Condenser pump/backup Condenser pump/backup
C9 reversing valve 2 Compressor 4 (or capacity Compressor 4 (or capacity Compressor 4 (or capacity not used condenser fan 2
control comp. 2) control comp. 2) control comp. 2)
C10 Warning Warning reversing valve 2 Warning Warning Warning
associated device
outputs H11= 6 H11= 7 H11= 8 H11= 9 H11= 10 H11= 11 H11= 12
C1 compressor 1 compressor 1 compressor 1 compressor 1 compressor 1 compressor 1 compressor 1
C2 1 step heater 1 step heater 1 step heater compressor 2 compressor 2 compressor 2 P25
C3 outlet fan outlet fan outlet fan outlet fan outlet fan outlet fan P26
C4 reversing valve 1 2 step heater condenser fan 1 reversing valve 1 heating step 1 heating step 1 P27
C5 alarm alarm alarm alarm alarm alarm P28
C6 compressor 3 compressor 3 compressor 3 compressor 3 compressor 3 compressor 3 compressore 3
C7 2 step heater P29 2 step heater compressor 4 P29
C8 open freecooling/ open freecooling open freecooling open freecooling/ open freecooling/ open freecooling/ P30
freeheating freeheating freeheating freeheating
C9 reversing valve 2 humidifier (ON/OFF) condenser fan 2 1 step heater heating step 2 humidifier P31
C10 close freecooling/ close freecooling close freecooling close freecooling/ close freecooling/ close freecooling/ P32
freeheating freeheating freeheating freeheating
Note: in the event of capacity-control, the rotation between compressor and corresponding valve
is disabled. FIFO or time logic can be used between the 2 circuits to optimise the starts or the
operating hours of the 2 compressors (1 per circuit).
With proportional inlet control, the dynamic set point (STD) and the corresponding proportional
band are adapted according to the DTE.
With outlet control and dynamic logic, that is, dead zone and activation/deactivation times, the
dead zone has a dynamic value.
In this case too, control will be optimised according to the actual DTE measured.
ENGLISH
H21= 1: the second pump is used only as a backup.
If the flow switch and corresponding alarm are activated, the pumps are switched over:
• if the alarm passes, a warning is shown on the display and the warning relay is activated, while
the unit continues to operate with the Backup pump. When the next alarm is activated the
pumps will be switched over.
• if the alarm remains active even with the second pump on for longer than the time set for P1,
the generic alarm is generated and the unit is switched OFF.
H21= 2: the second pump represents a backup pump. The two pumps are never used at the
same time but each 24 hours, are switched over. In the event of flow alarms, the logic is the same
as for setting 1. After being switched over due to the flow alarm, the 24-hour timer is set to zero.
H21= 3: the second pump is used as an ON/OFF device in the same way as the condenser fan
(which in this case is not present), in ON/OFF mode, with the same settings (in fact in this case the
pump replaces the fan, including the symbol).
H21= 4: the second pump is used for the condenser but is always ON. In this case the pump
symbol is
not managed.
Note: In the event of flow alarms with automatic reset, 10 attempts are made to restart the pump
every 90 seconds, for a maximum time of P02; after the 10 attempts, the alarm becomes manual
reset. With the second pump, the attempt consists in switching over the pump that is on, with the
same logic.
P05= 0: (default) high pressure, low pressure and antifreeze (low temperature) with manual reset;
P05= 1: all the alarms with automatic reset;
P05= 2: high pressure and antifreeze (low temperature) manual, low pressure automatic;
P05= 3: high pressure manual, low pressure and antifreeze (low temperature) automatic;
P05= 4: high and low pressure manual, antifreeze (low temperature) automatic; *: the high and low pressure alarms are managed in the
P05= 5: high and low pressure manual after the third activation in one hour*, antifreeze (low same way both for the transducers and the pressure
temperature) automatic; switches (digital input); if the unit is in standby the count
P05= 6: high and low pressure manual after the third activation in one hour*, antifreeze (low (3 times in one hour) is reset.
temperature) manual.
- Cooling/Heating logic
P06: If this parameter is set to 1, the operating logic of the Cooling/Heating logic is reversed (from
the keypad, the remote control and the digital input).
Symbol P06= 0 P06= 1
Cooling (Chiller) Heating (heat pump)
Heating (heat pump) Cooling (Chiller)
ENGLISH
- High pressure alarm from transducer set point
P18: Sets the value beyond which the high pressure alarm is generated. Each circuit will be
managed by its own transducer.
P18= 0: the function is disabled.
For all other values greater than 3.0, due to the hysteresis (3 bars), the alarm is managed according
to the set value.
- Low system start-up temperature alarm set point
P19: Represents a threshold for the low temperature (measured by probe B1) alarm, without
hysteresis; it is reset automatically (the alarm relay is not activated and the display shows the
message “ALt”).
- System start-up protection for high/low temperature
P20: If set to 1, this parameter enables the system protection function when starting, both at
power ON and when switching ON from Standby.
In chiller mode (cooling), for values of B1 greater than the set point P19, an alarm is activated and
the unit is not started (display “AHt”).
In heat pump mode (heating), for values lower than the set point P19, an alarm is activated and
the unit is not started (display “ALt”).
The alarm is reset automatically.
P20=0: the function is not enabled.
- Low pressure alarm waiting time in heat pump
P22: Delay in generating the low pressure alarm in heat pump mode
If the pressure remains below 1 bar for the time p22 and the circuit has 2 compressor steps, the
circuit can operate at part load (see P04). This preventive capacity control function remains active
until the pressure rises above F08-F09.
- Low pressure alarm waiting time during defrost
P23: Delay in generating the low pressure alarm in heat pump mode during defrost
- Deactivate compressors in capacity control for HP and LP
P24: Decide which compressor must be stopped in each circuit during capacity control
P24= 0 stops compressors 1 and 3
P24= 1 stops compressors 2 and 4
- Low pressure alarm set point from transducer
P33: : Sets the value beyond which the low pressure alarm is generated when the unit is
operating in heat pump mode. Each circuit will be managed according to its own transducer.
P33= 0 the function is disabled.
- Mute alarm relay using “PRg/mute” button
P35=0 the PRG/mute button does not alter the status of the relay, if the alarm is active and in
progress.
P35=1 the PRG/mute button alters the status of the relay even if the alarm is active and in
progress, as if it were a buzzer or a siren.
- High pressure alarm management
P36: the parameter is used to consider the high pressure alarm even when the compressor is
off or consider it only when the compressor is on, depending on whether the pressure switch is
directly connected to the digital input on the controller or via another circuit.
P36=0: high pressure alarm always considered (pressure switch connected directly to the digital input).
P36=1: high pressure alarm considered 2 seconds after starting the compressor.
• Control settings: parameters (r*)
- Cooling set point
r01: between r13 and r14
r02: cooling differential value of DTE when the unit is first started (autotuning enabled)
- Heating set point (heat pump)
r03: between r15 and r16
r04: heating differential value of DTE when the unit is first started (autotuning enabled)
- Compressor rotation
r05: The rotation of the compressors allows the operating hours to be balanced either statistically,
using FIFO logic, or absolutely, by counting the effective operating hours. Settings:
r05=0: rotation disabled; The customer can use compressors with different power ratings
according to the desired logic or manage the capacity-control functions. The compressors are
started/stopped in proportional mode.
r05=1: rotation with FIFO logic (first ON, first OFF, and vice-versa first OFF, first ON); in this mode
the operating hours are optimised together with the number of starts, even if the compressor
safety times are always respected.
r05=2: rotation with control of operating hours; in this way the compressors will have the same
operating hours, as the compressor with the least operating hours is always started first, again
observing the safety times. This does not however consider FIFO logic and does not optimise the
starts and stops. In the case of capacity controlled compressors (1 per circuit), FIFO logic or timed
operation will refer to the actual circuit and not the compressor valves. If, for example, when capacity
is required from circuit 1, compressor 1 starts first, capacity controlled (not at full capacity), and then
the valve is managed as a second step, so that the compressor will work at maximum efficiency. If
When stopping, the valve is managed first and then the actual compressor as a whole. Both
FIFO logic and timed operation will involve either one circuit or the other. The activation and
deactivation of the valves are not subject to timers, but rather only a hysteresis that is equal to
the set point and the differential of the step (in fact the valve performs the same function as a
hermetic compressor).
r05=3: direct correspondence between the digital inputs and the compressor relays (condensing
units only).
ON
In chiller (cooling) mode, the dead zone moves the cooling proportional band above the set
point by the value r07.
Key Figure 5.b.d:
r06: enable the dead zone (enabled if r06=1 or 3)
r07: dead zone
r03: heating set point
r04: heating differential
OFF
In heat pump (heating) mode, the dead zone moves the heating proportional band below the set
r03-r07-r04 r03-r07-r02/4 r03-r07 r03
point by the value r07.
r03-r07+r04*3/4 r03-r07+r04/4
Outlet temperature control by time r06 = 4 (only chiller) Fig. 5.b.d
This type of control is based on the need to maintain the outlet temperature as constant as
possible, despite the load being variable or the reduced inertia of the system.
The logic has the aim of keeping the temperature inside the dead zone.
If outside the zone, the compressors will be activated with the logic described below, so as to
return inside the dead zone, neither too quickly (using an integral or derivative), nor too slowly,
with fixed time
logic. There are two logical times involved: the activation time and deactivation time.
r08: The value set is used in the control algorithm (see timed outlet temperature control) as the
maximum time (at the start of the differential) for the activation of the compressors.
ENGLISH
- Compressor deactivation differential (if r06 = 4)
r12: This represents the temperature differential for the deactivation of the compressors,
according to the procedure described in “Deactivation time”.
set for the parameter r11 corresponding to the end of the differential for the deactivation of the
compressors, set by the parameter r12.
r01 Below this value, the deactivation time will be equal to the minimum set until reaching the
temperature temperature A04, after which all the compressors will be switched OFF, irrespective of the times.
compressor As the temperature moves away from the set point, the response of the process becomes more
A1 A4 r01-r12
compressor
dynamic.
deactivation time
stop
Fig. 5.b.f
r09
temperature
r03+r07-4 r03+r07 r03
Fig. 5.b.g
r10
deactivation time Deactivation time (heating)
In heating mode, if the temperature rises above the set point, the deactivation time will decrease
time
more the further the temperature moves away from the heating set point r03. At the end of the
differential r12, the time will be the minimum set by parameter r11.
r11
temperature
r03 r03+r12
comp.
deactivation time
Fig. 5.b.h
The changeover is managed differently depending on the type of unit, water source (air/water
Example of changeover for air/water and water/
and water/water) or air/air.
water units
Air/water and water/water units: 1
Changeover is disabled if the selected probe (r23) is not configured or is a pressure probe. When
changeover is enabled, in any cooling/heating inputs are ignored. 3 4
If the acqua terminal is used, set point r24 can be set on the terminal.
During defrost, automatic changeover is disabled. Only when the defrost ends can the operating
mode change. The same is true for the autostart function in antifreeze (see A10).
At power on the controller operates in the previous mode if the probe reading is within the r07 r07 2
hysteresis 24-r07 and 24+r07, otherwise it starts with the new mode. r04 r24 r02
Fig. 5.b.j
If the changeover probe reading is out-of-range the probe alarm is activated and the outputs are
deactivated.
If r07= 0 the differential for reversing the cycle is dictated by the first compressor step differential.
Key:
1. changeover;
2. changeover probe (r23); r07 r07
3. heating; r04 r24 r02
4. cooling. Fig. 5.b.k
Fig. 5.b.l
ENGLISH
The differential remains the same as for chiller mode (r02).
Key: 1 2
1. chiller; on on
2. chiller in low load;
3. heat pump; off off
4. heat pump in low load; r01 r01 + r02 5 r01 r01 + r29 5
5. temperature.
Fig. 5.b.m
3 4
on on
off off
r03 - r04 r03 5 r03 - r30 r03 5
Fig. 5.b.n
Freeheating can be enabled when: outside T - room T > freeheating differential (r30). Fig. 5.b.r
Key to Fig. 5.b.r:
1. out T; Example of freeheating
2. room T;
1
3. out T - f/heat diff ;
4. freeheating ON; 4
100%
5. freeheating OFF
6. time.
The compressors can be used to support freecooling/freeheating if the latter are insufficient to
provide for the thermal load. The proportional control band is respectively: 0%
1. divided by the number of compressor steps, when freecooling/heating is disabled (Fig. 5.b.s); 5
2. managed with freecooling/heating operating and the compressors activated (Fig. 5.b.t). 2 3
ENGLISH
r38: used to calculate the duty cycle for closing the damper.
1
2 Key:
Fig. 5.b.u 1. opening time;
2. cycle time.
The controller saves the significant events that stop (alarms) or limit (warnings) the operation of
the unit. Up to 25 events can be saved, highlighting:
— Event code;
— Start hours;
— Start minutes;
— Start day;
— Start month;
— End hours;
— End minutes;
— End day;
— End month.
The log is accessed by pressing PRG+SEL for 5s and entering the password 44.
The alarms saved are complete, as they include both the start and end of the event.
The alarms can be deleted individually by pressing UP and DOWN for 5s when the desired event
is displayed. If there are no alarms saved, “noH” is displayed. The table shows the possible alarms
that can be saved:
SV Display Type SV Display Type SV Display Type
All. Circ. 1 HP1 High pressure circuit 1 All. Sonde E5 Probe B5 alarm All. Evd 1 EP1 EEPROM error EVD 1
All Circ. 2 HP2 High pressure circuit 2 All. Sonde E6 Probe B6 alarm All. Evd 2 EP2 EEPROM error EVD 2
All. Circ. 1 LP1 Low pressure circuit 1 All. Sonde E7* Probe B7 alarm7 All. Evd 1 ES1 Probe error EVD 1
All Circ. 2 LP2 Low pressure circuit 2 All. Sonde E8* Probe B8 alarm All. Evd 2 ES2 Probe error EVD 2
All. Gen. TP General thermal overload All. Gen. ESP Expansion error All. Evd 1 EU1 Valve open error EVD 1 start
All. Circ. 1 tC1 Thermal overload circuit 1 All. Circ. 1 A1 Frost alarm circ. 1 All. Evd 2 EU2 Valve open error EVD 2 start
All. cir. 2 tC2 Thermal overload circuit 2 All. Circ. 2 A2 Frost alarm circ. 2 All. Evd 1 Eb1 EVD 1 battery alarm
All. Gen FL Flow switch alarm All. Gen. EHS High power supply voltage All. Evd 2 Eb2 EVD 2 battery alarm
All. Sonde E1 Probe B1 alarm All. Evd 1 Ed1 EVD1 tLAN error All. Sonda μAD Et uAD terminal probe alarm
All. Sonde E2 Probe B2 alarm All. Evd 2 Ed2 EVD2 tLAN error
All. Sonde E3* Probe B3 alarm OFF SH1 EVD1 overheat alarm
All. Sonde E4* Probe B4 alarm All. Evd 2 SH2 EVD2 overheat alarm
- Start hours for 2nd set point in cooling
t06 (I92): Hour when the second cooling set point starts(r21).
- Start minutes for 2nd set point in cooling
t07 (I93): Minutes when the second cooling set point starts (r21).
- End hours for 2nd set point in cooling
t08 (I94): Hour when the second cooling set point stops (r21).
- End minutes for 2nd set point in cooling
t09 (I95): Minutes when the second cooling set point stops (r21).
- Start hours for 2nd set point in heating
t10 (I96): Hours when the second heating set point starts (r22).
- Start minutes for 2nd set point in heating
t11 (I97): Minutes when the second heating set point starts (r22).
- End hours for 2nd set point in heating
t12 (I98): Hours when the second heating set point stops (r22).
- End minutes for 2nd set point in heating
t13 (I99): Minutes when the second heating set point stops (r22).
If a digital input is configured as the second set point from external contact (e.g. p08 = 13) the
time bands are ignored. If a digital input is configured as the second cooling set point from
external contact and heating set point from time band (e.g. p08 = 14), the cooling time bands are
ignored.
The second set point from external contact input has priority over the second cooling set point
from external contact and heating set point from time band.
- Start hours for low noise in cooling
t14: Start hours for low noise in cooling
- Start minutes for low noise in cooling
t15: Start minutes for low noise in cooling
- End hours for low noise in cooling
t16: End hours for low noise in cooling
- End minutes for low noise in cooling
t17: End minutes for low noise in cooling
- Start hours for low noise in heating
t18: Start hours for low noise in heating
- Start minutes for low noise in heating
t19: Start minutes for low noise in heating
- End hours for low noise in heating
t20: End hours for low noise in heating
- End minutes for low noise in heating
t21: End minutes for low noise in heating
56 μC2SE - +030220426 - rel. 2.5 - 27.11.2012
6. TABLE OF ALARMS
ENGLISH
Key to the table of alarms:
*: if the probe is set for the compensation function, in the event of probe faults, the unit continues to operate.
ON*: if the expansion card is not present.
EVD 1= EVD400 connected to μC2SE (1st circ.)
EVD 2= EVD400 connected to the expansion (2nd circ.)
alarm alarm type resetting Compressor pump fan heater Valve alarm warning superv. superv. variab. variab.
display variable description type
HP1 High pressure Depends on P05 OFF C1-2 - ON(60”) - - ON - 41 (R) Circuit 1 alarm Digital
HP2 High pressure Depends on P05 OFF C3-4 - ON(60”) - - ON - 42 (R) Circuit 2 alarm Digital
LP1 Low pressure Depends on P05 OFF C1-2 - OFF 1 - - ON - 41 (R) Circuit 1 alarm Digital
LP2 Low pressure Depends on P05 OFF C3-4 - OFF 2 - - ON - 42 (R) Circuit 2 alarm Digital
PL1 Capacity-control for low pressure Automatic OFF C2 - - - - - ON - Signal on display -
circuit 1
PL2 Capacity-control for low pressure Automatic OFF C4 - - - - - ON - Signal on display -
circuit 2
TP General overload Depends on P08 OFF OFF OFF - - ON - 45 (R) General warning Digital
tC1 Circuit 1 overload Depends on P08 OFF C1-2 - OFF 1 - - ON - 41 (R) Circuit 1 alarm Digital
tC2 Circuit 2 overload Depends on P08 OFF C3-4 - OFF 2 - - ON - 42 (R) Circuit 2 alarm Digital
LA advice Depends on P08 - - - - - ON* ON 50 (R) General advice Digital
FL Flow controller alarm Depends on P08 OFF OFF OFF - - ON - 45 (R) General alarm Digital
FLb Backup pump warning Automatic - - - - - - ON 50 (R) General advice Digital
E0 Regulation probe alarm Automatic - - - - - ON - - Signal on display -
E1 Probe B1 alarm Automatic OFF OFF OFF OFF - ON - 46 (R) Probe alarm Digital
E2 Probe B2 alarm Automatic OFF OFF OFF OFF - ON - 46 (R) Probe alarm Digital
E3* Probe B3 alarm Automatic OFF OFF OFF OFF - ON - 46 (R) Probe alarm Digital
E4* Probe B4 alarm Automatic OFF OFF OFF OFF - ON - 46 (R) Probe alarm Digital
E5 Probe B5 alarm Automatic OFF OFF OFF OFF - ON - 46 (R) Probe alarm Digital
E6 Probe B6 alarm Automatic OFF OFF OFF OFF - ON - 46 (R) Probe alarm Digital
E7* Probe B7 alarm Automatic OFF OFF OFF OFF - ON - 46 (R) Probe alarm Digital
E8* Probe B8 alarm Automatic OFF OFF OFF OFF - ON - 46 (R) Probe alarm Digital
Hc1-4 Hour warning C1-4 Automatic - - - - - - ON 47 (R) Compressor advice Digital
EPr EEPROM error during operation Automatic - - - - - - ON 50 (R) General advice Digital
EPb EEPROM error at the start-up Automatic OFF OFF OFF OFF OFF OFF OFF 45 (R) General alarm Digital
ESP Expansion Error Automatic OFF OFF OFF OFF OFF ON - 45 (R) General alarm Digital
EL1-2 Zero cross Automatic - - 100% - - ON* ON 52 (R) Fan advice Digital
dF1-2 Defrosting error Automatic - - - - - - ON 50 (R) General warning Digital
d1-2 Defrost on circuit in question - - - - - - - - - Signal on display -
Fd Dirty filter warning Automatic - - - - - - -ON - Signal on display -
A1 Frost alarm circ. 1 Depends on P05 OFF C1-2 - OFF 1 - - ON - 41 (R) Circuit 1 alarm Digital
A2 Frost alarm circ. 2 Depends on P05 OFF C3-4 - OFF 2 - - ON - 42 (R) Circuit 2 alarm Digital
Ht High temperature Automatic - - - - - ON* ON 51 (R) Temperature Digital
advice
Lt Low ambient temp. Depends on P05 - - - - - ON* ON 51 (R) Temperature Digital
advice
AHt High temperature at the start-up Automatic OFF - OFF OFF - - ON 50 (R) General warning Digital
ALt Low temperature at the start-up Automatic OFF - OFF OFF - - ON 50 (R) General warning Digital
ELS Low supply voltage Automatic - - - - - - ON 50 (R) General warning Digital
EHS High supply voltage Automatic OFF OFF OFF OFF OFF OFF OFF 45 (R) General alarm Digital
tEr Terminal communication error Automatic OFF OFF OFF OFF OFF ON - - Signal on display -
Ed1 EVD 1 tLAN error Automatic OFF C1-2 - OFF - - ON - 43 (R) EVD 1 warning Digital
Ed2 EVD 2 tLAN error Automatic OFF C3-4 - OFF - - ON - 44 (R) EVD 2 warning Digital
SH1 EVD 1 superheat alarm - OFF C1-2 - OFF- - - ON - 43 (R) EVD 1 warning Digital
SH2 EVD 2 superheat alarm - OFF C3-4 - OFF- - - ON - 44 (R) EVD 2 warning Digital
nO1 MOP 1 warning Automatic - - - - - - ON 48 (R) EVD 1 advice Digital
nO2 MOP 2 warning Automatic - - - - - - ON 49 (R) EVD 2 advice Digital
LO1 LOP 1 warning Automatic - - - - - - ON 48 (R) EVD 1 advice Digital
LO2 LOP 1 warning Automatic - - - - - - ON 49 (R) EVD 2 advice Digital
HA1 High inlet temperature warning Automatic - - - - - - ON 48 (R) EVD 1 advice Digital
circ.1
HA2 High inlet temperature warning Automatic - - - - - - ON 49 (R) EVD 2 advice Digital
circ. 2
EP1 EVD 1 Eeprom error Automatic OFF C1-2 - OFF- - - ON - 43 (R) EVD 1 warning Digital
EP2 EVD 2 Eeprom error Automatic OFF C3-4 - OFF- - - ON - 44 (R) EVD 2 warning Digital
ES1 EVD 1 probe error Automatic OFF C1-2 - OFF- - - ON - 43 (R) EVD 1 warning Digital
ES2 EVD 2 probe error Automatic OFF C3-4 - OFF- - - ON - 44 (R) EVD 2 warning Digital
EU1 Open valve EVD 1 error at the Automatic OFF C1-2 - OFF - - ON - 43 (R) EVD 1 warning Digital
start-up
EU2 Open valve EVD 2 error at the Automatic OFF C3-4 - OFF - - ON - 44 (R) EVD 2 warning Digital
start-up
Eb1 EVD 1 battery alarm Automatic OFF C1-2 - OFF - - ON - 43 (R) EVD 1 warning Digital
Eb2 EVD 2 battery alarm Automatic OFF C3-4 - OFF - - ON - 44 (R) EVD 2 warning Digital
L Low load warning Automatic - - - - - - - - Signal on display -
Ed1 tLan EVD 1 communication error Automatic OFF C1-2 - OFF - - ON - 43 (R) EVD 1 warning Digital
Ed2 tLan EVD 2 communication error Automatic OFF C3-4 - OFF - - ON - 44 (R) EVD 2 warning Digital
PH1 Low pressure circ. 1 warning - - - - - - - - - Signal on display -
PH2 Low pressure circ. 2 warning - - - - - - - - - Signal on display
SUL Low outlet temperature warning - - - - - - - - - Signal on display
CP1 compressor 1 alarm Automatic OFF C1 - - - - ON - 25 (R) Compr. error alarm Digital
CP2 compressor 2 alarm Automatic OFF C2 - - - - ON - 25 (R) Compr. error alarm Digital
CP3 compressor 3 alarm Automatic OFF C3 - - - - ON - 25 (R) Compr. error alarm Digital
CP4 compressor 4 alarm Automatic OFF C4 - - - - ON - 25 (R) Compr. error alarm Digital
Table 6.a
Note: The warning relay differs from the alarm relay as it is only activated for warnings, that is, signals only, which have no direct effect on the operation of the unit,
and the display does not show the alarm symbol (bell).
Compressor
N.B. The alarm relating to the circuit with the fault must not interact with the operation of the other circuit, as long as the condenser is not shared in common.
μC2SE - +030220426 - rel. 2.5 - 27.11.2012 57
HP1: High pressure circuit 1
The alarm is detected irrespective of the status of the pump and the compressors. The compressors
corresponding to circuit 1 are immediately stopped (ignoring the set protection times), the
ENGLISH
buzzer and alarm relay are activated, and the display starts flashing. The fans corresponding to the
condenser in circuit 1 are activated at maximum speed for 60 s, so as to oppose the alarm situation,
after which they are switched OFF. This alarm may also be generated when the high pressure limit
is exceeded (valid only when the pressure transducer is fitted) set by the parameter P18, which to
be enabled must be greater than 3.0 bars, due to the corresponding hysteresis.
HP2: High pressure circuit 2
As for HP1 but relating to circuit 2.
LP1: Low pressure circuit 1
The alarm depends on P15, P7 and P3.
P15= 0, P07= 0: the alarm is detected only if the compressors in circuit 1 are ON, and after the time
P03 from when the compressors started, otherwise it is immediate.
P15= 1, P07= 0: the alarm is detected even if the compressors in circuit 1 are off, after the time P03.
P15= 0, P07= 1: the alarm is detected only if the compressors in circuit 1 are ON, and after the time
P03 from when the compressors started, otherwise it is immediate, and if in heat pump mode, is
activated for pressure values less than 1 bar.
P15= 1, P07= 1: the alarm is detected also if the compressors in circuit 1 are Off, after the time P03,
and if in heat pump mode, is activated for pressure values lower then 1 bar. The hysteresis for this
alarm is 1 bar.
LP2: Low pressure circuit 2
As for LP1 but relating to circuit 2.
PL1: Capacity-control for low pressure circuit 1
Indicates that circuit 1 on the unit is operating in capacity control mode, due to low pressure (heat pump
only).
PL2: Capacity-control for low pressure circuit 2
As for PL1, but for circuit 2.
PH1: Compressor part load circuit 1
Indicates the part load of circuit 1 due to high pressure. This situation is signalled by the message
“PH1” on the display the activation of the warning relay.
PH2: Compressor part load circuit 2
As for PC1, but for circuit 2.
tP: General thermal overload
The alarm is detected irrespective of the status of the pump and the compressors. The compressors,
the pumps and fans stop (without observing the protection times) or are inhibited from starting,
the alarm relay is activated, the display flashes the corresponding message, and the LED flashes. It
can be reset either manually or automatically (see par. P08, P09, P10, P11, P12, P13).
tC1: Thermal overload circuit 1
As for tP but relating to circuit 1
tC2: Thermal overload circuit 2
As for tC1 but relating to circuit 2.
LA: generic warning
This represents a generic warning that appears on the display, from digital input, without modifying
the operation of the unit. With the 1st circuit module only, the alarm relay is activated, while with
the expansion card the warning relay can be used.
FL: flow alarm
This alarm is detected only if the pump is ON (excluding the delays when starting P01 and in steady
operation P02), irrespective of the status of the compressor. All of the outputs are disabled: pump,
compressor (without observing the OFF times), condenser fan, and the buzzer sounds, the alarm
relay is activated and the display flashes. The presence of the utility water pump must be enabled
(H50). It can be reset either manually or automatically (see P08, P09, P10, P11, P12, P13).
FLb: Backup pump warning
The warning activates the warning relay and displays the message “FLb”; reset is manual. This
indicates the operation of the backup pump (if present) due to a probable fault on the main pump,
suggesting that maintenance is required. If the flow alarm features automatic reset, the controller
will make 10 attempts to re-start the pumps, after which the FL alarm will replace FLb. If the flow
alarm features manual reset, when first activated the controller will display the alarm FLb, switching
over the pumps; when activated again the FL alarm will replace FLb
E0: control probe error
A control probe alarm tells the user that the μCH2SE configuration is not coherent with the
parameter settings, as the control probe is not available; the alarm relay is activated and the display
flashes.
E1 to E8: probe error detected even when the unit is in Standby
The presence of a probe alarm causes the deactivation of the compressor, the condenser fans, the
pump (outlet fan in AIR/AIR units) and the heaters (so as to avoid fires in the air/air units); the buzzer
and alarm relay are activated, and the display starts flashing. If the probe has a compensation
function, the unit will continue a operate correctly, with the exception of the corresponding
function, and the warning relay will be activated and a message shown on the display, from E1 to
E8 for probes from B1 to B8.
ENGLISH
signal is activated. The buzzer and the alarm relay are not activated, however the warning relay is
activated (with the expansion card fitted).
Epr, EPb: EEPROM error
A problem has occurred when saving the parameters to the unit’s non-volatile memory
(EEPROM); in the event of an Epr error, the μC2SE continues to perform the control functions with
the data present in the volatile memory (RAM), where there is a physical copy of all of the data.
After the first power failure the configuration will be lost. The buzzer and the alarm relay are not
activated. If the occurs when starting the unit, “EPb”, the controller will not operate.
ESP: communication error with expansion card
If the controller loses communication with the expansion card, the entire system will be stopped
to avoid adversely affecting the unit. The alarm relay is activated and the display will show the
message, with the red LED on steady.
EL1-2: warning, zero crossing error circuit 1-2
If the controller detects errors in the power supply, control may be lost over the fan speed. In this
case, the display will show a warning, and the fans will be controlled at maximum speed. The
alarm is reset automatically, so as to not affect the operation of the unit. If the expansion card is
used, the warning relay is activate)
dF1-2: warning, end defrost circuit 1-2 due to maximum time
If the defrost ends after the maximum time when end defrost by temperature or from external
contact has been selected, the unit displays the text dF1 for circuit 1 or dF2 for circuit 2.
The message is cancelled using the delete alarm procedure or when the next correct defrost
cycle is completed. The buzzer and the alarm relay are not activated. If the expansion card is used,
the warning relay is activated (if used).
A1: antifreeze alarm outlet limit circuit 1
The alarm is only detected in water chillers (H01= 2, 3, 4, 5 or 6) by the evaporator water outlet
probe (B2/B6) or, if the electronic expansion driver (EVD) is connected to the tLAN, based on
the evaporation temperature sent by the driver. The evaporator water outlet temperature is
compared against the threshold A01, while the evaporation temperature is compared against the
threshold A14.
The compressors in circuit 1 and the condenser fans in circuit 1 are immediately stopped, the
buzzer and alarm relay are activated, and the display starts flashing. If the μC2SE is in Standby, the
alarm condition is not detected, and only the heaters are managed. Reset depends on parameter
P5:
1. in the event of automatic reset, the unit restarts automatically if the temperature is above the
value
A01+A02 or A14+A02.
2. in the event of manual reset, the unit can restart manually even if the alarm is active.
After the time A03, if the alarm persists the unit will stop again.
For air/air units the parameter becomes the antifreeze-outlet limit alarm set point. If the outlet
limit is active, the freecooling damper is forced closed and the message SUL is shown on the
display.
A2: antifreeze alarm circuit 2
As for A1 but relating to circuit 2
Ht: high temperature warning
This alarm is activated when the threshold is exceeded (read by B1), set for the parameter P16. It is
delayed at power ON by the parameter P17 and causes the activation of the alarm relay and the
buzzer, without deactivating the outputs. It is reset automatically when conditions that caused the
alarm are no longer present.
Lt: low temperature warning
For direct expansion units (H01=0, 1) the alarm is used to measure a low room temperature using
probe B1 or B2 (depending on par. A06). The alarm may be reset manually or automatically, and
depends on the parameter P05. If the expansion is present, the corresponding relay is activated; in
the event of μC2SE module only, the alarm relay will be used.
AHt: high temperature warning when starting the system
The advice does not activate the relay, and displays the message “AHt”.
ALt: low temperature warning when starting the system
The advice does not activate the relay, and displays the message “ALt”.
ELS/EHS: warning, low/high power supply alarm
If the power supply voltage is too low or too high, the corresponding message is displayed.
In these cases, the correct operation of the μC2SE is no longer guaranteed. In the low voltage
conditions only the requests to deactivate the loads are effected. Any start-up requests remain
pending. The high voltage condition involves the deactivation of all the energised relays.
L: Low load warning
The warning does not activate the relay and displays the message “ L ”; reset is automatic.
tEr: terminal communication error
This alarm is only shown if μC2SE has been connected to a terminal. The alarm is generated a fixed
time (30 s) after μC2SE loses contact with the terminal. In this case the unit is disabled for safety
reasons.
When the defrost is on circuit 2, the display shows the message D2.
Fd: dirty filter warning
This warning is only shown if the temperature difference between the exchanger inlet and outlet
is higher than parameter A12.
Driver
All the driver alarms on the μC2SE that stop the unit feature automatic reset. Consequently, the
possibility to select the automatic resetting of the entire system must be selected for the drivers
by setting the corresponding parameters. The μC2SE can send the Go Ahead command according
to the normal procedure for resetting the alarms from the keypad.
ENGLISH
7.1 Connection diagram
Below is the connection diagram for the μC2SE.
Panel version
N
EV driver ESP EV driver
Expansion Line
EV Driver L
EV Driver board
multi multi multi multi
tLAN funct. funct. funct. funct.
GND B4 V+
G0 B1 B2 B3 ID5 ID3 ID1 Key/SPV
outlet probe
G GND GND Y GND ID4 ID2
cond. probe
inlet probe
multi funct.
multi funct.
multi funct.
high press.
pressure
low press.
P probe
temperature
probe To program key
RS485
option
digital
imput
N L
Line To serial link
Fig. 7.a
I/O layout
μC2SE Description
B1 Control probe (Evaporator inlet/ambient)
B2 Protection probe (evaporator outlet/outlet)
B3 Condenser/outside temperature probe
B4 (universal) Condenser pressure probe
ID1* Flow switch – thermal overload circuit 1 – cooling/heating – end defrost circuit 1 – step
1 condensing unit – second set point
ID2* Flow switch – thermal overload 1 circuit – cooling/heating – end defrost circuit 1 – step
2 condensing unit – second set point
ID3 High pressure circuit 1
ID4 Low pressure circuit 1
ID5 Remote ON/OFF – reverse cycle condensing unit if reversible
Y1 Ramp circuit 1 (condenser)
C1/2-NO1 Compressor 1
C1/2-NO2 Heater or reversing valve in 1st circuit
C3/4-NO3 Fan 1/evaporator pump
C3/4-NO4 Compressor 2 (capacity-control compressor 1)
C5-NO5 Alarm or reversing valve
Table 7.a
Expansion Description
B5 Output probe in common with 2 evaporators (only with 2 circuits)
B6 Circuit 2 protection probe (2nd evaporator output)
B7 2nd condenser temperature probe
B8 (universal) 2nd condenser pressure probe
ID6** Flow switch – thermal overload circuit 2 – end defrost circuit 2 – step 4 condensing
unit – second set point
ID7** Flow switch – thermal overload circuit 2 – end defrost circuit 2 – step 4 condensing
unit– second set point
ID8 High pressure circuit 2
ID9 Low pressure circuit 2
ID10
Y2 Ramp circuit 2 (condenser)
C6/7-NO6 Compressor 3 (1 in 2nd circuit)
C6/7-NO7 Heater or reversing valve in 2nd circuit
C8/9-NO8 Fan 2/condenser pump/backup
C8/9-NO9 Compressor 4 (capacity-control compressor 2) or reversing valve circuit 1 or reversing
valve circuit 2
C10-NO10 Warning or reversing valve circuit 2
Table 7.b
*= Any of the options for P08 can be selected (see Table 5.11)
**= Any of the options for P08 can be selected, except for E/I and E/I delay.
The following figure shows the connection diagram for the μC2SE expansion card, code
MCH200002*.
EV Driver N
EV driver Line
L
multi multi multi multi
funct. funct. funct. funct.
Top
Expansion board
Bottom
GND Tx/Rx GND B8 V+
G0 B5 B6 B7 ID10 ID8 ID6
inlet probe
pressure
multi funct.
multi funct.
multi funct.
high press.
low press.
P probe
temperature
probe
digital
input
t-LAN
N L
Line
Fig. 7.b
NOTE: The expansion features two LEDs on the main board (to see these, remove the top or
bottom door), which display its status by the following messages:
ON Flashing
green LED Board powered Board powered and serial communication with μC2SE in
progress
red LED 1 flash: Probe fault alarm
2 flashes: Zero crossing alarm (mains frequency not detected)
3 flashes: Serial communication alarm with EVD
4 flashes: Serial communication alarm with μC2SE
Table 7.c
The alarms are displayed in sequence and are separated from each other by pauses.
EEV driver
FCSER00000
Fig. 7.c
62 μC2SE - +030220426 - rel. 2.5 - 27.11.2012
7.4 Fan speed control board (code MCHRTF*)
The phase cutting boards (code MCHRTF****) are used to control the speed of the condenser
1
fans.
ENGLISH
2 GND Y
IMPORTANT: The power supply to the μC2SE (G and G0) and the MCHRTF**** board must be in
- +
phase. If, for example, the power supply to the μC2SE system is three-phase, make sure that the
primary of the transformer supplying the μC2SE board is connected to the same phase that
is connected to terminals N and L on the speed control board; therefore, do not use
380 Vac/24 Vac transformers to supply the controller if the phase and neutral are used to directly
power the speed control boards.
Connect the earth terminal (where envisaged) to the earth in the electrical panel.
Key:
1. to μchiller;
2. earth;
LOAD LINE 3. to motor.
3 220 Vac
Fig. 7.d
to μchiller
24 Vac Y GND 7.5 Fan ON/OFF control board (code CONVONOFF0)
The relay boards (code CONVONOFF0) are used for the ON/OFF management of the condenser
1 2 3 4 fans.
The control relay has a switchable power rating of 10 A at 250 Vac in AC1 (1/3 HP inductive).
5 6 7 8
No Com Nc
Fig. 7.e
to μchiller
24 Vac Y GND
7.6 PWM to 0 to 10Vdc (or 4 to 20 mA)conversion board for
1 2 3 4
fans (code CONV0/10A0)
The CONV0/10A0 boards convert the PWM signal at terminal Y on the μC2SE to a standard 0 to 10
Vdc (or 4 to 20 mA) signal. The FCS series three-phase controllers can be connected to the μC2SE
without using this module.
5 6 7 8
G0 0-10V G0 4-20mA
Fig. 7.f
- +
7.7 Minimum and maximum fan speed calculation
This procedure should only be performed when the fan speed control boards are sued (code
MCHRTF*).
it must be stressed that if the ON/OFF modules (code CONVONOFF0) or alternatively the PWM
to 0 to 10 V converters (code CONV0/10A0) are used, parameter F03 should be set to zero, and
parameter F04 to the maximum value.
Given the different types of motors existing on the market, the user must be able to set the
voltages supplied by the electronic board corresponding to the minimum and maximum
LOAD LINE
speeds. In this regard (and if the default values are not suitable), proceed as follows:
L N N L
• set parameter F02= 3 and set F03 and F04 to zero;
• the condenser control set point (evaporator in HP mode) has been modified to take the output
signal to the maximum value (PWM);
• increase F04 until the fan operates at a sufficient speed (make sure that, after having stopped it,
it can rotate freely when released);
Vac? • “copy” this value to parameter F03; this sets the voltage for the minimum speed;
• connect a voltmeter (set for AC, 250V) between the two “L” terminals (the two external
contacts);
• increase F04 until the voltage stabilises at around 2 Vac (inductive motors) or 1.6, 1.7 Vac
(capacitive motors). Once the value has been found, it will be evident that even when
increasing F04 the voltage no longer decreases. In any case do not increase F04 further so as to
Fig. 7.g avoid damaging the motor;
• restore the correct condenser set point (evaporator in HP mode).
The keys must be connected to the connector (4 pin AMP) fitted on the controllers, and can
work with the instruments ON or OFF, as indicated in the operating instructions for the specific
controller.
The two main functions (upload/download) that can be selected through two dip-switches
(which are placed under the battery cover). They are:
• Loading to the key the parameters of a controller (UPLOAD);
• Copying from the key to one or more controllers (DOWNLOAD).
Warning: the copying of the parameters is allowed only between instruments with the same
code. Data loading operation to the key is always allowed. To make identification of the key easier
CAREL has inserted a label on which you can describe the loaded programming or the machine Fig. 7.h Fig. 7.i
to which you are referring.
IMPORTANT NOTE: the key can be used only with controllers μC2SE that have the same
Firmware version.
Technical specifications
Power supply to the - Use three 1.5 V 190 mA batteries (Duracell D357H or equivalent)
PSOPZKEY00 - Maximum current supplied 50 mA max.
Power supply to the - switching power supply:
PSOPZKEYA0 Input 100 to 240 V~; (-10%, +10%); 50/60 Hz; 90 mA. Output: 5 Vdc; 650
mA
Operating conditions 0T50°C r.H. <90% non-condensing
Storage conditions -20T70°C r.H. <90% non-condensing
Case Plastic, dimensions 42x105x18 mm including prod and connector Figs.
1 and 2
Table 7.e
(Here we have dealt only with the base functions of the instrument. For the remaining specific functions,
see the manual of the instrument that is being used).
ENGLISH
The MCH2004850 serial option is used to connect the μC2SE controller to a supervisor network via
a standard RS485 serial line.
This option uses the input normally associated with the programming key, which has the dual
function of key connector/serial communication port.
Fig. 7.k
7.10 Terminals
The μC²SE features the following user interfaces:
Remote terminal
The remote terminal allows the complete configuration of the μC2SE from a remote position. The
buttons and indications on the display faithfully reproduce the μC2SE user interface. In addition,
PlantVisor can be connected to the remote terminal using the special accessory.
Product code:
MCH200TP00 for panel installation
MCH200TW00 for built-in assembly
Fig. 7.l For further information see the instruction sheet +050001065.
μAD
μAD is the μC2SE room terminal.
This terminal, fitted with built-in temperature and humidity probes, controls the temperature-
humidity conditions in the environment where its is installed, interacting with the units controlled
by the μC2SE.
The μAD can be used to set time bands, the temperature and humidity set point, switch the
system on/off and change operating mode simply and intuitively.
Product code:
ADMA001000: with NTC probe
ADMB001010: with NTC probe, RTC and buzzer
ADMG001010: with NTC and humidity probe, RTC and buzzer
ADMH001010: with NTC and humidity probe, RTC, buzzer and backlighting
Fig. 7.m
For further information see the instruction sheet +05000750 and the manual +030220465.
μAM
μAM is the μArea controller compatible with the μC2SE.
This can control up to 10 fan coils (fitted with the e-droFAN electronic controller). By analysing the
temperature-humidity conditions in the different rooms, μAM optimises the temperature of the
water produced by the chiller/HP, improving power consumption, performance and comfort.
In addition, the μAM centralises the data, such as set point, heat/cool mode and on/off for the
individual fan coil and the entire system, including time bands.
For further information see the instruction sheet +050000740 and the manual +030220460.
The following are the mechanical dimensions of each component in the μC2SE controller; all the
values are expressed in millimetres.
75 64
74
drilling template
comp
71x29 mm
x100
PRG
Sel
panel mounting
overall dimensions 91,5x36x5 mm
Fig. 8.a
Expansion
boar d
110
44
88
Expansion boar d
11
36 60
70 60
Fig. 8.b Fig. 8.c
5 75 5
31 3 56 85
59
Fig. 8.d
ENGLISH
Model A (component B C D E
side)
MCHRTF04C0 43 100 40 50 107
MCHRTF08C0 75 100 58 82 107
MCHRTF12C0 75 100 58 82 107
Note: the version with screw teminals code MCHRTF*D0 is available on request
Table 8.a
D D
A C A C
8 e 12 A B E 4A B E
Fig. 8.e
Model
MCHRTF10C0
Table 8.b
90
3 74.5 12.5 64
19
19
35.5
84
50
Ø4
29.5
15
3 74.5 12.5
Fig. 8.f
Description Code
μC2SE single circuit, 2 compressors, panel mounting MCH2001030
μC2SE single circuit, 2 compressors, panel mounting (20 pcs. multiple package) MCH2001031
μC2SE expansion board for 2nd. circuit maximum 4 compressors MCH2000020
μC2SE expansion board for 2nd. circuit maximum 4 compressors (10 pcs. multiple MCH2000021
package)
RS485 optional board for μC2SE panel version MCH2004850
Programming key for μC2SE PSOPZKEY00
ON/OFF fan card (only screw terminals) CONVONOFF0
PWM - 0 to 10 V fan card (only screw terminals) CONV0/10A0
Temperature probes for regulation or condensation control NTC***WP00
***depending on the length (015= 1.5 m, 030= 3 m, 060=6 m)
Pressure probes for condensing pressure control SPK*R*
** depending on the pressure (13= 150 PSI, 23= 75 PSI, 33= 500 PSI)
Connectors kit for code MCH2000001 (multiple package 20 pcs) MCH2CON001
Connectors kit for code MCH2000001 (multiple package 10 pcs) MCH2CON021
Kit cables 1 meter length MCHSMLCAB0
Kit cables 2 meter length MCHSMLCAB2
Kit cables 3 meter length MCHSMLCAB3
Remote terminal for MCH20000** for panel installation MCH200TP0* MCH200TP0*
Remote terminal for MCH20000** for wall-mounting MCH200TW0* MCH200TW0*
Supervisor serial connection kit for remote terminal MCH200TSV0
Fan speed PWM 4 A/230 Vac MCHRTF04C0
Fan speed PWM 8 A/230 Vac MCHRTF08C0
Fan speed PWM 12 A/230 Vac MCHRTF12C0
Fan speed PWM 10 A/230 Vac 1 Pc. Nor. Ind. MCHRTF10C0
Fan speed PWM 10 A/230 Vac 10 Pc. Nor. Ind. MCHRTF10C1
Table 9.a
ENGLISH
Range -40T80 °C, ±1.5 °C (excluding probe)
Pressure measurement error The % error with a voltage reading with a range of input from 0.5
to 4.5 is ± 2% (excluding probe).
The error in the converted value may vary according to the
settings of parameters /9, /10, /11, /12
Table 10.b
Characteristics of the connectors
The connectors may be purchased using CAREL code (MCHCON0***) or from the manufacturer
Molex®
Molex® codes of the connector Number of pins
39-01-2120 12
39-01-2140 14
Table 10.c
Max. number of insertion/removal cycles for the connectors: 25 cycles
Code of the contacts according to the cross-section of the connection cables to the 12- and 14-
pin connectors (use the special Molex® tool code 69008-0724 for crimping
Molex® code of the contact Cross-section of cables allowed
39-00-0077 AWG16 (1.308 mm2)
39-00-0038 AWG18-24 (0.823 to 0.205 mm2)
39-00-0046 AWG22-28 (0.324 to 0.081 mm2)
Table 10.d
In addition, the pre-wired kits MCHSMLC*** are also available
WARNINGS
• If one transformer is used to supply both the μC2SE and the accessories, all the G0 terminals
on the various controllers or the various boards must be connected to the same terminal on
the secondary, and all the G terminals to the other terminal on the secondary, so as to avoid
damaging the instrument;
• For use in residential environments, use shielded cable (two wires + shield earthed at both
ends, AWG 20-22) for the tLAN connections (EN 55014-1).
• Avoid short-circuits between V+ and GND so as to not damage the instrument;
• Perform all the maintenance and installation operations when the unit is not connected to the
power supply;
• Separate the power cables (relay outputs) from the cables corresponding to the probes, digital
inputs and serial line;
• Use a transformer dedicated exclusively to the electronic controllers for the power supply.
Protection against electric shock and maintenance warnings
The system made up of the control board (MCH200003*) and the other optional boards
(MCH200002*, MCH200485*, MCHRTF****, CONVONOFF*, CONV0/10A*, EVD000040*) represents a
control device to be integrated into class 1 or class 2 appliances.
The class of protection against electric shock depends on how the control device is integrated
into the unit built by the manufacturer.
Disconnect power before working on the board during assembly, maintenance and replacement.
The protection against short circuits must be guaranteed by the manufacturer of the appliance
that the controller will be fitted on.
Maximum length of the NTC/ratiometric probe
NTC/ratiometric probe connection cables 10 m
digital input connection cables 10 m
power output connection cables 5m
fan control output connection cables 5m
power cables 3m
Table 10.e
Agence/Agency: